(The provisions contained in this appendix are adopted as part of this code.)
A deck is an exposed exterior wood floor structure that is permitted to be attached to the structure or freestanding. Roofed porches (open or screened-in) are permitted to be constructed using these provisions.
Computer deck design programs are permitted to be accepted by the code official.
Support posts shall be supported by a minimum footing in accordance with Figure AM102.1(1) and Table AM102.1. Minimum footing depth shall be 12 inches (305 mm) below finished grade in accordance with Section R403.1.4. Tributary area is calculated as shown in Figure AM102.1(2).
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2.
FIGURE AM102.1(1)
SUPPORT POST FOOTING

For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2.
Note: Tributary area of shaded section on the free standing deck shown is 5' × 6' = 30 square feet (2.79 m2). Code will require a minimum footing of 8" × 16" (203 mm × 406 mm) in accordance with Table AM102.1.FIGURE AM102.1(2)
CALCULATED TRIBUTARY AREA
SIZE (inches) |
TRIBUTARY AREA (square feet) |
THICKNESS (inches) |
||
A × A | B × C | Precast | Cast-In-Place | |
8 × 16 | 8 × 16 | 36 | 4 | 6 |
12 × 12 | 12 × 12 | 40 | 4 | 6 |
16 × 16 | 16 × 16 | 70 | 8 | 8 |
— | 16 × 24 | 100 | — | 8 |
— | 24 × 24 | 150 | — | 8 |
- Footing values are based on single floor and roof loads.
- Support post must rest in center one-third of footing.
- Top of footing shall be level for full bearing support of post.
SUPPORT POST FOOTING
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2.
Note: Tributary area of shaded section on the free standing deck shown is 5' × 6' = 30 square feet (2.79 m2). Code will require a minimum footing of 8" × 16" (203 mm × 406 mm) in accordance with Table AM102.1.
CALCULATED TRIBUTARY AREA
When attached to a structure, the structure to which it is attached shall have a treated wood band for the length of the deck, or corrosion-resistant flashing shall be used to prevent moisture from coming in contact with the untreated framing of the structure. Aluminum flashing shall not be used in conjunction with deck construction. The deck band and the structure band shall be constructed in contact with each other except on brick veneer structures and where plywood sheathing is required and properly flashed. Siding shall not be installed between the structure and the deck band. If attached to a brick structure, neither the flashing nor a treated band for brick structure is required. In addition, the treated deckband shall be constructed in contact with the brick veneer. Flashing shall be installed in accordance with Figure AM103.1.

For SI: 1 inch = 25.4 mmFIGURE AM103.1
FLASHING FOR DECK ATTACHED TO STRUCTURE
For SI: 1 inch = 25.4 mm
FLASHING FOR DECK ATTACHED TO STRUCTURE
When a deck is supported at the structure by attaching the deck to the structure, Tables AM104.1(1) and AM104.1(2) shall apply for attaching the deck band to the structure.
For SI: 1 inch = 25.4, 1 foot = 304.8 mm
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
FASTENERS | 8' MAX JOIST SPANa | 16' MAX JOIST SPANa |
5⁄8" Hot-dip galvanized bolts with nut and washerb and 12d Common hot-dip galvanized nailsc |
1 @ 3'-6" o.c. and 2 @ 8" o.c. |
1 @ 1'-8" o.c. and 3 @ 6" o.c. |
OR | ||
Self-drilling screw fastenerd | 12" o.c. staggered | 6" o.c. staggered |
- Attachment interpolation between 8 foot and 16 foot joists span is allowed.
- Minimum edge distance for bolts is 21⁄2 inches.
- Nails must penetrate the supporting structure band a minimum of 11⁄2 inches.
- Self-drilling screw fastener having a minimum shank diameter of 0.195 inches and a length long enough to penetrate through the supporting structure band. The structure band shall have a minimum depth of 11⁄8 inches. Screw shall be evaluated by an approved testing agency for allowable shear load for Southern Pine to Southern Pine lumber of 250 pounds and shall have a corrosion-resistant finish equivalent to hot dip galvanized. Minimum edge distance for screws is 17⁄16 inches. A maximum of 1⁄2 inch thick wood structural panel is permitted to be located between the deck ledger and the structure band.
FASTENERS | 8' MAX JOIST SPANa | 16' MAX JOIST SPANa |
5⁄8" Hot-dip galvanized bolts with nut and washerb | 1 @ 2'-4" o.c. | 1 @ 1'-4" o.c. |
- Attachment interpolation between 8 foot and 16 foot joist span is allowed.
- Minimum edge distance for bolts is 21⁄2 inches.
If the deck band is supported by a minimum of 1⁄2 inch (13 mm) masonry ledge along the foundation wall, 5⁄8-inch (16 mm) hot-dip galvanized bolts with washers spaced at 48 inches (1219 mm) o.c. are permitted to be used for support.
Joist hangers or other means of attachment are permitted to be connected to the house band and shall be properly flashed.
Girders shall bear directly on the support post with the post attached at top to prevent lateral displacement or be connected to the side of the posts with two ⅝-inch (16 mm) hot-dip galvanized bolts with nut and washer. Girder support is permitted to be installed in accordance with Figure AM105.1(1) for top mount; Figure AM105.1(2) for side mount and Figure AM105.1(3) for split girders. See Figure AM105.1(4) for cantilevered girders.

