Heads up: There are no amended sections in this chapter.
This chapter defines notation and terminology used in this Code.
a = depth of equivalent rectangular stress block, in.
av = shear span, equal to distance from center of concentrated load to either: (a) face of support for continuous or cantilevered members, or (b) center of support for simply supported members, in.
Ab = area of an individual bar or wire, in.2
Abrg = net bearing area of the head of stud, anchor bolt, or headed deformed bar, in.2
Ac = area of concrete section resisting shear transfer, in.2
Acf = greater gross cross-sectional area of the slab-beam strips of the two orthogonal equivalent frames intersecting at a column of a two-way slab, in.2
Ach = cross-sectional area of a member measured to the outside edges of transverse reinforcement, in.2
Acp = area enclosed by outside perimeter of concrete cross section, in.2
Acs = cross-sectional area at one end of a strut in a strut-and-tie model, taken perpendicular to the axis of the strut, in.2
Act = area of that part of cross section between the flexural tension face and centroid of gross section, in.2
Acv = gross area of concrete section bounded by web thickness and length of section in the direction of shear force considered in the case of walls, and gross area of concrete section in the case of diaphragms, not to exceed the thickness times the width of the diaphragm, in.2
Acw = area of concrete section of an individual pier, horizontal wall segment, or coupling beam resisting shear, in.2
Af = area of reinforcement in bracket or corbel resisting design moment, in.2
Ag = gross area of concrete section, in.2 For a hollow section, Ag is the area of the concrete only and does not include the area of the void(s)
Ah = total area of shear reinforcement parallel to primary tension reinforcement in a corbel or bracket, in.2
Aj = effective cross-sectional area within a joint in a plane parallel to plane of beam reinforcement generating shear in the joint, in.2
A = total area of longitudinal reinforcement to resist torsion, in.2
Aℓ,min = minimum area of longitudinal reinforcement to resist torsion, in.2
An = area of reinforcement in bracket or corbel resisting factored tensile force Nuc, in.2
Anz = area of a face of a nodal zone or a section through a nodal zone, in.2
ANa = projected influence area of a single adhesive anchor or group of adhesive anchors, for calculation of bond strength in tension, in.2
ANao = projected influence area of a single adhesive anchor, for calculation of bond strength in tension if not limited by edge distance or spacing, in.2
ANc = projected concrete failure area of a single anchor or group of anchors, for calculation of strength in tension, in.2
ANco = projected concrete failure area of a single anchor, for calculation of strength in tension if not limited by edge distance or spacing, in.2
Ao = gross area enclosed by torsional shear flow path, in.2
Aoh = area enclosed by centerline of the outermost closed transverse torsional reinforcement, in.2
Apd = total area occupied by duct, sheathing, and prestressing reinforcement, in.2
Aps = area of prestressed longitudinal tension reinforcement, in.2
Apt = total area of prestressing reinforcement, in.2
As = area of nonprestressed longitudinal tension reinforcement, in.2
As' = area of compression reinforcement, in.2
Asc = area of primary tension reinforcement in a corbel or bracket, in.2
Ase,N = effective cross-sectional area of anchor in tension, in.2
Ase,V = effective cross-sectional area of anchor in shear, in.2
Ash = total cross-sectional area of transverse reinforcement, including crossties, within spacing s and perpendicular to dimension bc, in.2
Asi = total area of surface reinforcement at spacing si in the i-th layer crossing a strut, with reinforcement at an angle αi to the axis of the strut, in.2
As,min = minimum area of flexural reinforcement, in.2
Ast = total area of nonprestressed longitudinal reinforcement including bars or steel shapes, and excluding prestressing reinforcement, in.2
Asx = area of steel shape, pipe, or tubing in a composite section, in.2
At = area of one leg of a closed stirrup, hoop, or tie resisting torsion within spacing s, in.2
Atp = area of prestressing reinforcement in a tie, in.2
Atr = total cross-sectional area of all transverse reinforcement within spacing s that crosses the potential plane of splitting through the reinforcement being developed, in.2
Ats = area of nonprestressed reinforcement in a tie, in.2
Av = area of shear reinforcement within spacing s, in.2
Avd = total area of reinforcement in each group of diagonal bars in a diagonally reinforced coupling beam, in.2
Avf = area of shear-friction reinforcement, in.2
Avh = area of shear reinforcement parallel to flexural tension reinforcement within spacing s2, in.2
Av,min = minimum area of shear reinforcement within spacing s, in.2
AVc = projected concrete failure area of a single anchor or group of anchors, for calculation of strength in shear, in.2
AVco = projected concrete failure area of a single anchor, for calculation of strength in shear, if not limited by corner influences, spacing, or member thickness, in.2
A1 = loaded area for consideration of bearing strength, in.2
A2 = area of the lower base of the largest frustum of a pyramid, cone, or tapered wedge contained wholly within the support and having its upper base equal to the loaded area. The sides of the pyramid, cone, or tapered wedge shall be sloped one vertical to two horizontal, in.2
b = width of compression face of member, in.
bc = cross-sectional dimension of member core measured to the outside edges of the transverse reinforcement composing area Ash, in.
bf = effective flange width of T section, in.
bo = perimeter of critical section for two-way shear in slabs and footings, in.
bs = width of strut, in.
bslab = effective slab width resisting γfMsc, in.
bt = width of that part of cross section containing the closed stirrups resisting torsion, in.
bv = width of cross section at contact surface being investigated for horizontal shear, in.
bw = web width or diameter of circular section, in.
b1 = dimension of the critical section bo measured in the direction of the span for which moments are determined, in.
b2 = dimension of the critical section bo measured in the direction perpendicular to b1, in.
Bn = nominal bearing strength, lb
Bu = factored bearing load, lb
c = distance from extreme compression fiber to neutral axis, in.
cac = critical edge distance required to develop the basic strength as controlled by concrete breakout or bond of a post-installed anchor in tension in uncracked concrete without supplementary reinforcement to control splitting, in.
ca,max = maximum distance from center of an anchor shaft to the edge of concrete, in.
ca,min = minimum distance from center of an anchor shaft to the edge of concrete, in.
ca1 = distance from the center of an anchor shaft to the edge of concrete in one direction, in. If shear is applied to anchor, ca1 is taken in the direction of the applied shear. If tension is applied to the anchor, ca1 is the minimum edge distance. Where anchors subject to shear are located in narrow sections of limited thickness, see 17.5.2.4
ca2 = distance from center of an anchor shaft to the edge of concrete in the direction perpendicular to ca1, in.
cb = lesser of: (a) the distance from center of a bar or wire to nearest concrete surface, and (b) one-half the center-to-center spacing of bars or wires being developed, in.
cc = clear cover of reinforcement, in.
cNa = projected distance from center of an anchor shaft on one side of the anchor required to develop the full bond strength of a single adhesive anchor, in.
ct = distance from the interior face of the column to the slab edge measured parallel to c1, but not exceeding c1, in.
c1 = dimension of rectangular or equivalent rectangular column, capital, or bracket measured in the direction of the span for which moments are being determined, in.
c2 = dimension of rectangular or equivalent rectangular column, capital, or bracket measured in the direction perpendicular to c1, in.
C = cross-sectional constant to define torsional properties of slab and beam
Cm = factor relating actual moment diagram to an equivalent uniform moment diagram
d = distance from extreme compression fiber to centroid of longitudinal tension reinforcement, in.
d' = distance from extreme compression fiber to centroid of longitudinal compression reinforcement, in.
da = outside diameter of anchor or shaft diameter of headed stud, headed bolt, or hooked bolt, in.
da' = value substituted for da if an oversized anchor is used, in.
dagg = nominal maximum size of coarse aggregate, in.
db = nominal diameter of bar, wire, or prestressing strand, in.
dp = distance from extreme compression fiber to centroid of prestressing reinforcement, in.
dpile = diameter of pile at footing base, in.
D = effect of service dead load
eh = distance from the inner surface of the shaft of a J-or L-bolt to the outer tip of the J- or L-bolt, in.
e'N = distance between resultant tension load on a group of anchors loaded in tension and the centroid of the group of anchors loaded in tension, in.; eN' is always positive
e'V = distance between resultant shear load on a group of anchors loaded in shear in the same direction, and the centroid of the group of anchors loaded in shear in the same direction, in.; eV' is always positive
E = effect of horizontal and vertical earthquake-induced forces
Ec = modulus of elasticity of concrete, psi
Ecb = modulus of elasticity of beam concrete, psi
Ecs = modulus of elasticity of slab concrete, psi
EI = flexural stiffness of member, in.2-lb
(EI)eff = effective flexural stiffness of member, in.2-lb
Ep = modulus of elasticity of prestressing reinforcement, psi
Es = modulus of elasticity of reinforcement and structural steel, excluding prestressing reinforcement, psi
f'c = specified compressive strength of concrete, psi
= square root of specified compressive strength of concrete, psi
fci' = specified compressive strength of concrete at time of initial prestress, psi
= square root of specified compressive strength of concrete at time of initial prestress, psi
fce = effective compressive strength of the concrete in a strut or a nodal zone, psi
fcm = measured average compressive strength of concrete, psi
fct = measured average splitting tensile strength of lightweight concrete, psi
fd = stress due to unfactored dead load, at extreme fiber of section where tensile stress is caused by externally applied loads, psi
fdc = decompression stress; stress in the prestressing reinforcement if stress is zero in the concrete at the same level as the centroid of the prestressing reinforcement, psi
fpc = compressive stress in concrete, after allowance for all prestress losses, at centroid of cross section resisting externally applied loads or at junction of web and flange where the centroid lies within the flange, psi. In a composite member, fpc is the resultant compressive stress at centroid of composite section, or at junction of web and flange where the centroid lies within the flange, due to both prestress and moments resisted by precast member acting alone
fpe = compressive stress in concrete due only to effective prestress forces, after allowance for all prestress losses, at extreme fiber of section if tensile stress is caused by externally applied loads, psi
fps = stress in prestressing reinforcement at nominal flexural strength, psi
fpu = specified tensile strength of prestressing reinforcement, psi
fpy = specified yield strength of prestressing reinforcement, psi
fr = modulus of rupture of concrete, psi
fs = tensile stress in reinforcement at service loads, excluding prestressing reinforcement, psi
f's = compressive stress in reinforcement under factored loads, excluding prestressing reinforcement, psi
fse = effective stress in prestressing reinforcement, after allowance for all prestress losses, psi
ft = extreme fiber stress in the precompressed tension zone calculated at service loads using gross section properties after allowance of all prestress losses, psi
futa = specified tensile strength of anchor steel, psi
fy = specified yield strength for nonprestressed reinforcement, psi
fya = specified yield strength of anchor steel, psi
fyt = specified yield strength of transverse reinforcement, psi
F = effect of service lateral load due to fluids with well-defined pressures and maximum heights
Fnn = nominal strength at face of a nodal zone, lb
Fns = nominal strength of a strut, lb
Fnt = nominal strength of a tie, lb
Fun = factored force on the face of a node, lb
Fus = factored compressive force in a strut, lb
Fut = factored tensile force in a tie, lb
h = overall thickness, height, or depth of member, in.
ha = thickness of member in which an anchor is located, measured parallel to anchor axis, in.
hef = effective embedment depth of anchor, in.
hsx = story height for story x, in.
hu = laterally unsupported height at extreme compression fiber of wall or wall pier, in., equivalent to u for compression members
hv = depth of shearhead cross section, in.
hw = height of entire wall from base to top, or clear height of wall segment or wall pier considered, in.
hx = maximum center-to-center spacing of longitudinal bars laterally supported by corners of crossties or hoop legs around the perimeter of the column, in.
H = effect of service load due to lateral earth pressure, ground water pressure, or pressure of bulk materials, lb
I = moment of inertia of section about centroidal axis, in.4
Ib = moment of inertia of gross section of beam about centroidal axis, in.4
Icr = moment of inertia of cracked section transformed to concrete, in.4
Ie = effective moment of inertia for calculation of deflection, in.4
Ig = moment of inertia of gross concrete section about centroidal axis, neglecting reinforcement, in.4
Is = moment of inertia of gross section of slab about centroidal axis, in.4
Ise = moment of inertia of reinforcement about centroidal axis of member cross section, in.4
Isx = moment of inertia of structural steel shape, pipe, or tubing about centroidal axis of composite member cross section, in.4
k = effective length factor for compression members
kc = coefficient for basic concrete breakout strength in tension
kcp = coefficient for pryout strength
kf = concrete strength factor
kn = confinement effectiveness factor
Ktr = transverse reinforcement index, in.
= span length of beam or one-way slab; clear projection of cantilever, in.
a = additional embedment length beyond centerline of support or point of inflection, in.
c = length of compression member, measured center-to-center of the joints, in.
d = development length in tension of deformed bar, deformed wire, plain and deformed welded wire reinforcement, or pretensioned strand, in.
dc = development length in compression of deformed bars and deformed wire, in.
db = debonded length of prestressed reinforcement at end of member, in.
dh = development length in tension of deformed bar or deformed wire with a standard hook, measured from outside end of hook, point of tangency, toward critical section, in.
dt = development length in tension of headed deformed bar, measured from the bearing face of the head toward the critical section, in.
e = load bearing length of anchor for shear, in.
ext = straight extension at the end of a standard hook, in.
n = length of clear span measured face-to-face of supports, in.
o = length, measured from joint face along axis of member, over which special transverse reinforcement must be provided, in.
sc = compression lap splice length, in.
st = tension lap splice length, in.
t = span of member under load test, taken as the shorter span for two-way slab systems, in. Span is the lesser of: (a) distance between centers of supports, and (b) clear distance between supports plus thickness h of member. Span for a cantilever shall be taken as twice the distance from face of support to cantilever end
tr = transfer length of prestressed reinforcement, in.
u = unsupported length of column or wall, in.
v = length of shearhead arm from centroid of concentrated load or reaction, in.
w = length of entire wall, or length of wall segment or wall pier considered in direction of shear force, in.
1 = length of span in direction that moments are being determined, measured center-to-center of supports, in.
2 = length of span in direction perpendicular to 1, measured center-to-center of supports, in.
L = effect of service live load
Lr = effect of service roof live load
Ma = maximum moment in member due to service loads at stage deflection is calculated, in.-lb
Mc = factored moment amplified for the effects of member curvature used for design of compression member, in.-lb
Mcr = cracking moment, in.-lb
Mcre = moment causing flexural cracking at section due to externally applied loads, in.-lb
Mmax = maximum factored moment at section due to externally applied loads, in.-lb
Mn = nominal flexural strength at section, in.-lb
Mnb = nominal flexural strength of beam including slab where in tension, framing into joint, in.-lb
Mnc = nominal flexural strength of column framing into joint, calculated for factored axial force, consistent with the direction of lateral forces considered, resulting in lowest flexural strength, in.-lb
Mo = total factored static moment, in.-lb
Mp = required plastic moment strength of shearhead cross section, in.-lb
Mpr = probable flexural strength of members, with or without axial load, determined using the properties of the member at joint faces assuming a tensile stress in the longitudinal bars of at least 1.25fy and a strength reduction factor ϕ of 1.0, in.-lb
Msa = maximum moment in wall due to service loads, excluding PΔ effects, in.-lb
Msc = factored slab moment that is resisted by the column at a joint, in.-lb
Mu = factored moment at section, in.-lb
Mua = moment at midheight of wall due to factored lateral and eccentric vertical loads, not including PΔ effects, in.-lb
Mv = moment resistance contributed by shearhead reinforcement, in.-lb
M1 = lesser factored end moment on a compression member, in.-lb
M1ns = factored end moment on a compression member at the end at which M1 acts, due to loads that cause no appreciable sidesway, calculated using a first-order elastic frame analysis, in.-lb
M1s = factored end moment on compression member at the end at which M1 acts, due to loads that cause appreciable sidesway, calculated using a first-order elastic frame analysis, in.-lb
M2 = greater factored end moment on a compression member. If transverse loading occurs between supports, M2 is taken as the largest moment occurring in member. Value of M2 is always positive, in.-lb
M2,min = minimum value of M2, in.-lb
M2ns = factored end moment on compression member at the end at which M2 acts, due to loads that cause no appreciable sidesway, calculated using a first-order elastic frame analysis, in.-lb
M2s = factored end moment on compression member at the end at which M2 acts, due to loads that cause appreciable sidesway, calculated using a first-order elastic frame analysis, in.-lb
n = number of items, such as, bars, wires, monostrand anchorage devices, anchors, or shearhead arms
n = number of longitudinal bars around the perimeter of a column core with rectilinear hoops that are laterally supported by the corner of hoops or by seismic hooks. A bundle of bars is counted as a single bar
Na = nominal bond strength in tension of a single adhesive anchor, lb
Nag = nominal bond strength in tension of a group of adhesive anchors, lb
Nb = basic concrete breakout strength in tension of a single anchor in cracked concrete, lb
Nba = basic bond strength in tension of a single adhesive anchor, lb
Nc = resultant tensile force acting on the portion of the concrete cross section that is subjected to tensile stresses due to the combined effects of service loads and effective prestress, lb
Ncb = nominal concrete breakout strength in tension of a single anchor, lb
Ncbg = nominal concrete breakout strength in tension of a group of anchors, lb
Ncp = basic concrete pryout strength of a single anchor, lb
Ncpg = basic concrete pryout strength of a group of anchors, lb
Nn = nominal strength in tension, lb
Np = pullout strength in tension of a single anchor in cracked concrete, lb
Npn = nominal pullout strength in tension of a single anchor, lb
Nsa = nominal strength of a single anchor or individual anchor in a group of anchors in tension as governed by the steel strength, lb
Nsb = side-face blowout strength of a single anchor, lb
Nsbg = side-face blowout strength of a group of anchors, lb
Nu = factored axial force normal to cross section occurring simultaneously with Vu or Tu; to be taken as positive for compression and negative for tension, lb
Nua = factored tensile force applied to anchor or individual anchor in a group of anchors, lb
Nua,g = total factored tensile force applied to anchor group, lb
Nua,i = factored tensile force applied to most highly stressed anchor in a group of anchors, lb
Nua,s = factored sustained tension load, lb
Nuc = factored horizontal tensile force applied at top of bracket or corbel acting simultaneously with Vu, to be taken as positive for tension, lb
pcp = outside perimeter of concrete cross section, in.
ph = perimeter of centerline of outermost closed transverse torsional reinforcement, in.
Pc = critical buckling load, lb
Pn = nominal axial compressive strength of member, lb
Pn,max = maximum nominal axial compressive strength of a member, lb
Pnt = nominal axial tensile strength of member, lb
Pnt,max = maximum nominal axial tensile strength of member, lb
Po = nominal axial strength at zero eccentricity, lb
Ppu = factored prestressing force at anchorage device, lb
Ps = unfactored axial load at the design, midheight section including effects of self-weight, lb
Pu = factored axial force; to be taken as positive for compression and negative for tension, lb
PΔ = secondary moment due to lateral deflection, in.-lb
qDu = factored dead load per unit area, lb/ft2
qLu = factored live load per unit area, lb/ft2
qu = factored load per unit area, lb/ft2
Q = stability index for a story
r = radius of gyration of cross section, in.
R = cumulative load effect of service rain load
s = center-to-center spacing of items, such as longitudinal reinforcement, transverse reinforcement, tendons, or anchors, in.
si = center-to-center spacing of reinforcement in the i-th direction adjacent to the surface of the member, in.
so = center-to-center spacing of transverse reinforcement within the length o, in.
ss = sample standard deviation, psi
sw = clear distance between adjacent webs, in.
s2 = center-to-center spacing of longitudinal shear or torsional reinforcement, in.
S = effect of service snow load
Se = moment, shear, or axial force at connection corresponding to development of probable strength at intended yield locations, based on the governing mechanism of inelastic lateral deformation, considering both gravity and earthquake effects
Sm = elastic section modulus, in.3
Sn = nominal moment, shear, axial, torsional, or bearing strength
Sy = yield strength of connection, based on fy of the connected part, for moment, shear, or axial force, psi
t = wall thickness of hollow section, in.
tf = thickness of flange, in.
T = cumulative effects of service temperature, creep, shrinkage, differential settlement, and shrinkage-compensating concrete
Tcr = cracking torsional moment, in.-lb
Tt = total test load, lb
Tth = threshold torsional moment, in.-lb
Tn = nominal torsional moment strength, in.-lb
Tu = factored torsional moment at section, in.-lb
U = strength of a member or cross section required to resist factored loads or related internal moments and forces in such combinations as stipulated in this Code
vc = stress corresponding to nominal two-way shear strength provided by concrete, psi
vn = equivalent concrete stress corresponding to nominal two-way shear strength of slab or footing, psi
vs = equivalent concrete stress corresponding to nominal two-way shear strength provided by reinforcement, psi
vu = maximum factored two-way shear stress calculated around the perimeter of a given critical section, psi
vug = factored shear stress on the slab critical section for two-way action due to gravity loads without moment transfer, psi
Vb = basic concrete breakout strength in shear of a single anchor in cracked concrete, lb
Vc = nominal shear strength provided by concrete, lb
Vcb = nominal concrete breakout strength in shear of a single anchor, lb
Vcbg = nominal concrete breakout strength in shear of a group of anchors, lb
Vci = nominal shear strength provided by concrete where diagonal cracking results from combined shear and moment, lb
Vcp = nominal concrete pryout strength of a single anchor, lb
Vcpg = nominal concrete pryout strength of a group of anchors, lb
Vcw = nominal shear strength provided by concrete where diagonal cracking results from high principal tensile stress in web, lb
Vd = shear force at section due to unfactored dead load, lb
Ve = design shear force for load combinations including earthquake effects, lb
Vi = factored shear force at section due to externally applied loads occurring simultaneously with Mmax, lb
Vn = nominal shear strength, lb
Vnh = nominal horizontal shear strength, lb
Vp = vertical component of effective prestress force at section, lb
Vs = nominal shear strength provided by shear reinforcement, lb
Vsa = nominal shear strength of a single anchor or individual anchor in a group of anchors as governed by the steel strength, lb,
Vu = factored shear force at section, lb
Vua = factored shear force applied to a single anchor or group of anchors, lb
Vua,g = total factored shear force applied to anchor group, lb
Vua,i = factored shear force applied to most highly stressed anchor in a group of anchors, lb
Vuh = factored shear force along contact surface in composite concrete flexural member, lb
Vus = factored horizontal shear in a story, lb
wc = density, unit weight, of normalweight concrete or equilibrium density of lightweight concrete, lb/ft3
wu = factored load per unit length of beam or one-way slab, lb/in.
w/cm = water-cementitious material ratio
W = effect of wind load
x = shorter overall dimension of rectangular part of cross section, in
y = longer overall dimension of rectangular part of cross section, in
yt = distance from centroidal axis of gross section, neglecting reinforcement, to tension face, in.
α = angle defining the orientation of reinforcement
αc = coefficient defining the relative contribution of concrete strength to nominal wall shear strength
αf = ratio of flexural stiffness of beam section to flexural stiffness of a width of slab bounded laterally by centerlines of adjacent panels, if any, on each side of the beam
αfm = average value of αf for all beams on edges of a panel
αf1 = αf in direction of 1
αf2 = αf in direction of 2
αi = angle between the axis of a strut and the bars in the i-th layer of reinforcement crossing that strut
αs = constant used to calculate Vc in slabs and footings
αv = ratio of flexural stiffness of shearhead arm to that of the surrounding composite slab section
α1 = orientation of distributed reinforcement in a strut
α2 = orientation of reinforcement orthogonal to α1 in a strut
β = ratio of long to short dimensions: clear spans for two-way slabs, sides of column, concentrated load or reaction area; or sides of a footing
βb = ratio of area of reinforcement cut off to total area of tension reinforcement at section
βdns = ratio used to account for reduction of stiffness of columns due to sustained axial loads
βds = the ratio of maximum factored sustained shear within a story to the maximum factored shear in that story associated with the same load combination
βn = factor used to account for the effect of the anchorage of ties on the effective compressive strength of a nodal zone
βs = factor used to account for the effect of cracking and confining reinforcement on the effective compressive strength of the concrete in a strut
βt = ratio of torsional stiffness of edge beam section to flexural stiffness of a width of slab equal to span length of beam, center-to-center of supports
β1 = factor relating depth of equivalent rectangular compressive stress block to depth of neutral axis
γf = factor used to determine the fraction of Msc transferred by slab flexure at slab-column connections
γp = factor used for type of prestressing reinforcement
γs = factor used to determine the portion of reinforcement located in center band of footing
γv = factor used to determine the fraction of Msc transferred by eccentricity of shear at slab-column connections
δ = moment magnification factor used to reflect effects of member curvature between ends of a compression member
δs = moment magnification factor used for frames not braced against sidesway, to reflect lateral drift resulting from lateral and gravity loads
δu = design displacement, in.
Δcr = calculated out-of-plane deflection at midheight of wall corresponding to cracking moment Mcr, in.
Δn = calculated out-of-plane deflection at midheight of wall corresponding to nominal flexural strength Mn, in.
Δo = relative lateral deflection between the top and bottom of a story due to Vus, in.
Δfp = increase in stress in prestressing reinforcement due to factored loads, psi
Δfps = stress in prestressing reinforcement at service loads less decompression stress, psi
Δr = residual deflection measured 24 hours after removal of the test load. For the first load test, residual deflection is measured relative to the position of the structure at the beginning of the first load test. For the second load test, residual deflection is measured relative to the position of the structure at the beginning of the second load test, in.
Δs = out-of-plane deflection due to service loads, in.
Δu = calculated out-of-plane deflection at midheight of wall due to factored loads, in.
Δx = design story drift of story x, in.
Δ1 = maximum deflection, during first load test, measured 24 hours after application of the full test load, in.
Δ2 = maximum deflection, during second load test, measured 24 hours after application of the full test load. Deflection is measured relative to the position of the structure at the beginning of the second load test, in.
εt = net tensile strain in extreme layer of longitudinal tension reinforcement at nominal strength, excluding strains due to effective prestress, creep, shrinkage, and temperature
εty = value of net tensile strain in the extreme layer of longitudinal tension reinforcement used to define a compression-controlled section
θ = angle between axis of strut, compression diagonal, or compression field and the tension chord of the members
λ = modification factor to reflect the reduced mechanical properties of lightweight concrete relative to normalweight concrete of the same compressive strength
λa = modification factor to reflect the reduced mechanical properties of lightweight concrete in certain concrete anchorage applications
λΔ = multiplier used for additional deflection due to long-term effects
µ = coefficient of friction
ξ = time-dependent factor for sustained load
ρ = ratio of As to bd
ρ' = ratio of As' to bd
ρ = ratio of area of distributed longitudinal reinforcement to gross concrete area perpendicular to that reinforcement
ρp = ratio of Aps to bdp
ρs = ratio of volume of spiral reinforcement to total volume of core confined by the spiral, measured out-to-out of spirals
ρt = ratio of area of distributed transverse reinforcement to gross concrete area perpendicular to that reinforcement
ρv = ratio of tie reinforcement area to area of contact surface
ρw = ratio of As to bwd
ϕ = strength reduction factor
τcr = characteristic bond stress of adhesive anchor in cracked concrete, psi
τuncr = characteristic bond stress of adhesive anchor in uncracked concrete, psi
ψc = factor used to modify development length based on cover
ψc,N = factor used to modify tensile strength of anchors based on presence or absence of cracks in concrete
ψc,P = factor used to modify pullout strength of anchors based on presence or absence of cracks in concrete
ψc,V = factor used to modify shear strength of anchors based on presence or absence of cracks in concrete and presence or absence of supplementary reinforcement
ψcp,N = factor used to modify tensile strength of post-installed anchors intended for use in uncracked concrete without supplementary reinforcement to account for the splitting tensile stresses due to installation
ψcp,Na = factor used to modify tensile strength of adhesive anchors intended for use in uncracked concrete without supplementary reinforcement to account for the splitting tensile stresses due to installation
ψe = factor used to modify development length based on reinforcement coating
ψec,N = factor used to modify tensile strength of anchors based on eccentricity of applied loads
ψec,Na = factor used to modify tensile strength of adhesive anchors based on eccentricity of applied loads
ψec,V = factor used to modify shear strength of anchors based on eccentricity of applied loads
ψed,N = factor used to modify tensile strength of anchors based on proximity to edges of concrete member
ψed,Na = factor used to modify tensile strength of adhesive anchors based on proximity to edges of concrete member
ψed,V = factor used to modify shear strength of anchors based on proximity to edges of concrete member
ψh,V = factor used to modify shear strength of anchors located in concrete members with ha < 1.5ca1
ψr = factor used to modify development length based on confining reinforcement
ψs = factor used to modify development length based on reinforcement size
ψt = factor used to modify development length for casting location in tension
ψw = factor used to modify development length for welded deformed wire reinforcement in tension
Ωo = amplification factor to account for overstrength of the seismic-force-resisting system determined in accordance with the general building code

2.3 Terminology

AMENDMENT
This section has been amended at the state or city level.

adhesive—chemical components formulated from organic polymers, or a combination of organic polymers and inorganic materials that cure if blended together.

admixture—material other than water, aggregate, or hydraulic cement, used as an ingredient of concrete and added to concrete before or during its mixing to modify its properties.

aggregate—granular material, such as sand, gravel, crushed stone, and iron blast-furnace slag, used with a cementing medium to form concrete or mortar.

aggregate, lightweight—aggregate meeting the requirements of ASTM C330 and having a loose bulk density of 70 lb/ft3 or less, determined in accordance with ASTM C29.

anchor—a steel element either cast into concrete or post-installed into a hardened concrete member and used to transmit applied loads to the concrete.

anchor, adhesive—a post-installed anchor, inserted into hardened concrete with an anchor hole diameter not greater than 1.5 times the anchor diameter, that transfers loads to the concrete by bond between the anchor and the adhesive, and bond between the adhesive and the concrete.

anchor, cast-in—headed bolt, headed stud, or hooked bolt installed before placing concrete.

anchor, expansionpost-installed anchor, inserted into hardened concrete that transfers loads to or from the concrete by direct bearing or friction, or both.

anchor, horizontal or upwardly inclinedAnchor installed in a hole drilled horizontally or in a hole drilled at any orientation above horizontal.

anchor, post-installedanchor installed in hardened concrete; adhesive, expansion, and undercut anchors are examples of post-installed anchors.

anchor, undercutpost-installed anchor that develops its tensile strength from the mechanical interlock provided by undercutting of the concrete at the embedded end of the anchor. Undercutting is achieved with a special drill before installing the anchor or alternatively by the anchor itself during its installation.

anchor group—a number of similar anchors having approximately equal effective embedment depths with spacing s between adjacent anchors such that the projected areas overlap.

anchor pullout strength—the strength corresponding to the anchoring device or a major component of the device sliding out from the concrete without breaking out a substantial portion of the surrounding concrete.

anchorage device—in post-tensioned members, the hardware used to transfer force from prestressed reinforcement to the concrete.

anchorage device, basic monostrandanchorage device used with any single strand or a single 5/8 in. or smaller diameter bar that is in accordance with 25.8.1, 25.8.2, and 25.9.3.1(a).

anchorage device, basic multistrand—anchorage device used with multiple strands, bars, or wires, or with single bars larger than 5/8 in. diameter that satisfies 25.8.1, 25.8.2 and 25.9.3.1(b).

anchorage device, special—anchorage device that satisfies tests required in 25.9.3.1(c).

anchorage zone—in post-tensioned members, portion of the member through which the concentrated prestressing force is transferred to concrete and distributed more uniformly across the section; its extent is equal to the largest dimension of the cross section; for anchorage devices located away from the end of a member, the anchorage zone includes the disturbed regions ahead of and behind the anchorage device.

attachment—structural assembly, external to the surface of the concrete, that transmits loads to or receives loads from the anchor.

B-region—portion of a member in which it is reasonable to assume that strains due to flexure vary linearly through section.

base of structure—level at which horizontal earthquake ground motions are assumed to be imparted to a building. This level does not necessarily coincide with the ground level.

beam—member subjected primarily to flexure and shear, with or without axial force or torsion; beams in a moment frame that forms part of the lateral-force-resisting system are predominantly horizontal members; a girder is a beam.

boundary element—portion along wall and diaphragm edge, including edges of openings, strengthened by longitudinal and transverse reinforcement.

breakout strength, concrete—strength corresponding to a volume of concrete surrounding the anchor or group of anchors separating from the member.

building officialterm used to identify the Authority having jurisdiction or individual charged with administration and enforcement of provisions of the building code. Such terms as building commissioner or building inspector are variations of the title, and the term "building official" as used in this Code, is intended to include those variations, as well as others that are used in the same sense.

cementitious materials—materials that have cementing value if used in concrete either by themselves, such as portland cement, blended hydraulic cements, and expansive cement; or such materials in combination with fly ash, other raw or calcined natural pozzolans, silica fume, and slag cement.

collector—element that acts in axial tension or compression to transmit forces between a diaphragm and a vertical element of the lateral-force-resisting system.

column—member, usually vertical or predominantly vertical, used primarily to support axial compressive load, but that can also resist moment, shear, or torsion. Columns used as part of a lateral-force-resisting system resist combined axial load, moment, and shear. See also moment frame.

column capital—enlargement of the top of a concrete column located directly below the slab or drop panel that is cast monolithically with the column.

compliance requirements—construction-related code requirements directed to the contractor to be incorporated into construction documents by the licensed design professional, as applicable.

composite concrete flexural members—concrete flexural members of precast or cast-in-place concrete elements, constructed in separate placements but connected so that all elements respond to loads as a unit.

compression-controlled section—cross section in which the net tensile strain in the extreme tension reinforcement at nominal strength is less than or equal to the compression-controlled strain limit.

compression-controlled strain limit—net tensile strain at balanced strain conditions.

concrete—mixture of portland cement or any other cementitious material, fine aggregate, coarse aggregate, and water, with or without admixtures.

concrete, all-lightweight—lightweight concrete containing only lightweight coarse and fine aggregates that conform to ASTM C330.

concrete, lightweightconcrete containing lightweight aggregate and having an equilibrium density, as determined by ASTM C567, between 90 and 115 lb/ft3.

concrete, nonprestressed—reinforced concrete with at least the minimum amount of nonprestressed reinforcement and no prestressed reinforcement; or for two-way slabs, with less than the minimum amount of prestressed reinforcement.

concrete, normalweightconcrete containing only coarse and fine aggregates that conform to ASTM C33.

concrete, plainconcrete with no reinforcement or with reinforcement less than the minimum amount specified for reinforced concrete.

concrete, precastconcrete element cast elsewhere than its final position in the structure.

concrete, prestressedconcrete in which internal stresses have been introduced to reduce potential tensile stresses in concrete resulting from service loads.

concrete, reinforcedconcrete reinforced with at least the minimum amounts of nonprestressed or prestressed reinforcement required by this Code.

concrete, sand-lightweightlightweight concrete containing only normalweight fine aggregate that conforms to ASTM C33 and lightweight coarse aggregate that conforms to ASTM C330.

concrete, steel fiber-reinforcedconcrete containing a prescribed amount of dispersed, randomly oriented, discontinuous deformed steel fibers.

concrete strength, specified compressive, (f'c)—compressive strength of concrete used in design and evaluated in accordance with provisions of this Code, psi; wherever the quantity f'c is under a radical sign, the square root of numerical value only is intended, and the result has units of psi.

connection—region of a structure that joins two or more members; a connection also refers to a region that joins members of which one or more is precast.

connection, ductileconnection between one or more precast elements that experiences yielding as a result of the earthquake design displacements.

connection, strong—connection between one or more precast elements that remains elastic while adjoining members experience yielding as a result of earthquake design displacements.

construction documents—written and graphic documents and specifications prepared or assembled for describing the location, design, materials, and physical characteristics of the elements of a project necessary for obtaining a building permit and construction of the project.

contraction joint—formed, sawed, or tooled groove in a concrete structure to create a weakened plane and regulate the location of cracking resulting from the dimensional change of different parts of the structure.

cover, specified concrete—distance between the outermost surface of embedded reinforcement and the closest outer surface of the concrete.

crosstie—a continuous reinforcing bar having a seismic hook at one end and a hook not less than 90 degrees with at least a 6db extension at the other end. The hooks shall engage peripheral longitudinal bars. The 90-degree hooks of two successive crossties engaging the same longitudinal bars shall be alternated end for end.

D-region—portion of a member within a distance h of a force discontinuity or a geometric discontinuity.

DESIGN DISPLACEMENT. Total lateral displacement expected for the design-basis earthquakeas specified by Section 12.8.6 of ASCE 7.

design information—project-specific information to be incorporated into construction documents by the licensed design professional, as applicable.

design load combination—combination of factored loads and forces.

design story drift ratio—relative difference of design displacement between the top and bottom of a story, divided by the story height.

DETAILED PLAIN CONCRETE STRUCTURAL WALL. A wall complying with the requirements of Chapter 14, including 14.6.2.

development length—length of embedded reinforcement, including pretensioned strand, required to develop the design strength of reinforcement at a critical section.

discontinuity—abrupt change in geometry or loading.

distance sleeve—sleeve that encases the center part of an undercut anchor, a torque-controlled expansion anchor, or a displacement-controlled expansion anchor, but does not expand.

drop panel—projection below the slab used to reduce the amount of negative reinforcement over a column or the minimum required slab thickness, and to increase the slab shear strength.

duct—conduit, plain or corrugated, to accommodate prestressing reinforcement for post-tensioning applications.

durability—ability of a structure or member to resist deterioration that impairs performance or limits service life of the structure in the relevant environment considered in design.

edge distance—distance from the edge of the concrete surface to the center of the nearest anchor.

effective depth of section—distance measured from extreme compression fiber to centroid of longitudinal tension reinforcement.

effective embedment depth—overall depth through which the anchor transfers force to or from the surrounding concrete; effective embedment depth will normally be the depth of the concrete failure surface in tension applications; for cast-in headed anchor bolts and headed studs, the effective embedment depth is measured from the bearing contact surface of the head.

effective prestress—stress remaining in prestressed reinforcement after losses in 20.3.2.6 have occurred.

embedments—items embedded in concrete, excluding reinforcement as defined in Chapter 20 and anchors as defined in Chapter 17. Reinforcement or anchors welded, bolted or otherwise connected to the embedded item to develop the strength of the assembly, are considered to be part of the embedment.

embedments, pipe—embedded pipes, conduits, and sleeves.

embedment length—length of embedded reinforcement provided beyond a critical section.

equilibrium density—density of lightweight concrete determined in accordance with ASTM C567 after exposure to a relative humidity of 50 ± 5 percent and a temperature of 73.5 ± 3.5°F for a period of time sufficient to reach constant density.

expansion sleeve—outer part of an expansion anchor that is forced outward by the center part, either by applied torque or impact, to bear against the sides of the predrilled hole. See also anchor, expansion.

extreme tension reinforcement—layer of prestressed or nonprestressed reinforcement that is the farthest from the extreme compression fiber.

finite element analysis—a numerical modeling technique in which a structure is divided into a number of discrete elements for analysis.

five percent fractile—statistical term meaning 90 percent confidence that there is 95 percent probability of the actual strength exceeding the nominal strength.

headed deformed bars—deformed bars with heads attached at one or both ends.

headed bolt—cast-in steel anchor that develops its tensile strength from the mechanical interlock provided by either a head or nut at the embedded end of the anchor.

headed stud—a steel anchor conforming to the requirements of AWS D1.1 and affixed to a plate or similar steel attachment by the stud arc welding process before casting; also referred to as a welded headed stud.

headed shear stud reinforcementreinforcement consisting of individual headed studs or groups of studs, with anchorage provided by a head at each end, or by a head at one end and a common base rail consisting of a steel plate or shape at the other end.

hooked boltcast-in anchor anchored mainly by bearing of the 90-degree bend (L-bolt) or 180-degree bend (J-bolt) against the concrete, at its embedded end, and having a minimum eh equal to 3da.

hoop—closed tie or continuously wound tie, made up of one or several reinforcement elements, each having seismic hooks at both ends. A closed tie shall not be made up of interlocking headed deformed bars. See 25.7.4.

inspection—observation, verification, and required documentation of the materials, installation, fabrication, erection, or placement of components and connections to determine compliance with construction documents and referenced standards.

inspection, continuous—the full-time observation, verification, and required documentation of work in the area where the work is being performed.

inspection, periodic—the part-time or intermittent observation, verification, and required documentation of work in the area where the work is being performed.

isolation joint—separation between adjoining parts of a concrete structure, usually a vertical plane at a designed location such as to interfere least with performance of the structure, yet such as to allow relative movement in three directions and avoid formation of cracks elsewhere in the concrete, and through which all or part of the bonded reinforcement is interrupted.

jacking force—in prestressed concrete, temporary force exerted by a device that introduces tension into prestressing reinforcement.

joint—portion of structure common to intersecting members

licensed design professional—an individual who is licensed to practice structural design as defined by the statutory requirements of the professional licensing laws of the state or jurisdiction in which the project is to be constructed, and who is in responsible charge of the structural design.

load—forces or other actions that result from the weight of all building materials, occupants, and their possessions, environmental effects, differential movement, and restrained dimensional changes; permanent loads are those loads in which variations over time are rare or of small magnitude; all other loads are variable loads.

load, dead—(a) the weights of the members, supported structure, and permanent attachments or accessories that are likely to be present on a structure in service; or (b) loads meeting specific criteria found in the general building code; without load factors.

load, factoredload, multiplied by appropriate load factors.

load, live—(a) load that is not permanently applied to a structure, but is likely to occur during the service life of the structure (excluding environmental loads); or (b) loads meeting specific criteria found in the general building code; without load factors.

load, roof live—a load on a roof produced: (a) during maintenance by workers, equipment, and materials, and (b) during the life of the structure by movable objects, such as planters or other similar small decorative appurtenances that are not occupancy related; or loads meeting specific criteria found in the general building code; without load factors.

load, service—all loads, static or transitory, imposed on a structure or element thereof, during the operation of a facility, without load factors.

load path—sequence of members and connections designed to transfer the factored loads and forces in such combinations as are stipulated in this Code, from the point of application or origination through the structure to the final support location or the foundation.

Manufacturer's Printed Installation Instructions (MPII)—published instructions for the correct installation of an adhesive anchor under all covered installation conditions as supplied in the product packaging.

modulus of elasticity—ratio of normal stress to corresponding strain for tensile or compressive stresses below proportional limit of material.

moment frame—frame in which beams, slabs, columns, and joints resist forces predominantly through flexure, shear, and axial force; beams or slabs are predominantly horizontal or nearly horizontal; columns are predominantly vertical or nearly vertical.

moment frame, intermediate—cast-in-place beam-column frame or two-way slab-column frame without beams complying with 18.4.

moment frame, ordinary—cast-in-place or precast concrete beam-column or slab-column frame complying with 18.3.

moment frame, special—cast-in-place beam-column frame complying with 18.2.3 through 18.2.8; and 18.6 through 18.8. A precast beam-column frame complying with 18.2.3 through 18.2.8 and 18.9.

net tensile strain—the tensile strain at nominal strength exclusive of strains due to effective prestress, creep, shrinkage, and temperature.

nodal zone—volume of concrete around a node that is assumed to transfer strut-and-tie forces through the node.

node—point in a strut-and-tie model where the axes of the struts, ties, and concentrated forces acting on the joint intersect.

one-way construction—members designed to be capable of supporting all loads through bending in a single direction; see also two-way construction.

ORDINARY PRECAST STRUCTURAL WALL. A precast wall complying with the requirements of Chapters 1 through 13, 15, 16 and 19 through 26.

ORDINARY REINFORCED CONCRETE STRUCTURAL WALL.cast-in-place wall complying with the requirements of Chapters 1 through 13, 15, 16 and 19 through 26.

ORDINARY STRUCTURAL PLAIN CONCRETE WALL. A wall complying with the requirements of Chapter 14excluding 14.6.2.

pedestal—member with a ratio of height-to-least lateral dimension less than or equal to 3 used primarily to support axial compressive load; for a tapered member, the least lateral dimension is the average of the top and bottom dimensions of the smaller side.

plastic hinge region—length of frame element over which flexural yielding is intended to occur due to earthquake design displacements, extending not less than a distance h from the critical section where flexural yielding initiates.

post-tensioning—method of prestressing in which prestressing reinforcement is tensioned after concrete has hardened.

precompressed tension zone—portion of a prestressed member where flexural tension, calculated using gross section properties, would occur under service loads if the prestress force was not present.

pretensioning—method of prestressing in which prestressing reinforcement is tensioned before concrete is cast.

projected areaarea on the free surface of the concrete member that is used to represent the greater base of the assumed rectilinear failure surface.

projected influence area—rectilinear area on the free surface of the concrete member that is used to calculate the bond strength of adhesive anchors.

pryout strength, concrete—strength corresponding to formation of a concrete spall behind short, stiff anchors displaced in the direction opposite to the applied shear force.

reinforcement—steel element or elements embedded in concrete and conforming to 20.2 through 20.5. Prestressed reinforcement in external tendons is also considered reinforcement.

reinforcement, anchor—reinforcement used to transfer the design load from the anchors into the structural member.

reinforcement, bonded prestressed—pretensioned reinforcement or prestressed reinforcement in a bonded tendon.

reinforcement, deformed—deformed bars, welded bar mats, deformed wire, and welded wire reinforcement conforming to 20.2.1.3, 20.2.1.5, or 20.2.1.7, excluding plain wire.

reinforcement, nonprestressed—bonded reinforcement that is not prestressed.

reinforcement, plain—bars or wires conforming to 20.2.1.4 or 20.2.1.7 that do not conform to definition of deformed reinforcement.

reinforcement, prestressedprestressing reinforcement that has been tensioned to impart forces to concrete.

reinforcement, prestressing—high-strength reinforcement such as strand, wire, or bar conforming to 20.3.1.

reinforcement, supplementaryreinforcement that acts to restrain the potential concrete breakout but is not designed to transfer the design load from the anchors into the structural member.

reinforcement, welded deformed steel bar mat—mat conforming to 20.2.1.5 consisting of two layers of deformed bars at right angles to each other welded at the intersections.

reinforcement, welded wire—plain or deformed wire fabricated into sheets or rolls conforming to 20.2.1.7.

Seismic Design Category—classification assigned to a structure based on its occupancy category and the severity of the design earthquake ground motion at the site, as defined by the general building code. Also denoted by the abbreviation SDC.

seismic-force-resisting system—portion of the structure designed to resist earthquake effects required by the general building code using the applicable provisions and load combinations.

seismic hook—hook on a stirrup, hoop, or crosstie having a bend not less than 135 degrees, except that circular hoops shall have a bend not less than 90 degrees; hooks shall have an extension of at least 6db, but not less than 3 in. The hooks shall engage the longitudinal reinforcement and the extension shall project into the interior of the stirrup or hoop.

shear cap—projection below the slab used to increase the slab shear strength.

sheathing—material encasing prestressing reinforcement to prevent bonding of the prestressing reinforcement with the surrounding concrete, to provide corrosion protection, and to contain the corrosion-inhibiting coating.

side-face blowout strength, concrete—strength of anchors with deep embedment and thin side-face cover such that spalling occurs on the side face around the embedded head without breakout occurring at the top concrete surface.

spacing—center-to-center distance between adjacent items, such as longitudinal reinforcement, transverse reinforcement, prestressing reinforcement, or anchors.

spacing, clear—least dimension between the outermost surfaces of adjacent items.

span length—distance between supports.

special seismic systems—structural systems that use special moment frames, special structural walls, or both.

specialty insert—predesigned and prefabricated cast-in anchors specifically designed for attachment of bolted or slotted connections.

SPECIAL STRUCTURAL WALL. A cast-in-place or precast wall complying with the requirements of 18.2.4 through 18.2.8, 18.10 and 18.11, as applicable, in addition to the requirements for ordinary reinforced concrete structural walls or ordinary precast structural walls, as applicable. Where ASCE 7 refers to a "special reinforced concrete structural wall," it shall be deemed to mean a "special structural wall."

spiral reinforcement—continuously wound reinforcement in the form of a cylindrical helix.

splitting tensile strength (fct)—tensile strength of concrete determined in accordance with ASTM C496 as described in ASTM C330.

steel element, brittle—element with a tensile test elongation of less than 14 percent, or reduction in area of less than 30 percent at failure.

steel element, ductile—element with a tensile test elongation of at least 14 percent and reduction in area of at least 30 percent; steel element meeting the requirements of ASTM A307 shall be considered ductile; except as modified by for earthquake effects, deformed reinforcing bars meeting the requirements of ASTM A615, A706, or A955 shall be considered as ductile steel elements.

stirrupreinforcement used to resist shear and torsion forces in a member; typically deformed bars, deformed wires, or welded wire reinforcement either single leg or bent into L, U, or rectangular shapes and located perpendicular to, or at an angle to, longitudinal reinforcement. See also tie.

strength, designnominal strength multiplied by a strength reduction factor ϕ.

strength, nominal—strength of a member or cross section calculated in accordance with provisions and assumptions of the strength design method of this Code before application of any strength reduction factors.

strength, required—strength of a member or cross section required to resist factored loads or related internal moments and forces in such combinations as stipulated in this Code.

stretch length—length of anchor, extending beyond concrete in which it is anchored, subject to full tensile load applied to anchor, and for which cross-sectional area is minimum and constant.

structural concreteconcrete used for structural purposes, including plain and reinforced concrete.

structural diaphragm—member, such as a floor or roof slab, that transmits forces acting in the plane of the member to vertical elements of the lateral-force-resisting system. A structural diaphragm may include chords and collectors as part of the diaphragm.

structural integrity—ability of a structure through strength, redundancy, ductility, and detailing of reinforcement to redistribute stresses and maintain overall stability if localized damage or significant overstress occurs.

structural system—interconnected members designed to meet performance requirements.

structural truss—assemblage of reinforced concrete members subjected primarily to axial forces.

structural wallwall proportioned to resist combinations of shears, moments, and axial forces in the plane of the wall; a shear wall is a structural wall.

structural wall, ordinary reinforced concrete—a wall complying with Chapter 11.

structural wall, ordinary plain concrete—a wall complying with Chapter 14.

structural wall, intermediate precast—a wall complying with 18.5.

structural wall, special—a cast-in-place structural wall in accordance with 18.2.3 through 18.2.8 and 18.10; or a precast structural wall in accordance with 18.2.3 through 18.2.8 and 18.11.

strut—compression member in a strut-and-tie model representing the resultant of a parallel or a fan-shaped compression field.

strut, bottle-shapedstrut that is wider at mid-length than at its ends.

strut-and-tie model—truss model of a member or of a D-region in such a member, made up of struts and ties connected at nodes and capable of transferring the factored loads to the supports or to adjacent B-regions.

tendon—in post-tensioned members, a tendon is a complete assembly consisting of anchorages, prestressing reinforcement, and sheathing with coating for unbonded applications or ducts filled with grout for bonded applications.

tendon, bondedtendon in which prestressed reinforcement is continuously bonded to the concrete through grouting of ducts embedded within the concrete cross section.

tendon, external—a tendon external to the member concrete cross section in post-tensioned applications.

tendon, unbondedtendon in which prestressed reinforcement is prevented from bonding to the concrete. The prestressing force is permanently transferred to the concrete at the tendon ends by the anchorages only.

tension-controlled section—a cross section in which the net tensile strain in the extreme tension steel at nominal strength is greater than or equal to 0.005.

tie—(a) loop of reinforcing bar or wire enclosing longitudinal reinforcement; a continuously wound transverse bar or wire in the form of a circle, rectangle, or other polygonal shape without reentrant corners enclosing longitudinal reinforcement; see also stirrup, hoop; (b) tension element in a strut-and-tie model.

transfer—act of transferring stress in prestressing reinforcement from jacks or pretensioning bed to concrete member.

transfer length—length of embedded pretensioned reinforcement required to transfer the effective prestress to the concrete.

two-way construction—members designed to be capable of supporting loads through bending in two directions; some slabs and foundations are considered two-way construction. See also one-way construction.

wall—a vertical element designed to resist axial load, lateral load, or both, with a horizontal length-to-thickness ratio greater than 3, used to enclose or separate spaces.

wall segment—portion of wall bounded by vertical or horizontal openings or edges.

wall segment, horizontal—segment of a structural wall, bounded vertically by two openings or by an opening and an edge.

wall segment, vertical—segment of a structural wall, bounded horizontally by two openings or by an opening and an edge; wall piers are vertical wall segments.

wall pier—a vertical wall segment within a structural wall, bounded horizontally by two openings or by an opening and an edge, with ratio of horizontal length to wall thickness (w/bw) less than or equal to 6.0, and ratio of clear height to horizontal length (hw/w) greater than or equal to 2.0.

water-cementitious materials ratio—ratio of mass of water, excluding that absorbed by the aggregate, to the mass of cementitious materials in a mixture, stated as a decimal.

work—the entire construction or separately identifiable parts thereof that are required to be furnished under the construction documents.

yield strength—specified minimum yield strength or yield point of reinforcement; yield strength or yield point shall be determined in tension according to applicable ASTM standards as modified by this Code.

UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING