1001.1 General

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Means of egress systems for buildings or portions thereof shall be maintained in accordance with the applicable building code and Section 1031.
It shall be unlawful to alter a building or structure in a manner that will reduce the number of exits or the capacity of the means of egress to less than required by this code.

1001.3 Overcrowding

AMENDMENT
This section has been amended at the state or city level.
Overcrowding, admittance of any person beyond the approved occupant load established by the USBC or other building code under which the building was constructed, or obstructing aisles, passageways, or any part of the means of egress shall not be allowed. The fire code official, upon finding any condition that constitutes a life safety hazard, shall be authorized to cause the event to be stopped until such condition or obstruction is corrected.

1003.1 Applicability

AMENDMENT
This section has been amended at the state or city level.
The general requirements specified in Sections 1003 through 1015 shall apply to the maintenance of the building.

1003.2 Ceiling Height

AMENDMENT
This section has been amended at the state or city level.
The means of egress ceiling height shall be maintained in accordance with the applicable building code.

1003.3 Protruding Objects

AMENDMENT
This section has been amended at the state or city level.
Protruding objects on circulation paths shall comply with the requirements of Sections 1003.3.1 and 1003.3.4.

1003.3.1 Headroom

AMENDMENT
This section has been amended at the state or city level.
Minimum headroom shall be maintained in accordance with the applicable building code.

1003.3.2 Post-Mounted Objects

AMENDMENT
This section has been amended at the state or city level.

1003.3.3 Horizontal Projections

AMENDMENT
This section has been amended at the state or city level.

1003.3.4 Clear Width

ILLUSTRATION
Protruding objects shall not reduce the minimum clear width of accessible routes.

1003.4 Floor Surface

AMENDMENT
This section has been amended at the state or city level.
Slip and trip hazards in the means of egress shall be abated.

1003.5 Elevation Change

AMENDMENT
This section has been amended at the state or city level.

1003.6 Means of Egress Continuity

AMENDMENT
This section has been amended at the state or city level.
Means of egress continuity shall be maintained in accordance with the applicable building code.

1003.7 Elevators, Escalators and Moving Walks

AMENDMENT
This section has been amended at the state or city level.

1004.1 Design Occupant Load

AMENDMENT
This section has been amended at the state or city level.
The design occupant load shall be maintained in accordance with the applicable building code.

1004.1.1 Cumulative Occupant Loads

AMENDMENT
This section has been amended at the state or city level.

1004.1.1.1 Intervening Spaces or Accessory Areas

AMENDMENT
This section has been amended at the state or city level.

1004.1.1.2 Adjacent Levels for Mezzanines

AMENDMENT
This section has been amended at the state or city level.

1004.1.1.3 Adjacent Stories

AMENDMENT
This section has been amended at the state or city level.

1004.1.2 Areas Without Fixed Seating

AMENDMENT
This section has been amended at the state or city level.

1004.2 Increased Occupant Load

AMENDMENT
This section has been amended at the state or city level.

1004.3 Posting of Occupant Load

AMENDMENT
This section has been amended at the state or city level.
Every room or space that is an assembly occupancy and where the occupant load of that room or space is 50 or more shall have the occupant load of the room or space posted in a conspicuous place near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or the owner's authorized agent.

1004.4 Fixed Seating

AMENDMENT
This section has been amended at the state or city level.

1004.5 Outdoor Areas

AMENDMENT
This section has been amended at the state or city level.
The means of egress for outdoor areas shall be maintained in accordance with the applicable building code.

1004.6 Multiple Occupancies

AMENDMENT
This section has been amended at the state or city level.
Where a building contains two or more occupancies, the means of egress requirements shall be maintained in accordance with the applicable building code.

1005.1 General

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
All portions of the means of egress system shall be sized in accordance with the applicable building code.

1005.2 Minimum Width Based on Component

AMENDMENT
This section has been amended at the state or city level.
The minimum width of any means of egress components shall be maintained in accordance with the applicable building code.

1005.3 Required Capacity Based on Occupant Load

AMENDMENT
This section has been amended at the state or city level.
The required capacity of the means of egress for any room, area, space or story shall be maintained in accordance with the applicable building code.

1005.3.1 Stairways

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
The capacity, in inches, of means of egress stairways shall be maintained in accordance with the applicable building code.

1005.3.2 Other Egress Components

AMENDMENT
This section has been amended at the state or city level.

1005.4 Continuity

AMENDMENT
This section has been amended at the state or city level.
The minimum width or required capacity of the means of egress required from any story of a building shall be maintained in accordance with the applicable building code.

1005.5 Distribution of Minimum Width and Required Capacity

AMENDMENT
This section has been amended at the state or city level.

1005.6 Egress Convergence

AMENDMENT
This section has been amended at the state or city level.
Where the means of egress from stories above and below converge at an intermediate level, the capacity of the means of egress from the point of convergence shall be maintained in accordance with the applicable code.

1005.7 Encroachment

AMENDMENT
This section has been amended at the state or city level.
Encroachments into the required means of egress width shall be in accordance with the provisions of the applicable building code.

1005.7.1 Doors

AMENDMENT
This section has been amended at the state or city level.

1005.7.2 Other Projections

AMENDMENT
This section has been amended at the state or city level.

1005.7.3 Protruding Objects

AMENDMENT
This section has been amended at the state or city level.

1006.1 General

AMENDMENT
This section has been amended at the state or city level.
The number of exits or exit access doorways required within the means of egress system shall be maintained in accordance with the applicable building code.

1006.2 Egress From Spaces

AMENDMENT
This section has been amended at the state or city level.
Egress from spaces shall be maintained in accordance with the applicable building code.

1006.2.1 Egress Based on Occupant Load and Common Path of Egress Travel Distance

AMENDMENT
This section has been amended at the state or city level.

1006.2.1.1 Three or More Exits or Exit Access Doorways

AMENDMENT
This section has been amended at the state or city level.

1006.2.2 Egress Based on Use

AMENDMENT
This section has been amended at the state or city level.

1006.2.2.1 Boiler, Incinerator and Furnace Rooms

AMENDMENT
This section has been amended at the state or city level.

1006.2.2.2 Refrigeration Machinery Rooms

AMENDMENT
This section has been amended at the state or city level.

1006.2.2.3 Refrigerated Rooms or Spaces

AMENDMENT
This section has been amended at the state or city level.

1006.2.2.4 Day Care Means of Egress

AMENDMENT
This section has been amended at the state or city level.

1006.2.2.5 Vehicular Ramps

AMENDMENT
This section has been amended at the state or city level.

