As referenced by Chapter 30 of the New York City Building Code, the
provisions of ASME A17.1—00 with supplements A17.1a—02 and A17.1b—03 shall be
modified in accordance with this chapter. The section numbers correlate to those
in the referenced ASME standard. Refer to the rules of the department for any
subsequent additions, modifications or deletions that may have been made to this
standard in accordance with Section 28-103.19 of the Administrative
Code.
1.3 Add or revise the following definitions to section 1.3 as follows:
Delete and revise the definition "Designated Level" to read as
follows:
Designated Level: For the
purpose of applying Section 2.27.3, designated level shall mean the street floor
or other level that best serves the needs of emergency personnel for fire
fighting or rescue purposes.
Hospital Emergency Service:
A special operating control function that may be provided for elevators in
occupancy group I-2 (Hospital) or other applicable medical facilityused to
transport a patient in a life or death situation.
Delete and revise the definition "Installation Placed Out of
Service" to read as follows:
(a) An electric elevator, dumbwaiter, sidewalk elevator or material lift
whose suspension ropes have been removed, whose car and counterweight rest at the
bottom of the hoistway, and whose hoistway doors have been permanently barricaded
or sealed in the closed position on the hoistway side.
(b) A hydraulic elevator, dumbwaiter, sidewalk elevator or material lift
whose car rests at the bottom of the hoistway; whose pressure piping has been
disassembled and a removed from the premises; whose hoistway doors have been
permanently barricaded or sealed in the closed position.
(c) An escalator or moving walk whose entrances have been permanently
barricaded.
Patient Elevator: An
elevator located in a building classified in occupancy group I-2 (Hospital)
reserved for the "sole" use of vertical transportation of non-ambulatory patients
who are incapable of self-preservation because of age, physical or mental
disability. Hospital staff or other passengers transporting a patient are
permitted to ride with the patient. Such elevators must be operated by a
designated attendant and shall meet the requirements of §2.27.4 and
§2.27.5.3.
Zero Clearance Vestibule. A
space on the elevator lobby between the exterior of the hoistway door and the
security door attached to the elevator hoistway.
2.1.6.2. On sides not used for loading and
unloading:
(a) Recesses,
except those necessary for installation of elevator equipment, shall not be
permitted;
(b) Beams, floor slabs, or other
building construction making an angle less than 75 degrees with the horizontal
shall not project more than [100 mm (4 in.)] 50 mm (2 in) inside the hoistway
enclosure unless the top surface of the projection is beveled at an angle not
less than 75 degrees with the horizontal;
(c)
Separator beams between adjacent elevators are not required to have
bevels;
(d) Where setbacks exceeding [100
mm (4 in.)] 50 mm (2 in) occur in the enclosure wall, the top of the setback
shall be beveled at an angle of not less than 75 degrees with the
horizontal;
(e) Bevels are not required if
the projections and setbacks are covered with material conforming to the
following:
(i) It shall be equal to or stronger than 1.110 mm
(0.0437 in.) wire;
(ii) It shall have
openings not exceeding 25 mm (1 in.); and
(iii)
It shall be supported and braced such that it will not deflect more than 25
mm (1 in.) when subjected to a force of 4.79 kPa (100 lbs per
sq ft) applied horizontally at any point.
Add new sub-section (e) to 2.7.3.4.1 to read as follows:
2.7.3.4.1 Access doors to machine rooms and overhead machinery spaces shall:
(e) Be labeled "ELEVATOR MACHINE ROOM", with letters not less than 51 mm (2 in) high.
2.7.5 Lighting, Temperature, and Humidity in Machine Rooms and Machinery Spaces.
Add new section 2.7.5.3 to read as follows:
2.7.5.3 A duplex receptacle rated at not less than 20A, 120V with ground fault circuit interrupter shall be provided in each machine room and machinery space. The receptacle shall not be used for permanently installed equipment.
2.7.8 Remote Machine and Control Rooms.
Delete and revise section 2.7.8.4 to read as follows:
2.7.8.4 A permanent two-way voice communication shall be provided between the lobby fire command station (where required or provided), the elevator car and elevator machine room, and/or control room.
SECTION 2.8
EQUIPMENT IN HOISTWAYS AND MACHINE ROOMS
2.8.1 Electrical Equipment and Wiring.
Revise section 2.8.1.2 to read as follows:
2.8.1.2 Only such electrical wiring, raceways, and cables used directly in connection with the elevator, including wiring for signals, for communication with the car, fire department communications equipment, for lighting, heating, air conditioning, and ventilating the car, for fire detecting systems, for pit sump pumps, and for heating and lighting the hoistway and/or machine room and equipment allowed in §2.14.1.9.1(d) shall be permitted to be installed inside the hoistway.
Delete and revise section 2.8.2.3 to read as follows:
2.8.2.3 Sprinkler systems are not permitted in control/machine rooms.
SECTION 2.11
PROTECTION OF HOISTWAY OPENINGS
2.11.1 Entrances and Emergency Doors Required. Revise section 2.11.1.1 to read as follows:
2.11.1.1 Hoistway Landing Entrances. All elevator hoistway-landing openings shall be provided with entrances that shall guard the full height and width of the openings. Entrances shall be at least 2030 mm (80 in.) in height and [800 mm (31.5 in.)] 915mm (36 in.) in width.
Revise Subsection (a) of 2.11.1.2 to read as follows:
2.11.1.2 Emergency doors in blind hoistways. Where an elevator is installed in a single blind hoistway, there shall be installed in the blind portion of the hoistway an emergency door at every third floor, but not more than 11 m (36 ft) from sill to sill, conforming to the following:
The clear opening shall be at least [700mm (28 in.)] 915mm (36 in.) wide and 2030 mm (80 in.) high.
2.11.2 Types of entrances.
Delete and revise Section 2.11.2.1 to read as follows:
2.11.2.1 Passenger elevators. For passenger elevators,entrances shall be one of the following types:
Horizontally sliding;
Horizontally swinging, single-section;
Hand-or power-operated vertically sliding that slide up to open.
Delete and revise Section 2.11.2.2 to read as follows:
2.11.2.2 Freight elevators. For freight elevators, entrances shall be one of the following types:
Horizontally sliding;
Swinging, single-section;
Center-opening, two-horizontally swinging, subject to restrictions of Section 2.11.2.3;
Vertically sliding biparting counterbalanced (see Section 2.16.4); or
Vertically sliding counterweighted, single or multisection.
2.11.6 Opening of hoistway doors. Revise Section 2.11.6.2 to read as follows:
2.11.6.2 Means shall not be provided for locking out the service doors at:
The top terminal landing;
The bottom terminal landing;
The designated sky lobby and sky lobby alternate [and alternate] landings for elevators equipped with Phase I Emergency Recall Operation, when Phase I is effective; [and]
Any landing for elevators equipped with Phase II Emergency In-Car Operation when Phase II is effective [.];
2.11.6.5 Elevator landings provided with a zero clearance vestibule [not to exceed 150 mm (6 in) from the elevator hoistway door] are permissible only when locking devices accessible from the car are installed exclusively on the door that separates the zero clearance vestibule from the occupied floor space.
2.11.7 Glass in hoistway doors.
Revise Sections 2.11.7.1, 2.11.7.1.1 and 2.11.7.1.2 to read as follows:
2.11.7.1 Vision panels. Manually operated or self-closing hoistway doors of the vertically or horizontally sliding type, for elevators with automatic or continuous-pressure operation, shall be provided with a vision panel. [Vision panels shall not be required at landings of automatic operation elevators where a hall position indicator is provided.] In multi doors, the vision panelis required in one only, but is permitted to be placed in all sections. All horizontally swinging elevator doors shall be provided with vision panels. Vision panels are permitted for any type of hoistway door. Vision panels shall not be required at the landing of automatic operation elevators equipped with horizontally side sliding car and hoistway doors.
Where required or used, vision panels shall conform to 2.11.7.1.1 through 2.11.7.1.7.
2.11.7.1.1 The area of any single vision panel shall not be less than [0.015 m2(24 in2)] 0.008 m2(12 in2), and the total area of one or more panels in any hoistway door shall not be more than [0.055 m2(85 in2)] 0.026 m2(40 in2).
2.11.7.1.2 Each clear panel opening shall reject a ball [150 mm (6in)] 102 mm (4 in.) in diameter.
2.11.11 Entrances, horizontal slide type.
Revise Subsection (a) of Section 2.11.11.6 to read as follows:
2.11.11.6 Bottom guides. Bottom guides shall conform to the following:
The bottom of each panel shall be guided by [one] two or more members.
2.11.15 Marking.
Add new text to Section 2.11.15.1 and revise to read as follows:
2.11.15.1 Labeling of tested assembly. In jurisdictions not enforcing the NBCC, 2.11.15.1.1 and 2.11.15.1.2 apply. Where required by this code, the entire entrance assembly shall be of an approved type.
SECTION 2.12
HOISTWAY-DOOR LOCKING DEVICES AND
ELECTRIC CONTACTS, AND
HOISTWAY ACCESS SWITCHES
Delete and revise the heading of Section 2.12 to read as follows:
SECTION 2.12
HOISTWAY-DOOR LOCKING DEVICES AND
HOISTWAY ACCESS SWITCHES AND
ELEVATOR PARKING DEVICES
2.12.3 Hoistway-door combination mechanical locks and electric contacts.
Delete Section 2.12.3 in its entirety.
Section 2.12.3 Reserved.
2.12.4 Listing/certification door locking devices and door or gate electric contacts.
Delete and revise Section 2.12.4.1 to read as follows:
2.12.4.1 Type tests. Each type and make of hoistway-door interlock, electric contact, and door or gate electric contact shall be of an approved type.
Delete and revise Subsection (b) of Section 2.12.4.3 to read as follows:
2.12.4.3 Identification marking.
(b) The approved agency's name, date of approval and identifying number or symbol;
Add new Section 2.12.6.2.6 to read as follows:
2.12.6.2.6 Elevator parking device.
Parking devices required. Existing elevators that are operated from within the car only shall have elevator-parking devices installed at every landing that is equipped with an unlocking device. On elevators that are not operated from within the car only, an elevator parking device shall be provided at one landing and may be provided at other landings. This device shall be located at a height not greater than 2.11 m (6 ft 11 in) above the floor. Parking devices are not required for elevators having hoistway doors that are automatically unlocked when the car is within the landing zone.
General design requirements.Parking devices shall conform to the following requirements:
They shall be mechanically or electrically operated.
They shall be designed and installed so that friction or sticking or the breaking of any springs used in the device will not permit opening or unlocking a door when the car is outside the landing zone of that floor.
Springs, where used, shall be of the restrained compression type, to prevent separation of the parts in case the spring breaks.
Delete and revise Section 2.12.7.3.2 to read as follows:
2.12.7.3.2 The car cannot be operated at a speed greater than 0.35 m/s (75 ft/min).
Delete and revise Section 2.13.2.1.2 to read as follows:
2.13.2.1.2 Collapsible car gates shall not be power opened.
SECTION 2.14
CAR ENCLOSURES, CAR DOORS AND GATES AND
CAR ILLUMINATION
2.14.2.1.1: Materials in their end use configuration, other than those covered by 2.14.2.1.2 through 2.14.2.1.6, shall conform to the following requirements, based on the tests conducted in accordance with the requirements of ASTM E 84, UL 723, or NFPA 255:
Delete and revise Subsection (a) of 2.14.2.5 to read as follows:
2.14.2.5 Vision panels. Vision panels are not required, but where used, shall:
Be of a total area of not more than 0.047 m2(72 in2), and contain no single glass panel having a width exceeding 101 mm (4 in.);
2.14.4 Passenger and freight car doors and gates, general requirements.
Revise Section 2.14.4.11 to read as follows:
2.14.4.11 Closed position of car doors or gates. Car doors or gates shall be considered to be in the closed position under the following conditions:
For horizontally sliding doors or gates, when the clear open space between the leading edge of the door or gate and the nearest face of the jamb does not exceed [50 mm (2 in.)] 25 mm (1 in.) except where car-doors are provided with a car door interlock(s), 10 mm (0.375 in.);
For vertically sliding counterweighted doors or gates, when the clear open space between the leading edge of the door or gate and the car platform sill does not exceed [50mm (2 in.)] 25mm (1 in.); and
For horizontally sliding center-opening doors, or vertically sliding biparting counterbalanced doors, when the door panels are within [50 mm (2 in.)] 25 mm (1 in.) of contact with each other, except where horizontally sliding center opening car door sare provided with a car door interlock(s), 10mm (0.375 in.).
2.14.7 Illumination of car and lighting fixtures. Revise Section 2.14.7.1.4 to read as follows:
2.14.7.1.4 Each elevator shall be provided with [an] a guarded electric light and convenience outlet fixture on the car top and under the car platform.
