UpCodes vs. ICC
One of the benefits of open access to our laws is the opportunity to innovate and create new tools we can all benefit from.
We've spent years building the technology to integrate and keep codes up-to-date. Along the way, we've defended the right for everyone to access laws for free. ICC has launched two lawsuits against us to prevent us from doing so (lawsuit one, lawsuit two). One danger of an organization like ICC acting as a gatekeeper is relying on their ability to keep the codes accurate and up-to-date. Unfortunately, they have consistently failed to do so.
In ICC's second lawsuit, they pointed out about 2 dozen issues from UpCodes' 1,000,000+ sections of law we host (which were promptly addressed).
In an initial review at the time of writing this article (Summer 2020), we found 400+ sections where ICC either has an error or not the most up-to-date code.
| # | Section | UpCodes (Summer 2020) | ICC (Summer 2020) | Gov. Reference |
|---|---|---|---|---|
Washington | ||||
| 1 | 202 | Accurate and fully up-to-date | Missing definition of “Mass Timber”, “NONCOMBUSTIBLE PROTECTION”, “mass timer wall” in classification #2 of “WALL, LOAD BEARING” | |
| 2 | 403.3.2 | Accurate and fully up-to-date | Missing “and buildings of Type IV-A and IV-B that are more than 120 feet in building height,” in the first sentence | |
| 3 | 504.4 | Accurate and fully up-to-date | Missing columns for “A”, “B”, and “C” under TYPE IV Construction | |
| 4 | 508.4.4.1 | Accurate and fully up-to-date | Missing last sentence “Mass timber elements serving as fire barriers or horizontal assemblies to separate occupancies in Type IV-B or IV-C construction shall be separated from the interior of the building with an approved thermal barrier consisting of a minimum of ½ inch (12.7 mm) gypsum board or a material that is tested in accordance with and meets the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275.” | |
| 5 | 509.4.1.1 | Accurate and fully up-to-date | Omits Section 509.4.1.1. | |
| 6 | 602.4 | Accurate and fully up-to-date | Section is outdated. This sentence is missing “Mass timber elements shall meet the fire-resistance rating requirements of this section based on either the fire-resistance rating of the noncombustible protection, the mass timber, or a combination of both and shall be determined in accordance with Section 703.2 or 703.3. The minimum dimensions and permitted materials for building elements shall comply with the provisions of this section including Table 602.4.4 and Section 2304.11. Mass timber elements of Types IV-A, IV-B and IV-C construction shall be protected with noncombustible protection applied directly to the mass timber in accordance with Sections 602.4.1 through 602.4.3. The time assigned to the noncombustible protection shall be determined in accordance with Section 703.8 and comply with Section 722.7.” as well as the exceptions. | |
| 7 | 602.4.1 | Accurate and fully up-to-date | Section is outdated.
Incorrectly displays in the title “Fire-retardant-treated wood in exterior walls”,
Incorrectly displays in the body “Fire-retardant-treated wood framing complying with Section 2303.2 shall be permitted within exterior wall assemblies with a 2-hour rating or less.” | |
| 8 | 602.4.1.1 | Accurate and fully up-to-date | Omits Section 602.4.1.1 Exterior protection to Section 602.4.1.6 Shafts | |
| 9 | 602.4.1.2 | Accurate and fully up-to-date | Omits Section 602.4.1.2 and its subsection. | |
| 10 | 602.4.1.3 | Accurate and fully up-to-date | Omits Section 602.4.1.3. | |
| 11 | 602.4.1.4 | Accurate and fully up-to-date | Omits Section 602.4.1.4. | |
| 12 | 602.4.1.5 | Accurate and fully up-to-date | Omits Section 602.4.1.5. | |
| 13 | 602.4.1.6 | Accurate and fully up-to-date | Omits Section 602.4.1.6. | |
| 14 | 602.4.2 | Accurate and fully up-to-date | Section is outdated.
Incorrectly displays in the title, "Cross-laminated timber in exterior walls".
Incorrectly displays in the body, "Cross-laminated timber complying with Section 2303.1.4 shall be permitted within exterior wall assemblies with a 2-hour rating or less, provided the exterior surface of the cross-laminated timber is protected by one the following..." | |
| 15 | 602.4.2.1 | Accurate and fully up-to-date | Omits Section 602.4.2.1 Exterior protection through Section 602.4.2.6 Shafts | |
| 16 | 602.4.3 | Accurate and fully up-to-date | Section is outdated.
Incorrectly displays in the title “Columns”,
Incorrectly displays in the body "Wood columns shall be sawn or glued laminated and shall be not less than 8 inches (203 mm), nominal, in any dimension where supporting floor loads and not less than 6 inches (152 mm) nominal in width and not less than 8 inches (203 mm) nominal in depth where supporting roof and ceiling loads only. Columns shall be continuous or superimposed and connected in an approved manner. Protection in accordance with Section 704.2 is not required.” | |
| 17 | 602.4.3.1 | Accurate and fully up-to-date | Omits Sections 602.4.3.1 Exterior protection through Section 602.4.3.6 Shafts | |
| 18 | 602.4.4 | Accurate and fully up-to-date | Section is outdated.
Incorrectly displays in the title “Floor framing”,
Incorrectly displays in the body "Wood beams and girders shall be of sawn or glued-laminated timber and shall be not less than 6 inches (152 mm) nominal in width and not less than 10 inches (254 mm) nominal in depth. Framed sawn or glued-laminated timber arches, which spring from the floor line and support floor loads, shall be not less than 8 inches (203 mm) nominal in any dimension. Framed timber trusses supporting floor loads shall have members of not less than 8 inches (203 mm) nominal in any dimension.” | |
| 19 | 602.4.4.1 | Accurate and fully up-to-date | Omits Section 602.4.4.1 Fire-retardant-treated wood in exterior walls through Section 602.4.4.9 Exterior structural members | |
| 20 | 703.8 | Accurate and fully up-to-date | Omits Section 703.8. | |
| 21 | 703.9 | Accurate and fully up-to-date | Omits Section 703.9. | |
| 22 | 718.2.1 | Accurate and fully up-to-date | Missing Item #9 | |
| 23 | 722.7 | Accurate and fully up-to-date | Omits 722.7 Fire-resistance rating of mass timber and all its subsections | |
| 24 | 803.3 | Accurate and fully up-to-date | Missing at end of section “except in interior exit stairways, interior exit ramps, and exit passageways.” | |
| 25 | 907.2.3 | Accurate and fully up-to-date | Section is outdated.
Incorrectly shows in the body, "A manual fire alarm system that initiates the occupant notification signal meeting the requirements of Section 907.5 and installed in accordance with Section 907.6 shall be installed in Group E occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system..."
Missing list items #1 to #2.9.
Incorrectly showing "Reserved" in Exception #2.
Incorrect numbering for the 3rd Exception, it should become the 4th exceotion.
