The provisions of this chapter shall govern the conduct of all construction or demolition operations with regard to the safety of the public and property. For regulations relating to the safety of persons employed in construction or demolition operations, OSHA Standards shall apply.
Nothing in this chapter shall be construed to relieve persons engaged in construction or demolition operations from complying with other applicable provisions of law, nor is it intended to alter or diminish any obligation otherwise imposed by law on the owner, construction manager, general contractor, contractors, materialmen, registered design professionals, or other party involved in a construction or demolition project to engage in sound design and engineering, safe construction or demolition practices including but not limited to debris removal, and to act in a reasonable and responsible manner to maintain a safe construction or demolitionsite.
Contractors, construction managers, and subcontractors engaged in building work shall institute and maintain safety measures and provide all equipment or temporary construction necessary to safeguard all persons and property affected by such contractor's operations.
Inspection of operations for compliance with the provisions of this chapter may be performed by, or under, the authority of the person superintending the work. Unless otherwise specified by the provisions of this chapter, inspection and test reports relating to operations within the scope of this chapter shall be maintained by the permit holder or the person responsible for the inspection and made available to the department upon request.
Any equipment or device, except hand tools, that would affect public safety when operated shall be inspected by the person superintending the work or by his or her designated representative before the equipment or device is used on a specific job. Such inspection shall be made, and every defect or unsafe condition shall be corrected before use is permitted.
Any unsafe equipment or device shall immediately be made safe or removed from the site. Periodic inspection of equipment shall be performed during construction or demolition operations, and a record of such inspections shall be kept at the site for the duration of the work and made available to the department upon request.
Temporary equipment and constructions shall be designed so that the allowable stress values for the material as specified by this code are not exceeded.
No structure, device, or equipment, whether permanent or temporary, including all partly or fully completed elements or sections of the building, shall be loaded in excess of its design capacity.
Whenever design is required by the provisions of this chapter, such design shall be executed by, or under, the supervision of a registered design professional who shall cause his or her seal and signature to be affixed to any drawings or specifications that may be required for the work unless specifically indicated by this chapter that the design may be executed by another individual. All such documents shall be kept at the site for inspection by the commissioner for the duration of the job.
Where a site is enclosed with a fence in accordance with Section 3307.7, a project information panel meeting the requirements of Sections 3301.9.1.1 through 3301.9.1.6 shall be posted. Required project information panels shall be in place throughout the duration that the fence remains at the site.
Exceptions:
At a site where the project permit was issued or renewed prior to June 1, 2013, signs meeting the requirement of Section 3301.9.3 may be posted in lieu of a project information panel. Such signs shall be removed and a project information panel in accordance with the requirements of this section installed upon date of the first permit renewal on or after June 1, 2013.
Project information panels at government-owned sites may be modified by department rule.
Project information panels shall contain the following information:
A rendering, elevation drawing, or zoning diagram of the building exterior that does not contain logos or commercially recognizable symbols;
A title line stating "Work in Progress:" and specifying the intended type(s) of zoning use(s) (e.g. Residential, Commercial, Manufacturing, Retail, Office, Hospital, School);
Anticipated project completion date;
The corporate name, address, and telephone number of the owner of the property;
Website address or phone number to contact for project information;
The corporate name and telephone number of the general contractor, or for a demolitionsite, the demolition contractor;
The statement, in both English and Spanish, "TO ANONYMOUSLY REPORT UNSAFE CONDITIONS AT THIS WORK SITE, CALL 311."; and
A copy of the primary project permit, with accompanying text "To see other permits issued on this property, visit: www.nyc.gov/buildings." The permit shall be laminated or encased in a plastic covering to protect it from the elements or shall be printed directly onto the project information panel.
Exception: A rendering, elevation drawing, or zoning diagram of the building exterior is not required for demolition projects.
*Section BC 3301.9.1.1 was amended by: Local Law 47 of 2013 — Update Page #75.This law has an
effective date of July 01, 2013.
A project information panel shall be posted on the fence on each perimeter fronting a public thoroughfare. Where such perimeter is more than 150 feet in length, a project information panel shall be posted at each corner. Such panels shall be posted on the fence at a height of 4 feet (1219 mm) above the ground, with such distance measured from the ground to the bottom edge of the panel.
*Section BC 3301.9.1.2 was amended by: Local Law 47 of 2013 — Update Page #75.This law has an
effective date of July 01, 2013.
Project information panels shall be constructed out of a durable and weatherproof material such as vinyl, plastic, or aluminum, and such material shall be flame retardant in accordance with NFPA 701 or listed under UL 214.
*Section BC 3301.9.1.3 was amended by: Local Law 47 of 2013 — Update Page #75.This law has an
effective date of July 01, 2013.
Project information panels shall be 6 feet (1829 mm) wide and 4 feet (1219 mm) high, with the content required by Section 3301.9.1.1 arranged in accordance with Figures 3301.9.1.4(1) and 3301.9.1.4(2). The content required by Section 3301.9.1.1, items number 2 through 7 shall be written in the Calibri font or similar sans serif font style, with letters a minimum of 1 inch (25mm) high, as measured by the upper case character. Such letters shall be white, on a blue background, with such blue color of a shade matching Pantone 296M, RGB 15, 43, 84, or CMYK 100, 88, 38, 35.
Exceptions:
The dimensions for a project information panel posted in conjunction with a demolition project shall be 2 feet 4 inches (711 mm) wide and 4 feet (1219 mm) high, in accordance with Figure 3301.9.1.4(1).
For constructionsites with a street frontage less than 60 feet (18 288 mm), the dimensions for a project information panel, other than that posted in conjunction with a demolition project, shall be 55 inches (1397 mm) wide and 36.5 inches (927 mm) high, in accordance with Figure 3301.9.1.4(3).
*Section BC 3301.9.1.4 was amended by: Local Law 47 of 2013 — Update Page #75.This law has an effective date of July 01, 2013.
*FIGURE 3301.9.1.4(1)
FENCE PROJECT INFORMATION PANEL TEXT DETAIL
*Section BC 3301.9.1.4(1) was amended by: Local Law 47 of 2013 — Update Page #75.This law has an effective date of July 01, 2013.
*FIGURE 3301.9.1.4(2)
FENCE PROJECT INFORMATION PANEL LAYOUT
*Section BC 3301.9.1.4(2) was amended by: Local Law 47 of 2013 — Update Page #75.This law has an effective date of July 01, 2013.
*FIGURE 3301.9.1.4(3)
FENCE PROJECT INFORMATION PANEL LAYOUT FOR SMALL LOTS
*Section BC 3301.9.1.4(3) was amended by: Local Law 47 of 2013 — Update Page #75.This law has an effective date of July 01, 2013.
Project information panels shall be maintained so that the panel remains legible, securely attached, and free of sharp edges, protruding nails, or similar hazards. Content required by Section 3301.9.1.1 shall not be obscured by panel attachments, including but not limited to grommets or grommet holes.
*Section BC 3301.9.1.6 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
Where a sidewalk shed is installed, a sidewalk shed parapet panel meeting the requirements of Sections 3301.9.2.1 through 3301.9.2.6 shall be posted. Required sidewalk shed parapet panels shall be in place throughout the duration that the sidewalk shed remains at the site.
Exceptions:
At a site where the sidewalk shed permit was issued or renewed prior to July 1, 2013, signs meeting the requirement of Section 3301.9.4 may be posted in lieu of a sidewalk shed parapet panel. Such signs shall be removed and a sidewalk shed parapet panel in accordance with the requirements of this section installed upon date of the first permit renewal on or after July 1, 2013.
Sidewalk shed parapet panels not included in a best constructionsite management program shall contain the following information and be arranged in accordance with Figure 3301.9.2.1(1):
Name (which may incorporate a logo) of the contractor responsible for the site or where there is no contractor, the name (which may incorporate a logo) of the owner of the site; and
The statement "For more information, visit www.nyc.gov/buildings."
*Section BC 3301.9.2.1.1 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
In addition to the requirements of section 3301.9.2.1.1, for a site maintained in accordance with a best constructionsite management program accepted by the commissioner as set forth in Section 3301.9.2.7, either the name or logo of such program, with the department's program acceptance logo, may be placed on the sidewalk shed parapet panel in accordance with Figure 3301.9.2.1(2).
*Section BC 3301.9.2.1.2 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
Sidewalk shed parapet panels shall be posted on the parapet that runs along the long axis of the sidewalk shed. Such sign:
Shall not be posted above or below the level of the parapet; and
Shall be posted at least 3 feet (914 mm) and no more than 6 feet (1828 mm) from the left edge of the sidewalk shed parapet, as viewed from the perspective of an individual on the sidewalk opposite the long axis of the sidewalk shed and facing the sidewalk shed; or
Where a project information panel in accordance with Section 3301.9.1 is posted on the fence, the horizontal center of the sidewalk shed parapet panel shall be in line with a vertical plane drawn through the horizontal center of the project information panel and the sidewalk shed parapet panel shall be posted in accordance with Figure 3301.9.2.2.
*Section BC 3301.9.2.2 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
Sidewalk shed parapet panels shall be constructed out of a durable and weatherproof material such as vinyl, plastic, or aluminum, and such material shall be flame retardant in accordance with NFPA 701 or listed under UL 214.
*Section BC 3301.9.2.3 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
Sidewalk shed parapet panels shall be 3 feet (914 mm) high and 6 feet (1829 mm) wide, with the content required by Section 3301.9.2.1 arranged in accordance with Figures 3301.9.2.1(1) and 3301.9.2.1(2). The sign shall have a white background. The content required by item number 1 of Section 3301.9.2.1.1 must be written in Calibri font or similar sans serif font style, and such letters shall be blue, with such blue color a shade matching Pantone 296M, RGB 15, 43, 84, or CMYK 100, 88, 38, 35.
*Section BC 3301.9.2.4 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
Sidewalk shed parapet panels shall be maintained so that the panel remains legible, securely attached, and free of sharp edges, protruding nails, or similar hazards. Content required by Section 3301.9.2.1 shall not be obscured by sign attachments, including but not limited to grommets or grommet holes.
*Section BC 3301.9.2.6 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
The department shall have the authority to create standards established by rule for the acceptance of a program that ensures best constructionsite management practices, and to set forth the basis and process for removal of such acceptance and for the removal of the program's name and logo from the sidewalk shed parapet panel located at a particular site.
*Section BC 3301.9.2.7 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
Where a site is enclosed with a fence in accordance with Section 3307.7, and a project information panel is not required in accordance with Section 3301.9.1, asign or signs meeting the requirements of Sections 3301.9.3.1 through 3301.9.3.3 shall be posted. Required signs shall be in place throughout the duration that the fence remains at the site.
*Section BC 3301.9.3 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
One or more signs needed to accommodate the following information shall be posted on the fence on each perimeter fronting a public thoroughfare at a height of no more than 12 feet (3658 mm) above the ground, with such distance measured from the ground to the top of the sign;
The name, address, and telephone number of the owner of the property;
The name, address, and telephone number of the general contractor, or for a demolitionsite, the demolition contractor; and
The statement, in both English and Spanish, "TO ANONYMOUSLY REPORT UNSAFE CONDITIONS AT THIS WORK SITE THAT ENDANGER WORKERS, CALL 311."
*Section BC 3301.9.3.1 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
Project signs shall be constructed of 3/4 inch (19 mm) plywood or material of equivalent strength, durability and weatherproofing, including but not limited to sheet metal, aluminum, vinyl, or plastic. The letters on such panels shall be black on a white background. Such panels shall be no larger than that needed to accommodate the information required by Section 3301.9.3.1 in letters no less than 3 inches (76 mm) high.
*Section BC 3301.9.3.3 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
Where a sidewalk shed is installed, and a sidewalk shed parapet panel is not required in accordance with Section 3301.9.2, asign readily visible from the street shall be posted on the parapet that runs along the long axis of the sidewalk shed. Such sidewalk shed sign shall be in place throughout the duration that the sidewalk shed remains at the site. Such sidewalk shed sign shall include:
The corporate name, address, and telephone number of the sidewalk shed permit holder;
Signs required by law to be displayed at a construction or demolitionsite shall be posted within the site, readily visible to workers, and shall not be posted in any location readily visible to the public unless otherwise required by law.
*Section BC 3301.9.5 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
When a protective structure is constructed in accordance with Section 3307, atemporary sign may be posted on such protective structure when the structure is adjacent to any building and obscures from view a lawful and existing sign. The temporary sign shall comply with the following requirements:
The temporary sign shall be securely fastened to the face of the protective structure at a location directly in front of such business storefront;
No projecting temporary signs shall be permitted, and all temporary signs shall be limited to a maximum height of 4 feet (1219 mm), and when affixed to a sidewalk shed shall not project above the parapet;
No temporary signs shall be permitted on the ends of any protective structure, unless the lawful and existing sign would otherwise be obscured from view by a deck or parapet of a sidewalk shed or bridge; and
ARTICULATING BOOM CRANE. A power operated machine for lifting or lowering a load and moving it horizontally that utilizes a boom consisting of a series of folding pin connected structural members, typically manipulated to extend or retract by power from hydraulic cylinders, with or without a hoisting mechanism integral to the machine.
AXLE. The shaft or spindle with which or about which a wheel rotates. On truck and wheel mounted cranes it refers to an automotive type of axle assembly including housing, gearing, differential, bearings and mounting appurtenances.
BEARER (PUTLOG). A horizontal transverse scaffold member (which may be supported by legs or runners) upon which the scaffoldplatform rests and joins scaffold uprights, posts, poles, and similar members.
BOOM. A section or strut, of which the heel (lower end) is affixed to a base, carriage or support, and whose upper end supports a cable and sheaves where the load is lifted by means of wire rope and a hook.
BOOM POINT. The outward end of the top section of the boom, containing the hoist sheave assembly.
BRAKE. A device used for retarding or stopping motion by friction or power means.
BUCKET HOIST. A power or manually operated suspended bucket contained by guide rails used for raising or lowering material exclusively and controlled from a point outside the conveyance.
CABLEWAY. A power operated system for moving loads in a generally horizontal direction in which the loads are conveyed on an overhead cable, track or carriage.
CERTIFICATE OF APPROVAL. A certificate issued by the department upon review and approval of the engineering and testing of a specific make and model of hoisting equipment to ensure compliance with the applicable provisions of this code and its referenced standards
CLAMSHELL. A shovel bucket with two jaws which clamp together by their own weight when it is lifted by a closing line.
*CLIMBING/JUMPING. The raising or lowering of a tower or climber crane to different floors or levels of a building or structure.
*Section BC 3302.1 was amended by: Local Law 46 of 2008. This law has an effective date of December 22, 2008.
COMMERCIAL TRUCK MOUNTED CRANE (BOOM TRUCK). Acrane consisting of a rotating superstructure (center post or turntable), boom, operating machinery, and one or more operator's stations mounted on a frame attached to a commercial truck chassis, usually retaining a payload hauling capability whose power source usually powers the crane. Its function is to lift, lower, and swingloads at various radii.
COMPETENT PERSON. One who is capable of identifying existing predictable hazards in the surroundings or conditions that are unsanitary, hazardous or dangerous, and who has authorization to take prompt corrective measures to eliminate such hazards.
*CONCRETE WASHOUT WATER. Wastewater from the rinsing of equipment used to mix, transport, convey, and/or place concrete. Such equipment shall include, but not be limited to, concrete buckets, concrete hose lines and pumps, boots, shovels, finishing tools, wheelbarrows, motorized concrete carts, concrete pour funnels and the chute of concrete mixer trucks.
Exceptions:
This term shall not include wastewater from the rinsing of equipment involved in the preparation, conveyance or application of concrete that is
mixed on site if the total quantity of concrete is less than or equal to one and one half cubic yards, or
from bagged ready mix if the total quantity of concrete is less than or equal to sixty (60) eighty pound bags, or eighty (80) sixty pound bags, or the equivalent.
This term shall not include wastewater from the rinsing of the wheels, undercarriage or chassis of concrete mixer trucks.
*Section BC 3302.1 was amended by: Local Law 70 of 2011. This law has an effective date of July 1, 2012.
CORNER SCAFFOLD (ANGLE SCAFFOLD). A suspended scaffold consisting of an assembly of two or more platforms connected non-lineraly and designed and manufactured to fit around a corner or a projecting part of a building.
COUNTERWEIGHT. Weight used to supplement the weight of the machine in providing stability for lifting loads.
CRANE. A power operated machine for lifting or lowering a load and moving it horizontally which utilizes wire rope and in which the hoisting mechanism is an integral part of the machine. The definition of a crane shall also include articulating boom crane, regardless of whether it has a hoisting mechanism integral to the machine.
CRAWLER CRANE. Acrane consisting of a rotating superstructure with a power plant, operating machinery, and boom, mounted on a base and equipped with crawler treads for travel. Its function is to lift, lower, and swingloads at various radii.
DEBRIS NET or NETTING. A netting of a fine mesh of a size and strength sufficient to catch debris such as falling tools and materials.
DEMOLITION, FULL. The dismantling, razing, or removal of all of a building or structure, including all operations incidental thereto.
DEMOLITION, PARTIAL. The dismantling, razing, or removal of structural members, floors, interior bearing walls, and/or exterior walls or portions thereof, including all operations incidental thereto.
DERRICK. An apparatus consisting of a mast or equivalent member held at the end by guys or braces, with or without a boom, for use with a hoisting mechanism and operating ropes, for lifting or lowering a load and moving it horizontally.
*DISMANTLING. The final process of taking apart, piece by piece, in a specific sequence, the components of a crane. Dismantling shall include climbing and jumping.
*Section BC 3302.1 was amended by: Local Law 46 of 2008. This law has an effective date of December 22, 2008.
DRUM. The cylindrical member around which a rope is wound for raising and lowering the load or boom.
*ERECTION. The assembly and placement of crane sections and components into place, including all operations incidental thereto. Erection shall include climbing and jumping.
*Section BC 3302.1 was amended by: Local Law 46 of 2008. This law has an effective date of December 22, 2008.
GUY. Aropeused to steady or secure the mast or other members in the desired position.
HEAVY DUTY SIDEWALK SHED. A sidewalk shed designed to carry a live load of at least 300 pounds per square foot (1465 kg/m2).
HOISTING MACHINE. A power operated machine used for lifting or lowering a load, utilizing a drum and a wire rope, excluding elevators. This shall include but not be limited to a crane, derrick, cableway and hydraulic lifting system, and articulating booms.
HOISTING EQUIPMENT. Equipment used to raise and lower personnel and/or material with intermittent motion.
JIB. An extension attached to the boom point to provide added boom length for lifting specified loads. The jib may be in line with the boom or offset to various angles in the vertical plane of the boom.
JUMP (JUMPING). The process of adding or removing mast or tower sections to equipment that has already been erected.
LAY. That distance measured along a wire rope in which one strand makes one complete helical convolution about the core or center.
LIGHT DUTY SIDEWALK SHED. A sidewalk shed designed to carry a live load of at least 150 pounds per square foot (732.3 kg/m2)
LOAD RATINGS.Crane and derrick ratings in pounds (kilograms) established by the manufacturer in accordance with standards set forth in rules promulgated by the commissioner.
LOAD RATING CHART. A full and complete range of manufacturer's craneload ratings at all stated operating radii, boom angles, work areas, boom lengths and configurations, jib lengths and angles (or offset), as well as alternative ratings for use and nonuse of optional equipment on the crane, such as outriggers and extra counterweights, that affect ratings.
LOWER LOAD BLOCK. The assembly of hook or shackle, swivel, sheaves, pins and frame suspended by the hoisting ropes.
MAST-CLIMBING WORK PLATFORMS. A powered device consisting of an elevating platform mounted on a base or chassis and mast, that when erected is capable of supporting personnel, material, equipment and tools on a deck or platform that is capable of traveling vertically in infinitely adjustable increments to reach the desired work level.
PERSONNEL HOIST. A mechanism and its hoistway, equipped with a car that moves vertically on guide members, used for hoisting or lowering workers or workers and materials for the construction, alteration or demolition of a building structure or other work
PLATFORM. A work surface elevated above lower levels. Platforms can be constructed using individual wood planks, fabricated planks, or fabricated decks.
POWER BUGGIES. An automotive vehicle designed or used for the transportation of materials on or about construction or demolitionsites. It shall not include automobiles, motor trucks, general purpose tractors, or excavating or material handling machinery.
QUALIFIED PERSON. A person who by possession of a recognized degree, certificate or professional standing, or who by knowledge, training and experience, has demonstrated his or her ability to solve or resolve problems related to the subject matter, the work or the project.
RUNBACK STRUCTURE. A temporary system of hoistway landing runways, vertical supports and horizontal diaphragms designed to bridge between the hoistway and the parent structure and to transmit both vertical and horizontal loads to the supporting structure and/or foundation.
STRUCTURAL NET or NETTING. A system of nets capable of complying with the prototype test described in ANSI A10.11-1989.
SUPERSTRUCTURE. The rotating upper frame structure of the machine and the operating machinery mounted thereon.
SUPPORTED SCAFFOLD. One or more platforms supported by outrigger beams, brackets, poles, legs, uprights, posts, frames, including pre-fabricated frames that are mechanized but not motorized, or any similar rigid support, including back structures connecting hoistways to buildings, and including structures where sidewalk protection is constructed as an integral part of the apparatus.
TOWER. A vertical structural frame consisting of columns and bracing that are capable of supporting working and dynamic loads and transmitting them to the support(s).
All exposed, electrically charged, moving or otherwise dangerous parts of machines and construction or demolition equipment shall be located, guarded, shielded, or barricaded so as to prevent contact by the public.
Hose lines, wires, ropes, pipes, chains and conduits shall be located so that they will not constitute a tripping hazard. Where it is necessary to carry such lines across sidewalks, or any public way, they shall either be suspended at least 8 feet (2438 mm) above the walks, or suitable chamfered planks or a pedestrian bridge shall be provided.
Contractors sheds and offices located within 30 feet (9144 mm) of new construction or existing buildings shall be made of metal or other noncombustible material. Fire retardant treated wood may be used when protected from the weather.
The location of all existing utilities and service lines shall be determined and adequate measures taken, or devices provided, to safeguard the public and property before such utilities are disturbed. If any utility is to be removed, relocated, or have its service interrupted, the utility company or city agency affected shall be notified at least 72 hours in advance.
Fire preventive, sanitary, or other facilities that have been provided for the protection of life, health, and property shall be continuously maintained and protected unless authorization is obtained from the agency having jurisdiction to temporarily or permanently disconnect such facility.
All temporary electrical equipment and wiring shall meet the requirements of the New York City Electrical Code, and shall be maintained in compliance with such requirements. Portions of permanent electrical installations may be used for temporary operations provided the requirements of the New York City Electrical Code are met.
The person superintending the work shall notify the utility company affected at least 72 hours before the commencement of work that may affect a power line, above or below ground.
No street or sidewalk shall be closed either in whole or in part without a permit from the department of transportation. Such permit shall be displayed at the job site.
The closing or temporary use of streets or sidewalks or the obstruction of any part thereof shall comply with the requirements of the department of trans- portation.
All areas used by the public shall be maintained free from ice, snow, grease, debris, equipment, materials, projections, tools, or other items, substances, or conditions that may constitute a slipping, tripping, or other hazard.
Waste dumpsters, debris boxes and skip boxes shall comply with the following:
Waste dumpsters, debris boxes and skip boxes shall be secured by rope, cable or chocking at wheels at the end of the workday in order to prevent movement. Such waste dumpsters, debris boxes and skip boxes shall not be placed at the edge of the building at any time, except when being moved from the floor or building.
Containers containing debris or waste shall be covered at the end of the workday and at any time when full to near the rim. Containers need not be covered when they are not in use or while stored in a fully enclosed space at the end of the workday.
Sufficient containers of metal, canvas, plastic or other material acceptable to the commissioner shall be available for the storage of all garbage and debris.
A daily inspection shall be made for construction or demolition debris on all floors and if the building is a major building, such inspection shall be noted in the site safety log.
When not being used, materials, equipment and tools that might fall from levels above areas used by the public shall be kept away from edges or openings.
When exterior walls are not in place, stored material shall be kept at least 10 feet (3048 mm) back from the perimeter of the building. However, when the floor area is less than 1,000 square feet (304.8 square meters), stored material may be kept not less than 5 feet (1524 mm) back from the perimeter of the building.
Material may be stored between 5 and 10 feet (1524 and 3048 mm) back from the perimeter of the building when such material weighs less than 750 pounds (340.2 kg).
Material stored on floors of a building or elsewhere on the site shall be secured when not being used.
Storage of materials at top working floors shall comply with the following:
Material may be stored within 2 feet (610 mm) of the edge of a building provided that such material is stored not more than two stories below the stripping operation on concrete structures, or the uppermost concrete floor on steel frame structures. Such material shall be secured against accidental movement. Storage of material on all other floors shall conform to Section 3303.4.5.1 and shall be secured when not being used.
No material shall hang over the edge of a building unless banded and braced preparatory to relocation at the end of the workday. Where such material is so banded and braced, it may overhang the floor of the stripping operation by not more than one-third of its length so long as it is relocated on the next workday for concrete operations.
Where the steel mill and lumber mill are located, material may overhang for relocation until the next workday. No more than two floors shall be designated as steel mills or lumber mills.
Combustible waste material or combustible debris shall not be permitted to accumulate, and shall be removed from the site at reasonable intervals in accordance with the requirements of the New York City Fire Code.
Precautions shall be taken to prevent concrete or mortar washings, sand, grit, or any other material that would cause clogging from entering a sewer or drain.
Chute enclosures shall comply with the following requirements:
Material chutes that are at an angle of more than forty-five degrees with the horizontal shall be entirely enclosed on all sides, except for openings at the floor levels for the receiving of materials. Such openings shall not exceed 48 inches (1219 mm) in height, measured along the wall of the chute, and all openings, except the top opening, shall be closed and secured when not in use.
Chutes at an angle of less than forty-five degrees with the horizontal may be open on the upper side.
Chute construction shall comply with the following requirements:
Every chute used to convey waste material from a building shall be rigidly supported and braced throughout its height. Chutes less than 24 inches (610 mm) in maximum dimension shall be constructed of not less than 1-inch (25.4 mm) (nominal) wood or 1/8 inch (3.18 mm) thick steel. Chutes more than 24 inches (610 mm) in maximum dimensions shall be constructed of not less than 2-inch (51 mm) (nominal) wood or 3/16 inch (4.76 mm) thick steel.
Chutes shall be provided with a metal impact plate where material is forced to change direction while falling.
A gate shall be provided at the lower end of every chute to control the loading of material into trucks and to close the chute at all other times. Splash-boards or baffles shall be erected to prevent materials from rebounding into the street or under the sidewalk shed.
A bumper or curb at least 4 inches by 4 inches (102 by 102 mm) in section shall be provided at each chute opening where such opening is level with, or below, the floor or platform. Every space between the chute and the edge of the opening in the floor or platform shall be solidly planked.
When used in the following applications, all chutes constructed of combustible material shall be covered on the exterior with corrugated steel sheeting having a minimum thickness of 24 gauge through their entire height. Alternatively, chutes shall be constructed of non-combustible material:
Where salamanders or other heating equipment are used to provide temporary heating during the placing of concrete for a floor, an escape hatch shall be provided from the floor where the concrete is being placed and shall extend through at least one story immediately below such floor. The escape hatch shall be located as near to the center of the building as practical.
The escape hatch shall be constructed with at least two ladders enclosed in a metal shield. The ladders shall extend from a distance of 3 feet (914 mm) above the floor under construction to at least two stories below, unless such floor is less than two stories above the lowest floor. The metal shield shall enclose the ladders on all sides from the top of the floor where the concrete is being placed to at least the top of the floor next below. The inside dimensions between faces of the shield shall be not less than 3 feet 8 inches (1118 mm).
The space between the shield and the perimeter of the opening in the floor under construction and also between the shield and the perimeter of the opening in the floor next below, shall be decked over with 2-inch (51 mm) or heavier planking covered with plywood or sheet metal so as to make the decking smoke tight. At the termination of the ladders, the opening in the floor shall be covered completely with 2-inch (51 mm) planking or other material of equivalent strength.
No hazardous or combustible material shall be kept at the site unless water supply for fire protection, either temporary or permanent, is available at the site.
When work reaches a height greater than 75 feet (22 860 mm) in a building for which a standpipe system will be required, a permanent or temporary standpipe meeting the requirements of Section 905 shall be kept in a state of readiness at all times for use by fire fighting personnel. No standpipe shall be considered to be in a state of readiness unless it is painted red in accordance with the provisions of Section 905.11 of this code. The system shall be a dry system when freezing conditions may be encountered.
Existing standpipe systems in structures undergoing demolition shall be maintained as dry standpipes. At the commencement of demolition, the standpipe risers shall be capped above the outlet on the floor immediately below the floor being demolished so as to maintain the standpipe system on all lower floors for Fire Departmentuse. Cutting and capping of standpipes during demolition work shall be performed only by a licensed master plumber or licensed master fire suppression piping contractor who has obtained a permit for such work. Standpipe hose, nozzles and spanners are not required to be maintained and may be removed at any time. Siamese hose connections shall be kept free from obstruction and shall be marked by a metal sign reading, "Standpipe Siamese Connection" and by a red light at night. The red paint required pursuant to Section 905.11 of this code shall be maintained during any demolition operations. All existing house check valves shall remain in place until completion of the demolition work.
The standpipe system may be used for water supply necessary to demolition operations. In freezing weather, such standpipe system shall be completely drained after use to prevent freezing. Existing standpipe systems shall not be utilized to convey compressed air unless the standpipe consists of two or more risers. In such case and upon fire department approval, one of the risers may be used to convey compressed air to any floor or portion of the premises.
*Section BC 3303.8 was amended by: Local Law 60 of 2009 — Update #26. This law has an effective date of Mar. 2, 2010.
Air pressurized alarm systems shall be provided as set forth in items 1 through 5 below. The provisions of NFPA 14, Chapter 12, as modified by Appendix Q, shall also apply.
Demolitions. In vacant buildings and structures undergoing demolition, all existing standpipes shall be maintained in a state of readiness as dry standpipes in accordance with Item 2 of Section 3303.8 and shall be provided with an air pressurized alarm system.
New buildings and structures. All required permanent or temporary standpipes shall be in a state of readiness once the work reaches a height greater than 75 feet (22 860 mm) and shall contain an air pressurized alarm system.
Submission of application. An application to install an air pressurized alarm system shall be filed by a registered design professional and a permit obtained by a licensed master plumber or licensed master fire suppression piping contractor. A licensed electrician shall obtain all required electrical permits in accordance with Chapter 3 of Title 27 of the Administrative Code.
Specifications. The following provisions shall apply to the air pressurized alarm system:
Pressure. Pressure shall be maintained in the standpipe and cross connections at all times and shall not exceed 25 psig (172 kPag) by utilizing nitrogen or an air compressor with an air dryer. The supervisory pressure shall be as determined by a registered design professional.
Automatic air pressurized alarm activation. The alarm shall be automatically activated when the pressure drops below the supervisory pressure or rises above the maximum pressure of 25 psig (172 kPag). When the alarm is activated, notification shall be made to the Fire Department in accordance with Section 901.7.7 of the New York City Fire Code, all work at the site shall cease, except as provided in Item 4.2.1, and an investigation of the entire standpipe system and air compressor shall be immediately performed to determine the cause of the alarm. Unless authorized by the Fire Department, no construction or demolition work shall resume until the standpipe system is repaired and the appropriate pressure is restored, except that any repairs to the standpipe system needed to restore the required pressure shall be undertaken immediately and the standipe system restored as soon as possible. There shall be compliance with the requirements of Section 901.7.7 of the New York City Fire Code while the standpipe system is out of service. Upon completion of repairs to the standpipe system a full inspection of such system shall be performed, which shall include, among other things, visually tracing the standpipe, including risers, cross connections and siamese connections to verify that no breach exists and checking all gauges of the standpipe system to ensure the standpipe system has been restored to a state of readiness.
Notwithstanding the provisions of Item 4.2, the activation of the alarm shall not require the cessation of work necessary for the completion of concrete pouring operations in progress at the time of alarm activation, where such cessation would cause a cold joint that would impair the structural integrity of the finished construction. The continuation of such operations shall be permitted only until an orderly termination of such operations can be effectuated. The site safety manager or coordinator shall record the names and locations of any employees necessary for the completion of the concrete pouring operations and provide them to the Fire Department personnel who arrive on the scene.
Air compressor. The air compressor shall be designed to automatically cut in and cut out at the supervisory pressure and shall be tied into the standpipe system between the siamese connections and the house check valves. The air compressor shall utilize an air dryer during times when freezing conditions exist to condition the air entering the dry standpipe system.
Alarm. The standpipe alarm system shall utilize pressure switches and control equipment to annunciate a local audible alarm on site that can be heard during working and non-working hours. The audible signal of the horn shall be at least 15 dBA above the ambient noise level but no more than 110 dBA.
Power supply. The standpipe alarm system shall be connected to an active, dedicated power supply at all times.
Check valves. Check valves shall be installed to prevent water from entering the air compressor.
Locks and caps. All control valves shall be chained and locked in the appropriate position and shall be provided with capped outlets. All hose valves shall also be provided with capped outlets.
Fire Department connections. Three inch (76 mm) iron hose plugs with gaskets in Fire Department connection swivels shall be provided.
Drainage. Provisions shall be made to drain water in any trapped sections of the dry standpipe system that are subject to freezing.
Manual air release connection. A minimum 2.5-inch (64 mm) connection located immediately downstream of the Fire Department Siamese connection check valve shall be provided and piped to a location immediately adjacent to the Siamese connections. This line shall be fitted with a 2.5-inch (64 mm) hose valve and shall allow for release of the pressurized air from the dry standpipe system. The number of air release valves provided shall be such that the air pressure shall be released in no more than 3 minutes, which shall be verifiable by an actual air release test performed at the time of the initial installation,
Construction documents. Plans shall identify all standpipe risers, cross connections, siamese connections, any intermediate check valves that have to be removed, proposed location of the air release connections, designation of the supervisory pressure, complete information regarding the alarm system, and procedures for the safe pressurization and depressurization of the system.
Signage. Signage shall be provided at all Siamese connections indicating that the dry standpipe system is pressurized and showing the location of the manual air release
Planned removal from service of standpipe system and standpipe air pressurized alarm. Whenever the standpipe system is to be placed out of service for the addition of a new section to the system, removal of an existing section as demolition operations progress, or other planned event, the standpipe alarm may be temporarily deactivated subject to compliance with the requirements of Section 901.7.7 of the New York City Fire Code. Where a site safety manager or coordinator is required by Section 3310.5 of this code, all alarm activations, inspections, and repairs shall be logged into the log book maintained by such site safety manager or coordinator. If the standpipe system is not returned to a state of readiness and the alarm reactivated within 2 hours of such planned removal from service, all construction or demolition work at the site shall cease, unless otherwise approved by the Fire Department.
*Section BC 3303.8.1 was added by: Local Law 64 of 2009 — Update #28. This law has an effective date of Feb. 4, 2010.
Required exits, existing structural elements, fire protection devices and sanitary safeguards shall be maintained at all times during remodeling, alterations, repairs or additions to any building or structure.
Exception: When such required elements or devices are being remodeled, altered or repaired and adequate alternate provisions are made.
Where repairs or alterations are conducted in occupied buildings, barricades, signs, drop cloths, and other protective means shall be erected as required to provide reasonable protection for the occupants against hazard and nuisance. In buildings containing occupied dwelling units, all work shall be performed in accordance with a tenant protection plan as required by Chapter 1 of Title 28 of the Administrative Code.
Where a building being constructed reaches a height greater than 50 feet (15 240 mm) or four stories, or where an existing unoccupied building exceeding 50 feet (15 240 mm) in height is altered, at least one temporary lighted stairway shall be provided, unless one or more of the permanent stairways are erected or maintained as the construction progresses. Demolition work shall comply with item 6 of 3306.9.9.
The maximum distance between the working deck of such a building under construction or alteration and the highest floor accessible to a temporary or permanent stair shall be no more than 40 feet or 4 floors. In concreteconstruction, the working deck is the floor being formed. In steel construction the working deck is the floor where the metal decking and steel components are being placed before concrete is poured.
Whenever construction or demolition work reaches a height greater than 75 feet (22 860 mm), at least one elevator meeting the requirements of Chapter 30, or a hoist meeting the requirements of Section 3318 shall be kept in readiness at all times for Fire Departmentuse. The maximum distance between the highest accessible floor from a temporary elevator or hoist and the working deck of the building under construction or demolition shall be no more than 75 feet (22 860 mm) or 7 floors. In concreteconstruction, the working deck is the floor being formed. In steel construction the working deck is the floor where the metal decking and steel components are being placed before concrete is poured.
If the travel of the hoist cannot be increased due to inclement weather, it shall be increased by the end of the next working day.
If any construction or demolition operation is abandoned, discontinued or interrupted, asolid fence meeting the requirements of Section 3307.7 shall be provided to protect the public from potential hazards on the site.
When permits have expired and when no permits have been issued within three months of the cessation of excavation operations, the lot shall be filled and graded to eliminate all steep slopes, holes, obstructions, or similar sources of hazard.
Fill shall consist of clean, noncombustible material. The final surface shall be graded in such a manner as to drain the lot, eliminate pockets in the fill, and prevent the accumulation of water, without damaging any foundations on the premises or on adjoining property.
No condition shall be created as a result of construction or demolition operations that will interfere with natural surface drainage.
Water courses, drainage ditches, etc., shall not be obstructed by refuse, waste building materials, earth, stones, tree stumps, branches, or other debris that may interfere with surface drainage or cause the impoundment of surface waters.
All concrete washout water shall be collected and contained in or on the concrete mixer truck or in pre-manufactured watertight containers specifically designed and fabricated for the purpose of collecting and containing concrete washout water on-site. Such containers shall be of sufficient quantity and size to accommodate all rinsing operations required on-site so as not to delay the timely return of concrete ready mix trucks to the concrete plant and shall be protected from breach or overflow at all times.
*Section BC 3303.15.1 was added by: Local Law 70 of 2011 — Update #56. This law has an effective date of July 1, 2012.
Rinsing operations and concrete washout water containers shall not be located less than 30 feet from any sewer, drain, catch basin, or body of water without the written approval of the commissioner.
*Section BC 3303.15.2 was added by: Local Law 70 of 2011 — Update #56. This law has an effective date of July 1, 2012.
Collected concrete washout water shall be transported off site for treatment and disposal or contained on site until completely evaporated. Any hardened concrete remaining after evaporation shall be disposed of, reused or recycled.
*Section BC 3303.15.3 was added by: Local Law 70 of 2011 — Update #56. This law has an effective date of July 1, 2012.
The provisions of this section shall apply to all excavations, including those made for the purposes of taking earth, sand, gravel, or other material, as well as for purposes of construction or demolition. During excavation, the provisions of Section 3309 for the protection of adjoining property shall also apply.
Stumps and roots shall be removed from the soil to a depth of at least 12 inches (305 mm) below the surface of the ground in the area to be occupied by the building. Wood forms which have been used in placing concrete, if within the ground or between foundation sills and the ground, shall be removed before a building is occupied or used for any purpose. Before completion, loose or casual wood shall be removed from direct contact with the ground under the building.
No earthwork within the property line shall commence unless the permit holder notifies the department, via phone or electronically, at least 24 hours, but no more than 48 hours prior to the commencement of such work. The notification shall state the date that such earthwork is to commence. Should the notification date fall on a weekend or official holiday, the permit holder shall notify the department on the last business day before the commencement date.
In the event that the earthwork does not begin on the date provided in the notification to the department, the permit holder shall notify the department of its cancellation not more than 24 hours prior to but no later than the date for which the earthwork was scheduled. Should the cancellation date fall on a weekend or an official holiday, the permit holder shall notify the department on the next business day after the intended commencement date. The permit holder shall notify the department of a new intended commencement date pursuant to the provisions above.
The commissioner may issue a stop work order if there is a failure to provide notice as required in this section and if the work is found to violate any of the provisions of this code, the Zoning Resolution, or other applicable laws or rules. Upon the issuance of such stop work order, the work shall be stopped for a minimum of three business days to enable the department to take any other appropriate action to ensure that the earthwork is being performed in a safe manner. The earthwork shall not recommence until the stop work order has been lifted.
Exceptions:
Hand excavation work that extends 5 feet (1524 mm) or less below the grade existing at the time of earthwork commencement and is 2 feet (610 mm) or more from an existing foundation. This exception shall not apply to any hand excavation work performed anywhere in existing or demolished basements or cellars that adjoin existing foundations.
Excavations for geotechnical observation that do not exceed 10 feet (3048 mm) in length, width or diameter and that are excavated under the supervision of a registered design professional.
Work on cemetery grounds for burials.
Emergency work performed by the Department of Housing Preservation and Development (HPD) or other agency as directed by the commissioner or work on unsafe buildings performed by HPD or other agency pursuant to a precept.
When an excavation to a depth of 5 to 10 feet (1524 mm to 3048 mm) is to be made within 10 feet (3048 mm) of an adjacent building, or when any excavation over 10 feet (3048 mm) is to be made anywhere on the site, the person causing an excavation to be made shall provide written notice to the owners of the adjacent building or buildings not less than 10 days prior to the scheduled starting date of the excavation. The written notice shall provide a description of the work to be performed, the time frame and schedule, and contact information of the person causing the excavation and of the department. Foundation or earthwork that is to be done with the use of explosives shall also be subject to the notification requirements set forth in Sections 3307.5.3 and 3307.5.4 of the New York City Fire Code.
*Section BC 3304.3.2 was amended by: Local Law 26 of 2008 — Update Page #3. This law has an effective date of July 01, 2008.
Whenever excavation or drilling, for any purpose, to a depth greater than 100 feet (30 480 mm) is proposed in a block that has any part of its boundary falling within 500 feet (152 m) horizontal distance from the centerline of any water tunnel as measured at or near the surface (the "Corridor"), or whenever excavation of any depth is proposed within 200 feet (60 960 mm) of any subway, an approval and permit shall be obtained from the New York CityDepartment of Environmental Protection and from the New York CityTransit Authority, respectively. The owner of the premises or the contractor shall notify the New York CityDepartment of Environmental Protection or the New York CityTransit Authority prior to commencement of any such activity. The issuance of any permit or approval by the department shall not relieve the applicant of the obligation to comply with any approval or permitting requirements of the New York CityDepartment of Environmental Protection or the New York CityTransit Authority.
Whenever drilling or excavation is planned deeper than five hundred (500) feet below grade, apermit may be required from the New York State Department of Environmental Conservation. The issuance of any permit or approval by the department shall not relieve the applicant of the obligation to comply with any approval or permitting requirements of the New York State Department of Environmental Conservation. Whenever any drilling for borings or geothermal wells is planned, the owner of the premises or the contractor shall notify the New York State Department of Environmental Conservation prior to commencement of such activity to determine if a permit is necessary.
The sides of all excavations, including related or resulting embankments, that are 5 feet (1524 mm) or greater in depth or height measured from the level of the adjacent ground surface to the deepest point of the excavation, shall be protected and maintained by shoring, bracing, sheeting, sheet piling, or by other retaining structures as may be necessary to prevent the sides of the excavation from caving in before permanent supports are provided. Such methods of protection shall be subject to special inspection in accordance with the provisions of Chapter 17.
Alternatively, excavation sides may be sloped not steeper than 45 degrees or stepped so that the average slope is not steeper than 45 degrees with no step more than 5 feet (1524 mm) high, provided such slope does not endanger any structure, including subsurface structures. Deviation from the foregoing limitations for cut slopes shall be permitted only upon the completion of a soil investigation report acceptable to the commissioner.
Sheet piling and bracing used in trench excavations shall be at least equivalent in strength to that specified in Tables 3304.4.1.1(1) and 3304.4.1.1(2).
TABLE 3304.4.1.1(1)
MINIMUM SIZES OF TIMBER BRACING AND TIMBER SHEET PILING FOR TRENCHES 4 FEET WIDE OR LESSa
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Note for Table 3304.4.1 (1): A steel sheet piling and bracing of equivalent strength may be substituted for wood sheet piling and timber bracing.
TABLE 3304.4.1.1(2)
MINIMUM SIZES OF TIMBER BRACING AND TIMBER SHEET PILING FOR TRENCHES 4 TO 8 FEET WIDEa
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Note for Table 3304.4.1 (2): A steel sheet piling and bracing of equivalent strength may be substituted for wood sheet piling and timber bracing.
All sides or slopes of excavations or embankments shall be inspected after rainstorms, or any other hazard-increasing event, and safe conditions shall be restored.
A standard guardrail that meets the requirements of Section 3307.8, or a solid enclosure at least 3 feet 6 inches (1067 mm) high shall be provided along the open sides of excavations, except that such standard guardrail or solid enclosure may be omitted from a side or sides when access to the adjoining area is precluded, or where side slopes are one vertical to three horizontal or flatter.
Excavated material and superimposed loads such as equipment and trucks shall not be placed closer to the edge of the excavation than a distance equal to one and one-half times the depth of such excavation, unless the excavation is in rock or unless the sides of the excavation have been sloped or sheet piled (or sheeted) and shored to withstand the lateral force imposed by such superimposed loads. When sheet piling is used, it shall extend at least 6 inches (152 mm) above the natural level of the ground. In the case of open excavations with side slopes, the edge of excavation shall be taken as the toe of the slope.
Where trenching more than 5 feet (1524 mm) in depth is done by a mechanical digger, the required protection shall follow the boom as closely as practical.
All excavations shall be drained and the drainage maintained as long as the excavation continues or remains. Where necessary, pumping shall be used, provided proper permits are obtained from the New York CityDepartment of Environmental Protection.
Demolition operations shall not commence until the applicable pedestrian and adjoining property protection is in place as required by Sections 3307, 3308, and 3309.
A safety zoneapproved by the commissioner shall be provided around the demolition area. Fences that meet the requirements of Section 3307.7 shall be erected to prevent persons other than workers from entering such safety zone.
Exception.Partial demolition operations limited to the interior components of the building where mechanical demolition equipment, other than handheld devices, are not used.
The permit holder shall notify the department via phone or electronically, at least 24 hours, but no more than 48 hours prior to the commencement of such work.
Adjoining property owners shall be notified of upcoming demolition operations in writing not less than 10 days prior to the scheduled starting date of the demolition. The written notice shall provide a description of the work to be performed, the timeframe and schedule, and contact information of the person causing the demolition and of the department. Demolition or removal work that is to be done with the use of explosives shall also be subject to the notification requirements set forth in Sections 3307.5.3 and 3307.5.4 of the New York City Fire Code.
Exception.Partial demolition operations limited to the interior components of the building where mechanical demolition equipment, other than handheld devices, are not used.
*Section BC 3306.3.2 was amended by: Local Law 26 of 2008 — Update #3. This law has an effective date of July 1, 2008.
Where mechanical demolition equipment, other than handheld devices, is to be used in the full or partial demolition of a building or is to be used to remove debris or move material, approval of the commissioner for the use of the mechanical demolition equipment must be obtained prior to the commencement of demolition operations.
Unless permitted by the commissioner, mechanical demolition equipment shall not be used where a building or portion thereof occupied by one or more persons is located within the safety zone.
Demolitions performed as emergency work pursuant to Section 28-215.1 of the Administrative Code when such work is monitored by a qualified person with experience in demolition operations who is employed by the city agency that has been directed to perform or arrange for the performance of such work. If the department or such city agency determines that there is a need for supervision of the work by an engineer, such city agency shall retain an engineer or cause an engineer to be retained to supervise the demolition operations.
Full demolition where the demolition is to be accomplished without any mechanical demolition equipment, including handheld mechanical equipment, for:
Submittal documents shall be approved by the department before demolition work begins. Such submittal documents shall be signed, sealed, and submitted by a registered design professional and shall contain, at a minimum, the following:
Plans, sections, and details of the building or portion thereof to be demolished clearly showing the extent, sequence, and means and methods of demolition;
Bracing and shoring necessary to support all demolition operations through all sequences of the demolition;
Where mechanical demolition equipment, other than handheld devices, is to be used, a listing and description of all such proposed equipment to be used in the demolition, including the scope of equipment work and positioning of equipment on the existing structure. The description of the equipment shall include calculations showing the adequacy of the existing structure to support loads imposed by such equipment. If more than one piece of demolition equipment is proposed to be used at the same time, the effect of the simultaneous loads imposed on the existing structure shall be described and investigated; and
A description of compliance with the applicable provisions of Section 3306.9 of this code.
*Section BC 3306.5.1 was amended by: Local Law 57 of 2009 — Update Page #23.This law has an effective date of December 02, 2009.
Submittal documents for full or partial demolition using mechanical equipment other than handheld shall be signed, sealed and submitted by an engineer.
*Section BC 3306.5.1.1 was amended by: Local Law 57 of 2009 — Update Page #23.This law has an effective date of December 02, 2009.
The approved set of submittal documents shall be kept at the site at all times and be accessible for inspection. It shall be a violation of this code to use mechanical equipment, whether handheld or other than handheld, to perform full or partial demolitions unless the approved submittal documents required by Section 3306.5.1 are available for inspection. Failure to make submittal documents available on site may result in the issuance of a stop work order.
*Section BC 3306.5.2 was amended by: Local Law 57 of 2009 — Update Page #23.This law has an effective date of December 02, 2009.
Where mechanical demolition equipment, other than handheld devices, is to be used in the full or partial demolition of a building from within the building, or is to be used within the building to remove debris or move material, such demolition operation shall be subject to special inspection in accordance with the provisions of Chapter 17. The special inspector shall visit the site a minimum of three times: before demolition operations start, during demolition, and at the conclusion of demolition.
Steel, reinforced concrete and heavy timber construction shall be demolished column length-by-column length and tier-by-tier. Any structural member that is being dismembered shall not support any load other than its own weight, and such member shall be chained or lashed in place to prevent any uncontrolled swing or drop.
Structural members shall not be thrown or dropped from the building, but shall be slowly and carefully lowered by hoists equipped with adequate brakes and non-reversing safety devices.
Service utility connections shall be discontinued and capped, and certifications to that effect issued by the representative utility company shall be filed with the department.
No party wall balcony or horizontal fire exit shall be demolished, removed, or obstructed in any manner that would destroy the full effectiveness of such fire exit as a means of egress, unless a substitute means of egress meeting the requirements of Chapter 10 has been provided.
When existing sprinkler systems with siamese hose connections are present in structures undergoing full or partial demolition, such systems shall be maintained as a non-automatic sprinkler system, except as provided in Section 3306.9.6.1. When demolition starts, the sprinkler risers shall be capped immediately below the floor being demolished so as to maintain the sprinkler system on all lower floors for Fire Departmentuse. Cutting and capping of sprinklers during demolition work shall be performed only by a licensed master plumber or licensed master fire suppression piping contractor who has obtained a permit for such work. Siamese hose connections shall be kept free from obstruction and shall be marked by a metal sign reading "Sprinkler Siamese Connection" and by a red light at night. The red paint required pursuant to Section 903.6 of this code shall be maintained during any demolition operations.
*Section BC 3306.9.6 was amended by: Local Law 60 of 2009 — Update #26. This law has an effective date of March 2, 2010.
Requests for a variance from the sprinkler requirements of this section shall be limited to requests to remove a damaged or inoperable sprinkler system or a portion of such system in connection with demolitions or gut rehabilitations. Applications for construction document approvals for such requests shall be filed with the department by a registered design professional in accordance with the following procedure:
The filed application shall include a complete report prepared by the professional describing the extent of the damage and attesting as to why the system cannot be restored; and
The applicant shall file the request for variance with the Fire Department;
The Fire Department shall review and recommend any necessary safety measures required as a condition of granting the variance; and
The applicant shall submit the Fire Department's recommendation to the department along with proof of satisfactory implementation of such safety measures.
*Section BC 3306.9.6.1 was added by: Local Law 60 of 2009 — Update #26. This law has an effective date of Mar. 2, 2010.
Hazards shall be removed in accordance with the following requirements:
Before commencement of actualdemolition, all glass in windows, doors, skylights, and fixtures shall be removed.
In any structure more than 25 feet high (7620 mm), any window or other exterior wall opening that is within 20 feet (6096 mm) of a floor opening used for the passage of debris from floors above shall be solidly boarded up or otherwise substantially covered, unless such window or opening is so located as to preclude the possibility of any person being injured by material that may fall from such window or opening.
Before demolition is started, the cellar and all floors shall be thoroughly cleaned of combustible materials and debris. All fixtures and equipment that would cause voids in the fill shall be removed. If the cellar is to be filled to grade, the first floor construction shall be removed and the existing cellar floor shall be broken up to the extent necessary to provide ground drainage and prevent accumulation of water. If the cellar is not to be filled, positive cellar drainage shall be provided.
All asbestos shall be removed and certifications to that effect shall be filed with the department and the Department of Environmental Protection.
Demolition of walls and partitions shall comply with the following requirements:
Demolition of walls and partitions shall proceed in a systematic manner, and all work above each tier of floor beams shall be completed before any of the supporting structural members are disturbed.
Sections of masonrywalls shall not be loosened or permitted to fall in such masses as to affect the carrying capacity of floors or the stability of structural supports.
No wall, chimney, or other structural part shall be left in such condition that it may collapse or be toppled by wind, vibration or any other cause.
No section of wall with a height more than 22 times its thickness shall be permitted to stand without bracing designed by a registered design professional.
Where brick or masonrychimneys cannot be safely toppled or dropped, all materials shall be dropped down on the inside of such chimneys.
All enclosed vertical shafts and stairs shall be maintained enclosed at all floors except the uppermost floor being demolished, and all work on the uppermost floor shall be completed before stair and shaft enclosures on the floor below are disturbed. All hand rails and banisters shall be left in place until actualdemolition of such floor is in progress.
No bearing partition shall be removed from any floor until the floor framing system on the floor above has been removed and lowered. All header beams and headers at stair openings and chimneys shall be carefully examined, and where required shall be shored from the cellar floor through successive floors. All operations shall be continually inspected as the work progresses to detect any hazards that may develop.
Material shall not be stored on catch platforms, working platforms, floors, or stairways of any structure, except that any one floor of a building to be demolished may be used for the temporary storage of material when such floor can be evaluated by an engineer and proven to be of adequate strength to support one and one-half times the load to be superimposed. Such evaluation by the engineer shall be maintained by the permit holder and made available to the department upon request.
Storage spaces shall not interfere with access to any stairway or passageway, and suitable barricades shall be provided so as to prevent material from sliding or rebounding into any space accessible to the public. All material shall be safely piled in such storage locations in a manner that will not overload any part of the structure or create any hazard.
Before any material is stored on any floor, the existing flooring adjacent to bearing walls, shear walls, beams and columns shall be removed and the connections of the floor framing system to the bearing walls, shear walls, beams and columns shall be carefully examined by a competent person to ascertain their condition and adequacy to support such material. If the connections are found to be in poor condition or inadequate to support the stored material, no material shall be deposited on the floor until these connections are shored from the cellar floor through each successive floor or otherwise strengthened to safely support such material.
In buildings of noncombustible construction, floor slabs to an elevation of not more than 25 feet (7620 mm) above the legally established curb level may be removed to provide temporary storage for debris, provided that:
Debris stored in the cellar shall not be piled above the level of the adjacent exterior grade unless the contractor provides sheet-piling, shoring, bracing, or such other means necessary to insure the stability of the walls and to prevent any wall from collapsing due to horizontal loading created by the debris as determined by a registered design professional.
Debris, bricks, and similar material shall be removed through openings in the floors of the structure, or by means of chutes, buckets, or hoists that comply with the provisions of this chapter. Openings in any floor shall not aggregate more than 25 percent of the area of that floor unless it can be shown by submission from a registered design professional to the satisfaction of the commissioner that larger openings will not impair the stability of the structure.
Every opening used for the removal of debris in every floor, except the top or working floor, shall be provided with a tight enclosure from floor to floor, equivalent to that afforded by planking not less than 2 inches (51 mm) in thickness. As an alternative, in buildings not more than 6 stories in height, such openings may be protected by a tight temporary covering equivalent to that afforded by planks not less than 2 inches (51 mm) in thickness and laid close. Wherever such covering has been temporarily removed to permit debris removal, floor openings shall be protected by standard guardrails that meet the requirements of Section 3307.8. Such covering shall be promptly replaced in position upon the ceasing of such work at the end of each workday.
Every opening not used for the removal of debris in any floor shall be solidly planked over.
A licensed exterminator shall effectively treat the premises for rodent extermination as per the requirements of the Department of Health and Mental Hygiene.
All work required for structural stability and permanent waterproofing of adjacent buildings must be completed prior to demolitionsign-off.
At the completion of demolition operations, unless new construction is to follow within a period of three months, the site shall be graded, drained, or otherwise protected as provided in Section 3303.13.
Pedestrians shall be protected during construction, alteration, remodeling, or demolition activities as required by this section and the rules of the Department of Transportation. Signs shall be provided to direct pedestrian traffic.
Other than as specified in Section 3301.9 and 3301.10, there shall be no sign, information, pictorial representation, or any business or advertising messages posted on a sidewalk shed, bridge, fence, or other protective structure listed in this section that is erected at the construction or demolitionsite.
Where a protective structure required by this section obscures from view a lawful existing sign, atemporary sign may be installed in accordance with Section 3301.10. No illuminated signs shall be permitted on any protective structure required by this section.
*Section BC 3307.1.1 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 1, 2013.
A sidewalk, walkway, or temporary walkway shall be provided for pedestrian travel in front of every construction or demolitionsite unless the Department of Transportation authorizes the sidewalk to be fenced or closed.
Temporary walkways shall comply with the following:
Temporary walkways shall be of sufficient width to accommodate the pedestrian traffic, but in no case shall it be less than 5 feet (1524 mm) in width, and shall be provided with a durable walking surface.
All temporary walkways shall be illuminated at all times either by daylight or electric light. The level of illumination shall be a minimum of 1 foot-candle (11 lux) measured at the level of the walking surface. All lamps shall be enclosed in vandal-proof fixtures, have a minimum luminous efficacy of 45 lumens per watt or greater and be rated to operate at temperatures of 5 degrees Fahrenheit and higher. Electric lighting units shall be inspected daily; and burned out or inoperative units shall be replaced or repaired immediately. Photosensors may be used to control electric lighting according to the amount of daylight available. All photosensors shall be equipped for fail-safe operation ensuring that if the sensor or control fails, the lamps will provide the lighting levels required by this section.
Temporary walkways shall be provided with adequate slopes so that they are accessible and shall be designed to support all imposed loads, and in no case shall the design live load be less than 150 pounds per square foot (732.3 kg/m2).
Where permission has been granted by the Department of Transportation to locate a temporary walkway beyond the curb line, such temporary walkway shall be provided with a guardrail in accordance with the Department of Transportation's requirements.
*Section BC 3307.2.1 was amended by: Local Law 51 of 2010 — Update #45. This law has an effective date of July 1, 2011.
Foot bridges shall be of sufficient width to accommodate the pedestrian traffic, but in no case shall it be less than 5 feet (1524 mm) in width, and shall be provided with a durable walking surface.
All foot bridges shall be illuminated at all times either by daylight or electric light. The level of illumination shall be a minimum of 1 foot-candle (11 lux) measured at the level of the sidewalk walking surface. All lamps shall be enclosed in vandal-proof fixtures, shall have a minimum luminous efficacy of 45 lumens per watt or greater, and be rated to operate at temperatures of 5 degrees Fahrenheit and higher. Electric lighting units shall be inspected daily; and burned out or inoperative units shall be replaced or repaired immediately. Photosensors may be used to control electric lighting according to the amount of daylight available. All photosensors shall be equipped for fail-safe operation ensuring that if the sensor or control fails, the lamps will provide the lighting levels required by this section.
Foot bridges shall be provided with adequate slopes so that they are accessible and shall be designed to support all imposed loads and in no case shall the design live load be less than 150 pounds per square foot (732.3 kg/m2). The walkway on such bridge shall be provided with guardrails for its entire length and shall have cleats to prevent slipping. Where planks are used to pave the walkway, they shall be laid close and securely fastened to prevent displacement. Planks shall be of uniform thickness, and all exposed ends on ramps shall be provided with beveled fillers to eliminate tripping hazards.
*Section BC 3307.2.2 was amended by: Local Law 51 of 2010 — Update #45. This law has an effective date of July 1, 2011.
Unless the street is officially closed to the public during construction or demolition operations pursuant to a permit from the Department of Transportation, the following minimum safeguards shall be provided for the protection of the public.
A sidewalk shed that meets the requirements of Section 3307.6 shall be erected as follows:
When a structure higher than 40 feet (12 192 mm) is to be constructed and the horizontal distance from the top of the structure to the inside edge of the sidewalk, walkway or temporary walkway is equal to one-half or less of the height of the structure.
When a structure higher than 25 feet (7620 mm) is to be demolished and the horizontal distance from the top of the structure to the inside edge of the sidewalk, walkway or temporary walkway is equal to one-half or less of the height of the structure, or when a structure 25 feet (7620 mm) or less is to be demolished and a sidewalk shed is required by the commissioner as part of a safety zone per Section 3306.2.1.
When, regardless of the height of the structure or the horizontal distance between the structure and the sidewalk, walkway or temporary walkway, material or debris is to be moved by a hoist, crane, derrick, or chute over a sidewalk, walkway or temporary walkway that is not closed to the public.
When a portion of a facade over 40 feet (12 192 mm) above curb level is being altered or repaired and the horizontal distance from the portion of the structure being altered or repaired to the inside edge of the sidewalk, walkway or temporary walkway is less than one-half the height of the structure being altered or repaired.
Exception: Access to walkways that are not under the jurisdiction of the Department of Transportation, and that are located in an area that is within a distance equal to or less than half the height of the highest work area, may be closed off by the authority having jurisdiction in lieu of providing a sidewalk shed provided the walkway is not required as part of the means of ingress or egress for a building.
All new construction or demolitionsites, regardless of the height of the building to be constructed or demolished, shall be enclosed with a fence that meets the requirements of Section 3307.7.
A fence may be used in lieu of a sidewalk shed when a structure higher than 40 feet (12 192 mm) is to be constructed, or a structure higher than 25 feet (7620 mm) is to be demolished, and the horizontal distance from the structure being built or demolished to the inside edge of the sidewalk, walkway or temporary walkway is between one-half and three-quarters of the height of the structure.
For cases that do not fall within the circumstances described in Sections 3307.3.1 and 3307.3.2, a standard guardrail that meets the requirements of Section 3307.8 may be constructed along the inside edge of the sidewalk, walkway or temporary walkway. The rail shall be returned at its ends to the extent necessary to effectively close off the site.
If permission to close the sidewalk has been obtained from the Department of Transportation, the railing may be constructed along the curb or outside of the curb to such extent as approved by the Department of Transportation.
Openings in sidewalk sheds, fences, barriers, and railings for loading and unloading purposes shall be kept closed at all times except during actual loading and unloading operations.
Where a material pile or other obstruction, or an excavation, opening, or other hazard is located in or adjacent to a public way, such hazard shall be indicated by red flags or signs during daylight hours, and by red lanterns, red lights, oil flares, flashing beacons, lighted signs, or equivalent devices from sunset to sunrise. Such warning devices shall be located no more than 30 feet (9144 mm) apart.
In areas where special danger to the public exists, such as at vehicle entrances and exits, hoisting areas, points of storage of explosives or highly flammable material, or discharge ends of chutes, descriptive warning signs shall be provided. Such warning signs shall contain the word "DANGER" in prominent letters and, where in, or adjacent to, apublic way, shall be illuminated from sunset to sunrise. Barricades and/or designated personnel shall be provided to the extent necessary to keep the public away from such areas or to guide them around the areas.
Whenever any work is being performed over, on, or in close proximity to a highway, street, or similar public way, control and protection of traffic shall be provided by barricades, signals, signs, flagperson, or other devices, equipment, and personnel in accordance with the requirements of the Department of Transportation.
Where a building being constructed or demolished occupies a ground area between 5,000 square feet (1524 m2), and 40,000 square feet (12 192 m2), a competent watchperson shall be on duty at the site during all hours when operations are not in progress. Where the construction or demolition area occupies a ground area of more than 40,000 square feet (12 192 m2), at least one additional watchperson shall be on duty for each additional 40,000 square feet (12 192 m2) of construction or demolition area, or fraction thereof. The watchperson shall be familiar with the location of street fire alarm boxes and the location and use of fire fighting equipment on the job site.
A flagperson shall be provided whenever intermittent operations are conducted on, or adjacent to, areas open to use by persons other than workers, or when dangerous operations, such as blasting, may affect such areas.
Sidewalk sheds shall be erected when required by Section 3307.3.1. No sidewalk shed shall be erected without a permit in accordance with the requirements of Chapter 1 of Title 28. Following the receipt of a permit to erect a sidewalk shed, the permit holder shall post a sign on the sidewalk shed that meets the requirements of Section 3301.9.5.
Every sidewalk shed deck shall be designed and constructed as a heavy duty sidewalk shed to carry a live load of at least 300 pounds per square foot (1464.6 kg/m2). However, alight duty sidewalk shed constructed to carry a live load of 150 pounds per square (732.3 kg/m2) foot may be used when the building to be constructed, altered, or demolished is less than 100 feet (30 480 mm) in height.
Exception: Sidewalk sheds that provide a base for a scaffold or contractor's shed shall be designed by an engineer to have a live load capable of supporting the scaffold or contractor's shed plus an additional 200 pounds per square foot (976.4 kg/m2). No storage is allowed on sidewalk sheds that support scaffolds or contractor sheds unless the sidewalk shed has been designed to have a live load capable of supporting the scaffold or contractor's shed, the total storage load, and an additional 200 pounds per square foot (976.4 kg/m2). The ground where the shed is to be constructed shall be examined by an engineer to determine it is capable of supporting the total load.
When a sidewalk shed is required for the construction or alteration of a structure, the work shall stop at a height of 40 feet (12 192 mm) unless, and until, the sidewalk shed has been completed. Such shed shall remain in place until the structure is enclosed, all exterior work completed and the sash is glazed above the second story, the exterior of the facade is cleaned down, and until completion of all outside handling of material, equipment and machinery, and all dismantling of material hoists, or climber or tower cranes including the use of a derrick in their removal, above the second story.
When a sidewalk shed is required for the demolition of a structure, the sidewalk shed shall be completed before any demolition work is performed. Such shed shall remain in place until the structure has been razed to the height of the shed.
Protection shall be provided for those sidewalks or walkways that are in front of the building to be constructed, altered, or demolished. Sidewalks or walkways in a plaza or other similar space that lead from the street to an entrance or exit into or out of the building that cannot be officially closed shall be similarly protected.
Where deemed necessary by the commissioner, the deck shall cover the entire width of the sidewalk or walkway in front of the building, except for reasonably small clearances at the building line and the curb. In all other instances, the sidewalk shed shall protect the sidewalk or walkway to a minimum 5 foot (1524 mm) width. Sidewalk sheds may extend beyond the curb to such extent as may be approved by the Department of Transportation pursuant to a permit from such department.
Unless constructed solely to comply with Section 3307.3.1, item 3, sidewalk sheds shall extend 5 feet (1524 mm) past the building when the building is less than 100 feet (30 480 mm) in height, and 20 feet (6096 mm) past the building when the building is over 100 feet (30 480 mm) in height, regardless of whether such extensions are in front of the property being developed or in front of adjacent property. Extensions of sidewalk sheds complying with the foregoing shall be constructed so as not to unreasonably obstruct, either visually or physically, entrances, egress, driveways, and show windows of adjacent properties.
Sidewalk sheds shall be constructed in accordance with the following:
Sidewalk sheds shall be constructed out of wood, steel, or other materials having equivalent strength and suitability.
The members of the sidewalk shed shall be adequately braced and connected to prevent displacement or distortion of the framework. Where posts supporting the shed deck are placed beyond the curb, such posts shall be protected against displacement by vehicles as directed by the Department of Transportation. Such placement shall require a permit from the Department of Transportation.
The upright members of the sidewalk shed shall be plumb. The tolerance is L/100. "L" is measured as the distance from the ground to the first x-brace or bottom of the beam.
The deck of the sidewalk shed shall consist of planking laid closely and made tight.
Unless the top deck of the sidewalk shed is built solidly against the face of the structure in such a manner that no material can fall onto the sidewalk, the side of the shed toward the structure shall be solidly sealed with wood or other suitable material for the full height of the shed. Solid sliding or in swinging gates may be provided as necessary for the proper prosecution of the work.
The outer side and ends of the deck of the shed shall be provided with a substantial enclosure at least 3 feet 6 inches (1067 mm) high. Such enclosure may be vertical or inclined outward at approximately 45 degrees (0.79 rad), and shall consist of boards laid close together and secured to braced uprights, of galvanized wire screen not less than no. 16 steel wire gage with a 1/2 inch (13 mm) mesh, of corrugated metal, or of solid plywood. Temporary removal of portions of the enclosure shall be permitted for handling material.
All sidewalk sheds shall provide protection for the full width of the shed extending upward at an angle of 45 degrees (0.79 rad) from the ends of the deck and outward a horizontal distance of at least 5 feet (1524 mm) beyond the ends of the shed. Such sloping end protection shall be constructed to meet the requirements of numbered items two and three with substantial outriggers bearing on and securely attached to the deck.
The passageway under the shed shall have a minimum clear ceiling height of 8 feet (2438 mm).
Sidewalk sheds erected on or after June 1, 2013 shall be painted the color of hunter green.
*Section BC 3307.6.4 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 1, 2013.
The use of sidewalk sheds shall be in accordance with the following:
Material and debris shall not be stored on sidewalk sheds unless the shed has been so designed for storage in accordance with rules promulgated by the commissioner.
The underside of sidewalk sheds shall be lighted at all times either by daylight or electric light. The level of illumination shall be a minimum of 1 foot-candle (11 lux) measured at the level of the sidewalk walking surface. All lamps shall be enclosed in vandal-proof fixtures, have a minimum luminous efficacy of 45 lumens per watt or greater, and be rated to operate at temperatures of 5 degrees Fahrenheit and higher. Electric lighting units shall be inspected daily; and burned out or inoperative units shall be replaced or repaired immediately. Photosensors may be used to control electric lighting according to the amount of daylight available. All photosensors shall be equipped for fail-safe operation ensuring that if the sensor or control fails, the lamps will provide the lighting levels required by this section.
*Section BC 3307.6.5 was amended by: Local Law 51 of 2010 — Update Page #75. This law has an effective date of July 1, 2011.
When required by this code, fences shall be at least 8 feet (2438 mm) high and constructed of wood or other suitable material. They shall be built solid for their entire length, except for openings with solid sliding or in swinging gates as are required for the proper prosecution of the work, and for viewing panels, which shall be blocked with plexiglass or equivalent nonfrangible material.
The fence shall be constructed along the inside edge of the sidewalk, walkway or temporary walkway. If permission to close the sidewalk has been obtained from the Department of Transportation, such fence may be erected along the curb or outside of the curb to such extent as approved by the Department of Transportation. The fence shall be returned at its ends to the extent necessary to effectively close off the site.
Viewing panels shall be provided in solid fences erected on or after July 1, 2013, at a rate of one for every 25 linear feet (7.6 m) per frontage, with a minimum of one per frontage. Viewing panels shall be 12 x 12 inches (305 x 305 mm) in size and shall be blocked with plexiglass or an equivalent nonfrangible material. The top of the viewing panel shall be located no more than 6 feet (1829 mm) above the level of the ground, and the bottom of the viewing panel shall be located no less than 3 feet (914 mm) above the level of the ground.
*Section BC 3307.7.1 was amended by: Local Law 47 of 2013 — Update Page #75. This law has an effective date of July 01, 2013.
A standard guardrail shall consist of a 2 inch by 4 inch (51 by 102 mm) wood top rail or equivalent capable of withstanding, without failure, a force applied in any downward or horizontal direction at any point along its top edge of at least 200 pounds (90.7 kg). The guardrail shall be not less than 3 feet (914 mm) nor more than 3 feet 6 inches (1067 mm) above the platform and there shall be a 1 inch by 4 inch (25 by 102 mm) wood intermediate rail midway between the top rail and the floor or standard toeboard, both supported by 2 inch by 4 inch (51 by 102 mm) wood posts spaced not more than 8 feet (2438 mm) apart.
To provide necessary openings for intermittent operations one or more sections of a required railing may be hinged or supported in sockets. When supported in sockets, rails shall be so constructed that they cannot be jolted out. A button or hook may be used to hold the rail in a fixed position. Substantial chains or ropes may be used to guard such openings in standard railings. Where so used, the chains or ropes shall be taut at the same height as the rails of the standard railing.
In lieu of wood construction, posts and rails may be constructed of at least 11/4 inch (32 mm) diameter standard pipe of at least 2 inch by 21/4 inch (51 by 57 mm) angles. Spacing of rails and posts shall be as required above
Where a toeboard is required, it shall be at least 5 1/2 inches (140 mm) high and constructed of metal, wood, or other substantial material. It shall be installed along the edge of the floor, opening, platform, ramp, or runway. Such standard toeboard shall be securely fastened to the posts and installed so that no open space exists between the floor and the standard toeboard.
Pedestrian protection required by this chapter or by the Department of Transportation shall be maintained in place and kept in good order for the entire length of time pedestrians may be endangered. The owner or the owner's agent, upon the completion of the construction or demolition activity, shall immediately remove sidewalk sheds, fences, guard rails, temporary walkways, debris and other obstructions and leave such public property in as good a condition as it was before such work was commenced.
In the event the Department of Transportation must repair, maintain, or install intersection control signs or electrical equipment, including traffic signals or street lighting poles at a location where pedestrian protection required by this chapter is located, such pedestrian protection shall be removed as directed by the department of buildings as long as the removal is deemed to be safe and, if necessary, suitable appropriate pedestrian protection that does not interfere with the work of the Department of Transportation is installed.
Horizontal and vertical safety netting shall be provided when required below. Safety netting is required in addition to the sidewalk sheds, fences, and other pedestrian protection required by Section 3307.
Exception: Asupported scaffold may be used in lieu of horizontal safety netting provided the bottom, outer faces and ends of the scaffold are enclosed with debris netting or its equivalent so as to prevent the falling of material and debris.
When in the course of construction the building reaches a height of 4 stories or 40 feet (12 192 mm), vertical safety netting shall be maintained at each story except at the story at grade, the story immediately above the sidewalk shed and the roof level where a parapet is installed.
When exterior walls are being constructed, altered or repaired at a height greater than 6 stories or 75 feet (22 860 mm), horizontal safety netting shall be provided on the sides of the structure where the structure is not enclosed. A structure shall be considered to be enclosed when the permanent facade is completed except for the windows. Such windows shall be protected to a height specified in Section 3308.3 unless there is a sill not less than 2 feet 6 inches (762 mm) in height and vertical mullions or piers with a maximum opening of 5 feet (1524 mm) and a non-corrosive wire cable capable of withstanding a load of at least 200 pounds (90.7 kg) applied in any direction except upward.
When during the course of construction the building reaches a height of 6 stories or 75 feet (22 860 mm), horizontal safety netting shall be maintained at a level not more than two stories or 30 feet (9144 mm) below the stripping operation on concrete structures or the uppermost finished (and walkable) concrete floor on steel frame structures. The horizontal safety netting may be removed after the formwork for the topmost level of concrete is removed or after the topmost level of concrete for a steel building is poured.
When demolition of the exterior walls or the roof of a structure occurs at a height greater than 6 stories or 75 feet (22 860 mm), horizontal safety netting shall be provided. The horizontal safety netting shall be constructed and maintained not more than two stories or 30 feet (9144 mm) below the story from which the exterior walls and roof are being removed until the demolition has progressed to within six stories or 75 feet (22 860 mm) off the ground or adjoining roof level
When tarpaulins encase one or more floors immediately below the finished concrete floor in order to maintain temporary heat, the horizontal nets may be located no more than three floors below the finished concrete floor.
Required horizontal safety netting may be omitted in designated crane and derrick lifting areas so long as such lifting area is as indicated on the crane application and on the site safety program.
Horizontal safety netting shall consist of a horizontal system of nets and their supports that meet requirements set forth in department rules, and shall include a structural net lined with a debris net of a size and strength sufficient to catch falling tools and materials.
Horizontal safety netting shall project outward horizontally from the edge of the floor a minimum distance of 10 feet (3048 mm).
Vertical safety netting shall consist of a vertical system of nets and their supports that meet requirements set forth in department rules. Vertical safety netting shall be of a fine mesh of a size and strength sufficient to contain falling tools and materials. Wall opening screens, grills or tarpaulins may be used in lieu of vertical safety netting, provided that they shall be of such construction and mounting as to retain debris.
On every story where vertical safety netting is required, it shall extend from the floor to a height of not less than 60 inches (1524 mm). Vertical safety nets and their components shall also meet the requirements set forth in rules promulgated by the commissioner.
The holder of the work permit and his or her designee shall be responsible for the installation and maintenance of all horizontal and vertical netting, and for complying with the requirements of this section.
Where requests are made regarding interpretations, consultations, and reconsiderations of safety netting, the commissioner may, in specific cases, modify these regulations where proper methods are proposed to be employed.
Any appeal shall state the specific relief requested and shall make reference to the Site Safety Program, where applicable, the practical difficulty, proposed equivalencies consistent with public safety, and any stipulations.
Adjoining public and private property shall be protected from damage during construction or demolition work. Protection must be provided for footings, foundations, party walls, chimneys, skylights and roofs. Provisions shall be made to control water run-off and erosion during construction or demolition activities.
The responsibility of affording any license to enter adjoining property shall rest upon the owner of the adjoining property involved; and in case any tenant of such owner fails or refuses to permit the owner to afford such license, such failure or refusal shall be a cause for the owner to dispossess such tenant through appropriate legal proceedings for recovering possession of real property.
When permission to enter upon adjoining property has been obtained, a physical examination of such property shall be conducted by the person causing the construction or demolition operations prior to the commencement of the operations and at reasonable periods during the progress of the work. Observed conditions shall be recorded by the person causing the construction or demolition operations, and such records shall be made available to the department upon request.
Regardless of the excavation or fill depth, the person who causes an excavation or fill to be made shall, at all times and at his or her own expense, preserve and protect from damage any adjoining structures, provided such person is afforded a license in accordance with the requirements of Section 3309.2 to enter and inspect the adjoining buildings and property, and to perform such work thereon as may be necessary for such purpose. If the person who causes the excavation or fill is not afforded a license, such duty to preserve and protect the adjacent property shall devolve to the owner of such adjoining property, who shall be afforded a similar license with respect to the property where the excavation is to be made.
No excavation work to a depth of 5 to 10 feet (1524 mm to 3048 mm) within 10 feet (3048 mm) of an adjacent building, or an excavation over 10 feet (3048 mm) anywhere on the site shall commence until the person causing an excavation to be made has documented the existing conditions of all adjacent buildings in a pre-construction survey.
The following additional requirements shall apply during excavation:
The person causing the excavation shall support the vertical load of the adjoining structure by proper foundations, underpinning, or other equivalent means where the level of the foundations of the adjoining structure is at or above the level of the bottom of the new excavation.
Where the existing adjoining structure is below the level of the new construction or demolition, provision shall be made to support any increased vertical or lateral load on the existing adjoining structure caused by the new construction or demolition.
Where the new construction or demolition will result in a decrease in the frost protection for an existing foundation below the minimums established in Section 1805.2.1, the existing foundation shall be modified as necessary to restore the required frost protection.
Where a party wall will be affected by excavation, regardless of the depth, the person who causes the excavation to be made shall preserve such party wall at his or her own expense so that it shall be, and shall remain, in a safe condition. Where an adjoining party wall is intended to be used by the person causing an excavation to be made, and such party wall is in good condition and sufficient for the uses of the existing and proposed buildings, it shall be the duty of such person to protect such party wall and support it by proper foundations, so that it shall be and remain practically as safe as it was before the excavation was commenced.
Whenever underpinning is required to preserve and protect an adjacent property from construction or excavation work, the person who causes the construction or excavation work shall, at his or her own expense, underpin the adjacent building provided such person is afforded a license in accordance with the requirements of Section 3309.2 to enter and inspect the adjoining buildings and property, and to perform such work thereon as may be necessary for such purpose. If the person who causes the construction or excavation is not afforded a license, such duty to preserve and protect the adjacent property shall devolve to the owner of the adjoining property, who shall be afforded a similar license with respect to the property where the excavation is to be made.
Whenever subsurface operations are conducted that may impose loads or movements on adjoining property, such as driving of piles, compaction of soils, or soil solidification, the effects of such operations on adjoining property and structures shall be monitored.
Where placement of a foundation will cause changes in the ground water level under adjacent buildings, the effects of such changes on the stability and settlement of the adjacent foundations shall be investigated and provision shall be made to prevent damage to such buildings.
When, in the opinion of the commissioner, a potential hazard exists, elevations of the adjacent buildings shall be recorded by a registered design professional at intervals of 24 hours or less as determined by the commissioner to ascertain if movement has occurred.
When the regulation of a lot requires the ground on such lot to be raised or lowered and kept higher than the ground of the adjoining lot, provided the ground of such adjoining lot is not maintained at a grade lower than in conformity with the street or streets on which it is situated, or where an excavation has been made or a fill placed on any lot meeting the curb level requirements, and the adjoining land is maintained at a grade in conformity with or lower than the streets or streets on which it is situated, and is without permanent structures other than frame sheds or similar structures, a retaining structure shall be constructed for the safe support of adjoining ground, unless the bank between the adjoining properties is maintained at a safe angle of repose. Any necessary retaining wall shall be built and maintained jointly by the owners on each side, unless otherwise agreed to by both owners.
Where any owner maintains his or her ground either higher or lower than the legal regulation prescribed in the Administrative Code, the surplus retaining structure that may be necessary to support such height or provide for such excavation shall be made at the sole expense of such owner, and any additional thickness that may be required shall be built on the land of such owner.
Any retaining structure erected as provided above, standing partly on the land of each owner, may be removed by either owner when the original reason for the erection of such retaining structure ceases to exist.
When any construction or demolition operation exposes or breaches an adjoining wall, including load bearing and non load-bearing walls as well as party walls and non party walls, the person causing the construction or demolition operation shall, at his or her own expense, perform the following:
Maintain the structural integrity of such walls, have a registered design professional investigate the stability and condition of the wall, and take all necessary steps to protect such wall.
Maintain all required fire exits and passageways or provide substitutions meeting the requirements of this code.
Cut off close to the walls all beams in party walls, remove stub ends without weakening existing masonry, clean beam pockets of loose mortar, bend over all wallanchors at the beam ends in the standing wall, and brick-up all open beam holes with sound brick and cement mortar.
During demolition operations, where the floor beams of the adjacent building bear on the party wall, the person causing the demolition shall ascertain that such beams are anchored into the wall and, where such anchorage is lacking, shall provide anchorage or otherwise brace the standing wall.
During demolition operations, all non load-bearing chimney breasts, projections and any other debris exposed on party walls shall be examined and monitored by the person causing the demolition. Removal of such items shall be made under the supervision of a registered design professional only if the stability of the adjacent building or structure will not be affected. All openings shall be bricked up flush on the exterior side of the party wall. All masonry that is in poor condition shall be pointed and patched.
Where the waterproof integrity of an adjoining wall or building has been impaired due to construction or demolition operations, the person causing the construction or demolition operations shall, at his or her own expense, provide all necessary measures to permanently waterproof the adjoining wall or building in order to restore the weatherproof integrity of such adjoining wall or building. This shall include, but is not limited to:
Bending over and flashing all roofing material of adjoining buildings;
Sealing and permanently waterproofing all doors or other openings in party walls;
Properly sealing all cornices, where cut;
Pointing up and making waterproof any walls and parapets and any walls that have been disturbed;
Removing all exposed furring, lath, and plaster on party walls; and
Removing, replacing, and firmly anchoring any loose wall material.
Whenever any building is to be constructed or demolished above the roof of an adjoining building, it shall be the duty of the person causing such building to be constructed or demolished to protect the roof, skylights and other roof outlets of the adjoining building from damage, and to use every reasonable means to avoid interference with the use of the adjoining building during the course of construction or demolition. Such person shall be afforded a license in accordance with the requirements of Section 3309.2 to enter and inspect the adjoining building and perform such work thereon as may be necessary for such purpose; otherwise, the duty of protecting the roof, skylights and other roof outlets of the adjoining building shall devolve upon the owner of such adjoining building.
In addition, any person having the duty to alter or maintain chimneys of any adjoining building under and pursuant to the provisions of this code or the New York City Mechanical Code or other applicable laws and rules, shall likewise be afforded a license in accordance with the requirements of Section 3309.2 to enter and inspect such adjoining building and perform such work thereon as may be necessary for such purpose; otherwise, such duty shall devolve upon the owner of such adjoining building.
No trees outside the property line within the public right of way shall be disturbed or removed without the permission of the commissioner of the department of parks and recreation. Protection meeting the requirements of the department of parks and recreation shall be provided around the trunks of all such trees, and written notification shall also be made to the department of parks and recreation at least 48 hours prior to commencement of such work. No deleterious, caustic, or acid materials shall be dumped or mixed within 10 feet (3048 mm) of any such tree, nor shall salt for the removal of ice or snow be applied when runoff will drain to a tree.
This section outlines the requirements for site safety programs for major building construction or demolition that are in addition to the other applicable requirements of this chapter. These requirements are not intended to supersede other applicable city, state or federal requirements that address site safety and construction or demolition activity.
A site safety plan and site safety program is not required for the alteration of the faade of a major building between 10 and 14 stories in height.
A site safety plan and site safety program is not required for partial demolition operations in major buildings where the partial demolition operation is limited to the interior components of the building and where mechanical demolition equipment, other than handheld devices, are not used.
Asite safety coordinator certified by the department in accordance with the requirements of Chapter 4 of Title 28 of the Administrative Code may be used instead of a site safety manager for a major building that is:
Less than 100,000 square feet (30 480 m2) of lot coverage.
Asite safety manager or coordinator is not required for partial demolition operations in major buildings where the partial demolition operation is limited to the interior components of the building and where mechanical demolition equipment, other than handheld devices, are not used.
It shall be the responsibility of the builder/owner, agent, construction manager, or general contractor (the "Contractor") to designate a site safety manager or coordinator who must be present on a construction or demolitionsite when required, and who shall be responsible for all site safety requirements as specified in this chapter.
In the event that an alternate manager or coordinator will be acting as the full-time safety manager or coordinator for a period longer than two weeks, the department must be so notified. Any permanent change of site safety manager or coordinator requires immediate notification of the department. No proposed alternate manager or coordinator shall have as his or her primary duty the job of site safety manager or coordinator on any other construction or demolition project.
The contractor shall notify all of its supervisory personnel and all of its subcontractors working on the construction or demolitionsite of the name and responsibilities of the site safety manager or coordinator. The contractor shall state to its directly employed personnel and also to its subcontractors that the site safety manager or coordinator is responsible for monitoring compliance with laws and rules governing site safety, and that they are required to obey and implement all orders and directives relating to safety requirements.
In the event the site safety manager or coordinator discovers violation of the site safety regulations, he or she shall immediately notify the person or persons responsible for creating the violation, whether these persons are employed by the contractor or by subcontractors. If the site safety manager or coordinator is unable to obtain the cooperation of these persons in correcting the violation, he or she shall inform his or her direct supervisor immediately and request that the supervisor order the necessary corrective action. If the supervisor of the site safety manager or coordinator is not present at the site or is otherwise unavailable, the site safety manager or coordinator shall notify any other supervisory personnel of the contractor present on the job or any other responsible manager or officer of the contractor. All such violations and corrective work shall be recorded in the daily log.
It is the responsibility of the site safety manager or coordinator to monitor compliance with the safety requirements of this chapter and to perform all other safety duties assigned by the owner or contractor to meet legal requirements.
The site safety manager or coordinator) shall meet on a weekly basis with the designated representative of each subcontractor to ascertain that all subcontractors are complying with the applicable provisions of this chapter.
The site safety manager or coordinator shall, at a minimum, in accordance with rules promulgated by the department, conduct daily checks to ensure that a standpipe system is available and in a state of readiness at all times for use by fire fighting personnel, by verifying:
That valves are in place at each story below the construction floor;
That standpipes are connected to a water source or siamese connection; and
That siamese hose connections are free from obstruction and are marked by a red light and sign that reads, "Standpipe Siamese Connection."
The site safety manager or coordinator shall also, in accordance with such rules, conduct weekly checks to verify that no breach exists by visually tracing the standpipe, including risers, cross connections and siamese connections. A record of all such inspections shall be maintained by such site safety manager or coordinator in a log book.
*Section BC 3310.8.1.1 was added by: Local Law 59 of 2009 — Update #25. This law has an effective date of Sept. 3, 2009.
The site safety manager or coordinator shall immediately notify the department directly if he or she discovers any of the following conditions in the routine performance of the job:
Upon proper notification to the department of the existence of any of the above-noted circumstances, any responsibility the site safety manager or coordinator has under this code arising out of, relating to, or as a result of the existence of that circumstance, shall cease.
It shall be the responsibility of the site safety manager or coordinator to inspect personally, on a regular basis, specific areas and items on the construction or demolitionsite, as prescribed by rules promulgated by the commissioner, and to notify responsible personnel employed by the general contractor, construction manager or any subcontractor when violations of this chapter occur. The site safety manager or coordinator shall maintain a log of the inspection in accordance with the requirements set forth in rules promulgated by the commissioner.
In addition to the above requirements, the site safety manager or coordinator shall use reasonable prudence to ensure that safety is maintained at the job site as job conditions dictate.
The following additional personnel shall be employed to oversee concrete operations at major buildings as defined in section 3310.2 and such other classes of buildings or operations as the commissioner may designate by rule. These personnel shall coordinate directly with the site safety manager or coordinator designated in accordance with section 3310.6. In all instances, the designated site safety manager or coordinator retains responsibility for ensuring compliance with the provisions of section 3310 of this code and all applicable rules, and for signing the site safety log. The name and contact information of the additional site safety personnel shall be recorded in the site safety log.
*Section BC 3310.9 was added by: Local Law 40 of 2008 — Update #9. This law has an effective date of Jan. 1, 2009.
Beginning January 1, 2009, aconcrete safety manager shall be designated by the concrete contractor at those sites where the concrete portion of the project involves the pouring of a minimum of 2,000 cubic yards of concrete or such lesser amount as the commissioner may determine by rule. Concrete safety managers shall have five years of experience in concrete operations and shall have satisfactorily completed, by July 1, 2009 or within the five calendar years prior to registration, a thirty hour course approved by the commissioner that is sufficient to qualify the individual as a competent person under OSHA standards to oversee concrete operations, including such topics as formwork design, construction and stripping operations, rebar handling, and rigging. Concrete safety managers shall register with the department in the same manner as construction superintendents, and shall provide evidence of meeting the eligibility requirements set forth herein. As of July 1, 2009, no person shall perform the duties of a concrete safety manager without being registered as such with the department. The commissioner shall promulgate rules establishing the duration that such registration shall be valid and the requirements for renewal of the registration. The concrete safety manager shall be present during all concrete operations. For purposes of this section, "concrete operations" shall mean the pouring of concrete and the construction and stripping of concrete forms and related activities as specified by the commissioner.
*Section BC 3310.9.1 was added by: Local Law 40 of 2008 — Update #9. This law has an effective date of Jan. 1, 2009.
Design and construction of the tool must be such as to safely retain all internal pressures that may occur during its operation. The discharge mechanism shall be such that the projectile cannot be discharged by dropping the tool. The discharge mechanism shall be such that the discharge of each projectile shall be dependent on a separate and distinct act by the operator, and all safety features shall be durable.
A tool shall have such other characteristics as the commissioner may find necessary. Such other characteristics may include devices and materials external to the tool itself but associated with its function, and may also include in respect to high velocity projectile tools the basic requirements set forth above for explosive powered tools that discharge projectiles with comparable velocities.
Every projectile tool shall be properly maintained. No such tool shall be used if any part necessary to retain internal pressures or to prevent accidental discharge of a projectile is not in sound and operable condition.
The operation of projectile tools shall comply with the following:
A projectile tool shall be operated only by an authorized operator who shall be the owner, lessee, or other person having custody of the tool, or any other person whom he or she may authorize to operate it.
While a projectile tool is in the care and custody of an authorized operator, no other person shall handle or in any way utilize or modify it.
No authorized operator of a projectile tool shall leave it unattended while it is in a condition to discharge a projectile.
No person shall use a projectile tool for any purpose other than that for which it was manufactured.
No person shall point a projectile tool at another person or hold it at an angle that allows the projectile to fly free.
No person shall use a projectile tool in such a way as to endanger persons who may be in the vicinity.
5.6 Selection of load. No employer shall knowingly furnish to an employee for use in a tool any cartridge or load not suitable for safe use in that tool, whether by reason of excessive power, improper design or poor material. The operator shall use due care to select the proper cartridges or power loads, or other means of controlling the force of the explosion so that the tool develops no more than the necessary pressure to bring about the desired penetration. In doing so, the operator shall be guided by the manufacturer's specifications.
5.6.1 Proper Load. When doubt exists as to proper load, the operator shall make a trial shot to test the surface and the strength of the material to be penetrated. The trial shot shall be made with the lowest power level and then increasing strength until a proper fastening is made. During this test, the operator and all bystanders shall adhere to all safety rules including but not limited to wearing goggles and hard hats required for the job.
12.1 Powder-actuated tools using ammunition (power loads) shall be approved by the commissioner or other approved agency.
12.2 Labeling. A certificate or label indicating that the tool is approved shall be attached to the toolbox or operator's manual and shall be made available for inspection upon request of the commissioner.
The transportation, handling, storage, installation, connection, ventilation, and use of all volatile flammable oils, flammable and combustible mixtures, compressed gases, and other hazardous materials shall comply with the New York City Fire Code, and shall also be safeguarded in accordance with the requirements of Section 3307.4.2.
All scaffolds shall be erected and maintained so that the safety of public and property will not be endangered by falling material, tools or debris, or by collapse of the scaffold.
The permit holder or person directly in charge of any suspended scaffold supported by c-hooks or outrigger beams shall notify the department in a form and manner specified by the department at least 24 hours, but not more than 48 hours, prior to the installation or use of such scaffolding equipment.
The permit holder or person directly in charge of any scaffolding equipment shall immediately notify the commissioner following any accident involving scaffolding equipment. Following an incident, no person shall permit either of the following, without the permission of the commissioner:
Supported scaffolds 40 feet (12 192 mm) or more in height, outrigger scaffolds, and suspension scaffolds, including all supports, fastenings, connections and details, shall not be erected or installed unless and until a written permit has been issued by the commissioner on the basis of plans, drawings, and specifications. Copies of the permit shall be posted in a conspicuous location at the site visible to the general public. Copies of the approved plans shall be maintained at the site and made available to the commissioner upon request.
Exceptions:
Any two-point suspended scaffold supported by a parapet using C-hooks that meet the requirements of Section 3314.10.2 provided that prior notification is provided to the department in accordance with Section 3314.1.1.
Following the receipt of a permit to erect or suspend a scaffold, the permit holder shall post a sign that meets the requirements of Section 3301.9.6. Such sign shall be clearly visible from the street. Other than as required by Section 3301.10, there shall be no information, pictorial representation, or business or advertising messages posted on a scaffold.
Each scaffold and its components shall be capable of supporting, without failure, its own weight and at least four times the maximum intended load applied or transmitted to it in accordance with Section 3314.3.3. Each suspension rope, including connecting hardware, used on non-adjustable suspension scaffolds shall be capable of supporting, without failure, at least six times the maximum intended load applied or transmitted to the rope.
Where applicable, scaffolds and their connections to the building or structure shall be designed for wind loads as prescribed in Section 1609.
Copies of the plans, drawings, and specifications for all supports, fastenings, connections, and details shall be kept at the site and made available to the commissioner upon request.
When more than one trade is to use a scaffold simultaneously, the scaffold shall, at a minimum, be designed for a minimum of 50 pounds per square foot (244 kg/m2).
When plans are required by this section, they shall include a plan view, an elevation view, details of anchorage, scaffold designation in accordance with Section 3314.3.3 and, for supported scaffolds, the number of planked levels and the number of levels to be loaded simultaneously.
All scaffolds shall be designed for one of the intended loads described in Section 3314.3.3.1 to 3314.3.3.4. No scaffold shall be loaded in excess of the maximum load for which it is designed. Loads shall not be concentrated so as to cause stresses in excess of the allowable values designated for the applicable material described in this code.
The light duty scaffold is to be used for loads up to 25 pounds per square foot (122.05 kg/m2), and is intended for use by carpenters, painters, or others of similar trades. It shall not be used to support loads more severe than those imposed by such workers and a minimum amount of lightweight materials.
The medium duty scaffold is to be used for loads up to 50 pounds per square foot (244.1 kg/m2), and is intended for use by bricklayers, plasterers, pipe fitters or other similar trades. It shall not be used to support loads more severe than those imposed by such workers and a moderate amount of their materials.
The heavy duty scaffold is to be used for loads up to 75 pounds per square foot (366.15 kg/m2), and is intended for use by stone masons. It shall not be used to support loads more severe than those imposed by such workers and a reasonable supply of their materials.
The extra heavy duty scaffold is to be used for loads exceeding 75 pounds per square foot (366.15 kg/m2) and shall be designed in accordance with Section 3314.3.1.4.
Scaffolds that require a permit or design shall be erected and installed in accordance with the construction documents, drawings, and specifications for the scaffold. Upon completion of the installation of the scaffold, an inspection report verifying that the scaffold has been installed in accordance with the design drawings, construction documents and specifications shall be prepared by the designer, installer, or an approved inspection agency designated by both the designer and installer.
Every damaged or weakened scaffold shall be immediately repaired or secured and shall not be used until satisfactory repairs have been completed, and the scaffold is inspected under the provisions of Section 3314.4.3.
All scaffolds, except for suspended scaffolds, shall be inspected daily before each use by a competent person designated by the trade(s) using the scaffold. A record of such daily inspections shall be maintained and available at the site where the scaffold has been erected. Suspended scaffolds shall be inspected in accordance with Section 3314.4.3.1.
Before use, all suspended scaffolds shall be inspected daily by the licensed rigger or his or her foreman in accordance with Section 404 of Title 28 of the Administrative Code, or the licensed sign hanger or his or her foreman in accordance with Section 415 of Title 28 of the Administrative Code, or the superintendent of construction if the work is not performed by or under the supervision of a licensed rigger or sign hanger in accordance with the exception to Section 404.1 of Title 28 of the Administrative Code and Section 415.2 of Title 28 of the Administrative Code.
A record of such inspections shall be kept and maintained at the job site and shall be readily available and presented to department personnel upon request. The record shall be signed by the individual responsible for the inspection and shall also show the individual's name clearly and legibly printed.
Only workers with experience in erecting, repairing, maintaining, modifying, or removing supported scaffolds and with the training required by this paragraph shall be employed to perform this work. They shall be supervised by a designated superintendent or foreman who shall enforce such measures as necessary for the protection of the public and property.
No person shall knowingly permit or cause an individual who does not have the experience and training required by this paragraph to perform any of the work described in this paragraph.
Workers who erect, repair, maintain, modify or remove supported scaffolds 40 feet (12 192 mm) or more in height shall, at a minimum, have completed a department-approved training program or course that is at least 32 hours long, and shall complete a department-approved 8-hour refresher program or course every 4 years thereafter. The training program or course shall be based on the United States Department of Labor Occupational Safety and Health Department ("OSHA") scaffold safety and training guidelines and the scaffold requirements of this chapter. The training program or course shall be conducted by a registered New York State Department of Labor apprenticeship training program or by an educational institution or school chartered, licensed or registered by the New York State Department of Education or by a provider approved by the department and presented by an instructor(s) deemed qualified and competent in accordance with OSHA regulations.
Successful completion of the training program or course shall be evidenced by a dated scaffold certificate of completion issued by the provider of the training program or course. The certificate or a valid wallet card version of the certificate shall be readily available to the commissioner upon request, and shall be deemed valid for four years from its date of issuance.
Workers who erect, repair, maintain, modify, or remove a sidewalk shed that provides a base for a scaffold 40 feet (12 192 mm) or more in height are subject to the above requirements.
The requirement that a refresher program or course be completed every four years shall apply retroactively to individuals who satisfied such requirements prior to the effective date of this code.
*Section BC 3314.4.5 was amended by: Local Law 24 of 2008 — Update #2. This law has an effective date of July 1, 2008.
Every worker who uses a supported scaffold to perform his or her job tasks shall complete a department-approved four-hour training program or course, and a department-approved four-hour refresher program or course every four years thereafter, that includes instruction on the nature of electrical hazards, fall and falling object hazards, material handling on scaffolds, personal protection equipment, the nature of braces and tiebacks and their safe removal and the maximum intended load and load-handling capacities of scaffolds. The training program or course shall be conducted by a registered New York State Department of Labor apprenticeship training program or by an educational institution or school chartered, licensed or registered by the New York State Department of Education or by a provider approved by the department, and presented by an instructor(s) deemed qualified and competent in accordance with OSHA regulations.
Successful completion of the training program or course shall be evidenced by a dated scaffold user certificate issued by the provider of the training program or course. The certificate or a valid wallet card version of the certificate shall be readily available to the commissioner upon request, and shall be deemed valid for four years from its date of issuance.
No person shall knowingly permit or cause an individual who does not have the training required by this paragraph to use a supported scaffold.
The requirement that a refresher program or course be completed every four years shall apply retroactively to individuals who satisfied such requirements prior to the effective date of this code.
*Section BC 3314.4.6 was amended by: Local Law 24 of 2008 — Update #2. This law has an effective date of July 1, 2008.
The provisions of paragraphs 3314.4.5 and 3314.4.6 of this subdivision shall not apply to:
the erection, dismantling, repair, maintenance or modification of any supported scaffold performed by an employee of a public utility when such supported scaffold is located within the interior of a building or structure owned or operated by such utility and when such utility has a safety training program of not less than 32 hours for its employees who erect, dismantle, repair, maintain or modify such scaffolds; or
employees of a public utility performing work while using a supported scaffold, provided that such employees are trained, pursuant to the United States department of labor occupational safety and health administration's requirements, to be able to recognize the hazards associated with the type of supported scaffold being used, and to understand the procedures to control those hazards; or
the erection, dismantling, repair, maintenance or modification of stand alone, one story sidewalk sheds; or
a registered architect or professional engineer who is using a supported scaffold to perform inspections, as long as the architect or engineer does not perform work from or participate in the erection, dismantling, repair, maintenance or modification of any building or structure, including the supported scaffold.
*Section BC 3314.4.7 was added by: Local Law 24 of 2008 — Update #2. This law has an effective date of July 1, 2008.
Exception:Platformsused solely as walkways or used solely by workers performing scaffold erection and dismantling shall be planked to provide safe working conditions.
Each platform unit shall be installed so that the space between adjacent units and the space between the platform and the uprights is no more than 1 inch (25 mm) wide except where a qualified person can demonstrate that a wider space is necessary.
All lumber used in scaffolds or their supports shall be at least equal in strength and quality to construction grade lumber in accordance with Section 2301. See Table 3314.5.2 for the maximum span for scaffold planks.
The end of a platform shall extend over the centerline of its support a minimum of 6 inches (152 mm) unless cleated or otherwise restrained by hooks or equivalent means.
The end of a platform 10 feet (3048 mm) or less in length shall not extend over the centerline of its support more than 12 inches (305 mm) unless the platform and its tiedown are designed by a qualified person or the platform has guardrails to prevent access to the cantilevered end.
The end of a platform more than 10 feet (3048 mm) in length shall not extend over the centerline of its support more than 18 inches (457 mm) unless the platform and its tiedown are designed by a qualified person or the platform has guardrails to prevent access to the cantilevered end.
The footings and anchorage for every scaffold shall be sound and rigid, capable of carrying the maximum load without excessive settlement or deformation and secure against movement in any direction. Supports such as barrels, boxes, loose brick, loose stone, or other unstable materials shall not be used.
Safe points of anchorage include structural members of a building. Window cleaners anchors, window frames, mullions, handrails, standpipes, vents and other piping systems, electrical conduit, outrigger beams, counterweights or similar elements shall not be used as anchors or braceback points.
Lifeline anchorage shall be fastened to a fixed safe point of anchorage, shall be independent of the scaffold, and shall be protected from sharp edges and abrasion.
Loads from supported and suspended scaffolds imposed on an existing roof or floor or similar structure shall not be concentrated so as to cause stresses in excess of the allowable values designated for the applicable material described in this code.
The overhang of outrigger beams shall not exceed that specified by the design and the inboard length of beam shall be at least one and one-half times the outboard length.
The wire rope suspenders shall be securely fastened to the outrigger beams by steel shackles or equivalent means. The shackles and outrigger beams shall be placed so that the ropes will hang vertically.
Except for scaffoldplatforms 6 feet (3048 mm) or less above the ground, the open sides and ends of every scaffoldplatform shall be provided with a guardrail system and toeboard, unless otherwise specified for the particular type of scaffold. The guardrail system shall be installed before the scaffold is released for use by workers other than the workers who are erecting or dismantling the scaffold.
Where it is possible for the public to pass under, or next to a scaffold, the space between the top rail and toeboard shall be enclosed with a wire screen composed of not less than no. 18 steel wire gage with a maximum 1/2 inch (13 mm) mesh or equivalent synthetic safety netting. For the purpose of this provision the term "where it is possible for the public to pass under, or next to a scaffold" shall mean when the setback from the scaffold to the area used by the public is a distance equal to or less than half the height of the scaffold.
The top edge height of the toprails or equivalent member shall be installed between 38 inches and 45 inches (965 and 1143 mm) above the platform surface.
When midrails, screens, mesh, intermediate vertical members, solidpanels, or equivalent structural members are used, they shall be installed between the top edge of the guardrail system and the scaffoldplatform.
When mid-rails are used, they shall be installed at a height approximately midway between the top edge of the guardrail system and the scaffoldplatform.
When screens or mesh are used, they shall extend from the top edge of the guardrail system to the scaffoldplatform and along the entire opening between supports.
Each top rail or equivalent member of a guardrail system shall be capable of withstanding, without failure, a force applied in any downward or horizontal direction at any point along its top edge of at least:
Midrails, screens, mesh intermediate vertical members, solidpanels, and equivalent structural members of a guardrail system shall be capable of withstanding, without failure, a force applied in any downward or horizontal direction at any point along the midrail or other member of at least:
A toeboard shall be erected along the edge of the platform and shall be solid or with openings of not more than 1 inch (25 mm) along its longest dimension.
Toeboards shall be capable of withstanding, without failure, a force of at least 50 pounds (22.7 kg) applied in any downward or horizontal direction at any point along the toeboard.
The top edge of the toeboard shall be at least 3 1/2 inches (89 mm) high from the level of the walking/working surface and there shall be not more than a 1/4 inch (6 mm) clearance above the walking/working surface.
Asupported scaffold with a height-to-base ratio (including outriggers supports, if used) of more than four to one (4:1) shall be restrained from tipping by guying, tying, bracing or equivalent means as follows:
Guys, ties or braces shall be installed at locations where horizontal members support both inner and outer legs.
Guys, ties, or braces shall be installed according to the manufacturer's recommendations, or as designed in accordance with Section 3314.3, or at a minimum, the first guy, tie or brace shall be installed at a horizontal member and not more than a distance 4 times the least plan dimension from the base support and be repeated vertically at locations of horizontal members every 20 feet (6096 mm) or less thereafter for scaffolds 3 feet (914 mm) wide or less and every 26 feet (7925 mm) or less thereafter for scaffolds greater than 3 feet (914 mm) wide. The top guy, tie, or brace shall be placed no further than 4 times the least plan dimension from the top. Such guys, ties, or braces shall be installed at each end of the scaffold and at horizontal intervals not to exceed 30 feet (9144 mm) measured from one end (not both) towards each other.
Guys, ties, braces, or outriggers shall be used to prevent tipping of supported scaffolds in all circumstances where an eccentric load, such as a cantilevered work platform, is applied or is transmitted to the scaffold.
Supported scaffold poles, legs, posts, frames, and uprights shall be plumb and braced to prevent swaying and displacement. The tolerance shall not exceed L/100, where L is the distance measured from the ground or grade elevation to the first X-brace or bottom of the first bearer or frame horizontal member.
Suspended scaffolds shall be erected and operated in such a manner that suspension elements are vertical and in a plane parallel to the wall at all times. The installation or change of position of any suspended scaffold shall be performed under the supervision of a licensed master or special rigger, or a licensed sign hanger, or his designated foreman who shall ensure the safety of such operation.
All suspended scaffold support devices, such as outrigger beams, C-hooks, parapet clamps, and similar devices shall rest on surfaces capable of supporting at least 4 times the load imposed on them by the scaffold operating at the rated load of the hoist. The support shall be inspected by a competent person prior to installation.
Outrigger beams shall be placed perpendicular to the face of the building or structure.
Exception: Where a licensed rigger or engineer can demonstrate to the commissioner's satisfaction that it is not possible to place an outrigger beam perpendicular to the face of the building or structure, the outrigger beam may be placed at a different angle, provided opposing angle tiebacks are used.
The inboard ends of the suspended scaffoldoutrigger beam shall be stabilized by bolts or other direct connections to the floor or roof deck, or they shall have their inboard ends stabilized by counterweights.
Exception: Multi-point adjustable suspended scaffolds shall not be stabilized by counterweights.
Outrigger beams shall be installed with all bearing supports perpendicular to the beam centerline and shall set and maintain the web in a vertical position. The shackle or clevis with which the rope is attached to the outrigger beam shall be placed directly over the centerline of the stirrup.
Tiebacks shall be installed perpendicular to the face of the building, or opposing angle tiebacks shall be installed. Single tiebacks installed at an angle are prohibited.
Suspended scaffold support devices, such as C-hooks, cornice hooks, roof hooks, roof irons, parapet clamps or other similar devices shall meet the following requirements:
Support devices shall be made of steel, wrought iron or materials of equivalent strength.
Such devices shall be supported by bearing blocks.
Support devices shall be secured against movement by tiebacks installed at right angles to the face of the building or structure or by opposing angle tiebacks installed and secured to a structurally sound point of anchorage as prescribed in Section 3314.6.
Tiebacks shall be equivalent in strength to the hoisting rope.
When winding drum hoists are used on a suspended scaffold, they shall contain not fewer than four wraps of the suspension rope at the lowest point of scaffoldtravel. When other types of hoists are used, the suspension ropes shall be long enough to allow the scaffold to be lowered to the level below without the rope end passing through the hoist, or the rope end shall be configured or provided with means to prevent the end from passing through the hoist.
Ropes shall be replaced or removed if any of the following conditions exist, and as otherwise prescribed by rule of the department:
Any physical damage that impairs the function and strength of the rope.
Presence of kinks that might impair the tracking or wrapping of the rope around the drum(s) or sheave(s).
Presence of abrasion, corrosion, scrubbing, flasttening or peening causing the loss of more than one-third of the original diameter of the outside wires.
Heat damage caused by a torch or any damage caused by contact with electrical wires.
Evidence that the secondary brake has been activated during an overspeed condition and has engaged the suspension rope.
When acids or other corrosive substances are used on a scaffold, the ropes shall be shielded, treated to protect against corrosive substances, or made of a material that will not be damaged by the corrosive substance being used.
An insulated thimble shall be used to attach each suspension wire rope to its hanging support. Excessive suspension wire rope and any additional independent lines from grounding shall be insulated.
The suspension wire rope shall be covered with insulating material extending at least 4 feet (1219 mm) above the hoist. If there is a tail line below the hoist, it shall be insulated to prevent contact with the platform. The portion of the tail line that hangs free below the scaffold shall be guided or retained or both so that it does not become grounded.
In addition to a work lead attachment required by the welding process, a grounding conductor shall be connected from the scaffold to the structure. The size of the connector shall be at least the size of the welding process work lead, and this conductor shall not be in series with the welding process or the work piece.
There shall be a minimum of three wire rope clips installed a minimum of six rope diameters apart. The clips shall be retightened to the manufacturer's specifications after initial loading. U-bolt clips shall not be used at the point of suspension. When U-bolt clips are used, the U-bolt shall be placed over the dead end of the rope and the saddle shall be placed over the live end of the rope.
All wood pole scaffolds 40 feet (12 192 mm) high or less shall be constructed in accordance with the minimum nominal sizes and maximum spacings shown in Tables 3314.12.1 (1) through 3314.12.1 (6). Wood pole scaffolds more than 40 feet (12 192 mm) high shall be designed in accordance with Section 3314.3.
Poles or uprights(min) Pole foundation (min) Max. pole spacing (longitudinal) Max. width of scaffold Bearers or putlogs (min) Max. spacing of bearers or putlogs Ledgers (minimum) Vertical spacing of ledgers (max) Nonsupporting stringers Tie-ins Bracing Planking
Not more than 6' span
Up to 10'span
Toeboards Guardrails
3'' x 4'' or 2'' x 6''
4'' x 4''
4'' x 6'' 2'' x 9'' 10' - 0'' 5' - 0'' 3'' x 4'' or 2'' x 6'' (on 8' x,10'' 2'' x 9'' (on edge) 7'' x 0'' 1'' x 6'' or 11/4'' x 4'' 1'' x 6'' 1'' x 6''
11/4'' x 9'' 2'' x 9'' 2'' x 9'' 2''x 4''
Top 60' 4''x 4''
Lower Sect. 4''x 6''
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa.
Poles or uprights(min) Pole foundation (min) Max. pole spacing (longitudinal) Max. width of scaffold Bearers or putlogs (min) Max. spacing of bearers or putlogs Ledgers (minimum) Vertical spacing of ledgers (max) Nonsupporting stringers Tie-ins Bracing Planking Toeboards Guardrails
3'' x 4'' or 2'' x 6''
4'' x 4''
5'-0''
4'' x 6'' 2'' x 9'' 6' - 0''
6' - 0'' 2'' x 9'' (on edge) 7' x 0'' 2'' x 4'' 1'' x 6'' 1'' x 6'' 2'' x 9'' 2'' x 9'' 2''x 4''
Top 60' 4'' x 6''
Lower Sect. 6'' x 6''
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa.
TABLE 3314.12.1(4)
MINIMUM SIZE AND MAXIMUM SPACING OF MEMBERS OF INDEPENDENT WOOD POLE LIGHT DUTY SCAFFOLDS
Poles or uprights(min) Pole foundation (min) Max. pole spacing (longitudinal)
With 11/4'' x 9''
With 2'' x 9'' ledgers
Max. pole spacing (transverse) Ledgers (minimum) Vertical spacing of ledgers (max) Bearers (minimum) Nonsupporting stringers Bracing Planking
Not more than 6' span
Up to 8' span
Toeboards Guardrails
2'' x 4''
3'' x 4'' or 2'' x 6''
4'' x 4'' 2'' x 9'' 6' - 0''
10' - 0'' 10' - 0''a 11/4'' x 9'' (on edge) or 2'' x 7'' x 0'' 11/4'' x 9'' (on edge) 1'' x 4'' 1'' x 4''
11/4'' x 9'' 2'' x 9'' 1'' x 6'' 2''x 4''
Top 60' 4'' x 4''
Lower Sect. 4'' x 6''
For SI: 1 inch = 25.4 mm, 1 foot 304.8 mm, 1 pound per square foot = 47.88 Pa.
A total base dimension in both directions to be at least 25 percent of height.
TABLE 3314.12.1(5)
MINIMUM SIZE AND MAXIMUM SPACING OF MEMBERS OF INDEPENDENT WOOD POLE MEDIUM DUTY SCAFFOLDS
Poles or uprights(min) Pole foundation (min) Max. pole spacing (longitudinal) Max. pole spacing (transverse) Ledgers (minimum) Vertical spacing of ledgers (max) Bearers (minimum) Nonsupporting stringers Bracing Planking
Not more than 6' span
Up to 8' span
Toeboards Guardrails
3'' x 4'' or 2'' x 6''
4'' x 4''
5'-0''
4'' x 6'' 2'' x 9'' 8'' x -0'' 10' x 0''a 2'' x 9''(on edge) 6' - 0'' 2'' x 9'' (on edge) 11/4'' x 4'' or 1'' x 6'' 1'' x 6''
11/4'' x 9'' 2'' x 9'' 2'' x 9'' 2'' x 4''
Top 60' 4'' x 6''
Lower Sect. 6'' x 6''
For SI: 1 inch = 25.4 mm, 1 foot 304.8 mm, 1 pound per square foot = 47.88 Pa.
A total base dimension in both directions to be at least 25 percent of height.
TABLE 3314.12.1(6)
MINIMUM SIZE AND MAXIMUM SPACING OF MEMBERS OF INDEPENDENT WOOD POLE HEAVY DUTY SCAFFOLDS
Poles or uprights(min) Pole foundation (min) Max. pole spacing (longitudinal) Max. pole spacing (transverse) Ledgers (minimum) Vertical spacing of ledgers (max) Bearers (minimum) Nonsupporting stringers Bracing Planking Toeboards Guardrails
4'' x 4''
4'' x 4''
4'' x 6'' 2'' x 9'' 6' - 0'' 10' x 0''a 2'' x 9'' (on edge) 5' x, 2" x 9'' (on edge) 11/4'' x 9'' 1'' x 6'' 2'' x 9'' 2'' x 9'' 2'' x 4''
Top 60' 4'' x 6''
Lower Sect. 6'' x 6''
For SI: 1 inch = 25.4 mm, 1 foot 304.8 mm, 1 pound per square foot = 47.88 Pa.
A total base dimension in both directions to be at least 25 percent of height
When a new working level is desired, the existing planks shall be left undisturbed until the new working level is framed. As the platform level is abandoned with the progress of the work, all members other than the planking, railing and toeboards shall be left intact. When removing a scaffold, the sequence of removing the members shall be the reverse of that used in erection.
All lumber and timber shall be fastened at the various joints with sufficient nails or bolts of a suitable size to produce a secure joint capable of withstanding the design load. Table 3314.12.3 provides minimum requirements for size and number of nails. All nails shall be driven full length.
Any other suitable material, or dimensions other than those indicated, may be used for wood pole scaffoldconstruction provided it is at least equivalent in strength and suitability to the comparable wood scaffold it is designed to replace, and approval of the commissioner has been obtained.
Wooden scaffold poles shall be plumb and the foot ends shall be secured against lateral movement. Where wood poles are spliced, the squared end of the upper section shall bear uniformly on the squared end of the lower section and the two ends shall be rigidly fastened together with two or more wood splice plates, each at least 4 feet (1219 mm) in length. The plates shall be placed at right angles to each other, shall overlap the abutting ends of the pole equally, and shall have a combined sectional area not less than 50 percent of the cross sectional area of the pole. Splicing of adjacent poles shall be staggered. Splices shall be close to ledgers, but so located as not to interfere with the fastenings.
Wood pole scaffolds shall be braced and stayed to prevent movement away from the building. Diagonal or equivalent bracing shall be provided to prevent the poles from moving in a direction parallel to the building face and shall be so installed that every spliced section of every pole is braced to adjacent poles.
Where planks are butted end to end, parallel putlogs or bearers shall be provided not more than 8 inches (203 mm) apart so that the butted ends rest on separate putlogs or bearers. Ends shall be nailed or cleated.
Where platform planks are used with overlapping ends, the ends of both the upper and lower planks shall overlap the putlog or bearer by at least 6 inches (152 mm).
Planks shall be laid close together and shall be of sufficient length to extend over three bearers.
Ledgers shall not be spliced between poles but shall overlap the poles at each end by at least 4 inches (102 mm). Where ledgers lap each other, bearing-blocks attached to the pole shall be provided to support the ledger.
The ends of all wooden braces shall overlap the nailed fastenings by an amount sufficient to prevent the ends of the braces from splitting.
All putlogs shall be set with the greater dimension vertical and shall be long enough to project beyond the outer edge of the poles by at least 12 inches (305 mm). Putlogs shall be supported on the ledger and located against the side of the poles and fastened to either the pole or the ledger. The other end of the putlog shall rest in the wall of the building, with at least a 4 inch (102 mm) bearing, and shall not be notched or cut down, except for light duty scaffolds, which may be notched or cut down to fit into a space made by the removal of a brick. In such cases, the notch shall be made on the top of the putlog just deep enough to permit it to be inserted in the hole in the wall.
Bearers shall be set with their greater dimensions vertical, and shall be long enough to project over the ledgers beyond the outer row of poles by at least 12 inches (305 mm) and beyond the inner row of poles by at least 2 inches (51 mm). Bearers shall be supported on the ledgers, located against the sides of the poles and fastened to the ledgers.
Frames and panels shall be joined together vertically by coupling or stacking pins or equivalent means. Where uplift can occur, the frames or panels shall be locked together vertically by pins or equivalent means.
Brackets used to support cantilevered loads shall be seated with side-brackets parallel to the frame and end-brackets at 90 degrees to the frames, shall not be bent or twisted from these positions and shall be used only to support light duty loads as defined in Section 3314.3.3, unless the design provisions of Section 3314.3 have been met.
The fulcrum point of the beam shall rest on a secure bearing at least 6 inches (152 mm) in each horizontal dimension. The beam shall be secured against movement and shall be securely braced against tipping at both the fulcrum point and the inboard end.
The inboard ends of outrigger beams shall be securely fixed to resist all vertical, horizontal, and torsional forces. Pull-out tests for adhesive and expansions anchors, if used, shall be approved by the commissioner.
Two-point suspension platforms shall be at least 20 inches (508 mm) but not more than 36 inches (914 mm) in width unless designed by an engineer. Each end of the platform shall be supported by a stirrup or hanger that meets the requirements of Section 3315.15.2, and the platform shall be securely fastened thereto. Not more than two hangers or stirrups shall be used to support one scaffold.
Hangers or stirrups shall be of steel or wrought iron. Each such hanger shall be formed to properly fit the platform and the hoist mechanism. The hanger or stirrup shall be placed at least 6 inches (152 mm) but not more than 18 inches (457 mm) from the end of the platform unless the manufacturer specifies otherwise.
Not more than two workers shall be permitted to work on one scaffold at one time except where the scaffold is designed to hold more. Written permission from the commissioner shall be required for more than two workers on the scaffold.
The number of people allowed on a corner or angle scaffold shall not be more than the number of motors required to keep the scaffold stable, unless otherwise designed by an engineer.
Certification from the engineer that he/she has reviewed the manufacturer's design calculations and testing or prepared sufficient calculations of his/her own and found them to conform to this code; and
The equipment setting for corner and angle scaffolds shall be inspected by the department prior to its use. Additional inspection by the department shall be required each time the equipment is moved to a different position.
During raising or lowering, the levels of the various sections of the scaffolds shall be kept uniform and the differential height between sections shall be minimized.
Where a ladder is used to approach a platform, the ladder shall be secured to the scaffold;
Handholds shall be provided for safe passage from the ladder to the platform;
Unless temporarily braced to an adjacent structure, the ratio of the platform height to the least base dimension shall be such as to assure stability, but in no case shall such height be more than four times the least base dimension;
Provisions shall be made to prevent the scaffold from falling during movement from one location to another;
While the scaffold is in use, it shall rest upon a stable footing and shall stand plumb. The casters or wheels shall be locked in position; and
While the scaffold is being moved, no person shall be permitted to ride on it, and all tools, equipment and material shall be removed.
Mast-climbing work platforms, including all supports, fastenings, connections, and details shall not be erected or installed unless and until a written permit has been issued by the commissioner on the basis of construction documents, drawings, and specifications. Copies of the written permit application shall be kept at the site and made available to the commissioner upon request. Such permit shall be issued in accordance with rules promulgated by the commissioner.
Runways and ramps for the use of motor vehicles may consist of an earthfill or may be structurally supported. Such runways and ramps shall have a clear width of not less than 12 feet (3658 mm) with timber curbs at least 8 inches by 8 inches (203 mm by 203 mm) placed parallel to, and secured to, the sides of the runway or ramp. The flooring of structurally supported ramps shall consist of no smaller than 3 inch (76 mm) planking full size, undressed, or equivalent material, with spans designed for the loads to be imposed.
Runways and ramps for the use of workers shall be at least 1 foot 6 inches (457 mm) in clear width. Where used for wheelbarrows, handcarts, or hand-trucks, runways and ramps shall be at least 3 feet (914 mm) in clear width. Flooring shall consist of at least 2 inch (51 mm) planking spanning as permitted by Table 3314.5.2, laid close, butt-joined, and securely fastened.
Ramps shall have a slope not steeper than one in four. If the slope is steeper than one in eight, the ramp shall be provided with cleats spaced not more than 14 inches (356 mm) apart and securely fastened to the planking to afford a foothold. Spaces in the cleats may be provided for the passage of the wheels of vehicles. The total rise of a continuous rampused by workers carrying material or using wheelbarrows, hand-carts, or hand-trucks shall not exceed 12 feet (3658 mm) unless broken by horizontal landings at least 4 feet (1219 mm) in length.
All runways and ramps located more than 5 feet (1524 mm) above the ground or floor shall be provided with a standard guardrail and standard toeboard that meets the requirements of Section 3307.8 on open sides.
Where it is possible for the public to pass under, or next to, runways or ramps, the space between the top rail and the standard toeboard shall be enclosed with a wire screen composed of not less than no. 18 steel wire gage with a maximum 1/2 inch (12.7 mm) mesh.
Platformsused as working areas, or for the unloading of wheelbarrows, hand-trucks, or carts shall have a floor consisting of at least 2 inch (51 mm) planking spanning as permitted by Table 3314.5.2. Platforms for the use of motor trucks shall have a floor of at least 3 inch (76 mm) planking, full size, undressed or equivalent materials with spans designed for the loads to be imposed. Planking shall be laid close and shall be butt-joined and securely fastened.
Every platform more than 5 feet (1524 mm) above the ground or above a floor shall be provided with a standard guardrail and standard toeboard that meets the requirements of Section 3307.8, except that the side of the platformused for the loading or unloading of vehicles may be protected by a timber curb at least 8 inches by 8 inches (203 mm by 203 mm) for motor trucks or 4 inches by 4 inches (102 mm by 102 mm) for wheelbarrows and hand-trucks in lieu of the standard guardrail and standard toeboard.
Where it is possible for the public to pass under, or next to, platforms, the space between the top rail and the standard toeboard shall be enclosed with a wire screen composed of not less than no. 18 steel wire gage with a maximum 1/2 inch (12.7 mm) mesh.
They shall be able to sustain, without failure, at least four times the maximum live load for which they are intended.
The minimum width, inside of curbs, for any ramp, runway, or platform shall be 2 feet (610 mm) wider than the outside width of any power buggy operated thereon without passing, and 3 feet (914 mm) wider than twice such buggy width in the places where passing occurs.
All runways shall be essentially level transversely.
Curbs shall be furnished along all buggy traffic paths that are nearer than 10 feet (3048 mm) horizontally to any unenclosed area, shaft, or other open space into which or through which a fall of more than 12 inches (305 mm) from such surface is possible, except as set forth in numbered item seven.
Where curbs are not required because the buggy is operated on a surface not over 12 inches (305 mm) above another surface, the lower surface shall be strong enough to sustain the loaded vehicle in the event of a fall thereon.
Curbs may be omitted at actual dumping points more than 12 inches (305 mm) above other surfaces if the edge over which dumping occurs is provided with bumpers or other means that will effectively stop the buggy from running over the edge while dumping.
Curbs must be at least 7 inches (178 mm) high, securely fastened, and capable of resisting side impact, and shall be equivalent to at least 2 inch by 8 inch (51 mm by 203 mm) plank set on edge against uprights securely fastened and braced at not more than 4 foot (1219 mm) intervals.
Hoisting equipment, its supports and runback structures shall be installed, operated, and maintained to eliminate hazard to the public or to property. It shall be unlawful to operate any such equipment that is not provided with a positive means for preventing the unauthorized operation of such machine. The means whereby such machines may be made inoperative shall be accepted by the department.
Following the receipt of a permit to install a hoist, the permit holder shall post a sign that meets the requirements of Section 3301.9.6. Such sign shall be clearly visible from the street.
Only operators designated by the person causing such hoisting equipment to be used shall operate such hoisting machinery. Operators and signalmen/signalwomen shall be qualified for the operation they perform. The operator shall be responsible for making the machine inoperative before he or she leaves the machine.
Hoisting equipment, its supports and runback structures shall be operated in compliance with the manufacturing specifications, the requirements of this code, and rules promulgated by the commissioner. If there is a discrepancy, the stricter requirement shall be met.
Personnel and building materials connected with or related to the building project shall not be moved by the hoist while it is being installed, jumped, dismantled or altered.
Hoisting equipment, its supports and runback structures shall be maintained in compliance with the manufacturing specifications and rules promulgated by the commissioner. If there is a discrepancy, the stricter requirement shall be met.
The equipment user or his or her designated representative shall obtain a written permit issued by the commissioner on the basis of construction documents, drawings and specifications prior to erecting or installing all power-operated, material hoists, including any runback structure or supports.
Exception: Power-operated, non-guided material hoists with a maximum capacity of one ton or less and installed on new construction, or on alterations where the operation of the hoist is confined within the property and the site is protected in accordance with Section 3307.
Material hoists, bucket hoists and their components shall be constructed in compliance with the manufacturing specifications, the requirements of this code, and rules promulgated by the commissioner. If there is a discrepancy, the stricter requirement shall be met.
Upon completion of the installation of the hoisting equipment and/or its runback structure, an inspection report verifying that the hoist has been installed in accordance with the design drawings, construction documents and specifications shall be prepared by the designer, installer or an approved inspection agency designated by both the designer and installer.
Notwithstanding any other provision of law, material hoists with a manufacturer's capacity over one ton shall be operated only by persons holding a Class A or Class B Hoisting Machine Operators License except during installation, jumping, dismantling or alteration operations.
The equipment user or his or her designated representative shall obtain a written permit issued by the commissioner on the basis of construction documents, drawings and specifications prior to erecting or installing all power-operated, material hoists, including any runback structure or supports.
Personnel hoists and their components shall be constructed in compliance with the manufacturer's specifications, this code, and rules promulgated by the commissioner. If there is a discrepancy, the stricter requirement shall be met.
Upon completion of the installation of the hoisting equipment and/or its runback structure, an inspection report verifying that the hoist has been installed in accordance with the design drawings, construction documents and specifications shall be prepared by the designer, installer or third party designated by both the designer and installer and acceptable to the commissioner.
When the hoist is equipped with manual controls, the hoist shall be operated by a competent qualified operator. Only the operator authorized by the equipment user shall operate the hoist.
No person shall at any time make any required safety device or electrical protective device inoperative except when necessary during tests, inspections and maintenance.
Immediately upon completion of the tests, inspections and maintenance, such devices shall be restored to their normal operating condition in conformance with the applicable requirements of this section.
The requirements of this section shall not apply to excavating or earth-moving equipment, except cranesused with clamshells.
The requirements of this section shall not apply to cranes or derricks performing an emergency use pursuant to the lawful order of the head of any department.
The requirements of this section shall not apply to mobile cranes, including jibs and any other extensions to the boom not exceeding 50 feet (15 240 mm) in length and with a manufacturer's rated capacity of 3 tons (2722 kg) or less.
The requirements of this section shall not apply to mobile cranes, including jibs and any other extensions, exceeding 50 feet (15 240 mm) but not exceeding 135 feet (41 148 mm) in length, and with a manufacturer's rated capacity of 3 tons (2722 kg) or less, except that a certificate of operation, as provided for in Section 3319.5, shall be required. The requirement for a certificate of operation shall not apply to such a craneused exclusively as a man basket. The commissioner may, by rule, exempt other mobile cranes of limited size from any or all requirements of this section.
The requirements of this section shall not apply to hoisting machines permanently mounted on the bed of material delivery trucks that are used exclusively for loading and unloading such trucks, provided that the length of boom does not exceed the length of the truck bed by more than 5 feet (1524 mm) and that any material transported thereon shall not be raised more than 2 feet (610 mm) in the unloading process. Operators of such equipment shall be exempt from licensing requirements described in Chapter 4 of Title 28 of the Administrative Code.
The requirements of this section shall not apply to cranes or derricksused in industrial or commercial plants or yards not used for the construction of the facility. Floating cranes, floating derricks, and cranes and derricksused on floating equipment shall also be exempt from the requirements of this section. Operators of such equipment shall be exempt from the licensing requirements described in Chapter 4 of Title 28 of the Administrative Code.
The requirements of this section shall not apply to augurs, churn-drills and other drilling equipment not used for hoisting any objects. Operators of such equipment shall be exempt from the licensing requirements described in Chapter 4 of Title 28 of the Administrative Code.
The requirements of this section shall not apply to derricks having a maximum rated capacity not exceeding 1 ton (907 kg).
The requirements of this section shall not apply to mechanic's truck with a hoisting device when used in activities related to the maintenance and repair of construction-related equipment.
The requirements of this section shall not apply to articulating boom cranes that do not have an integral hoisting mechanism, and that are used exclusively for loading and unloading of trucks or trailers, provided that the length of boom does not exceed 135 feet (41 148 mm) and that any material transported thereon shall not be raised more than 100 feet (30 480 mm) in the unloading process. Operators of such equipment shall be exempt from licensing requirements described in Chapter 4 of Title 28 of the Administrative Code.
A new certificate of approval shall be required when a crane or derrick is modified or altered to increase the boom length, jibs or any extensions to the boom beyond the maximum approval length or when the load ratings are increased.
If the owner of the covered crane or derrick applies for renewal of a certificate of operation within not more than 60 nor less than 30 days prior to the date of its expiration, such owner may continue to use the covered crane or derrick until the department grants or denies a new certificate;
An application for a new certificate of operation shall be submitted when attachments that affect the stability or structure of the crane or derrick are added. Calculations and load rating charts as required by rules promulgated by the commissioner shall be submitted with the renewal request.
Upon approval of the application, a copy of such approval shall be given to the applicant. It shall be unlawful to operate the equipment that is the subject of the approval until it has been inspected and found to be satisfactory by the department as set forth in rules promulgated by the commissioner. Upon inspection and a finding of satisfactory compliance, the approval shall be deemed a certificate of on-site inspection, which shall expire one year from the date of issuance. Acertificate of on-site inspection may be renewed in accordance with rules promulgated by the commissioner;
The certificate of on-site inspection is y valid only if the conditions and statements contained in the approved application are complied with and the crane or derrick is operated in conformance with the provisions of this section and the rules applicable thereto.
An erection, jumping, climbing and dismantling plan for tower or climber cranes, other than truck and crawler mounted tower cranes, shall be submitted to the department by a licensed engineer. The plan must be prepared by a licensed engineer in conjunction with a licensed rigger and must be in compliance with the manufacturer's recommendation for erection, jumping, climbing, or dismantling of the specific crane where such manufacturer's recommendations exist. The plan must be filed with the certificate of on-site inspection application as required by section 3319.3. No erection, jumping, climbing, or dismantling of a tower or climber crane shall take place without the prior issuance of a certificate of on-site inspection by the cranes and derricks unit. The plan shall include the following:
Identification of the equipment proposed to be used; including all machines proposed to be used in the erection or dismantling;
A detailed identification of the assemblies and components required for the erection and dismantling of the equipment;
Location of the equipment, sidewalk sheds (or Department of Transportation street closing permits, if applicable), surrounding buildings, protection for their roofs and the pick-up points, loads, and radius of swing of all loads. In addition, the safe load from the approvedload radius chart shall be submitted for lift radius;
A weight list of all assemblies and components proposed to be lifted. Components are to be clearly marked with their weight painted on the assembly or stamped on metal tags attached to the assembly. The manufacturer of the climber or tower crane shall certify the weight of assemblies and components. Alternately, in lieu of painted weight markings or metal tags, or when the manufacturer's certification is not available, the licensed engineer applicant shall certify an erection, jumping, climbing or dismantling weight list indicating how such weights were determined;
The center of gravity of all asymmetrical components shall be located and shown;
A sequence of operation detailing the erection, jumping, climbing, and dismantling, along with the rigging materials to be used in such operations;
The certification of the calibration as required in item 6 of section 3319.8.8;
The names and contact information of the licensed master, climber or tower crane rigger, rigger foreman, and the crane safety coordinator or designee, along with the name and contact information of the company performing the erection, dismantling, climbing and/or jumping work.
*Section BC 3319.8.1 was added by: Local Law 46 of 2008 — Update #13. This law has an effective date of December 22, 2008.
The general contractor must hold a safety coordination meeting prior to the initial erection, as well as the dismantling or initial jump down, of a climber or tower crane. No work related to the erection, climbing, jumping or dismantling of the tower or climber crane may be performed without the safety coordination meeting having taken place. The following parties must be present at the safety coordination meeting:
General contractor or designee;
Professional engineer of record for the crane or designee;
Licensed master, tower or climber crane rigger and rigger foreman;
The general contractor must coordinate a pre-jump safety meeting no more than 24 hours prior to each instance of a tower or climber cranejump or climb. No work related to the jumping or climbing of the tower or climber crane may be performed without the pre-jump safety meeting having taken place. The following parties must be present at the pre-jump safety meeting:
General contractor or designee;
Licensed master, tower or climber crane rigger and rigger foreman;
The general contractor must notify the department at least 48 hours in advance of any safety coordination meeting or pre-jump safety meeting. No work related to the erecting, jumping, climbing, or dismantling of the tower or climber crane is to be performed without prior notice of the meeting having been given to the department.
*Section BC 3319.8.4.1 was added by: Local Law 46 of 2008 — Update #13. This law has an effective
date of December 22, 2008.
A time schedule including date and time of day that the erection, jumping, climbing, or dismantling is proposed to take place shall be provided as soon as it is known by the general contractor.
*Section BC 3319.8.4.2 was added by: Local Law 46 of 2008 — Update #13. This law has an effective
date of December 22, 2008.
The general contractor, or his or her designee, and/or the company erecting, jumping, climbing, or dismantling the tower or climber crane shall keep a log on site and available to the department at all times that shall include:
the dates and times of all safety coordination meetings and pre-jump safety meetings held;
the names, titles, and company affiliations of all those present at the meetings;
a summary of what was discussed during each meeting, including specific tasks and the name of the person to whom they were assigned;
a list of the decisions made at the meeting; and
certification of worker training pursuant to Section 3319.10.
*Section BC 3319.8.6 was added by: Local Law 46 of 2008 — Update #13. This law has an effective
date of December 22, 2008.
Prior to jumping or climbing a tower or climber crane, the engineer of record for the crane must provide the department with a certified, signed, and sealed report stating that:
he or she (or his or her designee) has inspected the crane installation prior to the pre-jump safety meeting, and providing the date of inspection;
he or she has found no hazardous conditions during the crane inspection or any other condition within his or her purview that adversely affects the safety of erection, dismantling, climbing, or jumping operations;
the crane is installed according to the plans approved by the department as well as in accordance with the manufacturer's specifications to the extent applicable; and
the appropriate technical testing records for the crane, including torque, plumb, and magnetic particle or other appropriate reports comply with safety requirements and with the manufacturer's specifications.
*Section BC 3319.8.7 was added by: Local Law 46 of 2008 — Update #13. This law has an effective date of December 22, 2008.
The erection, jumping, climbing, and dismantling operations for tower and climber cranes shall be subject to the following requirements:
The licensed master, tower or climber crane rigger, the rigger foreman, and the crane safety coordinator or designee, shall be present at the job site during erection, jumping, climbing, and dismantling of the tower or climber crane;
The approved erection, jumping, climbing, or dismantling procedure and sequence, with weights of assemblies and components clearly marked, shall be given by the crane safety coordinator to the licensed operator of the crane or derrick and to the rigger prior to commencement of the work;
No tower or climber crane shall be placed, erected or disassembled in any roadway, sidewalk, or street unless a permit is first obtained from the New York CityDepartment of Transportation;
All accepted or approved installed safety devices on a crane involved in the erection, jumping, climbing, or dismantling procedure shall have been calibrated within the time period provided by department rules or manufacturer's specifications; and
The safety devices of the tower or climber crane shall be inspected by the licensed crane operator as part of the inspection procedure.
*Section BC 3319.8.8 was added by: Local Law 46 of 2008 — Update #13. This law has an effective date of December 22, 2008.
Nylon slings shall only be used in conjunction with climber or tower crane erection, jumping, climbing, and dismantling if the manufacturer's manual specifically states or recommends the use of nylon slings. Nylon slings shall not be used unless softening mechanisms have been applied to all sharp edges.
*Section BC 3319.9.1 was added by: Local Law 45 of 2008 —Update #12. This law has an effective date of Oct. 22, 2008.
All workers engaged in the erection, jumping, climbing, rigging, or dismantling of a climber or tower crane, including the licensed rigger and the rigger foreman, shall have satisfactorily completed a department-approved training course of not less than thirty hours. Such course shall, at a minimum, include instruction on fall protection, crane assembly and disassembly, pre-lift planning, weights and materials, the use of slings, lifting/lowering loads, signaling and other proper means of communication with the crane operator, crane and hoist inspections, rigging requirements, and generally how to avoid accidents with cranes and hoists. The commissioner may by rule identify additional types of cranes for which such training is necessary. Any person who, within the three years prior to the effective date of this section, has successfully completed at least a thirty-hour training course need not take a second thirty-hour course, provided such person can provide to the department a dated certificate as set forth in this section evidencing completion of such a training course. Such person shall, however, take a department-approved eight-hour re-certification course within three years of the initial course and every three years thereafter. Successful completion of the training or re-certification course shall be evidenced by a dated certificate issued by the provider of the training or re-certification course. The certificate shall include such information as specified by the department by rule. The certificate, or a valid wallet card version thereof, shall be readily available to the commissioner upon request.
*Section BC 3319.10.1 was added by: Local Law 44 of 2008—Update #11. This law has an effective date of March 23, 2009.
Such training or refresher course shall be conducted (i) pursuant to a registered New York state department of labor training program, or (ii) by a provider approved by the department.
Prior to erecting, jumping, climbing or dismantling the climber or tower crane, or other crane type the commissioner specifies by rule, the master, climber or tower crane rigger shall certify in the meeting log, described in Section 3319.8.6, that the rigger foreman and all other members of the "jumping crew" and back-up personnel have satisfactorily completed all training requirements.
*Section BC 3319.10.2 was added by: Local Law 44 of 2008—Update #11. This law has an effective date of March 23, 2009.
Material handling equipment shall be installed, operated, and maintained to eliminate hazard to the public or to property. It shall be unlawful to operate any such equipment that is not provided with a positive means for preventing the unauthorized operation of such machine. The means whereby such machines may be made inoperative shall be acceptable to the commissioner.
Only operators designated by the person causing such machinery to be used shall operate material handling machinery. Operators and signalmen/singalwomen shall be experienced at the operation they perform. The operator shall be responsible for making the machine inoperative before he or she leaves the machine.