For SI: 1 inch = 25.4 mm.FIGURE AM105.1(1)
TOP MOUNT/FLUSH GIRDER

For SI: 1 inch = 25.4 mm.FIGURE AM105.1(2)
SIDE MOUNT DROPPED GIRDER

For SI: 1 inch = 25.4 mm.FIGURE AM105.1(3)
SPLIT GIRDER

For SI: 1 inch = 25.4 mm.FIGURE AM105.1(4)
CANTILIEVERED DROPPED GIRDER
For SI: 1 inch = 25.4 mm.
TOP MOUNT/FLUSH GIRDER
For SI: 1 inch = 25.4 mm.
SIDE MOUNT DROPPED GIRDER
For SI: 1 inch = 25.4 mm.
SPLIT GIRDER
For SI: 1 inch = 25.4 mm.
CANTILIEVERED DROPPED GIRDER
Maximum allowable spans for wood deck girders, as shown in Figure AM105.2, shall be in accordance with Table AM105.2. Girder plies shall be fastened with two rows of 10d (3-inch × 0.128-inch) nails minimum at 16 inches (406 mm) on center along each edge. Girders shall be permitted to cantilever at each end up to one-fourth of the actual beam span. Splices of multispan beams shall be located at interior post locations.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound = 0.454 kg.
FIGURE AM105.2
TYPICAL DECK GIRDER SPANS
SPECIESc | SIZEd | DECK JOIST SPAN LESS THAN OR EQUAL TO: (feet) |
||||||
---|---|---|---|---|---|---|---|---|
6 | 8 | 10 | 12 | 14 | 16 | 18 | ||
Southern pine | 2 – 2 × 6 | 6-11 | 5-11 | 5-4 | 4-10 | 4-6 | 4-3 | 4-0 |
2 – 2 × 8 | 8-9 | 7-7 | 6-9 | 6-2 | 5-9 | 5-4 | 5-0 | |
2 – 2 × 10 | 10-4 | 9-0 | 8-0 | 7-4 | 6-9 | 6-4 | 6-0 | |
2 – 2 × 12 | 12-2 | 10-7 | 9-5 | 8-7 | 8-0 | 7-6 | 7-0 | |
3 – 2 × 6 | 8-2 | 7-5 | 6-8 | 6-1 | 5-8 | 5-3 | 5-0 | |
3 – 2 × 8 | 10-10 | 9-6 | 8-6 | 7-9 | 7-2 | 6-8 | 6-4 | |
3 – 2 × 10 | 13-0 | 11-3 | 10-0 | 9-2 | 8-6 | 7-11 | 7-6 | |
3 – 2 × 12 | 15-3 | 13-3 | 11-10 | 10-9 | 10-0 | 9-4 | 8-10 | |
Douglas fir-larche, hem-fire, spruce-pine-fire, redwood, western cedars, ponderosa pinef, red pinef | 3 × 6 or 2 – 2 × 6 | 5-5 | 4-8 | 4-2 | 3-10 | 3-6 | 3-1 | 2-9 |
3 × 8 or 2 – 2 × 8 | 6-10 | 5-11 | 5-4 | 4-10 | 4-6 | 4-1 | 3-8 | |
3 × 10 or 2 – 2 × 10 | 8-4 | 7-3 | 6-6 | 5-11 | 5-6 | 5-1 | 4-8 | |
3 × 12 or 2 – 2 × 12 | 9-8 | 8-5 | 7-6 | 6-10 | 6-4 | 5-11 | 5-7 | |
4 × 6 | 6-5 | 5-6 | 4-11 | 4-6 | 4-2 | 3-11 | 3-8 | |
4 × 8 | 8-5 | 7-3 | 6-6 | 5-11 | 5-6 | 5-2 | 4-10 | |
4 × 10 | 9-11 | 8-7 | 7-8 | 7-0 | 6-6 | 6-1 | 5-8 | |
4 × 12 | 11-5 | 9-11 | 8-10 | 8-1 | 7-6 | 7-0 | 6-7 | |
3 – 2 × 6 | 7-4 | 6-8 | 6-0 | 5-6 | 5-1 | 4-9 | 4-6 | |
3 – 2 × 8 | 9-8 | 8-6 | 7-7 | 6-11 | 6-5 | 6-0 | 5-8 | |
3 – 2 × 10 | 12-0 | 10-5 | 9-4 | 8-6 | 7-10 | 7-4 | 6-11 | |
3 – 2 × 12 | 13-11 | 12-1 | 10-9 | 9-10 | 9-1 | 8-6 | 8-1 |
- Ground snow load, live load = 40 psf, dead load = 10 psf, L/Δ = 360 at main span, L/Δ = 180 at cantilever with a 220-pound point load applied at the end.
- Girders supporting deck joists from one side only.
- No. 2 grade, wet service factor.
- Girder depth shall be greater than or equal to depth of joists with a flush beam condition.
- Includes incising factor.
- Northern species. Incising factor not included.
TYPICAL DECK GIRDER SPANS
Girder spans for covered decks shall be in accordance with Tables R602.7(1) and (2).
Maximum allowable spans for wood deck joists, as shown in Figure AM106.1, shall be in accordance with Table AM106.1. Deck joists shall be permitted to cantilever not greater than one-fourth of the actual, adjacent joist span.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound = 0.454 kg.
