ADOPTS WITH AMENDMENTS:

International Building Code 2009 (IBC 2009)

Heads up: There are no amended sections in this chapter.
The provisions of this chapter shall control the classification of all buildings and structures, and spaces therein, as to use and occupancy.
Structures or portions of structures shall be classified with respect to occupancy in one or more of the groups listed below. A room or space that is intended to be occupied at different times for different purposes shall comply with all of the requirements that are applicable to each of the purposes for which the room or space will be occupied. Structures with multiple occupancies or uses shall comply with Section 508. Where a structure, or portion thereof, is proposed for a purpose which is not specifically provided for in this code, such structure, or portion thereof, shall be classified in the group which the occupancy most nearly resembles, according to the fire safety and relative hazard involved, and as approved by the commissioner.
  1. Assembly (see Section 303): Groups A-1, A-2, A-3, A-4 and A-5.
  2. Business (see Section 304): Group B.
  3. Educational (see Section 305): Group E.
  4. Factory and Industrial (see Section 306): Groups F-1 and F-2.
  5. High Hazard (see Section 307): Groups H-1, H-2, H-3, H-4 and H-5.
  6. Institutional (see Section 308): Groups I-1, I-2, I-3 and I-4.
  7. Mercantile (see Section 309): Group M.
  8. Residential (see Section 310): Groups R-1, R-2 and R-3.
  9. Storage (see Section 311): Groups S-1 and S-2.
  10. Utility and Miscellaneous (see Section 312): Group U.
For a listing of occupancy group classifications that corresponds with uses listed in the New York City Zoning Resolution, refer to department rules.
Assembly Group A occupancy includes, among others, the use of a building or structure or a portion thereof, excluding a dwelling unit, for the gathering of any number of persons for purposes such as civic, social or religious functions, recreation, food or drink consumption, awaiting transportation, or similar group activities; or when occupied by 75 persons or more for educational or instructional purposes.

Exceptions:
  1. A building or nonaccessory tenant space used for assembly purposes with an occupant load of fewer than 75 persons shall be classified as a Group B occupancy, except that the number of plumbing fixtures for such a building or space is permitted to be calculated in accordance with the requirements for assembly occupancies.
  2. A room or space used for assembly purposes with an occupant load of fewer than 75 persons and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy, except that the number of plumbing fixtures for such a room or space is permitted to be calculated in accordance with the requirements for assembly occupancies.
Assembly occupancies shall include the following:

A-1 Assembly uses, usually with fixed seating, intended for the production and viewing of the performing arts or motion pictures including, but not limited to:

Motion picture theaters

Symphony and concert halls

Television and radio studios admitting an audience

Theaters

A-2 Assembly uses intended for food and/or drink consumption including, but not limited to:

Banquet halls

Cabarets

Cafeterias, except as provided for in A-3

Dance halls Night clubs Restaurants Taverns and bars

A-3 Assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to:

Amusement arcades

Art galleries

Bowling alleys

Cafeterias for children up to and including the 12th grade

Classrooms and instructional rooms with 75 persons or more; such rooms with fewer than 75 persons shall be classified as Group B or E

Community halls

Courtrooms

Custodial care facilities with 75 or more persons, providing care to persons over the age of 2, where no more than four occupants are incapable of responding to an emergency situation without physical assistance from staff

Dance studio or instruction (not including food or drink consumption)

Exhibition halls

Funeral parlors

Gymnasiums (without spectator seating)

Religious houses of worship

Indoor swimming pools (without spectator seating)

Indoor tennis courts (without spectator seating)

Lecture halls

Museums

Waiting areas in transportation terminals

Pool and billiard parlors

School auditoriums

A-4 Assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to:

Arenas

Skating rinks

Swimming pools

Tennis courts

A-5 Assembly uses intended for participation in or viewing outdoor activities including, but not limited to:

Amusement park structures

Bleachers

Grandstands

Stadiums
A Certificate of Operation shall be required, as per Section 28-117.1, for the following places of assembly:
  1. Indoor places of assembly used or intended for use by 75 persons or more, including open spaces at 20 feet (6096 mm) or more above or below grade, such as roofs or roof terraces.
  2. Outdoor places of assembly used and intended for use by 200 persons or more.

304.1 Business Group B

ILLUSTRATION
Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional, service-type transactions, or for conducting public or civic services, including the incidental storage of records and accounts and the incidental storage of limited quantities of stocks of goods for office use or purposes. Business Group B occupancies shall include, but not be limited to, the following:

Airport traffic control towers

Ambulatory health care facilities

*Animal hospitals, kennels, pounds, veterinary clinics and pet shops

Banks

Barber and beauty shops

Civic administration offices

Clinic—outpatient, including group medical centers, and neighborhood family care centers

Custodial care facilities with fewer than 75 persons, providing care to persons over the age of 2, where no more than four occupants are incapable of responding to an emergency situation without physical assistance from staff

Dry cleaning and laundries; pick-up and delivery stations and self-service

Educational occupancies for students above the 12th grade, where not classified in Group A. Such occupancy may be used occasionally for educational purposes offered to children through the 12th grade

Electronic data processing

Laboratories; nonproduction testing and research, as per Section 424

Libraries when not classified in Group E

Motor vehicle showrooms

Offices

Post offices

Photocopying and printing shops using electronic printing equipment

Professional services (architects, attorneys, dentists, physicians, engineers, etc.)

Radio and television stations not admitting an audience

Telephone exchanges

Training and skill development not within a school or academic program


*Section 304.1 was amended by Local Law 78 of 2015. This law has an effective date of December 31, 2015.

The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.

CLINIC, OUTPATIENT. Buildings or portions thereof used to provide medical care on less than a 24-hour basis to individuals who are not rendered incapable of self-preservation by the services provided.
Educational Group E occupancy includes, among others, the use of a building or structure, or a portion thereof, by five or more persons at any one time for educational purposes offered to children through the 12th grade and where no more than two children are under the age of 2, including but not limited to the following:

Academies

Day care facilities where no more than two children are under the age of 2

Libraries accessory to Group E occupancies

Schools


Exceptions:
  1. Classrooms and instructional rooms with 75 or more persons shall be classified as Group A-3.
  2. Day care services provided within a dwelling unit as described in Section 310.
  3. Custodial care facilities with up to 30 children under the age of 2 are permitted to be classified as Group E when the rooms where such children are cared for are located on the level of exit discharge and each of these child care rooms has an exit door directly to the exterior.
Factory Industrial Group F occupancy includes, among others, the use of a building or structure, or a portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair, cleaning, laundering or processing operations that are not classified as a Group H hazardous occupancy. Factory Industrial Group F occupancy also includes certain mechanical and/or electrical equipment rooms in accordance with Section 306.3.
Factory industrial uses which are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, the following:

Aircraft (manufacturing, not to include repair)

Aircraft repairs

Automobiles and other motor vehicles, manufacturing

Automobiles and other motor vehicles, repairs

Bakeries

Beverages; over 16 percent alcohol content

Boats

Boat repairs

Brooms or brushes

Canvas or similar fabric

Carpets and rugs

Carpets and rugs, cleaning, using or storing solvents having a flash point between 100°F (38°C) and 138.2°F (59°C) (Tag closed cup)

Clothing

Disinfectants

Dry cleaning and dyeing using or storing solvents having a flash point between 100°F (38°C) and 138.2°F (59°C) (Tag closed cup)

Electric generation plants

Engines (including rebuilding)

Food processing, except meat slaughtering or preparation of fish for packing

Furniture

Hemp products

Jute products

Laboratories; for production (moderate-hazard), that may involve the synthesis or storage of materials that constitute a physical or health hazard in quantities below those found in Tables 307.1(1) and 307.1(2)

Leather products

Metals; finishing, plating, grinding, sharpening, polishing, cleaning, rustproofing, heat treatment or similar processes

Millwork (sash and door)

Motion pictures filming (without spectators)

Musical instruments

Optical goods

Paper mills or products

Photographic film

Plastic products

Printing or publishing

Recreational vehicles

Refuse incineration

Shoes

Soaps and detergents

Textiles

Tobacco

Trailers

Upholstering

Wood; distillation

Woodworking (cabinet) using no more than 2 quarts (1.9 L) per day or storing no more than 20 gallons (75.7 L) of paint, varnish, lacquer or shellac
Factory industrial uses that involve the cleaning, laundering, fabrication or manufacturing of noncombustible materials which during finishing, packing or processing do not involve a significant fire hazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following:

Appliances

Athletic equipment

Automobile laundries

Automobile wrecking establishments

Beverages; up to and including 16 percent alcohol content; bottling works

Beverages; nonalcoholic

Bicycles

Brick and masonry

Business machines

Cameras and photo equipment

Carpets and rugs, cleaning, using or storing solvents having a flash point above 138.2°F (59°C) (Tag closed cup)

Ceramic products

Construction and agricultural machinery

Dry cleaning and dyeing using or storing solvents having a flash point above 138.2°F (59°C) (Tag closed cup)

Electronics

Food processing; meat slaughtering or preparation of fish for packing

Foundries

Glass products

Gypsum

Ice

Laboratories; for production (low-hazard), that may involve the synthesis or storage of materials that constitute a physical or health hazard in quantities below those found in Tables 307.1(1) and 307.1(2)

Laundries

Machinery

Mechanical and/or electrical equipment rooms that are neither identified as incidental uses in Table 509 nor classified as the occupancy within which they are located per Section 508.1

Metal products (fabrication and assembly), not including flammable metals and alloys listed in Section 307

Plastic products; nonflammable

Printing; incidental to primary use, area not exceeding 2,000 square feet (185.8 m2)

Television filming (without spectators)
Locations of spaces classified in Factory Group F may be restricted within a building containing a Group R occupancy pursuant to Section 510.8.
High-Hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those allowed in control areas complying with Section 414, based on the maximum allowable quantity limits for control areas set forth in Tables 307.1(1) and 307.1(2). Hazardous occupancies are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in accordance with this section, the requirements of Section 415 and the New York City Fire Code.

Exceptions: The following shall not be classified as Group H, but shall be classified as the occupancy that they most nearly resemble.
  1. Buildings and structures occupied for the application of flammable finishes, provided that such buildings or areas conform to the requirements of Section 416 and the New York City Fire Code.
  2. Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conforming to the New York City Fire Code.
  3. Closed piping system containing flammable or combustible liquids or gases utilized for the operation of machinery or equipment.
  4. Cleaning establishments that utilize combustible liquid solvents having a flash point of 140°F (60°C) or higher in closed systems employing equipment listed by an approved testing agency, provided that this occupancy is separated from all other areas of the building by 1-hour fire barriers constructed in accordance with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 712, or both.
  5. Cleaning establishments that utilize a liquid solvent having a flash point at or above 200°F (93°C).
  6. Liquor stores and distributors without bulk storage.
  7. Refrigeration systems.
  8. The storage or utilization of materials for agricultural purposes on the premises.
  9. Stationary batteries utilized for facility emergency or standby power, uninterrupted power supply or telecommunication facilities, provided that the batteries are provided with safety venting caps and ventilation is provided in accordance with the New York City Mechanical Code.
  10. Corrosives shall not include personal or household products in their original packaging used in retail display or commonly used building materials.
  11. Buildings and structures occupied for aerosol storage shall be classified as Group S-1, provided that such buildings conform to the requirements of the New York City Fire Code.
  12. Display and storage of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in quantities not exceeding the maximum allowable quantity per control area in Group M or S occupancies complying with Section 414.2.5.
  13. The storage of black powder, smokeless propellant and small arms primers in Groups M and R-3 and special industrial explosive devices in Groups B, F, M and S, provided such storage conforms to the quantity limits and requirements prescribed in the New York City Fire Code.
  14. Laboratories for nonproduction testing, research, experimental, instructional or educational purposes, in compliance with Section 424.


TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa, j, m, n, q

MATERIAL CLASS GROUP
WHEN THE
MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDEDq
STORAGEb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas
SCF
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas
SCF
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Combustible
liquidc, i, r
II H-2 or H-3 Not
Applicable
120d, e Not
Applicable
Not
Applicable
120d Not
Applicable
Not
Applicable
30d
IIIA H-2 or H-3 330d, e 330d 80d
IIIB Not
Applicable
13,200e, f 13,200f 3,300f
Combustible
fiber
Loose H-3 (100) Not
Applicable
Not
Applicable
(100) Not
Applicable
Not
Applicable
(20) Not
Applicable
Baleds (1,000) (1,000) (200)
Cryogenics
flammable
Not
Applicable
H-2 Not
Applicable
45d Not
Applicable
Not
Applicable
45d Not
Applicable
Not
Applicable
10d
Cryogenics
oxidizing
Not
Applicable
H-3 Not
Applicable
45d Not
Applicable
Not
Applicable
45d Not
Applicable
Not
Applicable
10d
Explosives Division 1.1 H-1 1e, g (1)e, g Not
Applicable
0.25g (0.25)g Not
Applicable
0.25g (0.25)g
Division 1.2 H-1 1e, g (1)e, g 0.25g (0.25)g 0.25g (0.25)g
Division 1.3 H-1 or H-2 5e, g (5)e, g 1g (1)g 1g (1)g
Division 1.4 H-3 50e, g (50)e, g 50g (50)g Not
Applicable
Not
Applicable
Division 1.4G H-3 125d, e, l Not Applicable Not Applicable Not
Applicable
Not
Applicable
Not
Applicable
Division 1.5 H-1 1e, g (1)e, g 0.25g (0.25)g 0.25g 0.25g
Division 1.6 H-1 1d, e, g Not Applicable Not Applicable Not
Applicable
Not
Applicable
Not
Applicable
Flammable gas Gaseous H-2 Not
Applicable
Not
Applicable
1,000d, e Not
Applicable
Not
Applicable
1,000d, e Not
Applicable
Not
Applicable
Liquefied (150)d, e Not
Applicable
(150)d, e Not
Applicable
Flammable
liquidsc, k
IAo H-2
or
H-3
Not
Applicable
30d, e Not
Applicable
Not
Applicable
30d Not
Applicable
Not
Applicable
10d
IB and IC 120d, e 120d 30d
Combination
Flammable
liquid
(IAo, IB, IC)
Not
Applicable
H-2
or
H-3
Not
Applicable
120d, e, h Not
Applicable
Not
Applicable
120d, h Not
Applicable
Not
Applicable
30d, h
Flammable
solids5
Not
Applicable
H-3 Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Pigs, ingots,
billets, heavy
castings
1,000d, e 1,000d 1,000d
Light castings,
light metallic
products
125d, e 125d 25d
Scraps,
shavings,
powders, dusts
1d, e 1d 1d
All others 125d, e 125d 25d
Inert gas Gaseous Not
Applicable
Not
Applicable
Not
Applicable
Not
Limited
Not
Applicable
Not
Applicable
Not
Limited
Not
Applicable
Not
Applicable
Liquefied Not
Applicable
Not
Applicable
Not
Applicable
Not
Limited
Not
Applicable
Not
Applicable
Not
Limited
Not
Applicable
Not
Applicable
Cryogenic inert Not
Applicable
Not
Applicable
Not
Applicable
Not
Applicable
Not
Limited
Not
Applicable
Not
Applicable
Not
Limited
Not
Applicable
Not
Applicable
Organic peroxidep Unclassified
Detonable
H-1 1e, g (1)e, g Not
Applicable
0.25g (0.25)g Not
Applicable
0.25g (0.25)g
I H-2 5d, e (5)d, e 1d (1)d 1d (1)d
II H-3 50d, e (50)d, e 50d (50)d 10d (10)d
III H-3 125d, e (125)d, e 125d (125)d 25d (25)d
IV Not
Applicable
Not
Limited
Not
Limited
Not
Limited
No
Limited
Not
Limited
Not
Limited
V Not
Applicable
Not
Limited
Not
Limited
Not
Limited
Not
Limited
Not
Limited
Not
Limited

