Climate zones from Figure R301.1 or Table R301.1 shall be used in determining the applicable requirements from Chapter 4. Locations not in Table R301.1 (outside the United States) shall be assigned a climate zone based on Section R301.3.
FIGURE R301.1 CLIMATE ZONES
TABLE R301.1 CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
Key: A ‒ Moist, B ‒ Dry, C ‒ Marine. Absence of moisture designation indicates moisture regime is irrelevant.
Asterisk (*) indicates a warm-humid location.
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
FIGURE R301.1 CLIMATE ZONES
TABLE R301.1 CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
Key: A ‒ Moist, B ‒ Dry, C ‒ Marine. Absence of moisture designation indicates moisture regime is irrelevant.
Asterisk (*) indicates a warm-humid location.
US STATES | ||||
ALABAMA | 3A Lee | 7 Kodiak Island | 3A Calhoun | 3A Monroe |
3A Limestone | 7 Lake and Peninsula | 4A Carroll | 3A Montgomery | |
3A Autauga* | 3A Lowndes* | 7 Matanuska-Susitna | 3A Chicot | 3A Nevada |
2A Baldwin* | 3A Macon* | 8 Nome | 3A Clark | 4A Newton |
3A Barbour* | 3A Madison | 8 North Slope | 3A Clay | 3A Ouachita |
3A Bibb | 3A Marengo* | 8 Northwest Arctic | 3A Cleburne | 3A Perry |
3A Blount | 3A Marion | 7 Prince of Wales | 3A Cleveland | 3A Phillips |
3A Bullock* | 3A Marshall | Outer Ketchikan | 3A Columbia* | 3A Pike |
3A Butler* | 2A Mobile* | 7 Sitka | 3A Conway | 3A Poinsett |
3A Calhoun | 3A Monroe* | 7 Skagway-Hoonah | 3A Craighead | 3A Polk |
3A Chambers | 3A Montgomery* | Angoon | 3A Crawford | 3A Pope |
3A Cherokee | 3A Morgan | 8 Southeast Fairbanks | 3A Crittenden | 3A Prairie |
3A Chilton | 3A Perry* | 7 Valdez-Cordova | 3A Cross | 3A Pulaski |
3A Choctaw* | 3A Pickens | 8 Wade Hampton | 3A Dallas | 3A Randolph |
3A Clarke* | 3A Pike* | 7 Wrangell-Petersburg | 3A Desha | 3A Saline |
3A Clay | 3A Randolph | 7 Yakutat | 3A Drew | 3A Scott |
3A Cleburne | 3A Russell* | 8 Yukon-Koyukuk | 3A Faulkner | 4A Searcy |
3A Coffee* | 3A Shelby | ARIZONA | 3A Franklin | 3A Sebastian |
3A Colbert | 3A St. Clair | 5B Apache | 4A Fulton | 3A Sevier* |
3A Conecuh* | 3A Sumter | 3B Cochise | 3A Garland | 3A Sharp |
3A Coosa | 3A Talladega | 5B Coconino | 3A Grant | 3A St. Francis |
3A Covington* | 3A Tallapoosa | 4B Gila | 3A Greene | 4A Stone |
3A Crenshaw* | 3A Tuscaloosa | 3B Graham | 3A Hempstead* | 3A Union* |
3A Cullman | 3A Walker | 3B Greenlee | 3A Hot Spring | 3A Van Buren |
3A Dale* | 3A Washington* | 2B La Paz | 3A Howard | 4A Washington |
3A Dallas* | 3A Wilcox* | 2B Maricopa | 3A Independence | 3A White |
3A DeKalb | 3A Winston | 3B Mohave | 4A Izard | 3A Woodruff |
3A Elmore* | ALASKA | 5B Navajo | 3A Jackson | 3A Yell |
3A Escambia* | 2B Pima | 3A Jefferson | CALIFORNIA | |
3A Etowah | 7 Aleutians East | 2B Pinal | 3A Johnson | |
3A Fayette | 7 Aleutians West | 3B Santa Cruz | 3A Lafayette* | 3C Alameda |
3A Franklin | 7 Anchorage | 4B Yavapai | 3A Lawrence | 6B Alpine |
3A Geneva* | 8 Bethel | 2B Yuma | 3A Lee | 4B Amador |
3A Greene | 7 Bristol Bay | ARKANSAS | 3A Lincoln | 3B Butte |
3A Hale | 7 Denali | 3A Little River* | 4B Calaveras | |
3A Henry* | 8 Dillingham | 3A Arkansas | 3A Logan | 3B Colusa |
3A Houston* | 8 Fairbanks North Star | 3A Ashley | 3A Lonoke | 3B Contra Costa |
3A Jackson | 7 Haines | 4A Baxter | 4A Madison | 4C Del Norte |
3A Jefferson | 7 Juneau | 4A Benton | 4A Marion | 4B El Dorado |
3A Lamar | 7 Kenai Peninsula | 4A Boone | 3A Miller* | 3B Fresno |
3A Lauderdale | 7 Ketchikan Gateway | 3A Bradley | 3A Mississippi | 3B Glenn |
3A Lawrence |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
4C Humboldt | 3B Yuba | 5B Montrose | 2A Escambia* | 2A Taylor* |
2B Imperial | COLORADO | 5B Morgan | 2A Flagler* | 2A Union* |
4B Inyo | 4B Otero | 2A Franklin* | 2A Volusia* | |
3B Kern | 5B Adams | 6B Ouray | 2A Gadsden* | 2A Wakulla* |
3B Kings | 6B Alamosa | 7 Park | 2A Gilchrist* | 2A Walton* |
4B Lake | 5B Arapahoe | 5B Phillips | 2A Glades* | 2A Washington* |
5B Lassen | 6B Archuleta | 7 Pitkin | 2A Gulf* | GEORGIA |
3B Los Angeles | 4B Baca | 5B Prowers | 2A Hamilton* | |
3B Madera | 5B Bent | 5B Pueblo | 2A Hardee* | 2A Appling* |
3C Marin | 5B Boulder | 6B Rio Blanco | 2A Hendry* | 2A Atkinson* |
4B Mariposa | 5B Broomfield | 7 Rio Grande | 2A Hernando* | 2A Bacon* |
3C Mendocino | 6B Chaffee | 7 Routt | 2A Highlands* | 2A Baker* |
3B Merced | 5B Cheyenne | 6B Saguache | 2A Hillsborough* | 3A Baldwin |
5B Modoc | 7 Clear Creek | 7 San Juan | 2A Holmes* | 4A Banks |
6B Mono | 6B Conejos | 6B San Miguel | 2A Indian River* | 3A Barrow |
3C Monterey | 6B Costilla | 5B Sedgwick | 2A Jackson* | 3A Bartow |
3C Napa | 5B Crowley | 7 Summit | 2A Jefferson* | 3A Ben Hill* |
5B Nevada | 6B Custer | 5B Teller | 2A Lafayette* | 2A Berrien* |
3B Orange | 5B Delta | 5B Washington | 2A Lake* | 3A Bibb |
3B Placer | 5B Denver | 5B Weld | 2A Lee* | 3A Bleckley* |
5B Plumas | 6B Dolores | 5B Yuma | 2A Leon* | 2A Brantley* |
3B Riverside | 5B Douglas | CONNECTICUT | 2A Levy* | 2A Brooks* |
3B Sacramento | 6B Eagle | 2A Liberty* | 2A Bryan* | |
3C San Benito | 5B Elbert | 5A (all) | 2A Madison* | 3A Bulloch* |
3B San Bernardino | 5B El Paso | DELAWARE | 2A Manatee* | 3A Burke |
3B San Diego | 5B Fremont | 2A Marion* | 3A Butts | |
3C San Francisco | 5B Garfield | 4A (all) | 2A Martin* | 3A Calhoun* |
3B San Joaquin | 5B Gilpin | DISTRICT OF COLUMBIA | 1A Miami-Dade* | 2A Camden* |
3C San Luis Obispo | 7 Grand | 1A Monroe* | 3A Candler* | |
3C San Mateo | 7 Gunnison | 4A (all) | 2A Nassau* | 3A Carroll |
3C Santa Barbara | 7 Hinsdale | FLORIDA | 2A Okaloosa* | 4A Catoosa |
3C Santa Clara | 5B Huerfano | 2A Okeechobee* | 2A Charlton* | |
3C Santa Cruz | 7 Jackson | 2A Alachua* | 2A Orange* | 2A Chatham* |
3B Shasta | 5B Jefferson | 2A Baker* | 2A Osceola* | 3A Chattahoochee* |
5B Sierra | 5B Kiowa | 2A Bay* | 2A Palm Beach* | 4A Chattooga |
5B Siskiyou | 5B Kit Carson | 2A Bradford* | 2A Pasco* | 3A Cherokee |
3B Solano | 7 Lake | 2A Brevard* | 2A Pinellas* | 3A Clarke |
3C Sonoma | 5B La Plata | 1A Broward* | 2A Polk* | 3A Clay* |
3B Stanislaus | 5B Larimer | 2A Calhoun* | 2A Putnam* | 3A Clayton |
3B Sutter | 4B Las Animas | 2A Charlotte* | 2A Santa Rosa* | 2A Clinch* |
3B Tehama | 5B Lincoln | 2A Citrus* | 2A Sarasota* | 3A Cobb |
4B Trinity | 5B Logan | 2A Clay* | 2A Seminole* | 3A Coffee* |
3B Tulare | 5B Mesa | 2A Collier* | 2A St. Johns* | 2A Colquitt* |
4B Tuolumne | 7 Mineral | 2A Columbia* | 2A St. Lucie* | 3A Columbia |
3C Ventura | 6B Moffat | 2A DeSoto* | 2A Sumter* | 2A Cook* |
3B Yolo | 5B Montezuma | 2A Dixie* | 2A Suwannee* | 3A Coweta |
2A Duval* |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
3A Crawford | 2A Lanier* | 3A Taylor* | 5B Cassia | 4A Crawford |
3A Crisp* | 3A Laurens* | 3A Telfair* | 6B Clark | 5A Cumberland |
4A Dade | 3A Lee* | 3A Terrell* | 5B Clearwater | 5A DeKalb |
4A Dawson | 2A Liberty* | 2A Thomas* | 6B Custer | 5A De Witt |
2A Decatur* | 3A Lincoln | 3A Tift* | 5B Elmore | 5A Douglas |
3A DeKalb | 2A Long* | 2A Toombs* | 6B Franklin | 5A DuPage |
3A Dodge* | 2A Lowndes* | 4A Towns | 6B Fremont | 5A Edgar |
3A Dooly* | 4A Lumpkin | 3A Treutlen* | 5B Gem | 4A Edwards |
3A Dougherty* | 3A Macon* | 3A Troup | 5B Gooding | 4A Effingham |
3A Douglas | 3A Madison | 3A Turner* | 5B Idaho | 4A Fayette |
3A Early* | 3A Marion* | 3A Twiggs* | 6B Jefferson | 5A Ford |
2A Echols* | 3A McDuffie | 4A Union | 5B Jerome | 4A Franklin |
2A Effingham* | 2A McIntosh* | 3A Upson | 5B Kootenai | 5A Fulton |
3A Elbert | 3A Meriwether | 4A Walker | 5B Latah | 4A Gallatin |
3A Emanuel* | 2A Miller* | 3A Walton | 6B Lemhi | 5A Greene |
2A Evans* | 2A Mitchell* | 2A Ware* | 5B Lewis | 5A Grundy |
4A Fannin | 3A Monroe | 3A Warren | 5B Lincoln | 4A Hamilton |
3A Fayette | 3A Montgomery* | 3A Washington | 6B Madison | 5A Hancock |
4A Floyd | 3A Morgan | 2A Wayne* | 5B Minidoka | 4A Hardin |
3A Forsyth | 4A Murray | 3A Webster* | 5B Nez Perce | 5A Henderson |
4A Franklin | 3A Muscogee | 3A Wheeler* | 6B Oneida | 5A Henry |
3A Fulton | 3A Newton | 4A White | 5B Owyhee | 5A Iroquois |
4A Gilmer | 3A Oconee | 4A Whitfield | 5B Payette | 4A Jackson |
3A Glascock | 3A Oglethorpe | 3A Wilcox* | 5B Power | 4A Jasper |
2A Glynn* | 3A Paulding | 3A Wilkes | 5B Shoshone | 4A Jefferson |
4A Gordon | 3A Peach* | 3A Wilkinson | 6B Teton | 5A Jersey |
2A Grady* | 4A Pickens | 3A Worth* | 5B Twin Falls | 5A Jo Daviess |
3A Greene | 2A Pierce* | HAWAII | 6B Valley | 4A Johnson |
3A Gwinnett | 3A Pike | 5B Washington | 5A Kane | |
4A Habersham | 3A Polk | 1A (all)* | ILLINOIS | 5A Kankakee |
4A Hall | 3A Pulaski* | IDAHO | 5A Kendall | |
3A Hancock | 3A Putnam | 5A Adams | 5A Knox | |
3A Haralson | 3A Quitman* | 5B Ada | 4A Alexander | 5A Lake |
3A Harris | 4A Rabun | 6B Adams | 4A Bond | 5A La Salle |
3A Hart | 3A Randolph* | 6B Bannock | 5A Boone | 4A Lawrence |
3A Heard | 3A Richmond | 6B Bear Lake | 5A Brown | 5A Lee |
3A Henry | 3A Rockdale | 5B Benewah | 5A Bureau | 5A Livingston |
3A Houston* | 3A Schley* | 6B Bingham | 5A Calhoun | 5A Logan |
3A Irwin* | 3A Screven* | 6B Blaine | 5A Carroll | 5A Macon |
3A Jackson | 2A Seminole* | 6B Boise | 5A Cass | 4A Macoupin |
3A Jasper | 3A Spalding | 6B Bonner | 5A Champaign | 4A Madison |
2A Jeff Davis* | 4A Stephens | 6B Bonneville | 4A Christian | 4A Marion |
3A Jefferson | 3A Stewart* | 6B Boundary | 5A Clark | 5A Marshall |
3A Jenkins* | 3A Sumter* | 6B Butte | 4A Clay | 5A Mason |
3A Johnson* | 3A Talbot | 6B Camas | 4A Clinton | 4A Massac |
3A Jones | 3A Taliaferro | 5B Canyon | 5A Coles | 5A McDonough |
3A Lamar | 2A Tattnall* | 6B Caribou | 5A Cook | 5A McHenry |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
5A McLean | 5A Boone | 5A Miami | 5A Appanoose | 5A Jasper |
5A Menard | 4A Brown | 4A Monroe | 5A Audubon | 5A Jefferson |
5A Mercer | 5A Carroll | 5A Montgomery | 5A Benton | 5A Johnson |
4A Monroe | 5A Cass | 5A Morgan | 6A Black Hawk | 5A Jones |
4A Montgomery | 4A Clark | 5A Newton | 5A Boone | 5A Keokuk |
5A Morgan | 5A Clay | 5A Noble | 6A Bremer | 6A Kossuth |
5A Moultrie | 5A Clinton | 4A Ohio | 6A Buchanan | 5A Lee |
5A Ogle | 4A Crawford | 4A Orange | 6A Buena Vista | 5A Linn |
5A Peoria | 4A Daviess | 5A Owen | 6A Butler | 5A Louisa |
4A Perry | 4A Dearborn | 5A Parke | 6A Calhoun | 5A Lucas |
5A Piatt | 5A Decatur | 4A Perry | 5A Carroll | 6A Lyon |
5A Pike | 5A De Kalb | 4A Pike | 5A Cass | 5A Madison |
4A Pope | 5A Delaware | 5A Porter | 5A Cedar | 5A Mahaska |
4A Pulaski | 4A Dubois | 4A Posey | 6A Cerro Gordo | 5A Marion |
5A Putnam | 5A Elkhart | 5A Pulaski | 6A Cherokee | 5A Marshall |
4A Randolph | 5A Fayette | 5A Putnam | 6A Chickasaw | 5A Mills |
4A Richland | 4A Floyd | 5A Randolph | 5A Clarke | 6A Mitchell |
5A Rock Island | 5A Fountain | 4A Ripley | 6A Clay | 5A Monona |
4A Saline | 5A Franklin | 5A Rush | 6A Clayton | 5A Monroe |
5A Sangamon | 5A Fulton | 4A Scott | 5A Clinton | 5A Montgomery |
5A Schuyler | 4A Gibson | 5A Shelby | 5A Crawford | 5A Muscatine |
5A Scott | 5A Grant | 4A Spencer | 5A Dallas | 6A O'Brien |
4A Shelby | 4A Greene | 5A Starke | 5A Davis | 6A Osceola |
5A Stark | 5A Hamilton | 5A Steuben | 5A Decatur | 5A Page |
4A St. Clair | 5A Hancock | 5A St. Joseph | 6A Delaware | 6A Palo Alto |
5A Stephenson | 4A Harrison | 4A Sullivan | 5A Des Moines | 6A Plymouth |
5A Tazewell | 5A Hendricks | 4A Switzerland | 6A Dickinson | 6A Pocahontas |
4A Union | 5A Henry | 5A Tippecanoe | 5A Dubuque | 5A Polk |
5A Vermilion | 5A Howard | 5A Tipton | 6A Emmet | 5A Pottawattamie |
4A Wabash | 5A Huntington | 5A Union | 6A Fayette | 5A Poweshiek |
5A Warren | 4A Jackson | 4A Vanderburgh | 6A Floyd | 5A Ringgold |
4A Washington | 5A Jasper | 5A Vermillion | 6A Franklin | 6A Sac |
4A Wayne | 5A Jay | 5A Vigo | 5A Fremont | 5A Scott |
4A White | 4A Jefferson | 5A Wabash | 5A Greene | 5A Shelby |
5A Whiteside | 4A Jennings | 5A Warren | 6A Grundy | 6A Sioux |
5A Will | 5A Johnson | 4A Warrick | 5A Guthrie | 5A Story |
4A Williamson | 4A Knox | 4A Washington | 6A Hamilton | 5A Tama |
5A Winnebago | 5A Kosciusko | 5A Wayne | 6A Hancock | 5A Taylor |
5A Woodford | 5A LaGrange | 5A Wells | 6A Hardin | 5A Union |
INDIANA | 5A Lake | 5A White | 5A Harrison | 5A Van Buren |
5A LaPorte | 5A Whitley | 5A Henry | 5A Wapello | |
5A Adams | 4A Lawrence | IOWA | 6A Howard | 5A Warren |
5A Allen | 5A Madison | 6A Humboldt | 5A Washington | |
5A Bartholomew | 5A Marion | 5A Adair | 6A Ida | 5A Wayne |
5A Benton | 5A Marshall | 5A Adams | 5A Iowa | 6A Webster |
5A Blackford | 4A Martin | 6A Allamakee | 5A Jackson | 6A Winnebago |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
6A Winneshiek | 4A Haskell | 4A Sedgwick | 2A Iberville* | 6A Cumberland |
5A Woodbury | 4A Hodgeman | 4A Seward | 3A Jackson* | 6A Franklin |
6A Worth | 4A Jackson | 4A Shawnee | 2A Jefferson* | 6A Hancock |
6A Wright | 4A Jefferson | 5A Sheridan | 2A Jefferson Davis* | 6A Kennebec |
KANSAS | 5A Jewell | 5A Sherman | 2A Lafayette* | 6A Knox |
4A Johnson | 5A Smith | 2A Lafourche* | 6A Lincoln | |
4A Allen | 4A Kearny | 4A Stafford | 3A La Salle* | 6A Oxford |
4A Anderson | 4A Kingman | 4A Stanton | 3A Lincoln* | 6A Penobscot |
4A Atchison | 4A Kiowa | 4A Stevens | 2A Livingston* | 6A Piscataquis |
4A Barber | 4A Labette | 4A Sumner | 3A Madison* | 6A Sagadahoc |
4A Barton | 5A Lane | 5A Thomas | 3A Morehouse | 6A Somerset |
4A Bourbon | 4A Leavenworth | 5A Trego | 3A Natchitoches* | 6A Waldo |
4A Brown | 4A Lincoln | 4A Wabaunsee | 2A Orleans* | 6A Washington |
4A Butler | 4A Linn | 5A Wallace | 3A Ouachita* | 6A York |
4A Chase | 5A Logan | 4A Washington | 2A Plaquemines* | MARYLAND |
4A Chautauqua | 4A Lyon | 5A Wichita | 2A Pointe Coupee* | |
4A Cherokee | 4A Marion | 4A Wilson | 2A Rapides* | 4A Allegany |
5A Cheyenne | 4A Marshall | 4A Woodson | 3A Red River* | 4A Anne Arundel |
4A Clark | 4A McPherson | 4A Wyandotte | 3A Richland* | 4A Baltimore |
4A Clay | 4A Meade | KENTUCKY | 3A Sabine* | 4A Baltimore (city) |
5A Cloud | 4A Miami | 2A St. Bernard* | 4A Calvert | |
4A Coffey | 5A Mitchell | 4A (all) | 2A St. Charles* | 4A Caroline |
4A Comanche | 4A Montgomery | LOUISIANA | 2A St. Helena* | 4A Carroll |
4A Cowley | 4A Morris | 2A St. James* | 4A Cecil | |
4A Crawford | 4A Morton | 2A Acadia* | 2A St. John the | 4A Charles |
5A Decatur | 4A Nemaha | 2A Allen* | Baptist* | 4A Dorchester |
4A Dickinson | 4A Neosho | 2A Ascension* | 2A St. Landry* | 4A Frederick |
4A Doniphan | 5A Ness | 2A Assumption* | 2A St. Martin* | 5A Garrett |
4A Douglas | 5A Norton | 2A Avoyelles* | 2A St. Mary* | 4A Harford |
4A Edwards | 4A Osage | 2A Beauregard* | 2A St. Tammany* | 4A Howard |
4A Elk | 5A Osborne | 3A Bienville* | 2A Tangipahoa* | 4A Kent |
5A Ellis | 4A Ottawa | 3A Bossier* | 3A Tensas* | 4A Montgomery |
4A Ellsworth | 4A Pawnee | 3A Caddo* | 2A Terrebonne* | 4A Prince George's |
4A Finney | 5A Phillips | 2A Calcasieu* | 3A Union* | 4A Queen Anne's |
4A Ford | 4A Pottawatomie | 3A Caldwell* | 2A Vermilion* | 4A Somerset |
4A Franklin | 4A Pratt | 2A Cameron* | 3A Vernon* | 4A St. Mary's |
4A Geary | 5A Rawlins | 3A Catahoula* | 2A Washington* | 4A Talbot |
5A Gove | 4A Reno | 3A Claiborne* | 3A Webster* | 4A Washington |
5A Graham | 5A Republic | 3A Concordia* | 2A West Baton | 4A Wicomico |
4A Grant | 4A Rice | 3A De Soto* | Rouge* | 4A Worcester |
4A Gray | 4A Riley | 2A East Baton Rouge* | 3A West Carroll | MASSACHSETTS |
5A Greeley | 5A Rooks | 3A East Carroll | 2A West Feliciana* | |
4A Greenwood | 4A Rush | 2A East Feliciana* | 3A Winn* | 5A (all) |
5A Hamilton | 4A Russell | 2A Evangeline* | MAINE | MICHIGAN |
4A Harper | 4A Saline | 3A Franklin* | ||
4A Harvey | 5A Scott | 3A Grant* | 6A Androscoggin | 6A Alcona |
2A Iberia* | 7 Aroostook | 6A Alger |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
5A Allegan | 7 Mackinac | 6A Carver | 7 Otter Tail | 3A Clarke |
6A Alpena | 5A Macomb | 7 Cass | 7 Pennington | 3A Clay |
6A Antrim | 6A Manistee | 6A Chippewa | 7 Pine | 3A Coahoma |
6A Arenac | 6A Marquette | 6A Chisago | 6A Pipestone | 3A Copiah* |
7 Baraga | 6A Mason | 7 Clay | 7 Polk | 3A Covington* |
5A Barry | 6A Mecosta | 7 Clearwater | 6A Pope | 3A DeSoto |
5A Bay | 6A Menominee | 7 Cook | 6A Ramsey | 3A Forrest* |
6A Benzie | 5A Midland | 6A Cottonwood | 7 Red Lake | 3A Franklin* |
5A Berrien | 6A Missaukee | 7 Crow Wing | 6A Redwood | 3A George* |
5A Branch | 5A Monroe | 6A Dakota | 6A Renville | 3A Greene* |
5A Calhoun | 5A Montcalm | 6A Dodge | 6A Rice | 3A Grenada |
5A Cass | 6A Montmorency | 6A Douglas | 6A Rock | 2A Hancock* |
6A Charlevoix | 5A Muskegon | 6A Faribault | 7 Roseau | 2A Harrison* |
6A Cheboygan | 6A Newaygo | 6A Fillmore | 6A Scott | 3A Hinds* |
7 Chippewa | 5A Oakland | 6A Freeborn | 6A Sherburne | 3A Holmes |
6A Clare | 6A Oceana | 6A Goodhue | 6A Sibley | 3A Humphreys |
5A Clinton | 6A Ogemaw | 7 Grant | 6A Stearns | 3A Issaquena |
6A Crawford | 7 Ontonagon | 6A Hennepin | 6A Steele | 3A Itawamba |
6A Delta | 6A Osceola | 6A Houston | 6A Stevens | 2A Jackson* |
6A Dickinson | 6A Oscoda | 7 Hubbard | 7 St. Louis | 3A Jasper |
5A Eaton | 6A Otsego | 6A Isanti | 6A Swift | 3A Jefferson* |
6A Emmet | 5A Ottawa | 7 Itasca | 6A Todd | 3A Jefferson Davis* |
5A Genesee | 6A Presque Isle | 6A Jackson | 6A Traverse | 3A Jones* |
6A Gladwin | 6A Roscommon | 7 Kanabec | 6A Wabasha | 3A Kemper |
7 Gogebic | 5A Saginaw | 6A Kandiyohi | 7 Wadena | 3A Lafayette |
6A Grand Traverse | 6A Sanilac | 7 Kittson | 6A Waseca | 3A Lamar* |
5A Gratiot | 7 Schoolcraft | 7 Koochiching | 6A Washington | 3A Lauderdale |
5A Hillsdale | 5A Shiawassee | 6A Lac qui Parle | 6A Watonwan | 3A Lawrence* |
7 Houghton | 5A St. Clair | 7 Lake | 7 Wilkin | 3A Leake |
6A Huron | 5A St. Joseph | 7 Lake of the Woods | 6A Winona | 3A Lee |
5A Ingham | 5A Tuscola | 6A Le Sueur | 6A Wright | 3A Leflore |
5A Ionia | 5A Van Buren | 6A Lincoln | 6A Yellow | 3A Lincoln* |
6A Iosco | 5A Washtenaw | 6A Lyon | Medicine | 3A Lowndes |
7 Iron | 5A Wayne | 7 Mahnomen | MISSISSIPPI | 3A Madison |
6A Isabella | 6A Wexford | 7 Marshall | 3A Marion* | |
5A Jackson | MINNESOTA | 6A Martin | 3A Adams* | 3A Marshall |
5A Kalamazoo | 6A McLeod | 3A Alcorn | 3A Monroe | |
6A Kalkaska | 7 Aitkin | 6A Meeker | 3A Amite* | 3A Montgomery |
5A Kent | 6A Anoka | 7 Mille Lacs | 3A Attala | 3A Neshoba |
7 Keweenaw | 7 Becker | 6A Morrison | 3A Benton | 3A Newton |
6A Lake | 7 Beltrami | 6A Mower | 3A Bolivar | 3A Noxubee |
5A Lapeer | 6A Benton | 6A Murray | 3A Calhoun | 3A Oktibbeha |
6A Leelanau | 6A Big Stone | 6A Nicollet | 3A Carroll | 3A Panola |
5A Lenawee | 6A Blue Earth | 6A Nobles | 3A Chickasaw | 2A Pearl River* |
5A Livingston | 6A Brown | 7 Norman | 3A Choctaw | 3A Perry* |
7 Luce | 7 Carlton | 6A Olmsted | 3A Claiborne* | 3A Pike* |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
3A Pontotoc | 5A Chariton | 4A Mississippi | 4A Webster | 4A Cumberland |
3A Prentiss | 4A Christian | 4A Moniteau | 5A Worth | 4A Essex |
3A Quitman | 5A Clark | 4A Monroe | 4A Wright | 4A Gloucester |
3A Rankin* | 4A Clay | 4A Montgomery | MONTANA | 4A Hudson |
3A Scott | 5A Clinton | 4A Morgan | 5A Hunterdon | |
3A Sharkey | 4A Cole | 4A New Madrid | 6B (all) | 5A Mercer |
3A Simpson* | 4A Cooper | 4A Newton | NEBRASKA | 4A Middlesex |
3A Smith* | 4A Crawford | 5A Nodaway | 4A Monmouth | |
2A Stone* | 4A Dade | 4A Oregon | 5A (all) | 5A Morris |
3A Sunflower | 4A Dallas | 4A Osage | NEVADA | 4A Ocean |
3A Tallahatchie | 5A Daviess | 4A Ozark | 5A Passaic | |
3A Tate | 5A DeKalb | 4A Pemiscot | 5B Carson City (city) | 4A Salem |
3A Tippah | 4A Dent | 4A Perry | 5B Churchill | 5A Somerset |
3A Tishomingo | 4A Douglas | 4A Pettis | 3B Clark | 5A Sussex |
3A Tunica | 4A Dunklin | 4A Phelps | 5B Douglas | 4A Union |
3A Union | 4A Franklin | 5A Pike | 5B Elko | 5A Warren |
3A Walthall* | 4A Gasconade | 4A Platte | 5B Esmeralda | NEW MEXICO |
3A Warren* | 5A Gentry | 4A Polk | 5B Eureka | |
3A Washington | 4A Greene | 4A Pulaski | 5B Humboldt | 4B Bernalillo |
3A Wayne* | 5A Grundy | 5A Putnam | 5B Lander | 5B Catron |
3A Webster | 5A Harrison | 5A Ralls | 5B Lincoln | 3B Chaves |
3A Wilkinson* | 4A Henry | 4A Randolph | 5B Lyon | 4B Cibola |
3A Winston | 4A Hickory | 4A Ray | 5B Mineral | 5B Colfax |
3A Yalobusha | 5A Holt | 4A Reynolds | 5B Nye | 4B Curry |
3A Yazoo | 4A Howard | 4A Ripley | 5B Pershing | 4B DeBaca |
MISSOURI | 4A Howell | 4A Saline | 5B Storey | 3B Dona Ana |
4A Iron | 5A Schuyler | 5B Washoe | 3B Eddy | |
5A Adair | 4A Jackson | 5A Scotland | 5B White Pine | 4B Grant |
5A Andrew | 4A Jasper | 4A Scott | NEW HAMPSHIRE | 4B Guadalupe |
5A Atchison | 4A Jefferson | 4A Shannon | 5B Harding | |
4A Audrain | 4A Johnson | 5A Shelby | 6A Belknap | 3B Hidalgo |
4A Barry | 5A Knox | 4A St. Charles | 6A Carroll | 3B Lea |
4A Barton | 4A Laclede | 4A St. Clair | 5A Cheshire | 4B Lincoln |
4A Bates | 4A Lafayette | 4A St. Francois | 6A Coos | 5B Los Alamos |
4A Benton | 4A Lawrence | 4A St. Louis | 6A Grafton | 3B Luna |
4A Bollinger | 5A Lewis | 4A St. Louis (city) | 5A Hillsborough | 5B McKinley |
4A Boone | 4A Lincoln | 4A Ste. Genevieve | 6A Merrimack | 5B Mora |
5A Buchanan | 5A Linn | 4A Stoddard | 5A Rockingham | 3B Otero |
4A Butler | 5A Livingston | 4A Stone | 5A Strafford | 4B Quay |
5A Caldwell | 5A Macon | 5A Sullivan | 6A Sullivan | 5B Rio Arriba |
4A Callaway | 4A Madison | 4A Taney | NEW JERSEY | 4B Roosevelt |
4A Camden | 4A Maries | 4A Texas | 5B Sandoval | |
4A Cape Girardeau | 5A Marion | 4A Vernon | 4A Atlantic | 5B San Juan |
4A Carroll | 4A McDonald | 4A Warren | 5A Bergen | 5B San Miguel |
4A Carter | 5A Mercer | 4A Washington | 4A Burlington | 5B Santa Fe |
4A Cass | 4A Miller | 4A Wayne | 4A Camden | 4B Sierra |
4A Cedar | 4A Cape May | 4B Socorro |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
5B Taos | 4A Queens | 4A Clay | 4A Orange | 7 Divide |
5B Torrance | 5A Rensselaer | 4A Cleveland | 3A Pamlico | 6A Dunn |
4B Union | 4A Richmond | 3A Columbus* | 3A Pasquotank | 7 Eddy |
4B Valencia | 5A Rockland | 3A Craven | 3A Pender* | 6A Emmons |
NEW YORK | 5A Saratoga | 3A Cumberland | 3A Perquimans | 7 Foster |
5A Albany | 5A Schenectady | 3A Currituck | 4A Person | 6A Golden Valley |
6A Allegany | 6A Schoharie | 3A Dare | 3A Pitt | 7 Grand Forks |
4A Bronx | 6A Schuyler | 3A Davidson | 4A Polk | 6A Grant |
6A Broome | 5A Seneca | 4A Davie | 3A Randolph | 7 Griggs |
6A Cattaraugus | 6A Steuben | 3A Duplin | 3A Richmond | 6A Hettinger |
5A Cayuga | 6A St. Lawrence | 4A Durham | 3A Robeson | 7 Kidder |
5A Chautauqua | 4A Suffolk | 3A Edgecombe | 4A Rockingham | 6A LaMoure |
5A Chemung | 6A Sullivan | 4A Forsyth | 3A Rowan | 6A Logan |
6A Chenango | 5A Tioga | 4A Franklin | 4A Rutherford | 7 McHenry |
6A Clinton | 6A Tompkins | 3A Gaston | 3A Sampson | 6A McIntosh |
5A Columbia | 6A Ulster | 4A Gates | 3A Scotland | 6A McKenzie |
5A Cortland | 6A Warren | 4A Graham | 3A Stanly | 7 McLean |
6A Delaware | 5A Washington | 4A Granville | 4A Stokes | 6A Mercer |
5A Dutchess | 5A Wayne | 3A Greene | 4A Surry | 6A Morton |
5A Erie | 4A Westchester | 4A Guilford | 4A Swain | 7 Mountrail |
6A Essex | 6A Wyoming | 4A Halifax | 4A Transylvania | 7 Nelson |
6A Franklin | 5A Yates | 4A Harnett | 3A Tyrrell | 6A Oliver |
6A Fulton | NORTH CAROLINA | 4A Haywood | 3A Union | 7 Pembina |
5A Genesee | 4A Henderson | 4A Vance | 7 Pierce | |
5A Greene | 4A Hertford | 4A Wake | 7 Ramsey | |
6A Hamilton | 4A Alamance | 3A Hoke | 4A Warren | 6A Ransom |
6A Herkimer | 4A Alexander | 3A Hyde | 3A Washington | 7 Renville |
6A Jefferson | 5A Alleghany | 4A Iredell | 5A Watauga | 6A Richland |
4A Kings | 3A Anson | 4A Jackson | 3A Wayne | 7 Rolette |
6A Lewis | 5A Ashe | 3A Johnston | 4A Wilkes | 6A Sargent |
5A Livingston | 5A Avery | 3A Jones | 3A Wilson | 7 Sheridan |
6A Madison | 3A Beaufort | 4A Lee | 4A Yadkin | 6A Sioux |
5A Monroe | 4A Bertie | 3A Lenoir | 5A Yancey | 6A Slope |
6A Montgomery | 3A Bladen | 4A Lincoln | NORTH DAKOTA | 6A Stark |
4A Nassau | 3A Brunswick* | 4A Macon | 7 Steele | |
4A New York | 4A Buncombe | 4A Madison | 6A Adams | 7 Stutsman |
5A Niagara | 4A Burke | 3A Martin | 7 Barnes | 7 Towner |
6A Oneida | 3A Cabarrus | 4A McDowell | 7 Benson | 7 Traill |
5A Onondaga | 4A Caldwell | 3A Mecklenburg | 6A Billings | 7 Walsh |
5A Ontario | 3A Camden | 5A Mitchell | 7 Bottineau | 7 Ward |
5A Orange | 3A Carteret* | 3A Montgomery | 6A Bowman | 7 Wells |
5A Orleans | 4A Caswell | 3A Moore | 7 Burke | 7 Williams |
5A Oswego | 4A Catawba | 4A Nash | 6A Burleigh | OHIO |
6A Otsego | 4A Chatham | 3A New Hanover* | 7 Cass | |
5A Putnam | 4A Cherokee | 4A Northampton | 7 Cavalier | 4A Adams |
3A Chowan | 3A Onslow* | 6A Dickey | 5A Allen |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
5A Ashland | 5A Mahoning | 3A Bryan | 3A Okfuskee | 4C Linn |
5A Ashtabula | 5A Marion | 3A Caddo | 3A Oklahoma | 5B Malheur |
5A Athens | 5A Medina | 3A Canadian | 3A Okmulgee | 4C Marion |
5A Auglaize | 5A Meigs | 3A Carter | 3A Osage | 5B Morrow |
5A Belmont | 5A Mercer | 3A Cherokee | 3A Ottawa | 4C Multnomah |
4A Brown | 5A Miami | 3A Choctaw | 3A Pawnee | 4C Polk |
5A Butler | 5A Monroe | 4B Cimarron | 3A Payne | 5B Sherman |
5A Carroll | 5A Montgomery | 3A Cleveland | 3A Pittsburg | 4C Tillamook |
5A Champaign | 5A Morgan | 3A Coal | 3A Pontotoc | 5B Umatilla |
5A Clark | 5A Morrow | 3A Comanche | 3A Pottawatomie | 5B Union |
4A Clermont | 5A Muskingum | 3A Cotton | 3A Pushmataha | 5B Wallowa |
5A Clinton | 5A Noble | 3A Craig | 3A Roger Mills | 5B Wasco |
5A Columbiana | 5A Ottawa | 3A Creek | 3A Rogers | 4C Washington |
5A Coshocton | 5A Paulding | 3A Custer | 3A Seminole | 5B Wheeler |
5A Crawford | 5A Perry | 3A Delaware | 3A Sequoyah | 4C Yamhill |
5A Cuyahoga | 5A Pickaway | 3A Dewey | 3A Stephens | PENNSYLVANIA |
5A Darke | 4A Pike | 3A Ellis | 4B Texas | |
5A Defiance | 5A Portage | 3A Garfield | 3A Tillman | 5A Adams |
5A Delaware | 5A Preble | 3A Garvin | 3A Tulsa | 5A Allegheny |
5A Erie | 5A Putnam | 3A Grady | 3A Wagoner | 5A Armstrong |
5A Fairfield | 5A Richland | 3A Grant | 3A Washington | 5A Beaver |
5A Fayette | 5A Ross | 3A Greer | 3A Washita | 5A Bedford |
5A Franklin | 5A Sandusky | 3A Harmon | 3A Woods | 5A Berks |
5A Fulton | 4A Scioto | 3A Harper | 3A Woodward | 5A Blair |
4A Gallia | 5A Seneca | 3A Haskell | OREGON | 5A Bradford |
5A Geauga | 5A Shelby | 3A Hughes | 4A Bucks | |
5A Greene | 5A Stark | 3A Jackson | 5B Baker | 5A Butler |
5A Guernsey | 5A Summit | 3A Jefferson | 4C Benton | 5A Cambria |
4A Hamilton | 5A Trumbull | 3A Johnston | 4C Clackamas | 6A Cameron |
5A Hancock | 5A Tuscarawas | 3A Kay | 4C Clatsop | 5A Carbon |
5A Hardin | 5A Union | 3A Kingfisher | 4C Columbia | 5A Centre |
5A Harrison | 5A Van Wert | 3A Kiowa | 4C Coos | 4A Chester |
5A Henry | 5A Vinton | 3A Latimer | 5B Crook | 5A Clarion |
5A Highland | 5A Warren | 3A Le Flore | 4C Curry | 6A Clearfield |
5A Hocking | 4A Washington | 3A Lincoln | 5B Deschutes | 5A Clinton |
5A Holmes | 5A Wayne | 3A Logan | 4C Douglas | 5A Columbia |
5A Huron | 5A Williams | 3A Love | 5B Gilliam | 5A Crawford |
5A Jackson | 5A Wood | 3A Major | 5B Grant | 5A Cumberland |
5A Jefferson | 5A Wyandot | 3A Marshall | 5B Harney | 5A Dauphin |
5A Knox | OKLAHOMA | 3A Mayes | 5B Hood River | 4A Delaware |
5A Lake | 3A McClain | 4C Jackson | 6A Elk | |
4A Lawrence | 3A Adair | 3A McCurtain | 5B Jefferson | 5A Erie |
5A Licking | 3A Alfalfa | 3A McIntosh | 4C Josephine | 5A Fayette |
5A Logan | 3A Atoka | 3A Murray | 5B Klamath | 5A Forest |
5A Lorain | 4B Beaver | 3A Muskogee | 5B Lake | 5A Franklin |
5A Lucas | 3A Beckham | 3A Noble | 4C Lane | 5A Fulton |
5A Madison | 3A Blaine | 3A Nowata | 4C Lincoln | 5A Greene |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
5A Huntingdon | 3A Bamberg* | 5A Bennett | 6A Minnehaha | 4A Gibson |
5A Indiana | 3A Barnwell* | 5A Bon Homme | 6A Moody | 4A Giles |
5A Jefferson | 3A Beaufort* | 6A Brookings | 6A Pennington | 4A Grainger |
5A Juniata | 3A Berkeley* | 6A Brown | 6A Perkins | 4A Greene |
5A Lackawanna | 3A Calhoun | 6A Brule | 6A Potter | 4A Grundy |
5A Lancaster | 3A Charleston* | 6A Buffalo | 6A Roberts | 4A Hamblen |
5A Lawrence | 3A Cherokee | 6A Butte | 6A Sanborn | 4A Hamilton |
5A Lebanon | 3A Chester | 6A Campbell | 6A Shannon | 4A Hancock |
5A Lehigh | 3A Chesterfield | 5A Charles Mix | 6A Spink | 3A Hardeman |
5A Luzerne | 3A Clarendon | 6A Clark | 6A Stanley | 3A Hardin |
5A Lycoming | 3A Colleton* | 5A Clay | 6A Sully | 4A Hawkins |
6A McKean | 3A Darlington | 6A Codington | 5A Todd | 3A Haywood |
5A Mercer | 3A Dillon | 6A Corson | 5A Tripp | 3A Henderson |
5A Mifflin | 3A Dorchester* | 6A Custer | 6A Turner | 4A Henry |
5A Monroe | 3A Edgefield | 6A Davison | 5A Union | 4A Hickman |
4A Montgomery | 3A Fairfield | 6A Day | 6A Walworth | 4A Houston |
5A Montour | 3A Florence | 6A Deuel | 5A Yankton | 4A Humphreys |
5A Northampton | 3A Georgetown* | 6A Dewey | 6A Ziebach | 4A Jackson |
5A Northumberland | 3A Greenville | 5A Douglas | TENNESSEE | 4A Jefferson |
5A Perry | 3A Greenwood | 6A Edmunds | 4A Johnson | |
4A Philadelphia | 3A Hampton* | 6A Fall River | 4A Anderson | 4A Knox |
5A Pike | 3A Horry* | 6A Faulk | 4A Bedford | 3A Lake |
6A Potter | 3A Jasper* | 6A Grant | 4A Benton | 3A Lauderdale |
5A Schuylkill | 3A Kershaw | 5A Gregory | 4A Bledsoe | 4A Lawrence |
5A Snyder | 3A Lancaster | 6A Haakon | 4A Blount | 4A Lewis |
5A Somerset | 3A Laurens | 6A Hamlin | 4A Bradley | 4A Lincoln |
5A Sullivan | 3A Lee | 6A Hand | 4A Campbell | 4A Loudon |
6A Susquehanna | 3A Lexington | 6A Hanson | 4A Cannon | 4A Macon |
6A Tioga | 3A Marion | 6A Harding | 4A Carroll | 3A Madison |
5A Union | 3A Marlboro | 6A Hughes | 4A Carter | 4A Marion |
5A Venango | 3A McCormick | 5A Hutchinson | 4A Cheatham | 4A Marshall |
5A Warren | 3A Newberry | 6A Hyde | 3A Chester | 4A Maury |
5A Washington | 3A Oconee | 5A Jackson | 4A Claiborne | 4A McMinn |
6A Wayne | 3A Orangeburg | 6A Jerauld | 4A Clay | 3A McNairy |
5A Westmoreland | 3A Pickens | 6A Jones | 4A Cocke | 4A Meigs |
5A Wyoming | 3A Richland | 6A Kingsbury | 4A Coffee | 4A Monroe |
4A York | 3A Saluda | 6A Lake | 3A Crockett | 4A Montgomery |
RHODE ISLAND | 3A Spartanburg | 6A Lawrence | 4A Cumberland | 4A Moore |
3A Sumter | 6A Lincoln | 4A Davidson | 4A Morgan | |
5A (all) | 3A Union | 6A Lyman | 4A Decatur | 4A Obion |
SOUTH CAROLINA | 3A Williamsburg | 6A Marshall | 4A DeKalb | 4A Overton |
3A York | 6A McCook | 4A Dickson | 4A Perry | |
3A Abbeville | SOUTH DAKOTA | 6A McPherson | 3A Dyer | 4A Pickett |
3A Aiken | 6A Meade | 3A Fayette | 4A Polk | |
3A Allendale* | 6A Aurora | 5A Mellette | 4A Fentress | 4A Putnam |
3A Anderson | 6A Beadle | 6A Miner | 4A Franklin | 4A Rhea |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
4A Roane | 3B Brewster | 3B Ector | 3B Howard | 3B McCulloch |
4A Robertson | 4B Briscoe | 2B Edwards | 3B Hudspeth | 2A McLennan* |
4A Rutherford | 2A Brooks* | 3A Ellis* | 3A Hunt* | 2A McMullen* |
4A Scott | 3A Brown* | 3B El Paso | 4B Hutchinson | 2B Medina |
4A Sequatchie | 2A Burleson* | 3A Erath* | 3B Irion | 3B Menard |
4A Sevier | 3A Burnet* | 2A Falls* | 3A Jack | 3B Midland |
3A Shelby | 2A Caldwell* | 3A Fannin | 2A Jackson* | 2A Milam* |
4A Smith | 2A Calhoun* | 2A Fayette* | 2A Jasper* | 3A Mills* |
4A Stewart | 3B Callahan | 3B Fisher | 3B Jeff Davis | 3B Mitchell |
4A Sullivan | 2A Cameron* | 4B Floyd | 2A Jefferson* | 3A Montague |
4A Sumner | 3A Camp* | 3B Foard | 2A Jim Hogg* | 2A Montgomery* |
3A Tipton | 4B Carson | 2A Fort Bend* | 2A Jim Wells* | 4B Moore |
4A Trousdale | 3A Cass* | 3A Franklin* | 3A Johnson* | 3A Morris* |
4A Unicoi | 4B Castro | 2A Freestone* | 3B Jones | 3B Motley |
4A Union | 2A Chambers* | 2B Frio | 2A Karnes* | 3A Nacogdoches* |
4A Van Buren | 2A Cherokee* | 3B Gaines | 3A Kaufman* | 3A Navarro* |
4A Warren | 3B Childress | 2A Galveston* | 3A Kendall* | 2A Newton* |
4A Washington | 3A Clay | 3B Garza | 2A Kenedy* | 3B Nolan |
4A Wayne | 4B Cochran | 3A Gillespie* | 3B Kent | 2A Nueces* |
4A Weakley | 3B Coke | 3B Glasscock | 3B Kerr | 4B Ochiltree |
4A White | 3B Coleman | 2A Goliad* | 3B Kimble | 4B Oldham |
4A Williamson | 3A Collin* | 2A Gonzales* | 3B King | 2A Orange* |
4A Wilson | 3B Collingsworth | 4B Gray | 2B Kinney | 3A Palo Pinto* |
TEXAS | 2A Colorado* | 3A Grayson | 2A Kleberg* | 3A Panola* |
2A Comal* | 3A Gregg* | 3B Knox | 3A Parker* | |
2A Anderson* | 3A Comanche* | 2A Grimes* | 3A Lamar* | 4B Parmer |
3B Andrews | 3B Concho | 2A Guadalupe* | 4B Lamb | 3B Pecos |
2A Angelina* | 3A Cooke | 4B Hale | 3A Lampasas* | 2A Polk* |
2A Aransas* | 2A Coryell* | 3B Hall | 2B La Salle | 4B Potter |
3A Archer | 3B Cottle | 3A Hamilton* | 2A Lavaca* | 3B Presidio |
4B Armstrong | 3B Crane | 4B Hansford | 2A Lee* | 3A Rains* |
2A Atascosa* | 3B Crockett | 3B Hardeman | 2A Leon* | 4B Randall |
2A Austin* | 3B Crosby | 2A Hardin* | 2A Liberty* | 3B Reagan |
4B Bailey | 3B Culberson | 2A Harris* | 2A Limestone* | 2B Real |
2B Bandera | 4B Dallam | 3A Harrison* | 4B Lipscomb | 3A Red River* |
2A Bastrop* | 3A Dallas* | 4B Hartley | 2A Live Oak* | 3B Reeves |
3B Baylor | 3B Dawson | 3B Haskell | 3A Llano* | 2A Refugio* |
2A Bee* | 4B Deaf Smith | 2A Hays* | 3B Loving | 4B Roberts |
2A Bell* | 3A Delta | 3B Hemphill | 3B Lubbock | 2A Robertson* |
2A Bexar* | 3A Denton* | 3A Henderson* | 3B Lynn | 3A Rockwall* |
3A Blanco* | 2A DeWitt* | 2A Hidalgo* | 2A Madison* | 3B Runnels |
3B Borden | 3B Dickens | 2A Hill* | 3A Marion* | 3A Rusk* |
2A Bosque* | 2B Dimmit | 4B Hockley | 3B Martin | 3A Sabine* |
3A Bowie* | 4B Donley | 3A Hood* | 3B Mason | 3A San Augustine* |
2A Brazoria* | 2A Duval* | 3A Hopkins* | 2A Matagorda* | 2A San Jacinto* |
2A Brazos* | 3A Eastland | 2A Houston* | 2B Maverick | 2A San Patricio* |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
3A San Saba* | 3A Young | 4C Clark | 4A Gilmer | WISCONSIN |
3B Schleicher | 2B Zapata | 5B Columbia | 5A Grant | |
3B Scurry | 2B Zavala | 4C Cowlitz | 5A Greenbrier | 6A Adams |
3B Shackelford | UTAH | 5B Douglas | 5A Hampshire | 7 Ashland |
3A Shelby* | 5B Beaver | 6B Ferry | 5A Hancock | 6A Barron |
4B Sherman | 6B Box Elder | 5B Franklin | 5A Hardy | 7 Bayfield |
3A Smith* | 6B Cache | 5B Garfield | 5A Harrison | 6A Brown |
3A Somervell* | 6B Carbon | 5B Grant | 4A Jackson | 6A Buffalo |
2A Starr* | 6B Daggett | 4C Grays Harbor | 4A Jefferson | 7 Burnett |
3A Stephens | 5B Davis | 4C Island | 4A Kanawha | 6A Calumet |
3B Sterling | 6B Duchesne | 4C Jefferson | 5A Lewis | 6A Chippewa |
3B Stonewall | 5B Emery | 4C King | 4A Lincoln | 6A Clark |
3B Sutton | 5B Garfield | 4C Kitsap | 4A Logan | 6A Columbia |
4B Swisher | 5B Grand | 5B Kittitas | 5A Marion | 6A Crawford |
3A Tarrant* | 5B Iron | 5B Klickitat | 5A Marshall | 6A Dane |
3B Taylor | 5B Juab | 4C Lewis | 4A Mason | 6A Dodge |
3B Terrell | 5B Kane | 5B Lincoln | 4A McDowell | 6A Door |
3B Terry | 5B Millard | 4C Mason | 4A Mercer | 7 Douglas |
3B Throckmorton | 6B Morgan | 6B Okanogan | 5A Mineral | 6A Dunn |
3A Titus* | 5B Piute | 4C Pacific | 4A Mingo | 6A Eau Claire |
3B Tom Green | 6B Rich | 6B Pend Oreille | 5A Monongalia | 7 Florence |
2A Travis* | 5B Salt Lake | 4C Pierce | 4A Monroe | 6A Fond du Lac |
2A Trinity* | 5B San Juan | 4C San Juan | 4A Morgan | 7 Forest |
2A Tyler* | 5B Sanpete | 4C Skagit | 5A Nicholas | 6A Grant |
3A Upshur* | 5B Sevier | 5B Skamania | 5A Ohio | 6A Green |
3B Upton | 6B Summit | 4C Snohomish | 5A Pendleton | 6A Green Lake |
2B Uvalde | 5B Tooele | 5B Spokane | 4A Pleasants | 6A Iowa |
2B Val Verde | 6B Uintah | 6B Stevens | 5A Pocahontas | 7 Iron |
3A Van Zandt* | 5B Utah | 4C Thurston | 5A Preston | 6A Jackson |
2A Victoria* | 6B Wasatch | 4C Wahkiakum | 4A Putnam | 6A Jefferson |
2A Walker* | 3B Washington | 5B Walla Walla | 5A Raleigh | 6A Juneau |
2A Waller* | 5B Wayne | 4C Whatcom | 5A Randolph | 6A Kenosha |
3B Ward | 5B Weber | 5B Whitman | 4A Ritchie | 6A Kewaunee |
2A Washington* | VERMONT | 5B Yakima | 4A Roane | 6A La Crosse |
2B Webb | WEST VIRGINIA | 5A Summers | 6A Lafayette | |
2A Wharton* | 6A (all) | 5A Taylor | 7 Langlade | |
3B Wheeler | VIRGINIA | 5A Barbour | 5A Tucker | 7 Lincoln |
3A Wichita | 4A Berkeley | 4A Tyler | 6A Manitowoc | |
3B Wilbarger | 4A (all) | 4A Boone | 5A Upshur | 6A Marathon |
2A Willacy* | WASHINGTON | 4A Braxton | 4A Wayne | 6A Marinette |
2A Williamson* | 5A Brooke | 5A Webster | 6A Marquette | |
2A Wilson* | 5B Adams | 4A Cabell | 5A Wetzel | 6A Menominee |
3B Winkler | 5B Asotin | 4A Calhoun | 4A Wirt | 6A Milwaukee |
3A Wise | 5B Benton | 4A Clay | 4A Wood | 6A Monroe |
3A Wood* | 5B Chelan | 5A Doddridge | 4A Wyoming | 6A Oconto |
4B Yoakum | 4C Clallam | 5A Fayette | 7 Oneida | |
6A Outagamie |
(continued)
TABLE R301.1‒continued CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
6A Ozaukee | 7 Taylor | 6B Big Horn | 6B Sheridan | NORTHERN MARIANA ISLANDS |
6A Pepin | 6A Trempealeau | 6B Campbell | 7 Sublette | |
6A Pierce | 6A Vernon | 6B Carbon | 6B Sweetwater | |
6A Polk | 7 Vilas | 6B Converse | 7 Teton | 1A (all)* |
6A Portage | 6A Walworth | 6B Crook | 6B Uinta | PUERTO RICO |
7 Price | 7 Washburn | 6B Fremont | 6B Washakie | |
6A Racine | 6A Washington | 5B Goshen | 6B Weston | 1A (all)* |
6A Richland | 6A Waukesha | 6B Hot Springs | US TERRITORIES | VIRGIN ISLANDS |
6A Rock | 6A Waupaca | 6B Johnson | ||
6A Rusk | 6A Waushara | 6B Laramie | AMERICAN SAMOA | 1A (all)* |
6A Sauk | 6A Winnebago | 7 Lincoln | ||
7 Sawyer | 6A Wood | 6B Natrona | 1A (all)* | |
6A Shawano | WYOMING | 6B Niobrara | GUAM | |
6A Sheboygan | 6B Park | |||
6A St. Croix | 6B Albany | 5B Platte | 1A (all)* |
Warm humid counties are identified in Table R301.1 by an asterisk.
The climate zone for any location outside the United States shall be determined by applying Table R301.3(1) and then Table R301.3(2).
TABLE R301.3(1) INTERNATIONAL CLIMATE ZONE DEFINITIONS
TABLE R301.3(2) INTERNATIONAL CLIMATE ZONE DEFINITIONS
TABLE R301.3(1) INTERNATIONAL CLIMATE ZONE DEFINITIONS
MAJOR CLIMATE TYPE DEFINITIONS |
Marine (C) Definition‒Locations meeting all four criteria: |
1. Mean temperature of coldest month between -3°C (27°F) and 18°C (65°F). |
2. Warmest month mean < 22°C (72°F). |
3. At least four months with mean temperatures over 10°C (50°F). |
4. Dry season in summer. The month with the heaviest precipitation in the cold season has at least three times as much precipitation as the month with the least precipitation in the rest of the year. The cold season is October through March in the Northern Hemisphere and April through September in the Southern Hemisphere. |
Dry (B) Definition‒Locations meeting the following criteria: |
Not marine and Pin < 0.44 × (TF - 19.5) [Pcm < 2.0 × (TC + 7) in SI units] |
where: |
Pin = Annual precipitation in inches (cm) |
T = Annual mean temperature in °F (°C) |
Moist (A) Definition‒Locations that are not marine and not dry. |
Warm-humid Definition‒Moist (A) locations where either of the following wet-bulb temperature conditions shall occur during the warmest six consecutive months of the year: |
1. 67°F (19.4°C) or higher for 3,000 or more hours; or |
2. 73°F (22.8°C) or higher for 1,500 or more hours. |
For SI: °C = [(°F)-32]/1.8, 1 inch = 2.54 cm.
TABLE R301.3(2) INTERNATIONAL CLIMATE ZONE DEFINITIONS
ZONE NUMBER | THERMAL CRITERIA | |
IP Units | SI Units | |
1 | 9000 < CDD50°F | 5000 < CDD10°C |
2 | 6300 < CDD50°F ≤9000 | 3500 < CDD10°C ≤ 5000 |
3A and 3B | 4500 < CDD50°F ≤ 6300 AND HDD65°F ≤ 5400 | 2500 < CDD10°C ≤ 3500 AND HDD18°C ≤ 3000 |
4A and 4B | CDD50°F ≤ 4500 AND HDD65°F ≤ 5400 | CDD10°C ≤ 2500 AND HDD18°C ≤ 3000 |
3C | HDD65°F ≤ 3600 | HDD18°C ≤ 2000 |
4C | 3600 < HDD65°F ≤ 5400 | 2000 < HDD18°C ≤ 3000 |
5 | 5400 < HDD65°F ≤ 7200 | 3000 < HDD18°C ≤ 4000 |
6 | 7200 < HDD65°F ≤ 9000 | 4000 < HDD18°C ≤ 5000 |
7 | 9000 < HDD65°F ≤ 12600 | 5000 < HDD18°C ≤ 7000 |
8 | 12600 < HDD65°F | 7000 < HDD18°C |
For SI: °C = [(°F)-32]/1.8.
The tropical climate zone shall be defined as:
1. Hawaii, Puerto Rico, Guam, American Samoa, U.S. Virgin Islands, Commonwealth of Northern Mariana Islands; and
2. Islands in the area between the Tropic of Cancer and the Tropic of Capricorn.
1. Hawaii, Puerto Rico, Guam, American Samoa, U.S. Virgin Islands, Commonwealth of Northern Mariana Islands; and
2. Islands in the area between the Tropic of Cancer and the Tropic of Capricorn.
The interior design temperatures used for heating and cooling load calculations shall be a maximum of 72°F (22°C) for heating and minimum of 75°F (24°C) for cooling.
Materials, systems and equipment shall be identified in a manner that will allow a determination of compliance with the applicable provisions of this code.
An R-value identification mark shall be applied by the manufacturer to each piece of building thermal envelope insulation 12 inches (305 mm) or greater in width. Alternately, the insulation installers shall provide a certification listing the type, manufacturer and R-value of insulation installed in each element of the building thermal envelope. For blown or sprayed insulation (fiberglass and cellulose), the initial installed thickness, settled thickness, settled R-value, installed density, coverage area and number of bags installed shall be listed on the certification. For sprayed polyurethane foam (SPF) insulation, the installed thickness of the areas covered and R-value of installed thickness shall be listed on the certification. For insulated siding, the R-value shall be labeled on the product's package and shall be listed on the certification. The insulation installer shall sign, date and post the certification in a conspicuous location on the job site.
The thickness of blown-in or sprayed roof/ceiling insulation (fiberglass or cellulose) shall be written in inches (mm) on markers that are installed at least one for every 300 square feet (28 m2) throughout the attic space. The markers shall be affixed to the trusses or joists and marked with the minimum initial installed thickness with numbers not less than 1 inch (25 mm) in height. Each marker shall face the attic access opening. Spray polyurethane foam thickness and installed R-value shall be listed on certification provided by the insulation installer.
Insulating materials shall be installed such that the manufacturer's R-value mark is readily observable upon inspection.
U-factors of fenestration products (windows, doors and skylights) shall be determined in accordance with NFRC 100.
Exception: Where required, garage door U-factors shall be determined in accordance with either NFRC 100 or ANSI/DASMA 105.
U-factors shall be determined by an accredited, independent laboratory, and labeled and certified by the manufacturer.
Products lacking such a labeled U-factor shall be assigned a default U-factor from Table R303.1.3(1) or R303.1.3(2). The solar heat gain coefficient (SHGC) and visible transmittance (VT) of glazed fenestration products (windows, glazed doors and skylights) shall be determined in accordance with NFRC 200 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such a labeled SHGC or VT shall be assigned a default SHGC or VT from Table R303.1.3(3).
TABLE R303.1.3(1) DEFAULT GLAZED FENESTRATION U-FACTORS
TABLE R303.1.3(2) DEFAULT DOOR U-FACTORS
TABLE R303.1.3(3) DEFAULT GLAZED FENESTRATION SHGC AND VT
Exception: Where required, garage door U-factors shall be determined in accordance with either NFRC 100 or ANSI/DASMA 105.
U-factors shall be determined by an accredited, independent laboratory, and labeled and certified by the manufacturer.
Products lacking such a labeled U-factor shall be assigned a default U-factor from Table R303.1.3(1) or R303.1.3(2). The solar heat gain coefficient (SHGC) and visible transmittance (VT) of glazed fenestration products (windows, glazed doors and skylights) shall be determined in accordance with NFRC 200 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such a labeled SHGC or VT shall be assigned a default SHGC or VT from Table R303.1.3(3).
TABLE R303.1.3(1) DEFAULT GLAZED FENESTRATION U-FACTORS
FRAME TYPE | SINGLE PANE | DOUBLE PANE | SKYLIGHT | |
Single | Double | |||
Metal | 1.20 | 0.80 | 2.00 | 1.30 |
Metal with Thermal Break | 1.10 | 0.65 | 1.90 | 1.10 |
Nonmetal or Metal Clad | 0.95 | 0.55 | 1.75 | 1.05 |
Glazed Block | 0.60 |
TABLE R303.1.3(2) DEFAULT DOOR U-FACTORS
DOOR TYPE | U-FACTOR |
Uninsulated Metal | 1.20 |
Insulated Metal | 0.60 |
Wood | 0.50 |
Insulated, nonmetal edge, max 45% glazing, any glazing double pane | 0.35 |
TABLE R303.1.3(3) DEFAULT GLAZED FENESTRATION SHGC AND VT
SINGLE GLAZED | DOUBLE GLAZED | GLAZED BLOCK | |||
Clear | Tinted | Clear | Tinted | ||
SHGC | 0.8 | 0.7 | 0.7 | 0.6 | 0.6 |
VT | 0.6 | 0.3 | 0.6 | 0.3 | 0.6 |
The thermal resistance (R-value) of insulation shall be determined in accordance with the U.S. Federal Trade Commission R-value rule (CFR Title 16, Part 460) in units of h • ft2 • °F/Btu at a mean temperature of 75°F (24°C).
The thermal resistance (R-value) of insulated siding shall be determined in accordance with ASTM C 1363. Installation for testing shall be in accordance with the manufacturer's instructions.
Materials, systems and equipment shall be installed in accordance with the manufacturer's instructions and the International Building Code or International Residential Code, as applicable.
Insulation applied to the exterior of basement walls, crawlspace walls and the perimeter of slab-on-grade floors shall have a rigid, opaque and weather-resistant protective covering to prevent the degradation of the insulation's thermal performance. The protective covering shall cover the exposed exterior insulation and extend not less than 6 inches (153 mm) below grade.
Maintenance instructions shall be furnished for equipment and systems that require preventive maintenance. Required regular maintenance actions shall be clearly stated and incorporated on a readily accessible label. The label shall include the title or publication number for the operation and maintenance manual for that particular model and type of product.