ADOPTS WITHOUT AMENDMENTS:

NFPA 101, 2015

Heads up: There are no amended sections in this chapter.
The requirements of this chapter shall apply to new buildings or portions thereof used as educational occupancies. (See 1.3.1.)
The provisions of Chapter 1, Administration, shall apply.
The provisions of Chapter 4, General, shall apply.
Educational facilities that do not meet the definition of an educational occupancy shall not be required to comply with this chapter but shall comply with the following requirements:
  1. Instructional building — business occupancy
  2. Classrooms under 50 persons — business occupancy
  3. Classrooms, 50 persons and over — assembly occupancy
  4. Laboratories, instructional — business occupancy
  5. Laboratories, noninstructional — industrial occupancy
Educational occupancies shall include all buildings used for educational purposes through the twelfth grade by six or more persons for 4 or more hours per day or more than 12 hours per week.
Educational occupancies shall include preschools, kindergartens, and other schools meeting both of the following criteria:
  1. The purpose is primarily educational, even though the children who attend such schools are of preschool age.
  2. The children are all 24 months of age or older.
In cases where instruction is incidental to some other occupancy, the section of this Code governing such other occupancy shall apply.
Other occupancies associated with educational institutions shall be in accordance with the appropriate parts of this Code. (See Chapters 18, 20, 26, 28, 30, 40, and 42 and 6.1.14.)
Multiple occupancies shall be in accordance with 6.1.14.
Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies on a story-by-story basis.
Spaces subject to assembly occupancy shall comply with Chapter 12, including 12.1.3.2, which provides that, where auditorium and gymnasium egress lead through corridors or stairways also serving as egress for other parts of the building, the egress capacity shall be sufficient to allow simultaneous egress from auditorium and classroom sections.
In the case of an assembly occupancy of a type suitable for use only by the school occupant load, and therefore not subject to simultaneous occupancy, the same egress capacity shall be permitted to serve both sections.
Any building used for both classroom and dormitory purposes shall comply with the applicable provisions of Chapter 28 in addition to complying with Chapter 14.
Where classroom and dormitory sections are not subject to simultaneous occupancy, the same egress capacity shall be permitted to serve both sections.
For definitions, see Chapter 3, Definitions.
The contents of educational occupancies shall be classified in accordance with the provisions of Section 6.2.
The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space or shall be determined as the maximum probable population of the space under consideration, whichever is greater.
The occupant load of an educational occupancy, or a portion thereof, shall be permitted to be modified from that specified in 14.1.7.1 if the necessary aisles and exits are provided.
An approved aisle or seating diagram shall be required by the authority having jurisdiction to substantiate the modification permitted in 14.1.7.2.
Means of egress shall be in accordance with Chapter 7 and Section 14.2.
Rooms normally occupied by preschool, kindergarten, or first-grade students shall be located on a level of exit discharge, unless otherwise permitted by 14.2.1.4.
Rooms normally occupied by second-grade students shall not be located more than one story above a level of exit discharge, unless otherwise permitted by 14.2.1.4.
Rooms or areas located on floor levels other than as specified in 14.2.1.2 and 14.2.1.3 shall be permitted to be used where provided with independent means of egress dedicated for use by the preschool, kindergarten, first-grade, or second-grade students.
Components of means of egress shall be limited to the types described in 14.2.2.2 through 14.2.2.10.
Doors complying with 7.2.1 shall be permitted.
Any door in a required means of egress from an area having an occupant load of 100 or more persons shall be permitted to be provided with a latch or lock only if the latch or lock is panic hardware or fire exit hardware complying with 7.2.1.7.
Delayed-egress locking systems complying with 7.2.1.6.1 shall be permitted.
Access-controlled egress door assemblies complying with 7.2.1.6.2 shall be permitted.
Elevator lobby exit access door assemblies locking in accordance with 7.2.1.6.3 shall be permitted.
Stairs complying with 7.2.2 shall be permitted.
Smokeproof enclosures complying with 7.2.3 shall be permitted.
Horizontal exits complying with 7.2.4 shall be permitted.
Ramps complying with 7.2.5 shall be permitted.
Exit passageways complying with 7.2.6 shall be permitted.
Fire escape ladders complying with 7.2.9 shall be permitted.
Alternating tread devices complying with 7.2.11 shall be permitted.
Areas of refuge complying with 7.2.12 shall be permitted.
Capacity of means of egress shall be in accordance with Section 7.3.
Exit access corridors shall have not less than 6 ft (1830 mm) of clear width.
The number of means of egress shall be in accordance with Section 7.4.
Not less than two separate exits shall be in accordance with the following criteria:
  1. They shall be provided on every story.
  2. They shall be accessible from every part of every story and mezzanine; however, exit access travel shall be permitted to be common for the distance permitted as common path of travel by 14.2.5.3.
Means of egress shall be arranged in accordance with Section 7.5.

14.2.5.2

ILLUSTRATION
No dead-end corridor shall exceed 20 ft (6100 mm), other than in buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7, in which case dead-end corridors shall not exceed 50 ft (15 m).
Limitations on common path of travel shall be in accordance with 14.2.5.3.1 and 14.2.5.3.2.
Common path of travel shall not exceed 100 ft (30 m) in a building protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Common path of travel shall not exceed 75 ft (23 m) in a building not protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Every room or space larger than 1000 ft2 (93 m2) or with an occupant load of more than 50 persons shall comply with the following:
  1. The room or space shall have a minimum of two exit access doors.
  2. The doors required by 14.2.5.4(1) shall provide access to separate exits.
  3. The doors required by 14.2.5.4(1) shall be permitted to open onto a common corridor, provided that such corridor leads to separate exits located in opposite directions.
Every room that is normally subject to student occupancy shall have an exit access door leading directly to an exit access corridor or exit, unless otherwise permitted by one of the following:
  1. This requirement shall not apply where an exit door opens directly to the outside or to an exterior balcony or corridor as described in 14.2.5.9.
  2. One room shall be permitted to intervene between a normally occupied student room and an exit access corridor, provided that all of the following criteria are met:
    1. The travel from a room served by an intervening room to the corridor door or exit shall not exceed 75 ft (23 m).
    2. Clothing, personal effects, or other materials deemed hazardous by the authority having jurisdiction shall be stored in metal lockers, provided that they do not obstruct the exit access, or the intervening room shall be sprinklered in accordance with Section 9.7.
    3. One of the following means of protection shall be provided:
      1. The intervening room shall have approved fire detection that activates the building alarm.
      2. The building shall be protected by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Doors that swing into an exit access corridor shall be arranged to prevent interference with corridor travel. (See also 7.2.1.4.3.)
Aisles shall be not less than 30 in. (760 mm) wide.
The space between parallel rows of seats shall not be subject to the minimum aisle width, provided that the number of seats that intervenes between any seat and an aisle does not exceed six.
Exterior exit access shall comply with 7.5.3.
Travel distance shall comply with 14.2.6.1 through 14.2.6.3.
Travel distance shall be measured in accordance with Section 7.6.
Travel distance to an exit shall not exceed 150 ft (46 m) from any point in a building, unless otherwise provided in 14.2.6.3. (See also Section 7.6.)
Travel distance shall not exceed 200 ft (61 m) in educational occupancies protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Discharge from exits shall be arranged in accordance with Section 7.7.
Emergency lighting shall be provided in accordance with Section 7.9.
Means of egress shall have signs in accordance with Section 7.10.
Every room or space greater than 250 ft2 (23.2 m2) and used for classroom or other educational purposes or normally subject to student occupancy shall have not less than one outside window for emergency rescue that complies with all of the following, unless otherwise permitted by 14.2.11.1.2:
  1. Such windows shall be openable from the inside without the use of tools and shall provide a clear opening of not less than 20 in. (510 mm) in width, 24 in. (610 mm) in height, and 5.7 ft2 (0.5 m2) in area.
  2. The bottom of the opening shall be not more than 44 in. (1120 mm) above the floor, and any latching device shall be capable of being operated from not more than 54 in. (1370 mm) above the finished floor.
  3. The clear opening shall allow a rectangular solid, with a width and height that provides not less than the required 5.7 ft2 (0.5 m2) opening and a depth of not less than 20 in. (510 mm), to pass fully through the opening.
  4. Such windows shall be accessible by the fire department and shall open into an area having access to a public way.
The requirements of 14.2.11.1.1 shall not apply to any of the following:
  1. Buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7
  2. Where the room or space has a door leading directly to an exit or directly to the outside of the building
  3. Reserved
  4. Rooms located four or more stories above the finished ground level
Lockups in educational occupancies shall comply with the requirements of 22.4.5.
Any vertical opening, other than unprotected vertical openings in accordance with 8.6.9.1, shall be enclosed or protected in accordance with Section 8.6.
Where the provisions of 8.6.6 are used, the requirements of 14.3.5.4 shall be met.
Rooms or spaces for the storage, processing, or use of materials shall be protected in accordance with the following:
  1. Such rooms or spaces shall be separated from the remainder of the building by fire barriers having a minimum 1-hour fire resistance rating or protected by automatic extinguishing systems as specified in Section 8.7 in the following areas:
    1. Boiler and furnace rooms, unless such rooms enclose only air-handling equipment
    2. Rooms or spaces used for the storage of combustible supplies in quantities deemed hazardous by the authority having jurisdiction
    3. Rooms or spaces used for the storage of hazardous materials or flammable or combustible liquids in quantities deemed hazardous by recognized standards
    4. Janitor closets [see also 14.3.2.1(4)]
  2. Such rooms or spaces shall be separated from the remainder of the building by fire barriers having a minimum 1-hour fire resistance rating and protected by automatic extinguishing systems as specified in Section 8.7 in the following areas:
    1. Laundries
    2. Maintenance shops, including woodworking and painting areas
    3. Rooms or spaces used for processing or use of combustible supplies deemed hazardous by the authority having jurisdiction
    4. Rooms or spaces used for processing or use of hazardous materials or flammable or combustible liquids in quantities deemed hazardous by recognized standards
  3. Where automatic extinguishing is used to meet the requirements of 14.3.2.1(1) or (2), the protection shall be permitted in accordance with 9.7.1.2.
  4. Where janitor closets addressed in 14.3.2.1(1)(d) are protected in accordance with the sprinkler option of 14.3.2.1(1), the janitor closet doors shall be permitted to have ventilating louvers.
Cooking facilities shall be protected in accordance with 9.2.3. Openings shall not be required to be protected between food preparation areas and dining areas.
Stages and platforms shall be protected in accordance with Chapter 12.
Educational occupancy laboratories using chemicals shall be in accordance with 8.7.4.
Interior finish shall be in accordance with Section 10.2.
Interior wall and ceiling finish materials complying with Section 10.2 shall be permitted as follows:
  1. Exits — Class A
  2. Other than exits — Class A or Class B
  3. Low-height partitions not exceeding 60 in. (1525 mm) and used in locations other than exits — Class A, Class B, or Class C
Interior floor finish in exit enclosures and exit access corridors and spaces not separated from them by walls complying with 14.3.6 shall be not less than Class II.
Interior floor finish shall comply with 10.2.7.1 or 10.2.7.2, as applicable.
Educational occupancies shall be provided with a fire alarm system in accordance with Section 9.6.
The requirement of 14.3.4.1.1 shall not apply to buildings meeting all of the following criteria:
  1. Buildings having an area not exceeding 1000 ft2 (93 m2)
  2. Buildings containing a single classroom
  3. Buildings located not less than 30 ft (9.1 m) from another building
Initiation of the required fire alarm system, other than as permitted by 14.3.4.2.3, shall be by manual means in accordance with 9.6.2.1(1).
In buildings provided with automatic sprinkler protection, the operation of the sprinkler system shall automatically activate the fire alarm system in addition to the initiation means required in 14.3.4.2.1.
Manual fire alarm boxes shall be permitted to be eliminated in accordance with 14.3.4.2.3.1 or 14.3.4.2.3.2.
Manual fire alarm boxes shall be permitted to be eliminated where all of the following conditions apply:
  1. Interior corridors are protected by smoke detectors in accordance with Section 9.6.
  2. Auditoriums, cafeterias, and gymnasiums are protected by heat-detection devices or other approved detection devices.
  3. Shops and laboratories involving dusts or vapors are protected by heat-detection devices or other approved detection devices.