(continued)

TABLE 307.1(1)—continued MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa, j, m, n, q

MATERIAL CLASS GROUP
WHEN THE
MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDEDq
STORAGEb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas
SCF
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas
SCF
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Oxidizer 4 H-1 1g (1)e, g Not
Applicable
0.25g (0.25)g Not
Applicable
0.25g (0.25)g
3k H-2 10d, e (10)d, e 2d (2)d 2d (2)d
2 H-3 250d, e (250)d, e 250d (250)d 50d (50)d
1 H-3 4,000e,f (4,000)e,f 4,000f (4,000)f 1,000f (1,000)f
Oxidizing gas Gaseous H-3 Not
Applicable
Not
Applicable
1,500d, e Not
Applicable
Not
Applicable
1,500d, e
Liquefied (150)d, e Not
Applicable
(150)d, e Not
Applicable
Pyrophoric
materialp
detonable
Not
Applicable
H-1 1e, g (1)e, g 10e, g 0.25g (0.25)g 2e, g 0 0
Pyrophoric
material
nondetonable
Not
Applicable
H-2 4e, g (4)e, g 50e, g 1g (1)g 10e, g 0 0
Unstable
(reactive)p
detonable
4 H-1 1e, g (1)e, g 10e, g 0.25g (0.25)g 2e, g 0.25g (0.25)g
3 H-1 1e, g (1)e, g 10e, g 0.25g (0.25)g 2e, g 0.25g (0.25)g
Unstable
(reactive)
nondetonable
4 H-1 1e, g (1)e, g 10e, g 0.25g (0.25)g 2e, g 0.25g (0.25)g
3 H-1 or H-2 5d, e (5)d, e 50d, e 1d (1)d 10d, e 1d (1)d
2 H-3 50d, e (50)d, e 250d, e 50d (50)d 250d, e 10d (10)d
1 Not Applicable Not
Limited
Not Limited 750d, e Not
Limited
Not
Limited
Not
Limited
Not
Limited
Not
Limited
Water-reactive
detonablep
3 H-1 1e, g (1)e, g Not
Applicable
0.25g (0.25)g Not
Applicable
0.25g (0.25)g
2 H-1 1e, g (1)e, g 0.25g (0.25)g 0.25g (0.25)g
Water-reactive
nondetonable
3 H-2 5d, e (5)d, e Not
Applicable
5d (5)d Not
Applicable
1d (1)d
2 H-3 50d, e (50)d, e 50d (50)d 10d (10)d
1 Not Applicable Not
Limited
Not
Limited
Not
Limited
Not
Limited
Not
Limited
Not
Limited

For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
  1. For use of control areas, see Section 2703.8.3 of the New York City Fire Code.
  2. The aggregate quantity in storage, handling and use shall not exceed the quantity listed for storage.
  3. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
  4. Maximum allowable quantities, except for liquefied petroleum gas and flammable liquid motor fuel, shall be increased 100 percent in buildings protected throughout by a sprinkler system. Where Note e also applies, the increase for both notes shall be applied accumulatively.
  5. Maximum allowable quantities, except for liquefied petroleum gas and flammable liquid motor fuel, shall be increased 100 percent when stored in approved storage cabinets, gas cabinets, exhausted enclosures or listed safety cans. Listed safety cans shall be in accordance with Section 2705.1.10 of the New York City Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively.
  6. Quantities shall not be limited in a building protected throughout by a sprinkler system.
  7. Allowed only in buildings protected throughout by a sprinkler system.
  8. Containing not more than the maximum allowable quantity per control area of Class IA, Class IB or Class IC flammable liquids.
  9. Stationary fuel oil storage tanks shall comply with the requirements of the New York City Construction Codes, including the New York City Mechanical Code.
  10. Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
  11. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance and operation of equipment when the storage containers and the manner of storage are approved.
  12. Reserved.
  13. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 2703.1.2 of the New York City Fire Code.
  14. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with the requirements of Section 2703.11 of the New York City Fire Code, see Table 2703.11.1 of the New York City Fire Code.
  15. For purposes of this table, gasoline and other flammable liquid motor fuels are classified as a Class IA flammable liquid.
  16. Unclassified detonable organic peroxides (see Chapter 39 of the New York City Fire Code), detonable pyrophoric materials (see Chapter 41 of the New York City Fire Code), detonable unstable (reactive) materials (see Chapter 43 of the New York City Fire Code) and detonable water-reactive materials (see Chapter 44 of the New York City Fire Code) shall be treated as explosives for purposes of storage, handling and use (see Chapter 33 of the New York City Fire Code).
  17. The maximum allowable quantities shall be limited by Section 2706 of the New York City Fire Code for non-production laboratories classified as Occupancy Group B.
  18. For storage of flammable and combustible liquids in Group M occupancy, see Chapter 34 of the New York City Fire Code.
  19. Densely-packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.

TABLE 307.1(2) MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIAL POSING A HEALTH HAZARDa, b, c, i, j

MATERIAL STORAGEd USE-CLOSED SYSTEMSd USE-OPEN SYSTEMSd
Solid
pounds
Liquid
gallons
(pounds)e, f
Gas SCFe (pounds) Solid
poundse
Liquid
gallons
(pounds)e
Gas SCFe
(pounds)
Solid
pounds
e
Liquid
gallons
(pounds)
e
Corrosive 5,000 500 Gaseous 810f
Liquefied (150)h
5,000 500 Gaseous 810f
Liquefied (150)h
1,000 100
Highly
toxic
10 (10)h Gaseous 20g
Liquefied (4)g, h
10 (10)h Gaseous 20g
Liquefied (4)g, h
3 (3) h
Toxic 500 (500)h Gaseous 810f
Liquefied (150)f, h
500 (500) h Gaseous 810f
Liquefied (150)f, h
125 (125) h

For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
  1. For use of control areas, see Section 414.2.
  2. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are pack-aged in individual containers not exceeding 1.3 gallons.
  3. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with the New York City Fire Code.
  4. The aggregate quantity in storage, handling and use shall not exceed the quantity listed for storage.
  5. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note f also applies, the increase for both notes shall be applied accumulatively.
  6. Maximum allowable quantities may be increased 100 percent when stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the New York City Fire Code. Where Note e also applies, the increase for both notes shall be applied accumulatively.
  7. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures as specified in the New York City Fire Code.
  8. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
  9. For gallons of liquids, divide the amount in pounds by 10 in accordance with the New York City Fire Code.
  10. The maximum allowable quantities shall be limited by Section 424 for chemical laboratories classified as Occupancy Group B and operating as nonproduction facilities for testing, research, experimental, instructional or education purposes.
The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.

AEROSOL. A product that is dispensed from an aerosol container by a propellant, classified as follows.

Level 1. Aerosol products with a total chemical heat of combustion that is greater than 0 and less than or equal to 8,600 British thermal units per pound (Btu/lb) (20 kJ/g).

Level 2. Aerosol products with a total chemical heat of combustion that is greater than 8,600 Btu/lb (20 kJ/g), but less than or equal to 13,000 Btu/lb (30 kJ/g).

Level 3. Aerosol products with a total chemical heat combustion that is greater than 13,000 Btu/lb (30 kJ/g).

BALED COTTON. A natural seed fiber wrapped in and secured with industry accepted materials, typically consisting of burlap, woven polypropylene, polyethylene or cotton or sheet polyethylene, secured with wire or bands. The term baled cotton includes lint removed from the cottonseed (linters) and residual materials from the ginning process (motes).

