CODES

ADOPTS WITHOUT AMENDMENTS:

International Fire Code 2015 (IFC 2015)

Copyright

Preface

Effective Use of the International Fire Code

Legislation

Chapter 1 Scope and Administration

Chapter 2 Definitions

Chapter 3 General Requirements

Chapter 4 Emergency Planning and Preparedness

Chapter 5 Fire Service Features

Chapter 6 Building Services and Systems

Chapter 7 Fire and Smoke Protection Features

Chapter 8 Interior Finish, Decorative Materials and Furnishings

Chapter 9 Fire Protection Systems

Chapter 10 Means of Egress

Chapter 11 Construction Requirements for Existing Buildings

Chapter 12 through 19

Chapter 20 Aviation Facilities

Chapter 21 Dry Cleaning

Chapter 22 Combustible Dust-Producing Operations

Chapter 23 Motor Fuel-Dispensing Facilities and Repair Garages

Chapter 24 Flammable Finishes

Chapter 25 Fruit and Crop Ripening

Chapter 26 Fumigation and Insecticidal Fogging

Chapter 27 Semiconductor Fabrication Facilities

Chapter 28 Lumber Yards and Agro-Industrial, Solid Biomass and Woodworking Facilities

Chapter 29 Manufacture of Organic Coatings

Chapter 30 Industrial Ovens

Chapter 31 Tents and Other Membrane Structures

Chapter 32 High-Piled Combustible Storage

Chapter 33 Fire Safety During Construction and Demolition

Chapter 34 Tire Rebuilding and Tire Storage

Chapter 35 Welding and Other Hot Work

Chapter 36 Marinas

Chapter 37 Combustible Fibers

Chapter 38 through 49

Chapter 50 HAZARDOUS MATERIALS—GENERAL PROVISIONS

Chapter 51 Aerosols

Chapter 52 Reserved

Chapter 53 Compressed Gases

Chapter 54 Corrosive Materials

Chapter 55 Cryogenic Fluids

Chapter 56 Explosives and Fireworks

Chapter 57 Flammable and Combustible Liquids

Chapter 58 Flammable Gases and Flammable Cryogenic Fluids

Chapter 59 Flammable Solids

Chapter 60 Highly Toxic and Toxic Materials

Chapter 61 Liquefied Petroleum Gases

Chapter 62 Organic Peroxides

Chapter 63 Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids

Chapter 64 Pyrophoric Materials

Chapter 65 Pyroxylin (Cellulose Nitrate) Plastics

Chapter 66 Unstable (Reactive) Materials

Chapter 67 Water-Reactive Solids and Liquids

Chapter 68 through 79

Chapter 80 Referenced Standards

Appendix A Board of Appeals

Appendix B Fire-Flow Requirements for Buildings

Appendix C Fire Hydrant Locations and Distribution

Appendix D Fire Apparatus Access Roads

Appendix E Hazard Categories

Appendix F Hazard Ranking

Appendix G Cryogenic Fluids - Weight and Volume Equivalents

Appendix H Hazardous Materials Management Plan (Hmmp) and Hazardous Materials Inventory Statement (Hmis) Instructions

Appendix I Fire Protection Systems - Noncompliant Conditions

Appendix J Building Information Sign

Appendix K Construction Requirements for Existing Ambulatory Care Facilities

Appendix L Requirements for Fire Fighter Air Replenishment Systems

Appendix M HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKLER REQUIREMENT

The storage and use of unstable (reactive) materials shall be in accordance with this chapter. Compressed gases shall also comply with Chapter 53.

Exceptions:

1. Display and storage in Group M and storage in Group S occupancies complying with Section 5003.11.

2. Detonable unstable (reactive) materials shall be stored in accordance with Chapter 56.
Permits shall be required as set forth in Section 105.6.
The following term is defined in Chapter 2:

UNSTABLE (REACTIVE) MATERIAL.

Class 4.

Class 3.

Class 2.

Class 1.
Quantities of unstable (reactive) materials not exceeding the maximum allowable quantity per control area shall be in accordance with Sections 6603.1.1 through 6603.1.2.5.
The storage and use of unstable (reactive) materials in amounts not exceeding the maximum allowable quantity per control area indicated in Section 5003.1 shall be in accordance with Sections 5001, 5003, 6601 and 6603.
The indoor storage of unstable (reactive) materials shall be in accordance with Sections 6603.1.2.1 through 6603.1.2.5.
In Group A, E, I or U occupancies, any amount of Class 3 and 4 unstable (reactive) materials shall be stored in accordance with the following:

1. Class 3 and 4 unstable (reactive) materials shall be stored in hazardous material storage cabinets complying with Section 5003.8.7.

2. The hazardous material storage cabinets shall not contain other storage.
Class 3 and 4 unstable (reactive) materials shall not be stored or used within Group R occupancies.
Class 4 unstable (reactive) materials shall not be stored or used in retail sales portions of Group M occupancies.
Class 3 and 4 unstable (reactive) materials shall not be stored or used in offices of Group B, F, M or S occupancies.
In classrooms in Group B, F or M occupancies, any amount of Class 3 and 4 unstable (reactive) materials shall be stored in accordance with the following:

1. Class 3 and 4 unstable (reactive) materials shall be stored in hazardous material storage cabinets complying with Section 5003.8.7.

2. The hazardous material storage cabinets shall not contain other storage.
The storage and use of unstable (reactive) materials in amounts exceeding the maximum allowable quantity per control area indicated in Section 5003.1 shall be in accordance with Chapter 50 and this chapter.
Indoor storage of unstable (reactive) materials in amounts exceeding the maximum allowable quantity per control area indicated in Table 5003.1.1(1) shall be in accordance with Sections 5001, 5003, 5004 and this chapter.

In addition, Class 3 and 4 unstable (reactive) detonable materials shall be stored in accordance with the International Building Code requirements for explosives.
Storage of unstable (reactive) materials shall be in detached buildings when required in Section 5003.8.2.
Indoor storage rooms, areas and buildings containing Class 3 or 4 unstable (reactive) materials shall be provided with explosion control in accordance with Section 911.
In addition to Section 5004.12, floors of storage areas for liquids and solids shall be of liquid-tight construction.
Unstable (reactive) materials stored in quantities greater than 500 cubic feet (14 m3) shall be separated into piles, each not larger than 500 cubic feet (14 m3). Aisle width shall not be less than the height of the piles or 4 feet (1219 mm), whichever is greater.

Exception: Materials stored in tanks.
Unstable (reactive) materials shall not be stored in basements.
Outdoor storage of unstable (reactive) materials in amounts exceeding the maximum allowable quantities per control area indicated in Table 5003.1.1(3) shall be in accordance with Sections 5001, 5003, 5004 and this chapter.
Outdoor storage of Class 4 or 3 (detonable) unstable (reactive) material shall be in accordance with Table 5604.5.2(2). The number of pounds of material listed in the table shall be the net weight of the material present. Alternatively, the number of pounds of material shall be based on a trinitrotoluene (TNT) equivalent weight.
Outdoor storage of deflagratable Class 3 unstable (reactive) materials shall be in accordance with Table 5604.5.2(3). The number of pounds of material listed shall be the net weight of the material present.
Outdoor storage of Class 2 or 1 unstable (reactive) materials shall not be located within 20 feet (6096 mm) of buildings not associated with the manufacture or distribution of such materials, lot lines, public streets, public alleys, public ways or means of egress. The minimum required distance shall not apply when fire barriers without openings or penetrations having a minimum fire-resistance rating of 2 hours interrupt the line of sight between the storage and the exposure. The fire barrier shall either be an independent structure or the exterior wall of the building adjacent to the storage area.
Piles of unstable (reactive) materials shall not exceed 1,000 cubic feet (28 m3).
Aisle widths between piles shall not be less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.
The use of unstable (reactive) materials in amounts exceeding the maximum allowable quantity per control area indicated in Table 5003.1.1(1) or 5003.1.1(3) shall be in accordance with Sections 5001, 5003, 5005 and this chapter.
Resources