UpCodes logo
Table of contentsContents
The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be in accordance with city department of environmental protection requirements.
All roofs, paved areas, yards, courts and courtyards shall drain into a separate storm sewer system, or a combined sewer system, or to an approved place of disposal. In accordance with city department of environmental protection requirements, an approved system for beneficial collection and use of storm water may be installed in which case overflow from such a system shall be discharged to street storm sewer or street combined sewer.
Whenever an alteration increases impervious surfaces on the lot to greater than 20 percent of the impervious surfaces existing when the structure was constructed, such impervious surfaces shall drain into a storm sewer system, or a combined sewer system, or to an approved place of disposal.

Exception: Where the total area of impervious surfaces proposed to be increased by an alteration after the effective date of this code is less than or equal to 1,000 square feet (93 m2).
Storm water shall not be drained into sewers intended for sewage only.
The conductors and the building storm drain shall be tested in accordance with Section PC 312.
The size of a drainage pipe shall not be reduced in the direction of flow.
All connections and changes in direction of the storm drainage system shall be made with approved drainage-type fittings in accordance with Table 706.3. The fittings shall not obstruct or retard flow in the system.
Roofs shall be designed for the maximum possible depth of water that will pond thereon as determined by the relative levels of roof deck and overflow weirs, scuppers, edges or serviceable drains in combination with the deflected structural elements. In determining the maximum possible depth of water, all primary roof drains shall be assumed to be blocked.
Cleanouts shall be installed in the storm drainage system and shall comply with the provisions of this code for sanitary drainage pipe cleanouts.

Exception: Subsurface drainage system.
Backwater valves installed in a storm drainage system shall conform to Section PC 715.
Backwater valves shall be installed in storm drainage systems in accordance with Section 7.3.4 of ASCE 24 as modified by Appendix G of the New York City Building Code for all buildings located in the areas of special flood hazard, as established by Section G102.2 of Appendix G of the New York City Building Code.
*Section PC 1101.9.1 was added by: Local Law 83 of 2013 — Update Page #78. This law has an effective date of December 31, 2013.
Plastic piping and fittings shall not be used.
Exceptions:
  1. Plastic piping and fittings may be used in residential buildings five stories or less in height.
  2. Corrugated polyethylene piping and fittings, with a diameter of twelve inches (305 mm) or more may be used in connection with any type of building for underground yard drainage and storm water piping when used outside of the foundation wall of the building and not connecting to any piping system from the interior of the building.
Except as otherwise permitted by this code, no person shall perform site grading or land contour work, as defined in section 19-146 of the Administrative Code, which work would causes storm water to flow across sidewalks or onto an adjacent property.
The materials and methods utilized for the construction and installation of storm drainage systems shall comply with this section and the applicable provisions of Chapter 7.
Inside storm drainage conductors installed above ground shall conform to one of the standards listed in Table 702.1.
Underground building storm drain pipe shall conform to one of the standards listed in Table 702.2.
Building storm sewer pipe shall conform to one of the standards listed in Table 1102.4.

TABLE 1102.4
BUILDING STORM SEWER PIPE
MATERIAL STANDARD
Cast-iron pipe ASTM A 74; ASTM A 888;
CISPI 301
Concrete pipe ASTM C 14; ASTM C 76;
CAN/CSA A257.1M;
CAN/CSA A257.2M
Ductile-iron pipe AWWA C151
High density polyethylene
pipe (HIPE)a
ASTM D 3350
Nonasbestos fiber-cement pipe ASTM C 1449
Polyvinyl chloride (PVC)
plastic pipe (Type DWV,
SDR26, SDR35, SDR41, PS50
or PS100)
ASTM D 2665; ASTM D
3034; ASTM F 891; CSA
B182.2; CAN/CSA B182.4
Vitrified clay pipe ASTM C 4; ASTM C 700
Stainless steel drainage
systems, Type 31 6L
ASME A112.3.1
a. Approved plastic sewer for piping 12 inc hes and larger
Subsoil drains shall be open-jointed, horizontally split or perforated pipe conforming to one of the standards listed in Table 1102.5.

