ADOPTS WITH AMENDMENTS:

International Building Code 2009 (IBC 2009)

Heads up: There are no amended sections in this chapter.
This chapter governs the electrical components, equipment and systems used in buildings and structures covered by this code. Electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of the New York City Electrical Code.
Emergency and standby power systems shall be installed in accordance with the New York City Electrical Code, NFPA 110 and NFPA 111.
Systems relying on fuel supplies shall have an on-premises fuel supply sufficient for not less than 6-hour full-demand operation of the system. However, natural gas from the public utility street main shall be permitted as the sole fuel supply for (i) emergency power systems serving R-2 occupancies and (ii) standby power systems, provided that an outside gas cut-off valve separate from other gas services is installed in accordance with Section E.6 of Appendix E of the New York City Fuel Gas Code.
Stationary emergency and standby power generators shall be listed in accordance with UL 2200 and shall comply with Sections 2702.1.2.1 through 2702.1.2.3.
Emergency and standby power generators shall not be located in the same room as the main or primary electrical service equipment. Distribution associated with emergency and standby power systems shall not pass through the room containing the main or primary electrical service equipment.
Emergency and standby generators within a building shall be located within a dedicated room separated by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both.
Equipment and fuel tanks located within the emergency generator room shall be limited to equipment and fuel tanks associated with the emergency and standby power systems. Piping within the room shall be limited to sprinkler piping.

Exceptions:
  1. Uninterrupted conduits not associated with the emergency and standby power system may pass through the emergency generator room.
  2. Piping associated with generator cooling systems may be located within the emergency generator room.
Multiple generators supplying emergency power system loads only, or supplying emergency power system equipment in combination with optional standby loads as a common system, may share common fuel supplies and other common equipment and systems.
The emergency and standby power systems shall have capacity and ratings that supply all equipment required to be operational at the same time.
Where electrically powered fire pumps are connected to the emergency power system, overcurrent protection and feeder conductors shall be provided in accordance with the New York City Electrical Code. Automatic transfer switches shall be located in the same room as the fire pump as an integral part of the pump controller.
The installation of a required emergency or standby power system shall be subject to special inspection in accordance with Section 1704.
Fuel-burning equipment for an emergency or standby power system shall be registered with the Department of Environmental Protection in accordance with the requirements of Section 24-109 of the Administrative Code.
Automatic transfer devices, emergency generators and emergency or standby power system feeders shall comply with Sections 2702.1.7.1 through 2707.1.7.2.1.
All automatic transfer devices and emergency power system feeders that serve required emergency power system equipment shall not be located in the same room as the emergency power system equipment or the main or primary electrical service equipment.
Any automatic transfer device that is not located at the load shall be located within a dedicated room separated by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both.
Equipment located within the automatic transfer device room shall be limited to equipment associated with the emergency or standby power systems. Piping within the room shall be limited to sprinkler piping.
Emergency and standby power systems shall be provided where required by this section.
Emergency power shall be provided for voice/alarm communication systems in Group A occupancies in accordance with Section 907.5.2.2.4.
Standby power shall be provided for smoke control systems in accordance with Section 909.11.
Emergency power shall be provided for exit signs in accordance with Section 1011.5.3.
Emergency power shall be provided for means of egress illumination in accordance with Section 1006.3.
Standby power shall be provided for elevators that are part of an accessible means of egress in accordance with Section 1007.4.
Standby power shall be provided for horizontal sliding doors in accordance with Section 1008.1.4.3.
Emergency power shall be provided for semiconductor fabrication facilities in accordance with Section 415.8.10.
Standby power shall be provided for auxiliary inflation systems in accordance with Section 3102.8.2. Emergency power shall be provided for exit signs in tents and membrane structures.
Emergency or standby power shall be provided in occupancies with hazardous materials in accordance with Section 414.5.4 and the New York City Fire Code.
Emergency power shall be provided for occupancies with highly toxic or toxic materials in accordance with the New York City Fire Code.
Standby power shall be provided for occupancies with organic peroxides in accordance with the New York City Fire Code.
Emergency power shall be provided for occupancies with silane gas in accordance with the New York City Fire Code.
Standby power shall be provided for voice/alarm communication systems in covered mall buildings in accordance with Section 402.14.
Emergency power shall be provided for doors in Group I-3 occupancies in accordance with Section 408.4.2.
Standby power for elevators, including elevators provided to accommodate ambulance stretchers pursuant to Section 3002.4, shall be provided as set forth in Section 3003.1. Controls, elevator cab light, ventilation and associated equipment required for elevator operation shall be connected to emergency power.
Standby power shall be provided in airport traffic control towers in accordance with Section 412.3.5.
Standby power shall be provided for smokeproof enclosures as required by Section 909.20.6.2 and for pressurized elevator shafts provided in accordance with Section 708.14.2.5.
Emergency and standby power shall be required in those Group B, E and R-1 occupancies specified in this section:
  1. Group B occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest fire department vehicle access having a gross floor area over 15,000 square feet (1393.6 m2) per floor or a total gross floor area of 100,000 square feet (9290.3 m2) or more.
  2. Group E occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest level of Fire Department vehicle access having a gross floor area over 15,000 square feet (1393.6 m2) per floor or a total gross floor area of 100,000 square feet (9290.3 m2) or more.
  3. All Group R-1 occupancies.
With respect to such Occupancy Groups B, E and R-1, the following equipment, where such equipment is required by this code, shall be provided with an emergency power system:
  1. Exit signs and means of egress illumination required by Chapter 10;
  2. Elevator car lighting;
  3. Emergency voice/alarm communications systems, including Fire Department in-building Auxiliary Radio Communication systems (ARCs) provided where required or installed voluntarily in accordance with Section 917;
  4. Automatic fire detection systems;
  5. Fire alarm systems; and
  6. Electrically powered fire pumps, including manual fire pumps, automatic fire pumps and sprinkler booster pumps.
With respect to such Occupancy Groups B, E and R-1, the following equipment, where such equipment is required by this code, shall be provided with a standby power system:
  1. Ventilating systems used for smoke venting or control;
  2. Stair pressurization; and
  3. At least three elevators in a building at one time with manual transfer to other elevators as required by Section 3003.
  4. Power and lighting for the fire command center required by Section 403.4.5.
Emergency and standby power systems shall be maintained and tested in accordance with the New York City Fire Code and New York City Electrical Code.
In addition to any other loads, optional standby power systems shall be capable of providing power to the following systems upon failure of the normal power supply or the emergency or standby power system:
  1. Emergency lighting;
  2. Fire alarm systems; and
  3. Elevators as follows:
    1. For Group R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height, at least one elevator serving all floors, or one elevator per bank where different banks serve different portions of the building; or
    2. For all other buildings having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, at least one elevator that serves all floors.
Linked Resources
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Code Compare
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Bookmarks
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Amendment Styling
P
Amendment styling is not available for this code.