Heads up: There are no amended sections in this chapter.
Figures A-1 through A-4 are illustrations of appliances located in confined spaces.


FIGURE A-1 ALL AIR FROM INSIDE THE BUILDING
NOTE: Each opening shall have a free area of not less than 1 square inch per 1,000 Btu per hour of the total input rating of all appliances in the enclosure and not less than 100 square inches.
For SI: 1 square inch = 645 mm2, 1 British thermal unit per hour = 0.2931 W.



FIGURE A-2 ALL AIR FROM OUTDOORS—INLET AIR FROM VENTILATED CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC
NOTE: The inlet and outlet air openings shall each have a free area of not less than 1 square inch per 4,000 Btu per hour of the total input rating of all appliances in the enclosure.
For SI: 1 square inch = 645 mm2, 1 British thermal unit per hour = 0.2931 W.



FIGURE A-3 ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC
NOTE: The inlet and outlet air openings shall each have a free area of not less than 1 square inch per 4,000 Btu per hour of the total input rating of all appliances in the enclosure.
For SI: 1 foot = 304.8 mm, 1 square inch = 645 mm2, 1 British thermal unit per hour = 0.2931 W.



FIGURE A-4 ALL AIR FROM OUTDOORS THROUGH HORIZONTAL DUCTS OR DIRECT OPENINGS
NOTE: Each air duct opening shall have a free area of not less than 1 square inch per 2,000 Btu per hour of the total input rating of all appliances in the enclosure. If the appliance room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of not less than 1 square inch per 4,000 Btu per hour or the total input rating of all appliances in the enclosure.
For SI: 1 foot = 304.8 mm, 1 square inch = 645 mm2, 1 British thermal unit per hour = 0.2931 W.



For SI: 1 foot = 304.8 mm, 1 square inch = 645 mm2, 1 British thermal unit per hour = 0.2931 W.

NOTE:The air duct or direct opening shall have a free area of not less than 1 square inch per 3,000 Btu/h (734mm2/kW) of the total input rating of all appliances in the enclosure.
FIGURE A-4.1
ALL AIR FROM OUTDOORS THROUGH A SINGLE DUCT OR DIRECT OPENING


FIGURE A-5
CHIMNEY CONNECTOR SYSTEMS
For SI: 1 inch = 25.4 mm.

FIGURE A-5—continued
CHIMNEY CONNECTOR SYSTEMS
For SI: 1 inch = 25.4 mm