Chapter 5 Repairs

AMENDMENT
This section has been amended at the state or city level.

Section 501 General

AMENDMENT
This section has been amended at the state or city level.

501.1 Scope

AMENDMENT
This section has been amended at the state or city level.
Repairs, including the patching or restoration or replacement of damaged materials, elements, equipment or fixtures for the purpose of maintaining such components in good or sound condition with respect to existing loads or performance requirements, shall comply with the requirements of this chapter. Repairs to historic buildings need only comply with Chapter 9. Portions of the existing building or structure not being repaired shall not be required to comply with the requirements of this code applicable to newly constructed buildings or structures. Work on nondamaged components that is necessary for the required repair of damaged components shall be considered part of the repair and shall not be subject to the provisions of Chapter 6, 7 or 8. Routine maintenance required by Section 302, ordinary repairs exempt from permit in accordance with Section 108.2 of the VCC, and abatement of wear due to normal service conditions shall not be subject to the requirements for repairs in this section.

Exception: Repairs complying with the requirements of the building code under which the building or structure or the affected portions thereof was built, or as previously approved by the building official, shall be considered in compliance with the provisions of this code, unless the building or structure or the affected portions thereof is undergoing a substantial structural alteration as described in Section 604.7.1. New structural members added as part of the alteration or repairs shall comply with the VCC. Repairs of existing buildings in flood hazard areas shall comply with Section 503.

501.2 Conformance

AMENDMENT
This section has been amended at the state or city level.
The work shall not make the building less conforming than it was before the repair was undertaken. Repairs shall be done in a manner that maintains the following:
  1. Level of fire protection that is existing.
  2. Level of protection that is existing for the means of egress.
  3. Level of accessibility that is existing.

Section 502 Structural

AMENDMENT
This section has been amended at the state or city level.

502.1 General

AMENDMENT
This section has been amended at the state or city level.
Structural repairs shall be in compliance with this section and Section 501.2. Regardless of the scope of repair, new structural members and connections used for repair or rehabilitation shall comply with the detailing provisions of the VCC for new buildings of similar structure, purpose and location.

502.2 Repairs to Damaged Buildings

AMENDMENT
This section has been amended at the state or city level.
Repairs to damaged buildings shall comply with this section.

502.2.1 Less Than Substantial Structural Damage

AMENDMENT
This section has been amended at the state or city level.
For damage less than substantial structural damage, repairs shall be allowed that restore the building to its predamage state. New structural members and connection used for this repair shall comply with the detailing provisions of the VCC for new buildings of similar structure, purpose and location.

502.2.2 Substantial Structural Damage to Vertical Elements of the Lateral Force-Resisting System

AMENDMENT
This section has been amended at the state or city level.
A building that has sustained substantial structural damage to the vertical elements of its lateral forceresisting system shall be evaluated in accordance with Section 502.2.2.1, and either repaired in accordance with Section 502.2.2. or repaired and rehabilitated in accordance with Section 502.2.2.3, depending on the results of the evaluation.

Exceptions:
  1. Buildings assigned to Seismic Design Category A, B, or C whose substantial structural damage was not caused by earthquake need not be evaluated or rehabilitated for load combinations that include earthquake effects.
  2. One- and two-family dwellings need not be evaluated or rehabilitated for load combinations that include earthquake effects.

502.2.2.1 Evaluation

AMENDMENT
This section has been amended at the state or city level.
The building shall be evaluated by a registered design professional, and the evaluation findings shall be submitted to the building official. The evaluation shall establish whether the damaged building, if repaired to its predamage state, would comply with the provisions of the VCC for load combinations that include wind or earthquake effects, except that the seismic forces shall be the reduced VCC-level seismic forces.

Wind loads for this evaluation shall be those prescribed in Section 1609 of the VCC. Earthquake loads for this evaluation, if required, shall be permitted to be 75 percent of those prescribed in Section 1613 of the VCC. Alternatively, compliance with ASCE 41, using the performance objective in Table 305.2.2 for the applicable risk category, shall be deemed to meet the earthquake evaluation requirement.

502.2.2.2 Extent of Repair for Compliant Buildings

AMENDMENT
This section has been amended at the state or city level.
If the evaluation establishes that the building in its predamage condition complies with the provisions of Section 502.2.2.1, then repairs shall be permitted that restore the building to its predamage state.

502.2.2.3 Extent of Repair for Noncompliant Buildings

AMENDMENT
This section has been amended at the state or city level.
If the evaluation does not establish that the building in its predamage condition complies with the provisions of Section 502.2.2.1, then the building shall be rehabilitated to comply with the provisions of this section. The wind loads for the repair shall be as required by the building code in effect at the time of original construction, unless the damage was caused by wind, in which case the wind loads shall be in accordance with the VCC. The earthquake loads for this rehabilitation design shall be those required by the building code in effect at the time of original construction, but not less than the reduced VCC level seismic forces. New structural members and connections required by this rehabilitation design shall comply with the detailing provisions of the VCC for new buildings of similar structure, purpose and location. Alternatively, compliance with ASCE 41, using the performance objective in Table 305.2.2 for the applicable risk category, shall be deemed to meet the earthquake rehabilitation requirement.

502.2.3 Substantial Structural Damage to Gravity Load-Carrying Components

AMENDMENT
This section has been amended at the state or city level.
Gravity load-carrying components that have sustained substantial structural damage shall be rehabilitated to comply with the applicable provisions for dead and live loads in the VCC. Snow loads shall be considered if the substantial structural damage was caused by or related to snow load effects. Existing gravity load carrying structural elements shall be permitted to be designed for live loads approved prior to the damage. If the approved live load is less than that required by Section 1607 of the VCC, the area designed for the nonconforming live load shall be posted with placards of approved design indicating the approved live load. Nondamaged gravity load-carrying components that receive dead, live or snow loads from rehabilitated components shall also be rehabilitated if required to comply with the design loads of the rehabilitation design, or shown to have the capacity to carry the design loads of the rehabilitation design. New structural members and connections required by this rehabilitation design shall comply with the detailing provisions of the VCC for new buildings of similar structure purpose and location.

502.2.3.1 Lateral Force-Resisting Elements

AMENDMENT
This section has been amended at the state or city level.
Regardless of the level of damage to gravity elements of the lateral force-resisting system, if substantial structural damage to gravity load-carrying components was caused primarily by wind or earthquake effects, then the building shall be evaluated in accordance with Section 502.2.2.1 and, if noncompliant, rehabilitated in accordance with Section 502.2.2.3.

Exceptions:
  1. Buildings assigned to Seismic Design Category A, B, or C whose substantial structural damage was not caused by earthquake need not be evaluated or rehabilitated for load combinations that include earthquake effects.
  2. One- and two-family dwellings need not be evaluated or rehabilitated for load combinations that include earthquake effects.

Section 503 Flood Hazard Areas

AMENDMENT
This section has been amended at the state or city level.

503.1 Flood Hazard Areas

AMENDMENT
This section has been amended at the state or city level.
For buildings and structures, in flood hazard areas established in Section 1612.3 of the VCC, or Section R322 of the International Residential Code, as applicable, any repair that constitutes substantial improvement or repair of substantial damage of the existing building or structure shall comply with the flood design requirements for new construction and all aspects of the existing building or structure shall be brought into compliance with the requirements for new construction for flood design.

For buildings and structures in flood hazard areas established in Section 1612.3 of the VCC, or Section R322 of the International Residential Code, as applicable, any repairs do not constitute substantial improvement or repair of substantial damage of the existing building or structure are not required to comply with the flood design requirements for new construction.

Section 504 Electrical

AMENDMENT
This section has been amended at the state or city level.

504.1 Material

AMENDMENT
This section has been amended at the state or city level.
Existing electrical wiring and equipment undergoing repair shall be allowed to be repaired or replaced with like material.

504.1.1 Receptacles

AMENDMENT
This section has been amended at the state or city level.
Replacement of electrical receptacles shall comply with the applicable requirements of Section 406.4(D) of NFPA 70.

504.1.2 Plug Fuses

AMENDMENT
This section has been amended at the state or city level.
Plug fuses of the Edison-base type shall be used for replacements only where there is no evidence of over fusing or tampering per applicable requirements of Section 240.51(B) of NFPA 70.

504.1.3 Nongrounding-Type Receptacles

AMENDMENT
This section has been amended at the state or city level.
For replacement of nongrounding-type receptacles with grounding-type receptacles and for branch circuits that do not have an equipment grounding conductor in the branch circuitry, the grounding conductor of a grounding-type receptacle outlet shall be permitted to be grounded to any accessible point on the grounding electrode system or to any accessible point on the grounding electrode conductor in accordance with Section 250.130(C) of NFPA 70.

504.1.4 Group I-2 Receptacles

AMENDMENT
This section has been amended at the state or city level.
Non-"hospital grade" receptacles in patient bed locations of Group I-2 shall be replaced with "hospital grade" receptacles, as required by NFPA 99 and Article 517 of NFPA 70.

504.1.5 Grounding of Appliances

AMENDMENT
This section has been amended at the state or city level.
Frames of electric ranges, wall-mounted ovens, countermounted cooking units, clothes dryers and outlet or junction boxes that are part of the existing branch circuit for these appliances shall be permitted to be grounded to the grounded circuit conductor in accordance with Section 250.140 of NFPA 70.

Section 505 Mechanical

AMENDMENT
This section has been amended at the state or city level.

505.1 General

AMENDMENT
This section has been amended at the state or city level.
Existing mechanical systems undergoing repair shall not make the building less conforming than it was before the repair was undertaken.

505.2 Mechanical Draft Systems for Manually Fired Appliances and Fireplaces

AMENDMENT
This section has been amended at the state or city level.
A mechanical draft system shall be permitted to be used with manually fired appliances and fireplaces where such a system complies with all of the following requirements:
  1. The mechanical draft device shall be listed and installed in accordance with the manufacturer's installation instructions.
  2. A device shall be installed that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power at any time that the mechanical draft device is turned on. This device shall be equipped with a battery backup if it receives power from the building wiring.
  3. A smoke detector shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives power from the building wiring.

Section 506 Plumbing

AMENDMENT
This section has been amended at the state or city level.

506.1 Materials

AMENDMENT
This section has been amended at the state or city level.
Plumbing materials and supplies shall not be used for repairs that are prohibited in the International Plumbing Code.

506.2 Water Closet Replacement

AMENDMENT
This section has been amended at the state or city level.
The maximum water consumption flow rates and quantities for all replaced water closets shall be 1.6 gallons (6 L) per flushing cycle.

Exception: Blowout-design water closets 3.5 gallons (13 L) per flushing cycle.