ADOPTS WITH AMENDMENTS:

International Existing Building Code 2015 (IEBC 2015)

Heads up: There are no amended sections in this chapter.

Part 1 — Scope and Application

101.1 Title

AMENDMENT
This section has been amended at the state or city level.
These regulations shall be known as the North Carolina Existing Building Code as adopted by the North Carolina Building Code Council on June 13, 2017 to be effective January 1, 2019. References to the International Codes shall mean the North Carolina Codes. The North Carolina amendments to the International Codes are underlined.
The provisions of the International Existing Building Code shall apply to the repair, alteration, change of occupancy, addition to and relocation of existing buildings.
The intent of this code is to provide flexibility to permit the use of alternative approaches to achieve compliance with minimum requirements to safeguard the public health, safety and welfare insofar as they are affected by the repair, alteration, change of occupancy, addition and relocation of existing buildings.
This code shall apply to the repair, alteration, change of occupancy, addition and relocation of existing buildings, regardless of occupancy, subject to the criteria of Sections 101.4.1 and 101.4.2.

101.4.1 Buildings Not Previously Legally Occupied

AMENDMENT
This section has been amended at the state or city level.
A building or portion of a building that has not been previously legally occupied or used for its intended purpose in accordance with the laws in existence at the time of its completion shall be permitted to comply with the provisions of the laws in existence at the time of its original permit unless such permit has expired. Subsequent permits shall comply with the International Building Code or International Residential Code, as applicable, for new construction.

101.4.2 Buildings Previously Legally Occupied

AMENDMENT
This section has been amended at the state or city level.
The legal occupancy of any building existing on the date of adoption of this code shall be permitted to continue without change, except as is specifically covered in this code, the International Fire Code, or as is deemed necessary by the code official for the general safety and welfare of the occupants and the public.
Construction work covered in this code, including any related demolition, shall comply with the requirements of Chapter 15.

101.6 Appendices

AMENDMENT
This section has been amended at the state or city level.
Provisions in the appendices shall not apply unless specifically adopted or referenced in this code.
Repairs or alterations mandated by any property, housing, or fire safety maintenance code or mandated by any licensing rule or ordinance adopted pursuant to law shall conform only to the requirements of that code, rule, or ordinance and shall not be required to conform to this code unless the code requiring such repair or alteration so provides.

101.8 Requirements of Other State Agencies, Occupational Licensing Boards or Commissions

AMENDMENT
This section has been amended at the state or city level.
The North Carolina State Building Codes do not include all additional requirements for buildings and structures that may be imposed by other State agencies, occupational licensing boards and commissions. It shall be the responsibility of a permit holder, registered design professional, contractor or occupational license holder to determine whether any additional requirements exist.

101.9 Mixed Use Buildings

AMENDMENT
This section has been amended at the state or city level.
Each portion of a building shall be separately classified as to use. The requirements of this code shall apply to each portion of the building based on the occupancy classification of that portion, except that the most restrictive requirements of this code for fire suppression shall apply to the entire building.

Exception: An automatic fire suppression system shall not be required for uses that would not otherwise require suppression provided that there is a 1-hour separation between the uses requiring suppression and the other uses in the same building. A 2-hour fire separation shall be required to apply this exception to Group H.

101.10 High-Rise Buildings

AMENDMENT
This section has been amended at the state or city level.
High-rise buildings constructed prior to 1978 shall at a minimum comply with N.C.G.S. 143—138(i). The statute may be viewed at the following web address: http://www.ncga.state.nc.us/EnactedLegislation/Statutes/HTML/BySection/Chapter_143/GS_143-138.html.

101.11 Accessibility for Townhouses

AMENDMENT
This section has been amended at the state or city level.
In townhouses, where there are four or more dwelling units in a single structure, the provisions for accessibility of this code for Group R-3 shall apply.

101.12 Energy Conservation Exceptions

AMENDMENT
This section has been amended at the state or city level.
The following exceptions apply to energy conservation code provisions in existing buildings in accordance with NC General Statutes:
  1. In accordance with N.C.G.S. 143-138 (b18), no energy conservation code provisions shall apply to any structure for which the primary occupancy classification is Group F, S, or U. This exclusion shall apply to the entire building area.
  2. In accordance with the N.C.G.S. 143-138 (b19), for residential buildings, no energy conservation code provisions shall apply to detached and attached garages located on the same lot as a dwelling.
The delayed effective date of this Rule is January 1, 2020.
The Statutory authority for Rule-making is G. S. 143-136; 143-138.

UpCodes note: According to the 2017—2020 Approved Cumulative Amendments, prior to January 1, 2020, this section appeared as:

"101.12 Energy conservation

Per G.S. 143-138 (b18), no energy conservation code provisions shall apply to any structure for which the primary occupancy classification is Group F, S, or U. This exclusion shall apply to the entire building area.

The delayed effective date of this Rule is January 1, 2019.
The Statutory authority for Rule-making is G. S. 143-136; 143-138.
"
Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall be applicable. Where in any specific case different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern.
The provisions of this code shall not be deemed to nullify any provisions of local, state, or federal law.
References to chapter or section numbers or to provisions not specifically identified by number shall be construed to refer to such chapter, section, or provision of this code.
The codes and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections 102.4.1 and 102.4.2.
Exception: Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, the conditions of the listing shall govern.
Where conflicts occur between provisions of this code and referenced codes and standards, the provisions of this code shall apply.
Where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code, the provisions of this code as applicable, shall take precedence over the provisions in the referenced code or standard.
In the event that any part or provision of this code is held to be illegal or void, this shall not have the effect of making void or illegal any of the other parts or provisions.

Part 2 — Administration and Enforcement

Section 103 Department of Building Safety

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

103.1 Creation of Enforcement Agency

AMENDMENT
This section has been amended at the state or city level.

103.2 Appointment

AMENDMENT
This section has been amended at the state or city level.

103.3 Deputies

AMENDMENT
This section has been amended at the state or city level.

104.1 General

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.2 Applications and Permits

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.2.2 Preliminary Meeting

AMENDMENT
This section has been amended at the state or city level.

104.2.2.1 Building Evaluation

AMENDMENT
This section has been amended at the state or city level.

104.3 Notices and Orders

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.4 Inspections

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.5 Identification

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.6 Right of Entry

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.7 Department Records

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.8 Liability

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.8.1 Legal Defense

AMENDMENT
This section has been amended at the state or city level.

104.9 Approved Materials and Equipment

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

104.9.1 Used Materials and Equipment

AMENDMENT
This section has been amended at the state or city level.
Wherever there are practical difficulties involved in carrying out the provisions of this code, the code official shall have the authority to grant modifications for individual cases upon application of the owner or owner's authorized representative, provided the code official shall first find that special individual reason makes the strict letter of this code impractical, the modification is in compliance with the intent and purpose of this code and such modification does not lessen health, accessibility, life and fire safety, or structural requirements. The details of action granting modifications shall be recorded and entered in the files of the Department of Building Safety.

104.10.1 Flood Hazard Areas

AMENDMENT
This section has been amended at the state or city level.
For existing buildings located in flood hazard areas for which repairs, alterations and additions constitute substantial improvement, the code official shall not grant modifications to provisions related to flood resistance unless a determination is made that:
  1. The applicant has presented good and sufficient cause that the unique characteristics of the size, configuration or topography of the site render compliance with the flood-resistant construction provisions inappropriate.
  2. Failure to grant the modification would result in exceptional hardship.
  3. The granting of the modification will not result in increased flood heights, additional threats to public safety, extraordinary public expense nor create nuisances, cause fraud on or victimization of the public or conflict with existing laws or ordinances.
  4. The modification is the minimum necessary to afford relief, considering the flood hazard.
  5. A written notice will be provided to the applicant specifying, if applicable, the difference between the design flood elevation and the elevation to which the building is to be built, stating that the cost of flood insurance will be commensurate with the increased risk resulting from the reduced floor elevation and that construction below the design flood elevation increases risks to life and property.
Local ordinances more restrictive than the requirements of this section supersede these requirements.
The provisions of this code are not intended to prevent the installation of any material or to prohibit any design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material, design, or method of construction shall be approved where the code official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method, or work offered is, for the purpose intended, not less than the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety. Where the alternative material, design or method of construction is not approved, the code official shall respond in writing, stating the reasons the alternative was not approved.
Supporting data, where necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.
Whenever there is insufficient evidence of compliance with the provisions of this code or evidence that a material or method does not conform to the requirements of this code, or in order to substantiate claims for alternative materials or methods, the code official shall have the authority to require tests as evidence of compliance to be made at no expense to the jurisdiction. Test methods shall be as specified in this code or by other recognized test standards. In the absence of recognized and accepted test methods, the code official shall approve the testing procedures. Tests shall be performed by an approved agency. Reports of such tests shall be retained by the code official for the period required for retention.

