ADOPTS WITH AMENDMENTS:

International Building Code 2018 (IBC 2018)

Heads up: There are no amended sections in this chapter.

User note:

About this chapter: Plumbing systems are another key element of any building. Chapter 29 provides the necessary number of plumbing fixtures, including water closets, lavatories, bathtubs and showers. The quality and design of each fixture must be in accordance with the International Plumbing Code®.

The provisions of this chapter and the International Plumbing Code shall govern the design, construction, erection and installation of plumbing components, appliances, equipment and systems used in buildings and structures covered by this code. Toilet and bathing rooms shall be constructed in accordance with Section 1209. Private sewage disposal systems shall conform to the International Private Sewage Disposal Code. The International Fire Code, the International Property Maintenance Code and the International Plumbing Code shall govern the use and maintenance of plumbing components, appliances, equipment and systems. The International Existing Building Code and the International Plumbing Code shall govern the alteration, repair, relocation, replacement and addition of plumbing components, appliances, equipment and systems.

[P] 2902.1 Minimum Number of Fixtures

AMENDMENT
This section has been amended at the state or city level.

Plumbing fixtures shall be provided in the minimum number as shown in Table 2902.1 based on the actual use of the building or space. Uses not shown in Table 2902.1 shall be considered individually by the code official. The number of occupants shall be determined by this code.

[P] TABLE 2902.1

MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 2902.1.1 and 2902.2)

No.CLASSIFICATIONDESCRIPTIONWATER CLOSETS
(URINALS SEE
SECTION 424.2 OF THE
INTERNATIONAL PLUMBING CODE)
LAVATORIESBATHTUBS/
SHOWERS
DRINKING
FOUNTAINS
(SEE SECTION 410
OF THE
INTERNATIONAL PLUMBING CODE)
OTHER
MaleFemaleMaleFemale
1AssemblyTheaters and other buildings for the performing arts and motion picturesd1 per 1251 per 651 per 2001 per 5001 service sink
Nightclubs, bars, taverns, dance halls and buildings for similar purposesd1 per 401 per 401 per 751 per 5001 service sink
Restaurants, banquet halls and food courtsd1 per 751 per 751 per 2001 per 5001 service sink
Casino gaming areas1 per 100 for the first 400 and 1 per 250 for the remainder exceeding 4001 per 50 for the first 400 and 1 per 150 for the remainder exceeding 4001 per 250 for the first 750 and 1 per 500 for the remainder exceeding 7501 per 1,0001 service sink
Auditoriums without permanent seating, art galleries, exhibition halls, museums, lecture halls, libraries, arcades and gymnasiumsd1 per 1251 per 651 per 2001 per 5001 service sink
Passenger terminals and transportation facilitiesd1 per 5001 per 5001 per 7501 per 1,0001 service sink
Places of worship and other religious servicesd1 per 1501 per 751 per 2001 per 1,0001 service sink
Coliseums, arenas, skating rinks, pools and tennis courts for indoor sporting events and activities1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,5001 per 40 for the first 1,520 and 1 per 60 for the remainder exceeding 1,5201 per 2001 per 1501 per 1,0001 service sink
Stadiums, amusement parks, bleachers and grandstands for outdoor sporting events and activitiesf1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,5001 per 40 for the first 1,520 and 1 per 60 for the remainder exceeding 1,5201 per 2001 per 1501 per 1,0001 service sink
2BusinessBuildings for the transaction of business, professional services, other services involving merchandise, office buildings, banks, light industrial, ambulatory care and similar uses1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 501 per 40 for the first 80 and 1 per 80 for the remainder exceeding 801 per 1001 service sinke
3EducationalEducational facilities1 per 501 per 501 per 1001 service sinki
4Factory and industrialStructures in which occupants are engaged in work fabricating, assembly or processing of products or materials1 per 1001 per 1001 per 4001 service sink
5InstitutionalCustodial care facilities1 per 101 per 101 per 81 per 1001 service sink
Medical care recipients in hospitals and nursing homesb1 per roomc1 per roomc1 per 151 per 1001 service sink
Employees in hospitals and nursing homesb1 per 251 per 351 per 100
Visitors in hospitals and nursing homes1 per 751 per 1001 per 500
Prisonsb1 per cell1 per cell1 per 151 per 1001 service sink
Reformatories, detention centers and correctional centersb1 per 151 per 151 per 151 per 1001 service sink
Employees in reformitories, detention centers and correctional centersb1 per 251 per 351 per 100
Adult day care and child day care1 per 151 per 1511 per 1001 service sinki
6MercantileRetail stores, service stations, shops, salesrooms, markets and shopping centers1 per 5001 per 7501 per 1,0001 service sinke
7ResidentialHotels, motels, boarding houses (transient)1 per sleeping unit1 per sleeping unit1 per sleeping unit1 service sink
Dormitories, fraternities, sororities and boarding houses (not transient)1 per 101 per 101 per 81 per 1001 service sink
Apartment house1 per dwelling unit1 per dwelling unit1 per dwelling unit1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per 20 dwelling units
One- and two-family dwellings and lodging houses with five or fewer guestrooms1 per dwelling unit1 per 101 per dwelling unit1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per dwelling unit
Congregate living facilities with 16 or fewer persons1 per 101 per 101 per 81 per 1001 service sink
8StorageStructures for the storage of goods, warehouses, storehouses and freight depots, low and moderate hazard1 per 1001 per 1001 per 1,0001 service sink
  1. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by this code.
  2. Toilet facilities for employees shall be separate from facilities for inmates or care recipients.
  3. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted, provided that each patient sleeping unit has direct access to the toilet room and provisions for privacy for the toilet room user are provided.
  4. The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required.
  5. For business and mercantile classifications with an occupant load of 15 or fewer, a service sink shall not be required.
  6. The required number and type of plumbing fixtures for outdoor public swimming pools shall be in accordance with Utah Administrative Code, R392-302, Design, Construction and Operation of Public Pools.
  7. When provided, subject to footnote i, in public toilet facilities there shall be an equal number of diaper changing facilities in male toilet rooms and female toilet rooms.
  8. Non-residential child care facilities shall comply with additional sink requirements of Utah Administrative Code, R381-60-9, Hourly Child Care Centers, R381-70-9, Out of School Time Child Care Programs, and R381-100-9, Child Care Centers.
  9. A building owned by a state government entity or by a political subdivision of the state that allows access to the public shall provide diaper changing facilities in accordance with footnote h if:
    1. the building is newly constructed; or
    2. a bathroom in the building is renovated
    .

To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 2902.1. Fractional numbers resulting from applying the fixture ratios of Table 2902.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall first be summed and then rounded up to the next whole number.

Exception: The total occupant load shall not be required to be divided in half where approved statistical data indicate a distribution of the sexes of other than 50 percent of each sex.

The plumbing fixtures located in single-user toilet facilities and bathing rooms, including family or assisted-use toilet and bathing rooms that are required by Section 1109.2, shall contribute toward the total number of required plumbing fixtures for a building or tenant space. Single-user toilet facilities and bathing rooms, and family or assisted-use toilet rooms and bathing rooms shall be identified for use by either sex.
Where two or more toilet rooms are provided for each sex, the required number of lavatories shall be distributed proportionately to the required number of water closets.

Where plumbing fixtures are required, separate facilities shall be provided for each sex.

Exceptions:

  1. Separate facilities shall not be required for dwelling units and sleeping units.
  2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or fewer.
  3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or fewer.
  4. Separate facilities shall not be required in business occupancies in which the maximum occupant load is 25 or fewer.
Where a building or tenant space requires a separate toilet facility for each sex and each toilet facility is required to have only one water closet, two family or assisted-use toilet facilities shall be permitted to serve as the required separate facilities. Family or assisted-use toilet facilities shall not be required to be identified for exclusive use by either sex as required by Section 2902.4.

For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.


Exception: Public toilet facilities shall not be required for:

  1. Parking garages where operated without parking attendants.
  2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet (28 m2).

[P] 2902.3.1 Access

ILLUSTRATION
The route to the public toilet facilities required by Section 2902.3 shall not pass through kitchens, storage rooms or closets. Access to the required facilities shall be from within the building or from the exterior of the building. Routes shall comply with the accessibility requirements of this code. The public shall have access to the required toilet facilities at all times that the building is occupied.
Toilet rooms shall not open directly into a room used for the preparation of food for service to the public.

In occupancies other than covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).

Exception: The location and maximum distances of travel to required employee facilities in factory and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum distance of travel are approved.

In covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 300 feet (91 mm). In mall buildings, the required facilities shall be based on total square footage (m2) within a covered mall building or within the perimeter line of an open mall building, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The maximum distance of travel to central toilet facilities in mall buildings shall be measured from the main entrance of any store or tenant space. In mall buildings, where employees' toilet facilities are not provided in the individual store, the maximum distance of travel shall be measured from the employees' work area of the store or tenant space.
Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities. Required facilities shall be free of charge.
Where a toilet room is provided for the use of multiple occupants, the egress door for the room shall not be lockable from the inside of the room. This section does not apply to family or assisted-use toilet rooms.
Required public facilities shall be provided with signs that designate the sex as required by Section 2902.2. Signs shall be readily visible and located near the entrance to each toilet facility. Signs for accessible toilet facilities shall comply with Section 1111.
Directional signage indicating the route to the required public toilet facilities shall be posted in a lobby, corridor, aisle or similar space, such that the sign can be readily seen from the main entrance to the building or tenant space.
Drinking fountains shall not be required to be located in individual tenant spaces provided that public drinking fountains are located within a distance of travel of 500 feet (152 m) of the most remote location in the tenant space and not more than one story above or below the tenant space. Where the tenant space is in a covered or open mall, such distance shall not exceed 300 feet (91 440 mm). Drinking fountains shall be located on an accessible route.
Drinking fountains shall not be required for an occupant load of 15 or fewer.

[P] 2902.7 Toilet Facilities for Workers

AMENDMENT
This section has been amended at the state or city level.
Toilet facilities shall be provided for construction workers and such facilities shall be maintained in a sanitary condition. Construction worker toilet facilities of the nonsewer type shall conform to ANSI Z4.3.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING