601.1 Scope General

AMENDMENT
This section has been amended at the state or city level.
The provisions of this chapter shall govern the maintenance of mechanical and electrical facilities and equipment.

601.2 Responsibility

AMENDMENT
This section has been amended at the state or city level.

Section 602 Heating and Cooling Facilities

AMENDMENT
This section has been amended at the state or city level.
Heating facilities shall be provided in structures as required by this section.

602.2 Residential Occupancies

AMENDMENT
This section has been amended at the state or city level.

602.2 Heat Supply

AMENDMENT
This section has been amended at the state or city level.
Every owner and operator of a Group R-2 apartment building or other residential building who rents, leases, or lets one or more dwelling unit, rooming unit, dormitory, or guestroom on terms, either expressed or implied, to furnish heat to the occupants thereof shall supply heat during the period from October 15 to May 1 to maintain a temperature of not less than 68°F (20°C) in all habitable rooms, bathrooms, and toilet rooms. The code official may also consider modifications as provided in Section 104.5.2 when requested for unusual circumstances or may issue notice approving building owners to convert shared heating and cooling piping HVAC systems 14 calendar days before or after the established dates when extended periods of unusual temperatures merit modifying these dates.

Exception: When the outdoor temperature is below the winter outdoor design temperature for the locality, maintenance of the minimum room temperature shall not be required provided that the heating system is operating at its full design capacity. The winter outdoor design temperature for the locality shall be as indicated in Appendix D of the IPC.

602.2.1 Prohibited Use

AMENDMENT
This section has been amended at the state or city level.
In dwelling units subject to Section 602.2, one or more unvented room heaters shall not be used as the sole source of comfort heat in a dwelling unit.

602.3 Heat Supply

AMENDMENT
This section has been amended at the state or city level.

602.3 Occupiable Work Spaces

AMENDMENT
This section has been amended at the state or city level.
Indoor occupiable work spaces shall be supplied with heat during the period from October 1 to May 15 to maintain a minimum temperature of 65°F (18°C) during the period the spaces are occupied.

Exceptions:
  1. Processing, storage, and operation areas that require cooling or special temperature conditions.
  2. Areas in which persons are primarily engaged in vigorous physical activities.

602.4 Occupiable Work Spaces

AMENDMENT
This section has been amended at the state or city level.

602.4 Cooling Supply

AMENDMENT
This section has been amended at the state or city level.
Every owner and operator of a Group R-2 apartment building who rents, leases, or lets one or more dwelling units, rooming units, or guestrooms on terms, either expressed or implied, to furnish cooling to the occupants thereof shall supply cooling during the period from May 15 to October 1 to maintain a temperature of not more than 80°F (27°C) in all habitable rooms. The code official may also consider modifications as provided in Section 104.5.2 when requested for unusual circumstances or may issue notice approving building owners to convert shared heating and cooling piping HVAC systems 14 calendar days before or after the established dates when extended periods of unusual temperatures merit modifying these dates.

Exception: When the outdoor temperature is higher than the summer design temperature for the locality, maintenance of the room temperature shall not be required provided that the cooling system is operating at its full design capacity. The summer outdoor design temperature for the locality shall be as indicated in the IECC.
The required room temperatures shall be measured 3 feet (914 mm) above the floor near the center of the room and 2 feet (610 mm) inward from the center of each exterior wall.

603.1 Mechanical Equipment and Appliances

AMENDMENT
This section has been amended at the state or city level.
Required or provided mechanical equipment, appliances, fireplaces, solid fuel-burning appliances, cooking appliances, chimneys, vents, and water heating appliances shall be maintained in compliance with the code under which the appliances, system, or equipment was installed, kept in safe working condition, and capable of performing the intended function.

603.2 Removal of Combustion Products

AMENDMENT
This section has been amended at the state or city level.
Where required by the code under which installed, fuel-burning equipment and appliances shall be connected to an approved chimney or vent.
Required clearances to combustible materials shall be maintained.
Safety controls for fuel-burning equipment shall be maintained in effective operation.

603.5 Combustion Air

AMENDMENT
This section has been amended at the state or city level.
Where required by the code under which installed, a supply of air for complete combustion of the fuel shall be provided for the fuel-burning equipment.

603.6 Energy Conservation Devices

AMENDMENT
This section has been amended at the state or city level.

604.1 Facilities Required

AMENDMENT
This section has been amended at the state or city level.

604.1 Electrical System

AMENDMENT
This section has been amended at the state or city level.
Required or provided electrical systems and facilities shall be maintained in accordance with the applicable building code.

604.2 Service

AMENDMENT
This section has been amended at the state or city level.

604.3 Electrical System Hazards

AMENDMENT
This section has been amended at the state or city level.
Where it is found that the electrical system in a structure constitutes a hazard to the occupants or the structure by reason of deterioration or damage or for similar reasons, the code official shall require the defects to be corrected to eliminate the hazard.
The provisions of this section shall govern the repair and replacement of electrical systems and equipment that have been exposed to water.

604.3.1.1 Electrical Equipment

AMENDMENT
This section has been amended at the state or city level.
Electrical distribution equipment, motor circuits, power equipment, transformers, wire, cable, flexible cords, wiring devices, ground fault circuit interrupters, surge protectors, molded case circuit breakers, low-voltage fuses, luminaires, ballasts, motors, and electronic control, signaling, and communication equipment that have been exposed to water shall be replaced in accordance with the provisions of the VCC.

Exception: The following equipment shall be allowed to be repaired or reused where an inspection report from the equipment manufacturer, an approved representative of the equipment manufacturer, a third party licensed or certified electrician, or an electrical engineer indicates that the exposed equipment has not sustained damage that requires replacement:
  1. Enclosed switches, rated 600 volts or less;
  2. Busway, rated 600 volts or less;
  3. Panelboards, rated 600 volts or less;
  4. Switchboards, rated 600 volts or less;
  5. Fire pump controllers, rated 600 volts or less;
  6. Manual and magnetic motor controllers;
  7. Motor control centers;
  8. Alternating current high-voltage circuit breakers;
  9. Low-voltage power circuit breakers;
  10. Protective relays, meters, and current transformers;
  11. Low-voltage and medium-voltage switchgear;
  12. Liquid-filled transformers;
  13. Cast-resin transformers;
  14. Wire or cable that is suitable for wet locations and whose ends have not been exposed to water;
  15. Wire or cable, not containing fillers, that is suitable for wet locations and whose ends have not been exposed to water;
  16. Luminaires that are listed as submersible;
  17. Motors; or
  18. Electronic control, signaling, and communication equipment.

604.3.2 Abatement of Electrical Hazards Associated With Fire Exposure

AMENDMENT
This section has been amended at the state or city level.

604.3.2.1 Electrical Equipment

AMENDMENT
This section has been amended at the state or city level.
Electrical switches, receptacles and fixtures, including furnace, water heating, security system and power distribution circuits, that have been exposed to fire, shall be replaced in accordance with the provisions of the Virginia Construction Code.

Exception: Electrical switches, receptacles and fixtures that shall be allowed to be repaired or reused where an inspection report from the equipment manufacturer or an approved representative of the equipment manufacturer, a third party licensed or certified electrician, or an electrical engineer indicates that the equipment has not sustained damage that requires replacement.

605.1 Installation Electrical Components

AMENDMENT
This section has been amended at the state or city level.
Electrical equipment, wiring, and appliances shall be maintained in accordance with the applicable building code.

605.2 Receptacles

AMENDMENT
This section has been amended at the state or city level.

605.2 Power Distribution and Receptacles

AMENDMENT
This section has been amended at the state or city level.
Required or provided power circuits and receptacles shall be maintained in accordance with the code under which constructed and ground fault and arc-fault circuit interrupter protection shall be provided where required by the code in effect at the time of construction. All receptacle outlets shall have the appropriate faceplate cover for the location when required by the applicable building code.

605.3 Luminaires

AMENDMENT
This section has been amended at the state or city level.

605.3 Lighting Distribution and Luminaires

AMENDMENT
This section has been amended at the state or city level.
Required or provided lighting circuits and luminaires shall be maintained in accordance with the applicable building code.

605.4 Wiring Flexible Cords

AMENDMENT
This section has been amended at the state or city level.
Flexible cords shall not be run through doors, windows, or cabinets or concealed within walls, floors, or ceilings.

606.1 General

AMENDMENT
This section has been amended at the state or city level.
Elevators, dumbwaiters, and escalators shall be maintained in compliance with ASME A17.1. The most current certificate of inspection shall be on display at all times within the elevator or attached to the escalator or dumbwaiter; or, be available for public inspection in the office of the building operator ; or, be posted in a publicly conspicuous location approved by the code official. Where not displayed in the elevator or attached on the escalator or dumbwaiter, there shall be a notice where the certificate of inspection is available for inspection. An annual periodic inspection and test is required of elevators and escalators. A locality shall be permitted to require a six-month periodic inspection and test. All periodic inspections shall be performed in accordance with Section 8.11 of ASME A17.1. The code official may also provide for such inspection by an approved agency or through agreement with other local certified elevator inspectors. An approved agency includes any individual, partnership, or corporation who has met the certification requirements established by the VCS.
In buildings equipped with passenger elevators, not less than one elevator shall be maintained in operation at all times when the building is occupied.
Exception: Buildings equipped with only one elevator shall be permitted to have the elevator temporarily out of service for testing or servicing.
Duct systems shall be maintained free of obstructions and shall be capable of performing the required function.

607.2 Clothes Dryer Exhaust Duct

AMENDMENT
This section has been amended at the state or city level.
Required or provided clothes dryer exhaust systems shall be maintained in accordance with the applicable building code.