The provisions of this chapter shall control the classification of all buildings and structures as to use and occupancy.
Structures or portions of structures shall be classified with respect to occupancy in one or more of the groups listed in this section. A room or space that is intended to be occupied at different times for different purposes shall comply with all of the requirements that are applicable to each of the purposes for which the room or space will be occupied. Structures with multiple occupancies or uses shall comply with Section 508. Where a structure is proposed for a purpose that is not specifically provided for in this code, such structure shall be classified in the group that the occupancy most nearly resembles, according to the fire safety and relative hazard involved.
- Assembly (see Section 303): Groups A-1, A-2, A-3, A-4 and A-5.
- Business (see Section 304): Group B.
- Educational (see Section 305): Group E.
- Factory and Industrial (see Section 306): Groups F-1 and F-2.
- High Hazard (see Section 307): Groups H-1, H-2, H-3, H-4 and H-5.
- Institutional (see Section 308): Groups I-1, I-2, I-3 and I-4.
- Mercantile (see Section 309): Group M.
- Residential (see Section 310): Groups R-1, R-2, R-3 and R-4.
- Storage (see Section 311): Groups S-1 and S-2.
- Utility and Miscellaneous (see Section 312): Group U.
Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering of persons for purposes such as civic, social or religious functions; recreation, food or drink consumption or awaiting transportation.
A building or tenant space used for assembly purposes with an occupant load of less than 50 persons shall be classified as a Group B occupancy.
The following rooms and spaces shall not be classified as Assembly occupancies:
- A room or space used for assembly purposes with an occupant load of less than 50 persons and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy.
- A room or space used for assembly purposes that is less than 750 square feet (70 m2) in area and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy.
A room or space used for assembly purposes that is associated with a Group E occupancy is not considered a separate occupancy.
Accessory religious educational rooms and religious auditoriums with occupant loads of less than 100 per room or space are not considered separate occupancies.
Group A-1 occupancy includes assembly uses, usually with fixed seating, intended for the production and viewing of the performing arts or motion pictures including, but not limited to:
- Motion picture theaters
- Symphony and concert halls
- Television and radio studios admitting an audience
- Theaters
Group A-2 occupancy includes assembly uses intended for food and/or drink consumption including, but not limited to:
- Banquet halls
- Casinos (gaming areas)
- Nightclubs
- Restaurants, cafeterias and similar dining facilities (including associated commercial kitchens)
- Taverns and bars
Group A-3 occupancy includes assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to:
- Amusement arcades
- Art galleries
- Bowling alleys
- Community halls
- Courtrooms
- Dance halls (not including food or drink consumption)
Exhibition halls - Funeral parlors
- Gymnasiums (without spectator seating)
- Indoor swimming pools (without spectator seating)
Indoor tennis courts (without spectator seating) - Lecture halls
- Libraries
- Museums
- Places of religious worship
- Pool and billiard parlors
- Waiting areas in transportation terminals
Group A-4 occupancy includes assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to:
- Arenas
- Skating rinks
- Swimming pools
- Tennis courts
Group A-5 occupancy includes assembly uses intended for participation in or viewing outdoor activities including, but not limited to:
- Amusement park structures
- Bleachers
- Grandstands
- Stadiums
Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional or service-type transactions, including storage of records and accounts. Business occupancies shall include, but not be limited to, the following:
- Airport traffic control towers
- Ambulatory care facilities
- Animal hospitals, kennels and pounds
- Banks
- Barber and beauty shops
- Car wash
- Civic administration
- Clinic, outpatient
- Dry cleaning and laundries: pick-up and delivery stations and self-service
- Educational occupancies for students above the 12th grade
- Electronic data processing
- Food processing establishments and commercial kitchens not associated with restaurants, cafeterias and similar dining facilities not more than 2,500 square feet (232 m2) in area.
- Laboratories: testing and research
- Motor vehicle showrooms
- Post offices
- Print shops
- Professional services (architects, attorneys, dentists, physicians, engineers, etc.)
- Radio and television stations
- Telephone exchanges
- Training and skill development not in a school or academic program (this shall include, but not be limited to, tutoring centers, martial arts studios, gymnastics and similar uses regardless of the ages served, and where not classified as a Group A occupancy).
Educational Group E occupancy includes, among others, the use of a building or structure, or a portion thereof, by six or more persons at any one time for educational purposes through the 12th grade.
Religious educational rooms and religious auditoriums, which are accessory to places of religious worship in accordance with Section 303.1.4 and have occupant loads of less than 100 per room or space, shall be classified as Group A-3 occupancies.
This group includes buildings and structures or portions thereof occupied by more than five children older than 21/2 years of age who receive educational, supervision, child care centers, or personal care services for fewer than 24 hours per day. See Section 425 for special requirements for Day Care.
