  1. Each waste stack shall be vented by a stack vent that is the same size as the waste stack.
  2. Offsets shall be permitted in stack vents for waste stacks above the connection of the top-most fixture on the stack.
See Figure 12.19.6
Figure 12.19.6
WASTE STACK VENTING