2.15.8 Protection of platforms against fire. All platform materials exposed to the hoistway shall be either:
Metal; or
Other materials that, in their end use configuration, conform to the following requirements, based on the tests conducted in accordance with the requirements of ASTM E 84, UL 723, NFPA 255, or CAN/ULC-S 102.2, whichever is applicable (see Part 9):
Add new text to Section 2.20.9.5 to read as follows:
2.20.9.5 Wedge rope sockets. Wedge socket assemblies shall be of a design as shown in Fig. 2.20.9.5, and shall conform to 2.20.9.2 and 2.20.9.3, and 2.20.9.5.1 through 2.20.9.5.6. Wedge rope sockets are not permitted on counterweighted winding drum machines.
2.21.1.2 Retention of weight sections. Means shall be provided to retain weights in place in the event of buffer engagement or safety application or if they become broken. Where tie rods are used, a minimum of two shall be provided and they shall pass through all weight sections. Tie rods shall be provided with a lock nut and a cotter pin at each end.
Counterweight material shall be steel,iron or lead only and shall have a minimum melting temperature of 620 °F.
2.21.4 Compensation of means:
Revise Section 2.21.4 to read as follows:
2.21.4 Compensation means. Except for safety hooks, where used, compensation means, such as compensating ropes or chains or other mechanical means and their attachments used to tie the counterweight and car together, shall be capable of withstanding, with a factor of safety of 5, any forces to which the means is subjected with the elevator at rest. The maximum suspended weight of compensation means with car or counterweight at the top of its travel and one half-total weight of tension sheave assembly, where used, shall be included. The factor of safety for compensation means shall be based on the proof load, breaking strength, or test reports.
SECTION 2.22
BUFFERS AND BUMPERS
2.22.4 Oil buffers.
Add new Subsections (a) and (b) to Section 2.22.4. 6 as follows:
2.22.4.6 Means for determining oil level. Oil buffers shall be provided with means for determining that the oil level is within the maximum and minimum allowable limits. Glass sight gauges shall not be used.
A fixed inclined ladder shall be provided where the top of the buffer cylinder is over 1524 mm (5 ft.) in height above the pit floor.
A fixed vertical or inclined ladder fitted with an inspection and maintenance platform with guard rails shall be provided where the top of the car buffer cylinder is over 2134 mm (7 ft.) from the pit floor.
Delete and revise Section 2.24.10 to read as follows:
2.24.10 Means for inspection of gears. Each gear case of geared machines shall have access to permit inspection of the contact surfaces of the gears.
SECTION 2.25
TERMINAL-STOPPING DEVICES
2.25.3 Final terminal-stopping devices.
Add new Subsection (d) to Section 2.25.3.1 to read as follows:
2.25.3.1 General requirements. Final terminal-stopping devices shall conform to 2.25.1 and the following:(d) Final limit switches and bracket shall be permanently secured and pinned.
< b>(d) Final limit switches and bracket shall be permanently secured and pinned.
Add new Subsections 3 and 4 to Section 2.26.1.4.1(c) to read as follows:
2.26.1.4.1 General requirements.
(c)Inspection operating devices shall:
Be of the continuous-pressure type;
Be labeled "UP" and "DOWN," respectively;
(d) A separate device of the continuous-pressure type labeled "ENABLE" shall be provided adjacent to the inspection operating devices; and
(e) The inspection operating devices shall become effective only when the "ENABLE" device is activated.
Delete and revise Section 2.26.1.4.2 to read as follows:
2.26.1.4.2 Top-of-car inspection operation. Top-of-car inspection operation shall conform to 2.26.1.4.1 and the following:
A stop switch (see §2.26.2.8) shall be permanently located on the car top and readily accessible to a person standing at the hoistway entrance normally used for access to the car top.
The transfer switch [see §2.26.1.4.1(b)] shall be located on thecar top and shall be so designed as to prevent accidental transfer from the "INSPECTION" to "NORMAL" position.
The inspection operating devices [see §2.26.1.4.1(c)] shall be permitted to be of the portable type provided that:
the "ENABLE" device [see §2.26.1.4.2(c)], and a stop switch, in addition to the stop switch required in §2.26.1.4.2(a) are included in the portable unit; and
the flexible cord is permanently attached so that the portable unit cannot be detached from the car top.
Separate additional devices of the continuous-pressure type shall be permitted to be provided on the car top to make power door opening and closing and automatic car-leveling operative from the top of the car for testing purposes.
2.26.2 Electrical protective devices:
Delete and revise Section 2.26.2.5 to read as follows:
2.26.2.5 Emergency stop switch. On all elevators, an emergency stop switch shall be provided in the car, and located in or adjacent to each car operating panel. When open ("STOP" position), this switch shall cause the electric power to be removed from the elevator driving-machine motor and brake. Emergency stop switches shall:
Be of the manually opened and closed type;
Have red operating handles or buttons;
Be conspicuously and permanently marked "STOP," and shall indicate the "STOP" and "RUN" positions; and
While opened, cause the audible device to sound (see §2.27.1.1.1).
Delete Section 2.26.2.21 in its entirety:
Section 2.26.2.21 Reserved.
SECTION 2.27
EMERGENCY OPERATION AND
SIGNALING DEVICES
2.27.1 Car Emergency signaling devices.
Add new text to Section 2.27.1.1.1 as follows:
2.27.1.1.1 A two-way communications means between the car and a location in the building that is readily accessible to authorized and emergency personnel shall be provided.Means shall be provided to enable two-way voice communication between the machine room and the interior of the car.
Delete and revise Section 2.27.2.4.3 to read as follows:
2.27.2.4.3 Means shall be provided adjacent to the selector switch (es) to indicate that the elevator is at the designated level with the doors in the normally open position.
Revise Sections 2.27.3.1.1,2.27.3.1.2 and 2.27.3.1.3 to read as follows:
2.27.3.1.1 A [three] two-position key-operated switch shall be:
Provided [only] at the designated level for each single elevator or for each group of elevators;
Labeled "FIRE RECALL" and its positions marked ["RESET," "OFF," and "ON"] "NORMAL" and "FIREMAN SERVICE" (in that order) [,with the "OFF" position as the center position]. The "FIRE RECALL" letters shall be a minimum of 5mm (0.25 in.) high in red or a color contrasting with a red background;
Located in the lobby within sight of the elevator or all elevators in that group and shall be readily accessible.
2.27.3.1.2 An additional key-operated "FIRE RECALL" switch, with two-positions, marked ["OFF" and "ON"] "NORMAL" and "FIREMAN SERVICE" (in that order), shall be permitted [only] at the building fire control station.
2.27.3.1.3 The switch(s) shall be rotated clockwise to go from [the "RESET" (designated level switch only), to "OFF" to "ON"] "NORMAL" to "FIREMAN SERVICE" positions. Keys shall be removable in the ["OFF" and "ON"] "NORMAL" and "FIREMAN SERVICE" positions.
Delete and revise Section 2.27.3.2 to read as follows:
2.27.3.2 Phase I fire alarm activation.
2.27.3.2.1 Smoke detectors. Except as set forth in subparagraph k of this paragraph, smoke detectors installed in accordance with subparagraphs a, b, c or d shall initiate Phase I emergency recall operation.
In buildings where a fire command station is not required or provided, a single smoke detector shall be installed in the ceiling of each elevator landing over the call button on each floor.
In buildings where a fire command station is required or provided, either of the following shall apply:
An analog addressable smoke detector employing alarm verification shall be installed in the ceiling of each elevator landing over the call button on each floor, or
Two (2) smoke detectors for cross zoning shall be installed in the ceiling of each elevator landing on each floor and spaced as follows:
In an elevator landing containing one (1) or two (2) elevators, the distance between smoke detectors shall be the width of the hoistway(s) but not greater than ten (10) feet.
In an elevator landing containing three (3) or more elevators, the distance between smoke detectors shall be the distance between the centerlines of the end elevators but not greater than twenty (20) feet.
Associated Elevators:
In associated elevator machine rooms of the buildings described in subparagraph (a) above, asmoke detector shall be installed.
In associated elevator machine rooms of the buildings described in subparagraph (b) above, either of the following shall be installed:
An analog addressable smoke detector employing alarm verification; or
At least two (2) smoke detectors for cross zoning spaced twenty (20) feet apart but not closer to the hoistway enclosure walls one-fourth distance of the width of the machine room.
A smoke detector shall be installed at the top of the hoistway(s) in Occupancy Group R-2 where afire alarm system is installed or required. Smoke detectors may be installed in any other hoistway and shall be installed in hoistways that are sprinklered.
Smoke detectors are not required in elevator landings at an unenclosed landing which is open to the outside air.
In buildings described in subparagraph (a) above, where a single smoke detector is installed in the elevator landing, the activation of a smoke detector in any elevator landing, other than the sky lobby, shall cause all automatic elevators servicing the floor on which the sensing device is activated to return nonstop to the designated or sky lobby level, except as modified by the commissioner.
In buildings described in subparagraph (b) above, where either an analog addressable smoke detector or two (2) smoke detectors for cross zoning are installed, the activation of either an analog addressable smoke detector or any one of the two smoke detectors for cross zoning in any elevator lobby shall annunciate at the fire command station only with floor identification. After verification of an alarm condition either from the analog addressable smoke detector or from the first detector of cross zoning detectors, the completion of the delayed time period of an analog addressable smoke detector or the activation of both smoke detectors for cross zoning in any elevator lobby, other than the sky lobby, shall cause all automatic elevators servicing the floor on which the sensing device is activated to return nonstop to the designated or sky lobby level, except as modified by the commissioner.
In associated machine rooms described in Item 1 of subparagraph (c) above, the activation of the smoke detector in the elevator machine room shall cause all automatic elevators having any equipment located in that machine room, and any associated elevators of a group automatic operation, to return nonstop to the designated or sky lobby level, except as modified by the commissioner.
In associated machine rooms described in Item 2 of subparagraph (c) above, where either an analog addressable smoke detector or two (2) smoke detectors for cross zoning are installed, the activation of either an analog ad-dressable smoke detector or any one of the two smoke detectors for cross zoning in any elevator machine room shall annunciate at the fire command station only with floor identification. After verification of an alarm condition either from the analog addressable smoke detector or from the first detector of cross zoning detectors, the completion of the delayed time period of an analog addressable smoke detector or the activation of both smoke detectors for cross zoning in any elevator machine room shall cause all automatic elevators having any equipment located in that machine room, and any associated elevators of a group automatic operation, to return nonstop to the designated or sky lobby level, except as modified by the commissioner.
In addition to the activation of mechanical ventilation if provided { §2.1.4}, the activation of a smoke detector in any elevator hoistway shall cause all automatic elevators having any equipment located in the hoistway and any associated elevators of a group automatic operation, to return nonstop to the designated or sky lobby level.The operation of this subparagraph shall conform to the requirements of §2.27.3.1.
When the lowest landing of elevators is above the designated level, such as the sky lobby level, the activation of smoke detectors in the sky lobby level or the activation of the waterflow alarm {§2.27.3.2.2} on the sky lobby floor shall cause such elevators to return nonstop to a floor two stories above the sky lobby level or, in the absence of a stop at that floor, to the nearest landing above the sky lobby level.
Elevators shall react only to the first smoke detectorzone that is activated for that group.
Activation of smoke detectors to initiate elevator recall shall override any automatic programming for car stops but shall not affect the other elevator safety circuits.
The following buildings shall be exempt from the requirements of this section:
Buildings where the main use or dominant occupancy is classified in Occupancy Group R-2, except that they shall comply with the requirements of §2.27.3.2.1(d).
Existing buildings with occupied floors at or below 22 860 mm (75 ft) above the lowest Fire Department vehicle access level classified in OccupancyGroup E that have at least one elevator available at all times for immediate use by the Fire Department and that are in compliance with the Fire Department's regulations governing "life safety requirements for schools with students having physical disabilities."
Existing office buildings, one hundred feet or more in height and existing high-rise buildings as defined by the New York City Building Code equipped throughout with an automatic sprinkler system including a waterflow alarm.
2.27.3.2.2 Sprinkler waterflow alarm. In a building equipped throughout with an automatic sprinkler system, the activation of the waterflow alarm shall cause Phase I emergency recall operation to be initiated (§2.27.3.1).
Delete and revise Section 2.27.3.3 to read as follows:
2.27.3.3 Phase II emergency in-car operation. A three-position ("NORMAL," "HOLD," and "FIREMAN SERVICE" in that order) key-operated switch shall be provided in an operating panel in each car. The switch shall be rotated clockwise to go from the "NORMAL" to "HOLD" to "FIREMAN SERVICE" position. It shall become effective only when the designated or sky lobby level Phase I switch { §2.27.3.1 } is in the "FIREMAN SERVICE" position or asmoke detector or water-flow alarm has been activated, and the car has returned to the designated or sky lobby level by Phase I operation. The key shall be removable in "NORMAL" or "HOLD" position. The "NORMAL," "HOLD," and "FIREMAN SERVICE" positions shall not change the operation until the car is at a landing with the doors in the normal open position.
