ADOPTS WITH AMENDMENTS:

International Building Code 2015 (IBC 2015)

Heads up: There are no amended sections in this chapter.

[M] 2801.1 Scope

AMENDMENT
This section has been amended at the state or city level.
Mechanical appliances, equipment and systems shall be constructed and installed in accordance with this chapter, the International Mechanical Code and the International Fuel Gas Code. Masonry chimneys, fireplaces and barbecues shall comply with the International Mechanical Code and Chapter 21 of this code.
Exception: This code shall not govern the construction of water heaters, boilers and pressure vessels to the extent which they are regulated by the Virginia Boiler and Pressure Vessel Regulations (16VAC25-50). However, the building official may require the owner of a structure to submit documentation to substantiate compliance with those regulations.

2801.1.1 Required Heating in Dwelling Units

AMENDMENT
This section has been amended at the state or city level.
Heating facilities shall be required in every dwelling unit or portion thereof which is to be rented, leased or let on terms, either expressed or implied, to furnish heat to the occupants thereof. The heating facilities shall be capable of maintaining the room temperature at 65°F (18°C) during the period from October 15 to May 1 during the hours between 6:30 a.m. and 10:30 p.m. of each day and not less than 60°F (16°C) during other hours when measured at a point 3 feet (914 mm) above the floor and 3 feet (914 mm) from the exterior walls. The capability of the heating system shall be based on the outside design temperature required for the locality by this code.

2801.1.2 Required Heating in Nonresidential Structures

AMENDMENT
This section has been amended at the state or city level.
Heating facilities shall be required in every enclosed occupied space in nonresidential structures. The heating facilities shall be capable of producing sufficient heat during the period from October 1 to May 15 to maintain a temperature of not less than 65°F (18°C) during all working hours. The required room temperature shall be measured at a point 3 feet (914 mm) above the floor and 3 feet (914 mm) from the exterior walls.

Processing, storage and operation areas that require cooling or special temperature conditions and areas in which persons are primarily engaged in vigorous physical activities are exempt from these requirements.

2801.1.3 Changes to the International Mechanical Code

AMENDMENT
This section has been amended at the state or city level.
The following changes shall be made to the International Mechanical Code:  
  1. Add the following definition to Section 202 of the International Mechanical Code:

    POLLUTION CONTROL UNIT. Manufactured equipment that is installed in a grease exhaust duct system for the purpose of extracting smoke, grease particles, and odors from the exhaust flow by means of a series of filters.
  2. Change Section 401.2 of the International Mechanical Code to read:

    401.2 Ventilation required. Every occupied space shall be ventilated by natural means in accordance with Section 402 or by mechanical means in accordance with Section 403. Group R dwelling units shall be ventilated by mechanical means in accordance with Section 403. Ambulatory care facilities and Group I-2 occupancies shall be ventilated by mechanical means in accordance with Section 407.
  3. Change Section 403.3.1.1 of the International Mechanical Code to read:

    403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall not be less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1. Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.

    With the exception of smoking lounges and other designated areas where smoking is permitted, the ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces.
    Exception: The occupant load is not required to be determined based on the estimated maximum occupant load rate indicated in Table 403.3 where approved statistical data document the accuracy of an alternate anticipated occupant density.
  4. Add and change the following areas in Table 403.3.1.1 of the International Mechanical Code to read:

    OCCUPANCY CLASSIFICATION OCCUPANT
    DENSITY #/1000 ft2 a

    PEOPLE OUTDOOR AIRFLOW RATE IN
    BREATHING ZONE,
    Rp CFM/PERSON

    AREA OUTDOOR AIRFLOW RATE IN
    BREATHING ZONE,
    Ra CFM/FT2 a
    EXHAUST AIRFLOW RATE
    CFM/FT2 a

    Food and beverage service

           

    Bars or cocktail lounges designated as an area where smoking is permittedb

    100 30

    Cafeteria or fast food designated as an area where smoking is permittedb

    100 20

    Dining rooms designated as an area where smoking is permittedb

    70 20

    Public spaces

           

    Lounges designated as an area where smoking is permittedb

    100 30
  5. Change Section 504.8.2 of the International Mechanical Code to read:

    504.8.2 Duct installation. Exhaust ducts shall be supported at 4-foot (1219 mm) intervals and secured in place. The insert end of the duct shall extend into the adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with screws or similar fasteners that protrude into the inside of the duct.
  6. Change Section 505.1 of the International Mechanical Code to read:

    505.1 Domestic systems. Where domestic range hoods and domestic appliances equipped with downdraft exhaust are provided, such hoods and appliances shall discharge to the outdoors through sheet metal ducts constructed of galvanized steel, stainless steel, aluminum or copper. Such ducts shall have smooth inner walls, shall be airtight, shall be equipped with a backdraft damper, and shall be independent of all other exhaust systems.
    Exceptions:
    1. In Group R buildings, where installed in accordance with the manufacturer's installation instructions and where mechanical or natural ventilation is otherwise provided in accordance with Chapter 4, listed and labeled ductless range hoods shall not be required to discharge to the outdoors.
    2. Ducts for domestic kitchen cooking appliances equipped with downdraft exhaust systems shall be permitted to be constructed of Schedule 40 PVC pipe and fittings provided that the installation complies with all of the following:
      1. The PVC duct shall be installed under a concrete slab poured on grade.
      2. The underfloor trench in which the PVC duct is installed shall be completely backfilled with sand or gravel.
      3. The PVC duct shall extend not more than 1 inch (25 mm) above the indoor concrete floor surface.
      4. The PVC duct shall extend not more than 1 inch (25 mm) above grade outside of the building.
      5. The PVC duct shall be solvent cemented.
  7. Change Section 505.4 of the International Mechanical Code to read:

    505.4 Other than Group R. In other than Group R occupancies, where electric domestic cooking appliances are utilized for domestic purposes, such appliances shall be provided with domestic range hoods. Hoods and exhaust systems for such electric domestic cooking appliances shall be in accordance with Sections 505.1 and 505.2. In other than Group R occupancies, where fuel-fired domestic cooking appliances are utilized for domestic purposes, a Type I or Type II hood shall be provided as required for the type of appliances and processes in accordance with Section 507.1.
  8. Change Section 506.5 of the International Mechanical Code to read:

    506.5 Exhaust equipment. Exhaust equipment, including fans and grease reservoirs, shall comply with Sections 506.5.1 through 506.5.6 and shall be of an approved design or shall be listed for the application.
  9. Add Section 506.5.6 to the International Mechanical Code to read:

    506.5.6 Pollution control units. The installation of pollution control units shall be in accordance with the manufacturer's installation instructions and all of the following:
    1. Pollution control units shall be listed and labeled in accordance with UL 1978.
    2. Fans serving pollution control units shall be listed and labeled in accordance with UL 762.
    3. Pollution control units shall be mounted and secured in accordance with the manufacturer's installation instructions and the International Building Code.
    4. Pollution control units located indoors shall be listed and labeled for such use. Where enclosed duct systems, as required by Section 506.3.11, are connected to a pollution control unit, such unit shall be located in a room or space having the same fire-resistance rating as the duct enclosure. Access shall be provided for serving and cleaning of the unit. The space or enclosure shall be ventilated in accordance with the manufacturer's installation instructions.
    5. A clearance of not less than 18 inches (457 mm) shall be maintained between the pollution control unit and combustible material.
    6. Roof-mounted pollution control units shall be listed for exterior installation and shall be mounted not less than 18 inches (457 mm) above the roof.
    7. Exhaust outlets for pollution control units shall be in accordance with Section 506.3.13.
    8. An airflow differential pressure control shall be provided to monitor the pressure drop across the filter sections of a pollution control unit. When the airflow is reduced below the design velocity, the airflow differential pressure control shall activate a visual alarm located in the area where cooking operations occur.
    9. Pollution control units shall be provided with a factory installed fire suppression system.
    10. Service space shall be provided in accordance with the manufacturer's instructions for the pollution control unit and the requirements of Section 306.
    11. Wash down drains shall discharge through a grease interceptor and shall be sized for the flow. Drains shall be sealed with a trap or other approved means to prevent air bypass. Where a trap is utilized it shall have a seal depth that accounts for the system pressurization and evaporation between cleanings.
    12. Protection from freezing shall be provided for the water supply and fire suppression systems where such systems are subject to freezing.
    13. Duct connections to pollution control units shall be in accordance with Section 506.3.2.3. Where water splash or carryover can occur in the transition duct as a result of a washing operation, the transition duct shall slope downward toward the cabinet drain pan for a length not less than 18 inches (457 mm). Ducts shall transition to the full size of the unit inlet and outlet openings.
    14. Extra heavy duty appliance exhaust systems shall not be connected to pollution control units except where such units are specifically designed and listed for use with solid fuels.
    15. Pollution control units shall be maintained in accordance with the manufacturer's instructions.
  10. Change Section 607.5.5 of the International Mechanical Code to read:

    607.5.5 Shaft enclosures. Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing.
    Exceptions:
    1. Fire and smoke dampers are not required where steel exhaust subducts extend at least 22 inches (559 mm) vertically in exhaust shafts, provided there is a continuous airflow upward to the outside.
    2. Fire dampers are not required where penetrations are tested in accordance with ASTM E119 as part of the fireresistance-rated assembly.
    3. Fire and smoke dampers are not required where ducts are used as part of an approved smoke control system in accordance with Section 909 of the International Building Code.
    4. Fire and smoke dampers are not required where the penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.
    5. Smoke dampers are not required where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the International Building Code
  11. Add Section 607.6.2.2 to the International Mechanical Code to read:

    607.6.2.2 Equipment shutdown. Where ceiling radiation dampers are listed as static dampers, the HVAC equipment shall be effectively shut down to stop the airflow prior to the damper closing using one of the following methods:
    1. A duct detector installed in the return duct.
    2. An area smoke detector interlocked with the HVAC equipment.
    3. A listed heat sensor installed in the return duct. 

2801.1.4 Changes to the International Fuel Gas Code

AMENDMENT
This section has been amended at the state or city level.
The following changes shall be made to the International Fuel Gas Code:
  1. Change Section 301.1 of the International Fuel Gas Code to read:

    301.1 Scope. This code shall apply to the installation of fuel gas piping systems, fuel gas utilization equipment, and related accessories as follows:
    1. Coverage of piping systems shall extend from the point of delivery to the connections with gas utilization equipment. (See "Point of delivery.")
    2. Systems with an operating pressure of 125 psig (862 kPa gauge) or less.

      Piping systems for gas-air mixtures within the flammable range with an operating pressure of 10 psig (69 kPa gauge) or less.

      LP-gas piping systems with an operating pressure of 20 psig (140 kPa gauge) or less.
    3. Piping systems requirements shall include design, materials, components, fabrication, assembly, installation, testing and inspection.
    4. Requirements for gas utilization equipment and related accessories shall include installation, combustion and ventilation air and venting.

      This code shall not apply to the following:
      1. Portable LP-gas equipment of all types that are not connected to a fixed fuel piping system.
      2. Installation of farm equipment such as brooders, dehydrators, dryers, and irrigation equipment.
      3. Raw material (feedstock) applications except for piping to special atmosphere generators.
      4. Oxygen-fuel gas cutting and welding systems.
      5. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon monoxide, oxygen, and nitrogen.
      6. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms, and natural gas processing plants.
      7. Integrated chemical plants or portions of such plants where flammable or combustible liquids or gases are produced by chemical reactions or used in chemical reactions.
      8. LP-gas installations at utility gas plants.
      9. Liquefied natural gas (LNG) installations.
      10. Fuel gas piping in power and atomic energy plants.
      11. Proprietary items of equipment, apparatus, or instruments such as gas generating sets, compressors, and calorimeters.
      12. LP-gas equipment for vaporization, gas mixing, and gas manufacturing.
      13. Temporary LP-gas piping for buildings under construction or renovation that is not to become part of the permanent piping system.
      14. Installation of LP-gas systems for railroad switch heating.
      15. Installation of LP-gas and compressed natural gas (CNG) systems on vehicles.
      16. Except as provided in Section 401.1.1, gas piping, meters, gas pressure regulators, and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP-gas.
      17. Building design and construction, except as specified herein.
  2. Change Sections 310.1 and 310.1.1 of the International Fuel Gas Code to read:

    310.1 Pipe and tubing. Each above-group portion of a gas piping system that is likely to become energized shall be electrically continuous and bonded to an effective ground-fault current path. Gas piping shall be considered to be bonded where it is connected to appliances that are connected to the equipment grounding conductor of the circuit supplying that appliance. Corrugated stainless steel tubing (CSST) piping systems listed with an arc-resistant jacket or coating system in accordance with ANSI LC 1/CSA 6.26 shall comply with this section. Where any CSST segments of a piping system are not listed with an arc-resistant jacket or coating system in accordance with ANSI LC 1/CSA 6.26, Section 310.1.1 shall apply.

    310.1.1 CSST without arc-resistant jacket or coating system. CSST gas piping systems and piping systems containing one or more segments of CSST not listed with an arc-resistant jacket or coating system in accordance with ANSI LC 1/CSA 6.26 shall be bonded to the electrical service grounding electrode system or, where provided, the lightning protection electrode system; and shall comply with Sections 310.1.1.1 through 310.1.1.5. 
  3. Add Section 404.11.3 to the International Fuel Gas Code to read:

    404.11.3 Coating application. Joints in gas piping systems shall not be coated prior to testing and approval.
  4. Change Section 614.8.2 of the International Fuel Gas Code to read:

    614.8.2 Duct installation. Exhaust ducts shall be supported at 4-foot (1219 mm) intervals and secured in place. The insert end of the duct shall extend into the adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with screws or similar fasteners that protrude into the inside of the duct.
  5. Change the following referenced standard in Chapter 8 of the International Fuel Gas Code

    AISI

    American Iron and Steel Institute
    25 Massachusetts Avenue, NW Suite 800
    Washington DC 20001

    LC 1/CSA 6.26—14 Fuel Gas Piping Systems Using Corrugated Stainless Steel Tubing (CSST)

    310.1310.1.1403.5.4
     