The storage and use of water-reactive solids and liquids shall be in accordance with this chapter.

Exceptions:
  1. Display and storage in Group M and storage in Group S occupancies complying with Section 5003.11.
  2. Detonable water-reactive solids and liquids shall be stored in accordance with Chapter 56.

6701.2 Permits

AMENDMENT
This section has been amended at the state or city level.
Permits shall be required as set forth in Section 107.2.
The following term is defined in Chapter 2:

WATER-REACTIVE MATERIAL.

Class 3.

Class 2.

Class 1.

6703.1 Quantities Not Exceeding the Maximum Allowable Quantity Per Control Area Storage and Use.

AMENDMENT
This section has been amended at the state or city level.
The storage and use of water reactive solids and liquids shall be maintained in accordance with the applicable building code.

6703.2 Quantities Exceeding the Maximum Allowable Quantity Per Control Area

AMENDMENT
This section has been amended at the state or city level.

6704.1 Indoor Storage

AMENDMENT
This section has been amended at the state or city level.
Indoor storage of water-reactive solids and liquids shall be maintained in accordance with the applicable building code.

6704.1.1 Detached Storage

AMENDMENT
This section has been amended at the state or city level.

6704.1.2 Liquid-Tight Floor

AMENDMENT
This section has been amended at the state or city level.
Liquid-tight floors in storage areas for water reactive solids and liquids shall be maintained in accordance with the applicable building code.

6704.1.3 Waterproof Room

AMENDMENT
This section has been amended at the state or city level.
Where Class 3 water-reactive solids and liquids are stored in areas equipped with an automatic sprinkler system, the materials shall be stored in closed water-tight containers.

6704.1.5 Storage Configuration

AMENDMENT
This section has been amended at the state or city level.
Aisle widths between piles shall be maintained in accordance with the applicable building code.

6704.1.6 Explosion Control

AMENDMENT
This section has been amended at the state or city level.
Explosion control for indoor storage rooms shall be maintained in accordance with the applicable building code.
Outdoor storage of water-reactive solids and liquids in quantities exceeding the maximum allowable quantity per control area indicated in Table 5003.1.1(3) shall be in accordance with Sections 5001, 5003, 5004 and this chapter.
Outdoor storage of water-reactive solids and liquids shall be within tanks or closed water-tight containers and shall be in accordance with Sections 6704.2.2 through 6704.2.5.
Outdoor storage of Class 3 water-reactive solids and liquids shall not be within 75 feet (22 860 mm) of buildings, lot lines, public streets, public alleys, public ways or means of egress.
Outdoor storage of Class 2 water-reactive solids and liquids shall not be within 20 feet (6096 mm) of buildings, lot lines, public streets, public alleys, public ways or means of egress. A 2-hour fire barrier without openings or penetrations, and extending not less than 30 inches (762 mm) above and to the sides of the storage area, is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.
Class 3 water-reactive solids and liquids shall be limited to piles not greater than 500 cubic feet (14 m3).

Class 2 water-reactive solids and liquids shall be limited to piles not greater than 1,000 cubic feet (28 m3).

Aisle widths between piles shall not be less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.

6704.2.5 Containment

AMENDMENT
This section has been amended at the state or city level.
Secondary containment shall be provided in accordance with the applicable building code.
The use of water-reactive solids and liquids in amounts exceeding the maximum allowable quantity per control area indicated in Table 5003.1.1(1) or 5003.1.1(3) shall be in accordance with Sections 5001, 5003, 5005 and this chapter.