Heads up: There are no amended sections in this chapter.
The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated construction separation of adjacent spaces to safeguard against the spread of fire and smoke within a building and the spread of fire to or from buildings.
The following words and terms shall, for the purposes of this chapter, and as used elsewhere in this code, have the meanings shown herein.

ANNULAR SPACE. The opening around the penetrating item.

CEILING RADIATION DAMPER. A listed device installed in a ceiling membrane of a fire-resistance-rated floor/ceiling or roof/ceiling assembly to limit automatically the radiative heat transfer through an air inlet/outlet opening.

COMBINATION FIRE/SMOKE DAMPER. A listed device installed in ducts and air transfer openings designed to close automatically upon the detection of heat and to also resist the passage of air and smoke. The device is installed to operate automatically, controlled by a smoke detection system, and where required, is capable of being positioned from a remote command station.

CONCEALED SPACES. Enclosed spaces within partitions, walls, floors, roofs, stairs, furring, pipe chases and column enclosures and other similar spaces.


DRAFT STOP.A material, device or construction installed to restrict the movement of air within open spaces of concealed areas of building components such as crawl spaces, floor/ceiling assemblies, roof/ceiling assemblies and attics.

F RATING. The time period that the through-penetration fire stop system limits the spread of fire through the penetration when tested in accordance with ASTM E 814.

FIRE AREA. The aggregate floor area enclosed and bounded by firewalls, fire barriers, exterior walls or fire-resistance-rated horizontal assemblies of a building.

FIRE BARRIER. A fire-resistance-rated vertical or horizontal assembly of materials complying with Section 706 designed to restrict the spread of fire in which openings are protected.

FIRE DAMPER. A listed device, installed in ducts and air transfer openings of an air distribution system or smoke control system, designed to close automatically upon detection of heat, to interrupt migratory airflow, and to restrict the passage of flame. Fire dampers are classified for use in either static systems that will automatically shut down in the event of a fire, or in a dynamic system that continues to operate during a fire. A dynamic fire damper is tested and rated for closure under airflow.


FIRE DOOR ASSEMBLY. Any combination of a fire door, frame, hardware, and other accessories that together, as an opening protective, provide a specific degree of fire protection to the opening.

FIRE PARTITION. A vertical assembly of materials complying with Section 708, designed to restrict the spread of fire in which openings are protected.

FIRE PROTECTION RATING. The period of time that an opening protective assembly will maintain the ability to confine a fire as determined by tests prescribed in Section 715. Ratings are stated in hours or minutes.

FIRE RESISTANCE. That property of materials or their assemblies that prevents or retards the passage of excessive heat, hot gases or flames under conditions of use.

FIRE-RESISTANCE RATING. The period of time a building element, component or assembly maintains the ability to withstand fire exposure, continues to perform a given structural function, or both, as determined by the tests, or the methods based on tests, prescribed in Section 703.

FIRE-RESISTANT JOINT SYSTEM. An assemblage of specific materials or products that are designed, tested, and fire-resistance rated in accordance with either ASTM E 1966 or UL 2079 to resist for a prescribed period of time the passage of fire through joints made in or between fire-resistance-rated assemblies.

FIRE SEPARATION DISTANCE. The distance measured from the building face to the closest interior tax lot line, to the centerline of a street or other public space, or to an imaginary line between two buildings on the same tax lot. The distance shall be measured at right angles from the face of the wall.

FIRE WALL. A fire-resistance-rated smoke-tight wall having protected openings, which restricts the spread of fire and extends continuously from the foundation to or through the roof, with sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall.

FIRE WINDOW ASSEMBLY. A window, as an opening protective, constructed and glazed to give protection against the passage of fire, smoke, and hot gases.

FIREBLOCKING. A building material or an assembly of building materials that may or may not have a fire-resistance rating installed to resist the free passage of flame or hot gases to other areas of the building through concealed spaces in accordance with Section 717.


FLOOR FIRE DOOR ASSEMBLY. A combination of a fire door, a frame, hardware and other accessories installed, as an opening protective, in a horizontal plane, which together provide a specific degree of fire protection to a through opening in a fire-resistance-rated floor (see Section 712.4.6).

MEMBRANE PENETRATION. An opening made through one side (wall, floor or ceiling membrane) of an assembly.

MEMBRANE PENETRATION FIRESTOP. A material, device, or assemblage of specific materials or products that is designed, tested and fire-resistance rated to resist for a prescribed time period the passage of flame and heat through openings in a protective membrane in order to accommodate cables, cable trays, conduit, tubing, pipes or similar items.


SELF-CLOSING. As applied to a fire door or other opening, means equipped with an approved device that will ensure closing after having been opened.

SHAFT. An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, or floors and roof.

SHAFT ENCLOSURE. The walls or construction forming the boundaries of a shaft.

SMOKE BARRIER. A continuous membrane, either vertical or horizontal, such as a wall, floor, or ceiling assembly, that is designed and constructed in accordance with Section 709 to restrict the movement of smoke.

SMOKE COMPARTMENT. A space within a building enclosed by smoke barriers on all sides, including the top and bottom.

SMOKE DAMPER. A listed device installed in ducts and air transfer openings that is designed to resist the passage of air and smoke. The device is installed to operate automatically, controlled by a smoke detection system, and where required, is capable of being positioned from a remote command station.

SMOKE PARTITION. A continuous vertical assembly that is designed and constructed to restrict the movement of smoke and is not generally required to have a fire-resistance rating in accordance with Section 710.

T RATING. The time period that the penetration firestop system, including the penetrating item, limits the maximum temperature rise to 325°F (163°C) above its initial temperature through the penetration on the nonfire side when tested in accordance with ASTM E 814.

THROUGH PENETRATION. An opening that passes through an entire assembly.

THROUGH-PENETRATION FIRESTOP SYSTEM. An assemblage of specific materials or products that are designed, tested and fire-resistance rated to resist for a prescribed period of time the spread of fire through penetrations. The F and T rating criteria for penetration firestop systems shall be in accordance with ASTM E 814. See definitions of "F rating" and "T rating."
Materials prescribed herein for fire resistance shall conform to the requirements of this chapter.
The fire-resistance rating of building elements shall be determined in accordance with the test procedures set forth in ASTM E 119 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the assembly, sufficient data shall be made available to the commissioner to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire-resistance- rated building elements shall not reduce the required fire-resistance rating.

Exception: In determining the fire-resistance rating of exterior bearing walls, compliance with the ASTM E 119 criteria for unexposed surface temperature rise and ignition of cotton waste due to passage of flame or gases is required only for a period of time corresponding to the required fire-resistance rating of an exterior nonbearing wall with the same fire separation distance, and in a building of the same group. When the fire-resistance rating determined in accordance with this exception exceeds the fire-resistance rating determined in accordance with ASTM E 119, the fire exposure time period, water pressure, and application duration criteria for the hose stream test of ASTM E 119 shall be based upon the fire-resistance rating determined in accordance with this exception.
Interior walls and partitions of nonsymmetrical construction shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests conducted in compliance with ASTM E 119. When evidence is furnished to show that the wall was tested with the least fire-resistant side exposed to the furnace, subject to acceptance of the commissioner, the wall need not be subjected to tests from the opposite side (see Section 704.5 for exterior walls).
Combustible aggregates may be integrated with other materials to form a non-combustible material provided that the entire mixture, in the form in which it is to be used in construction, meets the requirement of this code for noncombustible construction.
Fire-resistance-rated assemblies tested under ASTM E 119 shall not be considered to be restrained unless evidence satisfactory to the commissioner is furnished by the registered design professional showing that the construction qualifies for a restrained classification in accordance with ASTM E 119. Restrained construction shall be identified on the plans.
The application of any of the alternative methods listed in this section shall be based on the fire exposure and acceptance criteria specified in ASTM E 119. The required fire resistance of a building element shall be permitted to be established by any of the following methods or procedures:
  1. Fire-resistance designs documented in approved sources.
  2. Prescriptive designs of fire-resistance-rated building elements as prescribed in Section 720.
  3. Calculations in accordance with Section 721.
  4. Engineering analysis based on a comparison of building element designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E 119.
  5. Alternative protection methods as allowed by Section 104.1.
The tests indicated in Sections 703.4.1 and 703.4.2 shall serve as criteria for acceptance of building materials as set forth in Sections 602.2, 602.3 and 602.4 in Type I, II, III and IV construction. The term "noncombustible" does not apply to the flame spread characteristics of interior finish or trim materials. A material shall not be classified as a noncombustible building construction material if it is subject to an increase in combustibility or flame spread beyond the limitations herein established through the effects of age, fabrication or erection techniques, moisture or other atmospheric conditions.
Materials required to be noncombustible shall be tested in accordance with ASTM E 136.
Materials having a structural base of noncombustible material as determined in accordance with Section 703.4.1 with a surfacing not more than 0.125 inch (3.18 mm) thick that has a flame spread index not greater than 50 when tested in accordance with ASTM E 84 shall be acceptable as noncombustible materials.
Exterior walls shall be fire-resistance rated and have opening protection as required by this section. Exterior wall construction shall comply with the provisions of Chapter 14 and Appendix D where applicable.
Cornices, eave overhangs, exterior balconies and similar architectural appendages, including but not limited to, fascias, belt courses, pilasters, surrounds, gutters, leaders, half-timber work, shutters, trellises, which extend beyond the floor area shall conform to the requirements of this section and Section 1406, provided, if removed or destroyed, will not reduce the structural stability of the building enclosure, and installed so as not to reduce the required fire resistance rating of the enclosure. Exterior egress balconies and exterior exit stairways shall comply with the requirements of this section, Section 1013.5, and Section 1022.1. Projections shall not extend beyond the distance determined by the following two methods, whichever results in the lesser projection:
  1. A point one-third the distance to the lot line from an assumed vertical plane located where protected openings are required in accordance with Section 704.8.
  2. More than 12 inches (305mm) into areas where openings are prohibited.
Projections from walls of Type III, IV or V construction shall be of any approved material.
Combustible projections located where openings are not permitted or where protection of openings is required shall be of at least 1-hour fire-resistance-rated construction, Type IV construction, or as required by Section 1406.3.
For the purposes of determining the required wall and opening protection and roof-covering requirements, buildings on the same tax lot shall be assumed to have an imaginary line between them.

Exception: Two or more buildings on the same tax lot shall either be regulated as separate buildings or shall be considered as portions of one building if the aggregate area of such buildings is within the limits specified in Chapter 5 for a single building. Where the buildings contain different occupancy groups or are of different types of construction, the area shall be that allowed for the most restrictive occupancy or construction.
Exterior walls shall be fire-resistance rated in accordance with Tables 601, 602, and Appendix D where applicable. The fire-resistance rating of exterior walls with a fire-separation distance of greater than 5 feet (1524 mm) shall be rated for exposure to fire from the inside. The fire-resistance rating of exterior walls with a fire-separation distance of 5 feet (1524 mm) or less shall be rated for exposure to fire from both sides.
The wall shall extend to the height required by Section 704.11 and shall have sufficient structural stability such that it will remain in place for the duration of time indicated by the required fire-resistance rating.
Where protected openings are not limited by Section 704.8, the limitation on the rise of temperature on the unexposed surface of exterior walls as required by ASTM E 119 shall not apply. Where protected openings are limited by Section 704.8, the limitation on the rise of temperature on the unexposed surface of exterior walls as required by ASTM E 119 shall not apply provided that a correction is made for radiation from the unexposed exterior wall surface in accordance with the following formula:


Ae = A + (Af x Feo) (Equation 7-1)
where:
Ae = Equivalent area of protected openings.
A = Actual area of protected openings.
Af = Area of exterior wall surface in the story under consideration exclusive of openings,on which the temperature limitations of ASTM E 119 for walls are exceeded.
Feo = An "equivalent opening factor" derived from Figure 704.7 based on the average temperature of the unexposed wall surface and the fire-resistance rating of the wall.


For SI: °C = [(°F) - 32] / 1.8.
FIGURE 704.7
EQUIVALENT OPENING FACTOR
The maximum area of unprotected or protected openings permitted in an exterior wall in any story shall not exceed the values set forth in Table 704.8. Where both unprotected and protected openings are located in the exterior wall in any story, the total area of the openings shall comply with the following formula:


(A / a + Au / au) ≤ 1.0 (Equation 7-2)

where:
A = Actual area of protected openings, or the equivalent area of protected openings, Ae (see Section 704.7).
a = Allowable area of protected openings.
Au = Actual area of unprotected openings.
au = Allowable area of unprotected openings.
TABLE 704.8
MAXIMUM AREA OF EXTERIOR WALL OPENINGSa,i
CLASSIFICATION
OF OPENING
FIRE SEPARATION DISTANCE (feet)
0 to 3e,h Greater
than 3 and not
more than 5b
Greater
than 5 and not
more than 10d,f
Greater
than 10 and not
more than 15c,d,f
Greater
than 15 and not
more than 20c,f
Greater
than 20 and not
more than 25c,f
Greater
than 25 and not
more than 30c,f
Greater
than 30
Unprotected Not
Permittedg
Not
Permittedb, g, k
10% 15% 25% 45% 70% No Limit
Protected Not
Permittedi, j
15%k 25%k 45%k 75%k No Limitk No Limitk No Limit
For SI: 1 foot = 304.8 mm.
  1. Values given are percentage of the area of the exterior wall.
  2. For occupancies in Group R-3, the maximum percentage of unprotected and protected exterior wall openings shall be 25 percent.
  3. The area of openings in an open parking structure with a fire separation distance of greater than 10 feet shall not be limited.
  4. For occupancies in Group H-2 or H-3, unprotected openings shall not be permitted for openings with a fire separation distance of 15 feet or less.
  5. For requirements for fire walls for buildings with differing roof heights, see Section 705.6.1.
  6. The area of unprotected and protected openings is not limited for occupancies in Group R-3, as applicable in Section 101.2, with a fire separation distance greater than 5 feet.
  7. Buildings whose exterior bearing wall, exterior nonbearing wall and exterior structural frame are not required to be fire-resistance rated shall be permitted to have unlimited unprotected openings.
  8. Includes accessory buildings to Group R-3.
  9. Protected openings through a wall or walls between buildings shall comply with Section 705.8.
  10. Protected openings within a fire separation distance of 3 feet or less are permitted for Occupancy Groups R-2 and R-3 provided such openings do not exceed 10 percent of the area of the façade of the story in which they are located. These openings shall not be credited towards meeting any mandatory natural light or ventilation requirements.
  11. In Group R-2 and R-3 occupancies with an exterior separation distance greater than 3 feet, openings shall be in accordance with percentages indicated as "Protected Classification of Opening" in Table 704.8. However, such openings shall not be required to be protected.
  12. Upon special application, the commissioner may permit exterior wall openings to be constructed in excess of the permitted area established by Table 704.8 if such openings at the time of their construction are located at least 60 feet in a direct line from any neighboring building, unless otherwise permitted by Section 704.3 for buildings onthe same lot. If any neighboring building is later altered or constructed to come within the above distance limitation, the affected exterior openings shall immediately be closed with construction meeting the fire-resistance-rating requirements for exterior wall construction of the building in which they are located. Such additional openings shall not be credited toward meeting any of the mandatory natural light or ventilation requirements unless they also comply with applicable provisions of Chapter 12 and the zoning resolution.
In buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the maximum allowable area of unprotected openings in occupancies other than Groups H-1, H-2 and H-3 shall be the same as the tabulated limitations for protected openings.
In occupancies other than Group H, unlimited unprotected openings are permitted in the first story of exterior walls facing a street that have a fire separation distance of greater than 15 feet (4572 mm), or facing an unoccupied space. The unoccupied space shall be on the same lot or dedicated for public use, shall not be less than 30 feet (9144 mm) in width, and shall have access from a street by a posted fire lane in accordance with the New York City Fire Code.
Openings in exterior walls in adjacent stories shall be separated vertically to protect against fire spread on the exterior of the buildings where the openings are within 5 feet (1524 mm) of each other horizontally in accordance with Section 715.4.8. Such openings shall be separated vertically at least 3 feet (914 mm) by spandrel girders, exterior walls or other similar assemblies that have a fire-resistance rating of at least 1 hour or by flame barriers that extend horizontally at least 30 inches (762 mm) beyond the exterior wall and that are at least as wide as the opening. Flame barriers shall also have a fire-resistance rating of at least 1 hour. The unexposed surface temperature limitations specified in ASTM E 119 shall not apply to the flame barriers or vertical separation unless otherwise required by the provisions of this code. Where a curtain wall assembly is used on the exterior wall, the intersection between the floor assembly and curtain wall assembly shall be protected in accordance with Section 713.4.
  Exceptions:
  1. This section shall not apply to buildings that are three stories or less in height.
  2. This section shall not apply to buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
  3. This section shall not apply to open parking garages.
  4. This section shall not apply to Occupancy Group A, E, I, or R.
For buildings on the same tax lot, approved protectives shall be provided in every opening that is less than 15 feet (4572 mm) vertically above the roof of an adjoining building or adjacent structure that is within a horizontal fire-separation distance of 15 feet (4572 mm) of the wall in which the opening is located.

Exception: Opening protectives are not required where the roof construction has a fire-resistance rating of not less than 1 hour for a minimum distance of 10 feet (3048 mm) from the adjoining building and the entire length and span of the supporting elements for the fire-resistance-rated roof assembly has a fire-resistance rating of not less than 1 hour.
Parapets shall be provided on exterior walls of buildings.

Exceptions: A parapet need not be provided on an exterior wall where any of the following conditions exist:
  1. The wall is not required to be fire-resistance rated in accordance with Table 602 because of fire separation distance.
  2. The building has an area of not more than 1,000 square feet (93 m2) on every floor.
  3. Walls that terminate at roofs of not less than 2-hour fire-resistance-rated construction.
  4. One-hour fire-resistance-rated exterior walls that terminate at the underside of the roof sheathing, deck or slab, provided that the entire building is covered with a Class A roof covering. Such roof shall not have openings located within 10 feet (3048 mm) of the 1-hour fire-resistance-rated exterior wall and not within 5 feet (1524 mm) for Groups R and U.
  4.1. Where the roof/ceiling framing elements are parallel to the walls, such framing and elements supporting such framing shall not be of less than 1-hour fire-resistance-rated construction for a width of 4 feet (1219 mm) measured from the interior side of the wall for Groups R and U and 10 feet (3048 mm) for other occupancies; or
  4.2. Where roof/ceiling framing elements are not parallel to the wall, the entire span of such framing and elements supporting such framing shall not be of less than 1-hour fire-resistance-rated construction.
  5. In occupancies of Groups R-2 and R-3, both provided with a Class A or B roof covering, the exterior wall shall be permitted to terminate at the roof sheathing or deck in Type III, IV and V construction provided:
  5.1. The roof sheathing or deck is constructed of approved noncombustible materials or of fire-retardant-treated wood, for a distance of 4 feet (1219 mm) from the perimeter; or
  5.2. The roof is protected with 0.625-inch (15.88 mm) Type X gypsum board directly beneath the underside of the roof sheathing or deck, supported by a minimum of nominal 2-inch (51 mm) ledgers attached to the sides of the roof framing members, for a minimum distance of 4 feet (1219 mm).
  6. Where the wall is permitted to have at least 25 percent of the exterior wall areas containing unprotected openings based on fire separation distance as determined in accordance with Section 704.8.
Parapets shall have the same fire-resistance rating as that required for the supporting wall, and on any side adjacent to a roof surface, shall have noncombustible faces for the uppermost 18 inches (457 mm), including counterflashing and coping materials. The height of the parapet shall not be less than 30 inches (762 mm) above the point where the roof surface and the wall intersect. Where the roof slopes toward a parapet at a slope greater than two units vertical in 12 units horizontal (16.7-percent slope), the parapet shall extend to the same height as any portion of the roof within a fire separation distance where protection of wall openings is required, but in no case shall the height be less than 30 inches (762 mm).
Windows required to be protected in accordance with Section 704.8, 704.9, or 704.10 shall comply with Section 715.4.8. Other openings required to be protected with fire doors or shutters in accordance with Sections 704.8, 704.9 and 704.10 shall comply with Section 715.3.

Exception: Fire protective assemblies are not required where the building is protected throughout by an automatic sprinkler system and the exterior openings are protected by an approved water curtain using automatic sprinklers approved for that use. The sprinklers and the water curtain shall be installed in accordance with NFPA 13, as modified in Appendix Q.
Where protected openings are not required by Section 704, windows and doors shall be constructed of any approved materials. Glazing shall conform to the requirements of Chapters 24 and 26.
Joints made in or between exterior walls required by this section to have a fire-resistance rating shall comply with Section 713.
  Exception: Joints in exterior walls that are permitted to have unprotected openings.
The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 713.4.
Penetrations by air ducts and air transfer openings in fire-resistance-rated exterior walls required to have protected openings shall comply with Section 716.
  Exception: Foundation vents installed in accordance with this code are permitted.
Each portion of a building separated by one or more fire walls that comply with the provisions of this section shall be considered a separate building. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates groups that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Concealed spaces in cornices and eaves shall comply with the provisions of Section 705.5.2.
Any wall located on a property line between adjacent buildings, which is used or adapted for joint service between the two buildings, shall be constructed as a fire wall in accordance with Section 705, and shall create separate buildings.
Attached one- and two-family dwellings shall be separated by walls constructed in accordance with Section 705 or Appendix M.
Fire walls shall have sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall for the duration of time indicated by the required fire-resistance rating.
Fire walls shall be constructed of any approved noncombustible materials.
Fire walls shall have a fire-resistance rating of not less than that required by Table 705.4.

TABLE 705.4
FIRE WALL FIRE-RESISTANCE RATINGS
GROUP FIRE-RESISTANCE RATING (hours)
A, B, E, H-4, I, R-1, R-2, U 3a
F-1, H-3b, H-5, M, S-1 3
H-1, H-2 4b
F-2, S-2, R-3, R-4 2
  1. Walls shall be not less than 2-hour fire-resistance rated where separating buildings of Type II or V construction.
  2. For Group H-1, H-2 or H-3 buildings, also see Sections 415.4 and 415.5.
Fire walls shall be continuous from exterior wall to exterior wall and shall extend at least 18 inches (457 mm) beyond the exterior surface of exterior walls.
  Exceptions:
  1. Fire walls shall be permitted to terminate at the interior surface of combustible exterior sheathing or siding provided the exterior wall has a fire-resistance rating of at least 1 hour for a horizontal distance of at least 4 feet (1219 mm) on both sides of the fire wall. Openings within such exterior walls shall be protected by fire assemblies having a fire protection rating of not less than 3/4 hour.
  2. Fire walls shall be permitted to terminate at the interior surface of noncombustible exterior sheathing, exterior siding or other noncombustible exterior finishes provided the sheathing, siding, or other exterior noncombustible finish extends a horizontal distance of at least 4 feet (1219 mm) on both sides of the fire wall.
  3. Fire walls shall be permitted to terminate at the interior surface of noncombustible exterior sheathing where the building on each side of the fire wall is protected by an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Where the fire wall intersects the exterior walls, the fire-resistance rating for the exterior walls on both sides of the fire wall shall have a 1-hour fire-resistance rating with 3/4 -hour opening protection where opening protection is required. The fire-resistance rating of the exterior wall shall extend a minimum of 4 feet (1219 mm) on each side of the intersection of the fire wall to exterior wall. Exterior wall intersections at fire walls that form an angle equal to or greater than 180 degrees (3.14 rad) do not need exterior wall protection.
Fire walls shall extend to the outer edge of horizontal projecting elements such as balconies, roof overhangs, canopies, marquees and architectural projections that are within 4 feet (1219 mm) of the fire wall.
  Exceptions:
  1. Noncombustible horizontal projecting elements without concealed spaces provided the exterior wall behind and below the projecting element has not less than 1-hour fire-resistance-rated construction for a distance not less than the depth of the projecting element on both sides of the fire wall. Openings within such exterior walls shall be protected by fire assemblies having a fire protection rating of not less than 3/4 hour.
  2. Noncombustible horizontal projecting elements with concealed spaces, provided a minimum 1-hour fire-resistance-rated wall extends through the concealed space. The projecting element shall be separated from the building by a minimum of 1-hour fire-resistance-rated construction for a distance on each side of the firewall equal to the depth of the projecting element. The wall is not required to extend under the projecting element where the building exterior wall is a minimum of 1-hour fire-resistance rated for a distance on each side of the firewall equal to the depth of the projecting element. Openings within such exterior walls shall be protected by fire assemblies having a fire protection rating of not less than 3/4 hour.
Fire walls shall extend from the foundation through the roof, to form a parapet at least 30 inches (762 mm) in height. Such parapet shall in no event extend to a point less than 4 inches (102 mm) above the highest point of peaked or gabled roof.
  Exceptions:
  1. Where a two-hour fire wall is permitted in accordance with Table 705.4, such wall shall be permitted to terminate at the underside of the roof sheathing, deck or slab provided:
  1.1. The lower roof assembly within 4 feet (1219 mm) of the wall has not less than a 1-hour fire-resistance rating and the entire length and span of supporting elements for the rated roof assembly has a fire-resistance rating of not less than 1 hour; and
  1.2. Openings in the roof shall not be located within 4 feet (1219 mm) of the fire wall; and
  1.3. Each building shall be provided with not less than a Class A roof covering.
  2. In buildings of Type I or II constructions, fire walls shall be permitted to terminate at the underside of noncombustible roof sheathing, deck, or slabs where both buildings are provided with not less than a Class A roof covering. Openings in the roof shall not be located within 4 feet (1219 mm) of the fire wall.
  3. In buildings of Type III, IV and V construction, fire walls shall be permitted to terminate at the underside of noncombustible roof sheathing or decks provided:
  3.1. There are no openings in the roof within 4 feet (1219 mm) of the fire wall; and
  3.2. The roof is covered with a minimum Class A roof covering.
  4. Buildings located above a parking garage designed in accordance with Section 509.2 shall be permitted to have the fire walls for the buildings located above the parking garage extend from the horizontal separation between the parking garage and the buildings.
Adjacent combustible members entering into a concrete or masonry firewall from opposite sides shall not have less than a 4-inch (102 mm) distance between embedded ends. Where combustible members frame into hollow walls or walls of hollow units, hollow spaces shall be solidly filled for the full thickness of the wall and for a distance not less than 4 inches (102 mm) above, below and between the structural members, with noncombustible materials approved for fire blocking.
Each opening through a fire wall, a party wall, or a through wall between two buildings shall be protected in accordance with Section 715.3 and shall not exceed 120 square feet (11 m2), with no dimension greater than 12 feet (3658 mm). The aggregate width of openings at any floor level shall not exceed 25 percent of the length of the wall.

Exception: Openings shall not be limited to 120 square feet (11 m2) where both buildings are equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. However, the aggregate width of all openings at any one floor level shall not exceed 25 percent of the length of the wall.
Penetrations through fire walls shall comply with Section 712.
Joints made in or between fire walls shall comply with Section 713.
Ducts and air transfer openings shall not penetrate fire walls.

Exception: Penetrations by ducts and air transfer openings of fire walls that are not on a tax lot line shall be allowed provided the penetrations comply with Sections 712 and 716. The size and aggregate width of all openings shall not exceed the limitations of Section 705.8.
Fire barriers used for separation of shafts, exits, exit passageways, horizontal exits or incidental use areas, to separate different occupancies, to separate a single occupancy into different fire areas, or to separate other areas where a fire barrier is required elsewhere in this code or the New York City Fire Code, shall comply with this section.
The walls and floor assemblies shall be of materials permitted by the building type of construction.
The fire-resistance rating of the walls and floor assemblies shall comply with this section.
The fire-resistance rating of the separation between building areas and an exit passageway shall comply with Section 1020.1.
The fire-resistance rating of the separation between building areas connected by a horizontal exit shall comply with Section 1021.1.
The fire barrier separating incidental use areas shall have a fire-resistance rating of not less than that indicated in Table 508.2.
Where the provisions of Section 508.3.3 are applicable, the fire barrier separating mixed occupancies shall have a fire-resistance rating of not less than that indicated in Section 508.3.3 based on the occupancies being separated.
*Section BC 706.3.6 was amended by: Local Law 8 of 2008. This law has an effective date of July 1, 2008.
The fire barrier separating a single occupancy into different fire areas shall have a fire-resistance rating of not less than that indicated in Table 706.3.7.

TABLE 706.3.7
FIRE-RESISTANCE RATING REQUIREMENTS FOR FIRE BARRIER ASSEMBLIES BETWEEN FIRE AREAS
OCCUPANCY GROUP FIRE-RESISTANCE RATING (hours)
H-1, H-2 4
F-1, H-3, S-1 3
A, B, E, F-2, H-4, H-5,
I, M, R, S-2
2
U 1
The fire-resistance rating of the fire barrier separating atriums shall comply with Section 404.5.
Fire barrier walls shall extend from the top of the floor/ceiling assembly below to the underside of the floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous through concealed spaces such as the space above a suspended ceiling. The supporting construction for fire barrier walls shall be protected to afford the required fire-resistance rating of the fire barrier supported except for 1-hour fire-resistance-rated incidental use area separations as required by Table 508.2 in buildings of Type IIB, IIIB and VB construction. Hollow vertical spaces within the fire barrier wall shall be fire-stopped at every floor level.
  Exceptions:
  1. The maximum required fire-resistance rating for assemblies supporting fire barriers separating tank storage as provided for in Section 415.7.2.1 shall be 2 hours, but not less than required by Table 601 for the building construction type.
  2. Shaft enclosure shall be permitted to terminate at a top enclosure complying with Section 707.12.
Horizontal fire barriers shall be constructed in accordance with Section 711.
Where exterior walls serve as a part of a required fire-resistance-rated enclosure, such walls shall comply with the requirements of Section 704 for exterior walls, and the fire-resistance-rated enclosure requirements of Section 706 shall not apply.

Exception: Exterior walls required to be fire-resistance rated in accordance with Section 1022.6.
Openings in a fire barrier wall shall be protected in accordance with Section 715. Openings shall be limited to a maximum aggregate width of 25 percent of the length of the wall, and the maximum area of any single opening shall not exceed 120 square feet (11 m2). Openings in vertical exit enclosures and exit passageways shall also comply with Sections 1019.1.1 and 1020.4, respectively.
  Exceptions:
  1. Openings shall not be limited to 120 square feet (11 m2) where adjoining fire areas are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. Openings for fire doors serving an exit enclosure shall not be limited to an aggregate width of 25 percent of the length of the wall.
  3. Openings shall not be limited to 120 square feet (11 m2) or an aggregate width of 25 percent of the length of the wall where the opening protective assembly has been tested in accordance with ASTM E 119 and has a minimum fire-resistance rating not less than the fire-resistance rating of the wall.
  4. Openings permitted in atrium enclosures shall comply with the provisions of Section 404.5.
Penetrations through fire barriers shall comply with Section 712.
Penetrations into an exit enclosure shall only be allowed when permitted by Sections 1019.1.2 and 1020.5.
Joints made in or between fire barriers shall comply with Section 713.
Penetrations by ducts and air transfer openings shall comply with Sections 712 and 716.
Penetrations by ducts and air transfer openings into an exit enclosure shall only be allowed when permitted by Sections 1019.1.2 and 1020.5.
The provisions of this section shall apply to vertical shafts where such shafts are required to protect openings and penetrations through floor/ceiling and roof/ceiling assemblies.
Openings through a floor/ceiling assembly shall be protected by a shaft enclosure complying with this section.
  Exceptions:
  1. A shaft enclosure is not required for openings totally within an individual residential dwelling unit and connecting four stories or less where such dwelling unit is fully sprinklered in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.
  2. A shaft enclosure is not required in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 for an escalator opening or stairway which is not a portion of the means of egress protected according to Item 2.1 or 2.2:
  2.1. Where the area of the floor opening between stories does not exceed twice the horizontal projected area of the escalator or stairway and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13, as modified in Appendix Q. In other than Groups B and M, this application is limited to openings that do not connect more than four stories.
  2.2. Where the opening is protected by approved power-operated automatic shutters at every floor penetrated. The shutters shall be of noncombustible construction and have a fire-resistance rating of not less than 1.5 hours. The shutter shall be so constructed as to close immediately upon the actuation of a smoke detector installed in accordance with Section 907.10 and shall completely shut off the well opening. Escalators shall cease operation when the shutter begins to close. The shutter shall operate at a speed of not more than 30 feet per minute (152.4 mm/s) and shall be equipped with a sensitive leading edge to arrest its progress where in contact with any obstacle, and to continue its progress on release therefrom.
  3. A shaft enclosure is not required for penetrations by pipe, tube, conduit, wire, cable, and vents protected in accordance with Section 712.4.
  4. A shaft enclosure is not required for penetrations by ducts protected in accordance with Section 712.4. Grease ducts shall be protected in accordance with the New York City Mechanical Code.
  5. In other than Group H Occupancies, a shaft enclosure is not required for floor openings complying with the provisions for atriums in Section 404.
  6. A shaft enclosure is not required for approved masonry chimneys, where annular space protection is provided at each floor level in accordance with Section 717.2.5.
  7. In other than Groups I-2 and I-3, a shaft enclosure is not required for a floor opening that complies with all of the following:
  7.1. Does not connect more than two stories.
  7.2. Is not part of the required means of egress system except as permitted in Section 1019.1.
  7.3. Is not concealed within the building construction.
  7.4. Is not open to a corridor in Group I and R occupancies where such corridor is required to be fire-resistance rated in accordance with Table 1016.1.
  7.5. Is not open to a corridor on nonsprinklered floors in any occupancy where such corridor is required to be fire-resistance rated in accordance with Table 1016.1.
  7.6. Is separated from floor openings serving other floors by construction conforming to required shaft enclosures.
  8. A shaft enclosure is not required for automobile ramps in open parking garages and enclosed parking garages constructed in accordance with Sections 406.3 and 406.4, respectively.
  9. A shaft enclosure is not required for floor openings between a mezzanine and the floor below.
  10. A shaft enclosure is not required for joints protected by a fire-resistant joint system in accordance with Section 713.
  11. Where permitted by other sections of this code.
The shaft enclosure shall be of materials permitted by the building type of construction.

Exception: Noncombustible materials shall be used for shaft enclosures in Groups I-1, R-1 and R-2 buildings irrespective of the building type of construction.
Shaft enclosures shall have a fire-resistance rating of not less than 2 hours where penetrating three stories or more and not less than 1 hour where penetrating fewer than three stories. The number of stories connected by the shaft enclosure shall include any basements or cellars, but not any mezzanines. Shaft enclosures shall be constructed as fire barriers in accordance with Section 706. Shaft enclosures shall have a fire-resistance rating not less than the floor assembly penetrated, but need not exceed 2 hours.
Where the roof construction is of combustible materials, shaft enclosure walls shall extend through the roof construction at least 30 inches (762 mm) above the roof. Where the roof construction is of noncombustible materials, shaft enclosure walls shall extend from the top of the floor/ceiling assembly below to the underside of the floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous through concealed spaces such as the space above a suspended ceiling. The supporting construction shall be protected to afford the required fire-resistance rating of the element supported. Hollow vertical spaces within the shaft enclosure construction wall shall be firestopped at every floor level.
  Exception: A shaft enclosure of a refuse or laundry chute shall extend through combustible or noncombustible roof construction at least 6 feet (1829 mm) above the roof.
Where exterior walls serve as a part of a required shaft enclosure, such walls shall comply with the requirements of Section 704 for exterior walls and the fire-resistance-rated enclosure requirements of Section 707.4 shall not apply.
  Exception: Exterior walls required to be fire-resistance rated in accordance with Section 1022.6.
Openings in a shaft enclosure shall be protected in accordance with Section 715 as required for fire barriers. Such openings shall be self-closing or automatic-closing by smoke detection. Automatic-closing by smoke detection is not permitted for required vertical exit doors.
Openings other than those necessary for the purpose of the shaft shall not be permitted in shaft enclosures.
Penetrations in a shaft enclosure shall be protected in accordance with Section 712 as required for fire barriers.
Penetrations other than those necessary for the purpose of the shaft shall not be permitted in shaft enclosures.
  Exception: Duct penetrations in accordance with Section 707.10, as permitted in Sections 1019.1.2, 1019.1.3, and 1020.5.
Penetrations of a shaft enclosure by ducts and air transfer openings shall comply with Sections 712 and 716.
Shafts that do not extend to the bottom of the building or structure shall:
  1. Be enclosed at the lowest level with construction of the same fire-resistance rating as the lowest floor through which the shaft passes, but not less than the rating required for the shaft enclosure; or
  2. Terminate in a room having a use related to the purpose of the shaft. The room shall be separated from the remainder of the building by construction having a fire-resistance rating and opening protectives at least equal to the protection required for the shaft enclosure.
  Exceptions:
  1. The fire-resistance-rated room separation is not required provided there are no openings in or penetrations of the shaft enclosure to the interior of the building except at the bottom. The bottom of the shaft shall be closed off around the penetrating items with materials permitted by Section 717.3.1 for draft stopping, or the room shall be provided with an approved automatic fire suppression system.
  2. A shaft enclosure containing a refuse chute or laundry chute shall not be used for any other purpose and shall terminate in a room protected in accordance with Section 707.13.4.
  3. The fire-resistance-rated room separation and the protection at the bottom of the shaft are not required provided there are no combustibles in the shaft and there are no openings or other penetrations through the shaft enclosure to the interior of the building.
A shaft enclosure that does not extend to the underside of the roof deck of the building shall be enclosed at the top with construction of the same fire-resistance rating as the topmost floor penetrated by the shaft, but not less than the fire-resistance rating required for the shaft enclosure.
Refuse and laundry chutes, access and termination rooms and incinerator rooms shall meet the requirements of Sections 707.13.1 through 707.13.6.
  Exception: Chutes serving and contained within a single dwelling unit.
A shaft enclosure containing a refuse or laundry chute shall not be used for any other purpose and shall have a fire-resistance rating of 2 hours. Openings into the shaft, including those from access rooms and termination rooms, shall be protected in accordance with this section and Section 715. Openings into chutes shall not be located in exit access corridors. Opening protectives shall be self-closing.
A shaft enclosure containing a refuse or laundry chute shall be constructed of noncombustible materials.
Access openings for refuse and laundry chutes shall be located in dedicated rooms or compartments completely enclosed by construction that has a fire-resistance rating of not less than 2 hours. Openings into the access rooms shall be protected by opening protectives having a fire protection rating of not less than 11/2 hour and shall be self-closing. Openings may be automatic-closing upon the detection of smoke provided that the storage of refuse, including recyclables, or laundry is not permitted in such access rooms.
  Exception: Access openings for refuse or laundry chutes located within a dwelling unit need not be located within a separate room or compartment.
Refuse and laundry chutes shall discharge into an enclosed room completely separated from the remainder of the building by construction that has a fire-resistance rating of not less than 3 hours. Openings into the termination room shall be protected by opening protectives having a fire protection rating of not less than 11/2 hours and shall be self-closing.
Incinerator rooms shall comply with Table 508.2.
An approved automatic fire sprinkler system shall be installed in accordance with Section 903.2.10.2.
Elevator hoist way and dumbwaiter enclosures shall be constructed in accordance with Section 707.4 and Chapter 30.
Elevator lobbies shall be provided in accordance with Section 403.9.1.
The following wall assemblies shall comply with this section.
  1. Walls separating tenant spaces in covered mall buildings as required by Section 402.7.2.
  2. Walls as required by Section 1016.1.
The walls shall be of materials permitted by the building type of construction.
The fire-resistance rating of the walls shall be 1 hour.
  Exception: Interior corridor walls as permitted by Table 1016.1.
Fire partitions shall extend from the top of the floor assembly below to the underside of the floor or roof slab or deck above or to the fire-resistance-rated floor/ceiling or roof/ceiling assembly above, and shall be securely attached thereto. If the partitions are not continuous to the deck, the space between the ceiling and the deck above shall be fire blocked or draft stopped in accordance with Sections 717.2.1 and 717.3.1 at the partition line. The supporting construction shall be protected to afford the required fire-resistance rating of the wall supported.
  Exceptions:
  1. The fire partition separating tenant spaces in a mall, complying with Section 402.7.2, is not required to extend beyond the underside of a ceiling that is not part of a fire-resistance-rated assembly. A wall is not required in attic or ceiling spaces above tenant separation walls.
  2. Fire blocking or draft stopping is not required at the partition line in Group R-2 buildings that do not exceed four stories in height provided the attic space is subdivided by draft stopping into areas not exceeding 3,000 square feet (279 m2) or above every two dwelling units, whichever is smaller.
  3. Fire blocking or draft stopping is not required at the partition line in buildings equipped with an automatic sprinkler system installed throughout in accordance with Section 903.3.1.1 or 903.3.1.2 provided that automatic sprinklers are installed in combustible floor/ceiling and roof/ceiling spaces.
Where exterior walls serve as a part of a required fire-resistance-rated enclosure, such walls shall comply with the requirements of Section 704 for exterior walls and the fire-resistance-rated enclosure requirements of Section 708.3 shall not apply.
Openings in a fire partition shall be protected in accordance with Section 715.
Penetrations through fire partitions shall comply with Section 712.
Joints made in or between fire partitions shall comply with Section 713.
Penetrations by ducts and air transfer openings shall comply with Sections 712 and 716.
Smoke barriers shall comply with this section.
Smoke barriers shall be of materials permitted by the building type of construction.
A 1-hour fire-resistance rating is required for smoke barriers.
  Exception: Smoke barriers constructed of minimum 0.10-inch-thick (2.5 mm) steel in Group I-3 buildings.
Smoke barriers shall form an effective membrane continuous from outside wall to outside wall and from floor slab to floor or roof deck above, including continuity through concealed spaces, such as those found above suspended ceilings, and interstitial structural and mechanical spaces. The supporting construction shall be protected to afford the required fire-resistance rating of the wall or floor supported in buildings of other than Type IIB, IIIB or VB construction.
  Exception: Smoke barrier walls are not required in interstitial spaces where such spaces are designed and constructed with ceilings that provide resistance to the passage of fire and smoke equivalent to that provided by the smoke barrier walls.
Openings in a smoke barrier shall be protected in accordance with Section 715.
  Exception: In Group I-2, where such doors are installed across corridors, a pair of opposite-swinging doors without a center mullion shall be installed having vision panels with approved fire-resistance-rated glazing materials in approved fire-resistance-rated frames, the area of which shall not exceed that tested. The doors shall be close fitting within operational tolerances, and shall not have undercuts, louvers or grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges and automatic-closing devices. Positive-latching devices are not required.
Penetrations through smoke barriers shall comply with Section 712.
Joints made in or between smoke barriers shall comply with Section 713.
Penetrations by duct and air transfer openings shall comply with Sections 712 and 716.
Smoke partitions installed as required elsewhere in the code shall comply with this section.
Smoke partitions shall be constructed of noncombustible materials. Glazing may be used provided it is heat-strengthened or tempered glazing complying and shall otherwise comply with Chapter 24, and shall be protected by sprinkler heads installed in a maximum of 6 feet (1829 mm) on center on each side of the smoke partition.
Unless required elsewhere in the code, smoke partitions are not required to have a fire-resistance rating.
Smoke partitions shall extend from the floor to the underside of the floor or roof deck above or to the underside of the ceiling above where the ceiling membrane is constructed to limit the transfer of smoke.
Windows shall be sealed to resist the free passage of smoke or be automatic-closing upon detection of smoke. Doors in smoke partitions shall comply with this section.
Doors in smoke partitions shall not include louvers.
Where required elsewhere in the code, doors in smoke partitions shall be tested in accordance with UL 1784 with an artificial bottom seal installed across the full width of the bottom of the door assembly. The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot [ft3/(min ft2)] (0.015424 m3/sm2 ) of door opening at 0.10 inch (24.9 Pa) of water for both the ambient temperature test and the elevated temperature exposure test.
Where required elsewhere in the code, doors in smoke partitions shall be self-closing or automatic-closing in accordance with Section 715.3.7.3.
The space around penetrating items and in joints shall be filled with an approved material to limit the free passage of smoke.
Air transfer openings in smoke partitions shall be provided with a smoke damper complying with Section 716.3.2.
  Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized.
Floor and roof assemblies required to have a fire-resistance rating shall comply with this section.
The floor and roof assemblies shall be of materials permitted by the building type of construction.
  Exception: Horizontal floor or roof assemblies shall be of noncombustible materials when such assemblies serve as a horizontal offset to a fire wall or fire barrier that is required to be noncombustible.
The fire-resistance rating of floor and roof assemblies shall not be less than that required by the building type of construction. Where the floor assembly separates mixed occupancies, the assembly shall have a fire-resistance rating of not less than that required by Section 508.3.3 based on the occupancies being separated. Where the floor assembly separates a single occupancy into different fire areas, the assembly shall have a fire-resistance rating of not less than that required by Section 706.3.7. Floor assemblies separating dwelling units in Group I-1 or R Occupancies shall be a minimum of 1-hour fire-resistance-rated construction.
Where the weight of lay-in ceiling panels, used as part of fire-resistance-rated floor/ceiling or roof/ceiling assemblies, is not adequate to resist an upward force of 1 lb/ft.2 (48 Pa), wire or other approved devices shall be installed above the panels to prevent vertical displacement under such upward force.
Access doors shall be permitted in ceilings of fire-resistance-rated floor/ceiling and roof/ceiling assemblies provided such doors are tested in accordance with ASTM E 119 as horizontal assemblies and labeled by an approved agency for such purpose.
In 1-hour fire-resistance-rated floor construction, the ceiling membrane is not required to be installed over unusable crawl spaces not intended for occupancy or storage, less than 24 inches (610 mm) in height. In 1-hour fire-resistance-rated roof construction, the floor membrane is not required to be installed where the unusable attic space above is not intended for occupancy or storage.
Assemblies shall be continuous without openings, penetrations or joints except as permitted by this section and Sections 707.2, 712.4 and 713. Skylights and other penetrations through a fire-resistance-rated roof deck are permitted to be unprotected, provided that the structural integrity of the fire-resistance-rated roof construction is maintained. Unprotected skylights shall not be permitted in roof construction required to be fire-resistance rated in accordance with Section 704.10. The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported.
Penetrations through fire-resistance-rated horizontal assemblies shall comply with Section 712.
Joints made in or between fire-resistance-rated horizontal assemblies shall comply with Section 713. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 713.4.
Penetrations by ducts and air transfer openings shall comply with Sections 712 and 716.
The provisions of this section shall govern the materials and methods of construction used to protect through penetrations and membrane penetrations.
All through-penetration and membrane-penetration firestop systems shall comply with the special inspection requirements of Chapter 17.
Where sleeves are used, they shall be securely fastened to the assembly penetrated. The space between the item contained in the sleeve and the sleeve itself and any space between the sleeve and the assembly penetrated shall be protected in accordance with this section. Insulation and coverings on or in the penetrating item shall not penetrate the assembly unless the specific material used has been tested as part of the assembly in accordance with this section.
Penetrations into or through fire walls, fire barriers, smoke barrier walls, and fire partitions shall comply with this section.
Through penetrations of fire-resistance-rated walls shall comply with Section 712.3.1.1 or 712.3.1.2.
  Exception: Where the penetrating items are steel, ferrous or copper pipes or steel conduits, the annular space between the penetrating item and the fire-resistance-rated wall shall be permitted to be protected as follows:
  1. In concrete or masonry walls where the penetrating item is a maximum 6-inch (152 mm) nominal diameter and the opening is a maximum 144 square inches (0.0929 m2), concrete, grout or mortar shall be permitted where installed the full thickness of the wall or the thickness required to maintain the fire-resistance rating; or
  2. The material used to fill the annular space shall prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.
Penetrations shall be installed as tested in an approved fire-resistance-rated assembly.
Through penetrations shall be protected by an approved penetration fire stop system installed as tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water and shall have an F rating of not less than the required fire-resistance rating of the wall penetrated.
Membrane penetrations shall be protected by a membrane penetration firestop installed in accordance with Section 712.3.1. Where walls and partitions are required to have a minimum 1-hour fire-resistance rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced.
  Exceptions:
  1. Steel electrical boxes that do not exceed 16 square inches (0.0103 m2) in area provided the total area of such openings does not exceed 100 square inches (0.0645 m2) for any 100 square feet (9.29 m2) of wall area. Outlet boxes on opposite sides of the wall shall be separated as shown:
  1.1. By a horizontal distance of not less than 24 inches (610 mm);
  1.2. By a horizontal distance of not less than the depth of the wall cavity where the wall cavity is filled with cellulose loose fill, rock wool or slag mineral wool insulation;
  1.3. By solid fire blocking in accordance with Section 717.2.1;
  1.4. By protecting both outlet boxes by listed putty pads; or
  1.5. By other listed materials and methods.
  2. Membrane penetrations for listed electrical outlet boxes of any material are permitted provided such boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. Outlet boxes on opposite sides of the wall shall be separated as follows:   2.1. By a horizontal distance of not less than 24 inches (610 mm);
  2.2. By solid fire blocking in accordance with Section 717.2.1;
  2.3. By protecting both outlet boxes by listed putty pads; or
  2.4. By other listed materials and methods.
  3. The annular space created by the penetration of a fire sprinkler provided it is covered by a metal escutcheon plate.
Penetrations of fire-resistance-rated walls by ducts and air transfer openings that are not protected with fire dampers shall comply with this section.
Noncombustible penetrating items shall not connect to combustible items beyond the point of fire stopping unless it can be demonstrated to the commissioner that the fire-resistance integrity of the wall is maintained.
Penetrations of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected in accordance with Section 707. Penetrations permitted by Exceptions 3 and 4 of Section 707.2 shall comply with Sections 712.4.1 through 712.4.4.
  Exception: Penetrations located within the same room or undivided area as floor openings not required to have a shaft enclosure in accordance with Exceptions 1, 2, 5, 7, 8 or 9 in Section 707.2.
Through penetrations of fire-resistance-rated horizontal assemblies shall comply with Section 712.4.1.1 or 712.4.1.2.
  Exceptions:
  1. Penetrations by steel, ferrous or copper conduits, pipes, tubes, vents, concrete, or masonry through a single fire-resistance-rated floor assembly where the annular space is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated. Penetrating items with a maximum 6-inch (152 mm) nominal diameter shall not be limited to the penetration of a single fire-resistance-rated floor assembly provided that the area of the penetration does not exceed 144 square inches (92 900 mm2) in any 100 square feet (9.3m2) of floor area.
  2. Penetrations in a single concrete floor by steel, ferrous or copper conduits, pipes, tubes and vents with a maximum 6-inch (152 mm) nominal diameter provided concrete, grout or mortar is installed the full thickness of the floor or the thickness required to maintain the fire-resistance rating. The penetrating items with a maximum 6-inch (152 mm) nominal diameter shall not be limited to the penetration of a single concrete floor provided that the area of the penetration does not exceed 144 square inches (0.0929 m2).
  3. Electrical outlet boxes of any material are permitted provided that such boxes are tested for use in fire-resistance-rated assemblies and installed in accordance with the tested assembly.
Penetrations shall be installed as tested in the approved fire-resistance-rated assembly.
Through penetrations shall be protected by an approved through-penetration fire stop system installed and tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water. The system shall have an F rating and a T rating of not less than 1 hour but not less than the required rating of the floor penetrated.
  Exception: Floor penetrations contained and located within the cavity of a wall do not require a T rating.
Penetrations of membranes that are part of a fire-resistance-rated horizontal assembly shall comply with Section 712.4.1.1 or 712.4.1.2. Where floor/ceiling assemblies are required to have a minimum 1-hour fire-resistance rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced.
  Exceptions:
  1. Membrane penetrations by steel, ferrous or copper conduits, electrical outlet boxes, pipes, tubes, vents, concrete, or masonry-penetrating items where the annular space is protected either in accordance with Section 712.4.1 or to prevent the free passage of flame and the products of combustion. Such penetrations shall not exceed an aggregate area of 100 square inches (64 500 mm2) in any 100 square feet (9.3 m2) of ceiling area in assemblies tested without penetrations.
  2. Membrane penetrations by listed electrical outlet boxes of any material are permitted provided such boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing.
  3. The annular space created by the penetration of a fire sprinkler provided it is covered by a metal escutcheon plate.
Penetrations of horizontal assemblies without a required fire-resistance rating shall meet the requirements of Section 707 or shall comply with Sections 712.4.3.1 through 712.4.3.2.
Noncombustible penetrating items that connect not more than three stories are permitted provided that the annular space is filled with an approved noncombustible material to resist the free passage of flame and the products of combustion.
Penetrating items that connect not more than two stories are permitted provided that the annular space is filled with an approved material to resist the free passage of flame and the products of combustion.
Penetrations of horizontal assemblies by ducts and air transfer openings that are not required to have dampers shall comply with this section. Ducts and air transfer openings that are protected with dampers shall comply with Section 716.
Noncombustible penetrating items shall not connect to combustible materials beyond the point of fire stopping unless it can be demonstrated that the fire-resistance integrity of the horizontal assembly is maintained.
Floor fire door assemblies used to protect openings in fire-resistance-rated floors shall be tested in the horizontal position in accordance with ASTM E 119, and shall achieve a fire-resistance rating not less than the assembly being penetrated. Floor fire doors shall be labeled by an approved agency.
Joints installed in or between fire-resistance-rated walls, floor or floor/ceiling assemblies and roofs or roof/ceiling assemblies shall be protected by an approved fire-resistant joint system designed to resist the passage of fire for a time period not less than the required fire-resistance rating of the wall, floor or roof in or between which it is installed. Fire-resistant joint systems shall be tested in accordance with Section 713.3. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 713.4.
  Exception: Fire-resistant joint systems shall not be required for joints in all of the following locations:
  1. Floors within a single dwelling unit.
  2. Floors where the joint is protected by a shaft enclosure in accordance with Section 707.
  3. Floors within atriums where the space adjacent to the atrium is included in the volume of the atrium for smoke control purposes.
  4. Floors within malls.
  5. Floors within open parking structures.
  6. Mezzanine floors.
  7. Walls that are permitted to have unprotected openings.
  8. Roofs where openings are permitted.
  9. Control joints not exceeding a maximum width of 0.625 inch (15.9 mm) and tested in accordance with ASTM E 119.
Fire-resistant joint systems shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to accommodate expected building movements and to resist the passage of fire and hot gases.
Fire-resistant joint systems shall be tested in accordance with the requirements of either ASTM E 1966 or UL 2079. Nonsymmetrical wall joint systems shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests. When evidence is furnished to show that the wall was tested with the least fire-resistant side exposed to the furnace, subject to acceptance of the commissioner, the wall need not be subjected to tests from the opposite side.
  Exception: For exterior walls with a horizontal fire separation distance greater than 5 feet (1524 mm), the joint system shall be required to be tested for interior fire exposure only.
Where fire resistance-rated floor or floor/ceiling assemblies are required, voids created at the intersection of the exterior curtain wall assemblies and such floor assemblies shall be sealed with an approved material or system to prevent the interior spread of fire. Such material or systems shall be securely installed and capable of preventing the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch (0.254 mm) of water column (2.5 Pa) for the time period at least equal to the fire-resistance rating of the floor assembly. Height and fire-resistance requirements for curtain wall spandrels shall comply with Section 704.9.
The fire-resistance rating of structural members and assemblies shall comply with the requirements for the type of construction and shall not be less than the rating required for the fire-resistance-rated assemblies supported.
  Exception: Fire barriers and fire partitions as provided in Sections 706.4 and 708.4, respectively.
The installation of all required sprayed-on fire protection shall be subject to the special inspection requirements of Section 1704.11.
Columns, girders, trusses, beams, lintels or other structural members that are required to have a fire-resistance rating and that support more than one floor or a roof, or support a load-bearing wall or a non-load-bearing wall more than one story high, shall be individually protected on all sides for the full length with materials having the required fire-resistance rating. Girders, trusses, beams, lintels or other structural members required to have a fire-resistance rating and that support only one floor or a roof, and/or a non-bearing wall not more than one story high, shall be protected by individual encasement, by a membrane or ceiling protection as specified in Section 711, or by a combination of both, which together provide the required fire-resistance rating. Columns shall also comply with Section 714.2.2.
Where columns require a fire-resistance rating, the entire column, including its connections to beams or girders, shall be individually protected. Where the column extends through a ceiling, fire resistance of the column shall be continuous from the top of the floor through the ceiling space to the top of the column.
The required thickness and construction of fire-resistance-rated assemblies enclosing trusses shall be based on the results of full-scale tests or combinations of tests on truss components or on approved calculations based on such tests that satisfactorily demonstrate that the assembly has the required fire resistance
The edges of lugs, brackets, rivets and bolt heads attached to structural members shall be protected to the highest fire-resistance rating of the members connected.
Thickness of protection for concrete or masonry reinforcement shall be measured to the outside of the reinforcement, including stirrups, ties and spiral reinforcing ties.
Pipes, wires, conduits, ducts or other service facilities shall not be embedded in the required fire protection of a structural member that is required to be individually encased; except that pipes, wires, and conduits may be installed in the space between the required fire protection and the structural member protected, provided that where such facilities pierce the required fire protection, the area of the penetration does not exceed two percent of the area of the fire protection on any one face, the penetrations are closed off with close-fitting metal escutcheons or plates, and the concealed space shall be firestopped at each story.
Where the fire protective covering of a structural member is subject to impact damage from moving vehicles, the handling of merchandise or other activity, the fire protective covering shall be protected by corner guards or by a substantial jacket of metal or other noncombustible material to a height adequate to provide full protection, but not less than 5 feet (1524 mm) from the finished floor.
Load-bearing structural members located within the exterior walls or exposed to the outdoors shall be provided with the highest fire-resistance rating as determined in accordance with the following:

  1. As required by Table 601 for the type of building element based on the type of construction of the building; and
  2. As required by Table 601 for exterior bearing walls based on the type of construction; and
  3. As required by Table 602 for exterior walls based on the fire separation distance.
Lintels over openings wider than 4 feet (1219 mm) in masonry walls, other than in walls of masonry veneer on wood frame structures, shall be fire protected as required by Section 714.2, when the full load over the opening is not relieved by a masonry arch of required strength.
  Exceptions:
  1. The members of an assembled metal lintel that support only outer face masonry that is securely bonded or anchored to backing need not be fire protected, provided that the inner members of the assembly support the full load imposed.
  2. The use of stone lintels in spans exceeding 4 feet (1219 mm) shall not be permitted unless supplemented by fire protected structural members or masonry arches of the required strength to support the superimposed loads.
Fire-resistance ratings for the isolation system shall meet the fire-resistance rating required for the columns, walls, or other structural elements in which the isolation system is installed in accordance with Table 601.
  Isolation systems required to have a fire-resistance rating shall be protected with approved materials or construction assemblies designed to provide the same degree of fire resistance as the structural element in which it is installed when tested in accordance with ASTM E 119 (see Section 703.2).
  Such isolation system protection applied to isolator units shall be capable of retarding the transfer of heat to the isolator unit in such a manner that the required gravity load-carrying capacity of the isolator unit will not be impaired after exposure to the standard time-temperature curve fire test prescribed in ASTM E 119 for a duration not less than that required for the fire resistance rating of the structure element in which it is installed.
  Such isolation system protection applied to isolator units shall be suitably designed and securely installed so as not to dislodge, loosen, sustain damage, or otherwise impair its ability to accommodate the seismic movements for which the isolator unit is designed and to maintain its integrity for the purpose of providing the required fire-resistance protection.
Opening protectives required by other sections of this code shall comply with the provisions of this section.
Labeled fire-resistance-rated glazing tested as part of a fire-resistance-rated wall assembly in accordance with ASTM E 119 shall not be required to comply with this section.
Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 715.3.1, 715.3.2 or 715.3.3 and the fire protection rating indicated in Table 715.3. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and NFPA 80.

  Exceptions:
  1. Labeled protective assemblies that conform to the requirements of this section or UL 10A, UL 14B and UL 14C for tin-clad fire door assemblies.
  2. Floor fire doors shall comply with Section 712.4.6.

TABLE 715.3
FIRE DOOR AND FIRE SHUTTER FIRE PROTECTION RATINGS
TYPE OF ASSEMBLY REQUIRED
ASSEMBLY
RATING
(hours)
MINIMUM FIRE
DOOR AND
FIRE SHUTTER
ASSEMBLY
RATING
(hours)
Fire walls and fire barriers having a
required fire-resistance rating greater
than 1 hour
4
3
2
11/2
3
3a
11/2
11/2
Fire barriers having a required
fire-resistance rating of 1 hour:
   Shaft, exit enclosure and exit
       passageway walls
   Other fire barriers
1

1
1

3/4
Fire partitions:
    Corridor walls
    Other partitions
1
1
3/4
3/4

Exterior walls
3
2
1
11/2
11/2
3/4
  1. Two doors, each with a fire protection rating of 11/2 hours, installed on opposite sides of the same opening in a fire wall, shall be deemed equivalent in fire protection rating to one 3-hour fire door.
Side-hinged and pivoted swinging doors shall be tested in accordance with NFPA 252 or UL 10C. After 5 minutes into the NFPA 252 test, the neutral pressure level in the furnace shall be established at 40 inches (1016 mm) or less above the sill.
Other types of doors, including swinging elevator doors, shall be tested in accordance with NFPA 252 or UL 10B. The pressure in the furnace shall be maintained as nearly equal to the atmospheric pressure as possible. Once established, the pressure shall be maintained during the entire test period.
Fire door assemblies located in corridor walls or smoke barrier walls having a fire-resistance rating in accordance with Table 715.3 shall be tested in accordance with NFPA 252 or UL 10C. Glazing material in any part of the door assembly, including transom lites and sidelites, shall be tested in accordance with NFPA 257 in accordance with Section 715.4. Fire door assemblies shall also meet the requirements for a smoke- and draft-control door assembly tested in accordance with UL 1784 with an artificial bottom seal installed across the full width of the bottom of the door assembly. The air leakage rate of the door assembly shall not exceed 3.0 cfm per square foot (0.01524 m3/slm2) of door opening at 0.10 inch (24.9 Pa) of water for both the ambient temperature and elevated temperature tests. Louvers shall be prohibited.
  Exceptions:
  1. Viewports that require a hole not larger than 1 inch (25 mm) in diameter through the door, have at least an 0.25-inch-thick (6.4 mm) glass disc and the holder is of metal that will not melt out where subject to temperatures of 1,700°F (927°C).
  2. Corridor door assemblies in occupancies of Group I-2 shall be in accordance with Section 407.3.1.
Fire door assemblies in vertical exit enclosures and exit passageways shall have a maximum transmitted temperature end point of not more than 450°F (232°C) above ambient at the end of 30 minutes of standard fire test exposure.
  Exception: The maximum transmitted temperature end point is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Fire-protection-rated glazing in excess of 100 square inches (0.065 m2) shall be permitted in fire door assemblies when tested in accordance with NFPA 252 as components of the door assemblies and not as glass lights, and shall have a maximum transmitted temperature end point of 450°F (232°C) in accordance with Section 715.3.4.
  Exception: The maximum transmitted temperature end point is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Fire door assemblies shall be labeled by an approved agency. The labels shall comply with NFPA 80, and shall be permanently affixed to the door or frame.
Fire doors shall be labeled showing the name of the manufacturer, the name of the third-party inspection agency, the fire protection rating and, where required for fire doors in exit enclosures by Section 715.3.4, the maximum transmitted temperature end point. Smoke and draft control doors complying with UL 1784 shall be labeled as such. Labels shall be approved and permanently affixed. The label shall be applied at the factory or location where fabrication and assembly are performed.
Oversized fire doors shall bear an oversized fire door label by an approved agency or shall be provided with a certificate of inspection furnished by an approved testing agency. When a certificate of inspection is furnished by an approved testing agency, the certificate shall state that the door conforms to the requirements of design, materials and construction, but has not been subjected to the fire test.
Smoke and draft control doors complying with UL 1784 shall be labeled in accordance with Section 715.3.5.1 and shall show the letter "S" on the fire rating label of the door. This marking shall indicate that the door and frame assembly are in compliance when listed or labeled gasketing is also installed.
Fire door frames shall be labeled showing the names of the manufacturer and the third-party inspection agency.
Fire-protection-rated glazing conforming to the opening protection requirements in Section 715.3 shall be permitted in fire door assemblies.
Wired glass used in fire doors shall comply with Table 715.4.3. Other fire-protection- rated glazing shall comply with the size limitations of NFPA 80.
  Exceptions:
  1. Fire-protection-rated glazing in fire doors located in fire walls shall be prohibited except that where serving as a horizontal exit, a self-closing swinging door shall be permitted to have a vision panel of not more than 100 square inches (0.065 m2) without a dimension exceeding 10 inches (254 mm).
  2. Fire-protection-rated glazing shall not be installed in fire doors having a 11/2-hour fire protection rating intended for installation in fire barriers, unless the glazing is not more than 100 square inches (0.065 m2) in area.

TABLE 715.4.3
FIRE DOOR AND FIRE SHUTTER FIRE PROTECTION RATINGS
OPENING FIRE
PROTECTION
RATING
MAXIMUM
AREA
(square inches)
MAXIMUM
HEIGHT
(inches)
MAXIMUM
WIDTH
(inches)
3 hours 0 0 0
11/2-hour doors in
exterior walls
0 0 0
1 and 11/2 hours 100 33 10
3/4 hour 1,296 54 54
Fire window
assemblies
1,296 54 54
For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm2.
Approved fire-protection-rated glazing used in fire doors in elevator and stairway shaft enclosures shall be so located as to furnish clear vision of the passageway or approach to the elevator or stairway.
Fire-protection-rated glazing shall bear a label or other identification showing the name of the manufacturer, the test standard and the fire protection rating. Such label or other identification shall be issued by an approved agency and shall be permanently affixed.
Fire-protection-rated glazing installed in fire doors or fire window assemblies in areas subject to human impact in hazardous locations shall comply with Chapter 24.
Fire doors shall be self-closing or automatic-closing in accordance with this section.
  Exception: Fire doors located in common walls separating sleeping units in Group R-1 shall be permitted without automatic-closing or self-closing devices.
Unless otherwise specifically permitted, single fire doors and both leaves of pairs of side-hinged swinging fire doors shall be provided with an active latch bolt that will secure the door when it is closed.
Automatic-closing fire doors installed in the following locations shall be automatic-closing by the actuation of smoke detectors installed in accordance with Section 907.10 or by loss of power to the smoke detector or hold-open device. Fire doors that are automatic-closing by smoke detection shall not have more than a 10-second delay before the door starts to close after the smoke detector is actuated.
  1. Doors installed across a corridor.
  2. Doors that protect openings in horizontal exits, exits or exit access corridors required to be of fire-resistance-rated construction.
  3. Doors that protect openings in walls required to be fire-resistance rated by Table 508.2.
  4. Doors installed in smoke barriers in accordance with Section 709.5.
  5. Doors installed in fire partitions in accordance with Section 708.6.
  6. Doors installed in a fire wall in accordance with Section 705.8.
Vertical sliding or vertical rolling steel fire doors in openings through which pedestrian's travel shall be heat activated or activated by smoke detectors with alarm verification.
Where fire shutters of the swinging type are installed in exterior openings, not less than one row in every three vertical rows shall be arranged to be readily opened from the outside, and shall be identified by distinguishing marks or letters not less than 6 inches (152 mm) high.
Where fire shutters of the rolling type are installed, such shutters shall include approved automatic-closing devices.
Glazing in fire window assemblies shall be fire protection rated in accordance with this section and Table 715.4. Glazing in fire doors shall comply with Section 715.3.6. Fire-protection-rated glazing installed as an opening protective in fire partitions, smoke barriers and fire barriers shall be tested in accordance with and shall meet the acceptance criteria of NFPA 257 for a fire protection rating of 45 minutes. Fire-protection-rated glazing shall also comply with NFPA 80. Fire-protection-rated glazing required in accordance with Section 704.12 for exterior wall opening protection shall be tested in accordance with and shall meet the acceptance criteria of NFPA 257 for a fire protection rating as required in Section 715.4.8.
  Exception: Wired glass in accordance with Section 715.4.3.

TABLE 715.4
FIRE WINDOW ASSEMBLY FIRE PROTECTION RATINGS
TYPE OF ASSEMBLY REQUIRED
ASSEMBLY
RATING
(hours)
MINIMUM FIRE
WINDOW
ASSEMBLY
RATING
(hours)
Interior walls:
Fire walls
Fire barriers and fire partitions

Smoke barriers

All
> 1
1
1

NPa
NPa
3/4
3/4
Exterior walls >1
1
11/2
3/4
Party walls All NPa
  1. Not permitted except as specified in Section 715.2.
NFPA 257 shall evaluate fire-protection-rated glazing under positive pressure. Within the first 10 minutes of a test, the pressure in the furnace shall be adjusted so at least two-thirds of the test specimen is above the neutral pressure plane, and the neutral pressure plane shall be maintained at that height for the balance of the test.
Nonsymmetrical fire-protection-rated glazing systems in fire partitions, fire barriers or in exterior walls with a fire separation of 5 feet (1524 mm) or less pursuant to Section 704 shall be tested with both faces exposed to the furnace, and the assigned fire protection rating shall be the shortest duration obtained from the two tests conducted in compliance with NFPA 257.
Steel window frame assemblies of 0.125-inch (3.2 mm) minimum solid section or of not less than nominal 0.048-inch-thick (1.2 mm) formed sheet steel members fabricated by pressing, mitering, riveting, interlocking or welding and having provision for glazing with 1/4-inch (6.4 mm) wired glass where securely installed in the building construction and glazed with 1/4-inch (6.4 mm) labeled wired glass shall be deemed to meet the requirements for a 3/4-hour fire window assembly. Wired glass panels shall conform to the size limitations set forth in Table 715.4.3.
Glazing other than wired glass in fire window assemblies shall be fire-protection-rated glazing installed in accordance with and complying with the size limitations set forth in NFPA 80.
Fire-protection-rated glazing shall be in the fixed position or be automatic-closing and shall be installed in approved frames.
Metal mullions that exceed a nominal height of 12 feet (3658 mm) shall be protected with materials to afford the same fire-resistance rating as required for the wall construction in which the protective is located.
Fire-protection-rated glazing used in fire window assemblies located in fire partitions and fire barriers shall be limited to use in assemblies with a maximum fire-resistance rating of 1 hour in accordance with this section.
Fire-protection-rated glazing shall be limited to fire partitions designed in accordance with Section 708 and fire barriers utilized in the applications set forth in Sections 706.3.5 and 706.3.6 where the fire-resistance rating does not exceed 1 hour.
The total area of windows shall not exceed 25 percent of the area of a common wall with any room.
Exterior openings, other than doors, required to be protected by Section 704.12, where located in a wall required by Table 602 to have a fire-resistance rating of greater than 1 hour, shall be protected with an assembly having a fire protection rating of not less than 1 1/2 hours. Exterior openings required to be protected by Section 704.8, where located in a wall required by Table 602 to have a fire-resistance rating of 1 hour, shall be protected with an assembly having a fire protection rating of not less than 3/4 hour. Exterior openings required to be protected by Section 704.9 or 704.10 shall be protected with an assembly having a fire protection rating of not less than 3/4 hour. Openings in nonfire-resistance-rated exterior wall assemblies that require protection in accordance with Section 704.8, 704.9 or 704.10 shall have a fire protection rating of not less than 3/4 hour.
Fire-protection-rated glazing shall bear a label or other identification showing the name of the manufacturer, the test standard, and the fire protection rating. Such label or identification shall be issued by an approved agency and shall be permanently affixed.
The provisions of this section shall govern the protection of ducts and air transfer openings in fire-resistance-rated assemblies.
Ducts and air transfer openings that penetrate fire-resistance-rated assemblies and are not required by this section to have dampers shall comply with the requirements of Section 712.
Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling dampers located within air distribution and smoke control systems shall be installed in accordance with the requirements of this section, the New York City Mechanical Code, the manufacturer's installation instructions and listing.
Where the installation of a fire damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized.
Provisions for operation by remote control of combination fire/smoke dampers shall be in accordance with Section 607.3.1.1 of the New York City Mechanical Code.
Fire dampers for hazardous exhaust duct systems shall comply with the New York City Mechanical Code.
Smoke dampers in supply airhandling systems having a capacity equal to or greater than 15,000 cfm (7.1 m3/s) shall be installed in accordance with Section 607.2.3 of the New York City Mechanical Code.
Dampers shall be listed and bear the label of an approved testing agency indicating compliance with the standards in this section. Fire dampers shall comply with the requirements of UL 555. Only fire dampers labeled for use in dynamic systems shall be installed in heating, ventilation and air-conditioning systems designed to operate with fans on during a fire. Smoke dampers shall comply with the requirements of UL 555S. Combination fire/smoke dampers shall comply with the requirements of both UL 555 and UL 555S. Ceiling radiation dampers shall comply with the requirements of UL 555C.
Fire dampers shall have the minimum fire protection rating specified in Table 716.3.1 for the type of penetration.

TABLE 716.3.1
FIRE DAMPER RATING
TYPE OF
PENETRATION
MINIMUM DAMPER RATING
(hours)
Less than 3-hour fire-
resistance-rated assemblies
1.5
3-hour or greater fire-
resistance-rated assemblies
3
The fire damper actuating device shall meet one of the following requirements:
  1. The operating temperature shall be approximately 50°F (10°C) above the normal temperature within the duct system, but not less than 160°F (71°C).
  2. The operating temperature shall be not more than 286°F (141°C) where located in a smoke control system complying with Section 909.
  3. Where a combination fire/smoke damper is located in a smoke control system complying with Section 909, the operating temperature rating shall be approximately 50°F (10°C) above the maximum smoke control system designed operating temperature, or a maximum temperature of 350°F (177°C). The temperature shall not exceed the UL 555S degradation test temperature rating for a combination fire/smoke damper.
Smoke damper leakage ratings shall not be less than Class II. Elevated temperature ratings shall not be less than 250°F (121°C).
The smoke damper shall close upon actuation of a listed smoke detector or detectors installed in accordance with Section 907.10 and one of the following methods, as applicable:
  1. Where a damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet (1524 mm) of the damper with no air outlets or inlets between the detector and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate.
  2. Where a damper is installed above smoke barrier doors in a smoke barrier, a spot-type detector listed for releasing service shall be installed on either side of the smoke barrier door opening.
  3. Where a damper is installed within an unducted opening in a wall, a spot-type detector listed for releasing service shall be installed within 5 feet (1524 mm) horizontally of the damper.
  4. Where a damper is installed in a corridor wall, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor.
  5. Where a total-coverage smoke detector system is provided within areas served by a heating, ventilation and air-conditioning (HVAC) system, dampers shall be permitted to be controlled by the smoke detection system.
  6. Smoke dampers that are part of an engineered smoke control system shall be controlled in accordance with Section 607.3.2.1 of the New York City Mechanical Code.
Fire and smoke dampers shall be provided with an approved means of access, large enough to permit inspection and maintenance of the damper and its operating parts. The access shall not affect the integrity of fire-resistance-rated assemblies. The access openings shall not reduce the fire-resistance rating of the assembly. Access points shall be permanently identified on the exterior by a label having letters not less than 0.5 inch (12.7 mm) in height reading: SMOKE DAMPER or FIRE DAMPER followed by an identification marking that is individual and unique to the damper accessed.
Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling radiation dampers shall be provided as specified in this section. Where an assembly is required to have both fire dampers and smoke dampers, combination fire/smoke dampers or a fire damper and a smoke damper shall be required.
  Exceptions:
  1. Smoke dampers shall not be required on air systems other than where necessary for the proper function of that system where the system is designed specifically to:
  1.1. Function as an engineered smoke-control system, including the provision of continuous air movement with the air-handling system;
  1.2. Provide air to other areas of the building during a fire emergency; or
  1.3. Provide pressure differentials during a fire emergency.
  2. Smoke dampers shall not be required to be located within a prescribed distance of a fire rated enclosure where isolation smoke dampers are used in air-handling equipment.
  3. Smoke dampers shall not be required in ducts where the air continues to move and the air-handling system installed is arranged to prevent recirculation of exhaust or return air under fire emergency conditions
Ducts and air transfer openings permitted in fire walls in accordance with Section 705.11 shall be protected with approved fire dampers and smoke dampers installed in accordance with their listing.
Duct and air transfer openings of fire barriers shall be protected with approved fire dampers installed in accordance with their listing. In addition, smoke dampers shall be installed in penetrations of public corridor walls in accordance with Section 716.5.4.1.
  Exception: Fire dampers are not required at penetrations of fire barriers where any of the following apply:
  1. Penetrations are tested in accordance with ASTM E 119 as part of the fire-resistance-rated assembly.
  2. Ducts are used as part of an approved smoke control system in accordance with Section 716.2.1 and Section 909.
  3. Such walls are penetrated by ducted HVAC systems, have a required fire-resistance rating of 1 hour or less, are in areas of other than Group H and are in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. For the purposes of this exception, a ducted HVAC system shall be a duct system for conveying supply, return or exhaust air as part of the structure's HVAC system. Such a duct system shall be constructed of sheet steel not less than 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals.
A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a public corridor wall constructed as a fire barrier.
  Exceptions:
  1. Smoke dampers are not required where the building is equipped throughout with an approved smoke control system in accordance with Section 909, and smoke dampers are not necessary for the operation and control of the system.
  2. Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than 0.019-inch (0.48 mm) in thickness and there are no openings serving the corridor.
  3. Smoke dampers are not required in corridor penetrations in Group R-2 buildings and spaces.
Ducts and air transfer openings shall not penetrate a shaft serving as an exit enclosure except as permitted by Section 1019.1.2.
*Section BC 716.5.3 was amended by: Local Law 8 of 2008. This law has an effective date of July 1, 2008.
Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing.
  Exceptions:
  1. Fire dampers are not required at penetrations of shafts where:
  1.1. Steel exhaust subducts are extended at least 22 inches (559 mm) vertically in exhaust shafts provided there is a continuous airflow upward to the outside, or
  1.2. Penetrations are tested in accordance with ASTM E 119 as part of the rated assembly, or
  1.3. Ducts are used as part of an approved smoke control system designed and installed in accordance with Section 909, and where the fire damper will interfere with the operation of the smoke control system, or
  1.4. The penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.
  2. In Group B occupancies, equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, smoke dampers are not required at penetrations of shafts where:
  2.1. Bathroom and toilet room exhaust openings with steel exhaust subducts, having a wall thickness of at least 0.019 inches (0.48 mm) that extend at least 22 inches (559 mm) vertically and the exhaust fan at the upper terminus, powered continuously in accordance with the provisions of Section 909.11, maintains airflow upward to the outside, or
  2.2. Ducts are used as part of an approved smoke control system, designed and installed in accordance with Section 909, and where the smoke damper will interfere with the operation of the smoke control system, or
  3. Smoke dampers are not required at penetration of exhaust or supply shafts in parking garages that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.
  4. Fire dampers and smoke dampers shall not be required at a shaft where the shaft is acting as an extension of the mechanical equipment room that it serves and the shaft and mechanical equipment room maintain fire and smoke separation required by the greater of the two spaces from the occupied portions of the building and meet the requirements of Section 707.11.
  5. Smoke dampers shall not be required to be located within a prescribed distance of a fire rated enclosure where isolation smoke dampers are used in air-handling equipment.
  6. Smoke dampers shall not be required in ducts where the air continues to move and the air-handling system installed is arranged to prevent recirculation of exhaust or return air under fire emergency conditions.
  7. Smoke dampers shall not be required in exhaust ducts or shafts where the exhaust fan is maintained in operation during occupancy, such as in bathroom and toilet room exhausts.
Shafts that constitute air ducts shall be limited in accordance with Section 607.5.5.2 of the New York City Mechanical Code.
Duct penetrations in fire partitions shall be protected with approved fire dampers installed in accordance with their listing.
  Exceptions: In occupancies other than Group H, fire dampers are not required where any of the following apply:
  1. The partitions are tenant separation and interior corridor walls in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and the duct is protected as a through penetration in accordance with Section 712.
  2. The duct system is constructed of approved materials in accordance with the New York City Mechanical Code and the duct penetrating the wall meets all of the following minimum requirements:
  2.1. The duct shall not exceed 100 square inches (0.06 m2).
  2.2. The duct shall be constructed of steel a minimum of 0.0217 inch (0.55 mm) in thickness.
  2.3. The duct shall not have openings that communicate the corridor with adjacent spaces or rooms.
  2.4. The duct shall be installed above a ceiling.
  2.5. The duct shall not terminate at a wall register in the fire-resistance-rated wall.
  2.6. A minimum 12-inch-long (0.30 m) by 0.060-inch-thick (1.52 mm) steel sleeve shall be centered in each duct opening. The sleeve shall be secured to both sides of the wall and all four sides of the sleeve with minimum 11/2-inch by 11/2-inch by 0.060-inch (0.038 m by 0.038 m by 1.52 mm) steel retaining angles. The retaining angles shall be secured to the sleeve and the wall with No. 10 (M5) screws. The annular space between the steel sleeve and wall opening shall be filled with rock (mineral) wool batting or approved equivalent on all sides.
A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a smoke barrier. Smoke dampers and smoke damper actuation methods shall comply with Section 716.3.2.1.
  Exception: Smoke dampers are not required where the openings in ducts are limited to a single smoke compartment and the ducts are constructed of steel.
Penetrations by ducts and air transfer openings of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected by a shaft enclosure that complies with Section 707 or shall comply with this section.
In occupancies other than Groups I-2 and I-3, a duct and air transfer opening system constructed of approved materials in accordance with the New York City Mechanical Code that penetrates a fire-resistance-rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection provided a fire damper is installed at the floor line and the penetration is fire blocked in accordance with Section 717.2.5.
  Exception: A duct serving a dwelling unit is permitted to penetrate three floors or less without a fire damper at each floor provided it meets all of the following requirements.
  1. The duct shall be contained and located within the cavity of a wall and shall be constructed of steel not less than 0.019 inch (0.48 mm) (26 gage) in thickness.
  2. The duct shall open into only one dwelling unit and the duct system shall be continuous from the unit to the exterior of the building.
  3. The duct shall not exceed 5-inch (127 mm) nominal diameter and the total area of such ducts shall not exceed 100 square inches (0.065 m2) in any 100 square feet (9.3 m2) of floor area.
  4. The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature conditions under a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.
  5. Grille openings located in a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with a ceiling radiation damper in accordance with Section 716.6.2.
Where duct systems constructed of approved materials in accordance with the New York City Mechanical Code penetrate a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly, shaft enclosure protection is not required provided an approved ceiling radiation damper and firestopping is installed at the ceiling line. Where a duct is not attached to a diffuser that penetrates a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly, shaft enclosure protection is not required provided an approved ceiling radiation damper and firestopping is installed at the ceiling line. Ceiling radiation dampers shall be tested in accordance with UL 555C and constructed in accordance with the details listed in a fire-resistance-rated assembly or shall be labeled to function as a heat barrier for air-handling outlet/inlet penetrations in the ceiling of a fire-resistance-rated assembly. Ceiling radiation dampers shall not be required where ASTM E 119 fire tests have shown that ceiling radiation dampers are not necessary in order to maintain the fire-resistance rating of the assembly. Ceiling radiation dampers shall not be required where exhaust duct penetrations are protected in accordance with Section 712.4.2 and the exhaust ducts are located within the cavity of a wall, and do not pass through another dwelling unit or tenant space.
Duct systems constructed of approved materials in accordance with the New York City Mechanical Code that penetrate non-fire-resistance-rated floor assemblies and that connect not more than two stories are permitted without shaft enclosure protection provided that the annular space between the assembly and the penetrating duct is filled with an approved noncombustible material to resist the free passage of flame and the products of combustion. Duct systems constructed of approved materials in accordance with the New York City Mechanical Code that penetrate non-fire-resistance-rated floor assemblies and that connect not more than three stories are permitted without shaft enclosure protection provided that the annular space between the assembly and the penetrating duct is filled with an approved noncombustible material to resist the free passage of flame and the products of combustion, and a fire damper is installed at each floor line.
  Exception: Fire dampers are not required in ducts within individual residential dwelling units.
Flexible ducts and air connectors shall not pass through any fire-resistance-rated assembly. Flexible air connectors shall not pass through any wall, floor or ceiling.
Fire blocking and draft stopping shall be installed in combustible and noncombustible concealed locations in accordance with this section. Fire blocking shall comply with Section 717.2. Draft stopping in floor/ceiling spaces and attic spaces shall comply with Sections 717.3 and 717.4, respectively. The permitted use of combustible materials in concealed spaces of noncombustible buildings shall be limited to the applications indicated in Section 717.5. Installations of fire blocking and draft stopping shall comply with the special inspection requirements of Chapter 17.
  Exception: Concealed spaces that are sprinklered in accordance with Chapter 9 or are constructed as a shaft.
In combustible and noncombustible construction, fire blocking shall be installed to cut off concealed draft openings (both vertical and horizontal) and shall form an effective barrier between floors, between a top story and a roof or attic space. Fire blocking shall be installed in the locations specified in Sections 717.2.2 through 717.2.7.
Fire blocking shall consist of 2-inch (51 mm) nominal lumber or two thicknesses of 1-inch (25 mm) nominal lumber with broken lap joints or one thickness of 0.719-inch (18.3 mm) wood structural panel with joints backed by 0.719-inch (18.3 mm) wood structural panel or one thickness of 0.75-inch (19 mm) particleboard with joints backed by 0.75-inch (19 mm) particleboard. Gypsum board, cement fiber board, batts or blankets of mineral wool or glass fiber or other approved materials installed in such a manner as to be securely retained in place shall be permitted as an acceptable fire block. Batts or blankets of mineral or glass fiber or other approved nonrigid materials shall be permitted for compliance with the 10-foot (3048 mm) horizontal fire blocking in walls constructed using parallel rows of studs or staggered studs. Loose-fill insulation material shall not be used as a fire block unless specifically tested in the form and manner intended for use to demonstrate its ability to remain in place and to retard the spread of fire and hot gases. The integrity of fire blocks shall be maintained.
Batts or blankets of mineral or glass fiber or other approved nonrigid materials shall be allowed as fire blocking in walls constructed using parallel rows of studs or staggered studs.
Fire blocking shall be provided in concealed spaces of stud walls and partitions, including furred spaces, and parallel rows of studs or staggered studs, as follows:
  1. Vertically at the ceiling and floor levels.
  2. Horizontally at intervals not exceeding 10 feet (3048 mm).
Fire blocking shall be provided at interconnections between concealed vertical stud wall or partition spaces and concealed horizontal spaces created by an assembly of floor joists or trusses, and between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings, cove ceilings and similar locations.
Fire blocking shall be provided in concealed spaces between stair stringers at the top and bottom of the run. Enclosed spaces under stairs shall also comply with Section 1019.1.5.
Where annular space protection is provided in accordance with Exception 6 of Section 707.2, Exception 1 of Section 712.4.2, or Section 712.4.3, fire blocking shall be installed at openings around vents, pipes, ducts, chimneys and fireplaces at ceiling and floor levels, with an approved material to resist the free passage of flame and the products of combustion. Factory-built chimneys and fireplaces shall be fire blocked in accordance with UL 103 and UL 127.
Fire blocking shall be installed within concealed spaces of exterior wall finish and other exterior architectural elements where permitted to be of combustible construction in Section 1406 or where erected with combustible frames, at maximum intervals of 20 feet (6096 mm). If non-continuous, such elements shall have closed ends, with at least 4 inches (102 mm) of separation between sections.
  Exceptions:
  1. Fire blocking of cornices is not required in single-family dwellings. Fire blocking of cornices of a two-family dwelling is required only at the line of dwelling unit separation.
  2. Fire blocking shall not be required where installed on noncombustible framing and the face of the exterior wall finish exposed to the concealed space is covered by one of the following materials:
  2.1. Aluminum having a minimum thickness of 0.019 inch (0.5 mm).
  2.2. Corrosion-resistant steel having a base metal thickness not less than 0.016 inch (0.4 mm) at any point.
  2.3. Other approved noncombustible materials.
Where wood sleepers are used for laying wood flooring on masonry or concrete fire-resistance-rated floors, the space between the floor slab and the underside of the wood flooring shall be filled with an approved material to resist the free passage of flame and products of combustion or fire blocked in such a manner that there will be no open spaces under the flooring that will exceed 20 square feet (1.86 m2) in area and such space shall be filled solidly under permanent partitions so that there is no communication under the flooring between adjoining rooms.
  Exceptions:
  1. Fire blocking is not required for slab-on-grade floors in gymnasiums.
  2. Fire blocking is required only at the juncture of each alternate lane and at the ends of each lane in a bowling facility.
In combustible and noncombustible construction, draft stopping shall be installed to subdivide floor/ceiling assemblies in the locations prescribed in Sections 717.3.2 through 717.3.3.
In noncombustible construction, draft stopping shall be of noncombustible materials. In combustible construction, draft stopping materials shall not be less than 0.5-inch (12.7 mm) gypsum board, 0.375-inch (9.5 mm) wood structural panel, 0.375-inch (9.5 mm) particleboard or other approved materials adequately supported. The integrity of draft stops shall be maintained.
Draft stopping shall be provided in floor/ceiling spaces in Group R buildings. Draft stopping shall be located above and in line with the dwelling unit separations.
  Exceptions:
  1. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.2, provided that automatic sprinklers are also installed in the combustible concealed spaces.
  3. Where laminated wood I-joist assemblies are used, the space between the ceiling and the floor or roof above shall be divided into approximately equal areas not greater than 500 square feet (46.5 m2).
  4. Draft stopping shall not be required where the structural members within the concealed ceiling space are individually protected on all sides for their full length with materials having the required fire resistance rating.
In occupancies other than Group R, draft stopping shall be installed so that horizontal floor areas do not exceed 3,000 square feet (279 m2).
  Exceptions:
  1. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. Draft stopping shall not be required where the structural members within the concealed ceiling space are individually protected on all sides for their full length with materials having the required fire resistance rating.
In combustible and noncombustible construction, draft stopping shall be installed to subdivide attic spaces and concealed roof spaces in the locations prescribed in Sections 717.4.2 and 717.4.3. Ventilation of concealed roof spaces shall be maintained in accordance with Section 1203.2.
Materials utilized for draft stopping of attic spaces shall comply with Section 717.3.1.
Openings in draft stop partitions provided in accordance with Section 1209.2 shall be protected by self-closing doors with automatic latches constructed as required for the partitions.
Draft stopping shall be provided in attics, mansards, overhangs or other concealed roof spaces of Group R-2 buildings with three or more dwelling units and in all Group R-1 buildings. Draft stopping shall be installed above, and in line with, dwelling unit separation walls that do not extend to the underside of the roof sheathing above.
  Exceptions:
  1. Draft stopping shall not be required where the structural members within the concealed attic space are individually protected on all sides for their full length with materials having the required fire resistance rating.
  2. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  3. In occupancies in Group R-2 that do not exceed four stories in height, the attic space shall be subdivided by draft stops into areas not exceeding 3,000 square feet (279 m2) or above every two dwelling units, whichever is smaller.
  4. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.2, provided that automatic sprinklers are also installed in the combustible concealed spaces.
  5. Where laminated wood I-joist assemblies are used, the space between the ceiling and the floor or roof above shall be divided into approximately equal areas not greater than 500 square feet (46.5 m2).
Draft stopping shall be installed in attics and concealed roof spaces, such that any horizontal area does not exceed 3,000 square feet (279 m2).
  Exceptions:
  1. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. Draft stopping shall not be required where the structural members within the concealed attic space are individually protected on all sides for their full length with materials having the required fire resistance rating.
  3. Where laminated wood I-joist assemblies are used, the space between the ceiling and the floor or roof above shall be divided into approximately equal areas not greater than 500 square feet (46.5 m2).
Combustibles shall not be permitted in concealed spaces of buildings of Type I or II construction.
  Exceptions:
  1. Combustible materials in accordance with Section 603.
  2. Combustible materials complying with Section 602 of the New York City Mechanical Code.
  3. Class A interior finish materials.
  4. Combustible piping within partitions or enclosed shafts installed in accordance with the provisions of this code. Combustible piping shall be permitted within concealed ceiling spaces where installed in accordance with the New York City Mechanical Code and the New York City Plumbing Code.
The minimum thickness of gypsum plaster or portland cement plaster used in a fire-resistance-rated system shall be determined by the prescribed fire tests. The plaster thickness shall be measured from the face of the lath where applied to gypsum lath or metal lath.
For fire-resistance purposes, 0.5 inch (12.7 mm) of unsanded gypsum plaster shall be deemed equivalent to 0.75 inch (19.1 mm) of one-to-three gypsum sand plaster or 1 inch (25 mm) of portland cement sand plaster.
In buildings of Type I and II construction, plaster shall be applied directly on concrete or masonry or on approved noncombustible plastering base and furring.
Plaster protection more than 1 inch (25 mm) in thickness shall be reinforced with an additional layer of approved lath embedded at least 0.75 inch (19.1 mm) from the outer surface and fixed securely in place.
  Exception: Solid plaster partitions or where otherwise determined by fire tests.
In reinforced concrete construction, gypsum plaster or portland cement plaster is permitted to be substituted for 0.5 inch (12.7 mm) of the required poured concrete protection, except that a minimum thickness of 0.375 inch (9.5 mm) of poured concrete shall be provided in reinforced concrete floors and 1 inch (25 mm) in reinforced concrete columns in addition to the plaster finish. The concrete base shall be prepared in accordance with Section 2510.7.
Insulating materials, including facings such as vapor retarders and vapor- permeable membranes, similar coverings, and all layers of single and multilayer reflective foil insulations, shall comply with the requirements of this section. Where a flame spread index or a smoke-development index is specified in this section, such index shall be determined in accordance with ASTM E 84. Any material that is subject to an increase in flame spread index or smoke-development index beyond the limits herein established through the effects of age, moisture, or other atmospheric conditions shall not be permitted. Fiberboard insulation shall comply with Chapter 23 and the requirements of this section. Foam plastic insulation shall comply with Chapter 26 and the requirements of this section. Duct and pipe coverings and linings in plenums shall comply with the New York City Mechanical Code.
  Exceptions: Exterior Insulation Finish Systems (EIFS) shall comply with Chapter 14 and Chapter 26.
Insulating materials used in noncombustible construction must either:
  1. Satisfactorily pass a test for determining non-combustibility of elementary materials, based on the test procedures of ASTM E 136; or
  2. Have a flame spread index not greater than 25, a smoke-development index not greater than 50, and be without evidence of continued progressive combustion when tested in accordance with ASTM E 84.
Insulating materials used in combustible construction shall have a flame spread index not greater than 25, a smoke-development index not greater than 450, and be without evidence of continuous progressive combustion when tested in accordance with ASTM E 84.
Insulating materials, where concealed as installed in buildings of any type construction, shall comply with Sections 719.1, 719.1.1 and 719.1.2. Concealed insulation shall be separated from the building interior by a thermal barrier consisting of at least 1/2-inch (12.7 mm) thick gypsum wallboard or approved equivalent.
  Exception: Cellulose loose-fill insulation that is not spray applied, complying with the requirements of Section 719.6, shall only be required to meet the smoke-development index of not more than 450.
Where such materials are installed in concealed spaces in buildings of Type III, IV or V construction, the flame spread and smoke-development limits do not apply to facings, coverings, and layers of reflective foil insulation that are installed behind and in substantial contact with the unexposed surface of the ceiling, wall or floor finish.
Insulation materials, where exposed as installed in buildings of any type construction, shall have a flame spread index of not more than 25 and a smoke-development index of not more than 50.
  Exception: Cellulose loose-fill insulation that is not spray applied complying with the requirements of Section 719.6 shall only be required to meet the smoke-development index of not more than 50.
Exposed insulation materials installed on attic floors shall have a critical radiant flux of not less than 0.12 watt per square centimeter when tested in accordance with ASTM E 970.
Upon exposure to fire, insulating materials used in building interiors, including facings such as vapor retarders and vapor permeable membranes, similar coverings, and all layers of single and multi-layer reflective foil insulation, shall not produce products of decomposition or combustion that are more toxic in point of concentration than those given off by wood or paper when decomposing or burning under comparable conditions in accordance with test standards approved by the department.
Loose-fill insulation materials that cannot be mounted in the ASTM E 84 apparatus without a screen or artificial supports shall comply with the flame spread and smoke-developed limits of Sections 719.2 and 719.3 when tested in accordance with CAN/ULC S102.2.
  Exception: Cellulose loose-fill insulation shall not be required to comply with this test method, provided such insulation complies with the requirements of Section 719.6.
The use of combustible roof insulation not complying with Sections 719.2 and 719.3 shall be permitted in any type construction provided it is applied on top of roof decking or slab and is covered with approved roof coverings directly applied thereto.
Cellulose loose-fill insulation shall comply with CPSC 16 CFR, Part 1209 and CPSC 16 CFR, Part 1404. Each package of such insulating material shall be clearly labeled in accordance with CPSC 16 CFR, Part 1209 and CPSC 16 CFR, Part 1404.
Insulation and covering on pipe and tubing shall comply with the requirements of the New York City Mechanical Code.
The provisions of this section contain prescriptive details of fire-resistance-rated building elements. The materials of construction listed in Tables 720.1(1), 720.1(2), and 720.1(3) shall be assumed to have the fire-resistance ratings prescribed therein. Where materials that change the capacity for heat dissipation are incorporated into a fire-resistance-rated assembly, fire test results or other substantiating data shall be made available to the commissioner to show that the required fire-resistance-rating time period is not reduced.

TABLE 720.1(1)
MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALSm
STRUCTURAL
PARTS TO BE
PROTECTED
ITEM
NUMBER
INSULATING MATERIAL USED MINIMUM THICKNESS OF
IN SULATING MATERIAL
FOR THE FOLLOWING
FIRE-RESISTANCE
PERIODS (inches)
4
hour
3
hour
2
hour
1
hour
  1. Steel columns
    and all of
    primary trusses
1-1.1 Carbonate, lightweight and sand-lightweight aggregate concrete, members 6''× 6'' or greater (not including sandstone, granite and siliceous gravel).a 21/2 2 11/2 1
1-1.2 Carbonate, lightweight and sand-lightweight aggregate concrete, members 8''× 8'' or greater (not including sandstone, granite and siliceous gravel).a 2 11/2 1 1
1-1.3 Carbonate, lightweight and sand-lightweight aggregate concrete, members 12'' × 12''or greater (not including sandstone, granite and siliceous gravel).a 11/2 1 1 1
1-1.4 Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 6''× 6'' or greater.a 3 2 11/2 1
1-1.5 Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 8''× 8'' or greater.a 21/2 2 1 1
1-1.6 Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 12'' × 12'' or greater.a 2 1 1 1
1-2.1 Clay or shale brick with brick and mortar fill.a 33/4 - - 21/4
1-3.1 4'' hollow clay tile in two 2'' layers; 1/2'' mortar between tile and column; 3/8'' metal mesh 0.046'' wire diameter in horizontal joints; tile fill.a 4 - - -
1-3.2 2'' hollow clay tile; 3/4''mortar between tile and column; 3/8''metal mesh 0.046'' wire diameter in horizontal joints; limestone concrete fill;a plastered with 3/4'' gypsum plaster. 3 - - -
1-3.3 2'' hollow clay tile with outside wire ties 0.08'' diameter at each course of tile or 3/8''metal mesh 0.046'' diameter wire in horizontal joints; limestone or trap-rock concrete fill 1 extending 1'' outside column on all sides. - - 3 -
1-3.4 2'' hollow clay tile with outside wire ties 0.08'' diameter at each course of tile with or without concrete fill; 3/4'' mortar between tile and column. - - - 2
1-4.1 Cement plaster over metal lath wire tied to 3/4" cold-rolled vertical channels with 0.049'' (No. 18 B.W. gage) wire ties spaced 3'' to 6'' on center. Plaster mixed 1:2 1/2 by volume, cement to sand. - - 21/2b 7/8
1-5.1 Vermiculite concrete, 1:4 mix by volume over paperbacked wire fabric lath wrapped directly around column with additional 2''× 2'' 0.065"/0.065'' (No. 16/16 B.W. gage) wire fabric placed 3/4'' from outer concrete surface. Wire fabric tied with 0.049'' (No. 18 B.W. gage) wire spaced 6''on center for inner layer and 2''on center for outer layer. 2 - - -
1-6.1 Perlite or vermiculite gypsum plaster over metal lath wrapped around column and furred 11/4'' from column flanges. Sheets lapped at ends and tied at 6'' intervals with 0.049'' (No. 18 B.W. gage) tie wire. Plaster pushed through to flanges. 11/2 1 - -
1-6.2 Perlite or vermiculite gypsum plaster over self-furring metal lath wrapped directly around column, lapped 1''and tied at 6''intervals with 0.049'' (No. 18 B.W. gage) wire. 13/4 13/8 1 -
1-6.3 Perlite or vermiculite gypsum plaster on metal lath applied to 3/4'' cold-rolled channels spaced 24'' apart vertically and wrapped flatwise around column. 11/2 - - -
1-6.4 Perlite or vermiculite gypsum plaster over two layers of 1/2'' plain full-length gypsum lath applied tight to column flanges. Lath wrapped with 1'' hexagonal mesh of No. 20 gage wire and tied with doubled 0.035'' diameter (No. 18 B.W. gage) wire ties spaced 23'' on center. For three-coat work, the plaster mix for the second coat shall not exceed 100 pounds of gypsum to 21/2 cubic feet of aggregate for the 3-hour system. 21/2 2 - -
1-6.5 Perlite or vermiculate gypsum plaster over one layer of 1/2'' plain full-length gypsum lath applied tight to column flanges. Lath tied with doubled 0.049'' (No. 18 B.W.gage) wire ties spaced 23'' on center and scratch coat wrapped with 1'' hexagonal mesh 0.035'' (No. 20 B.W. gage) wire fabric. For three-coat work, the plaster mix for the second coat shall not exceed 100 pounds of gypsum to 21/2 cubic feet of aggregate. - 2 - -
1-7.1 Multiple layers of 1/2'' gypsum wallboardc adhesivelyd secured to column flanges and successive layers. Wallboard applied without horizontal joints. Corner edges of each layer staggered. Wallboard layer below outer layer secured to column with doubled 0.049'' (No. 18 B.W. gage) steel wire ties spaced 15'' on center. Exposed corners taped and treated. - - 2 1
1-7.2 Three layers of 5/8'' Type X gypsum wallboard.c First and second layer held in place by 1/8'' diameter by 13/8'' long ring shank nails with 5/16'' diameter heads spaced 24''on center at corners. Middle layer also secured with metal straps at mid-height and 18'' from each end, and by metal corner bead at each corner held by the metal straps. Third layer attached to corner bead with 1" long gypsum wallboard screws spaced 12''on center. - - 17/8 -
1-7.3 Three layers of 5/8'' Type X gypsum wallboard,c each layer screw attached to 15/8''steel studs 0.018'' thick (No. 25 carbon sheet steel gage) at each corner of column.Middle layer also secured with 0.049''(No. 18 B.W. gage) double-strand steel wire ties, 24''on center. Screws are No. 6 by 1" spaced 24''on center for inner layer, No. 6 by 15/8''spaced 12''on center for middle layer and No. 8 by 21/4''spaced 12''on center for outer layer. - 17/8 - -
1-8.1 Wood-fibered gypsum plaster mixed 1:1 by weight gypsum-to-sand aggregate applied over metal lath.Lath lapped 1''and tied 6''on center at all end, edges and spacers with 0.049''(No. 18 B.W. gage) steel tie wires. Lath applied over 1/2''spacers made of 3/4''furring channel with 2''legs bent around each corner. Spacers located 1''from top and bottom of member and a maximum of 40''on center and wire tied with a single strand of 0.049''(No. 18 B.W. gage) steel tie wires. Corner bead tied to the lath at 6''on center along each corner to provide plaster thickness. - - 15/8 -
  1. Webs or flanges of steel beams and girders
2-1.1 Carbonate, lightweight and sand-lightweight aggregate concrete (not including sandstone, granite and siliceous gravel) with 3''or finer metal mesh placed 1''from the finished surface anchored to the top flange and providing not less than 0.025 square inch of steel area per foot in each direction. 2 11/2 1 1
2-1.2 Siliceous aggregate concrete and concrete excluded in Item 2-1.1 with 3''or finer metal mesh placed 1''from the finished surface anchored to the top flange and providing not less than 0.025 square inch of steel area per foot in each direction. 21/2 2 11/2 1
2-2.1 Cement plaster on metal lath attached to 3/4''cold-rolled channels with 0.049''(No. 18 B.W. gage) wire ties spaced 3''to 6''on center. Plaster mixed 1:2 1/2 by volume, cement to sand. - - 21/2b 7/8
2-3.1 Vermiculite gypsum plaster on a metal lath cage, wire tied to 0.165'' diameter (No. 8 B.W. gage) steel wire hangers wrapped around beam and spaced 16'' on center. Metal lath ties spaced approximately 5'' on center at cage sides and bottom. - 7/8 - -
2-4.1 Two layers of 5/8''Type X gypsum wallboardc are attached to U-shaped bracketsspaced 24''on center. 0.018''thick (No. 25 carbon sheet steel gage) 15/8''deep by 1''galvanized steel runner channels are first installed parallel to and on each side of the top beam flange to provide a1/2''clearance to the flange. The channel runners are attached to steel deck or concrete floor construction with approved fasteners spaced 12''on center. U-shaped brackets are formed from members identical to the channel runners. At the bent portion of the U-shaped bracket, the flanges of the channel are cut out so that 15/8''deep corner channels can be inserted without attachment parallel to each side of the lower flange.
As an alternate, 0.021''thick (No. 24 carbon sheet steel gage) 1''× 2''runner and corner angles may be used in lieu of channels, and the web cutouts in the U-shaped brackets may be omitted. Each angle is attached to the bracket with1/2''-long No. 8 self-drilling screws. The vertical legs of the U-shaped bracket are attached to the runners with one1/2''long No. 8 self-drilling screw. The completed steel framing provides a 21/8''and 11/2''space between the inner layer of wallboard and the sides and bottom of the steel beam, respectively. The inner layer of wallboard is attached to the top runners and bottom corner channels or corner angles with 11/4''-long No. 6 self-drilling screws spaced 16''on center. The outer layer of wallboard is applied with 13/4''-long No. 6 self-drilling screws spaced 8''on center. The bottom corners are reinforced with metal corner beads.
- - 11/4 -
2-4.2 Three layers of 5/8'' Type X gypsum wallboardc attached to a steel suspension system as described immediately above utilizing the 0.018'' thick (No. 25 carbon sheet steel gage) 1'' × 2'' lower corner angles. The framing is located so that a 21/8'' and 2'' space is provided between the inner layer of wallboard and the sides and bottom of the beam, respectively. The first two layers of wallboard are attached as described immediately above. A layer of 0.035'' thick (No. 20 B.W. gage) 1'' hexagonal galvanized wire mesh is applied under the soffit of the middle layer and up the sides approximately 2''. The mesh is held in position with the No. 6 15/8''-long screws installed in the vertical leg of the bottom corner angles. The outer layer of wallboard is attached with No. 6 21/4''-long screws spaced 8'' on center. One screw is also installed at the mid-depth of the bracket in each layer. Bottom corners are finished as described above. - 17/8 - -
  1. Bonded pretensioned reinforcement in prestressed concretee
3-1.1

Carbonate, lightweight, sand-lightweight and siliceousf aggregate concrete Beams or girders

Solid slabsh
4g

3g

2


21/2

11/2


11/2

1
  1. Bonded or unbonded post-tensioned tendons in prestressed concretee,i
4-1.1 Carbonate, lightweight, sand-lightweight and siliceousf aggregate concrete Unrestrained members:
    Solid slabsh 
    Beams and girdersj
    8'' wide 
    greater than 12'' wide


-



3




41/2
21/2


11/2

21/2
2


-

13/4
11/2
4-1.2 Carbonate, lightweight, sand-lightweight and siliceous aggregateRestrained members:k
    Solid slabsh
    Beams and girdersj
    8'' wide
    greater than 12wide


11/4

21/2
2


1

2
13/4


3/ 4
13/4
11/2


-

-
-
  1. Reinforcing steel in reinforced concrete columns, beams girders and trusses
5-1.1 Carbonate, lightweight and sand-lightweight aggregate concrete, members 12''or larger, square or round. (Size limit does not apply to beams and girders monolithic with floors.) Siliceous aggregate concrete, members 12''or larger, square or round. (Size limit does not apply to beams and girders monolithic with floors.) 11/2

2
11/2

11/2
11/2

11/2
11/2

11/2
  1. Reinforcing
    steel in reinforced concrete joistsl
6-1.1
6-1.2
Carbonate, lightweight and sand-lightweight aggregate concrete.
Siliceous aggregate concrete.
11/4
13/4
11/4
11/2
1
1
3/4
3/4
  1. Reinforcing and tie rods in floor and roof slabsl
7-1.1
7-1.2
Carbonate, lightweight and sand-lightweight aggregate concrete.
Siliceous aggregate concrete.
1
11/4
1
1
3/4
1
3/4
3/4
For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm2, 1 cubic foot = 0.0283 m3.
  1. Reentrant parts of protected members to be filled solidly.
  2. Two layers of equal thickness with a 3/4-inch airspace between.
  3. For all of the construction with gypsum wallboard described in Table 720.1(1), gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified fr the wallboard and the joints on the face layer are reinforced, and the entire surface is covered with a minimum of 1/16-inch gypsum veneer plaster.
  4. An approved adhesive qualified under ASTM E 119.
  5. Where lightweight or sand-lightweight concrete having an oven-dry weight of 110 pounds per cubic foot or less is used, the tabulated minimum cover shall be permitted to be reduced 25 percent, except that in no case shall the cover be less than 3/4 inch in slabs or 11/2 inches in beams or girders.
  6. For solid slabs of siliceous aggregate concrete, increase tendon cover 20 percent.
  7. Adequate provisions against spalling shall be provided by U-shaped or hooped stirrups spaced not to exceed the depth of the member with a clear cover of 1 inch.
  8. Prestressed slabs shall have a thickness not less than that required in Table 720.1(3) for the respective fire resistance time period.
  9. Fire coverage and end anchorages shall be as follows: Cover to the prestressing steel at the anchor shall be 1/2 inch greater than that required away from the anchor. Minimum cover to steel-bearing plate shall be 1 inch in beams and 3/4 inch in slabs.
  10. For beam widths between 8 inches and 12 inches, cover thickness shall be permitted to be determined by interpolation.
  11. Interior spans of continuous slabs, beams and girders shall be permitted to be considered restrained.
  12. For use with concrete slabs having a comparable fire endurance where members are framed into the structure in such a manner as to provide equivalent performance to that of monolithic concrete construction.
  13. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in GA 600 shall be accepted as if herein listed.


TABLE 720.1(2)
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p
MATERIAL ITEM
NUMBER
CONSTRUCTION MINIMUM FINISHED
THICKNESS FACE-TO-FACEb
(inches)
4 hour 3 hour 2 hour 1 hour
1.Brick of clay
   or shale
1-1.1 Solid brick of clay or shalec 6 4.9 3.8 2.7
1-1.2 Hollow brick, not filled. 5.0 4.3 3.4 2.3
1-1.3 Hollow brick unit wall, grout or filled with perlite vermiculite or expanded shale
aggregate.
.6..6 5.5 4.4 3.0
1-2.1 4'' nominal thick units at least 75 percent solid backed with a hat-shaped metal
furring channel 3/4''thick formed from 0.021''sheet metal attached to the brick wall on 24" centers with approved fasteners, and 1/2'' Type X gypsum wallboard attached to the metal furring strips with 1''-long Type S screws spaced 8'' on center.
- - 5d -
2.Combination
   of clay brick
   and load-
   bearing
   hollow clay
   tile
2-1.1 4''solid brick and 4''tile (at least 40 percent solid). - 8 - -
2-1.2 4''solid brick and 8''tile (at least 40 percent solid). 12 - - -
3.Concrete
   masonry units
3-1.1f,g Expanded slag or pumice. 4.7 4.0 3.2 2.1
3-1.2f,g Expanded clay, shale or slate. 5.1 4.4 3.6 2.6
3-1.3f Limestone, cinders or air-cooled slag. 5.9 5.0 4.0 2.7
3-1.4f,g Calcareous or siliceous gravel. 6.2 5.3 4.2 2.8
4. Solid
    concreteh,i
4-1.1 Siliceous aggregate concrete. 7.0 6.2 5.0 3.5
Carbonate aggregate concrete. 6.6 5.7 4.6 3.2
Sand-lightweight concrete. 5.4 4.6 3.8 2.7
Lightweight concrete. 5.1 4.4 3.6 2.5
5. Glazed or
    unglazed
    facing tile,
    nonload-bearing
5-1.1 One 2'' unit cored 15 percent maximum and one 4'' unit cored 25 percent maximum with 3/4' mortar-filled collar joint. Unit positions reversed in alternate courses. - 63/8 - -
5-1.2 One 2'' unit cored 15 percent maximum and one 4'' unit cored 40 percent maximum with 3/4''
mortar-filled collar joint. Unit positions side with 3/4'' gypsum plaster. Two wythes tied together every fourth course with No. 22 gage corrugated metal ties.
- 63/8 - -
5-1.3 One unit with three cells in wall thickness, cored 29 percent maximum. - - 6 -
5-1.4 One 2''unit cored 22 percent maximum and one 4''unit cored 41 percent maximum with1/4''mortar-filled collar joint. Two wythes tied together every third course with 0.030''(No. 22 galvanized sheet steel gage) corrugated metal ties. - - 6 -
5-1.5 One 4''unit cored 25 percent maximum with 3/4''gypsum plaster on one side. - - 43/4 -
5-1.6 One 4''unit with two cells in wall thickness, cored 22 percent maximum. - - - 4
5-1.7 One 4''unit cored 30 percent maximum with 3/4''vermiculite gypsum plaster on one side. - - 41/2 -
5-1.8 One 4''unit cored 39 percent maximum with 3/4''gypsum plaster on one side. - - - 41/2
6. Solid gypsum
    plaster
6-1.1 3/4'' by 0.055''(No. 16 carbon sheet steel gage)vertical cold-rolled channels, 16''on center with 2.6-pound flat metal lath applied to one face and tied with 0.049'' (No. 18 B.W. Gage) wire at 6''spacing. Gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate. - - - 2d
6-1.2 3/4'' by 0.055''(No. 16 carbon sheet steel gage) cold-rolled channels 16" on center with metal lath applied to one face and tied with 0.049'' (No. 18 B.W. gage) wire at 6'' spacing. Perlite or vermiculite gypsum plaster each side. For three-coat work, the plaster mix for the second coat shall not exceed 100 pounds of gypsumto 21/2 cubic feet of aggregate for the 1-hour system. - - 21/2d 2d
6-1.3 3/4'' by 0.055'' (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 16'' on center with 3/8''gypsum lath applied to one face and attached with sheet metal clips. Gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate. - - - 2d
6-2.1 Studless with 1/2'' full-length plain gypsum lath and gypsum plaster each side.Plaster mixed 1:1 for scratch coat and 1:2 for brown coat, by weight, gypsum to sand aggregate. - - - 2d
6-2.2 Studless with 1/2 '' full-length plain gypsum lath and perlite or vermiculite gypsum plaster each side. - - 21/2d 2d
6-2.3 Studless partition with 3/8'' rib metal lath installed vertically adjacent edges tied 6'' on center with No. 18 gage wire ties, gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate. - - - 2d
7. Solid perlite and
    portland cement
7-1.1 Perlite mixed in the ratio of 3 cubic feet to 100 pounds of portland cement and machine applied to stud side of 11/2'' mesh by 0.058-inch (No. 17 B.W. gage) paper-backed woven wire fabric lath wire-tied to 4''-deep steel trussed wire j studs 16'' on center. Wire ties of 0.049''(No. 18 B.W. gage) galvanized steel wire 6''on center vertically. - - 31/8d -
8. Solid neat wood
    fibered gypsum
    plaster
8-1.1 3/4'' by 0.055-inch (No. 16 carbon sheet steel gage) cold-rolled channels, 12'' on center with 2.5-pound flat metal lath applied to one face and tied with 0.049'' (No. 18 B.W. gage) wire at 6'' spacing. Neat gypsum plaster applied each side. - - 2d -
9. Solid wallboard
    partition
9-1.1 One full-length layer 1/2'' Type X gypsum wallboarde laminated to each side of 1 ''full-length V-edge gypsum coreboard with approved laminating compound.Vertical joints of face layer and coreboard staggered at least 3'' - - 2d -
10. Hollow
      (studless) gypsum
      wallboard partition
10-1.1 One full-length layer of 5/8'' Type X gypsum wallboarde attached to both sides of wood or metal top and bottom runners laminated to each side of 1'' × 6'' full-length gypsum coreboard ribs spaced 24'' on center with approved laminating compound. Ribs centered at vertical joints of face plies and joints staggered 24'' in opposing faces. Ribs may be recessed 6'' from the top and bottom. - - - 21/4d
10-1.2 1'' regular gypsum V-edge full-length backing board attached to both sides of wood or metal top and bottom runners with nails or 15/8'' drywall screws at 24'' on center. Minimum width of rumors 15/8''. Face layer of 1/2''regular full-length gypsum wallboard laminated to outer faces of backing board with approved laminating compound. - - 45/8d -
11. Noncombustible
      studs—interior
      partition with plaster
      each side
11-1.1 31/4''× 0.044'' (No. 18 carbon sheet steel gage) steel studs spaced 24''on center.5/8''gypsum plaster on metal lath each side mixed 1:2 by weight, gypsum to sand aggregate. - - - 43/4d
11-1.2 33/8''× 0.055'' (No. 16 carbon sheet steel gage) approved nailablek studs spaced 24" on center. 5/8''neat gypsum wood-fibered plaster each side over 3/8''rib metal lath nailed to studs with 6d common nails, 8''on center. Nails driven 1 1/4'' and bent over. - - 55/8 -
11-1.3 4''× 0.044''(No. 18 carbon sheet steel gage) channel-shaped steel studs at 16'' on center. On each side approved resilient clips pressed onto stud flange at 16'' vertical spacing, 1/4'' pencil rods snapped into or wire tied onto outer loop of clips, metal lath wire-tied to pencil rods at 6''intervals, 1" perlite gypsum plaster, each side - 75/8d - -
11-1.4 21/2''× 0.044''(No. 18 carbon sheet steel gage) steel studs spaced 16''on center.Wood fibered gypsum plaster mixed 1:1 by weight gypsum to sand aggregate applied on 3/4-pound metal lath wire tied to studs, each side. 3/4''plaster appliedover each face, including finish coat. - - 41/4d -
12. Wood studs interior
      partition with plaster
      each side
12-1.1l, m 2''× 4'' wood studs 16'' on center with 5/8''gypsum plaster on metal lath. Lath attached by 4d common nails bent over or No. 14 gage by 11/4'' by 3/4'' crown width staples spaced 6'' on center. Plaster mixed 1:11/2 for scratch coat and 1:3 for brown coat, by weight, gypsum to sand aggregate. - - - 51/8
12-1.2l 2'' × 4'' wood studs 16'' on center with metal lath and 7/8'' neat wood-fibered gypsum plaster each side. Lath attached by 6d common nails, 7'' on center.Nails driven 11/4'' and bent over. - - 51/2d -
12-1.3l 2'' × 4'' wood studs 16'' on center with 3/8'' perforated or plain gypsum lath and 1/2 ''gypsum plaster each side. Lath nailed with 11/8''by No. 13 gage by 19/64'' head plasterboard blued nails, 4'' on center. Plaster mixed 1:2 by weight,gypsum to sand aggregate. - - - 51/4
12-1.4 l 2'' × 4'' wood studs 16'' on center with 3/8'' Type X gypsum lath and 1/2''gypsum plaster each side. Lath nailed with 11/8''by No. 13 gage by 19/64 ''head plasterboard blued nails, 5'' on center. Plaster mixed 1:2 by weight, gypsum to sand aggregate. - - - 51/4
13.Non-cumbustible
     studs—interior
     partition with gypsum
     wallboard each side
13-1.1 0.0 18'' (No. 25 carbon sheet steel gage) channel-shaped studs 24'' on center with one full-length layer of 5/8'' Type X gypsum wallboarde applied vertically attached with 1'' long No. 6 drywall screws to each stud. Screws are 8'' on center around the perimeter and 12'' on center on the intermediate stud. The wallboard may be applied horizontally when attached to 35/8''studs and the horizontal joints are staggered with those on the opposite side. Screws for the horizontal application shall be 8'' on center at vertical edges and 12'' on center at intermediate studs. - - - 51/4
13-1.2 0.0 18'' (No. 25 carbon sheet steel gage) channel-shaped studs 25'' on center with two full-length layers of 1/2'' Type X gypsum wallboarde applied vertically each side. First layer attached with 1'' long, No. 6 drywall screws, 8'' on center around the perimeter and 12'' on center on the intermediate stud. Second layer applied with vertical joints offset one stud space from first layer using 15/8'' long, No. 6 drywall screws spaced 9'' on center along vertical joints, 12'' on center at intermediate studs and 24'' on center along top and bottom runners. - - - 27/8d
13-1.3 0.055'' (No. 16 carbon sheet steel gage) approved nailable metal studse 24''on center with full-length 5/8''Type X gypsum wallboarde applied vertically and nailed 7'' on center with 6d cement-coated common nails. Approved metal fastener grips used with nails at vertical butt joints along studs - - 35/8d -
14.Wood studs—interior
     partition with gypsum
     wallboard each side
14-1.1h,m 2''× 4'' wood studs 16'' on center with two layers of 3/8'' regular gypsum wallboarde each side, 4d coolern or wallboardn nails at 8'' on center first layer, 5d coolern or wallboardn nails at 8'' on center second layer with laminating compound between layers, joints staggered. First layer applied full length vertically, second layer applied horizontally or vertically - - - 47/8
14-1.2l,m 2''× 4'' wood studs 16'' on center with two layers 1/2'' regular gypsum wallboarde applied vertically or horizontally each sidek, joints staggered. Nail base layer with 5d coolern or wallboardn nails at 8'' on center face layer with 8d coolern or wallboardn nails at 8'' on center. - - - 5
14-1.3l,m 2''× 4'' wood studs 24'' on center with 5/8'' Type X gypsum wallboarde applied vertically or horizontally nailed with 6d coolern or wallboardn nails at 7'' on center with end joints on nailing members. Stagger joints each side. - - - 51/2
14-1.4l 2''× 4'' fire-retardant-treated wood studs spaced 24'' on center with one layer of 5/8'' Type X gypsum wallboarde applied with face paper grain (long dimension) parallel to studs. Wallboard attached with 6d coolern or wallboardn nails at 7'' on center. - - - 43/4
14-1.5l,m 2''× 4'' wood studs 16'' on center with two layers 5/8'' Type X gypsum wallboarde each side. Base layers applied vertically and nailed with 6d coolern or wallboardn nails at 9'' on center. Face layer applied vertically or horizontally and nailed with 8d coolern or wallboardn nails at 7'' on center. For nail-adhesive application, base layers are nailed 6'' on center. Face layers applied with coating of approved wallboard adhesive and nailed 12'' on center. - - - 41/4d
14-1.6l 2''× 3'' fire-retardant-treated wood studs spaced 24'' on center with one layer of 5/8'' Type X gypsum wallboarde applied with face paper grain (long dimension)at right angles to studs. Wallboard attached with 6d cement-coated box nails spaced 7'' on center. - - 6 -
15. Exterior or interior
      walls
15-1.1l,m Exterior surface with 3/4'' drop siding over 1/2'' gypsum sheathing on 2''× 4'' wood studs at 16'' on center, interior surface treatment as required for 1-hour-rated exterior or interior 2''× 4'' wood stud partitions. Gypsum sheathing nailed with 13/4'' by No. 11 gage by 7/16'' head galvanized nails at 8'' on center.Siding nailed with 7d galvanized smooth box nails. - - - 35/8d
15-1.2l,m 2''× 4'' wood studs 16'' on center with metal lath and 3/4'' cement plaster on each side. Lath attached with 6d common nails 7'' on center driven to 1'' minimum penetration and bent over. Plaster mix 1:4 for scratch coat and 1:5 for brown coat, by volume, cement to sand. - - - Varies
15-.1.3l,m 2''× 4'' wood studs 16'' on center with 7/8'' cement plaster (measured from the face of studs) on the exterior surface with interior surface treatment as required for interior wood stud partitions in this table. Plaster mix 1:4 for scratch coat and 1:5 for brown coat, by volume, cement to sand. - - - 53/8
15-1.4 35/8'' No. 16 gage noncombustible studs 16'' on center with 7/8'' cement plaster(measured from the face of the studs) on the exterior surface with interior surface treatment as required for interior, non bearing, noncombustible stud partitions in this table. Plaster mix 1:4 for scratch coat and 1:5 for brown coat,by volume, cement to sand. - - Varies
15-1.5m 25/8'' × 33/4'' clay face brick with cored holes over 1/2'' gypsum sheathing on exterior surface of 2'' × 4'' wood studs at 16'' on center and two layers 5/8'' Type X gypsum wallboarde on interior surface. Sheathing placed horizontally or vertically with vertical joints over studs nailed 6'' on center with 13/4'' × No. 11 gage by 7/16''head galvanized nails. Inner layer of wallboard placed horizontally or vertically and nailed 8''on center with 6d coolern or wall boardn nails. Outer layer of wallboard placed horizontally or vertically and nailed 8'' on center with 8d coolern or wallboardn nails. All joints staggered with vertical joints over studs.Outer layer joints taped and finished with compound. Nail heads covered with joint compound. 0.035 inch (No. 20 galvanized sheet gage) corrugated galvanized steel wall ties 3/4'' by 65/8'' attached to each stud with two 8d coolern or wallboardn nails every sixth course of bricks. - - - Variesd
15-1.6l,m 2''× 6'' fire-retardant-treated wood studs 16'' on center. Interior face has two layers of 5/8'' Type X gypsum with the base layer placed vertically and attached with 6d box nails 12''on center. The face layer is placed horizontally and attached with 8d box nails 8" on center at joints and 12'' on center elsewhere. The exterior face has a base layer of 5/8'' Type X gypsum sheathing placed vertically with 6d box nails 8'' on center at joints and 12'' on center elsewhere. An approved building paper is next applied, followed by self-furred exterior lath attached with 21/2'', No. 12 gage galvanized roofing nails with a 3/8'' diameter head and spaced 6''on center along each stud. Cement plaster consisting of a 1/2'' brown coat is then applied. The scratch coat is mixed in the proportion of 1:3 by weight,cement to sand with 10 pounds of hydrated lime and 3 pounds of approved additives or admixtures per sack of cement. The brown coat is mixed in the proportion of 1:4 by weight, cement to sand with the same amounts of hydrated lime and approved additives or admixtures used in the scratch coat. - - 10 -
15-1.7l,m 2''× 6'' wood studs 16'' on center. The exterior face has a layer of 5/8'' Type X gypsum sheathing placed vertically with 6d box nails 8'' on center at joints and 12'' on center elsewhere. An approved building paper is next applied, followed by 1'' by No. 18 gage self-furred exterior lath attached with 8d by 21/2'' long galvanized roofing nails spaced 6'' on center along each stud. Cement plaster consisting of a 1/2'' scratch coat, a bonding agent and a 1/2'' brown coat and a finish coat is then applied. The scratch coat is mixed in the proportion of 1:3 by weight, cement to sand with 10 pounds of hydrated lime and 3 pounds of approved additives or admixtures per sack of cement. The brown coat is mixed in the proportion of 1:4 by weight, cement to sand with the same amounts of hydrated lime and approved additives or admixtures used in the scratch coat. The interior is covered with 3/8''gypsum lath with 1'' hexagonal mesh of 0.035 inch(No. 20 B.W. gage) woven wire lath furred out 5/16'' and 1'' perlite or vermiculite gypsum plaster. Lath nailed with 11/8'' by No. 13 gage by 19/64'' head plasterboard glued nails spaced 5'' on center. Mesh attached by 13/4'' by No. 12 gage by 3/8'' head nails with 3/8'' furrings, spaced 8'' on center. The plaster mix shall not exceed 100 pounds of gypsum to 21/2 cubic feet of aggregate. - - 81/4 -
15-1.8l,m 2''× 6'' wood studs 16'' on center. The exterior face has a layer of 5/8'' Type X gypsum sheathing placed vertically with 6d box nails 8'' on center at joints and 12'' on center elsewhere. An approved building paper is next applied, followed by 11/2'' by No. 17 gage self-furred exterior lath attached with 8d by 21/2'' long galvanized roofing nails spaced 6'' on center along each stud. Cement plaster consisting of a 1/2'' scratch coat, and a 1/2'' brown coat is then applied. The plaster may be placed by machine. The scratch coat is mixed in the proportion of 1:4 by weight,plastic cement to sand. The brown coat is mixed in the proportion of 1:5 by weight, plastic cement to sand. The interior is covered with 3/8'' gypsum lath with 1'' hexagonal mesh of No. 20 gage woven wire lath furred out 5/16'' and 1''perlite or vermiculite gypsum plaster. Lath nailed with 11/8'' by No. 13 gage by 19/64'' head plasterboard glued nails spaced 5'' on center. Mesh attached by 13/4'' by No. 12 gage by 3/8'' head nails with 3/8'' furrings, spaced 8'' on center. The plaster mix shall not exceed 100 pounds of gypsum to 21/2 cubic feet of aggregate. - - 83/8 -
15-1.9 4'' No. 18 gage, nonload-bearing metal studs, 16'' on center, with 1'' portland cement lime plaster [measured from the back side of the 3/4-pound expanded metal lath] on the exterior surface. Interior surface to be covered with 1'' of gypsum plaster on 3/4-pound expanded metal lath proportioned by weight—1:2 for scratch coat, 1:3 for brown, gypsum to sand. Lath on one side of the partition fastened to 1/4'' diameter pencil rods supported by No. 20 gage metal clips,located 16' on center vertically, on each stud. 3'' thick mineral fiber insulating batts friction fitted between the studs. - - 83/8 -
15-1.10 Steel studs 0.060' thick, 4'' deep or 6' at 16'' or 24'' centers, with 1/2 '' Glass Fiber Reinforced Concrete (GFRC) on the exterior surface. GFRC is attached with flex anchors at 24'' on center, with 5'' leg welded to studs with two 1/2''-long flare-bevel welds, and 4'' foot attached to the GFRC skin with 5/8'' thick GFRC bonding pads that extend 21/2'' beyond the flex anchor foot on both sides. Interior surface to have two layers of 1/2'' Type X gypsum wallboarde The first layer of wallboard to be attached with 1''-long Type S buglehead screws spaced 24''on center and the second layer is attached with 15/8''-long Type S screws spaced at 12'' on center. Cavity is to be filled with 5 of 4 pcf (nominal) mineral fiber batts. GFRC has 11/2 ''returns packed with mineral fiber and caulked on the exterior. - - 61/2d -
15-1.11 Steel studs 0.060'' thick, 4'' deep or 6'' at 16'' or 24'' centers, respectively, with 1/2'' Glass Fiber Reinforced Concrete (GFRC) on the exterior surface. GFRC is attached with flex anchors at 24'' on center, with 5'' leg welded to studs with two 1/2''-long flare-bevel welds, and 4'' foot attached to the GFRC skin with 5/8''-thick GFRC bonding pads that extend 21/2'' beyond the flex anchor foot on both sides. Interior surface to have one layer of 5/8'' Type X gypsum wallboarde, attached with 11/4''-long Type S buglehead screws spaced 12'' on center. Cavity is to be filled with 5'' of 4 pcf (nominal) mineral fiber batts. GFRC has 11/2'' returns packed with mineral fiber and caulked on the exterior. - - 61/2 -
15-1.12q 2''× 6'' wood studs at 16'' with double top plates, single bottom plate; interior and exterior sides covered with 5/8'' Type X gypsum wallboard, 4' wide, applied horizontally or vertically with vertical joints over studs, and fastened with 21/4'' Type S drywall screws, spaced 12'' on center. - - - 61/8
15-1.13q 2''× 6'' wood studs at 16'' with double top plates, single bottom plate; interior and exterior sides covered with 5/8'' Type X gypsum wallboard, 4' wide, applied horizontally or vertically with vertical joints over studs, and fastened with 21/4'' Type S drywall screws, spaced 7'' on center. Cavity to be filled with 51/2'' mineral wool insulation minimum 2.58 pcf (nominal). - - - 61/4
15-1.14q 2''× 4'' wood studs at 16'' with double top plates, single bottom plate; interior and exterior sides covered with 5/8'' Type X gypsum wallboard and sheathing,respectively, 4' wide, applied horizontally or vertically with vertical joints over studs, and fastened with 21/4'' Type S drywall screws, spaced 12'' on center.Cavity to be filled with 31/2'' mineral wool insulation. - - - 43/4
15-1.15q 2'' × 6'' wood studs at 24'' centers with double top plates, single bottom plate;interior and exterior side covered with two layers of 5/8'' Type X gypsum wallboard, 4' wide, applied horizontally with vertical joints over studs. Base layer fastened with 21/4'' Type S drywall screws, spaced 24'' on center, and face layer fastened with Type S drywall screws, spaced 8'' on center, wallboard joints covered with paper tape and joint compound, fastened heads covered with joint compound. Cavity to be filled with 51/2'' mineral wool insulation. - - 73/4 -
16. Exterior walls rated
      for fire resistance
      from the inside only
      in accordance with
      Section 704.5.
16-1.1q 2'' × 4'' wood studs at 16'' centers with double top plates, single bottom plate;interior side covered with 5/8'' Type X gypsum wallboard, 4' wide, applied horizontally unblocked, and fastened with 21/4" Type S drywall screws, spaced 12'' on center, wallboard joints covered with paper tape and joint compound,fastener heads covered with joint compound. Exterior covered with 3/8'' wood structural panels (oriented strand board), applied vertically, horizontal joints blocked and fastened with 6d common nails (bright) —12'' on center in the field,and 6'' on center panel edges. Cavity to be filled with 31/2'' mineral wool insulation. Rating established for exposure from interior side only. - - - 41/2
16-1.2q 2" × 6" (51 mm x 152 mm) wood studs at 16'' centers with double top plates, single bottom plate; interior side covered with 5/8'' Type X gypsum wallboard, 4' wide,applied horizontally or vertically with vertical joints over studs and fastened with 21/4'' Type S drywall screws, spaced 12'' on center, wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound, exterior side covered with 7/16''wood structural panels (oriented strand board) fastened with 6d common nails (bright) spaced 12'' on center in the field and 6'' on center along the panel edges. Cavity to be filled with 51/2''mineral wool insulation. Rating established from the gypsum-covered side only. - - - 69/16
For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm2, 1 cubic foot = 0.0283 m3.
  1. Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood raming.
  2. Thickness shown for brick and clay tile are nominal thicknesses unless plastered, in which case thicknesses are net. Thickness shown for concrete masonry and clay masonry is equivalent thickness defined in Section 721.3.1 for concrete masonry and Section 721.4.1.1 for clay masonry. Where all cells are solid grouted or filled with silicone-treated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, the equivalent thickness shall be the thickness of the block or brick using specified dimensions as defined in Chapter 21. Equivalent thickness may also include the thickness of applied plaster and lath or gypsum wallboard, where specified.
  3. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is at least 75 percent of the gross cross-sectional area measured in the same plane.
  4. Shall be used for nonbearing purposes only.
  5. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and the entire surface is covered with a minimum of 1/16-inch gypsum veneer plaster.
  6. The fire-resistance time period for concrete masonry units meeting the equivalent thicknesses required for a 2-hour fire-resistance rating in Item 3, and having a thickness of not less than 75/8 inches is 4 hours when cores which are not grouted are filled with silicone-treated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, sand or slag having a maximum particle size of 3/8 inch.
  7. The fire-resistance rating of concrete masonry units composed of a combination of aggregate types or where plaster is applied directly to the concrete masonry shall be determined in accordance with ACI 216.1/TMS 216. Lightweight aggregates shall have a maximum combined density of 65 pounds per cubic foot.
  8. See also Note b. The equivalent thickness shall be permitted to include the thickness of cement plaster or 1.5 times the thickness of gypsum plaster applied in accordance with the requirements of Chapter 25.
  9. Concrete walls shall be reinforced with horizontal and vertical temperature reinforcement as required by Chapter 19.
  10. Studs are welded truss wire studs with 0.18 inch (No. 7 B.W. gage) flange wire and 0.18 inch (No. 7 B.W. gage) truss wires.
  11. Nailable metal studs consist of two channel studs spot welded back to back with a crimped web forming a nailing groove.
  12. Wood structural panels shall be permitted to be installed between the fire protection and the wood studs on either the interior or exterior side of the wood frame assemblies in this table, provided the length of the fasteners used to attach the fire protection are increased by an amount at least equal to the thickness of the wood structural panel.
  13. The design stress of studs shall be reduced to 78 percent of allowable Fc with the maximum not greater than 78 percent of the calculated stress with studs having a slenderness ratio le/d of 33.
  14. For properties of cooler or wallboard nails, see ASTM C 514, ASTM C 547 or ASTM F 1667.
  15. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in the GA 600 shall be accepted as if herein listed.
  16. NCMA TEK 5-8, shall be permitted for the design of fire walls.
  17. The design stress of studs shall be equal to a maximum of 100 percent of the allowable F'c calculated in accordance with Section 2306.


TABLE 720.1(3)
MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa,q
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTION THICKNESS OF FLOOR
OR ROOF SLAB
(inches)
MINIMUM THICKNESS
OF CEILING
(inches)
4
hour
3
hour
2
hour
1
hour
4
hour
3
hour
2
hour
1
hour
  1. Siliceous,aggregate concrete
1-1.1 Slab (no ceiling required). Minimum cover overnonprestressed reinforcement shall not be less than 3/4 inch.b 7.0 6.2 5.0 3.5 - - - -
  1. Carbonate aggregate concrete
2-1.1 6.6 5.7 4.6 3.2 - - - -
  1. Sand-lightweight concrete
3-1.1 5.4 4.6 3.8 2.7 - - - -
  1. Lightweight concrete
4-1.1 5.1 4.4 3.6 2.5 - - - -
  1. Reinforced concrete
5-1.1 Slab with suspended ceiling of vermiculite gypsum plaster over metal lath attached to 3/4'' cold-rolled channels spaced 12'' on center. Ceiling located 6'' minimum below joists. 3 2 - - 1 3/4 - -
5-2.1 3/8'' Type X gypsum wallboardc attached to 0.018 inch (No. 25 carbon sheet steel gage) by 7/8" deep by 25/8'' hat-shaped galvanized steel channels with 1''-long No. 6 screws. The channels are spaced 24'' on center, span 35'' and are supported along their length at 35''intervals by 0.033-inch (No. 21 galvanized sheet gage) galvanized steel flat strap hangers having formed edges that engage the lips of the channel. The strap hangers are attached to the side of the concrete joists with 5/32'' by 11/4'' long power-driven fasteners. The wallboard is installed with the long dimension perpendicular to the channels. All end joints occur on channels and supplementary channels are installed parallel to the main channels, 12'' each side, at end joint occurrences. The finished ceiling is located approximately 12" below the soffit of the floor slab. - - 21/2 - - - 5/8 -
  1. Steel joists constructed with a poured reinforced concrete slab on metal lath forms or steel form unitsd, e
6-1. 1 Gypsum plaster on metal lath attached to the bottom cord with single No. 16 gage or doubled No. 18 gage wire ties spaced 6'' on center. Plaster mixed 1:2 for scratch coat, 1:3 for brown coat, by weight,gypsum-to-sand aggregate for 2-hour system. For 3-hour system plaster is neat. - - 21/2 21/4 - - 3/4 5/8
6-2.1 Vermiculite gypsum plaster on metal lath attached to the bottom chord with single No.16 gage or doubled 0.049-inch (No. 18 B.W. gage) wire ties 6'' on center. - 2 - - - 5/8 - -
6-3.1 Cement plaster over metal lath attached to the bottom chord of joists with single No. 16 gage or doubled 0.049-inch (No. 18 B.W. gage) wire ties spaced 6'' on center. Plaster mixed 1:2 for scratch coat, 1:3 for brown coat for 1-hour system and 1:1 for scratch coat, 1:1 1/2 for brown coat for 2-hour system, by weight, cement to sand. - - - 2 - - - 5/8f
6-4.1 Ceiling of 5/8'' Type X wallboardc attached to 7/8'' deep by 25/8" by 0.02 1 inch (No. 25 carbon sheet steel gage) hat-shaped furring channels 12'' on center with 1''long No. 6 wallboard screws at 8" on center. Channels wire tied to bottom chord of joists with doubled 0.049 inch (No. 18 B.W. gage) wire or suspended below joists on wire hangers.g - - 21/2 - - - 5/8 -
6-5.1 Wood-fibered gypsum plaster mixed 1:1 by weight gypsum to sand aggregate applied over metal lath.Lath tied 6'' on center to 3/4" channels spaced 131/2'' on center. Channels secured to joists at each intersection with two strands of 0.049 inch (No. 18 B.W. gage) galvanized wire. - - 21/2 - - - 3/4 -
  1. Reinforced concrete slabs and joists with hollow clay tile fillers laid end to end in rows 21/2'' or more apart; reinforcement placed between rows and concrete cast around and over tile.
7-1.1 5/8'' gypsum plaster on bottom of floor or roof construction. - - 8h - - - 5/8 -
7-1.2 None - - - 51/2i -- - - -
  1. Steel joists constructed with a reinforced concrete slab on top poured on a 1/2" deep steel deck.e
8-1.1 Vermiculite gypsum plaster on metal lath attached to 3/4" cold-rolled channels with 0.049" (No. 18 B.W. gage) wire ties spaced 6'' on center. 21/2i - - - 3/4 - - -
  1. 3'' deep cellular steel deck with concrete slab on top.Slab thickness measured to top.
9-1.1 Suspended ceiling of vermiculite gypsum plaster base coat and vermiculite acoustical plaster on metal lath attached at 6'' intervals to 3/4'' cold-rolled channels spaced 12'' on center and secured to 11/2" cold-rolled channels spaced 36'' on center with 0.065'' (No. 16 B.W. gage) wire. 11/2'' channels supported by No. 8 gage wire hangers at 36'' on center.Beams within envelope and with a 21/2'' airspace between beam soffit and lath have a 4-hour rating. 21/2 - - - 11/8k - - -
  1. 11/2''-deep steel roof deck on steel framing. Insulation board, 30 pcf density, composed of wood fibers with cement binders of thickness shown bonded to deck with unified asphalt adhesive. Covered with a Class A or B roof covering.
10-1.1 Ceiling of gypsum plaster on metal lath. Lath attached to 3/4 furring channels with 0.049'' (No. 18 B.W. gage) wire ties spaced 6'' on center 3/4''channel saddle tied to 2''channels with doubled 0.065''(No. 16 B.W. gage) wire ties. 2''channels spaced 36'' on center suspended 2''below steel framing and saddle-tied with 0.165''(No. 8 B.W. gage) wire. Plaster mixed 1:2 by weight,gypsum-to-sand aggregate. - - 17/8 1 - - 3/4l 3/4l
  1. 11/2''-deep steel roof deck on steel-framing wood fiber insulation board, 17.5 pcf density on top applied over a 15-lb asphalt-saturated felt. Class A or B roof covering.
11-1.1 Ceiling of gypsum plaster on metal lath. Lath attached to 3/4'' furring channels with 0.049''(No. 18 B.W. gage) wire ties spaced 6'' on center.3/4'' channels saddle tied to 2'' channels with doubled 0.065'' (No. 16 B.W. gage) wire ties. 2'' channels spaced 36'' on center suspended 2''below steel framing and saddle tied with 0.165" (No. 8 B.W. gage) wire. Plaster mixed 1:2 for scratch coat and 1:3 for brown coat, by weight, gypsum-to-sand aggregate for 1-hour system. For 2-hour system,plaster mix is 1:2 by weight, gypsum-to-sand aggregate. - - 11/2 1 - - 7/8g 3/4l
  1. 11/2'' deep steel roof deck on steel-framing insulation of rigid board consisting of expanded perlite and fibers impregnated with integral asphalt waterproofing; density 9 to 12 pcf secured to metal roof deck by 1/2'' wide ribbons of waterproof, cold-process liquid adhesive spaced 6'' apart. Steel joist or light steel construction with metal roof deck, insulation, and Class A or B built-up roof covering.e
12-1.1 Gypsum-vermiculite plaster on metal lath wire tied at 6'' intervals to 3/4'' furring channels spaced 12'' on center and wire tied to 2'' runner channels spaced 32'' on center. Runners wire tied to bottom chord of steel joists. - - 1 - - - 7/8 -
  1. Double wood floor over wood joists spaced 16'' on center.m,n
13-1.1 Gypsum plaster over 3/8'' Type X gypsum lath. Lath initially applied with not less than four 11/8''by No.13 gage by 19/64'' head plasterboard blued nails per bearing. Continuous stripping over lath along all joist lines. Stripping consists of 3''wide strips of metal lath attached by 11/2 '' by No. 11 gage by 1/2'' head roofing nails spaced 6'' on center. Alternate stripping consists of 3''wide 0.049''diameter wire stripping weighing 1 pound per square yard and attached by No.16 gage by 11/2'' by 3/4'' crown width staples, spaced 4'' on center. Where alternate stripping is used, the lath nailing may consist of two nails at each end and one nail at each intermediate bearing. Plaster mixed 1:2 by weight,gypsum-to-sand aggregate. 7/8
13-1.2 Cement or gypsum plaster on metal lath. Lath fastened with 11/2'' by No. 11 gage by 7/16'' head barbed shank roofing nails spaced 5'' on center.Plaster mixed 1:2 for scratch coat and 1:3 for brown coat, by weight, cement to sand aggregate. 5/8
13-1.3 Perlite or vermiculite gypsum plaster on metal lath secured to joists with 11/2'' by No. 11 gage by 7/16'' head barbed shank roofing nails spaced 5'' on center. 5/8
13-1.4 1/2'' Type X gypsum wallboardc nailed to joists with 5d coolero or wallboardo nails at 6'' on center. End joints of wallboard centered on joists. 1/2
  1. Plywood stressed skin panels consisting of 5/8''-thick interior C-D (exterior glue) top stressed skin on 2'' × 6'' nominal (minimum) stringers. Adjacent panel edges joined with 8d common wire nails spaced 6'' on center. Stringers spaced 12''maximum on center.
14-1.1 1/2''-thick wood fiberboard weighing 15 to 18 pounds per cubic foot installed with long dimension parallel to stringers or 3/8'' C-D (exterior glue)plywood glued and/or nailed to stringers. Nailing to be with 5d coolero or wallboardo nails at 12'' on center. Second layer of 1/2'' Type X gypsum wallboardc applied with long dimension perpendicular to joists and attached with 8d coolero or wallboardo nails at 6'' on center at end joints and 8'' on center elsewhere. Wallboard joints staggered with respect to fiberboard joints. 1
  1. Vermiculite concrete slab proportioned 1:4 (portland cement to vermiculite aggregate) on a 11/2''-deep steel deck supported on individually protected steel framing. Maximum span of deck 6'-10'' where deck is less than 0.019 inch (No.26 carbon steel sheet gage)or greater. Slab reinforced with 4'' × 8'' 0.109/0.083'' (No.12/14 B.W. gage)welded wire mesh.
15-1.1 None - - - 3j - - - -
  1. Perlite concrete slab proportioned 1:6 (portland cement to perlite aggregate) on a 11/4''-deep steel deck supported on individually protected steel framing. Slab reinforced with 4'' × 8'' 0.109/0.083'' (No.12/14 B.W. gage) welded wire mesh.
16-1.1 None - - - 31/2j - - - -
  1. Perlite concrete slab proportioned 1:6 (portland cement to perlite aggregate) on a 9/16'' -deep steel deck supported by steel joists 4' on center.Class A or B roof covering on top.
17-1.1 Perlite gypsum plaster on metal lath wire tied to 3/4'' furring channels attached with 0.065-inch (No. 16 B.W. gage) wire ties to lower chord of joists. - 2p 2p - - 7/8 3/4 -
  1. Perlite concrete slab proportioned 1:6 (portlandcement to perlite aggregate) on 11/4'' -deep steel deck supported on individually protected steel framing. Maximum span of deck 6'-10'' where deck isless than 0.019'' (No. 26carbon sheet steel gage) and 8'-0'' where deck is 0.019'' (No. 26 carbon sheet steel gage) or greater.Slab reinforced with 0.042'' (No. 19 B.W. gage) hexagonal wire mesh. Class A or B roof covering on top.
18-1.1 None - 21/4p 21/4p - - - - -
  1. Floor and beam construction consisting of 3"-deep cellular steel floor unit mounted on steel members with 1:4 (proportion of portland cement to perlite aggregate) perlite-concrete floor slab on top.
19-1.1 Suspended envelope ceiling of perlite gypsum plaster on metal lath attached to 3/4'' cold-rolled channels, secured to 11/2'' cold-rolled channels spaced 42'' on center supported by 0.203 inch (No. 6 B.W. gage) wire 36'' on center. Beams in envelope with 3'' minimum airspace between beam soffit and lath have a 4-hour rating. 2p - - - 1l - -- -
  1. Perlite concrete proportioned 1:6 (portland cement to perlite aggregate) poured to 1/8-inch thickness above top of corrugations of 15/16''-deep galvanized steel deck maximum span 8'-0'' for 0.024-inch (No. 24 galvanized sheet gage)or 6'0'' for 0.019-inch(No. 26 galvanized sheet gage) with deck supported by individually protected,steel framing. Approved polystyrene foam plastic insulation board having a flame spread not exceeding 75 (1'' to 4'' thickness) with vent holes that approximate 3 percent of the board surface area placed on top of perlite slurry. A 2' by 4' insulation board contains six 23/4'' diameter holes. Board covered with 21/4'' minimum perlite concrete slab.Slab reinforced with mesh consisting of 0.042 inch (No. 19 B.W. gage) galvanized steel wire twisted together to form 2'' hexagons with straight 0.065 inch (No. 16 B.W. gage) galvanized steel wire woven into mesh and spaced 3''.Alternate slab reinforcement shall be permitted to consist of 4'' ×  8'', 0.109/0.238-inch (No. 12/4 B.W. gage), or 2" ×  2", 0.083/0.083-inch (No.14/14 B.W. gage) welded wire fabric. Class A or B roof covering on top.
20-1.1 None - - Varies - - - - -
  1. Wood joists, floor trusses and flat or pitched roof trusses spaced a maximum 24'' o.c. with 1/2'' wood structural panels with exterior glue applied at right angles to top of joist or top chord of trusses with 8d nails. The wood structural panel thickness shall not be less than nominal 1/2'' nor less than required by Chapter 23.
21-1.1 Base layer 5/8'' Type X gypsum wallboard applied at right angles to joist or truss 24'' o.c. with 11/4'' Type S or Type W drywall screws 24'' o.c. Face layer 5/8'' Type X gypsum wallboard or veneer base applied at right angles to joist or truss through base layer with 17/8'' Type S or Type W drywall screws 12'' o.c. at joints and intermediate joist or truss. Face layer Type G drywall screws placed 2'' back on either side of face layer end joints, 12'' o.c. - - - Varies - - - 11/4
  1. Steel joists, floor trusses and flat or pitched roof trusses spaced a maximum 24'' o.c. with 1/2'' wood structural panels with exterior glue applied at right angles to top of joist or top chord of trusses with No. 8 screws. The wood structural panel thickness shall not be less than nominal 1/2'' nor less than required by Chapter 23.
22-1.1 Base layer 5/8'' Type X gypsum board applied at right angles to steel framing 24'' on center with 1'' Type S drywall screws spaced 24'' on center. Face layer 5/8'' Type X gypsum board applied at right angles to steel framing attached through base layer with 15/8'' Type S drywall screws 12'' on center at end joints and intermediate joints and 11/2'' Type G drywall screws 12 inches on center placed 2'' back on either side of face layer end joints. Joints of the face layer are offset 24'' from the joints of the base layer. - - - Varies - - - 11/4
  1. Wood I-joist (minimum joist depth 91/4" with a minimum flange depth of 15/16'' and a minimum flange cross-sectional area of 2.3 square inches) at 24'' o.c. spacing with 1 × 4 (nominal) wood furring strip spacer applied parallel to and covering the bottom of the bottom flange of each member, tacked in place. 2" mineral fiber insulation, 3.5 pcf (nominal) installed adjacent to the bottom flange of the I-joist and supported by the 1 × 4 furring strip spacer.
23-1.1 1/2'' deep single leg resilient channel 16'' on center (channels doubled at wallboard end joints), placed perpendicular to the furring strip and joist and attached to each joist by 17/8'' Type S drywall screws. 5/8'' Type C gypsum wallboard applied perpendicular to the channel with end joints staggered at least 4' and fastened with 11/8'' Type S drywall screws spaced 7'' on center. Wallboard joints to be taped and covered with joint compound. - - - Varies - - - -
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.454 kg, 1 cubic foot = 0.0283m3,1 pound per square inch = 6.895 kPa = 1 pound per lineal foot = 1.4882 kg/m.
  1. Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing.
  2. When the slab is in an unrestrained condition, minimum reinforcement cover shall not be less than 15/8inches for 4-hour (siliceous aggregate only); 11/4inches for 4-and 3-hour; 1 inch for 2-hour (siliceous aggregate only); and 3/4 inch for all other restrained and unrestrained conditions.
  3. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and the entire surface is covered with a minimum of 1/16-inch gypsum veneer plaster.
  4. Slab thickness over steel joists measured at the joists for metal lath form and at the top of the form for steel form units.
    1. The maximum allowable stress level for H-Series joists shall not exceed 22,000 psi.
    2. The allowable stress for K-Series joists shall not exceed 26,000 psi, the nominal depth of such joist shall not be less than 10 inches and the nominal joist weight shall not be less than 5 pounds per lineal foot.
  5. Cement plaster with 15 pounds of hydrated lime and 3 pounds of approved additives or admixtures per bag of cement.
  6. Gypsum wallboard ceilings attached to steel framing shall be permitted to be suspended with 11/2-inch cold-formed carrying channels spaced 48 inches on center, which are suspended with No.8 SWG galvanized wire hangers spaced 48 inches on center. Cross-furring channels are tied to the carrying channels with No.18 SWG galvanized wire hangers spaced 48 inches on center. Cross-furring channels are tied to the carrying channels with No. 18 SWG galvanized wire (double strand) and spaced as required for direct attachment to the framing. This alternative is also applicable to those steel framing assemblies recognized under Note q.
  7. Six-inch hollow clay tile with 2-inch concrete slab above.
  8. Four-inch hollow clay tile with 11/2-inch concrete slab above.
  9. Thickness measured to bottom of steel form units.
  10. Five-eighths inch of vermiculite gypsum plaster plus 1/2 inch of approved vermiculite acoustical plastic.
  11. Furring channels spaced 12 inches on center.
  12. Double wood floor shall be permitted to be either of the following:
    1. Subfloor of 1-inch nominal boarding, a layer of asbestos paper weighing not less than 14 pounds per 100 square feet and a layer of 1-inch nominal tongue-and-groove finished flooring; or
    2. Subfloor of 1-inch nominal tongue-and-groove boarding or 15/32-inch wood structural panels with exterior glue and a layer of 1-inch nominal tongue-and-groove finished flooring or 19/32-inch wood structural panel finish flooring or a layer of Type I GradeM-1 particleboard not less than 5/8-inch thick.
  13. The ceiling shall be permitted to be omitted over unusable space, and flooring shall be permitted to be omitted where unusable space occurs above.
  14. For properties of cooler or wallboard nails, see ASTM C 514, ASTM C 547 or ASTM F 1667.
  15. Thickness measured on top of steel deck unit.
  16. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in the GA 600 shall be accepted as if herein listed.
The thickness of fire-resistant materials required for protection of structural members shall be not less than set forth in Table 720.1(1), except as modified in this section. The figures shown shall be the net thickness of the protecting materials and shall not include any hollow space in back of the protection.
Where required, metal ties shall be embedded in transverse joints of unit masonry for protection of steel columns. Such ties shall be as set forth in Table 720.1(1) or be equivalent thereto.
Cast-in-place concrete protection for steel columns shall be reinforced at the edges of such members with wire ties of not less than 0.18 inch (4.6 mm) in diameter wound spirally around the columns on a pitch of not more than 8 inches (203 mm) or by equivalent reinforcement.
The finish coat is not required for plaster protective coatings where they comply with the design mix and thickness requirements of Tables 720.1(1), 720.1(2) and 720.1(3).
For members having a single tendon or more than one tendon installed with equal concrete cover measured from the nearest surface, the cover shall not be less than that set forth in Table 720.1(1). For members having multiple tendons installed with variable concrete cover, the average tendon cover shall not be less than that set forth in Table 720.1(1), provided:
  1. The clearance from each tendon to the nearest exposed surface is used to determine the average cover.
  2. In no case can the clear cover for individual tendons be less than one-half of that set forth in Table 720.1(1). A minimum cover of 0.75 inch (19.1 mm) for slabs and 1 inch (25 mm) for beams is required for any aggregate concrete.
  3. For the purpose of establishing a fire-resistance rating, tendons having a clear covering less than that set forth in Table 720.1(1) shall not contribute more than 50 percent of the required ultimate moment capacity for members less than 350 square inches (0.226 m2) in cross-sectional area and 65 percent for larger members. For structural design purposes, however, tendons having a reduced cover are assumed to be fully effective.
The provisions of this section contain procedures by which the fire resistance of specific materials or combinations of materials is established by calculations. These procedures apply only to the information contained in this section and shall not be otherwise used. The calculated fire resistance of concrete, concrete masonry, and clay masonry assemblies shall be permitted in accordance with ACI 216.1/TMS 0216.1. The calculated fire resistance of steel assemblies shall be permitted in accordance with Chapter 5 of ASCE/SFPE 29.
The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.
  CERAMIC FIBER BLANKET. A mineral wool insulation material made of alumina-silica fibers and weighing 4 to 10 pounds per cubic foot (pcf) (64 to 160 kg/m3).
  CONCRETE, CARBONATE AGGREGATE. Concrete made with aggregates consisting mainly of calcium or magnesium carbonate, such as limestone or dolomite, and containing 40 percent or less quartz, chert, or flint.
  CONCRETE, CELLULAR. A lightweight insulating concrete made by mixing a preformed foam with portland cement slurry and having a dry unit weight of approximately 30 pcf (480 kg/m3).
  CONCRETE, LIGHTWEIGHT AGGREGATE. Concrete made with aggregates of expanded clay, shale, slag or slate or sintered fly ash or any natural lightweight aggregate meeting ASTM C 330 and possessing equivalent fire-resistance properties and weighing 85 to 115 pcf (1360 to 1840 kg/m3).
  CONCRETE, PERLITE. A lightweight insulating concrete having a dry unit weight of approximately 30 pcf (480 kg/m3) made with perlite concrete aggregate. Perlite aggregate is produced from a volcanic rock which, when heated, expands to form a glass-like material of cellular structure.
  CONCRETE, SAND-LIGHTWEIGHT. Concrete made with a combination of expanded clay, shale, slag, slate, sintered fly ash, or any natural lightweight aggregate meeting ASTM C 330 and possessing equivalent fire-resistance properties and natural sand. Its unit weight is generally between 105 and 120 pcf (1680 and 1920 kg/m3).
  CONCRETE, SILICEOUS AGGREGATE. Concrete made with normal-weight aggregates consisting mainly of silica or compounds other than calcium or magnesium carbonate, which contains more than 40-percent quartz, chert, or flint.
  CONCRETE, VERMICULITE. A lightweight insulating concrete made with vermiculite concrete aggregate which is laminated micaceous material produced by expanding the ore at high temperatures. When added to a portland cement slurry the resulting concrete has a dry unit weight of approximately 30 pcf (480 kg/m3).
  GLASS FIBERBOARD. Fibrous glass roof insulation consisting of inorganic glass fibers formed into rigid boards using a binder. The board has a top surface faced with asphalt and kraft reinforced with glass fiber.
  MINERAL BOARD. A rigid felted thermal insulation board consisting of either felted mineral fiber or cellular beads of expanded aggregate formed into flat rectangular units.
The provisions of this section contain procedures by which the fire-resistance ratings of concrete assemblies are established by calculations.
Cast-in-place and precast concrete walls shall comply with Section 721.2.1.1. Multiwythe concrete walls shall comply with Section 721.2.1.2. Joints between precast panels shall comply with Section 721.2.1.3. Concrete walls with gypsum wallboard or plaster finish shall comply with Section 721.2.1.4.
The minimum equivalent thickness of cast-in-place or precast concrete walls for fire-resistance ratings of 1 hour to 4 hours are shown in Table 721.2.1.1. For solid walls with flat vertical surfaces, the equivalent thickness is the same as the actual thickness. The values in Table 721.2.1.1 apply to plain, reinforced or prestressed concrete walls.

TABLE 721.2.1.1
MINIMUM EQUIVALENT THICKNESS OF CAST-IN-PLACE OR PRECAST CONCRETE WALLS, LOAD-BEARING OR NONLOAD-BEARING
CONCRETE
TYPE
MINIMUM SLAB THICKNESS (inches)
FOR FIRE-RESISTANCE RATING OF
1-hour 11/2-hour 2-hour 3-hour 4-hour
Siliceous 3.5 4.3 5.0 6.2 7.0
Carbonate 3.2 4.0 4.6 5.7 6.6
Sand-
Lightweight
2.7 3.3 3.8 4.6 5.4
Lightweight 2.5 3.1 3.6 4.4 5.1
For SI: 1 inch = 25.4 mm.
For hollow-core precast concrete wall panels in which the cores are of constant cross section throughout the length, calculation of the equivalent thickness by dividing the net cross-sectional area (the gross cross section minus the area of the cores) of the panel by its width shall be permitted.
Where all of the core spaces of hollow-core wall panels are filled with loose-fill material, such as expanded shale, clay, or slag, or vermiculite or perlite, the fire-resistance rating of the wall is the same as that of a solid wall of the same concrete