1006.3 Egress From Stories or Occupied Roofs

AMENDMENT
This section has been amended at the state or city level.
The means of egress system serving any story or occupied roof shall be maintained in accordance with the applicable building code.

1006.3.1 Egress Based on Occupant Load

AMENDMENT
This section has been amended at the state or city level.

1006.3.2 Single Exits

AMENDMENT
This section has been amended at the state or city level.

1006.3.2.1 Mixed Occupancies

AMENDMENT
This section has been amended at the state or city level.

1007.1 General

AMENDMENT
This section has been amended at the state or city level.
Exits, exit access doorways, and exit access stairways and ramps serving spaces, including individual building stories, shall be maintained in accordance with the applicable code.

1007.1.1 Two Exits or Exit Access Doorways

AMENDMENT
This section has been amended at the state or city level.

1007.1.1.1 Measurement Point

AMENDMENT
This section has been amended at the state or city level.

1007.1.2 Three or More Exits or Exit Access Doorways

AMENDMENT
This section has been amended at the state or city level.

1007.1.3 Remoteness of Exit Access Stairways or Ramps

AMENDMENT
This section has been amended at the state or city level.

1007.1.3.1 Three or More Exit Access Stairways or Ramps

AMENDMENT
This section has been amended at the state or city level.

1008.1 Means of Egress Illumination

AMENDMENT
This section has been amended at the state or city level.
Illumination provided in the means of egress shall be maintained in accordance with the applicable code.

1008.2 Illumination Required

AMENDMENT
This section has been amended at the state or city level.
Illumination provided for the means of egress serving a room or space shall be maintained in accordance with the applicable building code.

1008.2.1 Illumination Level Under Normal Power

AMENDMENT
This section has been amended at the state or city level.

1008.2.2 Exit Discharge

AMENDMENT
This section has been amended at the state or city level.

1008.3 Emergency Power for Illumination

AMENDMENT
This section has been amended at the state or city level.
The power supply for means of egress illumination shall be maintained in accordance with the applicable building code.

1008.3.1 General

AMENDMENT
This section has been amended at the state or city level.

1008.3.2 Buildings

AMENDMENT
This section has been amended at the state or city level.

1008.3.3 Rooms and Spaces

AMENDMENT
This section has been amended at the state or city level.

1008.3.4 Duration

AMENDMENT
This section has been amended at the state or city level.

1008.3.5 Illumination Level Under Emergency Power

AMENDMENT
This section has been amended at the state or city level.

1009.1 Accessible Means of Egress Required

AMENDMENT
This section has been amended at the state or city level.
Accessible means of egress shall be maintained in accordance with the applicable building code.

1009.2 Continuity and Components

AMENDMENT
This section has been amended at the state or city level.
Continuity and components provided for accessible means of egress shall be maintained in accordance with the applicable building code.

1009.2.1 Elevators Required

AMENDMENT
This section has been amended at the state or city level.

1009.3 Stairways

AMENDMENT
This section has been amended at the state or city level.
Stairways part of an accessible means of egress shall be maintained in accordance with the applicable building code.

1009.4 Elevators

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Elevators considered part of the means of egress shall be maintained in accordance with the applicable building code.

1009.5 Platform Lifts

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Platform lifts serving as a part of an accessible means of egress shall be maintained in accordance with the applicable building code.

1009.6 Areas of Refuge

AMENDMENT
This section has been amended at the state or city level.
Areas of refuge shall be maintained in accordance with the applicable building code.

1009.6.1 Travel Distance

AMENDMENT
This section has been amended at the state or city level.

1009.6.2 Stairway or Elevator Access

AMENDMENT
This section has been amended at the state or city level.

1009.6.3 Size

AMENDMENT
This section has been amended at the state or city level.

1009.6.4 Separation

AMENDMENT
This section has been amended at the state or city level.

1009.6.5 Two-Way Communication

AMENDMENT
This section has been amended at the state or city level.

1009.7 Exterior Areas for Assisted Rescue

AMENDMENT
This section has been amended at the state or city level.
Exterior areas for assisted rescue shall be maintained in accordance with the applicable building code.

1009.7.1 Size

AMENDMENT
This section has been amended at the state or city level.

1009.7.2 Separation

AMENDMENT
This section has been amended at the state or city level.

1009.7.3 Openness

AMENDMENT
This section has been amended at the state or city level.

1009.7.4 Stairways

AMENDMENT
This section has been amended at the state or city level.

1009.8 Two-Way Communication

AMENDMENT
This section has been amended at the state or city level.
Where provided, two-way communication systems shall be maintained in accordance with the applicable building code.

1009.8.1 System Requirements

AMENDMENT
This section has been amended at the state or city level.
Directions for the use of the two-way communication system, instructions for summoning assistance via the two-way communication system and written identification of the location shall be posted adjacent to the two-way communication system. Signage shall comply with the ICC A117.1 requirements for visual characters.

1009.9 Signage

ILLUSTRATION
Signage indicating special accessibility provisions shall be provided as shown:
  1. Each door providing access to an area of refuge from an adjacent floor area shall be identified by a sign stating: AREA OF REFUGE.
  2. Each door providing access to an exterior area for assisted rescue shall be identified by a sign stating: EXTERIOR AREA FOR ASSISTED RESCUE.
Signage shall comply with the ICC A117.1 requirements for visual characters and include the International Symbol of Accessibility. Where exit sign illumination is required by Section 1013.3, the signs shall be illuminated. Additionally, visual characters, raised character and braille signage complying with ICC A117.1 shall be located at each door to an area of refuge and exterior area for assisted rescue in accordance with Section 1013.4.
Directional signage indicating the location of all other means of egress and which of those are accessible means of egress shall be provided at the following:
  1. At exits serving a required accessible space but not providing an approved accessible means of egress.
  2. At elevator landings.
  3. Within areas of refuge.

1009.11 Instructions

ILLUSTRATION
In areas of refuge and exterior areas for assisted rescue, instructions on the use of the area under emergency conditions shall be posted. Signage shall comply with the ICC A117.1 requirements for visual characters. The instructions shall include all of the following:
  1. Persons able to use the exit stairway do so as soon as possible, unless they are assisting others.
  2. Information on planned availability of assistance in the use of stairs or supervised operation of elevators and how to summon such assistance.
  3. Directions for use of the two-way communication system where provided.

1010.1 Doors

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Doors serving a means of egress system shall be maintained in accordance with the applicable building code. Means of egress doors shall be readily distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Mirrors or similar reflecting materials shall not be used on means of egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials.

1010.1.1 Size of Doors

AMENDMENT
This section has been amended at the state or city level.

1010.1.1.1 Projections Into Clear Width

AMENDMENT
This section has been amended at the state or city level.

1010.1.2 Door Swing

AMENDMENT
This section has been amended at the state or city level.

1010.1.2.1 Direction of Swing

AMENDMENT
This section has been amended at the state or city level.

1010.1.3 Door Opening Force

AMENDMENT
This section has been amended at the state or city level.

1010.1.3.1 Location of Applied Forces

AMENDMENT
This section has been amended at the state or city level.

1010.1.4 Special Doors

AMENDMENT
This section has been amended at the state or city level.

1010.1.4.1 Revolving Doors

AMENDMENT
This section has been amended at the state or city level.

1010.1.4.1.1 Egress Component

AMENDMENT
This section has been amended at the state or city level.

1010.1.4.1.2 Other Than Egress Component

AMENDMENT
This section has been amended at the state or city level.

1010.1.4.2 Power-Operated Doors

AMENDMENT
This section has been amended at the state or city level.

1010.1.4.3 Special Purpose Horizontal Sliding, Accordion or Folding Doors

AMENDMENT
This section has been amended at the state or city level.
In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. Where two or more means of egress are required, not more than one-half of the exits or exit access doorways shall be equipped with horizontal sliding or vertical security grilles.

1010.1.5 Floor Elevation

AMENDMENT
This section has been amended at the state or city level.

1010.1.6 Landings at Doors

AMENDMENT
This section has been amended at the state or city level.

1010.1.7 Thresholds

AMENDMENT
This section has been amended at the state or city level.

1010.1.8 Door Arrangement

AMENDMENT
This section has been amended at the state or city level.
Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

1010.1.9.1 Hardware

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.2 Hardware Height

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.3 Locks and Latches

AMENDMENT
This section has been amended at the state or city level.
Where required, a readily visible durable sign is posted on the egress side on or adjacent to the door stating THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background and shall be maintained.

1010.1.9.4 Bolt Locks

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.5 Unlatching

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.5.1 Closet and Bathroom Doors in Group R-4 Occupancies

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.6 Controlled Egress Doors in Groups I-1 and I-2

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.7 Delayed Egress

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.8 Sensor Release of Electrically Locked Egress Doors

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.9 Electromagnetically Locked Egress Doors

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.10 Locking Arrangements in Correctional Facilities

AMENDMENT
This section has been amended at the state or city level.

1010.1.9.11 Stairway Doors

AMENDMENT
This section has been amended at the state or city level.

1010.1.10 Panic and Fire Exit Hardware

AMENDMENT
This section has been amended at the state or city level.

1010.1.10.1 Installation

AMENDMENT
This section has been amended at the state or city level.

1010.1.10.2 Balanced Doors

AMENDMENT
This section has been amended at the state or city level.

1010.2 Gates

AMENDMENT
This section has been amended at the state or city level.
Gates serving the means of egress system shall be maintained in accordance with the applicable building code.

1010.2.1 Stadiums

AMENDMENT
This section has been amended at the state or city level.

1010.3 Turnstiles

AMENDMENT
This section has been amended at the state or city level.
Turnstiles or similar devices shall be maintained in accordance with the applicable building code.

1010.3.1 High Turnstile

AMENDMENT
This section has been amended at the state or city level.

1010.3.2 Additional Door

AMENDMENT
This section has been amended at the state or city level.

Section 1011 Stairways

ILLUSTRATION

1011.1 General

AMENDMENT
This section has been amended at the state or city level.
Stairways serving occupied portions of a building shall be maintained in accordance with the applicable building code.

1011.2 Width and Capacity

AMENDMENT
This section has been amended at the state or city level.
The capacity of stairways shall be maintained in accordance with the applicable building code.

1011.3 Headroom

AMENDMENT
This section has been amended at the state or city level.
Headroom requirements for stairways shall be maintained in accordance with the applicable building code.

1011.4 Walkline

AMENDMENT
This section has been amended at the state or city level.
The walkline across winder treads shall be maintained in accordance with the applicable building code.

1011.5 Stair Treads and Risers

AMENDMENT
This section has been amended at the state or city level.
Stair treads and risers shall be maintained in accordance with the applicable building code.

1011.5.1 Dimension Reference Surfaces

AMENDMENT
This section has been amended at the state or city level.

1011.5.2 Riser Height and Tread Depth

AMENDMENT
This section has been amended at the state or city level.

1011.5.3 Winder Treads

AMENDMENT
This section has been amended at the state or city level.

1011.5.4 Dimensional Uniformity

AMENDMENT
This section has been amended at the state or city level.

1011.5.4.1 Nonuniform Height Risers

AMENDMENT
This section has been amended at the state or city level.

1011.5.5 Nosing and Riser Profile

AMENDMENT
This section has been amended at the state or city level.

1011.5.5.1 Nosing Projection Size

AMENDMENT
This section has been amended at the state or city level.

1011.5.5.2 Nosing Projection Uniformity

AMENDMENT
This section has been amended at the state or city level.

1011.5.5.3 Solid Risers

AMENDMENT
This section has been amended at the state or city level.

1011.6 Stairway Landings

AMENDMENT
This section has been amended at the state or city level.

1011.7 Stairway Construction

AMENDMENT
This section has been amended at the state or city level.

1011.7.1 Stairway Walking Surface

AMENDMENT
This section has been amended at the state or city level.

1011.7.2 Outdoor Conditions

AMENDMENT
This section has been amended at the state or city level.

1011.7.3 Enclosures Under Interior Stairways

AMENDMENT
This section has been amended at the state or city level.

1011.7.4 Enclosures Under Exterior Stairways

AMENDMENT
This section has been amended at the state or city level.

1011.8 Vertical Rise

AMENDMENT
This section has been amended at the state or city level.
Vertical rise of a flight of stairs shall be maintained in accordance with the applicable building code.

1011.9 Curved Stairways

AMENDMENT
This section has been amended at the state or city level.
Curved stairways with winder treads shall be maintained in accordance with the applicable building code.

1011.10 Spiral Stairways

AMENDMENT
This section has been amended at the state or city level.
Spiral stairways used as a component in the means of egress shall be maintained in accordance with the applicable building code.

1011.11 Handrails

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Handrails for stairways shall be maintained in accordance with the applicable building code.

1011.12 Stairway to Roof

AMENDMENT
This section has been amended at the state or city level.
Stairways to a roof shall be maintained in accordance with the applicable building code.

1011.12.1 Stairway to Elevator Equipment

AMENDMENT
This section has been amended at the state or city level.

1011.12.2 Roof Access

AMENDMENT
This section has been amended at the state or city level.

1011.13 Guards

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Guards shall be maintained in accordance with the applicable building code.

1011.14 Alternating Tread Devices

AMENDMENT
This section has been amended at the state or city level.
Alternating tread devices shall be maintained in accordance with the applicable building code.

1011.14.1 Handrails of Alternating Tread Devices

AMENDMENT
This section has been amended at the state or city level.

1011.14.2 Treads of Alternating Tread Devices

AMENDMENT
This section has been amended at the state or city level.

1011.15 Ships Ladders

AMENDMENT
This section has been amended at the state or city level.
Ships ladders shall be maintained in accordance with the applicable building code.

1011.15.1 Handrails of Ships Ladders

AMENDMENT
This section has been amended at the state or city level.

1011.15.2 Treads of Ships Ladders

AMENDMENT
This section has been amended at the state or city level.

1011.16 Ladders

AMENDMENT
This section has been amended at the state or city level.

1012.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this section shall apply to the maintenance of ramps used as a component of a means of egress.

1012.2 Slope

AMENDMENT
This section has been amended at the state or city level.
Ramp slopes shall be maintained in accordance with the applicable building code.

1012.3 Cross Slope

AMENDMENT
This section has been amended at the state or city level.
The cross slope for ramps shall be maintained in accordance with the applicable building code.

1012.4 Vertical Rise

AMENDMENT
This section has been amended at the state or city level.
The rise for any ramp run shall be maintained in accordance with the applicable building code.

1012.5 Minimum Dimensions

AMENDMENT
This section has been amended at the state or city level.
The minimum dimensions of means of egress ramps shall be maintained in accordance with the applicable building code.

1012.5.1 Width and Capacity

AMENDMENT
This section has been amended at the state or city level.

1012.5.2 Headroom

AMENDMENT
This section has been amended at the state or city level.

1012.5.3 Restrictions

AMENDMENT
This section has been amended at the state or city level.

1012.6 Landings

AMENDMENT
This section has been amended at the state or city level.
Landings serving ramps shall be maintained in accordance with the applicable building code.

1012.6.1 Slope

AMENDMENT
This section has been amended at the state or city level.

1012.6.2 Width

AMENDMENT
This section has been amended at the state or city level.

1012.6.3 Length

AMENDMENT
This section has been amended at the state or city level.

1012.6.4 Change in Direction

AMENDMENT
This section has been amended at the state or city level.

1012.6.5 Doorways

AMENDMENT
This section has been amended at the state or city level.

1012.7 Ramp Construction

AMENDMENT
This section has been amended at the state or city level.
The surface of ramps shall be of slip-resistant materials that are securely attached.

1012.7.2 Outdoor Conditions

AMENDMENT
This section has been amended at the state or city level.

1012.8 Handrails

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Handrails serving ramps shall be maintained in accordance with the applicable building code.

1012.9 Guards

AMENDMENT
This section has been amended at the state or city level.
Guards shall be maintained in accordance with the applicable building code.

1012.10 Edge Protection

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Edge protection shall be maintained in accordance with the applicable building code.

1012.10.1 Curb, Rail, Wall or Barrier

AMENDMENT
This section has been amended at the state or city level.

1012.10.2 Extended Floor or Ground Surface

AMENDMENT
This section has been amended at the state or city level.

1013.1 Where Required

AMENDMENT
This section has been amended at the state or city level.
Exits and exit access doors shall be maintained in accordance with the applicable building code.

1013.2 Floor-Level Exit Signs in Group R-1

AMENDMENT
This section has been amended at the state or city level.
Floor-level exit signs in Group R-1 buildings shall be maintained in accordance with the applicable building code.

1013.3 Illumination

AMENDMENT
This section has been amended at the state or city level.
Exit sign illumination shall be maintained in accordance with the applicable building code.

1013.4 Raised Character and Braille Exit Signs

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Raised character and braille exit signs shall be maintained in accordance with the applicable building code.

1013.5 Internally Illuminated Exit Signs

AMENDMENT
This section has been amended at the state or city level.
Electrically powered, self-luminous, and photoluminescent exit signs shall be maintained in accordance with the applicable building code.

1013.6 Externally Illuminated Exit Signs

AMENDMENT
This section has been amended at the state or city level.
Externally illuminated exit signs shall be maintained in accordance with the applicable building code.

1013.6.1 Graphics

AMENDMENT
This section has been amended at the state or city level.

1013.6.2 Exit Sign Illumination

AMENDMENT
This section has been amended at the state or city level.

1013.6.3 Power Source

AMENDMENT
This section has been amended at the state or city level.

Section 1014 Handrails

ILLUSTRATION

1014.1 Where Required

AMENDMENT
This section has been amended at the state or city level.
Handrails serving stairways, ramps, stepped aisles, and ramped aisles shall be maintained in accordance with the applicable building code.

1014.2 Height

AMENDMENT
This section has been amended at the state or city level.
Handrail height, shall be maintained in accordance with the applicable building code.

1014.3 Handrail Graspability

AMENDMENT
This section has been amended at the state or city level.
Handrail graspability shall be maintained in accordance with the applicable building code.

1014.3.1 Type I

AMENDMENT
This section has been amended at the state or city level.

1014.3.2 Type II

AMENDMENT
This section has been amended at the state or city level.

1014.4 Continuity

AMENDMENT
This section has been amended at the state or city level.
Handrail continuity shall be maintained in accordance with the applicable building code.

1014.5 Fittings

AMENDMENT
This section has been amended at the state or city level.

1014.6 Handrail Extensions

AMENDMENT
This section has been amended at the state or city level.

1014.7 Clearance

AMENDMENT
This section has been amended at the state or city level.
Clear space between a handrail and a wall or other surface shall be maintained in accordance with the applicable building code.

1014.8 Projections

AMENDMENT
This section has been amended at the state or city level.
Projections into the required width of aisles, stairways and ramps at each side shall not exceed the requirements of the applicable building code.

1014.9 Intermediate Handrails

AMENDMENT
This section has been amended at the state or city level.
Where provided, intermediate handrails shall be maintained in accordance with the applicable building code.

1015.1 General

AMENDMENT
This section has been amended at the state or city level.
Guards shall be maintained in accordance with the applicable building code.

1015.2 Where Required

AMENDMENT
This section has been amended at the state or city level.

1015.2.1 Glazing

AMENDMENT
This section has been amended at the state or city level.

1015.3 Height

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Guard height shall be maintained in accordance with the applicable building code.

1015.4 Opening Limitations

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Openings in guards shall be maintained in accordance with the applicable building code.

1015.5 Screen Porches

AMENDMENT
This section has been amended at the state or city level.
Guards provided for screen porches shall be maintained in accordance with the applicable building code.

1015.6 Mechanical Equipment, Systems and Devices

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Guards provided for mechanical equipment shall be maintained in accordance with the applicable building code.

1015.7 Roof Access

AMENDMENT
This section has been amended at the state or city level.
Guards provided for roof access shall be maintained in accordance with the applicable building code.

1015.8 Window Openings

AMENDMENT
This section has been amended at the state or city level.
Windows shall be maintained in accordance with the applicable building code.

1015.8.1 Window Opening Control Devices

AMENDMENT
This section has been amended at the state or city level.

1016.1 General

AMENDMENT
This section has been amended at the state or city level.
The exit access shall be maintained in accordance with the applicable building code.

1016.2 Egress Through Intervening Spaces

AMENDMENT
This section has been amended at the state or city level.
Egress through intervening spaces shall be maintained in accordance with the applicable building code.

1016.2.1 Multiple Tenants

AMENDMENT
This section has been amended at the state or city level.

1017.1 General

AMENDMENT
This section has been amended at the state or city level.
Travel distance within the exit access portion of the means of egress system shall be maintained in accordance with the applicable building code.

1017.2 Limitations

AMENDMENT
This section has been amended at the state or city level.

1017.2.1 Exterior Egress Balcony Increase

AMENDMENT
This section has been amended at the state or city level.

1017.2.2 Group F-1 and S-1 Increase

AMENDMENT
This section has been amended at the state or city level.

1017.3 Measurement

AMENDMENT
This section has been amended at the state or city level.

1017.3.1 Exit Access Stairways and Ramps

AMENDMENT
This section has been amended at the state or city level.

Section 1018 Aisles

ILLUSTRATION

1018.1 General

AMENDMENT
This section has been amended at the state or city level.
Aisles and aisle accessways serving as a portion of the exit access in the means of egress system shall be maintained in accordance with the applicable building code.

1018.2 Aisles in Assembly Spaces

AMENDMENT
This section has been amended at the state or city level.
Aisles and aisle accessways serving a room or space used for assembly purposes shall be maintained in accordance with the applicable building code.

1018.3 Aisles in Groups B and M

AMENDMENT
This section has been amended at the state or city level.
In Groups B and M occupancies, the aisle width shall be maintained in accordance with the applicable building code.

1018.4 Aisle Accessways in Group M

AMENDMENT
This section has been amended at the state or city level.
Aisle accessways in Group M shall be maintained in accordance with the applicable building code.

1018.5 Aisles in Other Than Assembly Spaces and Groups B and M

AMENDMENT
This section has been amended at the state or city level.
Aisles in other than assembly spaces and Groups B and M shall be maintained in accordance with the applicable building code.

1019.1 General

AMENDMENT
This section has been amended at the state or city level.
Exit access stairways and ramps serving as an exit access component in a means of egress system shall be maintained in accordance with the applicable building code.

1019.2 All Occupancies

AMENDMENT
This section has been amended at the state or city level.

1019.3 Occupancies Other Than Groups I-2 and I-3

AMENDMENT
This section has been amended at the state or city level.

1019.4 Group I-2 and I-3 Occupancies

AMENDMENT
This section has been amended at the state or city level.

Section 1020 Corridors

ILLUSTRATION

1020.1 Construction

AMENDMENT
This section has been amended at the state or city level.

1020.1 Maintenance

AMENDMENT
This section has been amended at the state or city level.
Corridors shall be maintained in accordance with the applicable building code.

1020.2 Width and Capacity

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
The width and capacity of corridors shall be maintained in accordance with the applicable building code.
The minimum width or required capacity of corridors shall be unobstructed.

Exception: Encroachments complying with Section 1005.7.

1020.4 Dead Ends

AMENDMENT
This section has been amended at the state or city level.

1020.5 Air Movement in Corridors

AMENDMENT
This section has been amended at the state or city level.

1020.5.1 Corridor Ceiling

AMENDMENT
This section has been amended at the state or city level.

1020.6 Corridor Continuity

AMENDMENT
This section has been amended at the state or city level.
The continuity of fire-resistance-rated corridors shall be maintained in accordance with the applicable building code.

1021.1 General

AMENDMENT
This section has been amended at the state or city level.
Balconies used for egress purposes shall be maintained in accordance with the applicable building code.

1021.2 Wall Separation

AMENDMENT
This section has been amended at the state or city level.
Wall separation for egress balconies shall be maintained in accordance with the applicable building code.

1021.3 Openness

AMENDMENT
This section has been amended at the state or city level.

1021.4 Location

AMENDMENT
This section has been amended at the state or city level.
The fire separation distance for exterior egress balconies shall be maintained in accordance with the applicable building code.

Section 1022 Exits

ILLUSTRATION

1022.1 General

AMENDMENT
This section has been amended at the state or city level.
An exit shall not be used for any purpose that interferes with its function as a means of egress. Once a given level of exit protection is achieved, such level of protection shall not be reduced until arrival at the exit discharge. Exits shall be continuous from the point of entry into the exit to the exit discharge. Exits shall be maintained in accordance with the applicable building code.

1022.2 Exterior Exit Doors

AMENDMENT
This section has been amended at the state or city level.
Exterior exit doors shall be maintained in accordance with the applicable building code.

1022.2.1 Detailed Requirements

AMENDMENT
This section has been amended at the state or city level.

1022.2.2 Arrangement

AMENDMENT
This section has been amended at the state or city level.

1023.1 General

AMENDMENT
This section has been amended at the state or city level.
Interior exit stairways and ramps serving as an exit component in a means of egress system shall be maintained in accordance with the applicable building code.

1023.2 Construction

AMENDMENT
This section has been amended at the state or city level.

1023.3 Termination

AMENDMENT
This section has been amended at the state or city level.

1023.3.1 Extension

AMENDMENT
This section has been amended at the state or city level.

1023.4 Openings

AMENDMENT
This section has been amended at the state or city level.
Interior exit stairway and ramp opening protectives shall be maintained in accordance with the applicable building code.

1023.5 Penetrations

AMENDMENT
This section has been amended at the state or city level.

1023.6 Ventilation

AMENDMENT
This section has been amended at the state or city level.
Equipment and ductwork for interior exit stairway and ramp ventilation shall be maintained in accordance with the applicable building code.

1023.7 Interior Exit Stairway and Ramp Exterior Walls

AMENDMENT
This section has been amended at the state or city level.
Exterior walls of the interior exit stairway or ramp shall be maintained in accordance with the applicable building code.

1023.8 Discharge Identification

AMENDMENT
This section has been amended at the state or city level.
An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided and maintained in accordance with the applicable building code.
A sign shall be provided at each floor landing in an interior exit stairway and ramp connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stairway or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be located 5 feet (1524 mm) above the floor landing in a position that is readily visible when the doors are in the open and closed positions. In addition to the stairway identification sign, a floor-level sign in visual characters, raised characters and braille complying with ICC A117.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level.

1023.9.1 Signage Requirements

AMENDMENT
This section has been amended at the state or city level.
Stairway identification signs shall comply with all of the following requirements:
  1. The signs shall be a minimum size of 18 inches (457 mm) by 12 inches (305 mm).
  2. The letters designating the identification of the interior exit stairway and ramp shall be not less than 11/2 inches (38 mm) in height.
  3. The number designating the floor level shall be not less than of 5 inches (127 mm) in height and located in the center of the sign.
  4. Other lettering and numbers shall be not less than 1 inch (25 mm) in height.
  5. Characters and their background shall have a nonglare finish. Characters shall contrast with their background with either light characters on a dark background or dark characters on a light background.

1023.10 Elevator Lobby Identification Signs

AMENDMENT
This section has been amended at the state or city level.
At landings in interior exit stairways where two or more doors lead to the floor level, any door with direct access to an enclosed elevator lobby shall be identified by signage located on the door or directly adjacent to the door stating "Elevator Lobby." Signage shall be in accordance with Section 1023.9.1, Items 4 and 5.

1023.11 Smokeproof Enclosures

AMENDMENT
This section has been amended at the state or city level.
Smokeproof enclosures shall be maintained in accordance with the applicable building code.

1023.11.1 Termination and Extension

AMENDMENT
This section has been amended at the state or city level.

1023.11.2 Enclosure Access

AMENDMENT
This section has been amended at the state or city level.

1024.1 Exit Passageways

AMENDMENT
This section has been amended at the state or city level.
Exit passageways serving as an exit component in a means of egress system shall be maintained in accordance with the applicable building code.

1024.2 Width

AMENDMENT
This section has been amended at the state or city level.
The minimum width or required capacity of exit passageways shall be maintained in accordance with the applicable building code.

1024.3 Construction

AMENDMENT
This section has been amended at the state or city level.

1024.4 Termination

AMENDMENT
This section has been amended at the state or city level.

1024.5 Openings

AMENDMENT
This section has been amended at the state or city level.
Exit passageway opening protectives shall be maintained in accordance with the applicable building code.

1024.6 Penetrations

AMENDMENT
This section has been amended at the state or city level.
Penetration protection shall be maintained in accordance with the applicable building code.

1024.7 Ventilation

AMENDMENT
This section has been amended at the state or city level.
Equipment and ductwork for exit passageway ventilation shall be maintained in accordance with the applicable building code.

1025.1 General

AMENDMENT
This section has been amended at the state or city level.
Luminous egress path markings shall be maintained in accordance with the applicable building code.

1025.2 Markings Within Exit Components

AMENDMENT
This section has been amended at the state or city level.
Egress path markings provided in interior exit stairways, interior exit ramps, and exit passageways shall be maintained in accordance with the applicable building code.

1025.2.1 Steps

AMENDMENT
This section has been amended at the state or city level.

1025.2.2 Landings

AMENDMENT
This section has been amended at the state or city level.

1025.2.3 Handrails

AMENDMENT
This section has been amended at the state or city level.

1025.2.4 Perimeter Demarcation Lines

AMENDMENT
This section has been amended at the state or city level.

1025.2.4.1 Floor-Mounted Demarcation Lines

AMENDMENT
This section has been amended at the state or city level.

1025.2.4.2 Wall-Mounted Demarcation Lines

AMENDMENT
This section has been amended at the state or city level.

1025.2.4.3 Transition

AMENDMENT
This section has been amended at the state or city level.

1025.2.5 Obstacles

AMENDMENT
This section has been amended at the state or city level.

1025.2.6 Doors Within the Exit Path

AMENDMENT
This section has been amended at the state or city level.

1025.2.6.1 Emergency Exit Symbol

AMENDMENT
This section has been amended at the state or city level.

1025.2.6.2 Door Hardware Markings

AMENDMENT
This section has been amended at the state or city level.

1025.2.6.3 Door Frame Markings

AMENDMENT
This section has been amended at the state or city level.

1025.3 Uniformity

AMENDMENT
This section has been amended at the state or city level.

1025.4 Self-Luminous and Photoluminescent

AMENDMENT
This section has been amended at the state or city level.
Self-luminous and photoluminescent egress path markings shall be maintained in accordance with the applicable building code.

1025.5 Illumination

AMENDMENT
This section has been amended at the state or city level.
Photoluminescent exit path markings shall be maintained in accordance with the applicable building code.

1026.1 Horizontal Exits

AMENDMENT
This section has been amended at the state or city level.
Horizontal exits serving as an exit in a means of egress system shall be maintained in accordance with the applicable building code.

1026.2 Separation

AMENDMENT
This section has been amended at the state or city level.
The separation between buildings or refuge areas connected by a horizontal exit shall be maintained in accordance with the applicable building code.

1026.3 Opening Protectives

AMENDMENT
This section has been amended at the state or city level.
Fire doors in horizontal exits shall be maintained in accordance with the applicable building code.

1026.4 Refuge Area

AMENDMENT
This section has been amended at the state or city level.
Where provided, the refuge area of a horizontal exit shall be maintained in accordance with the applicable building code.

1026.4.1 Capacity

AMENDMENT
This section has been amended at the state or city level.

1026.4.2 Number of Exits

AMENDMENT
This section has been amended at the state or city level.

1027.1 Exterior Exit Stairways and Ramps

AMENDMENT
This section has been amended at the state or city level.
Exterior exit stairways and ramps serving as an element of a required means of egress shall be maintained in accordance with the applicable building code.

1027.2 Use in a Means of Egress

AMENDMENT
This section has been amended at the state or city level.
Exterior exit stairways shall not be used as an element of a required means of egress.

1027.3 Open Side

AMENDMENT
This section has been amended at the state or city level.

1027.4 Side Yards

AMENDMENT
This section has been amended at the state or city level.

1027.5 Location

AMENDMENT
This section has been amended at the state or city level.

1027.6 Exterior Exit Stairway and Ramp Protection

AMENDMENT
This section has been amended at the state or city level.

1028.1 General

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
The exit discharge shall be maintained in accordance with the applicable building code.

1028.2 Exit Discharge Width or Capacity

AMENDMENT
This section has been amended at the state or city level.
The minimum width or required capacity of the exit discharge shall be maintained in accordance with the applicable building code.

1028.3 Exit Discharge Components

AMENDMENT
This section has been amended at the state or city level.
Exit discharge components shall be maintained in accordance with the applicable building code.

1028.4 Egress Courts

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Egress courts serving as a portion of the exit discharge in the means of egress system shall be maintained in accordance with the applicable building code.

1028.4.1 Width or Capacity

AMENDMENT
This section has been amended at the state or city level.
The required capacity of egress courts shall be maintained in accordance with the applicable building code.

1028.4.2 Construction and Openings

AMENDMENT
This section has been amended at the state or city level.

1028.5 Access to a Public Way

AMENDMENT
This section has been amended at the state or city level.
Where provided, access to a public way shall be maintained in accordance with the applicable building code.

Exception: Where access to a public way cannot be provided, a safe dispersal area shall be provided where all of the following are met:
  1. The area shall be of a size to accommodate not less than 5 square feet (0.46 m2) for each person.
  2. The area shall be located on the same lot not less than 50 feet (15 240 mm) away from the building requiring egress.
  3. The area shall be permanently maintained and identified as a safe dispersal area.
  4. The area shall be provided with a safe and unobstructed path of travel from the building.

Section 1029 Assembly

ILLUSTRATION

1029.1 General

AMENDMENT
This section has been amended at the state or city level.
The means of egress serving a room or space used for assembly purposes that contains seats, tables, displays, equipment or other material shall be maintained in accordance with the applicable building code.

1029.1.1 Bleachers

AMENDMENT
This section has been amended at the state or city level.

1029.1.1.1 Spaces Under Grandstands and Bleachers

AMENDMENT
This section has been amended at the state or city level.

1029.2 Assembly Main Exit

AMENDMENT
This section has been amended at the state or city level.
The assembly main exit shall be maintained in accordance with the applicable building code.

1029.3 Assembly Other Exits

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Other assembly exits shall be maintained in accordance with the applicable building code.

1029.4 Foyers and Lobbies

AMENDMENT
This section has been amended at the state or city level.

1029.5 Interior Balcony and Gallery Means of Egress

AMENDMENT
This section has been amended at the state or city level.
Interior balcony and gallery means of egress shall be maintained in accordance with the applicable building code.

1029.6 Capacity of Aisle for Assembly

AMENDMENT
This section has been amended at the state or city level.
The required capacity of aisles shall be maintained in accordance with the applicable building code.

1029.6.1 Without Smoke Protection

AMENDMENT
This section has been amended at the state or city level.

1029.6.2 Smoke-Protected Assembly Seating

AMENDMENT
This section has been amended at the state or city level.

1029.6.2.1 Smoke Control

AMENDMENT
This section has been amended at the state or city level.

1029.6.2.2 Roof Height

AMENDMENT
This section has been amended at the state or city level.

1029.6.2.3 Automatic Sprinklers

AMENDMENT
This section has been amended at the state or city level.

1029.6.3 Outdoor Smoke-Protected Assembly Seating

AMENDMENT
This section has been amended at the state or city level.

1029.7 Travel Distance

AMENDMENT
This section has been amended at the state or city level.
Travel distance shall be maintained in accordance with the applicable building code.

1029.8 Common Path of Egress Travel

AMENDMENT
This section has been amended at the state or city level.
The common path of egress travel shall be maintained in accordance with the applicable building code.

1029.8.1 Path Through Adjacent Row

AMENDMENT
This section has been amended at the state or city level.

1029.9 Assembly Aisles Are Required

AMENDMENT
This section has been amended at the state or city level.
Assembly aisles shall be maintained in accordance with the applicable building code.

1029.9.1 Minimum Aisle Width

AMENDMENT
This section has been amended at the state or city level.
The minimum clear width for aisles shall be maintained in accordance with the applicable building code.

1029.9.2 Aisle Catchment Area

AMENDMENT
This section has been amended at the state or city level.

1029.9.3 Converging Aisles

AMENDMENT
This section has been amended at the state or city level.

1029.9.4 Uniform Width and Capacity

AMENDMENT
This section has been amended at the state or city level.

1029.9.5 Dead End Aisles

AMENDMENT
This section has been amended at the state or city level.

1029.9.6 Aisle Measurement

AMENDMENT
This section has been amended at the state or city level.
There shall not be obstructions in the minimum width or required capacity of aisles.

Exception: Handrails are permitted to project into the required width of stepped aisles and ramped aisles in accordance with Section 1014.8.

1029.9.7 Stairways Connecting to Stepped Aisles

AMENDMENT
This section has been amended at the state or city level.

1029.9.8 Stairways Connecting to Vomitories

AMENDMENT
This section has been amended at the state or city level.

1029.10 Transitions

AMENDMENT
This section has been amended at the state or city level.
Transitions between stairways and stepped aisles shall be maintained in accordance with the applicable building code.

1029.10.1 Transitions and Stairways That Maintain Stepped Aisle Riser and Tread Dimensions

AMENDMENT
This section has been amended at the state or city level.

1029.10.2 Transitions to Stairways That Do Not Maintain Stepped Aisle Riser and Tread Dimensions

AMENDMENT
This section has been amended at the state or city level.

1029.10.2.1 Stairways and Stepped Aisles in a Straight Run

AMENDMENT
This section has been amended at the state or city level.

1029.10.2.2 Stairways and Stepped Aisles That Change Direction

AMENDMENT
This section has been amended at the state or city level.

1029.10.3 Transition Marking

AMENDMENT
This section has been amended at the state or city level.

1029.11 Construction

AMENDMENT
This section has been amended at the state or city level.

1029.11.1 Walking Surface

AMENDMENT
This section has been amended at the state or city level.

1029.11.2 Outdoor Conditions

AMENDMENT
This section has been amended at the state or city level.

1029.12 Aisle Accessways

AMENDMENT
This section has been amended at the state or city level.
Aisle accessways for seating at tables shall maintained in accordance with the applicable building code.

1029.12.1 Seating at Tables

AMENDMENT
This section has been amended at the state or city level.

1029.12.1.1 Aisle Accessway Capacity and Width for Seating at Tables

AMENDMENT
This section has been amended at the state or city level.

1029.12.1.2 Seating at Table Aisle Accessway Length

AMENDMENT
This section has been amended at the state or city level.

1029.12.2 Clear Width of Aisle Accessways Serving Seating in Rows

AMENDMENT
This section has been amended at the state or city level.

1029.12.2.1 Dual Access

AMENDMENT
This section has been amended at the state or city level.

1029.12.2.2 Single Access

AMENDMENT
This section has been amended at the state or city level.

1029.13 Assembly Aisle Walking Surfaces

AMENDMENT
This section has been amended at the state or city level.
Ramped and stepped aisles shall be maintained in accordance with the applicable building code.

1029.13.1 Ramped Aisles

AMENDMENT
This section has been amended at the state or city level.

1029.13.1.1 Cross Slope

AMENDMENT
This section has been amended at the state or city level.

1029.13.1.2 Landings

AMENDMENT
This section has been amended at the state or city level.

1029.13.1.3 Edge Protection

AMENDMENT
This section has been amended at the state or city level.

1029.13.2 Stepped Aisles

AMENDMENT
This section has been amended at the state or city level.

1029.13.2.1 Treads

AMENDMENT
This section has been amended at the state or city level.

1029.13.2.2 Risers

AMENDMENT
This section has been amended at the state or city level.

1029.13.2.2.1 Construction Tolerances

AMENDMENT
This section has been amended at the state or city level.

1029.13.2.3 Tread Contrasting Marking Stripe

AMENDMENT
This section has been amended at the state or city level.

1029.13.2.4 Nosing and Profile

AMENDMENT
This section has been amended at the state or city level.

1029.14 Seat Stability

AMENDMENT
This section has been amended at the state or city level.

1029.15 Handrails

AMENDMENT
This section has been amended at the state or city level.
Handrails serving ramped aisles shall be maintained in accordance with the applicable building code.

1029.15.1 Discontinuous Handrails

AMENDMENT
This section has been amended at the state or city level.

1029.15.2 Handrail Termination

AMENDMENT
This section has been amended at the state or city level.

1029.15.3 Mid-Aisle Termination

AMENDMENT
This section has been amended at the state or city level.

1029.15.4 Rails

AMENDMENT
This section has been amended at the state or city level.

1029.16 Assembly Guards

AMENDMENT
This section has been amended at the state or city level.
Guards adjacent to seating in a building, room or space used for assembly purposes shall be maintained in accordance with the applicable building code.

1029.16.1 Perimeter Guards

AMENDMENT
This section has been amended at the state or city level.
Perimeter guards shall be maintained in accordance with the applicable building code.

1029.16.2 Cross Aisles

AMENDMENT
This section has been amended at the state or city level.

1029.16.3 Sightline-Constrained Guard Heights

AMENDMENT
This section has been amended at the state or city level.

1029.16.4 Guards at the End of Aisles

AMENDMENT
This section has been amended at the state or city level.

1030.1 General

AMENDMENT
This section has been amended at the state or city level.
Emergency escape and rescue components of a building shall be maintained in accordance with the applicable building code.

1030.2 Minimum Size

AMENDMENT
This section has been amended at the state or city level.
Emergency escape and rescue openings shall be maintained in accordance with the applicable building code.

1030.2.1 Minimum Dimensions

AMENDMENT
This section has been amended at the state or city level.

1030.3 Maximum Height From Floor

AMENDMENT
This section has been amended at the state or city level.
Emergency escape and rescue opening height shall be maintained in accordance with the applicable building code.

1030.4 Operational Constraints

AMENDMENT
This section has been amended at the state or city level.
The operation of emergency escape and rescue openings shall be maintained in accordance with the applicable building code.

1030.5 Window Wells

AMENDMENT
This section has been amended at the state or city level.
Window wells shall be maintained in accordance with the applicable building code.

1030.5.1 Minimum Size

AMENDMENT
This section has been amended at the state or city level.

1030.5.2 Ladders or Steps

AMENDMENT
This section has been amended at the state or city level.
The means of egress for buildings or portions thereof shall be maintained in accordance with this section.
Required exit accesses, exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency where the building area served by the means of egress is occupied. An exit or exit passageway shall not be used for any purpose that interferes with a means of egress.
Security devices affecting means of egress shall be subject to approval of the fire code official. Security devices and locking arrangements in the means of egress that restrict, control, or delay egress shall be installed and maintained as required by this chapter.
A means of egress shall be free from obstructions that would prevent its use, including the accumulation of snow and ice.
In Group I-2, the required clear width for aisles, corridors and ramps that are part of the required means of egress shall comply with Section 1020.2. The facility shall have a plan to maintain the required clear width during emergency situations.

Exception: In areas required for bed movement, equipment shall be permitted in the required width where all the following provisions are met:
  1. 1. The equipment is low hazard and wheeled.
  2. 2. The equipment does not reduce the effective clear width for the means of egress to less than 5 feet (1525 mm).
  3. 3. The equipment is limited to:
    1. 3.1 Equipment and carts in use.
    2. 3.2 Medical emergency equipment.
    3. 3.3 Infection control carts.
    4. 3.4 Patient lift and transportation equipment.
  4. 4. Medical emergency equipment and patient lift and transportation equipment, when not in use, is required to be located on one side of the corridor.
  5. 5. The equipment is limited in number to a maximum of one per patient sleeping room or patient care room within each smoke compartment.
Exit signs shall be installed and maintained in accordance with Section 1013. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed.
Where a door is adjacent to, constructed similar to and can be confused with a means of egress door, that door shall be identified with an approved sign that identifies the room name or use of the room.
Means of egress doors shall be maintained in such a manner as to be distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress therefrom, or visibility thereof. Hangings and draperies shall not be placed over exit doors or otherwise be located to conceal or obstruct an exit. Mirrors shall not be placed on exit doors. Mirrors shall not be placed in or adjacent to any exit in such a manner as to confuse the direction of exit.
Required emergency escape and rescue openings shall be maintained in accordance with the code in effect at the time of construction, and the following: Required emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings provided the minimum net clear opening size complies with the code that was in effect at the time of construction and such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than that which is required for normal operation of the emergency escape and rescue openings.
All two-way communication systems for areas of refuge shall be inspected and tested on a yearly basis to verify that all components are operational. Where required, the tests shall be conducted in the presence of the fire code official. Records of inspection, testing and maintenance shall be maintained.
The floor identification signs required by Sections 1023.9 and 1104.24 shall be maintained in an approved manner.