Section 105 Permits

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

105.1 Required

AMENDMENT
This section has been amended at the state or city level.

105.1.1 Annual Permit

AMENDMENT
This section has been amended at the state or city level.

105.1.2 Annual Permit Records

AMENDMENT
This section has been amended at the state or city level.

105.2 Work Exempt From Permit

AMENDMENT
This section has been amended at the state or city level.

105.2.1 Emergency Repairs

AMENDMENT
This section has been amended at the state or city level.

105.2.2 Repairs

AMENDMENT
This section has been amended at the state or city level.

105.2.3 Public Service Agencies

AMENDMENT
This section has been amended at the state or city level.

105.3 Application for Permit

AMENDMENT
This section has been amended at the state or city level.

105.3.1 Action on Application

AMENDMENT
This section has been amended at the state or city level.

105.3.2 Time Limitation of Application

AMENDMENT
This section has been amended at the state or city level.

105.4 Validity of Permit

AMENDMENT
This section has been amended at the state or city level.

105.5 Expiration

AMENDMENT
This section has been amended at the state or city level.

105.6 Suspension or Revocation

AMENDMENT
This section has been amended at the state or city level.

105.7 Placement of Permit

AMENDMENT
This section has been amended at the state or city level.

Section 106 Construction Documents

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

106.1 General

AMENDMENT
This section has been amended at the state or city level.

106.2 Construction Documents

AMENDMENT
This section has been amended at the state or city level.

106.2.1 Construction Documents

AMENDMENT
This section has been amended at the state or city level.

106.2.2 Fire Protection System(s) Shop Drawings

AMENDMENT
This section has been amended at the state or city level.

106.2.3 Means of Egress

AMENDMENT
This section has been amended at the state or city level.

106.2.4 Exterior Wall Envelope

AMENDMENT
This section has been amended at the state or city level.

106.2.5 Site Plan

AMENDMENT
This section has been amended at the state or city level.

106.3 Examination of Documents

AMENDMENT
This section has been amended at the state or city level.

106.3.1 Approval of Construction Documents

AMENDMENT
This section has been amended at the state or city level.

106.3.2 Previous Approval

AMENDMENT
This section has been amended at the state or city level.

106.3.3 Phased Approval

AMENDMENT
This section has been amended at the state or city level.

106.3.4 Deferred Submittals

AMENDMENT
This section has been amended at the state or city level.

106.4 Amended Construction Documents

AMENDMENT
This section has been amended at the state or city level.

106.5 Retention of Construction Documents

AMENDMENT
This section has been amended at the state or city level.

106.6 Design Professional in Responsible Charge

AMENDMENT
This section has been amended at the state or city level.

Section 107 Temporary Structures and Uses

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

107.1 General

AMENDMENT
This section has been amended at the state or city level.

107.2 Conformance

AMENDMENT
This section has been amended at the state or city level.

107.3 Temporary Power

AMENDMENT
This section has been amended at the state or city level.

107.4 Termination of Approval

AMENDMENT
This section has been amended at the state or city level.

Section 108 Fees

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

108.1 Payment of Fees

AMENDMENT
This section has been amended at the state or city level.

108.2 Schedule of Permit Fees

AMENDMENT
This section has been amended at the state or city level.

108.3 Building Permit Valuations

AMENDMENT
This section has been amended at the state or city level.

108.4 Work Commencing Before Permit Issuance

AMENDMENT
This section has been amended at the state or city level.

108.5 Related Fees

AMENDMENT
This section has been amended at the state or city level.

108.6 Refunds

AMENDMENT
This section has been amended at the state or city level.

Section 109 Inspections

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

109.1 General

AMENDMENT
This section has been amended at the state or city level.

109.2 Preliminary Inspection

AMENDMENT
This section has been amended at the state or city level.

109.3 Required Inspections

AMENDMENT
This section has been amended at the state or city level.

109.3.1 Footing or Foundation Inspection

AMENDMENT
This section has been amended at the state or city level.

109.3.2 Concrete Slab or Under-Floor Inspection

AMENDMENT
This section has been amended at the state or city level.

109.3.3 Lowest Floor Elevation

AMENDMENT
This section has been amended at the state or city level.

109.3.4 Frame Inspection

AMENDMENT
This section has been amended at the state or city level.

109.3.5 Lath or Gypsum Board Inspection

AMENDMENT
This section has been amended at the state or city level.

109.3.6 Fire and Smoke-Resistant Penetrations

AMENDMENT
This section has been amended at the state or city level.

109.3.7 Other Inspections

AMENDMENT
This section has been amended at the state or city level.

109.3.8 Special Inspections

AMENDMENT
This section has been amended at the state or city level.

109.3.9 Final Inspection

AMENDMENT
This section has been amended at the state or city level.

109.4 Inspection Agencies

AMENDMENT
This section has been amended at the state or city level.

109.5 Inspection Requests

AMENDMENT
This section has been amended at the state or city level.

109.6 Approval Required

AMENDMENT
This section has been amended at the state or city level.

Section 110 Certificate of Occupancy

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

110.1 Altered Area Use and Occupancy Classification Change

AMENDMENT
This section has been amended at the state or city level.

110.2 Certificate Issued

AMENDMENT
This section has been amended at the state or city level.

110.3 Temporary Occupancy

AMENDMENT
This section has been amended at the state or city level.

110.4 Revocation

AMENDMENT
This section has been amended at the state or city level.

Section 111 Service Utilities

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

111.1 Connection of Service Utilities

AMENDMENT
This section has been amended at the state or city level.

111.2 Temporary Connection

AMENDMENT
This section has been amended at the state or city level.

111.3 Authority to Disconnect Service Utilities

AMENDMENT
This section has been amended at the state or city level.

Section 112 Board of Appeals

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

112.1 General

AMENDMENT
This section has been amended at the state or city level.

112.2 Limitations on Authority

AMENDMENT
This section has been amended at the state or city level.

112.3 Qualifications

AMENDMENT
This section has been amended at the state or city level.

Section 113 Violations

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

113.1 Unlawful Acts

AMENDMENT
This section has been amended at the state or city level.

113.2 Notice of Violation

AMENDMENT
This section has been amended at the state or city level.

113.3 Prosecution of Violation

AMENDMENT
This section has been amended at the state or city level.

113.4 Violation Penalties

AMENDMENT
This section has been amended at the state or city level.

Section 114 Stop Work Order

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

114.1 Authority

AMENDMENT
This section has been amended at the state or city level.

114.2 Issuance

AMENDMENT
This section has been amended at the state or city level.

114.3 Unlawful Continuance

AMENDMENT
This section has been amended at the state or city level.

Section 115 Unsafe Buildings and Equipment

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

115.1 Conditions

AMENDMENT
This section has been amended at the state or city level.

115.2 Record

AMENDMENT
This section has been amended at the state or city level.

115.3 Notice

AMENDMENT
This section has been amended at the state or city level.

115.4 Method of Service

AMENDMENT
This section has been amended at the state or city level.

115.5 Restoration

AMENDMENT
This section has been amended at the state or city level.

Section 116 Emergency Measures

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

116.1 Imminent Danger

AMENDMENT
This section has been amended at the state or city level.

116.2 Temporary Safeguards

AMENDMENT
This section has been amended at the state or city level.

116.3 Closing Streets

AMENDMENT
This section has been amended at the state or city level.

116.4 Emergency Repairs

AMENDMENT
This section has been amended at the state or city level.

116.5 Costs of Emergency Repairs

AMENDMENT
This section has been amended at the state or city level.

116.6 Hearing

AMENDMENT
This section has been amended at the state or city level.

Section 117 Demolition

AMENDMENT
This section has been amended at the state or city level.
See the North Carolina Administrative Code and Policies.

117.1 General

AMENDMENT
This section has been amended at the state or city level.

117.2 Notices and Orders

AMENDMENT
This section has been amended at the state or city level.

117.3 Failure to Comply

AMENDMENT
This section has been amended at the state or city level.

117.4 Salvage Materials

AMENDMENT
This section has been amended at the state or city level.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING