The design, construction, operation, and maintenance of soundstages and approved production facilities used
in motion picture and television industry productions shall
comply with NFPA 140 and Chapter 32.
Permits, where required, shall comply with
Section 1.12.
Where required by the AHJ, a permit shall be obtained
for any of the following activities:
- Use of pyrotechnic special effects
- Use of open flames
- Welding
- Use of flammable or combustible liquids or gases
- Use of aircraft
- Presence of motor vehicles within a building
- Productions with live audiences
- Change of use or change of occupancy classification [140:4.2]
- Use of the site as a production location [140:5.2]
Where required by the AHJ, a fire watch shall be provided for soundstages and approved production facilities where
pyrotechnic special effects are used. [140:4.4.1]
A fire watch shall be required for production locations
where pyrotechnic special effects are used, unless otherwise
waived by the AHJ. [140:5.4.1]
Where required by the AHJ, standby
fire personnel shall be provided for hazardous operations,
other than pyrotechnic special effects. [140:4.4.2] [140:5.4.2]
Foamed plastic materials used for decorative purposes,
scenery, sets, or props shall have a heat release rate not exceeding 100 kW where tested in accordance with UL 1975, Standard
for Fire Tests for Foamed Plastics Used for Decorative Purposes, or
where tested in accordance with NFPA 289 using the 20 kW
ignition source. [140:4.5.1] [140:5.5]
Combustible drapes, drops, and any other similar
combustible hangings or vertically placed materials shall
comply with one of the following options:
- The materials meet the requirements of NFPA 701.
- The materials exhibit a heat release rate not exceeding 100 kW when tested in accordance with NFPA 289 using the 20 kW ignition source.
- The materials are present in such limited quantity that a hazard of fire development or spread is minimal.
- The materials are considered by the AHJ to exhibit acceptable fire performance.
- Approved interim measures are provided for the period during which the combustible materials are present. [140:4.5.2]
Cut greens shall be treated with an approved or listed
fire retardant, and the process shall be repeated as often as
necessary to maintain its effectiveness. [140:4.5.3]
Smoking shall be prohibited on soundstages and in
approved production facilities unless otherwise provided in
32.5.2 or 32.5.3. [140:4.6.1] [140:5.6.1]
Smoking shall be permitted when it is a necessary part
of a performance, and only when the smoker is a member of
the cast. [140:4.6.2] [140:5.6.2]
Except where prohibited by the AHJ, smoking shall be
permitted where all of the following conditions are met:
- The smoking area is outdoors.
- Hazardous materials are not present.
- Approved ash trays or receivers are provided. [140:4.6.3] [140:5.6.3]
The use of pyrotechnic special effects and open flames
shall be subject to the approval of the AHJ. [140:4.3.1]
[140:5.3.1]
When an audience is present, NFPA 1126 shall be used
to regulate any pyrotechnic use. [140:4.3.2] [140:5.3.2]
When an audience is present, NFPA 160 shall be used
to regulate any flame effects use. [140:4.3.3] [140:5.3.3]
Fire department access shall
be maintained as required by the AHJ. [140:4.9] [140:5.9]
Soundstages and approved production
facilities shall maintain housekeeping in accordance with Chapters 10 and 19 where applicable.
Section 32.9 shall apply to new and existing
motion picture and television soundstages and approved
production facilities. [140:4.1]
Electrical equipment shall be in accordance with
Section 11.1. [140:4.8.1]
Soundstages and approved production facilities shall
be provided with a minimum of 35 W/ft2 (377 W /m2) dedicated for production lighting and power. [140:4.8.2]
The electrical distribution equipment used shall comply with UL 1640, Portable Power-Distribution Equipment, and the provisions of Article 530 of NFPA 70. [140:4.8.3]
The wiring method to electrical distribution equipment shall comply with the provisions of Article 530 of
NFPA 70. [140:4.8.4]
The location of portable, mobile, or stationary powergenerating equipment shall be subject to the approval of the
AHJ. [140:4.8.5]
Exterior penetrations shall be located near the
predesignated location for portable and mobile powergenerating equipment. [140:4.8.6]
Auxiliary power cables supplied from mobile generators or adjacent buildings shall not be routed through fire-rated windows and doors. [140:4.8.7]
Portable feeder cables shall be permitted to temporarily penetrate fire-rated walls, floors, or ceilings provided that all of the following apply:
- The opening is of noncombustible material.
- When in use, the penetration is sealed with a temporary seal of a listed firestop material.
- When not in use, the opening shall be capped with a material of equivalent fire rating.
Where the penetration utilizes a conduit, metal-threaded caps shall be attached to the pipe by means of chain
or cable and shall effectively cap the conduit when not in use.
[140:4.8.9]
The lighting equipment used shall comply with
UL 1573, Stage and Studio Luminaires and Connector Strips, and
the provisions of Article 530 of NFPA 70. [140:4.8.10]
Means of egress shall be in accordance with
NFPA 101 unless otherwise modified by 32.9.3.2 through
32.9.3.6. [140:4.10.1]
The maximum travel distance to an exit within the
soundstage shall be 150 ft (45 m). [140:4.10.2]
Soundstages and approved production facilities shall
have an aisle along the perimeter of the soundstage or facility
as approved by the AH] unless otherwise provided in 32.9.3.3.2.
[140:4.10.3]
A clear unobstructed aisle height of 7 ft (2.1 m)
shall be maintained. [140:4.10.3.1]
A soundstage or approved production facility with a
gross area not exceeding 1500 ft2 (139 m2) shall be exempt
from the perimeter aisle requirement of 32.9.3.3 provided
there is a minimum of two means of egress. [140:4.10.3.2]
Any door in a required means of egress from an area
having an occupant load of 100 or more persons shall be
permitted to be provided with a latch or lock only if it is panic
hardware or fire exit hardware. [140:4.10.5]
Means of egress shall be kept clear of obstructions
and tripping hazards. [140:4.10.6]
The automatic sprinkler system required by
32.9.4.1.2 shall be installed in accordance with Section 13.3
unless otherwise provided in 32.9.4.1.3.1 or 32.9.4.1.3.2.
[140:4.11.1.3]
The requirements of NFPA 13 prohibiting
obstructions to sprinkler discharge shall not be applicable if
approved mitigation is employed. [140:4.11.1.3.1]
The requirements of NFPA 13 prohibiting
obstructions to sprinkler discharge shall not be applicable if
the building sprinkler system meets the design criteria for
Extra Hazard, Group 2. [140:4.11.1.3.2]
The automatic sprinkler system required by
32.9.4.1.2 shall be maintained in accordance with 13.3.3.
[140:4.11.1.4]
Portable fire extinguishers shall be installed and
maintained in accordance with Section 13.6. [140:4.11.1.5]
Fire alarm system notification
appliances within soundstages and approved production facilities shall be permitted to be deactivated with the approval of
the AHJ during videotaping, filming, or broadcasting of
programs, provided the following conditions exist:
- In the event of alarm system activation, notification appliances shall activate at a location that is constantly attended during the videotaping, filming, or broadcasting of programs.
- The attendants of the location identified in 32.9.4.2(1) shall be provided with a means of communicating with the fire command center for the building, where one is provided, and with the occupants of the soundstage to initiate emergency action.
- Deactivation of notification appliances shall cause activation of a visual signal at an approved location, which shall remain illuminated while notification appliances on the soundstage are deactivated.
- The visual signal shall be identified by a sign that shall read, "When Illuminated, Soundstage Fire Alarm System Notification Appliances Are Deactivated."
Airconditioning, heating, and ventilating ductwork and related equipment shall be in good working order and in compliance with the requirements of the AHJ. [140:4.12]
Auxiliary power cables supplied from mobile
generators or adjacent buildings shall be permitted to be
routed through fire-rated windows and doors with the approval
of the AHJ. [140:5.8.3]
The production location shall be
provided with means of egress appropriate for the intended use
as approved by the AHJ. [140:5.10]
Building areas used as production locations shall
be designed, constructed, and maintained to protect the occupants not intimate with the initial fire development for the
time needed to evacuate, relocate, or defend in place.
[140:5.11.1]
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if approved
mitigation is employed. [140:5.11.4]
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design criteria for Extra Hazard,
Group 2. [140:5.11.5]
Waste or refuse shall not be
allowed to accumulate in any area or in any manner that
creates a fire hazard. [140:6.1]
The use, mixing, dispensing, and storage of flammable or combustible liquids shall be in accordance with this
Code and Chapter 66 and Chapter 69, as applicable, unless
otherwise permitted by 32.10.4.2.2. [140:6.2.1]
Approved flammable or combustible liquids and
liquefied petroleum gases used for special effects shall be
permitted. [140:6.2.2]
Welding shall be in accordance with
NFPA 51 and Chapter 41. [140:6.3]
When an audience is present during productions, provisions for life safety and means of egress shall be subject to the approval of the AHJ. [140:6.4]