TABLE 1102.5
SUBSOIL DRAIN PIPE
MATERIAL STANDARD
Cast-iron pipe ASTM A 74; ASTM A 888;
CISPI 301
Polyethylene (PE) plastic pipe ASTM F 405
Polyvinyl chloride (PVC)

   Plastic pipe (type sewer pipe,
   PS25, PS50 or PS100)
ASTM D 2729; ASTM F
891; CSA-B 182.2;
CAN/CSA-B182.4
Porous concrete pipe ASTM C 654
Vitrified clay pipe ASTMC 4; ASTM C 700
Stainless steel drainage
systems, Type 316L
ASME A112.3.1
Roof drains shall conform to ASME A112.21.2M or ASME A112.3.1.
Pipe fittings shall be approved for installation with the piping material installed, and shall conform to the respective pipe standards or one of the standards listed in Table 1102.7. The fittings shall not have ledges, shoulders or reductions capable of retarding or obstructing flow in the piping. Threaded drainage pipe fittings shall be of the recessed drainage type.

TABLE 1102.7
PIPE FITTINGS
MATERIAL STANDARD
Cast-iron ASME B16.4; ASME
b16.12; ASTM A 888;
CISPI 301; ASTM A 74
Chlorinated polyvinyl chloride
(CPVC) plastic
ASTM F 437; ASTM F
438; ASTM F 439
Gray iron andductile iron AWWA C110
High-density polyethylene
(HDPE)
ASTM D 3350
Malleable iron ASME B16.3
Plastic, general ASTM F 409
Polyethylene (PE) plastic ASTM D 2609
Polyvinyl chloride (PVC)
plastic
ASTM D 2464; ASTM D
2466; ASTM D 2467;
CSA-B137.2; ASTM D
2665; ASTM F 1866
Steel ASME B16.9; ASME
B16.11; ASME B16.28
Stainless steel drainage
Systems, Type 316L
ASME A112.3.1
Leaders and storm drains connected to a combined sewer shall be trapped. Individual storm water traps shall be installed on the storm water drain branch serving each conductor, or a single trap shall be installed in the main storm drain just before its connection with the combined building sewer or the public sewer. A hooded catch basin located within the street line shall be the equivalent of a building house trap for the connection to a street combined sewer.
Storm water traps shall be of the same material as the piping system to which they are attached.
Traps for individual conductors shall be the same size as the horizontal drain to which they are connected.
An accessible cleanout shall be installed on the building side of the trap.
Conductor pipes shall not be used as soil, waste or vent pipes, and soil, waste or vent pipes shall not be used as conductors.
The sanitary and storm drainage systems of a structure shall be entirely separate except for minor modifications to existing buildings having combined systems. Where a combined building drain is utilized, the building storm drain shall be connected in the same horizontal plane through a single-wye fitting to the combined sewer at least 10 feet (3048 mm) downstream from any soil stack. If a separate city storm sewer is not available, building sanitary drains shall be separate and shall only be permitted to connect to common building combined sewer downstream of building house trap.
Drains carrying clear water, i.e. air conditioning drips, pump drips, cooling water, etc. may discharge into the storm water drainage system through an indirect waste connection discharging into a trapped funnel or raised lip floor drain.
Roof drains shall have strainers extending not less than 4 inches (102 mm) above the surface of the roof immediately adjacent to the roof drain. Strainers shall have an available inlet area, above roof level, of not less than one and one-half times the area of the conductor or leader to which the drain is connected.
Roof drain strainers for use on sun decks, parking decks and similar areas that are normally serviced and maintained shall comply with Section 1105.1 or shall be of the flat-surface type, installed level with the deck, with an available inlet area not less than two times the area of the conductor or leader to which the drain is connected.
The connection between roofs and roof drains which pass through the roof and into the interior of the building shall be made water tight by the use of approved flashing material.
The size of the vertical conductors and leaders, gutters, building storm drains, building storm sewers, and any horizontal branches of such drains or sewers shall be based on the 100-year hourly rainfall rate of 3 inches (76 mm) per hour. Sizing for secondary and combined primary and secondary conductors, leaders and drains shall be in accordance with Section PC 1107.
Vertical conductors and leaders shall be sized for the maximum projected roof area, in accordance with Table 1106.2.

TABLE 1106.2
SIZE OF VERTICAL CONDUCTORS AND LEADERS
DIAMETER OF LEADER
(inches)a
HORIZONTALLY PROJECTED
ROOF AREA (square feet)
Rainfall rate (inches per hour)
3
2 960
3 2,930
4 6,130
5 11,530
6 17.995
8 38,660
For SI: 1 inch = 25.4 m m, 1 square foot = 0.0929m2.
  1. Sizes indicated are the diameter of circular piping. This table is applicable to piping of other shapes provided the cross-sectional shape fully encloses a circle of the diameter indicated in this table.
The size of the building storm drain, building storm sewer and their horizontal branches having a slope of one-half unit or less vertical in 12 units horizontal (4 percent slope) shall be based on the maximum projected roof area in accordance with Table 1106.3. The minimum slope of horizontal branches shall be one-eighth unit vertical in 12 units horizontal (1 percent slope) unless otherwise approved.

TABLE 1106.3
SIZE OF HORIZONTAL STORM DRAINGE PIPING
SIZE OF
HORIZONTAL PIPING
(inches)
HORIZONTALLY PROJECTED ROOF AREA
(square feet)
Rainfall rate (inches per hour)
3 6
1/8 Unit vertical in 12 units horizontal (1-percent slope)
3
4
5
6
8
10
12
15
1,096
2,506
4,453
7,133
15,330
27,600
44,400
72,800
548
1,253
2,227
3,566
7,600
13,800
22,200
39,650
1/4 unit vertical in 12 units horizontal (2-percent slope)
3
4
5
6
8
10
12
15
1,546
3,533
6,293
10,066
21,733
38,950
62,600
112,00
773
1,766
3,146
5,033
10,866
19,450
31,350
56,000
1/2 unit vertical in 12 units horizontal (4-percent slope)
3
4
5
6
8
10
12
15
2,295
5,010
8,900
13,700
30,650
55,200
88,800
158,800
1,096
2,500
4,450
7,140
15,320
27,600
44,400
79,250
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2
In sizing roof drains and storm drainage piping, one-half of the area of any vertical wall that diverts rainwater to the roof shall be added to the projected roof area for inclusion in calculating the required size of vertical conductors, leaders and horizontal storm drainage piping.
Parapet wall roof drainage scupper and overflow scupper location shall comply with the requirements of the New York city building code.
The size of semicircular gutters shall be based on the maximum projected roof area in accordance with Table 1106.6.

TABLE 1106.6
SIZE OF SEMICIRCULAR ROOF GUTTERS
DIAMETER OF GUTTERS
(inches)
HORIZONTALLY PROJECTED
ROOF AREA (square feet)
Rainfall rate (inches per hour)
3
1/16 unit vertical in 12 units horizontal (0.5-percent slope)
3
4
5
6
7
8
10
226
480
834
1,280
1,840
2,655
4,800
1/8 unit vertical 12 units horizontal (1-percent slope)
3
4
5
6
7
8
10
320
681
1,172
1,715
2,600
3,740
6,800
1/4 unit vertical in 12 units horizontal (2-percent slope)
3
4
5
6
7
8
10
454
960
1,668
2,560
3,860
5,310
9,600
1/2 unit vertical in 12 units horizontal (4-percent)
3
4
5
6
7
8
10
640
1,360
2,360
3,695
5,200
7,460
13,330
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929m2.
Secondary (emergency) roof drains or scuppers shall be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason. The inlet elevation of secondary (overflow) drains and the invert elevation of overflow scuppers should be not less than 2 inches (51 mm) or more than 4 inches (102 mm) above the low point of the (adjacent to) roof surface unless a safer water depth loading, including the required hydraulic head to maintain required flow rate out of the overflow drainage system that has been determined by the structural design.
Where practical secondary roof drain systems shall have the end point of discharge separate from the primary system. Discharge shall be above grade, in a location which would normally be observed by the building occupants or maintenance personnel. Where separate systems are impractical and to prevent water from flowing over sidewalk or pedestrian walkways, secondary drainage system may tie into the primary drainage system in the vertical conductors.
Secondary (emergency) roof drain systems shall be sized in accordance with Section PC 1106 based on the rainfall rate of 3 inches (76 mm) per hour. Scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by Section 1101.7. Scuppers shall not have an opening dimension of less than 4 inches (102 mm). Where secondary drainage systems tie into primary drainage systems, the combined primary and secondary system shall be sized based on their combined rainfall rate of 6 inches (152 mm) per hour.
The size of a combination sanitary and storm drain or sewer shall be computed in accordance with the method in Section 1106.3. The fixture units shall be converted into an equivalent projected roof or paved area. Where the total fixture load on the combined drain is less than or equal to 256 fixture units, the equivalent drainage area in horizontal projection shall be taken as 1333 square feet (124 m2). Where the total fixture load exceeds 256 fixture units, each additional fixture unit shall be considered the equivalent of 5.2 square feet (0.48 m2) of drainage area. These values are based on a rainfall rate of 3 inch (75 mm) per hour.
Where there is a continuous or semicontinuous discharge into the building storm drain or building storm sewer, such as from a pump, ejector, air conditioning plant or similar device, each gallon per minute of such discharge shall be computed as being equivalent to 32 square feet (2.97 m2) of roof area, based on a rainfall rate of 3 inches (75 mm) per hour.
The roof of a structure shall be designed for the storage of water where the storm drainage system is engineered for controlled flow. The controlled flow roof drain system shall be an engineered system in accordance with this section and Section 28—113.2.2 of the Administrative Code. The controlled flow system shall be designed based on the design rainfall rate in accordance with Section 1106.1.
The control devices shall be installed so that the rate of discharge of water per minute shall not exceed the values for continuous flow as indicated in Section 1109.1.
Runoff control shall be by control devices. Control devices shall be protected by strainers.
Not less than two roof drains shall be installed in roof areas 10,000 square feet (929 m2) or less and not less than four roof drains shall be installed in roofs over 10,000 square feet (929 m2) in area.
Subsoil drains shall be open-jointed, horizontally split or perforated pipe conforming to one of the standards listed in Table 1102.5. Such drains shall not be less than 4 inches (102 mm) in diameter. Where the building is subject to backwater, the subsoil drain shall be protected by an accessibly located backwater valve. Where subsoil drainage is discharged into a public sewer, the sub-soil drains shall discharge into a readily accessible silt and sand interceptor before being connected into the gravity drainage or sump system. Subsoil drainage shall discharge to a trapped area drain, sump, dry well or approved location above ground. The subsoil sump shall not be required to have either a gas-tight cover or a vent. The sump and pumping system shall comply with Section 1113.1.
Building subdrains located below the public sewer level shall discharge into a sump or receiving tank, the contents of which shall be automatically lifted and discharged into the drainage system as required for building sumps. The sump and pumping equipment shall comply with Section 1113.1.
The sump pump, pit and discharge piping shall conform to Sections 1113.1.1 through 1113.1.4.
The sump pump shall be of a capacity and head appropriate to anticipated use requirements.
The sump pit shall not be less than 18 inches (457 mm) in diameter and 24 inches (610 mm) deep, unless otherwise approved. The pit shall be accessible and located such that all drainage flows into the pit by gravity. The sump pit shall be constructed of tile, steel, plastic, cast-iron, concrete or other approved material, with a removable cover adequate to support anticipated loads in the area of use. The pit floor shall be solid and provide permanent support for the pump.
Electrical service outlets, when required, shall meet the requirements of the New York city electrical code.
Discharge piping shall meet the requirements of Section 1102.2, 1102.3 or 1102.4 and shall include a gate valve and a full flow check valve. Pipe and fittings shall be the same size as, or larger than, pump discharge tapping.

Exception: In one- and two-family dwellings, only a check valve shall be required, located on the discharge piping from the pump or ejector.