BALED COTTON, DENSELY PACKED. Baled cotton with a packing density of at least 22 pounds per cubic foot (360 kg/m3). A bale of densely-packed baled cotton typically measures 55 inches (1397 mm) in length, 21 inches (533.4 mm) in width, and 27.6 to 35.4 inches (701 to 899 mm) in height.

BARRICADE. A structure or other artificial or natural barrier constructed in connection with the storage, handling and use of explosives that is designed to withstand the rapid release of energy in an explosion and provides a shield from the impact of such explosion. A straight line from the top of any sidewall of a building containing explosives to the eaveline of any magazine or other building or to a point 12 feet (3658 mm) above the center of a railway or highway shall pass through such barrier.

Artificial barricade. An artificial mound or revetment, including a barrier constructed of sandbags, with a minimum thickness of 3 feet (914 mm).

Natural barricade. Terrain or other natural features of the ground.

BOILING POINT. The temperature at which the vapor pressure of a liquid equals the atmospheric pressure of 14.7 pounds per square inch (psi) (101 kPa) gage or 760 mm of mercury. Where an accurate boiling point is unavailable for the material in question, or for mixtures which do not have a constant boiling point, for the purposes of this classification, the 20-percent evaporated point of a distillation performed in accordance with ASTM D 86 shall be used as the boiling point of the liquid.

CLOSED SYSTEM. The use of any compressed gas and the use of a solid or liquid hazardous material in equipment or a vessel or system that remains closed during normal operations, such that vapors emitted during the operation of such equipment, vessel or system are not liberated outside of the equipment, vessel or system and the gas or hazardous material is not exposed to the atmosphere during such operation. Examples of closed systems include hazardous materials conveyed through a piping system into closed equipment or a closed vessel or system.

COMBUSTIBLE DUST. Finely divided solid material that is 420 microns or less in diameter, will pass through a U.S. standard No. 40 sieve and, when dispersed in air in insufficient concentrations, can be ignited by a flame, spark or other source of ignition.

COMBUSTIBLE FIBERS. Readily ignitable and free-burning materials in fibrous or shredded form, such as cocoa fiber, cotton, excelsior, hay, hemp, henequen, istle, jute, kapok, oakum, sisal, Spanish moss, straw, tow, wastepaper or other natural or synthetic fibers that possess similar qualities, but excluding densely packed baled cotton.

Exception: Moss used for medicinal purposes.

COMBUSTIBLE LIQUID. For the purposes of transportation, a combustible liquid as defined in the regulations of the United States Department of Transportation, as set forth in 49 CFR 173.120. For all other purposes, a liquid, other than a compressed gas or cryogenic fluid, having a closed cup flash point at or above 100°F (38°C) classified as follows:

Class II. Liquids having a closed cup flash point at or above 100°F (38°C) and below 140°F (60°C).

Class IIIA. Liquids having a closed cup flash point at or above 140°F (60°C) and below 200°F (93°C).

Class IIIB. Liquids having a closed cup flash point at or above 200°F (93°C).

COMPRESSED GAS. A material, or mixture of materials which:
  1. Is a gas at 68°F (20°C) or less at 14.7 psia (101 kPa) of pressure; and
  2. Has a boiling point of 68°F (20°C) or less at 14.7 psia (101 kPa) that is either liquefied, nonliquefied or in solution at that temperature and pressure, except those gases which have no other health- or physical-hazard properties are not considered to be compressed until the pressure in the packaging exceeds 41 psia (28 kPa) at 68°F (20°C).
The states of compressed gases are categorized as follows:

Nonliquefied compressed gases. Gases, other than those in solution, which are in a packaging under the charged pressure and are entirely gaseous at a temperature of 68°F (20°C).

Liquefied compressed gases. Gases that, in a packaging under the charged pressure, are partially liquid at a temperature of 68°F (20°C).

Compressed gases in solution. Nonliquefied gases that are dissolved in a solvent.

Compressed gas mixtures. A mixture of two or more compressed gases contained in a single packaging, the hazard properties of which are represented by the properties of the mixture as a whole.

CONTROL AREA. Spaces within a building where quantities of hazardous materials not exceeding the maximum allowable quantities per control area are stored, handled, or used, including any dispensing. See also definition of "Outdoor control area" in the New York City Fire Code.

CORROSIVE MATERIAL. A material that causes full thickness destruction of human skin at the site of contact within a specified period of time when tested by methods set forth in DOTn regulations 49 CFR 173.136 and 173.137, or a liquid that has a severe corrosion rate on steel or aluminum based on the criteria set forth in DOTn regulations 49 CFR 173.173(c)(2).

CRYOGENIC FLUID. A liquid having a boiling point lower than -130°F (-89.9°C) at 14.7 pounds per square inch absolute (psia) (an absolute pressure of 101.3 kPa).

DAY BOX. A portable magazine designed to hold explosive materials constructed in accordance with the requirements for a Type 3 magazine as defined and classified in Chapter 33 of the New York City Fire Code.

DEFLAGRATION. An exothermic reaction, such as the extremely rapid oxidation of a flammable dust or vapor in air, in which the reaction progresses through the unburned material at a rate less than the velocity of sound. A deflagration can have an explosive effect.

DETONATION. An exothermic reaction with explosive effect that utilizes shock compression as the principal heating mechanism and generates a shock wave in the material that establishes and maintains a reaction that progresses through the material at a rate greater than the velocity of sound.

DISPENSING. The pouring or transferring by other means of any material from a container, tank or similar vessel, which would release dusts, fumes, mists, vapors, or gases to the atmosphere, unless such release is prevented by a device, equipment or system designed for that purpose.

EXPLOSION. An effect produced by the sudden violent expansion of gases, whether or not accompanied by a shock wave or disruption, of enclosing materials, including the effects of the following sources of explosion:
  1. Chemical changes such as rapid oxidation, deflagration or detonation, decomposition of molecules and runaway polymerization (usually detonations).
  2. Physical changes such as pressure tank ruptures.
  3. Atomic changes (nuclear fission or fusion).
EXPLOSIVE. Any chemical compound, mixture or device, the primary or common purpose of which is to function by explosion. The term includes, but is not limited to, dynamite, black powder, pellet powder, initiating explosives, detonators, safety fuses, squibs, detonating cord, igniter cord, and igniters.

The term "explosive" includes any material determined to be within the scope of Chapter 40 of Title 18 of the United States Code and any material classified as an explosive by the hazardous materials regulations of the United States Department of Transportation, as set forth in 49 CFR 173.52, except fireworks. Explosives are classified in accordance with the following United States Department of Transportation classification and other terms in common usage.

United States Department of Transportation Class 1 explosives.

Division 1.1. Explosives that have a mass explosion hazard.

Division 1.2. Explosives that have a projection hazard but not a mass explosion hazard.

Division 1.3. Explosives that have a fire hazard and either a minor blast hazard or a minor projection hazard or both, but not a mass explosion hazard.

Division 1.4. Explosives that pose a minor explosion hazard. The explosive effects are largely confined to the package and no projection of fragments of appreciable size or range is to be expected. Such explosives are not subject to mass explosion when exposed to fire.

Division 1.5. Explosives that present a mass explosion hazard, but which are so insensitive that there is very little probability of initiation or of transition from burning to detonation under normal conditions of transport.

Division 1.6. Explosives consisting of extremely insensitive articles that do not present a mass explosion hazard, and present a negligible probability of accidental initiation or propagation.

High explosive. Explosives, including dynamite, that, when detonated, are characterized by a high rate of reaction, high pressure development, and the presence of a detonation wave, and that can be caused to detonate by means of a No. 8 test blasting cap, when unconfined.

Low explosive. Explosives that will burn or deflagrate when ignited, and which are characterized by a rate of reaction that is less than the speed of sound, and low pressure development. Examples of low explosives include black powder, igniter cords, igniters, safety fuses, small arms ammunition and primers, and propellants, 1.3C.

Mass-detonating explosives. Division 1.1, 1.2 and 1.5 explosives that, whether individually or in combination, or loaded into ammunition or containers, explode virtually instantaneously when a small portion is subjected to fire, concussion, impact, the impulse of an initiating agent, or the effect of a considerable discharge of energy from without, with severe explosive effect, including the potential for structural damage to adjacent objects, and explosive propagation to other explosives stored in proximity, such that two or more quantities in proximity must be considered as one for quantity-distance purposes.

FIREWORKS. Any article or device that does not present a mass explosion hazard, that is manufactured or used to produce a visible or audible effect for entertainment or other display purposes by combustion, deflagration or detonation that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein.

Fireworks, 1.3G. Large fireworks devices, classified as UN0335 by the United States Department of Transportation regulations, intended for use in fireworks displays and designed to produce audible or visible effects by combustion, deflagration or detonation including firecrackers containing more than 130 milligrams (2 grains) of explosive composition, aerial shells containing more than 40 grams of pyrotechnic material, and other display pieces which exceed the limits for classification as 1.4G fireworks.

Fireworks, 1.4G. Small fireworks devices, classified as UN 0336 by United States Department of Transportation regulations, containing restricted amounts of pyrotechnic materials designed primarily to produce visible or audible effects by combustion.

FLAMMABLE GAS. A material which has a boiling point and becomes a gas at 68°F (20°C) or less at 14.7 pounds per square inch absolute (psia) (101 kPa) of pressure which:
  1. Is ignitable at 14.7 psia (101 kPa) when in a mixture of 13 percent or less by volume with air, in accordance with testing procedures set forth in ASTM E 681; or
  2. Has a flammable range at 14.7 psia (101 kPa) with air of at least 12 percent, regardless of the lower explosive limit, in accordance with testing procedures set forth in ASTM E 681.
The limits specified shall be determined at 14.7 psia (101 kPa) of pressure and a temperature of 68°F (20°C) in accordance with ASTM E 681.

FLAMMABLE LIQUEFIED GAS. A liquefied compressed gas which, under a charged pressure, is partially liquid at a temperature of 68°F (20°C) and which is flammable.

FLAMMABLE LIQUID. For the purposes of transportation, a flammable liquid as defined in the regulations of the United States Department of Transportation, as set forth in 49 CFR 173.120. For all other purposes, a liquid, other than a compressed gas or cryogenic fluid, having a closed cup flash point below 100°F (38°C) classified as follows:

Class IA. Liquids having a flash point below 73°F (23°C) and a boiling point below 100°F (38°C).

Class IB. Liquids having a flash point below 73°F (23°C) and a boiling point at or above 100°F (38°C).

Class IC. Liquids having a flash point at or above 73°F (23°C) and below 100°F (38°C).

FLAMMABLE MATERIAL. A material capable of being readily ignited from common sources of heat or at a temperature of 600°F (316°C) or less.

FLAMMABLE SOLID. A solid, other than a blasting agent or other explosive, whether in elemental or alloy form, that is capable of causing fire through friction, absorption or moisture, spontaneous chemical change, or heat retained from manufacturing or processing, or which has an ignition temperature below 212°F (100°C) or which burns so vigorously and persistently when ignited as to create a serious hazard. A chemical shall be considered a flammable solid if upon testing using the method prescribed in CPSC regulations, as set forth in 16 CFR 1500.44, if it ignites and burns with a self-sustained flame at a rate greater than 0.1 inch (2.5 mm) per second along its major axis.

FLASH POINT. The minimum temperature in degrees Fahrenheit at which a liquid will give off sufficient vapors to form an ignitable mixture with air near the surface or in the container, but will not sustain combustion. The flash point of a liquid shall be determined by appropriate test procedure and apparatus as specified in ASTM D 56, ASTM D 93 or ASTM D 3278.

HANDLING. The movement of a material in its container, the removal of the material from its container, or any other action or process that may affect the material, other than its storage or use.

HAZARDOUS MATERIALS. Those chemicals or substances that are physical hazards or health hazards as defined and classified in this section and the New York City Fire Code, whether the materials are in usable or waste condition.

HEALTH HAZARD. A classification of a chemical for which there is statistically significant evidence that acute or chronic health effects are capable of occurring in exposed persons. The term "health hazard" includes chemicals that are toxic or highly toxic, and corrosive.

HIGHLY TOXIC MATERIAL. A chemical that is lethal at the following doses or concentrations:
  1. A chemical that has a median lethal dose (LD50) of 50 milligrams or less per kilogram of body weight when administered orally to albino rats weighing between 200 and 300 grams each; or
  2. A chemical that has a median lethal dose (LD50) of 200 milligrams or less per kilogram of body weight when administered by continuous contact for 24 hours (or less if death occurs within 24 hours) with the bare skin of albino rabbits weighing between 2 and 3 kilograms each; or
  3. A chemical that has a median lethal concentration (LC50) in air of 200 parts per million by volume or less of gas or vapor, or 2 milligrams per liter or less of mist, fume or dust, when administered by continuous inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats weighing between 200 and 300 grams each.
INCOMPATIBLE MATERIALS. Materials that, if mixed or combined, could explode, generate heat, gases or other by products, or react in such a way hazardous to life or property.

INERT GAS. A gas that is capable of reacting with other materials only under abnormal conditions such as high temperatures, pressures and similar extrinsic physical forces. Within the context of the code, inert gases do not exhibit either physical or health properties as defined (other than acting as a simple asphyxiant) or hazard properties other than those of a compressed gas. Some of the more common inert gases include argon, helium, krypton, neon, nitrogen and xenon.

OPEN SYSTEM. The use of a solid or liquid hazardous material in equipment or a vessel or system that remains open during normal operation such that vapors are emitted during the operation of such equipment, vessel or system and the material is exposed to the atmosphere during such operation. Examples of open systems for solids and liquids include dispensing from or into open beakers or containers, dip tank and plating tank operations.

ORGANIC PEROXIDE. An organic compound having a double oxygen or peroxy (-O-O-) in its chemical structure. Organic peroxides can present an explosion hazard (detonation or deflagration), can be shock sensitive, or can be susceptible to decomposition into various unstable compounds over an extended period of time and are classified as follows based upon their hazardous properties:

Class I. Organic peroxides that are capable of deflagration but not detonation.

Class II. Organic peroxides that burn very rapidly and that pose a moderate reactivity hazard.

Class III. Organic peroxides that burn rapidly and that pose a moderate reactivity hazard.

Class IV. Organic peroxides that burn in the same manner as ordinary combustibles and that pose a minimal reactivity hazard.

Class V. Organic peroxides that burn with less intensity than ordinary combustibles or do not sustain combustion and that pose no reactivity hazard.

Unclassified detonable. Organic peroxides that are capable of detonation and pose an extremely high explosion hazard through rapid explosive decomposition.

OXIDIZER. A material that readily yields oxygen or other oxidizing gas or that readily reacts to promote or initiate combustion of combustible materials, and if heated or contaminated can result in vigorous self-sustained decomposition, classified as follows:

Class 1. An oxidizer that causes a readily measurable increase in the burning rate of combustible materials with which it comes in contact, but less than a moderate increase.

Class 2. An oxidizer that causes a moderate increase in the burning rate of combustible materials with which it comes in contact.

Class 3. An oxidizer that causes a severe increase in the burning rate of combustible materials with which it comes in contact.

Class 4. An oxidizer that can undergo an explosive reaction due to contamination or exposure to thermal or physical shock and causes a severe increase in the burning rate of combustible materials with which it comes into contact.

