ADOPTS WITHOUT AMENDMENTS:

NFPA 101, 2015

Heads up: There are no amended sections in this chapter.
The requirements of Sections 11.1 through 11.11 shall apply to occupancies regulated by Chapters 12 through 42 that are in a special structure. The applicable provisions of Chapters 12 through 42 shall apply, except as modified by this chapter. Section 11.8 shall apply to high-rise buildings only where specifically required by Chapters 12 through 42.
For definitions see Chapter 3 Definitions.
Special terms used in this chapter are located within each special structure section.
Occupancies regulated by Chapters 12 through 42 that are in special structures shall meet the requirements of those chapters, except as modified by this chapter.
Classification of hazard of contents shall be in accordance with Section 6.2.
Minimum construction requirements shall be in accordance with the applicable occupancy chapter.
The occupant load of special structures shall be based on the use of the structure as regulated by Chapters 12 through 42.
Where another provision of this chapter requires an automatic sprinkler system, the automatic sprinkler system shall be installed in accordance with the subparts of 9.7.1.1 as permitted by the applicable occupancy chapter.
The provisions of Section 11.1 shall apply.
The means of egress provisions of the applicable occupancy chapter, Chapters 12 through 42, shall apply, except as modified by 11.2.2.2 through 11.2.2.10.
Open structures that are designed for occupancy by not more than three persons shall be permitted to be served by fire escape ladders complying with 7.2.9.
Open structures shall be exempt from the requirements for capacity of means of egress.
Open structures at the finished ground level are exempt from the requirements for number of means of egress.
Open structures occupied by not more than three persons, with travel distance of not more than 200 ft (61 m), shall be permitted to have a single exit.
Open structures shall be exempt from travel distance limitations.
Open structures permitted to have a single exit per 11.2.2.4 shall be permitted to have 100 percent of the exit discharge through areas on the level of exit discharge.
Open structures shall be exempt from illumination of means of egress requirements.
Open structures shall be exempt from emergency lighting requirements.
Open structures shall be exempt from marking of means of egress requirements.
Open structures shall be exempt from protection of vertical opening requirements.
Every open structure, other than those structures with only occasional occupancy, shall have automatic, manual, or other protection that is appropriate to the particular hazard and that is designed to minimize danger to occupants in case of fire or other emergency before they have time to use the means of egress.
Open structures shall be exempt from requirements for detection, alarm, and communications systems.
The provisions of Section 11.1 shall apply.
In towers protected throughout by an automatic sprinkler system in accordance with Section 9.7, the levels located below the observation level shall be permitted to be occupied only for the following uses that support tower operations:
  1. Use as electrical and mechanical equipment rooms, including emergency power, radar, communications, and electronics rooms
  2. *Incidental accessory uses
Electronic supervision of supervisory signals shall be provided in accordance with 9.7.2.1. Waterflow alarms shall be monitored in accordance with 9.7.2.2.
The means of egress provisions of the applicable occupancy chapter, Chapters 12 through 42, shall apply, except as modified by 11.3.2.2 through 11.3.2.10.
Towers, such as forest fire observation or railroad signal towers, that are designed for occupancy by not more than three persons shall be permitted to be served by fire escape ladders complying with 7.2.9.
Towers subject to occupancy by not more than 90 persons shall be permitted to use elevators in the means of egress in accordance with 7.2.13.
Means of egress for towers shall be provided for the number of persons expected to occupy the space.
Spaces not subject to human occupancy because of machinery or equipment shall be excluded from consideration.
Towers shall be permitted to have a single exit, provided that the following conditions are met:
  1. The tower shall be subject to occupancy by fewer than 25 persons.
  2. The tower shall not be used for living or sleeping purposes.
  3. The tower shall be of Type I, Type II, or Type IV construction. (See 8.2.1.)
  4. The tower interior wall and ceiling finish shall be Class A or Class B.
  5. No combustible materials shall be located within the tower, under the tower, or within the immediate vicinity of the tower, except necessary furniture.