2.27.3.3.1 When the Phase II switch is in the "FIREMAN SERVICE" position, the elevator shall be on Phase II operation, and the elevator shall operate as follows:
The elevator shall be operable only by a designated person in the car.
All corridor call buttons and directional lanterns shall remain inoperative. Car position indicators, where provided, shall remain in service. Hall position indicators, where provided, shall remain inoperative except at the designated level, sky lobby level and the fire control station, where they shall remain in service for Fire Department operations.
Only a continuous pressure door open button shall control the opening of power-operated doors. If the button is released prior to the door reaching the normal open position, the doors shall automatically close. §2.13.3.3, §2.13.4.2.1(b)(2), and §2.13.4.2.1(c) do not apply. On cars with two entrances, separate door-open buttons shall be provided for each entrance if both entrances can be opened at the same landing,
Open power-operated doors shall be closed only by momentary pressure on the door close button. On cars with two entrances, a separate door-close button shall be provided for each entrance if both entrances can be opened at the same landing.
Opening and closing of power operated car doors or gates that are opposite manual swing or manual slide hoistway doors shall conform to the requirements of §2.27.3.3.1(c) and (d). Door opening and closing buttons shall be provided in the car-operating panel.
Door reopening devices rendered inoperative, per §2.27.3.1.6(e) shall remain inoperative. Full speed closing is permitted. Corridor door opening and closing buttons, if provided, shall be rendered inoperative.
Every car shall be provided with a button marked "CALL CANCEL" located in the same car operating panel as the Phase II switch, which shall be effective during Phase II operation. When activated, all registered calls shall be canceled and a traveling car shall stop at or before the next available landing.
Floor selection buttons shall be provided in the car to permittravel to all landings served by the car and they shall be operative at all times. Means that prevent the operation of the floor selection buttons or door operating buttons shall be rendered inoperative.
A traveling car shall stop at the next available landing for which a car call was registered. When a car stops at a landing, all registered car calls shall be cancelled.
2.27.3.3.2 When the Phase II switch is in the "HOLD" position, the elevator shall be on Phase II operation. The car shall remain at the landing with its doors open. The door close buttons shall be inoperative.
2.27.3.3.3 When the Phase II switch is in the "NORMAL" position, the elevator is not at the designated or sky lobby level and Phase I is in effect, the elevator shall operate as follows.
Automatic power-operated horizontally-sliding doors shall close automatically and the car shall revert to Phase I operation { §2.27.3.1 } upon completion of door closing. All door reopening devices shall remain inoperative. Door open buttons shall remain operative. Full speed closing is permitted. If the Phase II switch is turned to the "FIREMAN SERVICE" or "HOLD" position prior to the completion of door closing, the doors shall reopen.
Elevators having power operated vertically sliding doors shall have corridor door open and close buttons rendered operative. All door reopening devices shall remain inoperative. Door closing shall be in accordance with the requirements of §2.27.3.3.1(d) Full speed closing is permitted. If the Phase II switch is turned to the "FIREMAN SERVICE" or "HOLD" position prior to the completion of door closing, the doors shall reopen. The car shall revert to Phase I operation { §2.27.3.1 } upon completion of door closing.
Elevators having manual doors shall revert to Phase I operation {§2.27.3.1} upon completion of door closing.
2.27.3.3.4 When the Phase II switch is in the "NORMAL position and the car is not at the designated or the sky lobby level, and Phase I is not in effect, the car shall remain at the landing with the doors open and door-close buttons inoperative and shall remain in Phase II.
2.27.3.3.5 Elevators shall be removed from Phase II operation only when:
The Phase II switch is in the "NORMAL" position and the car is at the designated or sky lobby level with the doors in the normal open position; or
The Phase II switch is in the "NORMAL" position when Phase I is in effect at the designated or sky lobby level with the doors in the normal open position.
2.27.3.3.6
For all elevators, applications filed after March 12, 1991 (the effective date of adoption of Cal #1 1-91-BCR), that propose the installation, alteration or change of controller, elevator machinery and any other work, excluding minor alteration and ordinary repairs, and applications filed for new elevators, the cost of which exceeds $10,000 per car over 12-month period, shall comply with the requirements of this subdivision.
In elevators complying with the requirements of paragraph (a) above, a 3 position switch labeled "NORMAL," "HOLD," and "FIREMAN SERVICE" shall be required to replace the existing 2 position switch ("NORMAL" and "FIREMAN SERVICE"). The new "HOLD" position shall be marked by engraving or by affixing a permanent label to the operating panel of the elevator.
Delete and revise Section 2.27.3.4 to read as follows:
2.27.3.4 Interruption of power. Upon the resumption of power following a power interruption, the car shall move in the down direction to designated or sky lobby level. Restoration of electrical power following a power interruption shall not cause any elevator to be removed from Phase I or Phase II operation.
Delete and revise Section 2.27.4.1 to read as follows:
2.27.4.1 Phase I emergency recall operation. A two-position key-operated switch shall be provided at the designated or the sky lobby level only for each single elevator or for each group of elevators. The two-position switch shall be "NORMAL" and "FIREMAN SERVICE" (in that order). The commissioner with the concurrence of the fire commissioner may allow an additional two-position key-operated switch marked "NORMAL" and FIREMAN SERVICE" (in that order) at another location. However, it shall not affect Phase I operation if the designated-level or sky lobby level smoke detector or waterflow alarm has been activated. The switch(es) shall be rotated clockwise to go from the "NORMAL" to "FIREMAN SERVICE" position. All keys shall be removable from any position.
No device, other than Phase I switch(es), smoke detectors in the elevator lobbies, machine room, or hoistway, or a waterflow alarm in lieu of smoke detectors in the elevator lobbies, shall initiate Phase I operation.
When all switches are in the "NORMAL" position, normal elevator service shall be retained and operation from the smoke detectors or waterflow alarm required shall be functional.
When a Phase I switch is in the "FIREMAN SERVICE" position, a visual and audible signal shall be provided to alert the attendant to return nonstop to the designated or sky lobby level. The visual signal shall read "FIRE RECALL —RETURN TO" {insert level to which the car should be returned (the designated level or sky lobby level)}. The smoke detectors or waterflow alarm shall be activated when Phase I is in effect.
Delete and revise Section 2.27.4.2 to read as follows:
2.27.4.2 Phase I smoke detectors or waterflow alarm devices activation. Smoke detectors shall be installed in accordance with the requirements of § 2.27.3.2 Phase I operation and shall be initiated when either any smoke or waterflow alarms are activated.
When the lowest landing of elevators is above the designated level, such as the sky lobby level, the activation of smoke detectors or a waterflow alarm in the sky lobby or sky lobby floor shall cause such elevators to return nonstop to a floor two stories above the sky lobby level or in the absence of a stop at that floor, to the nearest landing above the sky lobby level.
Elevators shall react only to the first smoke detectorzone that is activated for that group.
Activation of smoke detectors to initiate elevator recall shall override any automatic programming for car stops but shall not affect the other elevator safety circuits.
The buildings described in §2.27.3.2(1)(k) and meeting its requirements and buildings equipped throughout with an automatic sprinkler system are exempt from the requirements of this section.
2.27.5 Fire-fighters' emergency operation automatic elevators with designated attendant operation.
Delete and revise Section 2.27.5.2 to read as follows:
Elevators parked at a floor shall conform to the requirements of §2.27.3.1. At the completion of a time delay of not less than 15 seconds nor more than 60 seconds, elevators shall conform to the requirements of §2.27.3. There shall be no delay when the car is at the designated level.
A moving car shall conform the requirements of § 2.27.3.
Add three new Subsections 2.27.5.3.1, 2.27.5.3.2 and 2.27.5.3.3 to read as follows:
All patient elevator cars equipped with the special control function shall override normalautomatic operating modes for immediate recall of the patient elevator(s) to the landing at which the call is registered.
A visual and audible signal shall be activated within the patient elevator car to alert the passengers and/or attendant operator that the "hospital emergency service" function has been activated.
Upon arrival at the registered call landing, power operated doors shall open automatically and remain in the open position for a predetermined adjustable time period to allow the authorized personnel sufficient time to activate the "in-car" special operation function.
If the Phase I (§2.27.3.1) recall mode is initiated while the elevator is under "hospital emergency service" recall mode and "in-car" hospital emergency service is not activated, the elevator shall revert to Phase I (§2.27.3.1) operation.
Hospital emergency servicecorridor recall shall not override fire emergency Phase I (§2.27.3.1) or Phase II (§2.27.3.3) operation in effect.
The patient elevator(s) shall not be recalled under Phase I (§2.27.3. 1) operation after the activation of "in-car" operation mode.
Doors shall remain open until the authorized person registers the car call and initiates the door closing function.
The patient elevator shall travel directly to the selected landing, overriding normalcorridor call demand or Phase I (§2.27.3.1) recall and shall automatically open the doors upon the arrival at the selected landing, except when the smoke detector(s) are activated on the selected landing or the waterflow alarm is activated on that floor. In such case, before the patient elevator has reached the selected landing, the patient elevator shall stop at a floor two stories below the selected landing or in the absence of a stop at that floor, at the nearest landing below the selected landing.
When the patient elevator reaches the selected floor and the smoke detector(s) are activated on that landing or the waterflow alarm is activated on that floor before the doors are open, the patient elevator, without opening the doors, shall travel to a floor two stories below the selected landing or in the absence of a stop at that floor, to the nearest landing below the selected landing.
Doors shall remain open with the audible and visual signal functioning until the "in-car" switch is turned to the "NORMAL" position or for a predetermined adjustable time period to allow the removal of patients from the car and the patient elevator is placed into automatic, attendant or Phase I (§2.27.3. 1) if in effect, operating mode.
Delete and revise Section 2.27.8 to read as follows:
2.27.8 Switch keys. The switches required by § 2.27.2 through § 2.27.5 for all elevators in a building shall be operable only by a citywide standard key 2642. The citywide standard key shall be designed in accordance with the requirements of the Fire Department and shall be obtained only through Fire Department authorization. Citywide standard keys shall be kept on the premises by a person responsible for the maintenance and operation of the elevators in a location readily accessible to authorized persons in an emergency, but not where they are available to the public.
SECTION 2.29
IDENTIFICATION
Delete and revise Section 2.29.1 to read as follows:
2.29.1 Identification of equipment. Each elevator shall be assigned a unique alphabetical or numerical identification, a minimum of 6 mm(1/4 in.) in height. The identification number shall be applied to the following locations:
The driving machine;
MG and/or transformers set;
Controller;
Selector;
Governor;
Main line disconnect switch;
The crosshead, or where there is no crosshead, the car frame, such that it is visible from the top of the car;
The car operating panel, minimum of 13 mm (0.5 in.) in height;
Adjacent to or on every elevator entrance at the designated level, minimum of 75mm (3 in.) height; and
Each bank of elevators shall be identified by an alphabetic letter.
Add new Section 2.29.1.1 to read as follow:
2.29.1.1 New York City identification number. Each elevator shall be assigned a unique numerical identification a minimum of 6mm (1/4 in.) in height. The city identification number shall be applied to the following locations:
The driving machine;
MG and/or Transformers set;
Controller;
Main line disconnect switch;
The crosshead, or where there is no crosshead, the car frame, such that it is visible from the top of the car;
3.26.3 Anticreep and leveling operation. Revise Section 3.26.3.1.2 to read as follows:
3.26.3.1.2 The anticreep device shall maintain the car within [25mm (1 in.)] 13 mm (1/2 in) of the landing irrespective of the position of the hoistway door.
(b) The inside net platform area shall not exceed 18 ft2 (1.67 m2) and in no event shall be less than 1219mm by 1219 mm(4 ft by 4 ft) with a minimum 812mm (32 in.) clear door opening. The car operating panel shall be on the strike wall.
Delete and revise Section 6.1.3.3.5 it to read as follows:
6.1.3.3.5 Clearance between skirt and step. The clearance on either side of the steps between the step and the adjacent skirt panel shall not be more than 4 mm (0.16 in.), and the sum of the clearances on both sides shall be not more than 7 mm (0.28 in.).
Add new text to Subsection (c) of 6.1.3.3.6 to read as follows:
(c) The exposed surfaces of the skirt panels adjacent to the steps shall be smooth and made from a low friction material, or permanently treated with a friction-reducing material. Untreated surfaces, such as porcelain, enameled steel bronze, or stainless steel, are not acceptable.
Delete Section 6.1.3.3.7 in its entirety:
6.1.3.3.7 Reserved.
Delete and revise Section 6.1.3.3.8 to read as follows:
6.1.3.3.8 Skirt deflector devices. Deflector devices shall be required and extend from skirt panels parallel to the escalator path of travel. Means to secure such deflector devices are required to be on the exposed surface of the skirt. Any exposed fastener heads shall be of the tamper-resistant type and flush to within 1 mm (0.04 in.).
Revise Section 6.1.3.5.4 to read as follows:
6.1.3.5.4 Clearance between step threads. The maximum clearance between step treads on the horizontal run shall be 6 mm (0.25 in.). (See Appendix I, Fig. I7 [I6].)
Delete and revise Section 6.1.6.3.3 to read as follows:
6.1.6.3.6 Skirt obstruction device. Means shall be provided to cause the electric power to be removed from the escalator driving machine motor and brake, if an object becomes caught between the step and the skirt as the step approaches the upper comb plate, intermediate device or lower comb plate. On units having a run of 6096mm (20 ft.) or more, intermediate devices shall be provided on both sides of the escalator with devices located at intervals of 3048 mm (10 ft.)or less. The activation of an intermediate device shall stop the escalator at a rate not greater than 914 mm (3 ft.) per second square in the direction of travel. The upper and lower comb plate devices shall be located so that the escalator will stop before that object reaches the comb plate. The activation of any skirt device shall stop the escalator when a load equal to the brake rated load is applied while the escalator is running.
Revise Section 6.1.6.3.13 to read as follows:
6.1.6.3.13 Comb-step impact devices. Devices shall be provided that will cause the opening of the power circuit to the escalator driving machine motor and brake if either:
A horizontal force not greater than 1780 N (400 lbf) in the direction of travel is applied at either side, or not greater than 3560 N (800 lbf) applied at the center of the front edge of the comb plate; or
A resultant vertical force not greater than [670 N (150 lbf)] 268 N (60 lbf) in the upward direction is applied at the center of the front of the comb plate.
Revise Section 6.2.6.3.11 to read as follows:
6.2.6.3.11 Comb-pallet impact devices. Devices shall be provided that will cause the opening of the power circuit to the moving walk driving-machine motor and brake if either:
A horizontal force not greater than 1780 N (400 lbf) in the direction of travel is applied at either side, or not greater than 3560 N (800 lbf) applied at the center of the front edge of the comb plate; or
A resultant vertical force not greater than [670 N (150 lbf)] 268 N (60 lbf) in the upward direction is applied at the center of the front of the comb plate. These devices shall be of the manual-reset type.
Delete and revise Section 7.5.12.1.5 to read as follows:
7.5.12.1.5 The requirements of §2.26.2.5 do not apply. An emergency stop switch (switches) conforming to §2.26.2.5(a), (b), and (c) shall be provided to stop operation of the material lift, and the door and gate operation (if power operated). The emergency stop switch shall be located in each hall station.
Delete and revise Section 7.5.12.1.10 to read as follows:
7.5.12.1.10 The requirement of §2.26.2.15 applies.
Add new Note (p) to Section 8.1.2 to read as follows:
(p)The requirements of §2.14.1.10 and §5.1.11.1.2(d), side emergency exit doors apply.
8.1.4 Group 3: Emergency operation.
Delete and revise Section 8.1.4 to read as follows:
8.1.4 Group 3: Emergency operation. Group 3 covers access or operation of equipment by fire fighters and emergency personnel. This key shall be a citywide standard key 2642 as defined by the New York City Fire Department.
SECTION 8.4
ELEVATOR SAFETY REQUIREMENTS FOR
SEISMIC RISK ZONE 2 OR GREATER
8.4.4 Car enclosures, car doors and gates and car illumination.
8.6.4.10 Refastening or resocketing of car hoisting ropes on winding-drum machines.
Delete and revise Section 8.6.4.10.1 to read as follows:
8.6.4.10.1
The hoisting ropes of elevators having winding-drum driving-machines with 1:1 roping, if of the babbitted rope socket type, shall be resocketed at intervals no longer than:
1 year, for machines located over the hoistway;
2 years, for machines located below or at the side of the hoistway;
In addition to the foregoing requirements, rope fastenings shall be resocketed when an inspection reveals any evidence of failure at the shackle regardless of the period of time since last re-shackling.
Where auxiliary rope-fastening devices conforming to the requirements of §2.20.10 or where car hoist ropes with an additional approved type emergency clamping devices are installed, refastening at the period specified is not required provided that, where such devices are installed, all hoisting ropes shall be refastened on the failure or indication of failure of any rope fastening. Wedge clamp schackles shall not be used on drum machines.
Where the elevator is equipped with adrumcounterweight, the fastenings shall be examined for fatigue or damage at the socket. Where fatigue or damage is detected, the ropes shall be refastened in conformance with §8.6.4.10.2.
Delete and revise Section 8.6.4.10.3 to read as follows:
8.6.4.10.3 Tags. A legible metal tag shall be securely attached through one of the tapered rope sockets during each resocketing, (as shown in the diagram below) and shall bear the following information:
The name of the person or firm who performed the resocketing and;
The date on which the rope was resocketed. The material and marking of the tags shall conform to §2.16.3.3, except that the height of the letters and figures shall be not less than 1.5 mm (0.0625 in.).
Delete and revise Section 8.7.2. 13, Subsection (c) to read as follows:
8.7.2.13 Door reopening device.
(c)When fire-fighters' emergency operation is provided, door reopening devices and door closing during Phase I and Phase II shall comply with the requirements applicable at the time of installation or alteration.
8.7.2.14 Car enclosures, car doors, and gates and car illumination.
Revise Section 8.7.2.14.1 to read as follows:
8.7.2.14.1 Where an alteration consists of the installation of a new car, the installation shall conform to §2.12.6, §2.14, §2.15, and §2.17 (see also §8.7.2.15.1).
Delete and revise Subsection (e) of Section 8.7.2.14.2 to read as follows:
8.7.2.14.2
(e)Side emergency exits may be permanently fixed in the closed position provided that the corresponding side emergency exit on an adjacent car shall also be fixed in the closed position. The installation shall conform to §2.12.6.
Revise Section 8.7.2.14.3, Subsection (b)(2) to read as follows:
(4)Where the only hoistway alteration is the decrease in travel at the upper end of the travel, the installation shall be modified as follows:
Terminal stopping devices shall be provided based on the new top terminal landing location and the final limit switch shall be of the manual reset type.
A key controlled switch shall be provided in accordance with §8.1.5 (i.e., Group 4) requirements to by-pass the new top terminal stopping devices, when the elevator transfer switch is placed in the top-of-car inspection operation position, for access to the hoistway above the terminal landing.
The switch shall be manually operated, be labeled "Terminal By-Pass," and shall have two positions; by-pass and normal.
The switch shall be located in the hoistway, in the vicinity of the terminal limits and shall be accessible to a person standing on the car top. The car transfer switch shall not be removed from the top-of-car inspection operation position until the terminal limit by-pass switch is placed in the Normal position.
Existing terminal stopping devices shall remain functional. The hoistway door electro-mechanical safety interlocks shall remain in the safety circuit and locked with door panel(s) separately secured in closed position on the hoistway side.
The car operating panel shall be removed with associated labeling and signaling.
Where a driving machine is installed as part of an alteration, the installation shall conform to §2.7.2.2, §2.9, §2.10.1, §2.19, §2.20, §2.24, and §2.26.8. The requirements of §2.7.2.2 and §2.19 shall apply only to the extent that the existing installation permits.
Where a controller is installed as part of an alteration, it shall conform to §2.22, §2.25, §2.26.1.4, §2.26.1.5, §2.26.4 through §2.26.9, and §2.27.2 through §2.27.8.
Revise Subsection 8.7.2.27.5(e) to read as follows:
8.7.2.27.5 Change in type of motion control.
(e) Car overspeed protection and unintended movement protection shall conform to §2.19 to the extent that the existing installation permits. Where hoisting machinery is retained or altered in such a way that makes the installation of an emergency braking system per 2.19.3 impossible, conformance with §2.19 is not required.
SECTION 8.8
WELDING
8.8.1 Qualification of welders. Revise Section 8.8.1 read as follows:
8.8.1 Qualification of welders. Where required elsewhere in this code, welding of parts, except for tack welds later incorporated into finished welds, shall be undertaken:
by welders qualified in accordance with the requirements of Section 5 of ANSI/AWS D1.1, whereby the welders shall be qualified by the manufacturer or contractor; a professional consulting engineer; or a recognized testing laboratory; or
by a fabricator qualified to the requirements of CSA W47.1, whichever is applicable (see Part 9), and
8.10.1 General requirements for acceptance inspections and tests.
Delete and revise Section 8.10.1.1.3 to read as follows:
8.10.1.1 Persons authorized to make inspections and tests.
8.10.1.1.3 The inspector shall be a special inspector who meets the qualifications prescribed by rule of the department.
8.10.2. Inspection and test requirements for new installations
Delete and revise Subsection (o) of Section 8.10.2.2.2 to read as follows:
8.10.2.2.2 Machine room.
(o) Braking System. For passenger elevators and all freight elevators, the brake shall be tested for compliance with applicable requirements. A test of the brake shall be made with 125 percent of load. When the car returns to one of the lower landings, the main line switch shall be pulled while the car is running at inspection speed to ensure the brake has set and holds the load. The driving machine shall safely lower, stop, and hold the car with this load. Freight elevators of class C-2 loading shall sustain and level the elevator car. (§2.16.6) (Item §2.15 of A17.2).
Clearance between skirt and steps [§6.1.3.3.5 or §6.2.3.3.5(a), and §6.2.3.3.6(a)].
Height above step [§6.1.3.3.6(a) or §6.2.3.3.5(b), and §6.2.3.3.6(b)].
Deflection [§6.1.3.3.6(b) or §6.2.3.3.6(c)].
Smoothness [§6. 1.3.3.6(c) or §6.2.3.3.6(d)].
8.10.5 Acceptance inspection and tests of other equipment.
Delete Section 8.10.5.3 in its entirety.
8.10.5.3 Reserved.
SECTION 8.11
PERIODIC INSPECTIONS AND TESTS
8.11.1 General requirements for periodic inspections and tests.
Delete and revise Section 8.11.1.1 to read as follows:
8.11.1.1 Persons authorized to make inspections and Tests. The inspector shall be a special inspector who meets the qualifications prescribed by rule of the department.
Delete and revise Section 8.11.1.3 to read as follows:
8.11.1.3 Periodic inspection and test frequency. See Chapter 3 of Title 28 of the Administrative Code.(NOTE: Required intervals for periodic inspections and tests can be found in Table N1 as modified below in this appendix)
Table [8.11.1.3] N1
REQUIRED INSPECTION AND TEST INTERVALS IN "MONTHS"
8.11.1.4.1 Elevators not in use but available for service. Elevators not in use but available for service are those elevators whose power feed line has been disconnectedby opening the main line switch. All required tests shall be regularly performed and a periodic inspection shall be made, and fees shall be paid pursuant to this code. An elevator inspector shall verify that these tests and inspections are being performed, and that the power was interrupted.
8.11.1.4.1.1 Elevators placed out of service (dismantled). Elevators placed out of active service by dismantling shall meet the requirements for installations placed out of service. In addition, an application shall be filed with the department and an inspection fee charged. Thereafter, one (1) additional inspection per year shall be made to verify that the status is unchanged and fees shall be paid for such inspection. Before the installation is put back in service,an application shall be filed with the department. For access to the bottom of the hoistway, the requirements of §8.11.1.4.1.2(b)(4) shall apply.
8.11.1.4.1.2 Elevators removed and permanently discontinued — one elevator shaftway. When a single elevator with one elevator shaftway is removed and permanently discontinued, an application shall be filed with the department and inspection fees charged. Such process shall meet the following requirements:
If it is proposed to extend the floor at every story of the building, the new construction shall be the same or of similar construction as the existing adjacent floor and of equivalent or better fire resistive rating. All hoistway equipment shall be completely removed; rails may remain.
All hoistway equipment shall be completely removed; rails may remain. Except as provided in Item 4, all door and window assemblies opening onto masonry shaftway and masonry enclosed associated machine rooms shall be completely removed and the open space so created shall be filled with the same or similar material of equal thickness and of equivalent or better fire-restive rating as the adjacent masonry.
Except as provided in Item 3, all door and window assemblies opening onto the hoistway shaft that were originally enclosed with an open wire screen and subsequently enclosed with other than masonry units (i.e., metal lath and plaster or transit boards) shall remain. Such door and window assemblies shall be fastened in a closed position and shall be adequately welded or bolted shut. The assembly shall be enclosed in material of equal or similar thickness of equivalent or better fire-resistive rating as the adjacent enclosure.
The sidewalk elevator door at the street level shall be fastened in a closed position and shall be adequately welded shut. The underside of such door shall be properly reinforced and supported by steel beams and columns to support the same loading as the sidewalk.
Fire-fighter access to the bottom of the hoistway (elevator pit) shall be provided through the door assembly of the pit door and shall meet the following requirements:
If the machine room is located at or near the level of the bottom of the shaftway and is so located that access to the bottom of the shaftway is readily available through the machine room, the door to the machine room shall be kept closed with a heavy-duty dead bolt locking device.
If the machine room is located other than at or near the level of the bottom of the shaftway or the bottom of the shaftway is not otherwise readily accessible through the machine room, the lowermost door opening onto the shaftway shall be kept closed with a heavy-duty dead bolt locking device. A conspicuous sign of 26mm (1 in.) block letters with contrasting background permanently affixed to the door and shall read "HOISTWAY."
The key to the locking device required in Items (i) and (ii) above shall be kept by the building superintendent and shall be readily available to the commissioner or the commissioner's representative and to fire fighters.
The ventilation opening (smoke hole) in the flooring provided at the top of the hoistway immediately below the sheaves or at the level of the top of the machine room floor beams and the ventilation opening at the exterior portion of the machine room shall be maintained.
All electric service to the elevator hoistway and machine room shall be disconnected outside the confines of the elevator hoistway and machine room.
8.11.1.4.1.3 Elevators removed and permanently discontinued—multielevator shaftway. When a single elevator in multielevator shaftway is removed and permanently discontinued, an application shall be filed with the department and inspection fees charged. Such process shall meet the following requirements:
If it is proposed to extend the floor at every story of the building, the new construction shall be the same or of similar construction as the existing adjacent floor and of equivalent or better fire resistive rating. All hoistway equipment for the discontinued elevator shall be completely removed; rails may remain. The shaft enclosure shall be rearranged so that the remaining operating elevators are properly enclosed to maintain the integrity of the shaftway.
All hoistway equipment for the discontinued elevator shall be completely removed; rails may remain. All door assemblies serving the discontinued elevator, openings onto masonry shaftway shall be completely removed and the open space so created shall be filled with the same or similar material of equal thickness of equivalent or better fire-resistive rating as the adjacent masonry.
All door assemblies serving the discontinued elevator, opening onto the hoistway shaft that were originally enclosed with an open wire screen and subsequently enclosed with other than masonry units (i.e. metal lath and plaster or transite boards), shall remain. Such door assemblies shall be fastened in a closed position and shall be adequately welded shut. The assembly shall be enclosed in material of equivalent or better fire resistive rating as the adjacent enclosure.
8.11.1.4.2.1 Escalators not in use but available for service. Escalators not in use but available for service are those escalators whose power feed lines have been disconnected from the main line disconnect switch and whose entrances have been barricaded. All required tests shall be regularly performed and a periodic inspection shall be made, and fees shall be paid pursuant to this code. An elevator inspector shall verify that these tests and inspections are being performed, and that the power was interrupted.
8.11.1.4.2.2 Escalators discontinued or placed out of service. Escalators discontinued or placed out of service shall comply with § 8.11.1.4.2.1. An application shall be filed with the department and an inspection fee charged. Thereafter, one (1) additional inspection per year shall be made to verify that the status is unchanged and fees shall be paid for such inspection. Before the installation is put back in service, it shall be subject to all of the routine and periodic inspections and tests required by this code.
8.11.1.4.2.3 Escalators removed and permanently discontinued. An application shall be filed with the department and inspection fees charged. The escalator steps, newels, rails, all wire cables, and other equipment and machinery shall be completely removed. An opening created by the removal of the escalator shall be filled with new construction of the same or similar construction as the exist-ing adjacent floor and of equivalent or better fire restive rating.
8.11.1.4.3.1 Moving walks not in use but available for service. Moving walks not in use but available for service are those moving walks whose power feed lines have been disconnected from the main line disconnect switch and whose entrances have been barricaded. All required tests shall be regularly performed and a periodic inspection shall be made and fees charged. An elevator inspector shall verify that these tests and inspections are being performed, and that the power was interrupted.
8.11.1.4.3.2 Moving walk discontinued or placed out of service. Moving walks discontinued or placed out of service shall meet the requirements of § 8.11.1.4.3.1 except for periodic inspection. An application shall be filed with the department and inspection fees charged. Thereafter, one additional inspection per year shall be made to verify that the status is unchanged and fees shall be paid for such inspection. Before the installation is placed back in service, it shall be subject to all of the routine and periodic inspections and tests required by this code.
8.11.1.4.3.3 Moving walk removed and permanently discontinued. An application shall be filed with the department and inspection fees charged. The moving walk tread ways, newels, rails, all wire cables, and other equipment and machinery shall be completely removed. The truss may remain. An opening created by the removal of the moving walk shall be covered by new construction of the same or similar construction as the existing adjacent floor and of equivalent or better fire resisting rating.
Delete and revise Section 8.11.1.6 to read as follows:
8.11.1.6 Test tags. A metal test tag with the test date, the category number requiring the test, and the name of the person or firm performing the test shall be installed in the machine room and at the vicinity of the lower starting station of escalators and moving walks for all Category 1, 3 and 5 tests.
Add new language to Section 8.11.2.3.4 to read as follows:
8.11.2.3.4 Braking system. For passenger elevators and all freight elevators, the brake shall be tested for compliance with applicable requirements. The load shall be placed in the car as shown in Table 8.11.2.3.4 and the car run to the lowest landing by normal operating means. The driving machine shall safely lower, stop and hold the car with this load. Freight elevators of Class C-2 loading shall sustain and level the elevator car.
A test of the brake shall be made in accordance with§8.10.2.2.2 (o).
Delete Section 8.11.4.2.19 in its entirety.
Section 8.11.4.2.19 Reserved.
Delete and revise Section 8.11.4.2.20 to read as follows:
8.11.4.2.20 Clearance between step and skirt. Escalators installed under ASME A17. 1d—2000 shall be tested as follows:
The clearance between step and skirt shall be taken at each step. These measurements shall be made independently on each side of the escalator.
As referenced in section 3001.2 of the New York City Building Code, the provisions of ASME B20.1—03 shall be modified in accordance with this chapter. The section numbers correlate to those in the referenced ASME standard. Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to this standard in accordance with Section 28-103.19 of the Administrative Code.
This Standard applies to the design, construction, installation, maintenance, inspection, and operation of conveyors and conveying systems in relation to hazards. The conveyors may be of the bulk material, package, or unit handling types where the installation is designed for permanent, temporary, or portable operation.
This standard shall apply, with the exceptions noted below, to all conveyor installations.
This standard specifically excludes any conveyor designed for, installed for, or used [primarily] for the movement of human beings. This standard does, however, apply to certain conveying devices that incorporate within their supporting structure, work stations or operator's stations specifically designed for authorized personnel.
This standard does not apply to conveyors such as underground mine conveyors for which specific standards are already in effect, or to equipment such as industrial trucks, tractors, trailers, automatic guided vehicles, tiering machines (except pallet load tierers), cranes, hoists, power shovels, power scoops, bucket drag lines, trenchers, platform elevators designed to carry passengers or operator, manlifts, moving walks, movingstairways (escalators), highway or railroad vehicles, cable ways, tramways, dumbwaiters, pneumatic conveyors, robots or integral machine transfer devices. Some of the foregoing have specific standards.
The provisions of this Standard shall apply to equipment installed one year after the standard's date of issuance.
Conveyor, vertical reciprocating: a permanent reciprocating power or gravity actuated unit (not designed to carry passengers or an operator) that receives objects on a carrier and transmits these objects vertically between two or more levels.
6.21.1 Add new sub-sections d, e, f, g, h, i, j and k to section 6.21.1 to read as follows:
6.21.1 Safety Considerations
(d)Travel distance shall be limited to less than 22 860 mm (75 ft.) with a maximum of four (4) landings served.
(e) Conveyor(s) shall be enclosed in a two- (2) hour fire rated hoistway, equipped with a minimum 11/2 hour fire rated entrance at each landing served.
(f) Access at landings shall be a restricted area for authorized personnel with no public access.
(g) Where there is an occupied space or an unoccupied space not secured against unauthorized access under the hoistway, the conveyor shall be equipped with a safety designed to stop and hold the conveyor with the rated full load capacity independent of the hoisting or driving mechanism.
(h) The operating device shall not be located inside the conveyor enclosure and must be external to the hoistway at each landing served.
(i) The system shall incorporate a position indicator at each floor landing to register the location of the conveyor.
(j) The rated load capacity shall not be less than 239 kg/m2 (49 lbs. per sq. ft.) with a maximum capacity of 9072 kg (20,000 lbs.).
(k) The rated speed shall not exceed 406 mm/sec. (80 FPM).
(l) VRCs are permitted only in commercial and industrial occupancies.
6.21.2 Revise sub-sections (c) and (d) of 6.21.2 to read as follows:
6.21.2 Guarding.
(c)Vertical reciprocating conveyors designed to automatically receive and discharge material [may] shall have interlocked doors as in (b) above or, as an alternative, may be guarded by a suitable enclosure extending from the path of the moving carrier.
(d) Where the application requires that personnel walk onto the carrier to load or unload material, the carriers shall be provided with a conveyor enclosure securely fastened to the conveyor platform. The enclosure walls shall be of solid, grille or perforated construction; and shall be of such strength and support that when subjected to a leaning or falling rated load on the conveyor, the enclosure walls will not deflect or deform in a way that reduces running clearances to less than 13mm (0.5 in.). Enclosure entrance(s) shall be provided with solid doors or gates; and shall guard the full width opening with a minimum height of 2030mm (80 in.). Grille or perforated portions of conveyor enclosures and entrance gates shall reject a ball 38mm (1.5 in.) in diameter. [with standard railings, snap chains, or equivalent across the loading/unloading side(s). Snap chains shall be at least 39 in. at their lowest point.]
The provisions of American Society of Mechanical Engineers ("ASME") A17.3-2002 shall be modified in accordance with this chapter. The section numbers correlate to those in the referenced ASME standard.
*Section BC K301.1 and Chapter K3 were added by: 1 RCNY §3610-01 — Update #63.This rule was first effective on December 14, 2009. A subsequent amendment to 1 RCNY 3610-01 has an effective date of April 18, 2011.
SECTION 1.5 ALTERATIONS, MAINTENANCE, AND INSPECTIONS AND TESTS
1.5 Delete and revise the text of section 1.5 to read as follows:
Existing installations shall conform to the following requirements of ASME A17.1-00:
Requirement 8.10.8.11, Periodic and Acceptance Inspections and Tests;
Requirement 8.6.8.7, Alterations, Repairs, Replacements, and Maintenance.
In addition, existing installations shall conform to ASME Addenda A17.1a-02 andA17.1b-03, and Sections 1007.4, 1607.8.1, 3001.2, 3001.4, 3002.5, 3003.2 and 3409.7.2of the New York City Building Code.
Delete and revise Section 2.1.2 to read as follows:
2.1.2 Windows in Hoistway Enclosures. Every hoistway-window opening ten (10) stories or fewer above a thoroughfare, and every such window opening three (3) stories or fewer above the roof of an adjacent building, shall be guarded by one of the following:
Vertical bars at least 5/8 inch (16 mm) in diameter or equivalent, spaced not more than 10 inches (254 mm) apart, permanently and securely fastened in place; or
Metal-sash windows having solid-section steel muntins of not less than 1/8 inch (3.2 mm) thickness, spaced not more than 8 inches (203 mm) apart.
Exterior hoistway-windows shall be marked with the word "SHAFTWAY" in red letters at least 6 inches (152 mm) high on a white background.
2.5 Delete and revise Section 2.5 to read as follows:
2.5 Where the space below the hoistway is not permanently secured against access, the following requirements shall apply within one (1) year from the effective date of this rule:
The cars and counterweights shall be provided with spring or oil buffers.
Car and counterweight buffer supports shall be of sufficient strength to withstand without permanent deformation the impact resulting from buffer engagement of the car plus the rated load or the counterweight with an empty car at the following speeds:
Governor tripping speed where the safety is governor operated;
One hundred twenty five (125) percent of the rated speed, where the safety is not governor operated.
Delete and revise Section 2.6.3 to read as follows:
2.6.3 Hoistway Door Vision Panels. Hoistway door vision panels must be protected by protective grills made of number sixteen(16) gauge stainless or galvanized steel in accordance with the following specifications:
Grills shall be sized to fit within or over the vision panelframe and completely cover the vision panel opening in the elevator, car doors and hoistway doors.
Grills and vision panelframes shall be secured by means of non-reversible screws or other tamper proof fasteners.
Grills shall contain openings that shall not be larger than 19 mm (0.75 in) in diameter.
All cut edges shall be deburred.
The provisions of this section shall apply to both new and existing passenger cars. Requirements for such grills may be waived if certification is submitted that such elevator is operated manually or twenty four (24) hour doorman service is provided. A security guard shall not be considered doorman service.
For the purposes of this subparagraph, a vandal resistant 6 mm (0.25 in) polycarbonate sheet, such as Lexan, in two (2) layers, one (1) on each side of the required wire glass, may be used in lieu of the metal protective.
2.6.4 Door Hangers.
Delete Section 2.6.4 in its entirety.
Section 2.6.4 Reserved.
2.6.7 Bottom Guides.
Delete and revise Section 2.6.7 to read as follows:
2.6.7 Bottom Guides. Existing elevators in occupancy groups R-1, R-2 and E shall comply with the following requirements:
The bottom of each horizontally sliding hoistway door panel shall be equipped with bottom guiding members and bottom safety retainers.
The bottom of each horizontally sliding hoistway elevator door panel shall be guided by two or more members as described in ASME A17.1 §2.11.11.6.
Safety Retainers — The bottom of each horizontally sliding hoistway elevator door panel shall be provided with a means of retaining the door panel in position if the primary guiding means fail, and preventing displacement of the bottom of the door panel by not more than 19 mm (0.75 in) into the hoistway. Such Retainers shall be installed on the bottom, shaft side of each door panel, shall be fabricated of at least twelve (12) gauge stainless or galvanized steel, and shall engage the corresponding sill member by not less than 9.5 mm (0.375 in).
Exception: New elevator doors installed under the 1996/1997 or later additions of ASME A17.1.
The door panels shall be structurally sound and in such condition that the guide(s) and retainer(s) may be securely attached.
At least one bottom guide shall be installed near each end of every door panel.
A safety retainer(s) totaling at least 203 mm (8 in) in length shall be installed between the two (2) outermost guides.
On smaller sized door panels, where due to the width of the door panel, the space between the two (2) outermost bottom guides would be less than 203 mm (8 in), then either:
he length of the retainer may be reduced to a minimum 102 mm (4 in); or
When only one (1) bottom guide is provided near the center of the door, a 102 mm (4 in) retainer shall be installed on each side of the bottom guide. If the space between the bottom guide and the edge of the door is less than four inches, the length of the retainer may be reduced to the amount of the space between the bottom guide and the edge of the door.
Exception: New elevator doors installed under the 1996/1997 or later additions of ASME A17.1.
SECTION 2.7 HOISTWAY DOOR LOCKING DEVICES, PARKING DEVICES, AND ACCESS
2.7.3 Access to Hoistway.
Delete Section 2.7.3 in its entirety.
Section 2.7.3 Reserved.
2.7.4 Restricted Opening of Hoistway Doors and/or Car Doors on Passenger Elevators.
Delete Section 2.7.4 in its entirety.
Section 2.7.4 Reserved.
2.7.6 Add new Section 2.7.6 to read as follows:
2.7.6 Locks on elevators and elevator hoistway doors. In high rise buildings, no switch, lock or device of any kind shall be installed on any floor on or above the street floor on any elevator car or elevator hoistway door, except elevators used exclusively for freight, that shall prevent opening of such doors by anyone not having a key, unless fire department access to cars and hoistways is provided by a city-wide standard key number 2642.
3.4.1 Car Enclosures. Delete Section 3.4.1 in its entirety.
Section 3.4.1 Reserved.
3.4.2 Car Doors and Gates. Delete and revise Section 3.4.2 to read as follows:
3.4.2 Car Doors and Gates. Passenger and loft elevators shall comply with (a) and (b) of this section within three (3) years from the effective date of this rule:
Doors, Gates, and Electric Contacts. Cars shall have a car door or gate provided at each entrance equipped with a car door or gate electric contact. Car doors and/or gates shall conform to the following requirements:
They shall be positively opened by a lever or other device attached to and operated by the door or gate.
They shall be maintained in the open position by the action of gravity or by a restrained compression spring, or both, or by positive mechanical means.
They shall not be readily accessible.
Collapsible Gates. Collapsible car gates shall conform to the following requirements:
Collapsible car gates shall not be power opened to a distance exceeding one third (1/3) of the clear gate opening, and in no case more than 254 mm (10 in).
When fully closed (extended position), gates shall reject a ball 76 mm (3 in) in diameter for passenger elevators and 114 mm (4.5 in) for freight elevators.
Gates shall have at least every fourth vertical member guided at the top and every second vertical member guided at the bottom.
Handles of manually operated collapsible gates nearest the car operating device on elevators operated from the car only shall be so located that the nearest handle is not more than 1.22 m (48 in) from the car operating device when the gate is closed (extended position), and not more than 1.22 m (48 in) above the car floor. Gate handles shall be provided with finger guards.
3.4.4 Emergency Exits. Delete Section 3.4.4 in its entirety.
Section 3.4.4 Reserved.
3.4.5 Car Illumination. Delete and revise Section 3.4.5 to read as follows:
3.4.5 Car Illumination. The provisions of this section shall apply within one (1) year from the effective date of this rule:
Interiors of cars shall be provided with an electric light or lights. Not less than two (2) lamps shall be provided.
The minimum illumination at the car threshold, with the door closed, shall not be less than:
For passenger elevators: 5 fc (54 lx).
For freight elevators: 2 1/2 fc (27 lx).
Light control switches are not required, but if provided they shall be located in or adjacent to the operating device in the car. In elevators having automatic operation, they shall be of the key-operated type or located in a fixture with a locked cover.
Top of car light fixtures may be provided with a non-key-operated switch in or adjacent to the fixture.
3.5.3 Safeties to Stop Ascending Cars or Counterweights Prohibited. Delete Section 3.5.3 in its entirety.
Section 3.5.3 Reserved.
3.5.4 Application and Release of Safeties. Delete Section 3.5.4 in its entirety.
Section 3.5.4 Reserved.
3.5.5 Maximum Permissible Movement of Governor Rope to Operate the Safety Mechanism. Delete Section 3.5.5 in its entirety.
Section 3.5.5 Reserved.
3.5.6 Rail Lubricants and Lubricant Plate. Delete and revise Section 3.5.6 to read as follows:
3.5.6 Rail Lubricants. Rail lubricants or coatings that will reduce the holding power of the safety or prevent its functioning as required shall not be used.
3.9.2 Final Terminal Stopping Devices. Upper and lower final terminal electromechanical stopping devices shall be provided and arranged to prevent movement of the car by the normal operating devices in either direction of travel after the car has passed a terminal landing. Final terminal stopping devices shall be located as follows:
Winding Drum Driving Machines. Elevators having winding drum machines shall have stopping switches on the machines and also in the hoistway operated by the movement of the car.
3.10.1 Types of Operating Devices. Delete Section 3.10.1 in its entirety.
Section 3.10.1 Reserved.
3.10.3 Top-of-Car Operating Devices. Delete Section 3.10.3 in its entirety.
Section 3.10.3 Reserved.
3.10.4 Electrical Protective Devices Delete and revise Section 3.10.4 to read as follows:
3.10.4 Electrical Protective Devices. Electrical protective devices shall be provided within one (1) year from the effective date of this rule in accordance with the following:
Slack-Rope Switch. Winding drum machines shall be provided with a slack-rope device equipped with a slack-rope switch of the enclosed manually reset type that shall cause the electric power to be removed from the elevator driving machine motor and brake if the suspension ropes become slack.
Compensating Rope Sheave Switch. Compensating rope sheaves shall be provided with a compensating rope sheave switch or switches mechanically opened by the compensating rope sheave before the sheave reaches its upper or lower limit of travel to cause the electric power to be removed from the elevator driving machine motor and brake.
Motor Generator Over speed Protection. Means shall be provided to cause the electric power to be removed automatically from the elevator driving machine motor and brake should a motor generator set, driven by a direct current motor, over speed excessively.
Motor Field Sensing Means. Where direct current is supplied to an armature and shunt field of an elevator driving machine motor, a motor field current sensing means shall be provided, which shall cause the electric power to be removed from the motor armature and brake unless current is flowing in the shunt field of the motor. A motor field current sensing means is not required for static control elevators provided with a device to detect an over speed condition prior to, and independent of, the operation of the governor over speed switch. This device shall cause power to be removed from the elevator driving machine motor armature and machine brake.
Emergency Stop Switch. On all elevators, an emergency stop switch shall be provided in the car, and located in or adjacent to each car operating panel. When open (i.e. the "stop position"), this switch shall cause the electric power to be removed from the elevator driving-machine motor and brake. Emergency stop switches shall:
Be of the manual open and close type:
Have red operating handles or buttons;
Be conspicuously and permanently marked "STOP" and indicate the "STOP" and "RUN" positions; and
When open, cause an audible signaling device to sound.
Stop Switch in Pit. A stop switch, conforming to the following requirements shall be provided in the pit of every elevator. The switch shall be located adjacent to the normal pit access. The switch shall cause the electric power to be removed from the elevator driving machine motor and brake and shall:
Be of the manual open and close type:
Have red operating handles or buttons;
Be conspicuously and permanently marked "STOP" and indicate the "STOP" and "RUN" positions; and
Be positively opened mechanically and its opening shall not be solely dependent on a spring.
Buffer Switches for Gas Spring Return Oil Buffers. A buffer switch shall be provided for gas spring return oil buffers that will cause electric power to be removed from the elevator driving machine motor and brake if the plunger is not within 13 mm (0.5 in) of the fully extended position.
3.10.5 Power Supply Line Disconnecting Means. Delete Section 3.10.5 in its entirety.
Section 3.10.5 Reserved.
3.10.11 Add new Section 3.10.11 to read as follows:
3.10.11 Signal Systems on Car Switch Elevators. Elevators with car switch operation shall be provided with a signal system by means of which signals can be given from any landing whenever the elevator is desired at the landing.
3.11.1 Car Emergency Signaling Devices. Delete and revise Section 3.11.1 to read as follows:
3.11.1 Car Emergency Signaling Devices. Elevators shall be provided with the following signaling devices:
n all buildings, the elevator shall be provided with the following:
An audible signaling device, operable from the emergency stop switch, when provided, and from a switch marked "ALARM" that is located in or adjacent to each car operating panel. The signaling device shall be located inside the building and audible inside the car and outside the hoistway. One signaling device may be used for a group of elevators.
In buildings in which a building attendant (building employee, watchperson, etc.) is not continuously available to take action when the required emergency signal is operated, the elevators shall be provided with a means within the car for communicating with or signaling to a service which is capable of taking appropriate action when a building attendant is not available.
4.3.1 Connection to Driving Machine. Delete Section 4.3.1 in its entirety.
Section 4.3.1 Reserved.
4.3.2 Plunger Stops. Delete Section 4.3.2 in its entirety.
Section 4.3.2 Reserved.
4.3.3 Hydraulic Elevators. Delete and revise Section 4.3.3 to read as follows:
4.3.3 Hydraulic Elevators.Hydraulic elevators that have any portion of the cylinder buried in the ground and that do not have a double cylinder or a cylinder with a safety bulkhead shall, within five (5) years from the effective date of this rule:
Have the cylinder replaced with a double cylinder or a cylinder with a safety bulkhead protected from corrosion by one or more of the following methods:
Monitored cathodic protection;
A coating to protect the cylinder from corrosion that will withstand the installation process;
By a protective plastic casing immune to galvanic or electrolytic action, salt water, and other known underground conditions; or
Be provided with a device meeting the requirements of §3.5 or a device arranged to operate in the down direction at an overspeed not exceeding one hundred twenty five (125) percent of rated speed. The device shall mechanically act to limit the maximum car speed to the buffer striking speed, or stop the elevator car with rated load with a deceleration not to exceed 9.8 m/s2 (32.2 ft/s2), and shall not automatically reset. Actuation of the device shall cause power to be removed from the pump motor and control valves until manually reset; or
Have other means acceptable to the department to protect against unintended movement of the car as a result of uncontrolled fluid loss.
4.7.1 Operating Devices. Delete Section 4.7.1 in its entirety.
Section 4.7.1 Reserved.
4.7.2 Top-of-Car Operating Devices. Delete Section 4.7.2 in its entirety.
Section 4.7.2 Reserved.
4.7.3 Anticreep Leveling Devices. Delete Section 4.7.3 in its entirety.
Section 4.7.3 Reserved.
4.7.4 Electrical Protective Devices. Delete and revise Section 4.7.4 to read as follows:
4.7.4 Electrical Protective Devices. hen they apply to hydraulic elevators, the following electrical protective devices conforming to the requirements of §3.10.4 shall be provided:
Stop switches in the pit: and
Where such emergency doors are provided, in-car emergency exit door electric contacts. Such devices shall prevent the operation of the elevator by the normal operating device and shall prevent the moment of the car in response to the anticreep leveling device.
4.7.5 Power Supply Line Disconnecting Means. Delete Section 4.7.5 in its entirety.
5.3.1 Starting Switches. Delete and revise Section 5.3.1 as follows:
5.3.1 Starting Devices. In every new and existing escalator, starting devices shall be provided with the combination of a starting switch and a starting button. The escalator shall be started only after the activation of both the switch and the button.
Starting Switch. Starting switches shall be of continuous pressure spring return type and shall be operated by a cylinder type lock having five-pin, five-disc or five-tumbler combination. Starting switches shall be of three-position type and shall be clearly marked as follows:
NORMAL. A central position for the key entry and spring return position.
START-UP. A right side position for starting the escalator in the upward direction.
START-DOWN. A left side position for starting the escalator in the downward direction.
Location of starting devices. Starting devices shall be located at top and bottom of the escalator on the right side-facing newel.
(NOTE: The starting key shall be kept on the premises at all times and shall only be accessible to persons authorized to start escalators. It shall also be made available to the commissioner or the commissioner's representative.)
5.3.2 Emergency Stop Buttons. Delete and revise Section 5.3.2 as follows:
5.3.2 Emergency Stop Buttons Location. A red stop button shall be visibly located at the top and bottom landings on the right side facing the escalator. Remote stop buttons are prohibited except that any escalator connected to an automaticfire alarm system shall gradually stop not exceeding the speed of 0.91 m/s2 (3 ft per sec2) upon the activation of such system.
5.3.3 Speed Governor. Delete Section 5.3.3 in its entirety.
Section 5.3.3 Reserved.
5.3.4 Broken Step-Chain Device. Delete Section 5.3.4 in its entirety.
Section 5.3.4 Reserved.
5.3.5 Application of Brake. Delete Section 5.3.5 in its entirety.
Section 5.3.5 Reserved.
5.3.6 Broken Drive-Chain Device. Delete Section 5.3.6 in its entirety.
Section 5.3.6 Reserved.
5.3.7 Skirt Obstruction Device. Delete and revise Section 5.3.7 as follows:
5.3.7 Skirt Obstruction Device.Escalators shall comply with the following no later than January 1, 2014: Means shall be provided to cause the electric power to be removed from the escalator driving machine motor and brake if an object becomes caught between the step and the skirt as the step approaches the upper combplate, intermediate device or lower combplate. On units having a run of 6.10 m (20 ft) or more, intermediate devices shall be provided on both sides of the escalator with devices located at interval of 3.05 m (10 ft) or less. The activation intermediate devices shall stop the escalator at a rate not greater than 0.91 m/s2 (3 ftper sec2) in the direction of travel. The upper and lower combplate devices shall be located so that the escalator will stop before that object reaches the combplate. The activation of any skirt device shall stop the escalator with any loadup to full brake rated load with the escalator running.
5.3.12 Add new Section 5.3.12 to read as follows:
5.3.12 Comb-Step Stop Device. A device shall be provided that will cause the opening of the power circuit to the escalator driving machine motor and brake where a resultant vertical force not greater than 268 N (60 lbf) in the upward direction is applied at the center of the front of the comb-plate.
Existing hand powered freight elevators shall not be subject to the provisions of this rule. However, adequate protection of landing openings shall be provided by hinged or sliding doors which shall remain locked at all times except when the freight elevator is in use. Auxiliary gates not less than 914mm (36 in) in height, substantially constructed and secured in place, of wood or metal, or equivalent metal chains shall be installed. Such gates or chains may be arranged to lift vertically, to slide horizontally, or to swing. No part of any gate or chain shall project into the freight elevator shaft. Gates may be operated automatically or manually.
SECTION 7.1 HOISTWAY, HOISTWAY ENCLOSURES, AND RELATED CONSTRUCTION
8.2.11 Locking Devices for Hinged Swinging Doors or Vertically Lifting Covers in Sidewalks or Other Areas Exterior to the Building. Delete Section 8.2.11 in its entirety.
Section 8.2.11 Reserved.
8.2.12 Requirements for Electrical Wiring and Electrical Equipment. Delete Section 8.2.12 in its entirety.
Section 8.2.12 Reserved.
8.2.13 Clearance Between Loading Side of Car Platforms and Hoistway Enclosures. Delete Section 8.2.13 in its entirety.
The operation of power sidewalk elevators through openings in the sidewalk, or through openings in other exterior areas that are accessible to the public, and that are protected by hinged doors or vertically lifting covers, shall conform to the following:
The elevator shall be operated in both the up and down directions through the opening, only from the sidewalk or other exterior area. The operation shall be by means of:
Key-operated continuous-pressure-type up and down switches; or
Continuous-pressure-type up-and-down operating buttons on the free end of a detachable, flexible cord 1.52 m (5 ft) or less in length.
Key-operated switches shall be of continuous pressure spring return type, and shall be operated by a cylinder-type lock having not less than a five-pin or five disk combination with the key removable only when the switch is in the "OFF" position.
Key-operated switches and plug receptacles for flexible cords shall be mounted in weatherproof boxes with covers installed above the sidewalk or other area on the side of the building wall, located 457 mm (18 in) or less horizontally from one side of the opening.
Operating buttons may be provided in the elevator car and at any landing below the top landing, provided that such buttons shall operate the car only when the bow-iron or stanchions are not in contact with the doors or covers in the sidewalk of other exterior area.
When the bow-iron or stanchions are in contact with the doors or covers at the sidewalk or other exterior area, it shall be possible to operate the car only by means of either the key switches or the continuous-pressure type up-and-down buttons on the free end of the flexible cord specified in §8.2.14(a)(1).
Flexible cords and operating keys shall not be left where they are accessible to unauthorized persons for operation of the elevator.
The clearance on each side of the steps between step thread and the adjacent skirt panel shall be not more than 4.8 mm (0.188 in) and the edges shall be rounded.
The exposed surface of the skirt panels adjacent to the thread shall be smooth.
SECTION 9.1 PROTECTION OF FLOOR OPENINGS
9.1 Delete Section 9.1 in its entirety.
Section 9.1 Reserved.
SECTION 9.2 PROTECTION OF SUPPORTS AND MACHINE SPACES AGAINST FIRE
9.6.1 General. Delete Section 9.6.1 in its entirety.
Section 9.6.1 Reserved.
9.6.2 Starting Switch. Delete and revise Section 9.6.2 to read as follows:
9.6.2 Starting Devices. In every new and existing moving walk, starting devices shall be provided with the combination of a starting switch and a starting button. The escalator shall be started only after the activation of both the switch and the button.
Starting Switch.Starting switches shall be of continuous pressure spring return type and shall be operated by a cylinder type lock having five-pin, five-disc or five-tumbler combination. Starting switches shall be of three-position type and shall be clearly marked as follows:
NORMAL. A central position for the key entry and spring return position.
START-UP. A right side position for starting the escalator in the upward direction.
START-DOWN. A left side position for starting the escalator in the downward direction.
Location of starting devices. Starting devices shall be located at top and bottom of the escalator on the right side-facing newel.
(NOTE: The starting key shall be kept on the premises at all times and may only be accessible to persons authorized to start escalators. It shall also be made available to the commissioner or the commissioner's representative.)
9.6.3 Emergency Stop Buttons. Delete and revise Section 9.6.3 to read as follows:
9.6.3 Emergency Stop Buttons Location. A red stop button shall be visibly located at the top and bottom landings on the right side facing the moving walk. Remote stop buttons are prohibited except that any escalator connected to an automaticfire alarm system shall gradually stop not exceeding the speed of 0.91 m/s2 (3 ft per sec2) upon the activation of such system.
9.6.4 Speed Governor. Delete Section 9.6.4 in its entirety.
Section 9.6.4 Reserved.
9.6.5 Application of an Electrically Released Brake. Delete Section 9.6.5 in its entirety.
Section 9.6.5 Reserved.
9.6.6 Broken Drive-Chain Switch. Delete Section 9.6.6 in its entirety.
Section 9.6.6 Reserved.
9.6.10 Disconnected Motor Safety Device. Delete Section 9.6.10 in its entirety.
Section 9.6.10 Reserved.
9.6.12 Add new Section 9.6.12 to read as follows:
9.6.12 Comb-Pallet Stop Device. A device shall be provided that will cause the opening of the power circuit to the moving walk driving-machine motor and brake when a resultant vertical force not greater than 268 N (60 lbf) in the upward direction is applied at the center of the front of the comb-plate.
The provisions of American Society of Mechanical Engineers ("ASME") A17.1S-2005 must be modified in accordance with this chapter. The section numbers correlate to those in the referenced ASME standard.
*Section BC K401.1 and Chapter K4 were added by: 1 RCNY §3610-02 — Update #66.This rule has an effective date of February 24, 2012.
1.1 Delete and revise Section 1.1 to read as follows:
See ASME A17.1-2000 including A17.1a-2002 and A17.1b-2003 as amended by Chapter K1 of Appendix K of the New York City Building Code for additional, relevant requirements
CONTROL SPACE, ELEVATOR, DUMBWAITER, MATERIAL LIFT: a space outside the hoistway, intended for full bodily entry, which contains the motor controller. The space could also contain electrical and/or mechanical equipment used directly in connection with the elevator, dumbwaiter, or material lift, but not the electric driving machine or the hydraulic machine. (See Appendix Q).
Add the following sentence to the end of the definition "Machinery space, elevator, dumbwaiter, material lift":
Machinery space in hoistways may not contain a motion controller, a motor controller or an operation controller.
Delete and revise Section 2.1.4 to read as follows:
2.1.4 Control of smoke and hot gases. Hoistways must be provided with means to prevent the accumulation of smoke and hot gases when required by the New York City Building Code.
2.1.6 Projections, recesses and setbacks in hoistway enclosures.
Delete and revise Section 2.1.6.2 to read as follows:
2.1.6.2 On sides not used for loading and unloading:
Recesses, except those necessary for installation of elevator equipment, must not be permitted;
Beams, floor slabs, or other building construction making an angle less than 75 degrees with the horizontal must not project more than 50 mm (2 in) inside the hoistway enclosure unless the top surface of the projection is beveled at an angle not less than 75 degrees with the horizontal;
Separator beams between adjacent elevators are not required to have bevels;
Where setbacks exceeding 50 mm (2 in) occur in the enclosure wall, the top of the setback must be beveled at an angle of not less than 85 degrees with the horizontal;
Bevels are not required if the projections and setbacks are covered with material conforming to the following:
It must be equal to or stronger than 1.110 mm (0.0437 in) wire;
It must have openings not exceeding 25 mm (1 in);
It must be supported and braced such that it will not deflect more than 25 mm (1 in) when subjected to a force of 4.79 kPa (100 lbs per sq ft) applied horizontally at any point.
Delete and revise Section 2.2.2.5 to read as follows:
2.2.2.5 Elevators with sprinklers in the shaftway must be provided with a drain or sump pump.
2.2.4 Access to pits.
Delete and revise Section 2.2.4.1 to read as follows:
2.2.4.1 Access must be by means of the lowest hoistway door or by means of a separate pit access door, located at the level of the pit floor.
Add new Subsection (f) to Section 2.2.4.4 to read as follows:
(f) Pit doors must be labeled "DANGER: ELEVATOR PIT" with letters not less than 51 mm (2 in) high.
SECTION 2.7
MACHINERY SPACES, MACHINE ROOMS, CONTROL SPACES, AND CONTROL ROOMS
2.7.3 Access to machinery spaces, machine rooms, control spaces, and control rooms.
Add new Subsection (d) to Section 2.7.3.1.1 to read as follows:
(d) A control space and machinery space for elevators must only be located where working clearances required for the control space will not impede upon the path of travel in unrestricted areas. Where the elevator control space is located in a path of travel in an unrestricted area, a clear path of travel parallel to the control space must not be less than the required working clearance plus 1219 mm (48 in) perpendicular to the control space. A permanent barricade needed to establish the working clearances for the control space must be accessible to elevator personnel from the control space. The barricade must be deployed whenever the doors to the control space are in the open position. See figure Q-2.
Add new Subsection (d) to Section 2.7.3.4.1 to read as follows:
(d) Labeled "ELEVATOR EQUIPMENT" with letters not less than 51 mm (2 in) high.
Delete and revise the first sentence of Section 2.7.3.4.2 to read as follows:
Access doors to machine rooms, control rooms and control spaces must be provided.
Add new Subsection (d) to Section 2.7.3.4.6 to read as follows:
(d) Labeled "DANGER: ELEVATOR HOISTWAY" with letters not less than 51 mm (2 in) high and have an electrical safety switch that will remove power from the hoist machine and brake if the door is opened.
2.7.6 Location of machinery spaces, machine rooms, control spaces, control rooms, and equipment.
Delete and revise Section 2.7.6.2 to read as follows:
2.7.6.2 Location of machinery spaces and control spaces. Machinery spaces may be located inside or outside the hoistway. Control spaces are not permitted inside the hoistway. Control spaces are only permitted inside the building.
Delete and revise Section 2.7.6.3.4 to read as follows:
2.7.6.3.4 Where a governor is located inside the hoistway, means of access conforming to the requirements of 2.7.3.3 and 2.7.3.4 for inspection and servicing the governor must be provided from outside the hoistway.
Add new sentence to the end of Section 2.7.6.4 to read as follows:
These means must be permanently installed.
Delete and revise Subsection (d) of Section 2.7.6.4.3 to read as follows:
(d) If the car is moved manually, the effort required to move the car in the direction of load imbalance must not exceed 400 N (90 lbf). If the means used is removable, it must be stored outside the hoistway and access to the means must be with a key that is Group 1 Security. It must be suitably marked to indicate the machine for which it is intended. It must also contain instructions on its use and be labeled "Machine Brake Release".
SECTION 2.8
EQUIPMENT IN HOISTWAYS, MACHINERY SPACES, MACHINE ROOMS, CONTROL SPACES, AND CONTROL ROOMS
Delete and revise Section 2.8.3.3 to read as follows:
2.8.3.3 Sprinkler systems conforming to NFPA 13 or the NBCC, whichever is applicable (see Part 9), must be permitted to be installed in the hoistway or machinery space, subject to 2.8.3.3.1 through 2.8.3.3.4.
SECTION 2.11
PROTECTION OF HOISTWAY OPENINGS
2.11.1 Entrances and emergency doors required.
Delete and revise the last sentence of Section 2.11.1.1 to read as follows:
Entrances must be at least 2030 mm (80 in) in height and 915 mm (36 in) in width.
Delete and revise Subsection (a) of Section 2.11.1.2 to read as follows:
(a) The clear opening must be at least 915 mm (36 in) wide and 2030 mm (80 in) high.
2.11.2 Types of entrances.
Delete Subsection (c) of Section 2.11.2.1 in its entirety.
Subsection 2.11.2.1(c) Reserved.
Delete Subsection (c) of Section 2.11.2.2 in its entirety.
Subsection 2.11.2.2(c) Reserved.
2.11.6 Openings of hoistway doors.
Delete and revise Subsection (d) of Section 2.11.6.2 to read as follows:
(d) Any landing for elevator equipped with Phase II Emergency In-Car Operation when Phase II is effective.
Add new Subsection (e) to Section 2.11.6.2 to read as follows:
(e) Consecutive vacant floors.
Add new Subsection (f) to Section 2.11.6.2 to read as follows:
2.11.6.5.1 Elevator landings provided with a zero clearance vestibule (not to exceed 150 mm (6 in) from the elevator hoistway door) are permissible only when locking devices accessible from the car are installed exclusively on the door that separates the zero clearance vestibule from the occupied floor space.
2.11.6.5.2 Where the vestibule is not a zero clearance vestibule as defined in 2.11.6.5.1, locking devices at the vestibule will be permitted under any one of the following conditions:
A red telephone is installed in the vestibule near the elevator doors to communicate with lobby fire command station or building manager's office or to central service station when the building is not attended. Asign must be posted near the telephone. The sign must read "In Case of Fire or Other Emergency Use This Phone to Contact Lobby or Building Manager or Central Service Station";
The locking devices on the vestibule door leading to an exit are released upon activation of any detection or signaling devices, or power failure;
At least one exitstair is located within the vestibule.
2.11.7 Glass in hoistway doors.
Delete and revise Section 2.11.7.1 to read as follows:
2.11.7.1 Vision panels. For elevators with automatic or continuous-pressure operation, manually operated or self-closing hoistway doors of the vertically or horizontally sliding type must be provided with a vision panel. In multi-section doors, the vision panel is required in one section only, but is permitted to be placed in all sections. All horizontally swinging elevator doors must be provided with vision panels. Vision panels are permitted for any type of hoistway door. Vision panels are not required at the landing of automatic operation elevators equipped with horizontally sliding car and hoistway doors.Where required or used, vision panels must conform to 2.11.7.1.1 through 2.11.7.1.7.
Delete and revise Section 2.11.7.1.1 to read as follows:
2.11.7.1.1 The area of any single vision panel must not be less than 0.008 m2(12 in2), and the total area of one or more panels in any hoistway door must not be more than 0.026 m2(40 in2).
2.11.11 Entrances, horizontal slide type.
Delete and revise Subsection (a) of Section 2.11.11.6 to read as follows:
(a) The bottom of each panel must be guided by two or more members.
2.11.15 Marking.
Delete and revise Section 2.11.15.1 to read as follows:
2.11.15.1 Labeling of tested assembly. In jurisdictions not enforcing the NBCC, 2.11.15.1.1 and 2.11.15.1.2 apply. Where required by this code, the entire entrance assembly must be of an approved type.
SECTION 2.12
HOISTWAY DOOR LOCKING DEVICES AND ELECTRIC CONTACTS, AND HOISTWAY ACCESS SWITCHES
2.12.3 Hoistway door combination mechanical locks and electrical contacts.
Delete Section 2.12.3 in its entirety:
Section 2.12.3 Reserved.
2.12.4 Listing/certification door locking devices and door or gate electrical contacts.
Delete and replace Section 2.12.4.1 to read as follows:
2.12.4.1 Type tests. Each type and make of hoistway-door interlock, electric contact, and door or gate electric contact must be of an approved type. Hoistway-door combination mechanical locks and electrical contacts are not permitted.
Delete and revise Subsection (b) of Section 2.12.4.3 to read as follows:
(b) Identification marking.The approved agency's name, date of approval and identifying number or symbol.
2.12.7 Hoistway access switches.
Delete and revise Section 2.12.7.3.2 to read as follows:
2.12.7.3.2 The car cannot be operated at a speed greater than 0.35 m/s (75 ft/min).
SECTION 2.13
POWER OPERATION OF HOISTWAY DOORS AND CAR DOORS
2.13.2 Power opening.Delete and revise Section 2.13.2.1.2 to read as follows:
2.13.2.1.2 Collapsible car gates must not be power opened.
SECTION 2.14
CAR ENCLOSURES, CAR DOORS AND GATES, AND CAR ILLUMINATION
Delete and revise Section 2.14.2.1.1 to read as follows:
2.14.2.1 Materials in their end use configuration, other than those covered by 2.14.2.1.2 through 2.14.2.1.6, must conform to the following requirements, based on the tests conducted in accordance with the requirements of ASTM E 84, UL 723, or NFPA 255:
2.14.7 Illumination of cars and lighting fixtures.
Delete and revise Section 2.14.7.1.4 to read as follows:
2.14.7.1.4 Each elevator must be provided with a guarded electric light and convenience outlet fixture on the car top and under the car platform.
SECTION 2.18
SPEED GOVERNORS
2.18.4 Speed-governor overspeed switch.Add a new paragraph at the end of the main paragraph of Section 2.18.4.4 to read as follows:
An access door is required when the governor is installed at the top of the hoistway for access to reset switches by elevator personnel. The access door must comply with Section 2.7.3.4.6.
Delete and revise the Note to Section 2.18.4.4 to read as follows:
NOTE: Manual reset is defined here as personal intervention by elevator personnel at the governor.
2.18.5 Governor ropes.Delete and revise Section 2.18.5.1 to read as follows:
2.18.5.1 Material and factor of safety. Governor ropes must be a minimum of 6 mm (.25 in) and must comply with ASME A17.6-2010, Part 1 and ASME A17.1-2010 as referred to in A17.6-2010.
SECTION 2.20
SUSPENSION ROPES AND THEIR CONNECTIONS
2.20.3 Factor of safety.
Delete and revise Section 2.20.3 to read as follows:
2.20.3 Factor of safety. Suspension ropes must be stranded carbon steel wire ropes (minimum 8 mm (.3 in)) or noncircular elastomeric coated steel suspension members. They must comply with ASME A17.6-2010, Part 1 and Part 3 and ASME A17.1-2010 as referred to in A17.6-2010. Aramid fiber ropes are not permitted.
2.20.4 Minimum number and diameter of suspension ropes.
Delete and revise Section 2.20.4 to read as follows:
2.20.4 Minimum number and diameter of suspension ropes. Suspension ropes must be stranded carbon steel wire ropes (minimum 8 mm (.3 in)) or noncircular elastomeric coated steel suspension members. They must comply with ASME A17.6-2010, Part 1 and Part 3 and ASME A17.1-2010 as referred to in A17.6-2010. Aramid fiber ropes are not permitted.
Delete and revise Subsection (e) of Section 2.26.1.4.2 as follows:
(e) The inspection operating devices (see 2.26.1.4.1(c)) must be portable, with a cord length of the distance from the connection point to the farthest corner of the top of car, provided that
The "ENABLE" device (see 2.26.1.4.2(c)), and a stop switch, in addition to the stop switch required in 2.26.1.4.2(a) are included in the portable unit; and
The flexible cord is permanently attached so that the portable unit cannot be detached from the car top.
2.26.2 Electrical protective devices.
Delete and revise Section 2.26.2.5 to read as follows:
2.26.2.5 Emergency stop switch. On all elevators, an emergency stop switch must be provided in the car, and located in or adjacent to each car operating panel. When open ("STOP" position), this switch must cause the electric power to be removed from the elevator driving-machine motor and brake. Emergency stop switches must:
Be of the manually opened and closed type;
Have red operating handles or buttons;
Be conspicuously and permanently marked "STOP" and must indicate the "STOP" and "RUN" positions; and
While opened,cause the audible device to sound (see 2.27.1.2).
Delete and revise Section 2.27.1.1.1 to read as follows:
2.27.1.1.1 A two-way communications means between the car and a location in the building that is readily accessible to authorized and emergency personnel must be provided. Means must be provided to enable two-way voice communication between the machine, the control room, the control space and the interior of the car.
2.27.2 Emergency or standby power system.
Delete and revise Section 2.27.2.4.3 to read as follows:
2.27.2.4.3 Means must be provided adjacent to the selector switch(es) to indicate that the elevator is at the designated level with the doors in the normally open position.
Delete and revise Section 2.27.3 to read as follows:
2.27.3 Fire-fighters' emergency operation: automatic elevators. See Chapter K1 of Appendix K of the New York City Building Code, and replace the words "machine room" with "control room and control space".
Delete and revise Section 2.27.4 to read as follows:
2.27.4 Fire-fighter's emergency operation: nonautomatic elevators. See Chapter K1 of Appendix K of the New York City Building Code.
2.27.5 Firefighters' emergency operation: automatic elevators with designated-attendant operation.
Delete and revise Section 2.27.5 to read as follows:
2.27.5 Fire-fighter's emergency operation: automatic elevators with designated attendant operation. See Chapter K1 of Appendix K of the New York City Building Code.
2.27.8 Switch keys.
Delete and revise Section 2.27.8 to read as follows:
2.27.8 Switch keys. See Chapter K1 of Appendix K of the New York City Building Code.
Delete and revise Section 2.29.1 to read as follows:
2.29.1 Identification of equipment. In buildings with more than one elevator, each elevator must be assigned a unique alphabetical or numerical identification, a minimum of 50 mm (2 in) in height. The identification number must be applied to the following locations:
Driving machine;
MG and / or transformers;
Controller;
Selector;
Governor;
Main line disconnect switch;
The crosshead or, where there is no crosshead, the car frame, such that it is visible from the top of the car;
The car operating panel, minimum of 13 mm (0.5 in) in height;
Adjacent to or on every elevator entrance at the designated level, minimum of 75 mm (3 in) height; and
Each bank of elevators must be identified by a letter.
Add new Section 2.29.1.1 to read as follows:
2.29.1.1 New York City identification number. Each elevator must be assigned a unique numerical identification a minimum of 6 mm (.25 in) in height. The city identification number must be applied to the following locations:
The driving machine;
MG and / or transformers;
Controller;
Main line disconnect switch;
The crosshead or, where there is no crosshead, the car frame, such that it is visible from the top of the car;
2.29.3 Main line location signage. A permanent sign must be located on or adjacent to the Phase I key switch. The sign must indicate the location of the mainline disconnect switches for that bank of elevators. Lettering must be a minimum of 6 mm (0.25 in) high in red or a color contrasting with a red background.
3.6.2 Counterweight safety actuation.Delete and revise Section 3.6.2 to read as follows:
3.6.2 Car and counterweight safety actuation. Where the space referred to in 3.6 falls underneath the car or counterweight and/or its guides, the car and counterweight must be provided with a safety device.
SECTION 3.7
MACHINERY SPACES, MACHINE ROOMS, CONTROL SPACES, AND CONTROL ROOMS
Delete and revise the opening paragraph of Section 3.7.1 to read as follows:
3.7.1 Machinery spaces, machine rooms, control spaces, and control rooms must conform to the requirements of 2.7.1 through 2.7.7 and 2.7.9. Hydraulic machines and controllers are not permitted in the hoistway or pit.
Add new Subsection (w) to Section 8.1.2 to read as follows:
(w) The requirements of 2.14.1.10 (side emergency exit doors) apply.
NONMANDATORY APPENDIX Q
EXPLANATORY FIGURES FOR THE DEFINITIONS OF ELEVATOR MACHINERY SPACE, MACHINE ROOM, CONTROL SPACE, CONTROL ROOM, REMOTE MACHINE ROOM, OR REMOTE CONTROL ROOM