Rooms and spaces within places of religious worship providing such day care during religious functions shall be classified as part of the primary occupancy.
A facility having fivefour or fewer children receiving such day care shall be classified as part of the primary occupancy.
A facility such as the above within a dwelling unit and having fivefour or fewer children receiving such day care shall be classified as a Group R-3 occupancy or shall comply with the International Residential Code.
Residential Certificate or a Family License. Areas used for child day care purposes with a Residential Certificate R430-50 or a Family License, as defined in Utah Administrative Code, R430-90, Licensed Family Child Care, may be located in a Group R-2 or R-3 occupancy as provided in Section 310.5 or shall comply with the International Residential Code in accordance with Section R101.2.
Areas used for Hourly Child Care Centers, as defined in Utah Administrative Code, R430-60, Child Care Center as defined in Utah Administrative Code, R430-100, or Out of School Time Programs, as defined in Utah Administrative Code, R430-70, may be classified as accessory occupancies.
Factory Industrial Group F occupancy includes, among others, the use of a building or structure, or a portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations that are not classified as a Group H hazardous or Group S storage occupancy.
Factory industrial uses that are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, the following:
- Aircraft (manufacturing, not to include repair)
- Appliances
- Athletic equipment
- Automobiles and other motor vehicles
- Bakeries
- Beverages: over 16-percent alcohol content
- Bicycles
- Boats
- Brooms or brushes
- Business machines
- Cameras and photo equipment
- Canvas or similar fabric
- Carpets and rugs (includes cleaning)
- Clothing
- Construction and agricultural machinery
- Disinfectants
- Dry cleaning and dyeing
- Electric generation plants
- Electronics
- Engines (including rebuilding)
-
Food processing establishments and commercial kitchens not associated with restaurants, cafeterias and similar dining facilities more than 2,500 square feet (232 m2) in area.
- Furniture
- Hemp products
- Jute products
- Laundries
- Leather products
- Machinery
- Metals
- Millwork (sash and door)
- Motion pictures and television filming (without spectators)
- Musical instruments
- Optical goods
- Paper mills or products
- Photographic film
- Plastic products
- Printing or publishing
- Recreational vehicles
- Refuse incineration
- Shoes
- Soaps and detergents
- Textiles
- Tobacco
- Trailers
- Upholstering
- Wood; distillation
- Woodworking (cabinet)
Factory industrial uses that involve the fabrication or manufacturing of noncombustible materials that during finishing, packing or processing do not involve a significant fire hazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following:
High-hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those allowed in control areas complying with Section 414, based on the maximum allowable quantity limits for control areas set forth in Tables 307.1(1) and 307.1(2). Hazardous occupancies are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in accordance with this section, the requirements of Section 415 and the International Fire Code. Hazardous materials stored, or used on top of roofs or canopies, shall be classified as outdoor storage or use and shall comply with the International Fire Code.
MATERIAL | CLASS | GROUP WHEN THE MAXIMUM ALLOWABLE QUANTITY IS EXCEEDED | STORAGEb | USE-CLOSED SYSTEMSb | USE-OPEN SYSTEMSb | |||||
Solid pounds (cubic feet) | Liquid gallons (pounds) | Gas cubic feet at NTP | Solid pounds (cubic feet) | Liquid gallons (pounds) | Gas cubic feet at NTP | Solid pounds (cubic feet) | Liquid gallons (pounds) | |||
Combustible dust | NA | H-2 | See Note q | NA | NA | See Note q | NA | NA | See Note q | NA |
Combustible fiberq | Loose Baledo | H-3 | (100) (1,000) | NA | NA | (100) (1,000) | NA | NA | (20) (200) | NA |
Combustible liquidc, i | II IIIA IIIB | H-2 or H-3 H-2 or H-3 NA | NA | 120d, e 330d, e 13,200e, f | NA | NA | 120d 330d 13,200f | NA | NA | 30d 80d 3,300f |
Consumer fireworks | 1.4G | H-3 | 125e, d, l | NA | NA | NA | NA | NA | NA | NA |
Cryogenic flammable | NA | H-2 | NA | 45d | NA | NA | 45d | NA | NA | 10d |
Cryogenic inert | NA | NA | NA | NA | NL | NA | NA | NL | NA | NA |
Cryogenic oxidizing | NA | H-3 | NA | 45d | NA | NA | 45d | NA | NA | 10d |
Explosives | Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.4G Division 1.5 Division 1.6 | H-1 H-1 H-1 or H-2 H-3 H-3 H-1 H-1 | 1e, g 1e, g 5e, g 50e, g 125d, e, l 1e, g 1e, g | (1)e, g (1)e, g (5)e, g (50)e, g NA (1)e, g NA | NA | 0.25g 0.25g 1g 50g NA 0.25g NA | (0.25)g (0.25)g (1)g (50)g NA (0.25)g NA | NA | 0.25g 0.25g 1g NA NA 0.25g NA | (0.25)g (0.25)g (1)g NA NA (0.25)g NA |
Flammable gas | Gaseous Liquefied | H-2 | NA | NA (150)d, e | 1,000d, e NA | NA | NA (150)d, e | 1,000d, e NA | NA | NA |
Flammable liquidc | IA IB and IC | H-2 or H-3 | NA | 30d, e 120d, e | NA | NA | 30d 120d | NA | NA | 10d 30d |
Flammable liquid, combination (IA, IB, IC) | NA | H-2 or H-3 | NA | 120d, e, h | NA | NA | 120d, h | NA | NA | 30d, h |
Flammable solid | NA | H-3 | 125d, e | NA | NA | 125d | NA | NA | 25d | NA |
Inert gas | Gaseous Liquefied | NA NA | NA NA | NA NA | NL NL | NA NA | NA NA | NL NL | NA NA | NA NA |
Organic peroxide | UD I II III IV V | H-1 H-2 H-3 H-3 NA NA | 1e, g 5d, e 50d, e 125d, e NL NL | (1)e, g (5)d, e (50)d, e (125)d, e NL NL | NA | 0.25g 1d 50d 125d NL NL | (0.25)g (1)d (50)d (125)d NL NL | NA | 0.25g 1d 10d 25d NL NL | (0.25)g (1)d (10)d (25)d NL NL |
Oxidizer | 4 3k 2 1 | H-1 H-2 or H-3 H-3 NA | 1g 10d, e 250d, e 4,000e, f | (1)e, g (10)d, e (250)d, e (4,000)e, f | NA | 0.25g 2d 250d 4,000f | (0.25)g (2)d (250)d (4,000)f | NA | 0.25g 2d 50d 1,000f | (0.25)g (2)d (50)d (1,000)f |
Oxidizing gas | Gaseous Liquefied | H-3 | NA | NA (150)d, e | 1,500d, e NA | NA | NA (150)d, e | 1,500d, e NA | NA | NA |
Pyrophoric | NA | H-2 | 4e, g | (4)e, g | 50e, g | 1g | (1)g | 10e, g | 0 | 0 |
Unstable (reactive) | 4 3 2 1 | H-1 H-1 or H-2 H-3 NA | 1e, g 5d, e 50d, e NL | (1)e, g (5)d, e (50)d, e NL | 10e, g 50d, e 750d, e NL | 0.25g 1d 50d NL | (0.25)g (1)d (50)d NL | 2e, g 10d, e 750d, e NL | 0.25g 1d 10d NL | (0.25)g (1)d (10)d NL |
Water reactive | 3 2 1 | H-2 H-3 NA | 5d, e 50d, e NL | (5)d, e (50)d, e NL | NA | 5d 50d NL | (5)d (50)d NL | NA | 1d 10d NL | (1)d (10)d NL |
For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L. |
NL = Not Limited; NA = Not Applicable; UD = Unclassified Detonable. |
a. For use of control areas, see Section 414.2. |
b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. |
c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited provided the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs or consumer products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons. |
d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively. |
e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets, gas rooms or exhausted enclosures or in listed safety cans in accordance with Section 5003.9.10 of the International Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively. |
f. Quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. |
g. Allowed only in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. |
h. Containing not more than the maximum allowable quantity per control area of Class IA, IB or IC flammable liquids. |
i. The maximum allowable quantity shall not apply to fuel oil storage complying with Section 603.3.2 of the International Fire Code. |
j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. |
k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance purposes, operation or sanitation of equipment when the storage containers and the manner of storage are approved. |
l. Net weight of the pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of the fireworks is not known, 25 percent of the gross weight of the fireworks, including packaging, shall be used. |
m.For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the International Fire Code. |
n. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2). |
o. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class. |
p. The following shall not be included in determining the maximum allowable quantities: |
1. Liquid or gaseous fuel in fuel tanks on vehicles. |
2. Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with the International Fire Code. |
3. Gaseous fuels in piping systems and fixed appliances regulated by the International Fuel Gas Code. |
4. Liquid fuels in piping systems and fixed appliances regulated by the International Mechanical Code. |
5. Alcohol-based hand rubs classified as Class I or II liquids in dispensers that are installed in accordance with Sections 5705.5 and 5705.5.1 of the International Fire Code. The location of the alcohol-based hand rub (ABHR) dispensers shall be provided in the construction documents. |
q. Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3. |
MATERIAL | STORAGEb | USE-CLOSED SYSTEMSb | USE-OPEN SYSTEMSb | |||||
Solid poundsd, e | Liquid gallons (pounds)d, e | Gas cubic feet at NTP (pounds)d | Solid poundsd | Liquid gallons (pounds)d | Gas cubic feet at NTP (pounds)d | Solid poundsd | Liquid gallons (pounds)d | |
Corrosives | 5,000 | 500 | Gaseous 810e Liquefied (150) | 5,000 | 500 | Gaseous 810e Liquefied (150) | 1,000 | 100 |
Highly Toxic | 10 | (10) | Gaseous 20g Liquefied (4)g | 10 | (10) | Gaseous 20g Liquefied (4)g | 3 | (3) |
Toxic | 500 | (500) | Gaseous 810e Liquefied (150)e | 500 | (500) | Gaseous 810e Liquefied (150)e | 125 | (125) |
For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L. |
a. For use of control areas, see Section 414.2. |
b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. |
c. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs or consumer products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons. |
d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively. |
e. Maximum allowable quantities shall be increased 100 percent where stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the International Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively. |
f. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2). |
g. Allowed only where stored in approved exhausted gas cabinets or exhausted enclosures as specified in the International Fire Code. |
h. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. |
i. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the International Fire Code. |
An occupancy that stores, uses or handles hazardous materials as described in one or more of the following items shall not be classified as Group H, but shall be classified as the occupancy that it most nearly resembles.
- Buildings and structures occupied for the application of flammable finishes, provided that such buildings or areas conform to the requirements of Section 416 and the International Fire Code.
- Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conforming to the International Fire Code.
- Closed piping system containing flammable or combustible liquids or gases utilized for the operation of machinery or equipment.
- Cleaning establishments that utilize combustible liquid solvents having a flash point of 140°F (60°C) or higher in closed systems employing equipment listed by an approved testing agency, provided that this occupancy is separated from all other areas of the building by 1-hour fire barriers constructed in accordance with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711, or both.
- Cleaning establishments that utilize a liquid solvent having a flash point at or above 200°F (93°C).
- Liquor stores and distributors without bulk storage.
- Refrigeration systems.
- The storage or utilization of materials for agricultural purposes on the premises.
- Stationary batteries utilized for facility emergency power, uninterruptable power supply or telecommunication facilities, provided that the batteries are provided with safety venting caps and ventilation is provided in accordance with the International Mechanical Code.
- Corrosive personal or household products in their original packaging used in retail display.
- Commonly used corrosive building materials.
- Buildings and structures occupied for aerosol storage shall be classified as Group S-1, provided that such buildings conform to the requirements of the International Fire Code.
- Display and storage of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in quantities not exceeding the maximum allowable quantity per control area in Group M or S occupancies complying with Section 414.2.5.
- The storage of black powder, smokeless propellant and small arms primers in Groups M and R-3 and special industrial explosive devices in Groups B, F, M and S, provided such storage conforms to the quantity limits and requirements prescribed in the International Fire Code.
Hazardous materials in any quantity shall conform to the requirements of this code, including Section 414, and the International Fire Code.
The following terms are defined in Chapter 2:
AEROSOL
AEROSOL CONTAINER.
BALED COTTON.
BALED COTTON, DENSELY PACKED.
BARRICADE.
BOILING POINT.
CLOSED SYSTEM.
COMBUSTIBLE DUST.
COMBUSTIBLE FIBERS.
COMBUSTIBLE LIQUID.
COMPRESSED GAS.
CONTROL AREA.
CORROSIVE.
CRYOGENIC FLUID.
DAY BOX.
DEFLAGRATION.
DETONATION.
DISPENSING.
EXPLOSION.
EXPLOSIVE.
FIREWORKS.
FLAMMABLE GAS.
FLAMMABLE LIQUEFIED GAS.
FLAMMABLE LIQUID.
FLAMMABLE MATERIAL.
FLAMMABLE SOLID.
FLASH POINT.
HANDLING.
HAZARDOUS MATERIALS.
HEALTH HAZARD.
HIGHLY TOXIC.
INCOMPATIBLE MATERIALS.
INERT GAS.
OPEN SYSTEM.
OPERATING BUILDING.
ORGANIC PEROXIDE.
OXIDIZER.
OXIDIZING GAS.
PHYSICAL HAZARD.
PYROPHORIC.
PYROTECHNIC COMPOSITION.
TOXIC.
UNSTABLE (REACTIVE) MATERIAL.
WATER-REACTIVE MATERIAL.
AEROSOL
AEROSOL CONTAINER.
BALED COTTON.
BALED COTTON, DENSELY PACKED.
BARRICADE.
BOILING POINT.
CLOSED SYSTEM.
COMBUSTIBLE DUST.
COMBUSTIBLE FIBERS.
COMBUSTIBLE LIQUID.
Class II.
Class IIIA.
Class IIIB.
Class IIIA.
Class IIIB.
COMPRESSED GAS.
CONTROL AREA.
CORROSIVE.
CRYOGENIC FLUID.
DAY BOX.
DEFLAGRATION.
DETONATION.
DISPENSING.
EXPLOSION.
EXPLOSIVE.
High explosive.
Low explosive.
Mass-detonating explosives.
UN/DOTn Class 1 explosives.
Division 1.1.
Division 1.2.
Division 1.3.
Division 1.4.
Division 1.5.
Division 1.6.
Low explosive.
Mass-detonating explosives.
UN/DOTn Class 1 explosives.
Division 1.1.
Division 1.2.
Division 1.3.
Division 1.4.
Division 1.5.
Division 1.6.
FIREWORKS.
FLAMMABLE GAS.
FLAMMABLE LIQUEFIED GAS.
FLAMMABLE LIQUID.
Class IA.
Class IB.
Class IC.
Class IB.
Class IC.
FLAMMABLE MATERIAL.
FLAMMABLE SOLID.
FLASH POINT.
HANDLING.
HAZARDOUS MATERIALS.
HEALTH HAZARD.
HIGHLY TOXIC.
INCOMPATIBLE MATERIALS.
INERT GAS.
OPEN SYSTEM.
OPERATING BUILDING.
ORGANIC PEROXIDE.
OXIDIZER.
Class 4.
Class 3.
Class 2.
Class 1.
Class 3.
Class 2.
Class 1.
OXIDIZING GAS.
PHYSICAL HAZARD.
PYROPHORIC.
PYROTECHNIC COMPOSITION.
TOXIC.
UNSTABLE (REACTIVE) MATERIAL.
Class 4.
Class 3.
Class 2.
Class 1.
Class 3.
Class 2.
Class 1.
WATER-REACTIVE MATERIAL.
Class 3.
Class 2.
Class 1.
Class 2.
Class 1.
Buildings and structures containing materials that pose a detonation hazard shall be classified as Group H-1. Such materials shall include, but not be limited to, the following:
Detonable pyrophoric materials
Explosives:
Organic peroxides, unclassified detonable
Oxidizers, Class 4
Unstable (reactive) materials, Class 3 detonable and Class 4
Detonable pyrophoric materials
Explosives:
Division 1.1
Division 1.2
Division 1.3
Division 1.4
Division 1.5
Division 1.6
Division 1.2
Division 1.3
Division 1.4
Division 1.5
Division 1.6
Organic peroxides, unclassified detonable
Oxidizers, Class 4
Unstable (reactive) materials, Class 3 detonable and Class 4
The following occupancies containing explosive materials shall be classified as follows:
- Division 1.3 explosive materials that are used and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 occupancies.
- Articles, including articles packaged for shipment, that are not regulated as a Division 1.4 explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles shall be allowed in H-3 occupancies.
Buildings and structures containing materials that pose a deflagration hazard or a hazard from accelerated burning shall be classified as Group H-2. Such materials shall include, but not be limited to, the following:
- Class I, II or IIIA flammable or combustible liquids that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 pounds per square inch gauge (103.4 kPa).
- Combustible dusts where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3.
- Cryogenic fluids, flammable.
- Flammable gases.
- Organic peroxides, Class I.
- Oxidizers, Class 3, that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 pounds per square inch gauge (103 kPa).
- Pyrophoric liquids, solids and gases, nondetonable.
- Unstable (reactive) materials, Class 3, nondetonable.
- Water-reactive materials, Class 3.
Buildings and structures containing materials that readily support combustion or that pose a physical hazard shall be classified as Group H-3. Such materials shall include, but not be limited to, the following:
- Class I, II or IIIA flammable or combustible liquids that are used or stored in normally closed containers or systems pressurized at 15 pounds per square inch gauge (103.4 kPa) or less.
- Combustible fibers, other than densely packed baled cotton, where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3.
- Consumer fireworks, 1.4G (Class C, Common)
- Cryogenic fluids, oxidizing
- Flammable solids
- Organic peroxides, Class II and III
- Oxidizers, Class 2
- Oxidizers, Class 3, that are used or stored in normally closed containers or systems pressurized at 15 pounds per square inch gauge (103 kPa) or less
- Oxidizing gases
- Unstable (reactive) materials, Class 2
- Water-reactive materials, Class 2
Buildings and structures containing materials that are health hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the following:
- Corrosives
- Highly toxic materials
- Toxic materials
Semiconductor fabrication facilities and comparable research and development areas in which hazardous production materials (HPM) are used and the aggregate quantity of materials is in excess of those listed in Tables 307.1(1) and 307.1(2) shall be classified as Group H-5. Such facilities and areas shall be designed and constructed in accordance with Section 415.11.
Buildings and structures containing a material or materials representing hazards that are classified in one or more of Groups H-1, H-2, H-3 and H-4 shall conform to the code requirements for each of the occupancies so classified.
Institutional Group I occupancy includes, among others, the use of a building or structure, or a portion thereof, in which care or supervision is provided to persons who are or are not capable of self-preservation without physical assistance or in which persons are detained for penal or correctional purposes or in which the liberty of the occupants is restricted. Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-4.
The following terms are defined in Chapter 2:
24-HOUR BASIS.
CUSTODIAL CARE.
DETOXIFICATION FACILITIES.
FOSTERCHILD CARE FACILITIES.
HOSPITALS AND PSYCHIATRIC HOSPITALS.
INCAPABLE OF SELF-PRESERVATION.
MEDICAL CARE.
NURSING HOMES.
24-HOUR BASIS.
CUSTODIAL CARE.
DETOXIFICATION FACILITIES.
FOSTERCHILD CARE FACILITIES.
HOSPITALS AND PSYCHIATRIC HOSPITALS.
INCAPABLE OF SELF-PRESERVATION.
MEDICAL CARE.
NURSING HOMES.
The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.
TYPE I ASSISTED LIVING FACILITY. A residential facility licensed by the Utah Department of Health that provides a protected living arrangement for ambulatory, non-restrained persons who are capable of achieving mobility sufficient to exit the facility without the assistance of another person. Occupancies. Limited capacity, type I assisted living facilities with two to five residents shall be classified as R-3 occupancies. Small, type I assisted living facilities with six to sixteen residents shall be classified as R-4 occupancies. Large, type I assisted living facilities with over sixteen residents shall be classified as I-1 occupancies.
TYPE II ASSISTED LIVING FACILITY. A residential facility licensed by the Utah Department of Health that provides an array of coordinated supportive personal and health care services to residents who meet the definition of semi-independent.
Semi-Independent. A person who is:
TYPE I ASSISTED LIVING FACILITY. A residential facility licensed by the Utah Department of Health that provides a protected living arrangement for ambulatory, non-restrained persons who are capable of achieving mobility sufficient to exit the facility without the assistance of another person. Occupancies. Limited capacity, type I assisted living facilities with two to five residents shall be classified as R-3 occupancies. Small, type I assisted living facilities with six to sixteen residents shall be classified as R-4 occupancies. Large, type I assisted living facilities with over sixteen residents shall be classified as I-1 occupancies.
TYPE II ASSISTED LIVING FACILITY. A residential facility licensed by the Utah Department of Health that provides an array of coordinated supportive personal and health care services to residents who meet the definition of semi-independent.
Semi-Independent. A person who is:
- Physically disabled but able to direct his or her own care; or
- Cognitively impaired or physically disabled but able to evacuate from the facility with the physical assistance of one person. Occupancies. Limited capacity, type II assisted living facilities with two to five residents shall be classified as R-4 occupancies. Small, type II assisted living facilities with six to sixteen residents shall be classified as I-1 occupancies. Large, type II assisted living facilities with over sixteen residents shall be classified as I-2 occupancies.
Institutional Group I-1 occupancy shall include buildings, structures or portions thereof for more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised environment and receive custodial care. Buildings of Group I-1 shall be classified as one of the occupancy conditions specified in Section 308.3.1 or 308.3.2. This group shall include, but not be limited to, the following:
Alcohol and drug centers
Assisted living facilities. (see Section 308.2.1)
Congregate care facilities
Group homes
Halfway houses
Residential board and care facilities
Social rehabilitation facilities
Alcohol and drug centers
Assisted living facilities. (see Section 308.2.1)
Congregate care facilities
Group homes
Halfway houses
Residential board and care facilities
Social rehabilitation facilities
This occupancy condition shall include buildings in which all persons receiving custodial care who, without any assistance, are capable of responding to an emergency situation to complete building evacuation.
This occupancy condition shall include buildings in which there are any persons receiving custodial care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation.
A facility housing not fewer than six and not more than 16 persons receiving custodial care shall be classified as Group R-4.
A facility with five or fewer persons receiving custodial care shall be classified as Group R-3 or shall comply with the International Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or Section P2904 of the International Residential Code.
Institutional Group I-2 occupancy shall include buildings and structures used for medical care on a 24-hour basis for more than five personsthree persons who are incapable of self-preservation. This group shall include, but not be limited to, the following:
FosterChild care facilities
Detoxification facilities
Hospitals
Nursing homes (both intermediate care facilities and skilled nursing facilities)
Psychiatric hospitals
FosterChild care facilities
Detoxification facilities
Hospitals
Nursing homes (both intermediate care facilities and skilled nursing facilities)
Psychiatric hospitals
Buildings of Group I-2 shall be classified as one of the occupancy conditions specified in Section 308.4.1.1 or 308.4.1.2.
This occupancy condition shall include facilities that provide nursing and medical care but do not provide emergency care, surgery, obstetrics, or in-patient stabilization units for psychiatric or detoxification, including but not limited to nursing homes and foster care facilities.
This occupancy condition shall include facilities that provide nursing and medical care and could provide emergency care, surgery, obstetrics, or in-patient stabilization units for psychiatric or detoxification, including but not limited to hospitals.
A facility with fivefour or fewer persons receiving medical care shall be classified as Group R-3 or shall comply with the International Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or Section P2904 of the International Residential Code.
Institutional Group I-3 occupancy shall include buildings and structures that are inhabited by more than five persons who are under restraint or security. A Group I-3 facility is occupied by persons who are generally incapable of self-preservation due to security measures not under the occupants' control. This group shall include, but not be limited to, the following:
Buildings of Group I-3 shall be classified as one of the occupancy conditions specified in Sections 308.5.1 through 308.5.5 (see Section 408.1).
Correctional centers
Detention centers
Jails
Prerelease centers
Prisons
Reformatories
Detention centers
Jails
Prerelease centers
Prisons
Reformatories
Buildings of Group I-3 shall be classified as one of the occupancy conditions specified in Sections 308.5.1 through 308.5.5 (see Section 408.1).
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas, and other spaces where access or occupancy is permitted, to the exterior via means of egress without restraint. A Condition 1 facility is permitted to be constructed as Group R.
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas and any other occupied smoke compartment to one or more other smoke compartments. Egress to the exterior is impeded by locked exits.
This occupancy condition shall include buildings in which free movement is allowed within individual smoke compartments, such as within a residential unit comprised of individual sleeping units and group activity spaces, where egress is impeded by remote-controlled release of means of egress from such a smoke compartment to another smoke compartment.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Remote-controlled release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Staff-controlled manual release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.
Institutional Group I-4 occupancy shall include buildings and structures occupied by more than five four persons of any age who receive custodial care for fewer than 24 hours per day by persons other than parents or guardians, relatives by blood, marriage or adoption, and in a place other than the home of the person cared for. This group shall include, but not be limited to, the following:
Adult day care
Child day care
Adult day care
Child day care
A child day care facility that provides care for more than fivefour but not more than 100 children 21/ 2 years or less of ageunder the age of two, where the rooms in which the children are cared for are located on a level of exit discharge serving such rooms and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E. See Section 427 for special requirements for Day Care.
Rooms and spaces within places of religious worship providing such care during religious functions shall be classified as part of the primary occupancy.
A facility having fivefour or fewer persons receiving custodial care shall be classified as part of the primary occupancy. See Section 427 for special requirements for Day Care.
A facility such as the above within a dwelling unit and having five or fewer persons receiving custodial care shall be classified as a Group R-3 occupancy or shall comply with the International Residential Code.
Mercantile Group M occupancy includes, among others, the use of a building or structure or a portion thereof for the display and sale of merchandise, and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, the following:
Department stores
Drug stores
Markets
Motor fuel-dispensing facilities
Retail or wholesale stores
Sales rooms
Drug stores
Markets
Motor fuel-dispensing facilities
Retail or wholesale stores
Sales rooms
The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored or displayed in a single control area of a Group M occupancy shall not exceed the quantities in Table 414.2.5(1).
Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional Group I or when not regulated by the International Residential Code.
The following terms are defined in Chapter 2:
BOARDING HOUSE.
CONGREGATE LIVING FACILITIES.
DORMITORY.
GROUP HOME.
GUEST ROOM.
LODGING HOUSE.
PERSONAL CARE SERVICE.
TRANSIENT.
BOARDING HOUSE.
CONGREGATE LIVING FACILITIES.
DORMITORY.
GROUP HOME.
GUEST ROOM.
LODGING HOUSE.
PERSONAL CARE SERVICE.
TRANSIENT.
Residential Group R-1 occupancies containing sleeping units where the occupants are primarily transient in nature, including:
- Boarding houses (transient) with more than 10 occupants
- Congregate living facilities (transient) with more than 10
occupants - Hotels (transient)
- Motels (transient)
Residential Group R-2 occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including:
- Apartment houses
- Boarding houses (nontransient) with more than 16 occupants
- Congregate living facilities (nontransient) with more than 16 occupants
- Convents
- Dormitories
- Fraternities and sororities
- Hotels (nontransient)
- Live/work units
- Monasteries
- Motels (nontransient)
- Vacation timeshare properties
Residential Group R-3 occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, R-4 or I, including:
- Buildings that do not contain more than two dwelling units
- Boarding houses (nontransient) with 16 or fewer occupants
- Boarding houses (transient) with 10 or fewer occupants
- Care facilities that provide accommodations for five or fewer persons receiving care
- Congregate living facilities (nontransient) with 16 or fewer occupants
- Congregate living facilities (transient) with 10 or fewer occupants
- Lodging houses with five or fewer guest rooms
Care facilities for five or fewer persons receiving care that are within a single-family dwelling other than Child Care are permitted to comply with the International Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or Section P2904 of the International Residential Code. See Section 427 for special requirements for Child Day Care.
Owner-occupied lodging houses with five or fewer guest rooms shall be permitted to be constructed in accordance with the International Residential Code.
Areas used for child care purposes may be located in a residential dwelling unit under all of the following conditions and Section 427:
- Compliance with Utah Administrative Code, R710-8, Day Care Rules, as enacted under the authority of the Utah Fire Prevention Board.
- Use is approved by the Utah Department of Health, as enacted under the authority of the Utah Code, Title 26, Chapter 39, Utah Child Care Licensing Act, and in any of the following categories:
- Utah Administrative Code, R430-50, Residential Certificate Child Care.
- Utah Administrative Code, R430-90, Licensed Family Child Care.
- Compliance with all zoning regulations of the local regulator.
Residential Group R-4 occupancy shall include buildings, structures or portions thereof for more than five but not more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised residential environment and receive custodial care. Buildings of Group R-4 shall be classified as one of the occupancy conditions specified in Section 310.6.1 or 310.6.2. This group shall include, but not be limited to, the following:
Alcohol and drug centers
Assisted living facilities (see Section 308.2.1)
Congregate care facilities
Group homes
Halfway houses
Residential board and care facilities
Social rehabilitation facilities
Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3, except as otherwise provided for in this code.
Alcohol and drug centers
Assisted living facilities (see Section 308.2.1)
Congregate care facilities
Group homes
Halfway houses
Residential board and care facilities
Social rehabilitation facilities
Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3, except as otherwise provided for in this code.
This occupancy condition shall include buildings in which all persons receiving custodial care, without any assistance, are capable of responding to an emergency situation to complete building evacuation.
This occupancy condition shall include buildings in which there are any persons receiving custodial care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation.
Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage that is not classified as a hazardous occupancy.
A room or space used for storage purposes that is less than 100 square feet (9.3 m2) in area and accessory to another occupancy shall be classified as part of that occupancy. The aggregate area of such rooms or spaces shall not exceed the allowable area limits of Section 508.2.
Storage Group S-1 occupancies are buildings occupied for storage uses that are not classified as Group S-2, including, but not limited to, storage of the following:
- Aerosols, Levels 2 and 3
- Aircraft hangar (storage and repair)
- Bags: cloth, burlap and paper
- Bamboos and rattan
- Baskets
- Belting: canvas and leather
- Books and paper in rolls or packs
- Boots and shoes
- Buttons, including cloth covered, pearl or bone
- Cardboard and cardboard boxes
- Clothing, woolen wearing apparel
- Cordage
- Dry boat storage (indoor)
- Furniture
- Furs
- Glues, mucilage, pastes and size
- Grains
- Horns and combs, other than celluloid
-
Leather
Linoleum
Lumber - Motor vehicle repair garages complying with the maximum allowable quantities of hazardous materials listed in Table 307.1(1) (see Section 406.8)
- Photo engravings
- Resilient flooring
- Silks
- Soaps
- Sugar
- Tires, bulk storage of
- Tobacco, cigars, cigarettes and snuff
- Upholstery and mattresses
- Wax candles
Storage Group S-2 occupancies include, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of the following:
- Asbestos
- Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers
- Cement in bags
- Chalk and crayons
- Dairy products in nonwaxed coated paper containers
- Dry cell batteries
- Electrical coils
- Electrical motors
- Empty cans
- Food products
- Foods in noncombustible containers
- Fresh fruits and vegetables in nonplastic trays or containers
- Frozen foods
- Glass
- Glass bottles, empty or filled with noncombustible liquids
- Gypsum board
- Inert pigments
- Ivory
- Meats
- Metal cabinets
- Metal desks with plastic tops and trim
- Metal parts
- Metals
- Mirrors
- Oil-filled and other types of distribution transformers
- Parking garages, open or enclosed
- Porcelain and pottery
- Stoves
- Talc and soapstones
- Washers and dryers
Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of this code commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following:
- Agricultural buildings
- Aircraft hangars, accessory to a one- or two-family residence (see Section 412.5)
- Barns
- Carports
- Fences more than 6 feet (1829 mm) in height
- Grain silos, accessory to a residential occupancy
- Greenhouses
- Livestock shelters
- Private garages
- Retaining walls
- Sheds
- Stables
- Tanks
- Towers