Mising Exception #5 and its sub-items. | |
| 26 | 907.2.3.1 | Accurate and fully up-to-date | Omits Section 907.2.3.1. | |
| 27 | 907.2.6.1 | Accurate and fully up-to-date | The Exception is incorrectly displayed twice. | |
| 28 | 907.2.6.4 | Accurate and fully up-to-date | Missing Exception #2 | |
| 29 | 907.10.2 | Accurate and fully up-to-date | Missing “an ESA/NTS certified fire alarm designer (CFAD) level III fire,” in the first sentence. | |
| 30 | 907.10.3 | Accurate and fully up-to-date | Missing “or an ESA/NTS certified fire alarm technician (CFAT) level II fire” at the end of the section. | |
| 31 | 1004.1.2 | Accurate and fully up-to-date | Missing footnote b in the Occupant Load Factor column for Standing Space (Assembly without fixed seats). The columns also do not correspond properly. Example: Standing space is incorrectly showing 15 net of Occupant Load Factor instead of 5 netb | |
Ohio | ||||
| 32 | 2306.3 | Accurate and fully up-to-date | Incorrectly displays “No. 16 gage galvanized staple” under column “Fastener Size” of Table 2306.3(2) instead of “No. 11 gage galvanized staple”. | |
New Jersey | ||||
| 33 | 911.1.1 | Accurate and fully up-to-date | Section body incorrectly ends with: “the fire subcode official” | |
New York City | ||||
| 34 | 107.9.2 | Accurate and fully up-to-date | Shows outdated section body:
“Alternative automatic fire-extinguishing systems plans shall comply with Section 904.1.1.” | |
| 35 | 110.3.7 | Accurate and fully up-to-date | Omits Section 110.3.7. | |
| 36 | 1109.2.4 | Accurate and fully up-to-date | Omits Section 1109.2.4. | |
| 37 | 1110.2 | Accurate and fully up-to-date | Item 4 incorrectly reads:
“4. At each separate-sex toilet and bathing room indicating the location ...” | |
| 38 | 1110.3 | Accurate and fully up-to-date | Item 7 is missing. | |
| 39 | 1502.1 | Accurate and fully up-to-date | Missing definition for “SUSTAINABLE ROOFING ZONE”. | |
| 40 | 1511.2 | Accurate and fully up-to-date | Omits Section 1511.2. | |
| 41 | 1704.20.10 | Accurate and fully up-to-date | Displays Section 1704.20.10 Special requirements for work in occupied multiple dwellings even though it is no longer part of the law | |
| 42 | 202 | Accurate and fully up-to-date | Missing definition for “ANIMAL SERVICE FACILITY” | |
| 43 | 2111.1 | Accurate and fully up-to-date | Section title incorrectly says "definition" instead of "general" and omits body text that says “All masonry fireplaces shall be installed, altered and maintained in buildings in conformity with the applicable provisions of the New York City Air Pollution Control Code and no new masonry fireplaces shall be permitted except those that burn the types of fuel allowed by section 24-149.2 of such code.” | |
| 44 | 304.1 | Accurate and fully up-to-date | Section body incorrectly says "animal hospitals, kennels and pounds" instead of "animal hospitals, kennels, pounds, veterinary clinics and pet shops " | |
| 45 | 3113 | Accurate and fully up-to-date | Omits Section 3113. | |
| 46 | 3301.11 | Accurate and fully up-to-date | Omits Section 3301.11. | |
| 47 | 3301.12 | Accurate and fully up-to-date | Omits Section 3301.12. | |
| 48 | 3301.13 | Accurate and fully up-to-date | Omits Section 3301.13. | |
| 49 | 3302.1 | Accurate and fully up-to-date | Section body incorrectly omits definitions for “100-HOUR TRAINING PROGRAM,” “ACTIVELY PROCTORED ONLINE TRAINING,” “LIMITED SITE SAFETY TRAINING (SST) CARD,” “OSHA 10-HOUR CLASS,” “OSHA 30-HOUR CLASS,” “SITE SAFETY TRAINING (SST) CARD,” “SITE SAFETY TRAINING (SST) CREDIT,” “SITE SAFETY TRAINING (SST) FULL COMPLIANCE DATE,” “SITE SAFETY TRAINING (SST) PROVIDER,” “SITE SAFETY TRAINING (SST) SECOND COMPLIANCE DATE,” “SITE SAFETY TRAINING (SST) SUPERVISOR CARD,” “SITE 11 SAFETY TRAINING (SST) TASK FORCE” and “TEMPORARY SITE SAFETY TRAINING (SST) CARD” | |
| 50 | 3303.10.2 | Accurate and fully up-to-date | Omits Section 3303.10.2. | |
| 51 | 3303.10.3 | Accurate and fully up-to-date | Omits Section 3303.10.3. | |
| 52 | 3303.5.4 | Accurate and fully up-to-date | Section body incorrectly says "particulate matter" instead of "dust" | |
| 53 | 3304.3.3 | Accurate and fully up-to-date | Section body is incorrect, for example, "excavation or drilling" instead of "soil or foundation work" | |
| 54 | 3310.10 | Accurate and fully up-to-date | Section body incorrectly omits “and section 3321” | |
| 55 | 3310.10.1 | Accurate and fully up-to-date | Section body incorrectly says "All workers employed at a major building site shall receive a site-specific safety
orientation program. This program shall include a review of any hazardous activities of the job that are
relevant to the tasks and activities to be performed. All workers must attend such a program no later than
seven days after commencing their employment at the site." instead of "The requirements of Section 3301.11 shall
apply." | |
| 56 | 3314.20 | Accurate and fully up-to-date | Omits Section 3314.20. | |
| 57 | 3319.11 | Accurate and fully up-to-date | Omits Section 3319.11. | |
| 58 | 3319.13 | Accurate and fully up-to-date | Omits Section 3319.13. | |
| 59 | 3319.2.3 | Accurate and fully up-to-date | Omits Section 3319.2.3. | |
| 60 | 3319.8.1 | Accurate and fully up-to-date | Item (9) shows “and the crane saftey coordinator or designee” which was removed. | |
| 61 | 3319.8.2 | Accurate and fully up-to-date | Incorrectly showing Item (4) as being “Crane safety coordinator”. | |
| 62 | 3319.8.3 | Accurate and fully up-to-date | Incorrectly showing Item (3) as being “Crane safety coordinator”. | |
| 63 | 3319.8.8 | Accurate and fully up-to-date | Item (1) shows “and the crane saftey coordinator or designee” which was removed. | |
| 64 | 3321 | Accurate and fully up-to-date | Omits Section 3321 and all its subsections | |
| 65 | 402.3 | Accurate and fully up-to-date | Section body should omit “the department and” | |
| 66 | 902.1 | Accurate and fully up-to-date | Omits definition for “NATURAL GAS ALARM” | |
| 67 | 903.1.1 | Accurate and fully up-to-date | Section body is incorrect, for example, "the discharge of water would be hazardous" instead of "permitted by the New York City Fire Code, the Fire Department may approve the installation of" | |
| 68 | 903.2.11.9 | Accurate and fully up-to-date | Section body incorrectly says "Section 904.11" instead of "this code and the New York City Fire Code." | |
| 69 | 903.2.2 | Accurate and fully up-to-date | Title is “Group B ambulatory health care facilities” when it should be “Group B”.
Displays outdated items (1) and (2) when section no longer has any items. | |
| 70 | 903.2.2.1 | Accurate and fully up-to-date | Omits Section 903.2.2.1. | |
| 71 | 903.2.2.2 | Accurate and fully up-to-date | Omits Section 903.2.2.2. | |
| 72 | 903.3.1.1.1 | Accurate and fully up-to-date | Section Incorrectly starts with “Automatic sprinklers shall not be required in the following rooms” | |
| 73 | 903.3.3 | Accurate and fully up-to-date | Exception incorrectly reads “...with a fire-extinguishing system in accordance with Section 904”. | |
| 74 | 904.2 | Accurate and fully up-to-date | Shows an exception even though this section no longer has one. | |
| 75 | 904.2.1 | Accurate and fully up-to-date | Section incorrectly starts with “Each required commercial kitchen exhaust hood and duct system required by the New York City Fire Code ...” | |
| 76 | 907.1 | Accurate and fully up-to-date | Omits last sentence of sections: “Systems shall be tested and maintained in accordance with this code and the New York City Fire Code.” | |
| 77 | 907.1.1 | Accurate and fully up-to-date | Section incorrectly starts with “Construction documents for fire alarm systems shall be submitted for review and approval to the department and the...” | |
| 78 | 907.1.1.1 | Accurate and fully up-to-date | Section incorrectly starts with “Amendments to approved construction documents shall be submitted, reviewed and approved before the final inspection...” | |
| 79 | 907.2.11.5 | Accurate and fully up-to-date | Omits Section 907.2.11.5. | |
| 80 | 908.10 | Accurate and fully up-to-date | Omits Section 908.10. | |
| 81 | 908.11 | Accurate and fully up-to-date | Omits Section 908.11. | |
| 82 | 908.7.1.1.2 | Accurate and fully up-to-date | Omits “and Section 907.7.1” at the end of the section. | |
| 83 | 908.7.3 | Accurate and fully up-to-date | Missing part of last sentence: “and (ii) addressing the installation of such detectors or any alternative means of compliance in existing buildings.” | |
| 84 | 908.7.3.1 | Accurate and fully up-to-date | Omits Section 908.7.3.1. | |
| 85 | 917.1.1 | Accurate and fully up-to-date | Body Section incorrectly says “shall be submitted for review and approval to the department and the Fire Department” instead of “shall be submitted for [review and] approval to [the department and] the Fire Department” | |
| 86 | 3319.13 | Accurate and fully up-to-date | Omits Section 3319.13. | |
| 87 | Q107 | Accurate and fully up-to-date | Omits Section Q107 and its subsection. | |
| 88 | §28-101.4.3 | Accurate and fully up-to-date | Omits Exception 12.4. | |
| 89 | §28-103.1 | Accurate and fully up-to-date | Section body of item 5 incorrectly says, "and fire extinguishing systems for commercial cooking appliances." instead of "alternative automatic fire extinguishing systems, including but not limited to fire extinguishing systems for commercial cooking equipment, and fire protection plans" | |
| 90 | §28-103.11 | Accurate and fully up-to-date | Section body incorrectly omits “The department shall, on a weekly basis, send council members and community boards, by electronic mail, a copy of all completed applications for a new building or an alteration that will require a new certificate of occupancy for a building, received during the prior week, disaggregated by community board. In addition, the department shall post such information on its website on a weekly basis.” | |
| 91 | §28-103.1.1 | Accurate and fully up-to-date | Section body incorrectly says “and sprinkler, and fire alarm systems is required by” instead of “sprinkler systems, fire alarm systems and alternative automatic fire extinguishing systems is required by” | |
| 92 | §28-103.21 | Accurate and fully up-to-date | Section body is incorrect, for example, "within the city of New York that resulted in an injury and/or a fatality, either or both of which were reported to the department or of which the department otherwise became aware. Such list shall be updated monthly." instead of "where construction work subject to permitting by the commissioner resulted in (i) a fatality to any individual, including a member of the general public or a construction worker, or (ii) an injury to any individual, including a member of the general public or a construction worker..." | |
| 93 | §28-103.21.1 | Accurate and fully up-to-date | Omits Section §28-103.21.1. | |
| 94 | §28-103.25 | Accurate and fully up-to-date | Omits Section §28-103.25. | |
| 95 | §28-103.26 | Accurate and fully up-to-date | Omits Section §28-103.26. | |
| 96 | §28-103.27 | Accurate and fully up-to-date | Omits Section §28-103.27. | |
| 97 | §28-103.28 | Accurate and fully up-to-date | Omits Section §28-103.28. | |
| 98 | §28-103.29.1 | Accurate and fully up-to-date | Omits Section §28-103.29.1. | |
| 99 | §28-103.30 | Accurate and fully up-to-date | Omits Section §28-103.30. | |
| 100 | §28-103.31 | Accurate and fully up-to-date | Omits Section §28-103.31. | |
| 101 | §28-103.32 | Accurate and fully up-to-date | Omits Section §28-103.32. | |
| 102 | §28-103.33 | Accurate and fully up-to-date | Omits Section 103.33 and all its subsections. | |
| 103 | §28-103.35 | Accurate and fully up-to-date | Omits Section §28-103.35. | |
| 104 | §28-104.2 | Accurate and fully up-to-date | Omits last sentence: “The department shall provide written notification to owners of adjoining property at the time such application is submitted.” | |
| 105 | §28-104.2.1 | Accurate and fully up-to-date | Omits the two exceptions. | |
| 106 | §28-104.2.1.2 | Accurate and fully up-to-date | Omits last sentence: “The commissioner shall send an annual notification to registered design professionals who ...” | |
| 107 | §28-104.2.1.3.2 | Accurate and fully up-to-date | Omits the sentence item (iii): “(iii) knowingly orders or directs another registered design
professional to submit a professional certification of an application and/or construction and any
other related document that ...” | |
| 108 | §28-104.2.1.3.2.2 | Accurate and fully up-to-date | Omits item (ii): “(ii) may permanently revoke the professional certification privileges of an engineer or architect who knowingly orders or directs another registered design professional to, while on probation, professionally certify” | |
| 109 | §28-104.2.7.1 | Accurate and fully up-to-date | Omits Section §28-104.2.7.1. | |
| 110 | §28-104.2.8 | Accurate and fully up-to-date | Omits last sentence: “The department shall, on a weekly basis, send council members and community boards, by electronic mail, a copy of all notices of a first rejection for applications for a new building or an alteration that ...” | |
| 111 | §28-104.8.4 | Accurate and fully up-to-date | Omits sentence in first paragraph: “Such means and methods shall be described with particularity and in no case shall terms such as ...” | |
| 112 | §28-104.8.4.1 | Accurate and fully up-to-date | Omits Section §28-104.8.4.1. | |
| 113 | §28-104.8.4.2 | Accurate and fully up-to-date | Omits Section §28-104.8.4.2. | |
| 114 | §28-104.8.4.3 | Accurate and fully up-to-date | Omits Section §28-104.8.4.3. | |
| 115 | §28-105.11 | Accurate and fully up-to-date | Omits last two sentences of first paragraph. | |
| 116 | §28-105.1.2 | Accurate and fully up-to-date | Omits Section §28-105.1.2. | |
| 117 | §28-105.12.11 | Accurate and fully up-to-date | Omits Section §28-105.12.11. | |
| 118 | §28-105.12.7.1 | Accurate and fully up-to-date | Omits last 2 sentences: “The department shall provide such proof of such insurance together with ...” | |
| 119 | §28-105.12.8 | Accurate and fully up-to-date | Section body outdated, for example, omits last sentence: “Site safety plans shall require approval of the department where specified in this code or the New York city building code.” | |
| 120 | §28-105.12.9 | Accurate and fully up-to-date | Omits Section §28-105.12.9. | |
| 121 | §28-105.1.3 | Accurate and fully up-to-date | Omits Section §28-105.1.3. | |
| 122 | §28-105.1.4 | Accurate and fully up-to-date | Omits Section §28-105.1.4. | |
| 123 | §28-105.1.5 | Accurate and fully up-to-date | Omits Section §28-105.1.5. | |
| 124 | §28-105.2 | Accurate and fully up-to-date | Item (10) includes outdated text that was removed: “non-water systems, and fire suppression systems for commercial cooking equipment” | |
| 125 | §28-105.4 | Accurate and fully up-to-date | Omits items (8) and (9). | |
| 126 | §28-105.5 | Accurate and fully up-to-date | Omits last sentence of the section. | |
| 127 | §28-105.5.1 | Accurate and fully up-to-date | Omits second occurence of Section 105.5.1 (NYC has two sections with this section number). | |
| 128 | §28-105.5.2 | Accurate and fully up-to-date | Omits Section 105.5.2 and its subsection. | |
| 129 | §28-106.1.1 | Accurate and fully up-to-date | Has outdated text “with subdivision (o) of section 24-146.1”. Updated text is: “with subdivision (m) of section 24-136”. | |
| 130 | §28-106.1.2 | Accurate and fully up-to-date | Has outdated text “with subdivision (o) of section 24-146.1”. Updated text is: “with subdivision (m) of section 24-136”. | |
| 131 | §28-106.3 | Accurate and fully up-to-date | Has outdated section reference: “be permitted pursuant to section 24-146.3” instead of “pursuant to section 24-138” | |
| 132 | §28-106.4 | Accurate and fully up-to-date | Has outdated section reference: “ascribed in section 24-146.1” instead of “ascribed in section 24-136”. | |
| 133 | §28-109.1 | Accurate and fully up-to-date | Omits last sentence of first paragraph: “The fire protection plan shall be submitted in accordance with the rules and regulations of the fire department.” | |
| 134 | §28-112.12 | Accurate and fully up-to-date | Omits Section §28-112.12. | |
| 135 | §28-112.2 | Accurate and fully up-to-date | Certain cells from Table 28-112.2 are out of date, for example, in the first row, under “FILING FEE”, display “$0.12 for each square foot...” instead of “$0.06 for each square foot...” and omits text “The rates and fees set forth above shall be subject to increases as provided by department rules.” | |
| 136 | §28-116.2.1 | Accurate and fully up-to-date | Omits last sentence of the section: “The department shall conduct preliminary inspections of no less than 20 percent of buildings containing ...” | |
| 137 | §28-116.2.1.1 | Accurate and fully up-to-date | Omits Section §28-116.2.1.1. | |
| 138 | §28-116.2.4 | Accurate and fully up-to-date | Contains outdated text “with sections 28-116.2.4.1 through 28-116.2.4.2“ instead of “with sections 28-116.2.4.1 through 28-116.2.4.3”. | |
| 139 | §28-116.2.4.2 | Accurate and fully up-to-date | Omits exception at the end of the section. | |
| 140 | §28-116.2.4.3 | Accurate and fully up-to-date | Omits Section §28-116.2.4.3. | |
| 141 | §28-119.4 | Accurate and fully up-to-date | Omits Section §28-119.4. | |
| 142 | §28-201.2.1 | Accurate and fully up-to-date | Omits items, for example items (17), (18), (19). | |
| 143 | §28-201.2.2 | Accurate and fully up-to-date | Omits items (6) and (7). | |
| 144 | §28-201.2.3 | Accurate and fully up-to-date | Item (1) shows outdated text “a violation of section 28-313.1, or 28-313.2” instead of “a violation of section 28-313.1, 28-313.2 or 28-313.3”. | |
| 145 | §28-202.1 | Accurate and fully up-to-date | Missing all exceptions. | |
| 146 | §28-202.3 | Accurate and fully up-to-date | Omits Section 202.3 and its subsection 202.3.1. | |
| 147 | §28-202.4 | Accurate and fully up-to-date | Omits Section 202.4 and it subsection | |
| 148 | §28-203.1 | Accurate and fully up-to-date | Missing all exceptions. | |
| 149 | §28-204.1.1 | Accurate and fully up-to-date | Omits Section §28-204.1.1. | |
| 150 | §28-204.1.2 | Accurate and fully up-to-date | Omits Section §28-204.1.2. | |
| 151 | §28-204.1.3 | Accurate and fully up-to-date | Omits Section §28-204.1.3. | |
| 152 | §28-204.6 | Accurate and fully up-to-date | Omits the exception. | |
| 153 | §28-204.6.1 | Accurate and fully up-to-date | Omits second occurrence of Section 204.6.1 (NYC mistakenly has two different sections with the same refernece). | |
| 154 | §28-207.2.6 | Accurate and fully up-to-date | Has incorrect penalty amounts: “ a civil penalty in the amount of five thousand dollars for the initial violation and ten thousand dollars for every subsequent violation” | |
| 155 | §28-207.4 | Accurate and fully up-to-date | Omits last sentence of the section: “The written vacate order shall include the date by which the owner shall certify the correction of any and all violations giving rise to such vacate order.” | |
| 156 | §28-210.1.1 | Accurate and fully up-to-date | Omits Section §28-210.1.1. | |
| 157 | §28-210.3.1 | Accurate and fully up-to-date | Omits Section §28-210.3.1. | |
| 158 | §28-211.1.3 | Accurate and fully up-to-date | Omits Section §28-211.1.3. | |
| 159 | §28-211.1.4 | Accurate and fully up-to-date | Omits Section §28-211.1.4. | |
| 160 | §28-211.3 | Accurate and fully up-to-date | Omits Section 211.3 and its subsection 211.3.1. | |
| 161 | §28-213.1 | Accurate and fully up-to-date | Missing the exception. | |
| 162 | §28-213.1.1 | Accurate and fully up-to-date | Has outdated penalty amounts: “Notwithstanding the foregoing, no such penalty shall be less than five hundred dollars.” | |
| 163 | §28-213.1.2 | Accurate and fully up-to-date | Has outdated penalty amounts: “Notwithstanding the foregoing, no such penalty shall be less than five thousand dollars.” | |
| 164 | §28-213.5 | Accurate and fully up-to-date | Omits Section 213.5 and all its subsections. | |
| 165 | §28-213.6 | Accurate and fully up-to-date | Omits Section §28-213.6. | |
| 166 | §28-213.7 | Accurate and fully up-to-date | Omits Section §28-213.7. | |
| 167 | §28-219.4 | Accurate and fully up-to-date | Omits Section §28-219.4. | |
| 168 | §28-304.10 | Accurate and fully up-to-date | Missing text, for example, missing “shall be provided in
English, Spanish, and such other languages as the department may provide by rule” | |
| 169 | §28-304.10.1 | Accurate and fully up-to-date | Omits Section §28-304.10.1. | |
| 170 | §28-304.10.2 | Accurate and fully up-to-date | Omits Section §28-304.10.2. | |
| 171 | §28-308.1 | Accurate and fully up-to-date | Omits definition for “COOPERATIVE CORPORATION”. | |
| 172 | §28-308.4.1 | Accurate and fully up-to-date | Missing Exception #2: “A cooperative corporation that owns multiple covered buildings located on ...” | |
| 173 | 309 | Accurate and fully up-to-date | Section title incorrectly says “BENCHMARKING ENERGY AND WATER USE” instead of “BENCHMARKING ENERGY AND WATER USE AND DISCLOSURE OF ENERGY EFFICIENCY SCORES AND GRADES” | |
| 174 | §28-309.11 | Accurate and fully up-to-date | Omits Section §28-309.11. | |
| 175 | §28-309.12 | Accurate and fully up-to-date | Omits Section §28-309.12. | |
| 176 | §28-309.2 | Accurate and fully up-to-date | In definition of “CITY BUILDING”, Includes outdated Exception 1, which was removed and the other exceptions renumbered. | |
| 177 | §28-309.4 | Accurate and fully up-to-date | Omits the exception in this section. | |
| 178 | §28-309.4.1 | Accurate and fully up-to-date | Section starts with outdated text: “Where a unit or other space in a covered building, other than a dwelling unit, is occupied by...” | |
| 179 | §28-309.4.2 | Accurate and fully up-to-date | Omits text “Where energy use within separately metered
tenant spaces is omitted, records shall be maintained documenting the owner’s efforts to obtain such information” | |
| 180 | §28-309.4.3 | Accurate and fully up-to-date | Omits the exception in this section. | |
| 181 | §28-309.5.1 | Accurate and fully up-to-date | Contains outdated text that was removed: “Where
information is uploaded directly to the benchmarking tool by ...” | |
| 182 | §28-309.8 | Accurate and fully up-to-date | Contains outdated text that was removed: “... and no
later than every September first thereafter for city buildings, no later than September 1, 2012, and no later than every September first thereafter ...” | |
| 183 | §28-309.9 | Accurate and fully up-to-date | Contains outdated text in first sentence: “No later than December 31 of [2011, 2012 and 2013, respectively” | |
| 184 | §28-310.2 | Accurate and fully up-to-date | Definition for “COVERED BUILDING” is outdated, for example, displaying “a building that exceeds 50,000 gross square feet (4645 m2)” instead of “a building that exceeds 25,000 gross square feet (2323 m2)”. | |
| 185 | §28-310.3 | Accurate and fully up-to-date | Contains outdated text, for example, first sentence starts with “The lighting systems of covered buildings shall be upgraded to comply” instead of “No later than January 1, 2025 the lighting systems of covered buildings shall be in compliance with” | |
| 186 | §28-311.2 | Accurate and fully up-to-date | Omits Exception #2 under definition of “COVERED BUILDING”. | |
| 187 | §28-311.3 | Accurate and fully up-to-date | Contains outdated text: “each tenancy that is 10,000 gross square feet (929 m2) or less shall” instead of “each
tenancy that is 5,000 gross square feet (465 m2) or less shall”. | |
| 188 | §28-311.5 | Accurate and fully up-to-date | Contains outdated text in first sentence: “The owner of each covered building shall file a report with the department on or prior to January 1, 2025 prepared by” instead of “The owner of each covered building shall file a report in accordance with the rules of the department prepared by”. | |
| 189 | §28-312.1 | Accurate and fully up-to-date | Omits text “and natural gas” | |
| 190 | §28-312.2 | Accurate and fully up-to-date | In the exception, omits text “before April 25, 2012” and “ before October 25, 2012”. | |
| 191 | §28-312.3 | Accurate and fully up-to-date | Displays outdated text: “installed after the effective date of this article” instead of “installed after April 25, 2012”. | |
| 192 | §28-312.4 | Accurate and fully up-to-date | Exception contains outdated text that was removed: “within 7 years after the effective date of this section”. | |
| 193 | §28-312.5 | Accurate and fully up-to-date | Displays outdated text: “installed after the effective date of this section” instead of “installed after April 1, 2014”. | |
| 196 | §28-312.8 | Accurate and fully up-to-date | Omits Section §28-312.8. | |
| 197 | §28-313.3 | Accurate and fully up-to-date | Omits Section 313.3 and all its subsections. | |
| 198 | §28-315.10 | Accurate and fully up-to-date | Omits Section §28-315.10. | |
| 199 | §28-315.11 | Accurate and fully up-to-date | Omits Section §28-315.11. | |
| 200 | §28-315.2.3 | Accurate and fully up-to-date | Omits Section §28-315.2.3. | |
| 201 | §28-315.2.4 | Accurate and fully up-to-date | Omits Section §28-315.2.4. | |
| 202 | §28-315.3.1 | Accurate and fully up-to-date | Omits text, for example, omits last sentence: “The department may impose a fee for filing and reviewing such reports.” | |
| 203 | §28-315.3.2 | Accurate and fully up-to-date | Omits text, for example, omits last sentence: “The Department may impose a fee for filing and reviewing such reports.” | |
| 204 | §28-315.6.3 | Accurate and fully up-to-date | Omits Section §28-315.6.3. | |
| 205 | §28-315.9 | Accurate and fully up-to-date | Omits Section §28-315.9. | |
| 206 | 317 | Accurate and fully up-to-date | Omits Section 317 and all its subsections. | |
| 207 | 318 | Accurate and fully up-to-date | Omits Article 318 and all its subsections | |
| 208 | 319 | Accurate and fully up-to-date | Omits Article 319 and all its subsections | |
| 209 | 320 | Accurate and fully up-to-date | Omits Article 320 and all its subsections | |
| 210 | 321 | Accurate and fully up-to-date | Omits Article 321 and all its subsections | |
| 211 | 322 | Accurate and fully up-to-date | Omits Article 322 and all its subsections | |
| 212 | §28-401.15 | Accurate and fully up-to-date | Table values add a new row for “Lift director registration” | |
| 213 | §28-405.2 | Accurate and fully up-to-date | Section Body incorrectly says “include the operation of any hoisting machinery without limitation or restriction” instead of “include the operation of any hoisting machinery, except that” | |
| 214 | §28-405.3.2 | Accurate and fully up-to-date | Section Body incorrectly says “license shall have the following additional qualifications” instead of “license shall have the following qualifications” | |
| 215 | §28-405.3.2.1 | Accurate and fully up-to-date | Omits Section §28-405.3.2.1. | |
| 216 | §28-405.3.2.2 | Accurate and fully up-to-date | Omits Section §28-405.3.2.2. | |
| 217 | §28-424.3 | Accurate and fully up-to-date | Omits Section §28-424.3. | |
| 218 | §28-423.4 | Accurate and fully up-to-date | Omits Section §28-423.4. | |
| 219 | §28-504.1 | Accurate and fully up-to-date | Section body is incorrect, for example, displays “Applicability” instead of “Bicycle Access to Certain Office Buildings” | |
| 220 | §28-504.1.1 | Accurate and fully up-to-date | Section 28-504.2 should have been renamed to Section 28-504.1.1 | |
| 221 | §28-504.1.2 | Accurate and fully up-to-date | Section 28-504.3 should have been renamed to Section 28-504.1.2 | |
| 222 | §28-504.1.2.1 | Accurate and fully up-to-date | Omits Section §28-504.1.2.1. | |
| 223 | §28-504.1.2.2 | Accurate and fully up-to-date | Omits Section §28-504.1.2.2. | |
| 224 | §28-504.1.2.3 | Accurate and fully up-to-date | Omits Section §28-504.1.2.3. | |
| 225 | §28-504.1.2.4 | Accurate and fully up-to-date | Omits Section §28-504.1.2.4. | |
| 226 | §28-504.1.3 | Accurate and fully up-to-date | Section 28-504.4 should have been renamed to Section 28-504.1.3 | |
| 227 | §28-504.1.4 | Accurate and fully up-to-date | Section 28-504.6 should have been renamed to Section 28-504.1.4 | |
| 228 | §28-504.1.4.1 | Accurate and fully up-to-date | Omits Section §28-504.1.4.1. | |
| 229 | §28-504.1.4.2 | Accurate and fully up-to-date | Omits Section §28-504.1.4.2. | |
| 230 | §28-504.1.4.3 | Accurate and fully up-to-date | Omits Section §28-504.1.4.3. | |
| 231 | §28-504.1.5 | Accurate and fully up-to-date | Section 28-504.7 should have been renamed to Section 28-504.1.5 and amended. | |
| 232 | §28-504.3 | Accurate and fully up-to-date | The Section 28-504.3 shown on ICC was renamed to section 28-504.1.2 in No. 105 of the Local Laws of NYC. Then, also in the No. 105 edition of the Local Laws of NYC, a new and completely different Section 28-504.3 was added. Therefore, ICC currently shows an outdated section in place of the current section. | |
| 233 | §28-504.4 | Accurate and fully up-to-date | The Section 28-504.4 shown on ICC was renamed to section 28-504.1.3 in No. 105 of the Local Laws of NYC. Then, also in the No. 105 edition of the Local Laws of NYC, a new and completely different Section 28-504.4 was added. Therefore, ICC currently shows an outdated section in place of the current section. | |
| 234 | §28-505.1 | Accurate and fully up-to-date | Omits Section §28-505.1. | |
| 235 | §28-505.2 | Accurate and fully up-to-date | Omits Section §28-505.2. | |
| 236 | §28-505.3 | Accurate and fully up-to-date | Omits Section §28-505.3. | |
| 237 | §28-505.4 | Accurate and fully up-to-date | Omits Section §28-505.4. | |
| 238 | §28-505.5 | Accurate and fully up-to-date | Omits Section §28-505.5. | |
| 239 | §28-505.6 | Accurate and fully up-to-date | Omits Section §28-505.6. | |
| 240 | §28-505.7 | Accurate and fully up-to-date | Omits Section §28-505.7. | |
| 241 | §28-505.8 | Accurate and fully up-to-date | Omits Section §28-505.8. | |
| 242 | 504 | Accurate and fully up-to-date | Title incorrectly shows “Bicycle Access to Office Buildings” instead of “Bicycle Access to Buildings” | |
| 243 | 505 | Accurate and fully up-to-date | Omits Section 505. | |
| 244 | 106.8 | Accurate and fully up-to-date | Section body is incorrect, for example, includes text that should be omitted in item (5): “type of extinguishing system, the location of heat detection devices, nozzles, piping,”. | |
| 245 | 901.3 | Accurate and fully up-to-date | Omits Section 901.3. | |
| 246 | 901.4 | Accurate and fully up-to-date | Section incorrectly labelled as 901.3 instead of 901.4 | |
| 247 | 901.5 | Accurate and fully up-to-date | Section incorrectly labelled as 901.4 instead of 901.5 | |
| 248 | 901.6 | Accurate and fully up-to-date | Section incorrectly labelled as 901.5 instead of 901.6 | |
| 249 | 901.7 | Accurate and fully up-to-date | Section incorrectly labelled as 901.6 instead of 901.7 | |
| 250 | 202 | Accurate and fully up-to-date | Missing a definition: “SINGLE-OCCUPANT TOILET ROOM” | |
| 251 | 403.1 | Accurate and fully up-to-date | Note J is outdated, for example, showing “unisex” instead of “single-occupant”. | |
| 252 | 403.1.3 | Accurate and fully up-to-date | Omits Section 403.1.3. | |
| 253 | 403.2.1 | Accurate and fully up-to-date | Omits Section 403.2.1. | |
| 254 | 403.4 | Accurate and fully up-to-date | Section body is incorrect, for example, section body should include ”or, for a single-occupant toilet room, for all sexes.” | |
Oregon | ||||
| 255 | 908.7 | Accurate and fully up-to-date | Section body incorrectly excludes “Section 9.4.2.2 of NFPA 720 is not adopted.” | |
| 256 | 503.2.3 | Accurate and fully up-to-date | In Table 503.2.3(3), has outdated values. For example, the “MINIMUM EFFICIENCY” for the “SPVAC” row should be “10.0 ERR”, but here it is shown as “9.0 ERR”, “8.9 ERR” and “8.6 ERR”. | |
| 257 | 201.3 | Accurate and fully up-to-date | Section body incorrectly still includes “Fire Code, Fuel Gas Code” | |
| 258 | 202 | Accurate and fully up-to-date | Incorrectly still displays definition for “FIRE CODE” | |
| 259 | 502.4 | Accurate and fully up-to-date | Section body incorrectly says “ Section 608 of the Fire Code” instead of “Appendix N of the Building Code” | |
| 260 | 502.5 | Accurate and fully up-to-date | Section body incorrectly says “ Section 608.6.2 of the Fire Code” instead of “Appendix N of the Building Code” | |
| 261 | 502.7.2 | Accurate and fully up-to-date | Section body incorrectly says “ the Fire Code” instead of “Appendix N of the Building Code” | |
| 262 | 502.8.1 | Accurate and fully up-to-date | Exception incorrectly says “complying with Section 5904 of the Fire Code” instead of “complying with Appendix N of the Building Code”. | |
| 263 | 502.9.1 | Accurate and fully up-to-date | Section body incorrectly says “ Fire Code” instead of “Building Code” | |
| 264 | 502.9.5 | Accurate and fully up-to-date | Section body incorrectly says “ Fire Code” instead of “Building Code” | |
| 265 | 502.9.8.2 | Accurate and fully up-to-date | Section body incorrectly says “ Fire Code” instead of “Building Code” | |
| 266 | 502.9.8.3 | Accurate and fully up-to-date | Section body incorrectly says “ Fire Code” instead of “Building Code” | |
| 267 | 502.9.8.5 | Accurate and fully up-to-date | Section body incorrectly says “Fire Code” instead of “Building Code” | |
| 268 | 502.9.8.6 | Accurate and fully up-to-date | Section body incorrectly says “Fire Code” instead of “Building Code” | |
| 269 | 502.9.11 | Accurate and fully up-to-date | Section body incorrectly says “Chapter 64 of the Fire Code” instead of “the Building Code” | |
| 270 | 502.10 | Accurate and fully up-to-date | Section body incorrectly says “the Building Code and the Fire Code” instead of “the Building Code” | |
| 271 | 502.10.1 | Accurate and fully up-to-date | Text of item (8) incorrectly says “Section 2705.2.3.4 of the Fire Code” instead of “the Building Code” | |
| 272 | 502.10.3 | Accurate and fully up-to-date | Section body incorrectly says “Fire Code” instead of “Building Code” | |
| 273 | 502.16.2 | Accurate and fully up-to-date | Exception (1) incorrectly has “Fire Code” instead of “Building Code” | |
| 274 | 510.2.1 | Accurate and fully up-to-date | Section body incorrectly says “with this section and Fire Code” instead of “with this section and Building Code” | |
| 275 | 510.2.2 | Accurate and fully up-to-date | Section body incorrectly says “with this code and the Fire Code” instead of “with this section and the Building Code” | |
| 276 | 510.4 | Accurate and fully up-to-date | Section body incorrectly says “as defined in the Fire Code” instead of “as defined in the Building Code” | |
| 277 | 511.1.1 | Accurate and fully up-to-date | Section body is incorrect, for example, "installation is in accordance with NFPA 654 and 664" instead of "installation is in accordance with the Building Code, NFPA 654 and 664" | |
| 278 | 513.1 | Accurate and fully up-to-date | Section body incorrectly says “that are required by the Fire Code” instead of “that are required by the Building Code” | |
| 279 | 513.2 | Accurate and fully up-to-date | Section body incorrectly says “required by the Fire Code” instead of “required by the Building Code” | |
| 280 | 513.12 | Accurate and fully up-to-date | Section body incorrectly says “requirements of Chapter 9 of the Building Code or the Fire Code” instead of “requirements of Chapter 9 of the Building Code” | |
| 281 | 513.12.2 | Accurate and fully up-to-date | Section body incorrectly says “in accordance with the Building Code or the Fire Code” instead of “in accordance with the Building Code” | |
| 282 | 513.12.3 | Accurate and fully up-to-date | Section body incorrectly says “automatic sprinkler system complying with Section 903.3.1.1 of the Fire Code” instead of “automatic sprinkler system complying with the Building Code” | |
| 283 | 513.15 | Accurate and fully up-to-date | Section body incorrectly says “maintained as required by the Fire Code” instead of “maintained as required by the Building Code.” | |
| 284 | 513.16 | Accurate and fully up-to-date | Section incorrectly says “Fire Code” instead of “Building Code” | |
| 285 | 513.17 | Accurate and fully up-to-date | Section incorrectly says “Fire Code” instead of “Building Code” | |
| 286 | 513.18 | Accurate and fully up-to-date | Section incorrectly says “Fire Code” instead of “Building Code” | |
| 287 | 513.19 | Accurate and fully up-to-date | Section incorrectly says “Fire Code” instead of “Building Code” | |
| 288 | 606.2.1 | Accurate and fully up-to-date | The exception incorrectly has “Fire Code” instead of “Building Code” | |
| 289 | 606.4.1 | Accurate and fully up-to-date | Section incorrectly says “Section 907.2 of the Fire Code” instead of “Building Code” | |
| 290 | 908.7 | Accurate and fully up-to-date | Section incorrectly says “Fire Code” instead of “Building Code” | |
| 291 | 924.1 | Accurate and fully up-to-date | Section body incorrectly says “manufacturer’s installation instructions, NFPA 853, and the Fire Code.” instead of “manufacturer’s installation instructions, NFPA 853, and the Building Code .” | |
| 292 | 926.1 | Accurate and fully up-to-date | Section Body incorrectly says “requirements of this code, the Fire Code, the Mechanical Code and the Building Code” instead of “requirements of this code and the Building Code” | |
| 293 | 1105.9 | Accurate and fully up-to-date | Section incorrectly says “Section 603.10 of the Fire Code” instead of “Building Code” | |
| 294 | 1106.6 | Accurate and fully up-to-date | Section incorrectly says “Fire Code” instead of “Building Code” | |
| 295 | 1301.2 | Accurate and fully up-to-date | Section incorrectly says “Section 603.3 of the Fire Code” instead of “Building Code” | |
| 296 | 1301.5 | Accurate and fully up-to-date | Displays Section 1301.5 Tanks abandoned or removed even though it is no longer part of the law | |
| 297 | C412.1 | Accurate and fully up-to-date | Displays Section C412.1 General even though it is no longer part of the law | |
| 298 | C413.1 | Accurate and fully up-to-date | Displays Section C413.1 General even though it is no longer part of the law | |
| 299 | C632.1 | Accurate and fully up-to-date | Section body incorrectly says "NFPA 853, the Building Code and the Fire Code.” instead of “NFPA 853, and the Building Code ” | |
| 300 | C634.1 | Accurate and fully up-to-date | Section body incorrectly says "requirements of this code, the Fire Code and the Building Code” instead of “requirements of this code, and the Building Code” | |
| 301 | R327.2 | Accurate and fully up-to-date | Section body incorrectly does not include “The additional provisions of Section R327.4 shall apply
when a local municipality has adopted a local ordinance
specifically recognizing Section R327.4 and consistent with
Sections R327.4 through R327.4.8.” | |
| 302 | R327.3 | Accurate and fully up-to-date | Section body incorrectly says “Wildfire hazard zone. A wild fire hazard zone is an area legally determined by a jurisdiction to have special hazards caused by a combination of combustible natural fuels, topography and climatic conditions that result in a significant hazard of catastrophic fire over relatively long periods each year.”
instead of “Wildfire hazard zones shall be determined using criteria established by the Oregon Department of Forestry.” | |
| 303 | R327.3.1 | Accurate and fully up-to-date | Section body incorrectly does not include “. The provisions of Section R327.4 apply only to qualifying lots identified in Section R327.4.1.
Exception: Nonhabitable detached accessory structures, with an area of not greater than 400 square feet,
located at least 50 feet from all other structures on the
lot.” | |
| 304 | R327.4 | Accurate and fully up-to-date | Omits Section R327.4 and all its subsections. | |
Florida | ||||
| 305 | 102.8 | Accurate and fully up-to-date | Section body has incorrect placement of “during reroofing” | |
| 306 | 105.3 | Accurate and fully up-to-date | Section body incorrectly excludes “Effective October 1, 2017, a local enforcement agency shall post each type of building permit application on its website. Completed applications” | |
| 307 | 105.15 | Accurate and fully up-to-date | Section body incorrectly excludes “not including roof covering replacement or repair work associated with the prevention of degradation of the residence” | |
| 308 | 403.6.1 | Accurate and fully up-to-date | Section body incorrectly says “above the lowest level of fire department vehicle access,” instead of “measured from the elevation of street-level access to the level of the highest occupiable floor. | |
| 309 | 453.25.4.5.1 | Accurate and fully up-to-date | Section body is incorrect, for example, does not include“Exception: Exposed mechanical equipment or appliances fastened to a roof or installed on the ground in compliance with the code using rated stands, platforms, curbs, slabs, walls, or other means are deemed to comply with the wind resistance requirements of the 2007 Florida Building Code, as amended. Further support or enclosure of such mechanical equipment or appliances is not required by a state or local official having authority to enforce the Florida Building Code. ” | |
| 310 | 454.2.17.1.9 | Accurate and fully up-to-date | Section body does not include item 3. | |
| 311 | 903.2.1.2 | Accurate and fully up-to-date | Section body incorrectly does not include “A restaurant, cafeteria, or similar dining facility, including an associated commercial kitchen, is required to have sprinklers only if it has a fire area occupancy load of 200 patrons or more.” | |
| 312 | 1203.1 | Accurate and fully up-to-date | Section body incorrectly says "less than 5 air changes per hour" instead of "less than 3 air changes per hour | |
| 313 | 1609.1.1 | Accurate and fully up-to-date | Section body incorrectly excludes exception 8. | |
| 314 | 1620.1 | Accurate and fully up-to-date | Section body incorrectly excludes exception. | |
| 315 | 1620.6 | Accurate and fully up-to-date | Missing Exception | |
| 316 | 3007.7 | Accurate and fully up-to-date | Missing Exception #2 | |
| 317 | 3007.10.1 | Accurate and fully up-to-date | Missing Exception | |
| 318 | 3013 | Accurate and fully up-to-date | Omits Section 3013. | |
| 319 | 101.8 | Accurate and fully up-to-date | Section body incorrectly places “during reroofing” | |
| 320 | 301.1.5 | Accurate and fully up-to-date | Section body incorrectly places “during reroofing” | |
| 321 | 403.7 | Accurate and fully up-to-date | Section body is incorrect, for example, says “ Effective January 1, 2015” | |
| 322 | 703.2 | Accurate and fully up-to-date | Section body is incorrect, for example, say “ Effective January 1, 2015,” | |
| 323 | C104.5 | Accurate and fully up-to-date | Section body incorrectly says "reports of approved inspection agencies” instead of “inspection reports in whole or in part of from either individuals as defined in Section 553.993(5) or (7), Florida Statutes or approved inspection agencies” | |
| 324 | R101.4.9 | Accurate and fully up-to-date | Omits Section R101.4.9. | |
| 325 | R104.5 | Accurate and fully up-to-date | Section body incorrectly says "The code official is authorized to accept reports of approved inspection agencies, provided such agencies satisfy the requirements as to qualifications and reliability” instead of “The code official is authorized to accept inspection reports in whole or in part from either individuals as defined in Section 553.993(5) or (7), Florida Statutes or approved inspection agencies, provided such agencies satisfy the requirements as to qualifications and reliability” | |
| 326 | R402.4.1.2 | Accurate and fully up-to-date | Section body incorrectly says "Where required by the code official, Testing shall be conducted by an approved third party. ” instead of “Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. ” | |
| 327 | R403.2.2 | Accurate and fully up-to-date | Section body incorrectly says “Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.990, Florida Statutes, or as authorized by” instead of “Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i),” | |
| 328 | R405.5.2 | Accurate and fully up-to-date | Table values changed for “Air Exchange Rate” | |
| 329 | R406 | Accurate and fully up-to-date | Omits Section R406. | |
| 330 | 301.10 | Accurate and fully up-to-date | Section body incorrectly excludes exception. | |
| 331 | 301.15 | Accurate and fully up-to-date | Section body incorrectly excludes exception. | |
| 332 | 401.2 | Accurate and fully up-to-date | Section body incorrectly says "less than 5 air changes per hour" instead of "less than 3 air changes per hour | |
| 333 | R202 | Accurate and fully up-to-date | Missing item #4 for the definition of “FIRE SEPARATION DISTANCE | |
| 334 | R302.1 | Accurate and fully up-to-date | Missing Exception #7 | |
| 335 | R303.4 | Accurate and fully up-to-date | Section body incorrectly says "less than 5 air changes per hour" instead of "less than 3 air changes per hour | |
| 336 | P2709.2 | Accurate and fully up-to-date | Missing exceptions #1 and #2 | |
| 337 | R321.4 | Accurate and fully up-to-date | Omits Section R321.4. | |
| 338 | R4501.17.1.9 | Accurate and fully up-to-date | Missing item #3 | |
| 339 | 1010.9 | Accurate and fully up-to-date | Exception incorrectly reads “for ramped aisles” instead of “Handrails for ramped aisles” | |
North Carolina | ||||
| 340 | 508.4 | Accurate and fully up-to-date | Incorrect superscripts on some table values. | |
| 341 | 901.1 | Accurate and fully up-to-date | Section body incorrectly says "The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation, inspection, operation, testing and maintenance of all fire protection
systems.