FIGURE AM106.1
TYPICAL DECK JOIST SPANS
SPECIESa | SIZE | SPACING OF DECK JOISTS WITH NO CANTILEVERb (inches) | SPACING OF DECK JOISTS WITH CANTILEVERSc (inches) | ||||
---|---|---|---|---|---|---|---|
12 | 16 | 24 | 12 | 16 | 24 | ||
Southern pine | 2 × 6 | 9-11 | 9-0 | 7-7 | 6-8 | 6-8 | 6-8 |
2 × 8 | 13-1 | 11-10 | 9-8 | 10-1 | 10-1 | 9-8 | |
2 × 10 | 16-2 | 14-0 | 11-5 | 14-6 | 14-0 | 11-5 | |
2 × 12 | 18-0 | 16-6 | 13-6 | 18-0 | 16-6 | 13-6 | |
Douglas fir-larchd, hem-fird, spruce-pine-fird | 2 × 6 | 9-6 | 8-8 | 7-2 | 6-3 | 6-3 | 6-3 |
2 × 8 | 12-6 | 11-1 | 9-1 | 9-5 | 9-5 | 9-1 | |
2 × 10 | 15-8 | 13-7 | 11-1 | 13-7 | 13-7 | 11-1 | |
2 × 12 | 18-0 | 15-9 | 12-10 | 18-0 | 15-9 | 12-10 | |
Redwood, western cedars, ponderosa pinee, red pinee | 2 × 6 | 8-10 | 8-0 | 7-0 | 5-7 | 5-7 | 5-7 |
2 × 8 | 11-8 | 10-7 | 8-8 | 8-6 | 8-6 | 8-6 | |
2 × 10 | 14-11 | 13-0 | 10-7 | 12-3 | 12-3 | 10-7 | |
2 × 12 | 17-5 | 15-1 | 12-4 | 16-5 | 15-1 | 12-4 |
- No. 2 grade with wet service factor.
- Ground snow load, live load = 40 psf, dead load = 10 psf, L/Δ = 360.
- Ground snow load, live load = 40 psf, dead load = 10 psf, L/Δ = 360 at main span, L/Δ = 180 at cantilever with a 220-pound point load applied to end.
- Includes incising factor.
- Northern species with no incising factor.
- Cantilevered spans not exceeding the nominal depth of the joist are permitted.
TYPICAL DECK JOIST SPANS
Joist ends and bearing locations shall be provided with lateral restraint to prevent rotation. Where lateral restraint is provided by joist hangers or blocking between joists, their depth shall equal not less than 60 percent of the joist depth. Where lateral restraint is provided by rim joists, they shall be secured to the end of each joist with not less than (3) 10d (3-inch × 0.128-inch) nails or (3) No. 10 × 3-inch (76 mm) long wood screws.
Joists spans shall be in accordance with Table R502.3.1(2) with 40-pounds persquare-foot live load and 10-pounds per-square-foot dead load. Cantilevered floor joists shall be in accordance with Table R502.3.3(1).
Floor decking shall be No. 2 grade treated Southern Pine or equivalent. The minimum floor decking thickness shall be in accordance with Table AM107.1.
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
SPACING | DECKING (nominal) |
---|---|
12" o.c. | 1" S4S |
16" o.c. | 1" T&G |
19.2" o.c. | ¼" S4S |
24"-36" o.c. | 2" S4S |
Maximum height of deck support posts shall be in accordance with Table AM108.1.
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
POST SIZEa | MAXIMUM POST HEIGHTb, c |
---|---|
4" × 4" | 8'-0" |
6" × 6" | 20'-0" |
- This table is based on No. 2 Southern Pine posts.
- From top of footing to bottom of girder.
- Decks with post heights exceeding these requirements shall be designed by a registered design professional.
Decks shall be braced to provide lateral stability. Lateral stability shall be provided in accordance with one of the methods in Sections AM109.1.1 through AM109.1.5.
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2.
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.FIGURE AM109.1(1)
NO LATERAL BRACING
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.FIGURE AM109.1(2)
KNEE BRACING