  6. No high hazard occupancies shall be located within the tower or within its immediate vicinity.
  7. Where the tower is located above a building, the single exit from the tower shall be provided by one of the following:
    1. Exit enclosure separated from the building with no door openings to or from the building
    2. Exit enclosure leading directly to an exit enclosure serving the building, with walls and door separating the exit enclosures from each other, and another door allowing access to the top floor of the building that provides access to a second exit serving that floor
Towers with 360-degree line-of-sight requirements shall be permitted to have a single means of egress for a distance of travel not exceeding 75 ft (23 m), or 100 ft (30 m) if the tower is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
Electronic supervision of sprinkler system supervisory signals shall be provided in accordance with 9.7.2.1 and waterflow alarms shall be monitored in accordance with 9.7.2.2.
Towers where ladders are permitted by 11.3.2.2.1 shall be exempt from travel distance limitations.
Towers permitted to have a single exit per 11.3.2.4 shall be permitted to have 100 percent of the exit discharge through areas on the level of exit discharge.
Towers where ladders are permitted by 11.3.2.2.1 shall be exempt from illumination of means of egress requirements.
Towers where ladders are permitted by 11.3.2.2.1 shall be exempt from emergency lighting requirements.
Locations not routinely inhabited by humans shall be exempt from emergency lighting requirements.
Structures occupied only during daylight hours, with windows arranged to provide the required level of illumination of all portions of the means of egress during such hours, shall be exempt from emergency lighting requirements where approved by the authority having jurisdiction.
Towers where ladders are permitted by 11.3.2.2.1 shall be exempt from marking of means of egress requirements.
Locations not routinely inhabited by humans shall be exempt from marking of means of egress requirements.
Towers where ladders are permitted by 11.3.2.2.1 shall be exempt from protection of vertical opening requirements.
In towers where the support structure is open and there is no occupancy below the top floor level, stairs shall be permitted to be open with no enclosure required, or fire escape stairs shall be permitted.
Every tower, other than structures with only occasional occupancy, shall have automatic, manual, or other protection that is appropriate to the particular hazard and that is designed to minimize danger to occupants in case of fire or other emergency before they have time to use the means of egress.
Towers designed for occupancy by not more than three persons shall be exempt from requirements for detection, alarm, and communications systems.
The levels located below the observation level shall be permitted to be occupied only for the following uses that support tower operations:
  1. Use as electrical and mechanical equipment rooms, including emergency and standby power, radar, communications, and electronics rooms
  2. *Incidental accessory uses
New air traffic control towers shall be of Type I or Type II construction. (See 8.2.1.)
Air traffic control towers shall be permitted to have a single exit, provided that the following conditions are met in addition to the requirements of 11.3.2.4:
  1. Each level of new air traffic control towers, served by a single exit, shall be subject to a calculated occupant load of 15 or fewer persons.
  2. The requirements of 11.3.2.4.1(1) shall not apply to existing air traffic control towers.
  3. Smoke detection shall be provided throughout air traffic control towers to meet the requirements of partial coverage, as defined in 17.5.3.2 of NFPA 72, National Fire Alarm and Signaling Code, and shall include coverage of all of the following:
    1. Occupiable areas
    2. Common areas
    3. Work spaces
    4. Equipment areas
    5. Means of egress
    6. Accessible utility shafts
  4. The requirements of 11.3.2.4.1(5) shall not apply.
  5. Rooms or spaces used for the storage, processing, or use of combustible supplies shall be permitted in quantities deemed acceptable by the authority having jurisdiction.
Means of egress for air traffic control towers shall be provided for the occupant load, as determined in accordance with 7.3.1.
Shafts, stairs, and spaces and floors not subject to human occupancy shall be excluded from consideration in determining the total calculated occupant load of the tower as required by 11.3.2.4.1(1) and 11.3.4.4.1(1).
A single means of egress shall be permitted from the observation level of an air traffic control tower, as permitted by 11.3.2.4.2.
For other than existing, previously approved air traffic control towers, smokeproof exit enclosures complying with 7.2.3 shall be provided for all air traffic control tower exit stair enclosures.
Air traffic control towers shall comply with the requirements of 7.7.2, except as permitted by 11.3.4.4.6.2.
Existing, single-exit air traffic control towers shall be permitted to have discharge of the exit comply with one of the following:
  1. Discharge of the exit in a previously approved, single-exit air traffic control tower is permitted to a vestibule or foyer complying with the requirements of 7.7.2(4)(b).
  2. *Discharge of the exit in a single-exit air traffic control tower is permitted within the building to a location where two means of egress are available and are arranged to allow travel in independent directions after leaving the exit enclosure, so that both means of egress do not become compromised by the same fire or similar emergency.
For other than existing, previously approved air traffic control towers, air traffic control towers shall be provided with a fire alarm system in accordance with Section 9.6. Smoke detection shall be provided throughout the air traffic control tower to meet the requirements for selective coverage, as defined in 17.5.3.2 of NFPA 72, National Fire Alarm and Signaling Code, and shall include coverage of all of the following:
  1. At equipment areas
  2. Outside each opening into exit enclosures
  3. Along the single means of egress permitted from observation levels in 11.3.2.4.2
  4. Outside each opening into the single means of egress permitted from observation levels in 11.3.2.4.2
New air traffic control towers shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
New air traffic control towers where the floor of the cab is greater than 30 ft (9.1 m) above the lowest level of fire department vehicle access shall be protected throughout with a Class I standpipe system in accordance with Section 9.7. Class I standpipes shall be manual standpipes, as defined in NFPA 14, Standard for the Installation of Standpipe and Hose Systems, where permitted by the authority having jurisdiction.
Sleeping areas shall be prohibited in air traffic control towers.
The provisions of Sections 11.1 and 11.4 shall apply to those structures that are not under the jurisdiction of the U.S. Coast Guard and not designed and arranged in accordance with U.S. Coast Guard regulations.
The means of egress provisions of the applicable occupancy chapter, Chapters 12 through 42, shall apply, except as modified by 11.4.2.2 through 11.4.2.10.
Spaces in water-surrounded structures that are not subject to human occupancy because of machinery or equipment shall be exempt from the requirements for capacity of means of egress.
Structures permitted to have a single exit per the applicable occupancy chapter shall be permitted to have 100 percent of the exit discharge through areas on the level of exit discharge.
Locations not routinely inhabited by humans are exempt from emergency lighting requirements.
Structures occupied only during daylight hours, with windows arranged to provide the required level of illumination of all portions of the means of egress during such hours, shall be exempt from emergency lighting requirements where approved by the authority having jurisdiction.
Locations not routinely inhabited by humans shall be exempt from marking of means of egress requirements.
Every water-surrounded structure, other than structures with only occasional occupancy, shall have automatic, manual, or other protection that is appropriate to the particular hazard and that is designed to minimize danger to occupants in case of fire or other emergency before they have time to use the means of egress.
The provisions of Section 11.1 shall apply.
Piers used exclusively to moor cargo vessels and to store material shall be exempt from number of means of egress requirements where provided with proper means of egress from structures thereon to the pier and a single means of access to the mainland, as appropriate to the pier's arrangement.
Buildings on piers not meeting the requirements of 11.5.2.1 and occupied for other than cargo handling and storage shall be in accordance with both of the following:
  1. Means of egress shall be arranged in accordance with Chapters 12 through 43.
  2. One of the following measures shall be provided on piers extending over 150 ft (46 m) from shore to minimize the possibility that fire under or on the pier blocks the escape of occupants to shore:
    1. The pier shall be arranged to provide two separate ways to travel to shore, such as by two well-separated walkways or independent structures.
    2. The pier deck shall be open, fire resistive, and set on noncombustible supports.
    3. The pier shall be open, unobstructed, and not less than 50 ft (15 m) in width if less than 500 ft (150 m) long, or its width shall be not less than 10 percent of its length if more than 500 ft (150 m) long.
    4. The pier deck shall be provided with an approved automatic sprinkler system in accordance with Section 9.7 for combustible substructures and all superstructures.
    5. The sprinkler system specified in 11.5.2.2(2)(d) shall be supervised where required by the applicable occupancy chapter, Chapters 12 through 42.
Where immobile, attached to a building, or permanently fixed to a foundation, and where subject to human occupancy, the following vehicles shall comply with the requirements of this Code that are appropriate to buildings of similar occupancy:
  1. Trailers
  2. Railroad cars
  3. Streetcars
  4. Buses
  5. Conveyances similar to those in 11.6.1(1) through (4)
Any ship, barge, or other vessel permanently fixed to a foundation or mooring, or unable to get underway by means of its own power, and occupied for purposes other than navigation shall be subject to the requirements of this Code that apply to buildings of similar occupancy.
The provisions of Section 11.1 shall apply.
A structure or portion of a structure that does not have openings in compliance with 11.7.3.1.1 and 11.7.3.1.2 shall be designated as a limited access structure and shall comply with 11.7.3.4 and 11.7.3.5.
One-story structures shall have finished ground level doors or emergency access openings in accordance with 11.7.3.2 on two sides of the building, spaced not more than 125 ft (38 m) apart on the exterior walls.
Multiple-story structures shall comply with the following:
  1. The story at the finished ground level shall comply with 11.7.3.1.1.
  2. Other stories shall be provided with emergency access openings in accordance with 11.7.3.2 on two sides of the building, spaced not more than 30 ft (9.1 m) apart.
Emergency access openings shall consist of a window, panel, or similar opening that complies with all of the following:
  1. The opening shall have dimensions of not less than 22 in. (560 mm) in width and 24 in. (610 mm) in height and shall be unobstructed to allow for ventilation and rescue operations from the exterior.
  2. The bottom of the opening shall be not more than 44 in. (1120 mm) above the floor.
  3. The opening shall be readily identifiable from both the exterior and interior.
  4. The opening shall be readily openable from both the exterior and interior.
A structure or portion of a structure shall not be considered an underground structure if the story is provided, on not less than two sides, with not less than 20 ft2 (1.9 m2) of emergency access opening located entirely above the adjoining finished ground level in each 50 lineal ft (15 lineal m) of exterior enclosing wall area.
Underground and limited access structures, and all areas and floor levels traversed in traveling to the exit discharge, shall be protected by an approved, supervised automatic sprinkler system in accordance with Section 9.7, unless such structures meet one of the following criteria:
  1. They have an occupant load of 50 or fewer persons in new underground or limited access portions of the structure.
  2. They have an occupant load of 100 or fewer persons in existing underground or limited access portions of the structure.
  3. The structure is a one-story underground or limited access structure that is permitted to have a single exit per Chapters 12 through 43, with a common path of travel not greater than 50 ft (15 m).
Underground or limited access portions of structures and all areas traversed in traveling to the exit discharge, other than in one- and two-family dwellings, shall be provided with emergency lighting in accordance with Section 7.9.
The requirements of 11.7.3 shall apply.
Exits from underground structures with an occupant load of more than 100 persons in the underground portions of the structure and having a floor used for human occupancy located more than 30 ft (9.1 m) below the lowest level of exit discharge, or having more than one level located below the lowest level of exit discharge, shall be provided with outside smoke-venting facilities or other means to prevent the exits from becoming charged with smoke from any fire in the areas served by the exits.
The underground portions of an underground structure, other than an existing underground structure, shall be provided with approved automatic smoke venting in accordance with Section 9.3 where the underground structure has the following features:
  1. Occupant load of more than 100 persons in the underground portions of the structure
  2. Floor level used for human occupancy located more than 30 ft (9.1 m) below the lowest level of exit discharge, or more than one level located below the lowest level of exit discharge
  3. Combustible contents, combustible interior finish, or combustible construction
Exit stair enclosures in underground structures having a floor level used for human occupancy located more than 30 ft (9.1 m) below the lowest level of exit discharge, or having more than one level located below the lowest level of exit discharge, shall be provided with signage in accordance with 7.2.2.5.4 at each floor level landing traversed in traveling to the exit discharge. The signs shall include a chevron-shaped indicator to show direction to the exit discharge.
The provisions of Section 11.8 shall apply to the following:
  1. New high-rise buildings, as defined in 3.3.36.7
  2. Existing high-rise buildings as required by Chapters 13, 15, 17, 19, 21, 23, 26, 29, 31, 33, 37, 39, 40, 42, or 43
In addition to the requirements of Section 11.8, compliance with all other applicable provisions of this Code shall be required.
In other than newly constructed high-rise buildings, locks in accordance with 7.2.1.6.3 shall be permitted.
High-rise buildings shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. A sprinkler control valve and a waterflow device shall be provided for each floor.
High-rise buildings shall be protected throughout by a Class I standpipe system in accordance with Section 9.7.
A fire alarm system using an approved emergency voice/alarm communication system shall be installed in accordance with Section 9.6.
Two-way telephone service shall be in accordance with 11.8.4.2.1 and 11.8.4.2.2.
Two-way telephone communication service shall be provided for fire department use. This system shall be in accordance with NFPA 72, National Fire Alarm and Signaling Code. The communications system shall operate between the emergency command center and every elevator car, every elevator lobby, and each floor level of exit stairs.
The requirement of 11.8.4.2.1 shall not apply where the fire department radio system is approved as an equivalent system.
Emergency lighting in accordance with Section 7.9 shall be provided.
Emergency power requirements for electric fire pumps shall be in accordance with NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection.
Emergency power for detection, alarm, and communications systems shall be in accordance with NFPA 72, National Fire Alarm and Signaling Code.
Requirements for standby power shall be as specified in 11.8.5.4.1 through 11.8.5.4.4.
Type 60, Class 1, Level 1, standby power in accordance with NFPA 110, Standard for Emergency and Standby Power Systems, shall be provided.
The standby power system shall have a capacity and rating sufficient to supply all required equipment.
Selective load pickup and load shedding shall be permitted in accordance with NFPA 70, National Electrical Code.
The standby power system shall be connected to the following:
  1. Jockey pump, except as otherwise provided in 40.4.2 for special-purpose industrial occupancies
  2. Air compressor serving dry-pipe and pre-action systems, except as otherwise provided in 40.4.2 for special-purpose industrial occupancies
  3. Emergency command center equipment and lighting
  4. Not less than one elevator serving all floors, with standby power transferable to any elevator
  5. Mechanical equipment for smokeproof enclosures
  6. Mechanical equipment required to conform with the requirements of Section 9.3
  7. Stairway video monitoring equipment as required by 11.8.8
An emergency command center shall be provided in a location approved by the fire department.
The emergency command center shall contain the following:
  1. Voice fire alarm system panels and controls
  2. Fire department two-way telephone communication service panels and controls where required by another section of this Code
  3. Fire detection and fire alarm system annunciation panels
  4. Elevator floor location and operation annunciators
  5. Elevator fire recall switch in accordance with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators
  6. Elevator emergency power selector switch (es) where provided in accordance with ASME A17.1 /CSA B44
  7. Sprinkler valve and waterflow annunciators
  8. Emergency generator status indicators
  9. Controls for any automatic stairway door unlocking system
  10. Fire pump status indicators
  11. Telephone for fire department use with controlled access to the public telephone system
  12. Stairway video monitoring equipment as required by 11.8.8
Emergency action plans shall be provided in accordance with 4.8.2.
For high-rise buildings having an occupant load of 4,000 or more persons, real-time remote monitoring of exit stair usage shall be provided in accordance with 11.8.8.2 through 11.8.8.4 and shall be displayed at the emergency command center.
Where the monitoring system is integrated with a security system, the security system shall be in accordance with NFPA 731, Standard for the Installation of Electronic Premises Security Systems.
Where the monitoring system includes video cameras also used for video image smoke detection, the portions of the system used for such detection shall be in accordance with NFPA 72, National Fire Alarm and Signaling Code.
Approved video monitoring equipment shall be provided at the exit stairs immediately adjacent to exit stairway discharge doors to capture discharge from, entry to, and passage through the discharge floor landing.
Approved video monitoring equipment shall be provided for exit stairs above the level of exit discharge, at building height intervals not exceeding 5 stories, so that descent and ascent flows on the stairways, at the floor entry landings, can be remotely monitored.
Approved video monitoring equipment shall be provided, at locations stipulated by the authority having jurisdiction, for exit stairs below the level of exit discharge where levels are normally occupied by the public.
The provisions of Section 11.1 shall apply.
Membrane roofs shall be used in accordance with the following:
  1. Membrane materials shall not be used where fire resistance ratings are required for walls or roofs.
  2. Where every part of the roof, including the roof membrane, is not less than 20 ft (6100 mm) above any floor, balcony, or gallery, a noncombustible or limited-combustible membrane shall be permitted to be used as the roof in any construction type.
  3. With approval of the authority having jurisdiction, membrane materials shall be permitted to be used where every part of the roof membrane is sufficiently above every significant fire potential, such that the imposed temperature cannot exceed the capability of the membrane, including seams, to maintain its structural integrity.
Testing of membrane materials for compliance with the requirements of Section 11.9 for use of the categories of noncombustible and limited-combustible materials shall be performed on weathered-membrane material, as defined in 3.3.171.5.
The flame spread index of all membrane materials exposed within the structure shall be Class A in accordance with Section 10.2.
Roof membranes shall have a roof covering classification, as required by the applicable building codes, when tested in accordance with ASTM E 108, Standard Test Methods for Fire Tests of Roof Coverings, or ANSI/UL 790, Test Methods for Fire Tests of Roof Coverings.
All membrane structure fabric shall meet the flame propagation performance criteria contained in Test Method 2 of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films.
One of the following shall serve as evidence that the fabric materials have the required flame propagation performance:
  1. The authority having jurisdiction shall require a certificate or other evidence of acceptance by an organization acceptable to the authority having jurisdiction.
  2. The authority having jurisdiction shall require a report of tests made by other inspection authorities or organizations acceptable to the authority having jurisdiction.
Where required by the authority having jurisdiction, confirmatory field tests shall be conducted using test specimens from the original material, which shall have been affixed at the time of manufacture to the exterior of the structure.
The design, materials, and construction of the building shall be based on plans and specifications prepared by a licensed architect or engineer knowledgeable in tensioned-membrane construction.
Material loads and strength shall be based on physical properties of the materials verified and certified by an approved testing laboratory.
The membrane roof for structures in climates subject to freezing temperatures and ice buildup shall be composed of two layers separated by an air space through which heated air can be moved to guard against ice accumulation. As an alternative to the two layers, other approved methods that protect against ice accumulation shall be permitted.
Roof drains shall be equipped with electrical elements to protect against ice buildup that can prevent the drains from functioning. Such heating elements shall be served by on-site standby electrical power in addition to the normal public service. As an alternative to such electrical elements, other approved methods that protect against ice accumulation shall be permitted.
In addition to the general provisions of 11.9.1, the requirements of 11.9.3 shall apply to air-supported and air-inflated structures.
The pressurization system shall consist of one or more operating blower units. The system shall include automatic control of auxiliary blower units to maintain the required operating pressure. Such equipment shall meet the following requirements:
  1. Blowers shall be powered by continuous-rated motors at the maximum power required.
  2. Blowers shall have personnel protection, such as inlet screens and belt guards.
  3. Blower systems shall be weather protected.
  4. Blower systems shall be equipped with backdraft check dampers.
  5. Not less than two blower units shall be provided, each of which has capacity to maintain full inflation pressure with normal leakage.
  6. Blowers shall be designed to be incapable of overpressurization.
  7. The auxiliary blower unit(s) shall operate automatically if there is any loss of internal pressure or if an operating blower unit becomes inoperative.
  8. The design inflation pressure and the capacity of each blower system shall be certified by a professional engineer.
A fully automatic standby power system shall be provided. The system shall be either an auxiliary engine generator set capable of running the blower system or a supplementary blower unit that is sized for 1 times the normal operating capacity and is powered by an internal combustion engine.
The standby power system shall be fully automatic to ensure continuous inflation in the event of any failure of the primary power. The system shall be capable of operating continuously for a minimum of 4 hours.
The sizing and capacity of the standby power system shall be certified by a professional engineer.
Instructions in both operation and maintenance shall be transmitted to the owner by the manufacturer of the tensioned-membrane, air-supported, or air-inflated structure.
Annual inspection and required maintenance of each structure shall be performed to ensure safety conditions. At least biennially, the inspection shall be performed by a professional engineer, registered architect, or individual certified by the manufacturer.
Only labeled heating devices shall be used.
Fuel-fired heaters and their installation shall be approved by the authority having jurisdiction.
Containers for liquefied petroleum gases shall be installed not less than 60 in. (1525 mm) from any temporary membrane structure and shall be in accordance with the provisions of NFPA 58, Liquefied Petroleum Gas Code.
Tanks shall be secured in the upright position and protected from vehicular traffic.
Only labeled heaters shall be permitted.
Electric heaters, their placement, and their installation shall be approved by the authority having jurisdiction.
Heaters shall be connected to electricity by electric cable that is suitable for outside use and is of sufficient size to handle the electrical load.
The provisions of Section 11.1 shall apply.
Membrane structures designed to meet all the requirements of Section 11.10 shall be permitted to be used as temporary buildings subject to the approval of the authority having jurisdiction.
Temporary tensioned-membrane structures shall be permitted to comply with Section 11.11 instead of Section 11.10.
Roof membranes shall have a roof covering classification, as required by the applicable building codes, when tested in accordance with ASTM E 108, Standard Test Methods for Fire Tests of Roof Coverings, or ANSI/UL 790, Test Methods for Fire Tests of Roof Coverings.
All membrane structure fabric shall meet the flame propagation performance criteria contained in Test Method 2 of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films.
One of the following shall serve as evidence that the fabric materials have the required flame propagation performance:
  1. The authority having jurisdiction shall require a certificate or other evidence of acceptance by an organization acceptable to the authority having jurisdiction.
  2. The authority having jurisdiction shall require a report of tests made by other inspection authorities or organizations acceptable to the authority having jurisdiction.
Where required by the authority having jurisdiction, confirmatory field tests shall be conducted using test specimens from the original material, which shall have been affixed at the time of manufacture to the exterior of the structure.
The finished ground level enclosed by any temporary membrane structure, and the finished ground level for a reasonable distance but for not less than 10 ft (3050 mm) outside of such a structure, shall be cleared of all flammable or combustible material or vegetation that is not used for necessary support equipment. The clearing work shall be accomplished to the satisfaction of the authority having jurisdiction prior to the erection of such a structure. The premises shall be kept free from such flammable or combustible materials during the period for which the premises are used by the public.
Where prohibited by the authority having jurisdiction, smoking shall not be permitted in any temporary membrane structure.
Portable fire-extinguishing equipment of approved types shall be furnished and maintained in temporary membrane structures in such quantity and in such locations as directed by the authority having jurisdiction.
The design, materials, and construction of the building shall be based on plans and specifications prepared by a licensed architect or engineer knowledgeable in tensioned-membrane construction.
Material loads and strength shall be based on physical properties of the materials verified and certified by an approved testing laboratory.
The membrane roof for structures in climates subject to freezing temperatures and ice buildup shall be composed of two layers separated by an air space through which heated air can be moved to guard against ice accumulation. As an alternative to the two layers, other approved methods that protect against ice accumulation shall be permitted.
Roof drains shall be equipped with electrical elements to protect against ice buildup that can prevent the drains from functioning. Such heating elements shall be served by on-site standby electrical power in addition to the normal public service. As an alternative to such electrical elements, other approved methods that protect against ice accumulation shall be permitted.
In addition to the general provisions of 11.10.1, the requirements of 11.10.5 shall apply to air-supported and air-inflated structures.
The pressurization system shall consist of one or more operating blower units. The system shall include automatic control of auxiliary blower units to maintain the required operating pressure. Such equipment shall meet the following requirements:
  1. Blowers shall be powered by continuous-rated motors at the maximum power required.
  2. Blowers shall have personnel protection, such as inlet screens and belt guards.
  3. Blower systems shall be weather protected.
  4. Blower systems shall be equipped with backdraft check dampers.
  5. Not less than two blower units shall be provided, each of which has capacity to maintain full inflation pressure with normal leakage.
  6. Blowers shall be designed to be incapable of overpressurization.
  7. The auxiliary blower unit(s) shall operate automatically if there is any loss of internal pressure or if an operating blower unit becomes inoperative.
  8. The design inflation pressure and the capacity of each blower system shall be certified by a professional engineer.
A fully automatic standby power system shall be provided. The system shall be either an auxiliary engine generator set capable of running the blower system or a supplementary blower unit that is sized for 1 times the normal operating capacity and is powered by an internal combustion engine.
The standby power system shall be fully automatic to ensure continuous inflation in the event of any failure of the primary power. The system shall be capable of operating continuously for a minimum of 4 hours.
The sizing and capacity of the standby power system shall be certified by a professional engineer.
Instructions in both operation and maintenance shall be transmitted to the owner by the manufacturer of the tensioned-membrane, air-supported, or air-inflated structure.
Annual inspection and required maintenance of each structure shall be performed to ensure safety conditions. At least biennially, the inspection shall be performed by a professional engineer, registered architect, or individual certified by the manufacturer.
Only labeled heating devices shall be used.
Fuel-fired heaters and their installation shall be approved by the authority having jurisdiction.
Containers for liquefied petroleum gases shall be installed not less than 60 in. (1525 mm) from any temporary membrane structure and shall be in accordance with the provisions of NFPA 58, Liquefied Petroleum Gas Code.
Tanks shall be secured in the upright position and protected from vehicular traffic.
Only labeled heaters shall be permitted.
Heaters used inside a temporary membrane structure shall be approved.
Heaters shall be connected to electricity by electric cable that is suitable for outside use and is of sufficient size to handle the electrical load.
The provisions of Section 11.1 shall apply.
Tents shall be permitted only on a temporary basis.
Tents shall be erected to cover not more than 75 percent of the premises, unless otherwise approved by the authority having jurisdiction.
All tent fabric shall meet the flame propagation performance criteria contained in Test Method 2 of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films.
One of the following shall serve as evidence that the tent fabric materials have the required flame propagation performance:
  1. The authority having jurisdiction shall require a certificate or other evidence of acceptance by an organization acceptable to the authority having jurisdiction.
  2. The authority having jurisdiction shall require a report of tests made by other inspection authorities or organizations acceptable to the authority having jurisdiction.
Where required by the authority having jurisdiction, confirmatory field tests shall be conducted using test specimens from the original material, which shall have been affixed at the time of manufacture to the exterior of the tent.
There shall be a minimum of 10 ft (3050 mm) between stake lines.
Adjacent tents shall be spaced to provide an area to be used as a means of emergency egress. Where 10 ft (3050 mm) between stake lines does not meet the requirements for means of egress, the distance necessary for means of egress shall govern.
Tents not occupied by the public and not used for the storage of combustible material shall be permitted to be erected less than 10 ft (3050 mm) from other structures where the authority having jurisdiction deems such close spacing to be safe from hazard to the public.
Tents, each not exceeding 1200 ft2 (112 m2) in finished ground level area and located in fairgrounds or similar open spaces, shall not be required to be separated from each other, provided that safety precautions meet the approval of the authority having jurisdiction.
The placement of tents relative to other structures shall be at the discretion of the authority having jurisdiction, with consideration given to occupancy, use, opening, exposure, and other similar factors.
The finished ground level enclosed by any tent, and the finished ground level for a reasonable distance, but for not less than 10 ft (3050 mm) outside of such a tent, shall be cleared of all flammable or combustible material or vegetation that is not used for necessary support equipment. The clearing work shall be accomplished to the satisfaction of the authority having jurisdiction prior to the erection of such a tent. The premises shall be kept free from such flammable or combustible materials during the period for which the premises are used by the public.
Smoking shall not be permitted in any tent, unless approved by the authority having jurisdiction.
In rooms or areas where smoking is prohibited, plainly visible signs shall be posted that read as follows:

NO SMOKING

Portable fire-extinguishing equipment of approved types shall be furnished and maintained in tents in such quantity and in such locations as directed by the authority having jurisdiction.
Only labeled heating devices shall be used.
Fuel-fired heaters and their installation shall be approved by the authority having jurisdiction.
Containers for liquefied petroleum gases shall be installed not less than 60 in. (1525 mm) from any tent and shall be in accordance with the provisions of NFPA 58, Liquefied Petroleum Gas Code.
Tanks shall be secured in the upright position and protected from vehicular traffic.
Only labeled heaters shall be permitted.
Heaters used inside a tent shall be approved.
Heaters shall be connected to electricity by electric cable that is suitable for outside use and is of sufficient size to handle the electrical load.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING