This chapter governs the electrical components, equipment and systems used in buildings and structures covered by this code. Electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of the New York City Electrical Code.
*Section BC 2702 was amended by: Local Law 111 of 2013 - Update #83. This law has an effective date of December 02, 2013
Emergency and standby power systems shall be installed in accordance with the New York City Electrical Code, NFPA 110 and NFPA 111. Systems relying on fuel supplies shall have an on-premises fuel supply sufficient for not less than 6-hour full-demand operation of the system. However, natural gas from the public utility street main shall be permitted as the sole fuel supply for (i) emergency power systems serving R-2 occupancies and (ii) standby power systems, provided that an outside gas cut-off valve separate from other gas services is installed in accordance with Section E.6 of Appendix E of the New York City Fuel Gas Code.
*Section BC 2702.1 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency and standby power generators shall be listed in accordance with UL 2200.
*Section BC 2702.1.1 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
The emergency and standby power systems shall have capacity and ratings that supply all equipment required to be operational at the same time.
*Section BC 2702.1.2 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency and standby power systems shall be provided where required by this section.
*Section BC 2702.2 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency power shall be provided for voice/alarm communication systems in Group A occupancies in accordance with Section 907.2.1.2.
Standby power shall be provided for smoke control systems in accordance with Section 909.11.
*Section BC 2702.2.2 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency power shall be provided for means of egress illumination in accordance with Section 1006.3.
Standby power shall be provided for elevators that are part of an accessible means of egress in accordance with Section 1007.4.
*Section BC 2702.2.5 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Standby power shall be provided for horizontal sliding doors in accordance with Section 1008.1.3.3.
*Section BC 2702.2.6 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency power shall be provided for semiconductor fabrication facilities in accordance with Section 415.9.10.
Standby power shall be provided for auxiliary inflation systems in accordance with Section 3102.8.2. Emergency power shall be provided for exit signs in tents and membrane structures.
*Section BC 2702.2.8 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency or standby power shall be provided in occupancies with hazardous materials in accordance with Section 414.5.4 and the New York City Fire Code.
*Section BC 2702.2.9 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency power shall be provided for occupancies with highly toxic or toxic materials in accordance with the New York City Fire Code.
*Section BC 2702.2.10 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Standby power shall be provided for occupancies with organic peroxides in accordance with the New York City Fire Code.
*Section BC 2702.2.11 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency power shall be provided for occupancies with silane gas in accordance with the New York City Fire Code.
Standby power shall be provided for voice/alarm communication systems in covered mall buildings in accordance with Section 402.12.
*Section BC 2702.2.13 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency and standby power shall be provided in high-rise buildings in accordance with Sections 403.10 and 403.11.
*Section BC 2702.2.14 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency and standby power shall be provided in underground buildings in accordance with Sections 405.9 and 405.10.
*Section BC 2702.2.15 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency power shall be provided for doors in Group I-3 occupancies in accordance with Section 408.4.2.
Standby power for elevators, including elevators provided to accommodate ambulance stretchers pursuant to Section 3002.4, shall be provided as set forth in Section 3003.1.
*Section BC 2702.2.18 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Standby power shall be provided for smoke-proof enclosures as required by Section 909.20 and for pressurized elevator shafts provided in accordance with Item 5 of Section 403.9.1.1.
*Section BC 2702.2.19 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency and standby power shall be required in those Group B, E and R-1 occupancies specified in this section:
- Group B occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest fire department vehicle access having a gross floor area over 15,000 square feet (1393.6 m2) per floor or a total gross floor area of 100,000 square feet (9290.3 m2) or more.
- Group E occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest level of fire department vehicle access having a gross floor area over 15,000 square feet (1393.6 m2) per floor or a total gross floor area of 100,000 square feet (9290.3 m2) or more.
- All Group R-1 occupancies.
*Section BC 2702.2.20 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
With respect to such Occupancy Groups B, E and R-1, the following equipment, where such equipment is required by this code, shall be provided with an emergency power system:
- Exit signs and means of egress illumination required by Chapter 10;
- Elevator car lighting;
- Emergency voice/alarm communications systems;
- Automatic fire detection systems;
- Fire alarm systems; and
- Electrically powered fire pumps.
*Section BC 2702.2.20.1 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
With respect to such Occupancy Groups B, E and R-1, the following equipment, where such equipment is required by this code, shall be provided with a standby power system:
- Ventilating systems used for smoke venting or control;
- Stair pressurization; and
- At least three elevators in a building at one time with manual transfer to other elevators as required by Section 3003.
*Section BC 2702.2.20.2 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
Emergency and standby power systems shall be maintained and tested in accordance with the New York City Fire Code and New York City Electrical Code.
*Section BC 2702.3 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.
In addition to any other loads, optional standby power systems shall be capable of providing power to the following systems upon failure of the normal power supply or the emergency or standby power system:
- Emergency lighting;
- Fire alarm systems; and
- Elevators as follows:
- For Group R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height, at least one elevator serving all floors, or one elevator per bank where different banks serve different portions of the building; or
- For all other buildings having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, at least one elevator that serves all floors.
*Section BC 2702.4 was amended by: Local Law 111 of 2013 — Update #83. This law has an effective date of December 02, 2013.