OXIDIZING GAS. A gas that can support and accelerate combustion of other materials more than air does.

PHYSICAL HAZARD. A chemical for which there is evidence that it is a combustible liquid, compressed gas, cryogenic, explosive, flammable gas, flammable liquid, flammable solid, organic peroxide, oxidizer, pyrophoric or unstable (reactive) or water-reactive material.

PYROPHORIC MATERIAL. A material with an autoignition temperature in air, at or below a temperature of 130°F (54°C).

PYROTECHNIC MATERIAL. A chemical mixture consisting predominantly of solids that, upon ignition, are capable of producing a controlled, self-sustaining, and self-contained exothermic reaction, that functions without external oxygen, resulting in a visible or audible effect by combustion, deflagration, or detonation.

STANDARD CUBIC FEET (SCF). Cubic feet of gas at normal temperature and pressure (NTP).

TOXIC MATERIAL. A chemical that is lethal at the following doses or concentrations:
  1. A chemical that has a median lethal dose (LD50) of more than 50 milligrams per kilogram, but not more than 500 milligrams per kilogram of body weight when administered orally to albino rats weighing between 200 and 300 grams each; or
  2. A chemical that has a median lethal dose (LD50) of more than 200 milligrams per kilogram but not more than 1,000 milligrams per kilogram of body weight when administered by continuous contact for 24 hours (or less if death occurs within 24 hours) with the bare skin of albino rabbits weighing between 2 and 3 kilograms each; or
  3. A chemical that has a median lethal concentration (LC50) in air of more than 200 parts per million but not more than 2,000 parts per million by volume of gas or vapor, or more than 2 milligrams per liter but not more than 20 milligrams per liter of mist, fume or dust, when administered by continuous inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats weighing between 200 and 300 grams each.
Exception: For purposes of this code, chlorine shall be classified as a highly toxic material.

UNSTABLE (REACTIVE) MATERIAL. A material, other than an explosive, which in the pure state or as commercially produced, will vigorously polymerize, decompose, condense or become self-reactive and undergo other violent chemical changes, including explosion, when exposed to heat, friction or shock, or in the absence of an inhibitor, or in the presence of contaminants, or in contact with incompatible materials. Unstable (reactive) materials shall be classified as follows:

Class 1. Materials that in themselves are normally stable but which can become unstable at elevated temperatures and pressure.

Class 2. Materials that in themselves are normally unstable and readily undergo violent chemical change but do not detonate. This class includes materials that can undergo chemical change with rapid release of energy at normal temperatures and pressures, and that can undergo violent chemical change at elevated temperatures and pressures.

Class 3. Materials that in themselves are capable of detonation or of explosive decomposition or explosive reaction but which require a strong initiating source or which must be heated under confinement before initiation. This class includes materials that are sensitive to thermal or mechanical shock at elevated temperatures and pressures.

Class 4. Materials that in themselves are readily capable of detonation or explosive decomposition or explosive reaction at normal temperatures and pressures. This class includes materials that are sensitive to mechanical or localized thermal shock at normal temperatures and pressures.

WATER-REACTIVE MATERIAL. A material that explodes; violently reacts; produces flammable, toxic or other hazardous gases; or generates enough heat to cause auto-ignition or ignition of combustible materials upon exposure to water or moisture. Water-reactive materials are classified as follows:

Class 1. Materials that may react with water with some release of energy, but not violently.

Class 2. Materials that react violently with water or cause water to boil upon contact; produce flammable, toxic or other hazardous gases upon contact with water; or upon contact with water generate sufficient heat to cause auto-ignition of adjoining combustible materials.

Class 3. Materials that react explosively with water without requiring heat or confinement.
Buildings and structures containing materials that present a detonation hazard shall be classified as Group H-1. Such materials shall include, but not be limited to, the following:

Detonable pyrophoric materials

Explosives:

Division 1.1

Division 1.2

Division 1.3

Exception: Materials that are used and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 occupancies.

Division 1.4

Exception: Articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco and Firearms regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles shall be allowed in H-3 occupancies.

Division 1.5

Division 1.6

Organic peroxides, unclassified detonable

Oxidizers, Class 4

Unstable (reactive) materials, Class 3 detonable and Class 4

Pyrophoric materials, detonable

Water-reactive materials, Class 2 and 3, detonable

No part of this section shall be construed to authorize the manufacture, storage, sale or use of explosives, including fireworks, if otherwise prohibited by the New York City Fire Code and unless in compliance with the requirements of the New York City Fire Code.
Buildings and structures containing materials that present a deflagration hazard or a hazard from accelerated burning shall be classified as Group H-2. Such materials shall include, but not be limited to, the following:

Class I, II or IIIA flammable or combustible liquids which are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 psi (103.4 kPa) gage.

Combustible dusts

Cryogenic fluids, flammable

Flammable gases

Organic peroxides, Class I

Oxidizers, Class 3, that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 psi (103.3 kPa) gage.

Pyrophoric liquids, solids and gases, nondetonable

Unstable (reactive) materials, Class 3, nondetonable

Water-reactive materials, Class 3, nondetonable

No part of this section shall be construed to authorize an LPG-distribution facility if otherwise prohibited by the New York City Fire Code.
Buildings and structures containing materials that readily support combustion or present a physical hazard shall be classified as Group H-3. Such materials shall include, but not be limited to, the following:

Class I, II or IIIA flammable or combustible liquids which are used or stored in normally closed containers or systems pressurized at less than 15 psi (103 kPa) gage.

Combustible fibers

Cryogenic fluids, oxidizing

Flammable solids

Organic peroxides, Classes II and III

Oxidizers, Classes 1 and 2

Oxidizing gases

Unstable (reactive) materials, Class 2

Water-reactive materials, Class 2, nondetonable
Buildings and structures containing materials that are health hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the following:

Corrosives

Highly toxic materials

Toxic materials
Semiconductor fabrication facilities and comparable research and development areas in which hazardous production materials (HPM) are used and the aggregate quantity of materials is in excess of those listed in Tables 307.1(1) and 307.1(2). Such facilities and areas shall be designed and constructed in accordance with Section 415.8.
Buildings and structures containing a material or materials representing hazards that are classified in one or more of Groups H-1, H-2, H-3 and H-4 shall conform to the code requirements for each of the occupancies so classified.
Institutional Group I occupancy includes, among others, the use of a building or structure, or a portion thereof, in which people are cared for or live in a supervised environment, having physical limitations because of health or age are harbored for medical treatment or other care or treatment, or in which people are detained for penal or correctional purposes or in which the liberty of the occupants is restricted. Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-4.
For definitions of terms related to Group I occupancy classification, see Section 310.2.
This occupancy shall include buildings, structures or parts thereof housing persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services. The occupants are capable of self-preservation and capable of responding to an emergency situation without physical assistance from staff. Such occupancy shall be subject to the New York State Multiple Dwelling Law. This group shall include, but not be limited to, the following:

Adult homes, where occupants are capable of self-preservation (see Section 308.2.1)

Alcohol and drug abuse rehabilitation centers

Assisted living facilities

Community residences or intermediate-care facilities (see Section 308.2.2)

Congregate care facilities

Convalescent facilities

Enriched housing, where occupants are capable of self-preservation (see Section 308.2.1)

Halfway houses

Overnight facilities for children where all supervised occupants are under the age of 18, with no more than two children under the age of 2

Residential care facilities

Social rehabilitation facilities
Adult homes and enriched housing facilities operated pursuant to and meeting the additional construction requirements of Section 460 of the New York State Social Services Law and regulations of the New York State Department of Health offering care on a 24-hour basis to persons capable of self-preservation, in the same building, shall be classified as Group I-1.