For SI: 1 inch = 25.4, 1 foot = 304.8 mm.FIGURE AM109.1(3)
POST EMBEDMENT

For SI: 1 inch = 25.4, 1 foot = 304.8 mm.FIGURE AM109.1(4)
CROSS BRACING
POST SIZE | MAXIMUM TRIBUTARY AREA |
MAXIMUM POST HEIGHT |
EMPEDMENT DEPTH |
CONCRETE DIAMETER |
4" × 4" | 48 SF | 4'-0" | 2'-6" | 1'-0" |
6" × 6" | 120 SF | 6'-0" | 3'-6" | 1'-8" |
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
NO LATERAL BRACING
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
KNEE BRACING
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
POST EMBEDMENT
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
CROSS BRACING
When the deck floor height is less than 4 feet (1219 mm) above finished grade as shown in Figure AM109.1(1) and the deck is attached to the structure in accordance with Section AM104, lateral bracing is not required. Lateral bracing is not required for freestanding decks with a deck floor height 30 inches (762 mm) or less above finished grade.
4 × 4 wood knee braces are permitted to be provided on each column in both directions. The knee braces shall attach to each post at a point not less than 1⁄3 of the post length from the top of the post, and the braces shall be angled between 45 degrees (0.79 rad) and 60 degrees (1.05 rad) from the horizontal. Knee braces shall be bolted to the post and the girder/double band with one 5⁄8-inch (16 mm) hot-dip galvanized bolt with nut and washer at both ends of the brace as shown in Figure AM109.1(2)
For free standing decks without knee braces or diagonal bracing, lateral stability is permitted to be provided by embedding the post in accordance with Figure AM109.1(3) and Table AM109.1.
2 × 6 diagonal vertical cross bracing is permitted to be provided in two perpendicular directions for free standing decks or parallel to the structure at the exterior column line for attached decks. The 2 × 6 bracing shall be attached to the posts with one 5⁄8-inch (16 mm) hot-dip galvanized bolt with nut and washer at each end of each bracing member in accordance with Figure AM109.1(4).
For embedment of piles in coastal regions, see Chapter 46.
Stringer spans shall be no greater than 7 feet (2134 mm) between supports. Spacing between stringers shall be based upon decking material used in accordance with AM107.1. Each stringer shall have a minimum of 31⁄2 inches (89 mm) between step cut and back of stringer. If used, suspended headers shall be attached with 3⁄8-inch (9.5 mm) galvanized bolts with nuts and washers to securely support stringers at the top. See Figure AM 110.1.

For SI: 1 inch = 25.4, 1 foot = 304.8 mm.FIGURE AM110.1
STAIR STRINGER
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
STAIR STRINGER
Deck handrails, guards and general construction shall be as shown in Figure AM111.1.

For SI: 1 inch = 25.4, 1 foot = 304.8 mm.FIGURE AM111.1
DECK CONSTRUCTION
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
DECK CONSTRUCTION
Walkways over dunes in ocean hazard areas shall be constructed as shown in Figure AM112.1.

For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
* Posts for walkways over dunes or berms shall be embedded a minimum depth of 4' - 0" and post heights shall be limited to 5'- 0" above grade for 4 × 4 and 10' - 0" above grade for 6 × 6.Walkways or portions of walkways over 4' 0" in width shall comply with the requirements of Chapters 45 and 46. Maximum walkway surface height is 30" above grade without guard rails.
** Walkway stair runs are permitted to be greater than 12' without a landing.
*** Open risers permitted on ocean shoreline stair.
**** Horizontal guards permitted to have maximum 18 inch opening on cross-over walkway and ocean shoreline stair.FIGURE AM112.1
WALKWAYS OVER DUNES OR BERMS IN OCEAN HAZARD AREAS
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
* Posts for walkways over dunes or berms shall be embedded a minimum depth of 4' - 0" and post heights shall be limited to 5'- 0" above grade for 4 × 4 and 10' - 0" above grade for 6 × 6.Walkways or portions of walkways over 4' 0" in width shall comply with the requirements of Chapters 45 and 46. Maximum walkway surface height is 30" above grade without guard rails.
** Walkway stair runs are permitted to be greater than 12' without a landing.
*** Open risers permitted on ocean shoreline stair.
**** Horizontal guards permitted to have maximum 18 inch opening on cross-over walkway and ocean shoreline stair.
WALKWAYS OVER DUNES OR BERMS IN OCEAN HAZARD AREAS