The provisions of
Chapter 13 shall govern the materials, design, construction and installation of systems for the collection, storage, treatment and distribution of
nonpotable water . The use and application of
nonpotable water shall comply with laws, rules and ordinances applicable in the jurisdiction.
Nonpotable water for each end use application shall meet the minimum water quality requirements as established for the intended application by the laws, rules and ordinances applicable in the jurisdiction. Where
nonpotable water from different sources is
combined in a system, the system shall comply with the most stringent of the requirements of this code that are applicable to such sources.
Where chlorine is used for disinfection, the nonpotable water shall contain not more than 4 ppm (4mg/L) of chloramines or free chlorine when tested in accordance with ASTM D1253. Where ozone is used for disinfection, the nonpotable water shall not contain gas bubbles having elevated levels of ozone at the point of use.
Exception: Reclaimed water sources shall not be required to comply with these requirements.
Nonpotable water utilized for water closet and urinal flushing applications shall be filtered by a 100-micron or finer filter.
Exception: Reclaimed water sources shall not be required to comply with these requirements.
Nonpotable water outlets such as hose connections, open ended pipes and faucets shall be identified at the point of use for each outlet with signage that reads as follows: "Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER — DO NOT DRINK." The words shall be legibly and indelibly printed on a tag or sign constructed of corrosion-resistant waterproof material or shall be indelibly printed on the fixture. The letters of the words shall be not less than 0.5 inch (12.7 mm) in height and in colors in contrast to the background on which they are applied. In addition to the required wordage, the pictograph shown in Figure 1301.3 shall appear on the signage required by this section.
FIGURE 1301.3
PICTOGRAPH—DO NOT DRINK
Permits shall be required for the construction, installation, alteration and repair of
nonpotable water systems.
Construction documents , engineering calculations, diagrams and other such data pertaining to the
nonpotable water system shall be submitted with each permit application.
AMENDMENT
This section has been amended at the state or city level.
The existence of a
nonpotable water system shall be recorded on the deed of ownership for the property. The certificate of
occupancy shall not be issued until the documentation for the recording required under this section is completed by the property owner.
Piping,
plumbing components and materials used in collection and conveyance systems shall be of material approved by the manufacturer for the intended application.
The system shall be protected to prevent the entrance of insects and vermin into storage tanks and piping systems. Screen materials shall be compatible with contacting system components and shall not accelerate the corrosion of system components.
Where sustained freezing temperatures occur, provisions shall be made to keep storage tanks and the related piping from freezing.
Any storage tank or portion thereof that is above grade shall be protected from direct exposure to sunlight by one of the following methods:
Tank construction using opaque, UV-resistant materials such as heavily tinted plastic, fiberglass, lined metal, concrete, wood, or painted to prevent algae growth. Specially constructed sun barriers. Installation in garages, crawl spaces or sheds.
Where collected on site, water shall be collected in an
approved tank constructed of durable, nonabsorbent and corrosion-resistant materials. The storage tank shall be constructed of materials compatible with any disinfection systems used to treat water upstream of the tank and with any systems used to maintain water quality in the tank. Wooden storage tanks that are not equipped with a makeup water source shall be provided with a
flexible liner.
Storage tanks shall be supported on a firm base capable of withstanding the weight of the storage tank when filled to capacity. Storage tanks shall be supported in accordance with the
International Building Code .
Where the soil can become saturated, an underground storage tank shall be ballasted, or otherwise secured, to prevent the tank from floating out of the ground when empty. The
combined weight of the tank and hold down ballast shall meet or exceed the buoyancy force of the tank. Where the installation requires a foundation, the foundation shall be flat and shall be designed to support the weight of the storage tank when full, consistent with the bearing capability of adjacent soil.
Where installed below grade, storage tank installations shall be designed to withstand earth and surface structural loads without damage and with minimal deformation when empty or filled with water.
AMENDMENT
This section has been amended at the state or city level.
Where an uninterrupted supply is required for the intended application, potable or
reclaimed water shall be provided as a source of makeup water for the storage tank. The makeup water supply shall be protected against
backflow by a reduced pressure backflow prevention assembly or an air gap installed in accordance with
Section 608 . A
full-open valve located on the makeup water supply line to the storage tank shall be provided. Inlets to the storage tank shall be controlled by
fill valves or other automatic supply valves installed to prevent the tank from overflowing and to prevent the water level from dropping below a predetermined point. Where makeup water is provided, the water level shall not be permitted to drop below the source water inlet or the intake of any attached pump.
The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in
Table 606.5.4 . The overflow pipe shall be protected from insects or vermin and shall discharge in a manner consistent with
storm water runoff requirements of the jurisdiction. The overflow pipe shall discharge at a sufficient distance from the tank to avoid damaging the tank foundation or the adjacent property.
Drainage from overflow pipes shall be directed to prevent freezing on roof walkways. The overflow
drain shall not be equipped with a shutoff valve. A
cleanout shall be provided on each overflow pipe in accordance with
Section 708 .
Not less than one access opening shall be provided to allow inspection and cleaning of the tank interior. Access openings shall have an approved locking device or other approved method of securing access . Below-grade storage tanks, located outside of the building, shall be provided with a manhole either not less than 24 inches (610 mm) square or with an inside diameter not less than 24 inches (610 mm). Manholes shall extend not less than 4 inches (102 mm) above ground or shall be designed to prevent water infiltration. Finished grade shall be sloped away from the manhole to divert surface water. Manhole covers shall be secured to prevent unauthorized access . Service ports in manhole covers shall be not less than 8 inches (203 mm) in diameter and shall be not less than 4 inches (102 mm) above the finished grade level. The service port shall be secured to prevent unauthorized access .
Exception: Treated-water storage tanks that are less than 800 gallons (3028 L) in volume and installed below grade shall not be required to be equipped with a manhole provided that the tank has a service port of not less than 8 inches (203 mm) in diameter.
Storage tanks shall be provided with a vent sized in accordance with
Chapter 9 and based on the aggregate diameter of all tank influent pipes. The reservoir vent shall not be connected to
sanitary drainage system vents. Vents shall be protected from
contamination by means of an
approved cap or U-bend installed with the opening directed downward. Vent outlets shall extend not less than 4 inches (102 mm) above grade or as necessary to prevent surface water from entering the storage tank. Vent openings shall be protected against the entrance of vermin and insects in accordance with the requirements of
Section 1301.7 .
Tanks shall be provided with a means of emptying the contents for the purpose of service or cleaning. Tanks shall be drained by using a pump or by a
drain located at the lowest point in the tank. The tank
drain pipe shall discharge as required for overflow pipes and shall not be smaller in size than specified in
Table 606.5.7 . Not less than one
cleanout shall be provided on each
drain pipe in accordance with
Section 708 .
Each
nonpotable water storage tank shall be labeled with its rated capacity. The contents of storage tanks shall be identified with the words "CAUTION:
NONPOTABLE WATER — DO NOT DRINK." Where an opening is provided that could allow the entry of personnel, the opening shall be marked with the words, "DANGER — CONFINED SPACE." Markings shall be indelibly printed on the tank or on a tag or sign constructed of corrosion-resistant waterproof material that is mounted on the tank. The letters of the words shall be not less than 0.5 inch (12.7 mm) in height and shall be of a color in contrast with the background on which they are applied.
Storage tanks shall be tested in accordance with the following:
Storage tanks shall be filled with water to the overflow line prior to and during inspection. Seams and joints shall be left exposed and the tank shall remain water tight without leakage for a period of 24 hours.
After 24 hours, supplemental water shall be introduced for a period of 15 minutes to verify proper drainage of the overflow system and that there are no leaks. The tank drain shall be observed for proper operation. The makeup water system shall be observed for proper operation and successful automatic shutoff of the system at the refill threshold shall be verified.
If the owner of an on-site nonpotable water reuse system or rainwater collection and conveyance system elects to cease use of, or fails to properly maintain such system, the system shall be abandoned and shall comply with the following:
All system piping connecting to a utility-provided water system shall be removed or disabled. The distribution piping system shall be replaced with an approved potable water supply piping system. Where an existing potable pipe system is already in place, the fixtures shall be connected to the existing system. The storage tank shall be secured from accidental access by sealing or locking tank inlets and access points, or filling with sand or equivalent.
Nonpotable water collection and distribution piping and reclaimed water piping shall be separated from the building sewer and potable water piping underground by 5 feet (1524 mm) of undisturbed or compacted earth. Nonpotable water collection and distribution piping shall not be located in, under or above cesspools, septic tanks, septic tank drainage fields or seepage pits. Buried nonpotable water piping shall comply with the requirements of Section 306 .
Exceptions:
The required separation distance shall not apply where the bottom of the nonpotable water pipe within 5 feet (1524 mm) of the sewer is not less than 12 inches (305 mm) above the top of the highest point of the sewer and the pipe materials conform to Table 702.3 . The required separation distance shall not apply where the bottom of the potable water service pipe within 5 feet (1524 mm) of the nonpotable water pipe is not less than 12 inches (305 mm) above the top of the highest point of the nonpotable water pipe and the pipe materials comply with the requirements of Table 605.4 . Nonpotable water pipe is permitted to be located in the same trench with a building sewer , provided that such sewer is constructed of materials that comply with the requirements of Table 702.2 .The required separation distance shall not apply where a nonpotable water pipe crosses a sewer pipe, provided that the pipe is sleeved to not less than 5 feet (1524 mm) horizontally from the sewer pipe centerline on both sides of such crossing, with pipe materials that comply with Table 702.2 . The required separation distance shall not apply where a potable water service pipe crosses a nonpotable water pipe, provided that the potable water service pipe is sleeved for a distance of not less than 5 feet (1524 mm) horizontally from the centerline of the nonpotable pipe on both sides of such crossing, with pipe materials that comply with Table 702.2 . Irrigation piping located outside of a building and downstream of the backflow preventer is not required to meet the trenching requirements where nonpotable water is used for outdoor applications.
Sillcocks, hose bibbs, wall hydrants, yard hydrants and other outdoor outlets supplied by nonpotable water shall be located in a locked vault or shall be operable only by means of a removable key.
The provisions of ASTM E2635 and Section 1302 shall govern the construction, installation, alteration and repair of
on-site nonpotable water reuse systems for the collection, storage, treatment and distribution of on-site sources of
nonpotable water as permitted by the jurisdiction.
Collection piping conveying untreated water for reuse shall be installed in accordance with
Section 704 .
Collection piping conveying untreated water for reuse shall utilize
joints approved for use with the distribution piping and appropriate for the intended applications as specified in
Section 705 .
Collection piping conveying untreated water for reuse shall be sized in accordance with
drainage sizing requirements specified in
Section 710 .
Additional marking of collection piping conveying untreated water for reuse shall not be required beyond that required for
sanitary drainage ,
waste and vent piping by
Chapter 7 .
Untreated water collected for reuse shall be filtered as required for the intended end use. Filters shall be provided with
access for inspection and maintenance. Filters shall utilize a pressure gauge or other
approved method to provide indication when a filter requires servicing or replacement. Filters shall be installed with shutoff valves immediately upstream and downstream to allow for isolation during maintenance.
Where the intended application for
nonpotable water collected on site for reuse requires disinfection or other treatment or both, it shall be disinfected as needed to ensure that the required water quality is delivered at the point of use.
Nonpotable water collected on site containing untreated gray water shall be retained in collection reservoirs for not longer than 24 hours.
Gray water used for flushing water closets and urinals shall be disinfected and treated by an on-site water reuse treatment system complying with NSF 350.
Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table 1302.7.1 .
TABLE 1302.7.1
LOCATION OF NONPOTABLE WATER REUSE STORAGE TANKS
ELEMENT MINIMUM HORIZONTAL DISTANCE FROM STORAGE TANK (feet) Critical root zone (CRZ) of protected trees 2 Lot line adjoining private lots 5 Seepage pits 5 Septic tanks 5 Water wells 50 Streams and lakes 50 Water service 5 Public water main 10
For SI: 1 foot = 304.8 mm.
Outlets shall be located not less than 4 inches (102 mm) above the bottom of the storage tank and shall not skim water from the surface.
One three-way diverter valve listed and labeled to NSF 50 or other approved device shall be installed on collection piping upstream of each storage tank, or drainfield, as applicable, to divert untreated on-site reuse sources to the
sanitary sewer to allow servicing and inspection of the system. Bypass valves shall be installed downstream of fixture
traps and vent connections. Bypass valves shall be marked to indicate the direction of flow, connection and storage tank or drainfield connection. Bypass valves shall be provided with
access that allows for removal. Two shutoff valves shall not be installed to serve as a bypass valve.
Mechanical equipment including pumps, valves and filters shall be easily accessible and removable in order to perform repair, maintenance and cleaning. The minimum flow rate and
flow pressure delivered by the pumping system shall be appropriate for the application and in accordance with
Section 604 .
Where the water pressure supplied by the pumping system exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the
nonpotable water distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with
Section 604.8 .
Distribution piping shall conform to the standards and requirements specified in
Section 605 .
On-site
nonpotable water reuse distribution piping systems shall be designed and sized in accordance with
Section 604 for the intended application.
Tests and inspections shall be performed in accordance with Sections
1302.12.1 through
1302.12.6 .
Drain ,
waste and vent piping used for on-site water reuse systems shall be tested in accordance with
Section 312 .
The testing of makeup water supply piping and distribution piping shall be conducted in accordance with
Section 312.5 .
Inlets and vents to the system shall be inspected to verify that each is protected to prevent the entrance of insects and vermin into the storage tank and piping systems in accordance with
Section 1301.7 .
The quality of the water for the intended application shall be verified at the point of use in accordance with the requirements of the jurisdiction.
Operation and maintenance materials shall be supplied with nonpotable on-site water reuse systems in accordance with Sections
1302.13.1 through
1302.13.4 .
A detailed operations and maintenance manual shall be supplied in hardcopy form with all systems.
The manual shall include a detailed system schematic, and the locations and a list of all system components, including manufacturer and model number.
The manual shall provide a schedule and procedures for all system components requiring periodic maintenance. Consumable parts, including filters, shall be noted along with part numbers.
The manual shall include system startup and shutdown procedures. The manual shall include detailed operating procedures for the system.
The provisions of
Section 1303 shall govern the construction, installation, alteration and repair of
rainwater collection and conveyance systems for the collection, storage, treatment and distribution of
rainwater for nonpotable applications, as permitted by the jurisdiction.
Rainwater shall be collected only from above-ground impervious roofing surfaces constructed from
approved materials and where
approved , vehicular parking or pedestrian walking surfaces.
Downspouts and
leaders shall be connected to a debris excluder or equivalent device that is designed to remove leaves, sticks, pine needles and similar debris to prevent such from entering the storage tank.
First-flush diverters shall operate automatically and shall not rely on manually operated valves or devices. Diverted
rainwater shall not be drained to the roof surface, and shall be discharged in a manner consistent with the
storm water runoff requirements of the jurisdiction. First-flush diverters shall be provided with
access for maintenance and service.
Gutters and down-spouts shall be constructed of materials that are compatible with the collection surface and the
rainwater quality for the desired end use.
Joints shall be water tight.
Roof gutters, leaders and rainwater collection piping shall slope continuously toward collection inlets. Gutters and downspouts shall have a slope of not less than 1 /8 inch per foot (10.4 mm/m) along their entire length, and shall not permit the collection or pooling of water at any point.
Exception: Siphonic drainage systems installed in accordance with the manufacturer's instructions shall not be required to have a slope .
Gutters and downspouts shall be installed and sized in accordance with
Section 1106.6 and local rainfall rates.
Cleanouts shall be provided in the water conveyance system to allow
access to all filters, flushes, pipes and downspouts.
Water drained from the roof washer or debris excluder shall not be drained to the
sanitary sewer . Such water shall be diverted from the storage tank and discharge in a location that will not cause erosion or damage to property in accordance with the
International Building Code . Roof washers and debris excluders shall be provided with an automatic means of self-draining between rain events, and shall not
drain onto roof surfaces.
Collection piping conveying captured
rainwater shall utilize
joints approved for use with the distribution piping and appropriate for the intended applications as specified in
Section 705 .
Collected
rainwater shall be filtered as required for the intended end use. Filters shall be provided with
access for inspection and maintenance. Filters shall utilize a pressure gauge or other
approved method to provide indication when a filter requires servicing or replacement. Filters shall be installed with shutoff valves installed immediately upstream and downstream to allow for isolation during maintenance.
Where the intended application for
rainwater requires disinfection or other treatment or both, it shall be disinfected as needed to ensure that the required water quality is delivered at the point of use. Where chlorine is used for disinfection or treatment, water shall be tested for residual chlorine in accordance with ASTM D1253. The levels of residual chlorine shall not exceed that allowed for the intended use in accordance with the requirements of the jurisdiction.
Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table 1303.10.1 .
TABLE 1303.10.1
LOCATION OF RAINWATER STORAGE TANKS
ELEMENT MINIMUM HORIZONTAL DISTANCE FROM STORAGE TANK (feet) Critical root zone (CRZ) of protected trees 2 Lot line adjoining private lots 5 Seepage pits 5 Septic tanks 5
For SI: 1 foot = 304.8 mm.
Storage tank inlets shall be designed to introduce collected
rainwater into the tank with minimum turbulence, and shall be located and designed to avoid agitating the contents of the storage tank.
Outlets shall be located not less than 4 inches (102 mm) above the bottom of the storage tank and shall not skim water from the surface.
Mechanical equipment including pumps, valves and filters shall be provided with
access that allows for removal in order to perform repair, maintenance and cleaning. The minimum flow rate and
flow pressure delivered by the pumping system shall be appropriate for the application and in accordance with
Section 604 .
Where the water pressure supplied by the pumping system exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the
rainwater distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with
Section 604.8 .
Distribution piping utilized in rainwater collection and conveyance systems shall comply with Sections 1303.14.1 through 1303.14.3 .
Exception: Irrigation piping located outside of the building and downstream of a backflow preventer .
Distribution piping systems shall be designed and sized in accordance with
Section 604 for the intended application.
Tests and inspections shall be performed in accordance with Sections
1303.15.1 through
1303.15.9 .
Roof gutters shall be inspected to verify that the installation and
slope is in accordance with
Section 1303.5.1 . Gutters shall be tested by pouring not less than 1 gallon (3.8 l) of water into the end of the gutter opposite the collection point. The gutter being tested shall not leak and shall not retain standing water.
First-flush diverters shall be tested by introducing water into the collection system upstream of the diverter. Proper diversion of the first amount of water shall be in accordance with the requirements of
Section 1303.4 .
The testing of makeup water supply piping and distribution piping shall be conducted in accordance with
Section 312.5 .
AMENDMENT
This section has been amended at the state or city level.
Testing of a
backflow prevention assembly shall be conducted in accordance with Sections
312.10.1 ,
312.10.2 , and
312.10.3 .
Inlets and vents to the system shall be inspected to verify that each is protected to prevent the entrance of insects and vermin into the storage tank and piping systems in accordance with
Section 1301.7 .
The quality of the water for the intended application shall be verified at the point of use in accordance with the requirements of the jurisdiction.
ASTM E2727 shall be used to determine what, if any, site conditions impact the quality of collected raw
rainwater and whether those site conditions require treatment of the raw water for the intended end use or make the water unsuitable for specific end uses.
Operation and maintenance manuals shall be supplied with
rainwater collection and conveyance systems in accordance with Sections
1303.16.1 through
1303.16.4 .
A detailed operations and maintenance manual shall be supplied in hardcopy form with all systems.
The manual shall include a detailed system schematic, and locations and a list of all system components, including manufacturer and model number.
The manual shall provide a maintenance schedule and procedures for all system components requiring periodic maintenance. Consumable parts, including filters, shall be noted along with part numbers.
The manual shall include system startup and shutdown procedures, as
well as detailed operating procedures.
The provisions of this section shall govern the construction, installation, alteration and repair of systems supplying nonpotable
reclaimed water .
Where the
reclaimed water pressure supplied to the building exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the
reclaimed water distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with
Section 604.8 .
Distribution piping systems shall be designed and sized in accordance with
Section 604 for the intended application.
Nonpotable distribution piping labeling and marking shall comply with
Section 608.9 .
Tests and inspections shall be performed in accordance with Sections
1304.4.1 and
1304.4.2 .