CODE SNIPPET
12.19.6 Waste Stack Vents
Go To Full Code Chapter
- Each waste stack shall be vented by a stack vent that is the same size as the waste stack.
- Offsets shall be permitted in stack vents for waste stacks above the connection of the top-most fixture on the stack.
See Figure 12.19.6

Figure 12.19.6
WASTE STACK VENTING
WASTE STACK VENTING
Related Code Sections
12.19 Vents and Venting, Waste Stack Venting
, drinking fountains, floor drains, and similar fixtures shall be permitted to be vented by a waste stack that is sized and installed in accordance ...
12.19 Vents and Venting, Waste Stack Venting
, drinking fountains, floor drains, and similar fixtures shall be permitted to be vented by a waste stack that is sized and installed in accordance ...
12.19.6 Vents and Venting, Waste Stack Vents
Each waste stack shall be vented by a stack vent that is the same size as the waste stack. Offsets shall be permitted in stack vents for waste ...
12.19.6 Vents and Venting, Waste Stack Vents
Each waste stack shall be vented by a stack vent that is the same size as the waste stack. Offsets shall be permitted in stack vents for waste ...