" instead of "The provisions of the International Building Code shall specify where fire protection systems are required. The provisions of the International Fire Code shall determine the design, installation, inspection, operation, testing and maintenance of all fire protection systems.” | |
| 342 | 915.1.1 | Accurate and fully up-to-date | Incorrectly excludes “Group A-2” | |
| 343 | 915.1.2 | Accurate and fully up-to-date | Missing “Group A-2 occupancies” | |
| 344 | 915.1.3 | Accurate and fully up-to-date | Missing “Group A-2 occupancies” | |
| 345 | 915.4.1 | Accurate and fully up-to-date | Incorrectly excludes Exception #2 | |
| 346 | 1009.7.2 | Accurate and fully up-to-date | Incorrectly excludes Exception #2 | |
| 347 | 1010.1.9.11 | Accurate and fully up-to-date | Exception #3 is incorrect and Exception #6 should be omitted | |
| 348 | 1020.1 | Accurate and fully up-to-date | Item (f) is outdated and incorrectly ends with "in Types IB, IIB and VB construction." instead of “In Types IIB, IIIB, and VB construction.” | |
| 349 | 1705.4 | Accurate and fully up-to-date | Incorrectly excludes Exception #4 | |
| 350 | 2902.1 | Accurate and fully up-to-date | Incorrectly display “1 per 60” under column “BATHTUBS / SHOWERS” in the row for “Educational” occupancy group. | |
| 351 | 2902.1.1 | Accurate and fully up-to-date | Exception #2 is outdated. It is missing the last sentence “In multi-story structures, the residential units located not more than one story above or below the pool and pool deck may be included in the percentage. Travel from the pool to the required toilet facilities shall be on an accessible route.” The word “total” in the first sentence should have been removed and “feet” was updated to “foot horizontal travel distance” in the first sentence. | |
| 352 | 312.1 | Accurate and fully up-to-date | Incorrectly says “Fences more than 6 feet” instead of “Fences and ground signs more than 6 feet” | |
| 353 | H101.2 | Accurate and fully up-to-date | Missing Item #6 | |
| 354 | H109.2 | Accurate and fully up-to-date | Incorrectly excludes Exception | |
| 355 | 101.12 | Accurate and fully up-to-date | Missing first sentence and Exception #2. | |
| 356 | 403.11 | Accurate and fully up-to-date | Section body incorrectly says “classrooms in Group E occupancies shall be provided with carbon monoxide alarms” instead of “classrooms in Group E occupancies and Group A-2 occupancies that contain a fuel-burning appliance or a fuel-burning fireplace shall be provided with carbon monoxide alarms” | |
| 357 | 804.4.3 | Accurate and fully up-to-date | Section body incorrectly says “classrooms in Group E occupancies shall be provided with carbon monoxide alarms” instead of “classrooms in Group E occupancies and Group A-2 occupancies that contain a fuel-burning appliance or a fuel-burning fireplace shall be provided with carbon monoxide alarms” | |
| 358 | 1104.2 | Accurate and fully up-to-date | Section body incorrectly says “made to a building or structure of a Group I-1, I-2, I-4 or R occupancies” instead of “made to a building or structure of a Group A-2, I-1, I-2, I-4 or R occupancies” | |
| 359 | C101.2 | Accurate and fully up-to-date | Section body incorrectly says “Per N.C.G.S. 143-138 (b18), no energy conservation code” instead of “Per G.S. 143-138 (b18), no energy conservation code” | |
| 360 | R101.2 | Accurate and fully up-to-date | Missing Exception #1 | |
| 361 | R406.5 | Accurate and fully up-to-date | Section body says "Section R406 shall be performed by the registered design professional or certified HERS rater " instead of "Section R406 shall be performed by the licensed design professional or certified HERS rater " | |
| 362 | 314.4 | Accurate and fully up-to-date | Missing Exceptions for items #1 and #2 | |
| 363 | 319.1.11 | Accurate and fully up-to-date | Contains outdated text “with Chapter 11 and Section 1007” which should be “with the North Carolina Building Code, Chapter 11 and Section 1009”. | |
| 364 | 404.2.3 | Accurate and fully up-to-date | Showing outdated section with body:
“Where facilities develop a lockdown plan...” | |
| 365 | 404.2.3.1 | Accurate and fully up-to-date | Showing outdated section and list. For example, the body is missing items 4.1, 4.2, 4.3 and 4.4. | |
| 366 | 404.2.3.2 | Accurate and fully up-to-date | The title is incorrectly “Training Frequency” instead of “Drills” and the text of the body is also incorrect:
“The training frequency shall be included ...” | |
| 367 | 901.1 | Accurate and fully up-to-date | Showing outdated. Incorrectly showing, “The provisions of this chapter shall specify...” | |
| 368 | 903.2.8 | Accurate and fully up-to-date | Exception #4.3 is outdated. It incorrectly shows “Smoke detectors” instead of “Smoke alarms”. | |
| 369 | 907.9 | Accurate and fully up-to-date | Displays Section 907.9 Where required in existing buildings and structures even though it is no longer part of the law | |
| 370 | 914.3.1 | Accurate and fully up-to-date | Incorrect reference to Section 914.3.3 | |
| 371 | 915.1.1 | Accurate and fully up-to-date | Missing Group “A-2” | |
| 372 | 915.1.2 | Accurate and fully up-to-date | Missing “Group A-2 occupancies” | |
| 373 | 915.1.3 | Accurate and fully up-to-date | Missing “Group A-2 occupancies” | |
| 374 | 915.4.1 | Accurate and fully up-to-date | Missing Exception #2 | |
| 375 | 1009.7.2 | Accurate and fully up-to-date | Missing Exception #2 | |
| 376 | 311.4.1.1 | Accurate and fully up-to-date | Missing “Group A-2” | |
| 377 | 311.4.1.2 | Accurate and fully up-to-date | Missing “Group A-2 occupancies” | |
| 378 | 311.4.1.3 | Accurate and fully up-to-date | Missing “Group A-2 occupancies” | |
| 379 | 311.4.4.1 | Accurate and fully up-to-date | Missing Exception #2 | |
| 380 | 306.5 | Accurate and fully up-to-date | Missing Exception | |
| 381 | 313.4.1.2 | Accurate and fully up-to-date | Missing “Group A-2 occupancies” | |
| 382 | 313.4.1.3 | Accurate and fully up-to-date | Missing “Group A-2 occupancies” | |
| 383 | 313.4.4.1 | Accurate and fully up-to-date | Missing Exception #2 | |
| 384 | 202 | Accurate and fully up-to-date | Incorrectly displaying the last sentence of the section:
“The water service pipe shall terminate 5 feet (1524mm) outside the foundation wall.” | |
| 385 | 403.1 | Accurate and fully up-to-date | Missing footnote q in Drinking Fountain column of Business Classification | |
| 386 | 403.1.1 | Accurate and fully up-to-date | Incorrect Exception #2 | |
| 387 | 410.2 | Accurate and fully up-to-date | Incorrectly displays section body as “Deleted.” | |
| 388 | 605.3 | Accurate and fully up-to-date | Section body is incorrect, for example, "water distribution shall terminate 5 feet (1524 mm) outside the building." instead of "water distribution shall terminate at or before the full-open valve located at the entrance to the structure. D" | |
| 389 | R202 | Accurate and fully up-to-date | Missing definition for: “Farm Building” | |
| 390 | R305.1 | Accurate and fully up-to-date | Missing Exception #4 | |
| 391 | R310.2.6 | Accurate and fully up-to-date | Omits Section R310.2.6. | |
| 392 | R328 | Accurate and fully up-to-date | Omits R328 and all subsections. | |
| 393 | R602.7 | Accurate and fully up-to-date | Missing figures in first column in Table R602.7(1) | |
| 394 | N1101.1 | Accurate and fully up-to-date | Missing the exception | |
| 395 | N1106.2 | Accurate and fully up-to-date | Section body is incorrect, for example, "requires that the provisions identified in Sections N1101.14 through N1104" instead of “requires that the provisions identified in Sections N1101 through N1104" | |
| 396 | N1106.5 | Accurate and fully up-to-date | Section body incorrectly says “performed by the registered design professional” instead of “performed by the licensed design professional” | |
| 397 | P2503.6 | Accurate and fully up-to-date | Title is incorrectly shows “or pan” in the section title. | |
| 398 | P3002.2.1 | Accurate and fully up-to-date | Incorrectly references “Section P2905.4.1” | |
| 399 | P3101.2.1 | Accurate and fully up-to-date | Body Section incorrectly says “as provided in Section P3107.” instead of “as provided in Section P3110.” | |
| 400 | P3109.3 | Accurate and fully up-to-date | Wrong reference to “Section P3104.5” and “Section P3113.3” | |
| 401 | P3201.6 | Accurate and fully up-to-date | Wrong reference to “Section P2706.1.2.1” in Exception #3 | |
| 402 | P3201.7 | Accurate and fully up-to-date | Showing Trap Size “1 1/2” for row “5.7 gpm and less” instead of “2” | |
| 403 | R4603.6 | Accurate and fully up-to-date | Missing Table R4603.6 | |
| 404 | R4603.6.1 | Accurate and fully up-to-date | Omits Section R4603.6.1. | |
| 405 | R4603.6.2 | Accurate and fully up-to-date | Omits Section R4603.6.2. | |
| 406 | AM105.1 | Accurate and fully up-to-date | Missing Table AM105.1 | |
| 407 | AM109.1.2 | Accurate and fully up-to-date | TABLE AM109.1 is outdated, it incorrectly shows “TABLE AM109.1 POST EMBEDMENT FOR FREE STANDING DECKS”. | |
| 408 | AM109.1.3 | Accurate and fully up-to-date | Incorrectly shows ”TABLE AM109.1” instead of “TABLE AM109.2” | |
| 409 | 912.3 | Accurate and fully up-to-date | Missing row for Wet Vent Pipe Size “3” | |
Do you know of other ICC errors? Drop a us a line here or tweet at @upcodes.