Exception: Such a facility offering supervised care on a 24-hour basis for no more than 16 occupants capable of self-preservation, in the same building, may be classified in Group R in accordance with Section 310.
Community residences or intermediate-care facilities, operated pursuant to and meeting the additional construction requirements of the New York State Mental Hygiene Law and applicable regulations of the New York State Office of Mental Health and Office for People with Developmental Disabilities shall be classified as Group I-1.

Exceptions: Such facilities limited to 14 residents capable of self-preservation and three staff members per dwelling unit shall be classified as:
  1. Group R-1, where such facility does not occupy more than two dwelling units in a residential building classified as R-1 of Type I or II construction, or one dwelling unit in any other type of construction, and occupied on a transient basis; or
  2. Group R-2 where such facility does not occupy more than two dwelling units in a residential building classified R-2 of Type I or II construction, or one dwelling unit in any other type of construction, and occupied on a long-term basis; or
  3. Group R-3 where the number of dwelling units in the building does not exceed two.
This occupancy shall include buildings and structures used for medical, surgical, psychiatric, nursing or personal care on a 24-hour basis or overnight of more than two children under the age of 2, or more than three persons who are not capable of self-preservation and not capable of responding to an emergency situation without physical assistance from staff. This group shall include, but not be limited to, the following:

Adult homes, where occupants are not capable of self-preservation, operated pursuant to and meeting the additional construction requirements of Section 460 of the New York State Social Services Law and regulations of the New York State Department of Health

Child care facilities

Community residences or intermediate-care facilities, where occupants are not capable of self-preservation, operated pursuant to and meeting the additional construction requirements of the New York State Mental Hygiene Law and applicable regulations of the New York State Office of Mental Health and Office for People with Developmental Disabilities

Enriched Housing, where occupants are not capable of self-preservation, operated pursuant to and meeting the additional construction requirements of Section 460 of the New York State Social Services Law and regulations of the New York State Department of Health

Hospitals

Nursing homes

Mental hospitals where patients are not under restraint

Detoxification facilities

Exception: Such a facility offering care on a 24-hour basis for three or fewer persons who are not capable of self-preservation may occupy not more than one dwelling unit in a Group R occupancy.
The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.

CHILD CARE FACILITIES. Facilities that provide care on a 24-hour basis to more than five children, under the age of 2.

DETOXIFICATION FACILITIES. Facilities that serve patients who are provided treatment for substance abuse on a 24-hour basis and who are incapable of self-preservation or who are harmful to themselves or others.

HOSPITALS AND MENTAL HOSPITALS. Buildings or portions thereof used on a 24-hour basis for the medical, psychiatric, obstetrical or surgical treatment of inpatients who are incapable of self-preservation.

NURSING HOMES. Nursing homes are long-term care facilities on a 24-hour basis, including both intermediate care facilities and skilled nursing facilities, serving more than five persons and any of the persons are incapable of self-preservation.
This occupancy shall include buildings and structures that are inhabited by more than five persons who are under restraint or security. An I-3 facility is occupied by persons who are generally incapable of self-preservation due to security measures not under the occupants' control. This group shall include, but not be limited to, the following:

Correctional centers

Detention centers

Jails

Mental hospitals where patients are under restraint

Prerelease centers

Prisons

Reformatories

Buildings of Group I-3 shall be classified as one of the occupancy conditions indicated in Section 408.1.
This group shall include custodial care facilities providing care to more than two children under the age of 2, or to more than four persons over the age of 2 who are not capable of responding to an emergency situation without physical assistance from the staff. Such occupancy shall include, but not be limited to, adult custodial care facilities and day nurseries.

Exceptions:
  1. Custodial care facility as described in Section 303.
  2. Custodial care facility as described in Section 304.
  3. Custodial care facility as described in Exception 3 of Section 305.1.
  4. Such facility providing care within a dwelling unit as described in Section 310.
  5. Such facility providing care to children under the age of 2 in religious houses of worship during religious functions.
Mercantile Group M occupancy includes, among others, the use of a building or structure or a portion thereof, for the display and sale of merchandise, and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, the following:

Department stores

Drug stores

Markets

Motor fuel-dispensing facilities

Retail or wholesale stores

Sales rooms
The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored or displayed in a single control area of a Group M occupancy shall not exceed the quantities in Table 414.2.5(1).
Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for dwelling or sleeping purposes when not classified as Institutional Group I. Buildings containing three or more dwelling units shall be subject to the New York State Multiple Dwelling Law. Residential occupancies shall be classified as Group R-1, R-2, or R-3.
This occupancy shall include:
  1. Residential buildings or spaces occupied, as a rule, transiently, for a period less than one month, as the more or less temporary abode of individuals or families who are lodged with or without meals, including, but not limited to, the following:

    Class B multiple dwellings as defined in Section 27-2004 of the New York City Housing Maintenance Code and Section 4 of the New York State Multiple Dwelling Law, where not classified in Group I-1.

    Club houses

    Hotels (transient)

    Motels (transient)

    Rooming houses (boarding houses—transient)

    Settlement houses

    Vacation timeshares
  2. College or school student dormitories, except for student apartments classified as an R-2 occupancy.
  3. Congregate living units owned and operated by a government agency or not-for-profit organization, where the number of occupants in the dwelling unit exceeds the limitations of a family as defined, including, but not limited to, the following:

    Adult homes or enriched housing with 16 or fewer occupants requiring supervised care within the same building on a 24-hour basis

    Fraternity and sorority houses

    Homeless shelters
This occupancy shall include buildings or portions thereof containing sleeping units or more than two dwelling units that are occupied for permanent resident purposes as defined in subparagraph (a) of paragraph eight of subdivision a of Section 27-2004 of the New York City Housing Maintenance Code. Such occupancy shall be subject to the New York State Multiple Dwelling Law. This group shall include, but not be limited to, the following:

Adult homes or enriched housing with 16 or fewer occupants requiring supervised care on a 24-hour basis in the same building, provided that the number of occupants per dwelling unit does not exceed the definition of a family

Apartment houses

Apartment hotels (nontransient)

Class A multiple dwellings as defined in Section 27-2004 of the New York City Housing Maintenance Code and Section 4 of the New York State Multiple Dwelling Law, where not classified in Group I-1:
  1. Dwelling units where the resident of the unit provides custodial care to no more than four persons on less than a 24-hour basis and not overnight, where not classified in Group I-1.
  2. Dwelling units where the resident of the unit provides child custodial care as a family day care home registered with the New York City Department of Health and Mental Hygiene in accordance with the New York State Social Services Law with no more than six children between the ages of 2 and 13, or with no more than five children if any are under the age of 2, receiving supervised care on less than a 24-hour basis and not overnight, where not classified in Group I-1.
Convents and monasteries with more than 20 occupants in the building

Student apartments
This occupancy shall include buildings or portions thereof containing no more than 2 dwelling units, occupied, as a rule, for shelter and sleeping accommodation on a long-term basis for a month or more at a time, and are not classified in Group R-1, R-2 or I. This group shall include, but not be limited to, the following:

Convents and monasteries with fewer than 20 occupants in the building

Group homes

One- and two-family dwellings, including the following:
  1. Dwelling units where the resident of the unit provides custodial care to no more than four persons on less than a 24-hour basis and not overnight.
  2. Dwelling units where the resident of the unit provides child custodial care as a family day care home registered with the New York City Department of Health and Mental Hygiene in accordance with the New York State Social Services Law with no more than six children between the ages of 2 and 13, or with no more than five children if any are under the age of 2, receiving supervised care on less than a 24-hour basis and not overnight.
The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.

APARTMENT. A dwelling unit providing permanent provisions for both sanitation and kitchen facilities, occupied or arranged to be occupied by not more than one family maintaining a common household.

APARTMENT, STUDENT. An apartment occupied or arranged to be occupied by students enrolled at a single accredited college or university and maintaining a common household pursuant to a lease, sublease, or occupancy agreement directly with such college or university.

BOARDER (ROOMER, LODGER). A person who pays a consideration for living within the household and does not occupy such space as an incident of employment.

CONGREGATE LIVING UNIT. A dwelling unit, comprised of one or more habitable rooms separated by nonrated partitions, occupied or arranged to be occupied by more than one family or by persons who are not maintaining a common household. Creation of or conversion to such unit shall be subject to Section 27-2077 of the New York City Housing Maintenance Code.

CUSTODIAL CARE FACILITY. A building or part thereof occupied by persons, on less than a 24-hour basis and not overnight, who because of age, disability or other reasons, receive personal care services by individuals other than parents or guardians, relatives by blood, marriage, domestic partnership, or adoption, in a place other than the home of the person cared for.

DWELLING. A building or structure which is occupied in whole or in part as the home, residence or sleeping place of one or more families.

DWELLING, MULTIPLE. A dwelling which is either rented, leased, let or hired out, to be occupied, or is occupied, as the residence or home of three or more families living independently of each other. A multiple dwelling does not include a building used for occupancies in Groups I-2, I-3 or I-4.

DWELLING, ONE-FAMILY. Any building or structure designed and occupied exclusively for residence purposes on a long-term basis for more than a month at a time by not more than one family. One-family dwellings shall also be deemed to include a dwelling located in a series of one-family dwellings each of which faces or is accessible to a legal street or public thoroughfare, provided that each such dwelling unit is equipped as a separate dwelling unit with all essential services, and also provided that each such unit is arranged so that it may be approved as a legal one-family dwelling.

DWELLING, TWO-FAMILY. Any building or structure designed and occupied exclusively for residence purposes on a long-term basis for more than a month at a time by not more than two families. Two-family dwellings shall also be deemed to include a dwelling located in a series of two-family dwellings each of which faces or is accessible to a legal street or public thoroughfare, provided that each such dwelling is equipped as a separate dwelling with all essential services, and also provided that each such dwelling is arranged so that it may be approved as a legal two-family dwelling.

DWELLING UNIT. A single unit consisting of one or more habitable rooms and occupied or arranged to be occupied as a unit separate from all other units within a dwelling.

FAMILY.
  1. A single person occupying a dwelling unit and maintaining a common household with not more than two boarders, roomers or lodgers; or
  2. Two or more persons related by blood, adoption, legal guardianship, marriage or domestic partnership; occupying a dwelling unit and maintaining a common household with not more than two boarders, roomers or lodgers; or
  3. Not more than three unrelated persons occupying a dwelling unit and maintaining a common household; or
  4. Not more than three unrelated persons occupying a dwelling unit in a congregate housing or shared living arrangement and maintaining a common household; or
  5. Members of a group home; or
  6. Foster children placed in accordance with provisions of the New York State Social Services Law, their foster parent(s), and other persons related to the foster parents by blood, marriage or domestic partnership; where all residents occupy and maintain a common household with not more than two boarders, roomers or lodgers; or
  7. Up to seven unrelated students enrolled at a single accredited college or university occupying a student apartment and maintaining a common household pursuant to a lease, sublease, or occupancy agreement directly with such college or university, provided that:
    1. The entire structure in which the dwelling unit is located is fully sprinklered in accordance with Chapter 9; and
    2. Such occupancy does not exceed the maximums contained in Section 27-2075(a) of the New York City Housing Maintenance Code; and
    3. Prior to commencement of such occupancy, and on an annual basis thereafter such college or university has submitted a fire safety plan containing fire safety and evacuation procedures for such dwelling unit that is acceptable to the fire commissioner and in compliance with any rules promulgated by the Fire Commissioner; and
    4. The dwelling unit complies with additional occupancy and construction requirements as may be established by rule by the Housing Preservation and Development Commissioner.
A common household is deemed to exist if all household members have access to all parts of the dwelling unit. Lack of access to all parts of the dwelling unit establishes a rebuttable presumption that no common household exists.

GROUP HOME. A facility for the care and maintenance of not fewer than seven nor more than 12 children, supervised by the New York State Board of Social Welfare, and operated pursuant to and meeting any additional construction requirements of Section 374-C of the New York State Social Services Law and applicable regulations of the New York State Department of Social Services. Such a facility occupied by more than 12 children shall be classified as Group I-1.

PERSONAL CARE SERVICE. The care of residents who do not require chronic or convalescent medical or nursing care. Personal care involves responsibility for the safety of the resident while inside the building.

RESIDENTIAL CARE/ASSISTED LIVING FACILITIES. A building or part thereof housing persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment which provides personal care services. The occupants are capable of self-preservation and are capable of responding to an emergency situation without physical assistance from staff. This classification shall include, but not be limited to, the following: residential board and care facilities, assisted living facilities, halfway houses, congregate care facilities, social rehabilitation facilities, alcohol and drug abuse rehabilitation centers and convalescent facilities.

ROOMING HOUSE. A dwelling (i) which was originally erected as a single- or two-family private dwelling pursuant to the New York City Building Code in effect prior to December 6, 1968, (ii) which is a "Class B converted dwelling" as such term is defined in the New York City Housing Maintenance Code, and (iii) which has more than half of its habitable rooms as sleeping units. The creation of or conversion to a rooming house shall be limited by Section 27-2077 of the New York City Housing Maintenance Code.

SLEEPING UNIT. A dwelling unit, which may contain either toilet or kitchen facilities but not both. Any sleeping unit housing more than one family shall also be classified as a congregate living unit. The creation of or conversion to sleeping units shall be limited by Section 27-2077 of the New York City Housing Maintenance Code.

TRANSIENT. Occupancy of a dwelling unit or sleeping unit for not more than 30 days.
Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage, such as for warehouses, storage rooms, freight depots and distribution centers, when not classified as a hazardous occupancy.
Buildings occupied for storing any flammable or combustible materials that are likely to permit the development and production of fire with moderate rapidity including, but not limited to, storage of the following:

Aerosols, Levels 2 and 3

Aircraft hangar (storage and repair)

Bags; cloth, burlap and paper

Bamboos and rattan

Baskets

Belting; canvas and leather

Books and paper in rolls or packs

Boots and shoes

Buttons, including cloth covered, pearl or bone

Cardboard and cardboard boxes

Clothing, woolen wearing apparel

Cordage

Dry boat storage (indoor, not accessory to Group R)

Furniture

Furs

Glues, mucilage, pastes and size

Grains

Horns and combs, other than celluloid

Leather Linoleum Lumber Photo engravings

Resilient flooring Silks

Soaps Sugar Tires, bulk storage of

Tobacco, cigars, cigarettes and snuff

Upholstery and mattresses

Wax candles
Includes, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of the following:

Asbestos

Beverages up to and including 16 percent alcohol in metal, glass or ceramic containers

Cement in bags

Chalk and crayons

Dairy products in nonwaxed coated paper containers

Dry cell batteries

Electrical coils

Electrical motors

Empty cans

Food products

Foods in noncombustible containers

Fresh fruits and vegetables in nonplastic trays or containers

Frozen foods

Glass

Glass bottles, empty or filled with noncombustible liquids

Gypsum board

Inert pigments

Ivory

Meats

Metal cabinets

Metal desks with plastic tops and trim

Metal parts

Metals

Mirrors

Oil-filled and other types of distribution transformers

Parking garages, open or enclosed

Porcelain and pottery

Stoves

Talc and soapstones

Washers and dryers
Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of this code commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following:

Carports

Fences more than 6 feet (1829 mm) high

Private garages as per Section 406.1

Retaining walls

Sheds or greenhouses accessory to Group R-3 occupancies, that are freestanding, less than 120 square feet (11.15 m2) in area, not permanently affixed to the ground, and used for household goods or items associated with the garden or lawn. Any other shed shall be classified as either S-1 or S-2.

Tanks

Towers
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING