ADOPTS WITH AMENDMENTS:

International Wildland-Urban Interface Code 2015 (IWUIC 2015)

Heads up: There are no amended sections in this chapter.
Wildland-urban interface areas shall be provided with emergency vehicle access and water supply in accordance with this chapter.
The objective of this chapter is to establish the minimum requirements for emergency vehicle access and water supply for buildings and structures located in the wildland-urban interface areas.
General safety precautions shall be in accordance with this chapter. See also Appendix A.
Subdivisions shall comply with Sections 402.1.1 and 402.1.2.

402.1.1 Access

AMENDMENT
This section has been amended at the state or city level.
New subdivisions, as determined by this jurisdiction, shall be provided with fire apparatus access roads in accordance with the International Fire Code.

402.1.2 Water Supply

AMENDMENT
This section has been amended at the state or city level.
New subdivisions as determined by this jurisdiction shall be provided with water supply in accordance with the International Fire Code.
Individual structures shall comply with Sections 402.2.1 and 402.2.2.

402.2.1 Access

AMENDMENT
This section has been amended at the state or city level.
Individual structures hereafter constructed or relocated into or within wildland-urban interface areas shall be provided with fire apparatus access in accordance with the International Fire Code.

402.2.2 Water Supply

AMENDMENT
This section has been amended at the state or city level.
Individual structures hereafter constructed or relocated into or within wildland-urban interface areas shall be provided with a conforming water supply in accordance with the International Fire Code.
Exceptions:
  1. Structures constructed to meet the requirements for the class of ignition-resistant construction specified in Table 503.1 for a nonconforming water supply.
  2. Buildings containing only private garages, carports, sheds and agricultural buildings with a floor area of not more than 600 square feet (56 m2).

402.3 Existing Conditions

AMENDMENT
This section has been amended at the state or city level.
Existing address markers, roads and fire protection equipment shall be in accordance with the International Fire Code.

Section 403 Access

AMENDMENT
This section has been amended at the state or city level.

403.1 Restricted Access

AMENDMENT
This section has been amended at the state or city level.

403.2 Driveways

AMENDMENT
This section has been amended at the state or city level.

403.2.1 Dimensions

AMENDMENT
This section has been amended at the state or city level.

403.2.2 Length

AMENDMENT
This section has been amended at the state or city level.

403.2.3 Service Limitations

AMENDMENT
This section has been amended at the state or city level.

403.2.4 Turnarounds

AMENDMENT
This section has been amended at the state or city level.

403.2.5 Turnouts

AMENDMENT
This section has been amended at the state or city level.

403.2.6 Bridges

AMENDMENT
This section has been amended at the state or city level.

403.3 Fire Apparatus Access Road

AMENDMENT
This section has been amended at the state or city level.

403.4 Marking of Roads

AMENDMENT
This section has been amended at the state or city level.

403.4.1 Sign Construction

AMENDMENT
This section has been amended at the state or city level.

403.5 Marking of Fire Protection Equipment

AMENDMENT
This section has been amended at the state or city level.

403.6 Address Markers

AMENDMENT
This section has been amended at the state or city level.

403.6.1 Signs Along One-Way Roads

AMENDMENT
This section has been amended at the state or city level.

403.6.2 Multiple Addresses

AMENDMENT
This section has been amended at the state or city level.

403.6.3 Single Business Sites

AMENDMENT
This section has been amended at the state or city level.

403.7 Grade

AMENDMENT
This section has been amended at the state or city level.

Section 404 Water Supply

AMENDMENT
This section has been amended at the state or city level.

404.1 General

AMENDMENT
This section has been amended at the state or city level.

404.2 Water Sources

AMENDMENT
This section has been amended at the state or city level.

404.3 Draft Sites

AMENDMENT
This section has been amended at the state or city level.

404.3.1 Access

AMENDMENT
This section has been amended at the state or city level.

404.3.2 Pumper Access Points

AMENDMENT
This section has been amended at the state or city level.

404.4 Hydrants

AMENDMENT
This section has been amended at the state or city level.

404.5 Adequate Water Supply

AMENDMENT
This section has been amended at the state or city level.

404.6 Fire Department

AMENDMENT
This section has been amended at the state or city level.

404.7 Obstructions

AMENDMENT
This section has been amended at the state or city level.

404.8 Identification

AMENDMENT
This section has been amended at the state or city level.

404.9 Testing and Maintenance

AMENDMENT
This section has been amended at the state or city level.

404.10 Reliability

AMENDMENT
This section has been amended at the state or city level.

404.10.1 Objective

AMENDMENT
This section has been amended at the state or city level.

404.10.2 Clearance of Fuel

AMENDMENT
This section has been amended at the state or city level.

404.10.3 Standby Power

AMENDMENT
This section has been amended at the state or city level.
Where required by the code official, a fire protection plan shall be prepared.
The plan shall be based upon a site-specific wildfire risk assessment that includes considerations of location, topography, aspect, flammable vegetation, climatic conditions and fire history. The plan shall address water supply, access, building ignition and fire-resistance factors, fire protection systems and equipment, defensible space and vegetation management.
The cost of fire protection plan preparation and review shall be the responsibility of the applicant.