  4. Provision is made at a central point to manually activate the evacuation signal or to evacuate only affected areas.
Manual fire alarm boxes shall be permitted to be eliminated where both of the following conditions apply:
  1. The building is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
  2. Provision is made at a central point to manually activate the evacuation signal or to evacuate only affected areas.
Occupant notification shall be accomplished automatically in accordance with 9.6.3.
The occupant notification required by 14.3.4.3.1.1 shall utilize an emergency voice/alarm communication system in accordance with 9.6.3 where the building has an occupant load of more than 100.
Positive alarm sequence shall be permitted in accordance with 9.6.3.4.
In accordance with 9.6.3.10.2 the emergency voice/alarm communication system shall be permitted to be used for other emergency signaling or for class changes.
To prevent students from being returned to a building that is burning, the recall signal shall be separate and distinct from any other signals, and such signal shall be permitted to be given by use of distinctively colored flags or banners.
If the recall signal required by 14.3.4.3.1.5 is electric, the push buttons or other controls shall be kept under lock, the key for which shall be in the possession of the principal or another designated person in order to prevent a recall at a time when there is an actual fire.
Regardless of the method of recall signal, the means of giving the recall signal shall be kept under lock.
Emergency forces notification shall be accomplished in accordance with 9.6.4.
Carbon monoxide alarms or carbon monoxide detectors in accordance with Section 9.12 shall be provided in new educational occupancies in the locations specified as follows:
  1. On the ceilings of rooms containing permanently installed fuel-burning appliances
  2. Centrally located within occupiable spaces served by the first supply air register from a permanently installed, fuel-burning HVAC system
  3. Centrally located within occupiable spaces adjacent to a communicating attached garage
Carbon monoxide alarms and carbon monoxide detectors as specified in 14.3.4.4.1 shall not be required in the following locations:
  1. Garages
  2. Occupiable spaces with communicating attached garages that are open parking structures as defined in 3.3.272.7.4
  3. Occupiable spaces with communicating attached garages that are mechanically ventilated in accordance with the applicable mechanical code
Educational occupancy buildings exceeding 12,000 ft2 (1120 m2) shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Educational occupancy buildings four or more stories in height shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Every portion of educational buildings below the level of exit discharge shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Buildings with unprotected openings in accordance with 8.6.6 shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Where another provision of this chapter requires an automatic sprinkler system, the sprinkler system shall be installed in accordance with 9.7.1.1(1).
Corridors shall be separated from other parts of the story by walls having a 1-hour fire resistance rating in accordance with Section 8.3, unless otherwise permitted by one of the following:
  1. Corridor protection shall not be required where all spaces normally subject to student occupancy have not less than one door opening directly to the outside or to an exterior exit access balcony or corridor in accordance with 7.5.3.
  2. The following shall apply to buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7:
    1. Corridor walls shall not be required to be rated, provided that such walls form smoke partitions in accordance with Section 8.4.
    2. The provisions of 8.4.3.5 shall not apply to normally occupied classrooms.
  3. Where the corridor ceiling is an assembly having a 1-hour fire resistance rating where tested as a wall, the corridor walls shall be permitted to terminate at the corridor ceiling.
  4. Lavatories shall not be required to be separated from corridors, provided that they are separated from all other spaces by walls having not less than a 1-hour fire resistance rating in accordance with Section 8.3.
  5. Lavatories shall not be required to be separated from corridors, provided that both of the following criteria are met:
    1. The building is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
    2. The walls separating the lavatory from other rooms form smoke partitions in accordance with Section 8.4.
Educational occupancies shall be subdivided into compartments by smoke partitions having not less than a 1-hour fire resistance rating and complying with Section 8.4 where one or both of the following conditions exist:
  1. The maximum floor area, including the aggregate area of all floors having a common atmosphere, exceeds 30,000 ft2 (2800 m2).
  2. The length or width of the building exceeds 300 ft (91 m).
The requirement of 14.3.7.1 shall not apply to either of the following:
  1. Where all spaces normally subject to student occupancy have not less than one door opening directly to the outside or to an exterior or exit access balcony or corridor in accordance with 7.5.3
  2. Buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7
The area of any smoke compartment required by 14.3.7.1 shall not exceed 30,000 ft2 (2800 m2), with no dimension exceeding 300 ft (91 m).
Limited access buildings and underground buildings shall comply with Section 11.7.
Flexible plan and open plan buildings shall comply with the requirements of this chapter as modified by 14.4.3.2 through 14.4.3.5.
Each room occupied by more than 300 persons shall have two or more means of egress entering into separate atmospheres.
Where three or more means of egress are required, the number of means of egress permitted to enter into the same atmosphere shall not exceed two.
Flexible plan buildings shall be permitted to have walls and partitions rearranged periodically only if revised plans or diagrams have been approved by the authority having jurisdiction.
Flexible plan buildings shall be evaluated while all folding walls are extended and in use as well as when they are in the retracted position.
Alcohol-based hand-rub dispensers shall be protected in accordance with 8.7.3.1, unless all of the following requirements are met:
  1. Dispensers shall be installed in rooms or spaces separated from corridors and exits.
  2. The maximum individual dispenser fluid capacity shall be as follows:
    1. 0.32 gal (1.2 L) for dispensers in rooms
    2. 0.53 gal (2.0 L) for dispensers in suites of rooms
  3. The dispensers shall be separated from each other by horizontal spacing of not less than 48 in. (1220 mm).
  4. Storage of quantities greater than 5 gal (18.9 L) in a single fire compartment shall meet the requirements of NFPA 30, Flammable and Combustible Liquids Code.
  5. The dispensers shall not be installed over or directly adjacent to an ignition source.
  6. Dispensers installed directly over carpeted floors shall be permitted only in sprinklered rooms or spaces.
Utilities shall comply with the provisions of Section 9.1.
Heating, ventilating, and air-conditioning equipment shall comply with the provisions of Section 9.2.
Unvented fuel-fired heating equipment, other than gas space heaters in compliance with NFPA 54/ANSI Z223.1, National Fuel Gas Code, shall be prohibited.
Elevators, escalators, and conveyors shall comply with the provisions of Section 9.4.
Waste chutes, incinerators, and laundry chutes shall comply with the provisions of Section 9.5.
Emergency action plans shall be provided in accordance with Section 4.8.
Emergency egress drills shall be conducted in accordance with Section 4.7 and the applicable provisions of 14.7.2.3 as otherwise provided in 14.7.2.2.
Approved training programs designed for education and training and for the practice of emergency egress to familiarize occupants with the drill procedure, and to establish conduct of the emergency egress as a matter of routine, shall be permitted to receive credit on a one-for-one basis for not more than four of the emergency egress drills required by 14.7.2.3, provided that a minimum of four emergency egress drills are completed prior to the conduct of the first such training and practice program.
Emergency egress drills shall be conducted as follows:
  1. Not less than one emergency egress drill shall be conducted every month the facility is in session, unless both of the following criteria are met:
    1. In climates where the weather is severe, the monthly emergency egress drills shall be permitted to be deferred.
    2. The required number of emergency egress drills shall be conducted, and not less than four shall be conducted before the drills are deferred.
  2. All occupants of the building shall participate in the drill.
  3. One additional emergency egress drill, other than for educational occupancies that are open on a year-round basis, shall be required within the first 30 days of operation.
All emergency drill alarms shall be sounded on the fire alarm system.
It shall be the duty of principals, teachers, or staff to inspect all exit facilities daily to ensure that all stairways, doors, and other exits are in proper condition.
Open plan buildings shall require extra surveillance to ensure that exit paths are maintained clear of obstruction and are obvious.
Door openings shall be inspected in accordance with 7.2.1.15.
Draperies, curtains, and other similar furnishings and decorations in educational occupancies shall be in accordance with the provisions of 10.3.1.
Clothing and personal effects shall not be stored in corridors, unless otherwise permitted by one of the following:
  1. This requirement shall not apply to corridors protected by an automatic sprinkler system in accordance with Section 9.7.
  2. This requirement shall not apply to corridor areas protected by a smoke detection system in accordance with Section 9.6.
  3. This requirement shall not apply to storage in metal lockers, provided that the required egress width is maintained.
Artwork and teaching materials shall be permitted to be attached directly to the walls in accordance with the following:
  1. The artwork and teaching materials shall not exceed 20 percent of the wall area in a building that is not protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
  2. The artwork and teaching materials shall not exceed 50 percent of the wall area in a building that is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Approved open flames shall be permitted in laboratories and vocational/technical areas.