ADOPTS WITH AMENDMENTS:

NFPA 1, 2015

Heads up: There are no amended sections in this chapter.
This chapter shall apply to new, existing, permanent, or temporary buildings.
Where required by this Code, a type of building construction shall comply with NFPA 220, Standard on Types of Building Construction.
Fire safety construction features for new and existing occupancies shall comply with this Code and the referenced edition of NFPA 101.

12.3.1

ILLUSTRATION
The design and construction of fire walls and fire barrier walls that are required to separate buildings or subdivide a building to prevent the spread of fire shall comply with Section 12.3 and NFPA 221, Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier Walls.
In new buildings three stories or greater in height, a quality assurance program for the installation of devices and systems installed to protect penetration and joints shall be prepared and monitored by the RDP responsible for design. Inspections of firestop systems and fire-resistive joint systems shall be in accordance with 12.3.2.1 and 12.3.2.2.
Inspection of firestop systems of the types tested in accordance with ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire Stops, or /UL 1479, Standard for Fire Tests of Through-Penetration Firestops, shall be conducted in accordance with ASTM E 2174, Standard Practice for On-Site Inspection of Installed Fire Stops. [5000:40.9.1]
Inspection of fire-resistive joint systems of the types tested in accordance with ASTM E 1966, Standard Test Method for Fire-Resistive Joint Systems, or UL 2079, Standard for Tests for Fire Resistance of Buildings Joint Systems, shall be conducted in accordance with ASTM E 2393, Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers. [5000:40.9.2]
Required fire-resistive construction, including fire barriers, fire walls, exterior walls due to location on property, fire-resistive requirements based on type of construction, draft-stop partitions, and roof coverings, shall be maintained and shall be properly repaired, restored, or replaced where damaged, altered, breached, penetrated, removed, or improperly installed.
Where required, fire-rated gypsum wallboard walls or ceilings that are damaged to the extent that through openings exist, the damaged gypsum wallboard shall be replaced or returned to the required level of fire resistance using a listed repair system or using materials and methods equivalent to the original construction.
Where readily accessible, required fire-resistance-rated assemblies in high-rise buildings shall be visually inspected for integrity at least once every 5 years.
The person responsible for conducting the visual inspection shall demonstrate appropriate technical knowledge and experience in fire-resistance-rated design and construction acceptable to the AHJ.
A written report prepared by the person responsible for conducting the visual inspection shall be submitted to the AHJ documenting the results of the visual inspection.
The installation and maintenance of assemblies and devices used to protect openings in walls, floors, and ceilings against the spread of fire and smoke within, into, or out of buildings shall comply with Section 12.4 and NFPA 80, Standard for Fire Doors and Other Opening Protectives. [80:1.1]
With the exception of fabric fire safety curtain assemblies, Section 12.4 addresses assemblies that have been subjected to standardized fire tests. (See Chapter 20 of NFPA 80, Standard for Fire Doors and Other Opening Protectives.) [80:1.1.1]
Incinerator doors, record room doors, and vault doors are not covered in Section 12.4. [80:1.1.2]
Requirements for horizontally sliding, vertically sliding, and swinging doors as used in this Code do not apply to hoistway doors for elevators and dumbwaiters. [80:1.1.3]
Section 12.4 shall not cover fire resistance rated glazing materials and horizontally sliding accordion or folding assemblies fabricated for use as walls and tested as wall assemblies in accordance with ASTM E 119. [80:1.1.4]
Subsection 12.4.6 shall cover the inspection, testing, and maintenance of fire doors, fire shutters, fire windows, and opening protectives other than fire dampers and fabric fire safety curtains. [80:5.1.1.1]
Doors, shutters, and windows shall be operable at all times. [80:5.1.2.1]
Doors, shutters, and windows shall be kept closed and latched or arranged for automatic closing. [80:5.1.2.2]
Where it is necessary to replace fire doors, shutters, windows or their frames, glazing materials, hardware, and closing mechanisms, replacements shall meet the requirements for fire protection and shall be installed and tested as required by this section for new installations. [80:5.1.3]
In cases where a field modification to afire door or a fire door assembly is desired and is not permitted by 4.1.3.2 through 4.1.3.4 of NFPA 80, the laboratory with which the product or component being modified is listed shall be contacted through the manufacturer and a written or graphic description of the modifications shall be presented to that laboratory. [80:5.1.4.1]
Field modifications shall be permitted without a field visit from the laboratory upon written authorization from that laboratory. [80:5.1.4.2]
When the manufacturer is no longer available, the laboratory shall be permitted to provide an engineering evaluation supporting the field modification. [80:5.1.4.3]
Where a fire door or fire window opening no longer functions as an opening, or the door or window is removed and not replaced, the opening shall be filled to maintain the required rating of the wall assembly. [80:5.1.5]
Upon completion of the installation, door, shutters, and window assemblies shall be inspected and tested in accordance with 5.2.4 of NFPA 80. [80:5.2.1]
A record of all inspections and testing shall be signed by the inspector and kept for inspection by the AHJ. [80:5.2.2]
Records of acceptance tests shall be retained for the life of the assembly. [80:5.2.2.1]
Unless a longer period is required by Section 5.4 of NFPA 80, records shall be retained for a period of at least 3 years. [80:5.2.2.2]
The records shall be on a medium that will survive the retention period. Paper or electronic media shall be permitted. [72:14.6.2.3]
A record of all inspections and testing shall be provided that includes, but is not limited to, the following information:
  1. Date of inspection
  2. Name of facility
  3. Address of facility
  4. Name of person(s) performing inspections and testing
  5. Company name and address of inspecting company
  6. Signature of inspector of record
  7. Individual record of each inspected and tested fire door assembly
  8. *Opening identifier and location of each inspected and tested fire door assembly
  9. *Type and description of each inspected and tested fire door assembly
  10. *Verification of visual inspection and functional operation
  11. Listing of deficiencies in accordance with 12.4.6.6.3, 12.4.6.7, and 12.4.6.8 [80:5.2.2.4]
Upon completion of maintenance work, fire door assemblies shall be inspected and tested in accordance with 5.2.3 of NFPA 80. [80:5.2.2.5]
Acceptance testing of fire door and window assemblies shall be performed by a qualified person with knowledge and understanding of the operating components of the type of assembly being subject to testing. [80:5.2.3.1]
Before testing, a visual inspection shall be performed to identify any damaged or missing parts that can create a hazard during testing or affect operation or resetting. [80:5.2.3.2]
Acceptance testing shall include the closing of the door by all means of activation. [80:5.2.3.3]
A record of these inspections and testing shall be made in accordance with 5.2.2 of NFPA 80. [80:5.2.3.4]
Fire door assemblies shall be visually inspected from both sides to assess the overall condition of door assembly. [80:5.2.3.5.1]
As a minimum, the following items shall be verified:
  1. Labels are clearly visible and legible.
  2. No open holes or breaks exist in surfaces of either the door or frame.
  3. Glazing, vision light frames, and glazing beads are intact and securely fastened in place, if so equipped.
  4. The door, frame, hinges, hardware, and noncombustible threshold are secured, aligned, and in working order with no visible signs of damage.
  5. No parts are missing or broken.
  6. Door clearances do not exceed clearances listed in 4.8.4 and 6.3.1.7 of NFPA 80.
  7. The self-closing device is operational; that is, the active door completely closes when operated from the full open position.
  8. If a coordinator is installed, the inactive leaf closes before the active leaf.
  9. Latching hardware operates and secures the door when it is in the closed position.
  10. Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame.
  11. No field modifications to the door assembly have been performed that void the label.
  12. Meeting edge protection, gasketing and edge seals, where required, are inspected to verify their presence and integrity.
  13. Signage affixed to a door meets the requirements listed in 4.1.4 of NFPA 80. [80:5.2.3.5.2]
Fire door assemblies shall be visually inspected from both sides to assess the overall condition of door assembly. [80:5.2.3.6.1]
The following items shall be verified:
  1. Labels are clearly visible and legible.
  2. No open holes or breaks exist in surfaces of either the door or frame.
  3. Slats, endlocks, bottom bar, guide assembly, curtain entry hood, and flame baffle are correctly installed and intact for rolling steel fire doors.
  4. Glazing, vision light frames, and glazing beads are intact and securely fastened in place, if so equipped.
  5. Curtain, barrel, and guides are aligned, level, plumb, and true for rolling steel fire doors.
  6. Expansion clearance is maintained in accordance with manufacturer's listing.
  7. Drop release arms and weights are not blocked or wedged.
  8. Mounting and assembly bolts are intact and secured.
  9. Attachment to jambs are with bolts, expansion anchors, or as otherwise required by the listing.
  10. Smoke detectors, if equipped, are installed and operational.
  11. No parts are missing or broken.
  12. *Fusible links, if equipped, are in the location; chain/cable, s-hooks, eyes, and so forth, are in good condition; the cable or chain are not kinked, pinched, twisted, or inflexible; and links are not painted or coated with dust or grease.
  13. Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame.
  14. No field modifications to the door assembly have been performed that void the label.
  15. Doors have an average closing speed of not less than 6 in./sec (152 mm/sec) or more than 24 in./sec (610 mm/sec). [80:5.2.3.6.2]
All fire doors, fire shutters, and fire window assemblies shall be inspected and tested to check for proper operation and full closure. [80:5.2.3.7.1]
Resetting of the automatic-closing device shall be done in accordance with the manufacturer's instructions. [80:5.2.3.7.2]
Rolling steel fire doors shall be drop-tested twice. [80:5.2.3.7.3.1]
The first test shall be to check for proper operation and full closure. [80:5.2.3.7.3.2]
A second test shall be done to verify that the automatic-closing device has been reset correctly. [80:5.2.3.7.3.3]
Fusible links, release devices, and any other movable parts shall not be painted or coated with other materials that could interfere with the operation of the assembly. [80:5.2.3.8]
Periodic inspections and testing shall be performed not less than annually. [80:5.2.4.1]
As a minimum, the provisions of 12.4.6.6.3 shall be included in the periodic inspection and testing procedure. [80:5.2.4.2]
Inspection shall include an operational test for automatic-closing doors and windows to verify that the assembly will close under fire conditions. [80:5.2.4.3]
The assembly shall be reset after a successful test. [80:5.2.4.4]
Resetting of the release mechanism shall be done in accordance with the manufacturer's instructions. [80:5.2.4.5]
Hardware shall be examined, and inoperative hardware, parts, or other defective items shall be replaced without delay. [80:5.2.4.6]
Tin-clad and kalamein doors shall be inspected for dry rot of the wood core. [80:5.2.4.7]
Chains or cables employed shall be inspected for excessive wear, stretching, and binding. [80:5.2.4.8]
The operator, governor, and automatic-closing device on rolling steel fire doors shall be permitted to be retrofitted with a labeled retrofit operator under the conditions specified in 12.4.6.7.2 through 12.4.6.7.5. [80:5.3.1]
The retrofit operator shall be labeled as such. [80:5.3.2]
The retrofit operator shall be installed in accordance with its installation instructions and listing. [80:5.3.3]
The installation shall be acceptable to the AHJ. [80:5.3.4]
The retrofit operator shall be permitted to be provided by a manufacturer other than the original manufacturer of the rolling steel fire door on which it is retrofitted, provided its listing allows it to be retrofitted on that manufacturer's doors. [80:5.3.5]
As an alternate means of compliance with 12.4.6.6.4, subject to the AHJ, fire door assemblies shall be permitted to be inspected, tested, and maintained under a written performance-based program. [80:5.4.1]
Goals established under a performance-based program shall provide assurance that the fire door assembly will perform its intended function when exposed to fire conditions. [80:5.4.2]
Technical justification for inspection, testing, and maintenance intervals shall be documented in writing. [80:5.4.3]
The performance-based option shall include historical data acceptable to the AHJ. [80:5.4.4]
Repairs shall be made, and defects that could interfere with operation shall be corrected without delay. [80:5.5.1]
Damaged glazing material shall be replaced with labeled glazing. [80:5.5.2.]
Replacement glazing materials shall be installed in accordance with their individual listing. [80:5.5.3]
Any breaks in the face covering of doors shall be repaired without delay. [80:5.5.4]
Where a fire door, frame, or any part of its appurtenances is damaged to the extent that it could impair the door's proper emergency function, the following actions shall be performed:
  1. The fire door, frame, door assembly, or any part of its appurtenances shall be repaired with labeled parts or parts obtained from the original manufacturer.
  2. The door shall be tested to ensure emergency operation and closing upon completion of the repairs. [80:5.5.5]
If repairs cannot be made with labeled components or parts obtained from the original manufacturer or retrofitted in accordance with 12.4.6.7, the fire door frame, fire door assembly, or appurtenances shall be replaced. [80:5.5.6]
When holes are left in a door or frame due to changes or removal of hardware or plant-ons, the holes shall be repaired by the following methods:
  1. Install steel fasteners that completely fill the holes
  2. Fill the screw or bolt holes with the same material as the door or frame [80:5.5.7]
Interior finish in buildings and structures shall meet the requirements of NFPA 101 and this Code.
Classification of interior finish materials shall be in accordance with tests made under conditions simulating actual installations, provided that the AHJ is permitted to establish the classification of any material on which classification by a standard test is not available, unless otherwise provided in 12.5.2.2 or 12.5.2.4. [101: 10.2.1.1]
The provisions of 12.5.2.1 shall not apply to materials having a total thickness of less than 1/28 in. (0.9 mm) that are applied directly to the surface of walls and ceilings where both of the following conditions are met:
  1. The wall or ceiling surface is a noncombustible or limited combustible material.
  2. The materials applied meet the requirements of Class A interior wall or ceiling finish when tested in accordance with 12.5.4 using fiber cement board as the substrate material. [101: 10.2.1.2]
If a material having a total thickness of less than 1/28 in. (0.9 mm) is applied to a surface that is not noncombustible or not limited-combustible, the provisions of 12.5.2.1 shall apply. [101: 10.2.1.3]
Approved existing installations of materials applied directly to the surface of walls and ceilings in a total thickness of less than 1/28 in. (0.9 mm) shall be permitted to remain in use, and the provisions of 12.5.3 through 12.5.4.7.2 shall not apply. [101: 10.2.1.4]
Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied structurally or for decoration, acoustical correction, surface insulation, or other purposes shall be considered interior finish and shall not be considered decorations or furnishings. [101: 10.2.1.5]
Lockers constructed of combustible materials shall be considered interior finish. [101: 10.2.1.6]
Requirements for interior wall and ceiling finish shall apply as follows:
  1. Where specified elsewhere in this Code for specific occupancies in Chapter 20 and NFPA 101 (see Chapter 7 and Chapter 11 through Chapter 43 of NFPA 101)
  2. As specified in 12.5.4 through 12.5.7. [101: 10.2.2.1]
Interior floor finish shall comply with 12.5.8 under any of the following conditions:
  1. Where floor finish requirements are specified elsewhere in the Code
  2. Where the fire performance of the floor finish cannot be demonstrated to be equivalent to floor finishes with a critical radiant flux of at least 0.1 W/cm2 [101: 10.2.2.2]
Interior wall or ceiling finish that is required elsewhere in this Code to be Class A, Class B, or Class C shall be classified based on test results from ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test of Surface Burning Characteristics of Building Materials, except as indicated in 12.5.4.1 or 12.5.4.2. [101: 10.2.3]
Exposed portions of structural members complying with the requirements for Type IV (2HH) construction in accordance with NFPA 220, Standard on Types of Building Construction, or with the building code shall be exempt from testing and classification in accordance with ASTM E 84, or ANSI/UL 723. [101: 10.2.3.1]
Interior wall and ceiling finish tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and meeting the conditions of 12.5.4.7.2 shall be permitted to be used where interior wall and ceiling finish is required to be Class A in accordance with ASTM E 84 or ANSI/UL 723. [101: 10.2.3.2]
For fire-retardant coatings, see 12.5.7. [101: 10.2.3.3]
Products required to be tested in accordance with ASTM E 84 or ANSI/UL 723 shall be grouped in the classes described in 12.5.4.4.1 through 12.5.4.4.3 accordance with their flame spread and smoke development, except as indicated in 12.5.4.4.4. [101: 10.2.3.4]
Class A interior wall and ceiling finishes shall be those finishes with a flame spread index of 0-25 and a smoke developed index of 0-450 and shall include any material classified at 25 or less on the flame spread index test scale and 450 or less on the smoke developed index test scale. [101: 10.2.3.4.1]
Class B interior wall and ceiling finishes shall be those finishes with a flame spread index of 26-75 and a smoke developed index of 0-450 and shall include any material classified at more than 25 but not more than 75 on the flame spread index test scale and 450 or less on the smoke developed index test scale. [101: 10.2.3.4.2]
Class C interior wall and ceiling finishes shall be those finishes with a flame of 76-200 and a smoke developed index of 0-450 and shall include any material classified at more than 75 but not more than 200 on the flame spread index test scale and 450 or less on the smoke developed index test scale. [101: 10.2.3.4.3]
Existing interior finish shall be exempt from the smoke developed index criteria of 12.5.4.4.1 through 12.5.4.4.3. [101: 10.2.3.4.4]
The classification of interior finish specified in 12.5.4.4 shall be that of the basic material used by itself or in combination with other materials. [101: 10.2.3.5]
Wherever the use of Class C interior wall and ceiling finish is required, Class A or Class B shall be permitted. Where Class B interior wall and ceiling finish is required, Class A shall be permitted. [101: 10.2.3.6]
Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, shall comply with the criteria of 12.5.4.7.1. Products tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, shall comply with the criteria of 12.5.4.7.2. [101: 10.2.3.7]
The interior finish shall comply with all of the following when tested using method B of die test protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls:
  1. During the 40 kW exposure, flames shall not spread to the ceiling.
  2. The flame shall not spread to the outer extremities of the samples on the 8 ft × 12 ft (2440 mm × 3660 mm) walls.
  3. Flashover, as described in NFPA 265, shall not occur.
  4. For new installations, the total smoke released throughout the test shall not exceed 1000 m2. [101: 10.2.3.7.1]
The interior finish shall comply with all of the following when tested using the test protocol of NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth:
  1. During the 40 kW exposure, flames shall not spread to the ceiling.
  2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
  3. Flashover, as described in NFPA 286, shall not occur.
  4. The peak heat release rate throughout the test shall not exceed 800 kW.
  5. For new installations, the total smoke released throughout the test shall not exceed 1000 m2 [101: 10.2.3.7.2]
The use of textile materials on walls or ceilings shall comply with one of the following conditions:
  1. Textile materials meeting the requirements of Class A when tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E 2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics (see 12.5.4.4), shall be permitted on the walls or ceilings of rooms or areas protected by an approved automatic sprinkler system.
  2. Textile materials meeting the requirements of Class A when tested in accordance with ASTM E 84 or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E 2404 (see 12.5.4.4 ), shall be permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less.
  3. Textile materials meeting the requirements of Class A when tested in accordance with ASTM E 84 or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E 2404 (see 12.5.4.4), shall be permitted to extend not more than 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions.
  4. Previously approved existing installations of textile material meeting the requirements of Class A when tested in accordance with ASTM E 84 or ANSI/UL 723 (see 12.5.4.4) shall be permitted to be continued to be used.
  5. Textile materials shall be permitted on walls and partitions where tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth. Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls. (See 12.5.4.7.)
  6. Textile materials shall be permitted on walls, partitions, and ceilings where tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth (See 12.5.4.7.) [101: 10.2.4.1]
The use of expanded vinyl wall or expanded vinyl ceiling materials shall comply with one of the following conditions:
  1. Materials meeting the requirements of Class A when tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E 2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper, or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics (see 12.5.4.4), shall be permitted on the walls or ceilings of rooms or areas protected by an approved automatic sprinkler system.
  2. Materials meeting the requirements of Class A when tested in accordance with ASTM E 84 or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E 2404 (see 12.5.4.4), shall be permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less.
  3. Materials meeting the requirements of Class A when tested in accordance with ASTM E 84 or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E 2404 (see 12.5.4.4), shall be permitted to extend not more than 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions.
  4. Previously approved existing installations of materials meeting the requirements for the occupancy involved, when tested in accordance with ASTM E 84 or ANSI/UL 723 (see 12.5.4.4), shall be permitted to be continued to be used.
  5. Materials shall be permitted on walls and partitions where tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls. (See 12.5.4.7.)
  6. Materials shall be permitted on walls, partitions, and ceilings where tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth. (See 12.5.4.7.) [101: 10.2.4.2]
Cellular or foamed plastic materials shall not be used as interior wall and ceiling finish unless specifically permitted by 12.5.5.3.1 or 12.5.5.3.2. The requirements of 12.5.5.3 through 12.5.5.3.2 shall apply both to exposed foamed plastics and to foamed plastics used in conjunction with a textile or vinyl facing or cover. [101: 10.2.4.3]
Cellular or foamed plastic materials shall be permitted where subjected to large-scale fire tests that substantiate their combustibility and smoke release characteristics for the use intended under actual fire conditions. [101: 10.2.4.3.1]
One of the following fire tests shall be used for assessing the combustibility of cellular or foamed plastic materials as interior finish:
  1. NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criteria of 12.5.4.7.2.
  2. ANSI/UL 1715, Standard for Fire Test of Interior Finish Material (including smoke measurements, with total smoke release not to exceed 1000 m2)
  3. ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction
  4. ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Panels, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems [101: 10.2.4.3.1.1]
The tests shall be performed on a finished foamed plastic assembly related to the actual end-use configuration, including any cover or facing, and at the maximum thickness intended for use. [101: 10.2.4.3.1.2]
New installations of cellular or foamed plastic materials tested in accordance with ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction, or ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Panels, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems, shall also be tested for smoke release using NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criterion of 12.5.4.7.2. [101: 10.2.4.3.1.3]
Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent of the specific wall or ceiling area to which it is applied, provided that it is not less than 20 lb/ft3 (320 kg/m3) in density, is limited to 1/2 in. (13 mm) in thickness and 4 in. (100 mm) in width, and complies with the requirements for Class A or Class B interior wall and ceiling finish as described in 12.5.4.4; however, the smoke developed index shall not be limited. [101: 10.2.4.3.2]
Light-transmitting plastics shall be permitted to be used as interior wall and ceiling finish if approved by the AHJ. [101: 10.2.4.4]
Decorations and furnishings that do not meet the definition of interior finish, as defined in 3.3.112.2, shall be regulated by the provisions of Section 12.6. [101: 10.2.4.5]
Listed factory finished metal ceiling and wall panels meeting the requirements of Class A when tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials (see 12.5.4.4), shall be permitted to be finished with one additional application of paint. Such painted panels shall be permitted for use in areas where Class A interior finishes are required. The total paint thickness shall not exceed 1/28 in. (0.9 mm). [101: 10.2.4.6]
Polypropylene and high-density polyethylene materials shall not be permitted as interior wall or ceiling finish unless the material complies with the requirements of 12.5.4.7.2. The tests shall be performed on a finished assembly and on the maximum thickness intended for use. [101: 10.2.4.7]
For new installations, site-fabricated stretch systems containing all three components described in the definition in Chapter 3 of NFPA 101 shall be tested in the manner intended for use and shall comply with the requirements of 12.5.4 or 12.5.4.2. If the materials are tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with ASTM E 2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics. [101: 10.2.4.8]
Reflective insulation materials shall be tested in the manner intended for use and shall comply with the requirements of 10.2.3 of NFPA 101. If the materials are tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with ASTM E 2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics. [101: 10.2.4.9]
Interior wall and ceiling trim and incidental finish, other than wall base in accordance with 12.5.6.2 and bulletin boards, posters, and paper in accordance with 12.5.6.3, not in excess of 10 percent of the specific wall and ceiling areas of any room or space to which it is applied shall be permitted to be Class C materials in occupancies where interior wall and ceiling finish of Class A or Class B is required. [101: 10.2.5.1]
Interior floor trim material used at the junction of the wall and the floor to provide a functional or decorative border, and not exceeding 6 in. (150 mm) in height, shall meet the requirements for interior wall finish for its location or the requirements for Class II interior floor finish as described in 12.5.8.4 using the test described in 12.5.8.3. If a Class I floor finish is required, the interior floor trim shall be Class I. [101: 10.2.5.2]
Bulletin boards, posters, and paper attached directly to the wall shall not exceed 20 percent of the aggregate wall area to which they are applied. [101: 10.2.5.3.1]
The provision of shall not apply to artwork and teaching materials in sprinklered educational or day-care occupancies in accordance with 20.2.4.4.3 and 20.3.4.2.3.5.3. [101: 10.2.5.3.2]
The required flame spread or smoke development classification of existing surfaces of walls, partitions, columns, and ceilings shall be permitted to be secured by applying approved fire-retardant coatings to surfaces having higher flame spread ratings than permitted. Such treatments shall be tested, or shall be listed and labeled for application to the material to which they are applied, and shall comply with the requirements of NFPA 703, Standard for Fire Retardant-Treated Wood and Fire-Retardant Coatings for Building Materials. [101: 10.2.6.1]
Surfaces of walls, partitions, columns, and ceilings shall be permitted to be finished with factory-applied fire-retardant coated products that have been listed and labeled to demonstrate compliance with the requirements of ASTM E 2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, on the coated surface. [101: 10.2.6.2]
Fire-retardant coatings or factory-applied fire-retardant coated assemblies shall possess the desired degree of permanency and shall be maintained so as to retain the effectiveness of the treatment under the service conditions encountered in actual use. [101: 10.2.6.3]
Carpet and carpet-like interior floor finishes shall comply with ASTM D 2859, Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials. [101: 10.2.7.1]
Floor coverings, other than carpet for which 12.5.3.2 establishes requirements for fire performance, shall have a minimum critical radiant flux of 0.1 W/cm2. [101: 10.2.7.2]
Interior floor finishes shall be classified in accordance with 12.5.8.4, based on test results from NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, or ASTM E 648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source. [101: 10.2.7.3]
Interior floor finishes shall be grouped in the classes specified in 12.5.8.4.1 and 12.5.8.4.2 in accordance with the critical radiant flux requirements. [101: 10.2.7.4]
Class I interior floor finish shall have a critical radiant flux of not less than 0.45 W/cm2, as determined by the test described in 12.5.8.3. [101: 10.2.7.4.1]
Class II interior floor finish shall have a critical radiant flux of not less than 0.22 W/cm2, but less than 0.45 W/cm2, as determined by the test described in 12.5.8.3. [101: 10.2.7.4.2]
Wherever the use of Class II interior floor finish is required, Class I interior floor finish shall be permitted. [101: 10.2.7.5]
Other than as required in 12.5.5, where an approved automatic sprinkler system is installed in accordance with Section 13.3, Class C interior wall and ceiling finish materials shall be permitted in any location where Class B is required, and Class B interior wall and ceiling finish materials shall be permitted in any location where Class A is required. [101: 10.2.8.1]
Where an approved automatic sprinkler system is installed in accordance with Section 13.3, throughout the fire compartment or smoke compartment containing the interior floor finish, Class II interior floor finish shall be permitted in any location where Class I interior floor finish is required, and where Class II is required, the provisions of 12.5.8.2 shall apply. [101: 10.2.8.2]
Furnishings, contents, decorations, and treated finishes in buildings and structures shall meet the requirements of NFPA 101 and this Code.
Where required by the applicable provisions of this Code, draperies, curtains, and other similar loosely hanging furnishings and decorations shall meet the flame propagation performance criteria contained in Test Method 1 or Test Method 2, as appropriate, of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films. [101: 10.3.1]
Newly introduced upholstered furniture, except as otherwise permitted by Chapter 20, shall be resistant to a cigarette ignition (i.e., smoldering) in accordance with one of the following:
  1. The components of the upholstered furniture shall meet the requirements for Class I when tested in accordance with NFPA 260, Standard Methods of Tests and Classification System for Cigarette Ignition Resistance of Components of Upholstered Furniture.
  2. Mocked-up composites of the upholstered furniture shall have a char length not exceeding 11/2 in. (38 mm) when tested in accordance with NFPA 261, Standard Method of Test for Determining Resistance of Mock-Up Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes. [101: 10.3.2.1]
Newly introduced mattresses, except as otherwise permitted by Chapter 20, shall have a char length not exceeding 2 in. (51 mm) when tested in accordance with 16 CFR 1632, "Standard for the Flammability of Mattresses and Mattress Pads" (FF 4-72). [101: 10.3.2.2]
Where required by the applicable provisions of this Code, upholstered furniture, unless the furniture is located in a building protected throughout by an approved automatic sprinkler system, shall have limited rates of heat release when tested in accordance with ASTM E 1537, Standard Test Method for Fire Testing of Upholstered Furniture, as follows:
  1. The peak rate of heat release for the single upholstered furniture item shall not exceed 80 kW.
  2. The total heat released by the single upholstered furniture item during the first 10 minutes of the test shall not exceed 25 MJ. [101: 10.3.3]
Where required by the applicable provisions of this Code, mattresses, unless the mattress is located in a building protected throughout by an approved automatic sprinkler system, shall have limited rates of heat release when tested in accordance with ASTM E 1590, Standard Test Method for Fire Testing of Mattresses, as follows:
  1. The peak rate of heat release for the mattress shall not exceed 100 kW.
  2. The total heat released by the mattress during the first 10 minutes of the test shall not exceed 25 MJ. [101: 10.3.4]
Furnishings or decorations of an explosive or highly flammable character shall not be used. [101: 10.3.5]
Fire-retardant coatings shall be maintained to retain the effectiveness of the treatment under service conditions encountered in actual use. [101: 10.3.6]
Where required by the applicable provisions of this Code, furnishings and contents made with foamed plastic materials that are unprotected from ignition shall have a heat release rate not exceeding 100 kW when tested in accordance with UL 1975, Standard for Fire Tests for Foamed Plastics Used for Decorative Purposes, or when tested in accordance with NFPA 289, Standard Method of Fire Test for Individual Fuel Packages, using the 20 kW ignition source. [101: 10.3.7]
Where lockers constructed of combustible materials other than wood are used, the lockers shall be considered interior finish and shall comply with Section 12.5, except as permitted by 12.6.7.2. [101: 10.3.8.1]
Lockers constructed entirely of wood and of noncombustible materials shall be permitted to be used in any location where interior finish materials are required to meet a Class C classification in accordance with 12.5.4. [101: 10.3.8.2]

12.7 Fire Barriers

ILLUSTRATION
Fire barriers used to provide enclosure, subdivision, or protection under NFPA 101 and this Code shall be classified in accordance with one of the following fire resistance ratings:
  1. 3-hour fire resistance rating
  2. 2-hour fire resistance rating
  3. 1-hour fire resistance rating
  4. *1/2-hour fire resistance rating [101: 8.3.1.1]
The fire-resistive materials, assemblies, and systems used shall be limited to those permitted in this Code and this subsection. [101: 8.3.2.1]
Fire resistance-rated glazing tested in accordance with ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, or ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, shall be permitted. [101: 8.3.2.1.1]
New fire resistance-rated glazing shall bear the identifier "W-XXX" where "XXX" is the fire resistance rating in minutes. Such identification shall be permanently affixed. [101: 8.3.2.1.2]
The construction materials and details for fire-resistive assemblies and systems for walls described shall comply with all other provisions of this Code, except as modified herein. [101: 8.3.2.2]
Interior walls and partitions of nonsymmetrical construction shall be evaluated from both directions and assigned a fire resistance rating based on the shorter duration obtained in accordance with ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials or ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials. When the wall is tested with the least fire-resistive side exposed to the furnace, the wall shall not be required to be subjected to tests from the opposite side. [101: 8.3.2.3]
Openings required to have a fire protection rating by Table 12.7.4.2 shall be protected by approved, listed, labeled fire door assemblies and fire window assemblies and their accompanying hardware, including all frames, closing devices, anchorage, and sills in accordance with the requirements of Section 12.4, except as otherwise specified in this Code. [101: 8.3.3.1]
Fire resistance-rated glazing tested in accordance with ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, or ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, shall be permitted in fire door assemblies and fire window assemblies where tested and installed in accordance with their listings. [101: 8.3.3.1.1]
New fire resistance-rated glazing shall be marked in accordance with Table 12.7.3.12 and Table 12.7.4.2. Such marking shall be permanently affixed. [101: 8.3.3.1.2]
Fire protection ratings for products required to comply with 12.7.3 shall be as determined and reported by a nationally recognized testing agency in accordance with NFPA 252; ANSI/UL 10B, Standard for Fire Tests of Door Assemblies: or ANSI/UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies; NFPA 257; or ANSI/UL 9, Standard for Fire Tests of Window Assemblies. [101: 8.3.3.2]
Fire protection-rated glazing shall be evaluated under positive pressure in accordance with NFPA 257. [101: 8.3.3.2.1]
All products required to comply with 12.7.3.2 shall bear an approved label. [101: 8.3.3.2.2]
Labels on fire door assemblies shall be maintained in a legible condition. [101: 8.3.3.2.3.1]
In existing installations, steel door frames without a label shall be permitted where approved by the AHJ. [101: 8.3.3.2.3.2]
Unless otherwise specified, fire doors shall be self-closing or automatic-closing in accordance with 14.5.4. [101:8.3.3.3]
Floor fire door assemblies shall be tested in accordance with NFPA 288, Standard Methods of Fire Tests of Horizontal Fire Door Assemblies Installed in Horizontal Fire Resistance-Rated Assemblies, and shall achieve a fire resistance rating not less than the assembly being penetrated. Floor fire doors assemblies shall be listed and labeled. [101: 8.3.3.4]
Fire protection-rated glazing shall be permitted in fire barriers having a required fire resistance rating of 1 hour or less and shall be of an approved type with the appropriate fire protection rating for the location in which the barriers are installed. [101: 8.3.3.5]
Glazing in fire window assemblies, other than in existing fire window installations of wired glass and other fire-rated glazing material, shall be of a design that has been tested to meet the conditions of acceptance of NFPA 257; or ANSI/UL 9, Standard for Fire Tests of Window Assemblies. Fire protection-rated glazing in fire door assemblies, other than in existing fire-rated door assemblies, shall be of a design that has been tested to meet the conditions of acceptance of NFPA 252; ANSI/UL 10B, Standard for Fire Tests of Door Assemblies; or ANSI/UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies. [101: 8.3.3.6]
Fire resistance-rated glazing complying with 12.7.2.1.1 shall be permitted in fire doors and fire window assemblies in accordance with their listings. [101: 8.3.3.7]
Glazing materials that have been tested, listed, and labeled to indicate the type of opening to be protected for fire protection purposes shall be permitted to be used in approved opening protectives in accordance with Table 8.3.4.2 of NFPA 101 and in sizes in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives. [101: 8.3.3.8]
Existing installations of wired glass of 1/4 in. (6.3 mm) thickness and labeled for fire protection purposes shall be permitted to be used in approved opening protectives, provided that the maximum size specified by the listing is not exceeded. [101: 8.3.3.9]
Nonsymmetrical fire protection-rated glazing systems shall be tested with each face exposed to the furnace, and the assigned fire protection rating shall be that of the shortest duration obtained from the two tests conducted in compliance with NFPA 257; or ANSI/UL 9, Standard for Fire Tests of Window Assemblies. [101: 8.3.3.10]
The total combined area of glazing in fire-rated window assemblies and fire-rated door assemblies used in fire barriers shall not exceed 25 percent of the area of the fire barrier that is common with any room, unless the installation meets one of the following criteria:
  1. The installation is an existing fire window installation of wired glass and other fire-rated glazing materials in approved frames.
  2. The fire protection-rated glazing material is installed in approved existing frames. [101: 8.3.3.11]
New fire protection-rated glazing shall be marked in accordance with Table 12.7.3.12 and Table 12.7.4.2, and such marking shall be permanently affixed. [101: 8.3.3.12]

Table 12.7.3.12 Marking Fire-Rated Glazing Assemblies

Fire Test Standard Marking Definition of Marking
ASTM E 119, or ANSI/UL 263a W Meets wall assembly criteria
NFPA 257 OH Meets fire window assembly criteria, including the hose stream test
NFPA 252 D Meets fire door assembly criteria
  H Meets fire door assembly hose stream test
  T Meets 450°F (232°C) temperature rise criteria for 30 minutes
  XXX The time, in minutes, of fire resistance or fire protection rating of the glazing assembly

aASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, and ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials. [101: Table 8.3.3.12]

Fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives. [101: 8.3.3.13]
Every opening in a fire barrier shall be protected to limit the spread of fire and restrict the movement of smoke from one side of the fire barrier to the other. [101: 8.3.4.1]
The fire protection rating for opening protectives in fire barriers, fire-rated smoke barriers, and fire-rated smoke partitions shall be in accordance with Table 12.7.4.2, except as otherwise permitted in 12.7.4.3 or 12.7.4.4. [101: 8.3.4.2].

Table 12.7.4.2 Minimum Fire Protection Ratings for Opening Protectives in Fire Resistance-Rated Assemblies and Fire-Rated Glazing Markings

Component Walls and Partitions (hr) Fire Door Assemblies (hr) Door Vision Panel Maximum Size (in.2) Fire-Rated Glazing Marking Door Vision Panel Minimum Side Light/Transom Assembly Rating (hr) Fire-Rated Glazing Marking Side Light/Transom Panel Minimum Fire-Rated Windows Ratinga'b(hr) Fire Window Marking
Fire Protection Fire Resistance Fire Protection Fire Resistance Fire Protection Fire Resistance Fire Protection Fire Resistance
Elevator hoistways 2 11/2 155 in.2 ce D-H-90 or D-H-W-90 NP 2 NP D-H-W-120 NP 2 NP W-120
  1 1 155 in.2 ce D-H-60 or D-H-W-60 NP 1 NP D-H-W-60 NP 1 NP W-60
  1/2 1/2 85 in.2 d  v-20 or D-W-20 1/3 1/3 D-H-20 D-W-20 1/3 1/3 OH-20 W-30
Elevator lobby (per 7.2.13.4 of NFPA 101) 1 1 100 in.2 a ≤100 in.2, D-H-T-60 or D-H-W-60a
>100 in.2, D-H-W-60
NP 1 NP D-H-W-60     NP W-60
Vertical shafts, including stairways, exits, and refuse chutes 2 11/2 Maximum size tested D-H-90 or D-H-W-90 NP 2 NP D-H-W-120 NP 2 NP W-120
1 1 Maximum size tested D-H-60 or D-H-W-60 NP 1 NP D-H-W-60 NP 1 NP W-60
Replacement panels in existing vertical shafts 1/2 1/3 Maximum size tested D-20 or D-W-20 1/3 1/3 D-H-20 D-W-20 1/3 1/3 OH-20 W-30
Fire barriers 3 3 100 in.2 a ≤100 in.2, D-H-180 or D-H-W-180

>100 in.2, D-H-W-180
NP 3 NP D-H-W-180 NP 3 NP W-180
  2 11/2 Maximum size tested D-H-90 or D-H-W-90 NP 2 NP D-H-W-120 NP 2 NP W-120
  1 3/4 Maximum size testede D-H-45 or D-H-W-45 3/4e 3/4e D-H-45 D-H-W-45 3/4 3/4 OH-45 W-60
  1/2 1/3 Maximum size tested D-20 or D-W-20 1/3 1/3 D-H-20 D-W-20 1/3 1/3 OH-20 W-30
Horizontal exits 2 11/2 Maximum size tested D-H-90 or D-H-W-90 NP 2 NP D-H-W-120 NP 2 NP W-120
Horizontal exits served by bridges between buildings 2 3/4 Maximum size testede D-H-45 or D-H-W-45 3/4e 3/4e D-H-45 D-H-W-45 3/4 3/4 OH-45 W-120
Exit access corridorsf 1 1/3 Maximum size tested D-20 or D-W-20 3/4 3/4 D-H-45 D-H-W-20 3/4 3/4 OH-45 W-60
  1/2 1/3 Maximum size tested D-20 or D-W-20 1/3 1/3 D-H-20 D-H-W-20 1/3 1/3 OH-20 W-30
Smoke barriersf 1 1/3 Maximum size tested D-20 or D-W-20 3/4 3/4 D-H-45 D-H-W-20 3/4 3/4 OH-45 W-60
Smoke partitionsf,g 1/2 1/3 Maximum size tested D-20 or D-W-20 1/3 1/3 D-H-20 D-H-W-20 1/3 1/3 OH-20 W-30

For SI units, 1 in.2= .00064516 m2.

NP: Not permitted.

aFire resistance-rated glazing tested to ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, or ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, shall be permitted in the maximum size tested. (See 12.7.3.7.)

bFire-rated glazing in exterior windows shall be marked in accordance with Table 12.7.3.11.

cSee ASME A17.1, Safety Code for Elevators and Escalators, for additional information.

dSee ASTM A17.3, Safety Code for Existing Elevators and Escalators, for additional information.

eMaximum area of individual exposed lights shall be 1296 in.2 (0.84 m2) with no dimension exceeding 54 in. (1.37 m) unless otherwise tested. [80: Table 4.4.5, Note b, and 80:4.4.5.1]

fFire doors are not required to have a hose stream test per ANSI/UL 10B, Standard for Fire Tests of Door Assemblies; or ANSI/UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies.

hFor residential board and care, see 32.2.3.1 and 33.2.3.1 of NFPA 101. [101: Table 8.3.4.2]

Fire-rated glazing assemblies marked as complying with hose stream requirements (H) shall be permitted in applications that do not require compliance with hose stream requirements. Fire-rated glazing assemblies marked as complying with temperature rise requirements (T) shall be permitted in applications that do not require compliance with temperature rise requirements. Fire-rated glazing assemblies marked with ratings that exceed the ratings required by this Code (XXX) shall be permitted. [101: 8.3.4.2.1]
Existing fire door assemblies having a minimum 3/4-hour fire protection rating shall be permitted to continue to be used in vertical openings and in exit enclosures in lieu of the minimum 1-hour fire protection rating required by Table 12.7.4.2. [101: 8.3.4.3]
Where a 20-minute fire protection-rated door is required in existing buildings, an existing 13/4 in. (44 mm) solid-bonded wood-core door, an existing steel-clad (tin-clad) wood door, or an existing solid-core steel door with positive latch and closer shall be permitted, unless otherwise specified by Chapters 11 through 43 of NFPA 101. [101: 8.3.4.4]
The provisions of 12.7.5 shall govern the materials and methods of construction used to protect through-penetrations and membrane penetrations in fire walls, fire barrier walls, and fire resistance-rated horizontal assemblies. The provisions of 12.7.5 shall not apply to approved existing materials and methods of construction used to protect existing through-penetrations and existing membrane penetrations in fire walls, fire barrier walls, or fire resistance-rated horizontal assemblies, unless otherwise required by Chapter 11 through 43 of NFPA 101. [101: 8.3.5]
Penetrations for cables, cable trays, conduits, pipes, tubes, combustion vents and exhaust vents, wires, and similar items to accommodate electrical, mechanical, plumbing, and communications systems that pass through a wall, floor, or floor/ceiling assembly constructed as a fire barrier shall be protected by a firestop system or device. The firestop system or device shall be tested in accordance with ASTM E 814, Standard Test Method for Fire Tests of Through Penetration Fire Stops, or ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops, at a minimum positive pressure differential of 0.01 in. water column (2.5 N/m2) between the exposed and the unexposed surface of the test assembly. [101: 8.3.5.1]
The requirements of 12.7.5.1 shall not apply where otherwise permitted by any one of the following:
  1. Where penetrations are tested and installed as part of an assembly tested and rated in accordance with ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials or ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials
  2. Where penetrations through floors are enclosed in a shaft enclosure designed as a fire barrier
  3. Where concrete, grout, or mortar has been used to fill the annular spaces around cast-iron, copper, or steel piping that penetrates one or more concrete or masonry fire resistance-rated assemblies and both of the following criteria are also met:
    1. The nominal diameter of each penetrating item shall not exceed 6 in. (150 mm), and the opening size shall not exceed 1 ft2 (0.09 m2).
    2. The thickness of the concrete, grout, or mortar shall be the full thickness of the assembly.
  4. Where firestopping materials are used with the following penetrating items, the penetration is limited to one floor, and the firestopping material is capable of preventing the passage of flame and hot gases sufficient to ignite cotton waste when subjected to the time-temperature fire conditions of NFPA 251 under a minimum positive pressure differential of 0.01 in. water column (2.5 Pa) at the location of the penetration for the time period equivalent to the required fire resistance rating of the assembly penetrated:
    1. Steel, ferrous, or copper cables
    2. Cable or wire with steel jackets
    3. Cast-iron, steel, or copper pipes
    4. Steel conduit or tubing [101: 8.3.5.1.1]
The maximum nominal diameter of the penetrating item, as indicated in 12.7.5.1.1(4)(a) through (d), shall not be greater than 4 in. (100 mm) and shall not exceed an aggregate 100 in.2 (64,520 mm2) opening in any 100 ft2 (9.3 m2) of floor or wall area. [101: 8.3.5.1.2]
Firestop systems and devices shall have a minimum 1-hour F rating, but not less than the required fire resistance rating of the fire barrier penetrated. [101: 8.3.5.1.3]
Penetrations in fire resistance-rated horizontal assemblies shall be required to have a T rating of at least 1 hour, but not less than the fire resistance rating of the horizontal assembly, and shall not be required for either of the following:
  1. Floor penetrations contained within the cavity of a wall assembly
  2. Penetrations through floors or floor assemblies where the penetration is not in direct contact with combustible material [101: 8.3.5.1.4]
Where the penetrating item uses a sleeve to penetrate the wall or floor, the sleeve shall be securely set in the wall or floor, and the space between the item and the sleeve shall be filled with a material that complies with 12.7.5.1. [101: 8.3.5.2]
Insulation and coverings for penetrating items shall not pass through the wall or floor unless the insulation or covering has been tested as part of the firestop system or device. [101: 8.3.5.3]
Where designs take transmission of vibrations into consideration, any vibration isolation shall meet one of the following conditions:
  1. It shall be provided on either side of the wall or floor.
  2. It shall be designed for the specific purpose. [101: 8.3.5.4]
Where piping penetrates a fire resistance-rated wall or floor assembly, combustible piping shall not connect to noncombustible piping within 36 in. (915 mm) of the firestop system or device without demonstration that the transition will not reduce the fire resistance rating, except in the case of previously approved installations. [101: 8.3.5.5.1]
Unshielded couplings shall not be used to connect noncombustible piping to combustible piping unless it can be demonstrated that the transition complies with the fire-resistive requirements of 12.7.5.1. [101: 8.3.5.5.2]
Membrane penetrations for cables, cable trays, conduits, pipes, tubes, combustion vents and exhaust vents, wires, and similar items to accommodate electrical, mechanical, plumbing, and communications systems that pass through a membrane of a wall, floor, or floor/ceiling assembly constructed as a fire barrier shall be protected by a firestop system or device and shall comply with 12.7.5.1 through 12.7.5.5.2. [101: 8.3.5.6.1]
The firestop system or device shall be tested in accordance with ASTM E 814, Standard Test Method for Fire Tests of Through Penetration Fire Stops, or ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops, at a minimum positive pressure differential of 0.01 in. water column (2.5 N/m2) between the exposed and the unexposed surface of the test assembly, unless one of the following applies:
  1. Membrane penetrations of ceilings that are not an integral part of a fire resistance-rated floor/ceiling or roof/ceiling assembly shall be permitted.
  2. Membrane penetrations of steel, ferrous, or copper conduits, pipes, tubes, or combustion vents or exhaust vents shall be permitted where the annular space is protected with an approved material, and the aggregate area of the openings does not exceed 0.7 ft2 (0.06 m2) in any 100 ft2 (9.3 m2) of ceiling area.
  3. Electrical outlet boxes and fittings shall be permitted, provided that such devices are listed for use in fire resistance-rated assemblies and are installed in accordance with their listing.
  4. The annular space created by the membrane penetration of a fire sprinkler shall be permitted, provided that the space is covered by a metal escutcheon plate. [101: 8.3.5.6.2]
Where walls or partitions are required to have a minimum 1-hour fire resistance rating, recessed fixtures shall be installed in the wall or partition in such a manner that the required fire resistance is not reduced, unless one of the following is met:
  1. Any steel electrical box not exceeding 0.1 ft2 (0.01 m2) shall be permitted where the aggregate area of the openings provided for the boxes does not exceed 0.7 ft2 (0.06 m2) in any 100 ft2 (9.3 m2) of wall area, and, where outlet boxes are installed on opposite sides of the wall, the boxes shall be separated by one of the following:
    1. Horizontal distance of not less than 24 in. (610 mm)
    2. Horizontal distance of not less than the depth of the wall cavity, where the wall cavity is filled with cellulose loose-fill, rockwool, or slag wool insulation
    3. *Solid fireblocking
    4. Other listed materials and methods
  2. Membrane penetrations for any listed electrical outlet box made of any material shall be permitted, provided that such boxes have been tested for use in fire resistance-rated assemblies and are installed in accordance with the instructions included in the listing.
  3. The annular space created by the membrane penetration of a fire sprinkler shall be permitted, provided that the space is covered by a metal escutcheon plate.
  4. Membrane penetrations by electrical boxes of any size or type, which have been listed as part of a wall opening protective material system for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing shall be permitted. [101: 8.3.5.6.3]
Openings in fire barriers for air-handling ductwork or air movement shall be protected in accordance with 11.2.1. [101: 8.3.5.7]
The provisions of 12.7.5.8 shall govern the materials and methods of construction used to protect joints in between and at the perimeter of fire barriers or, where fire barriers meet other fire barriers, the floor or roof deck above, or the outside walls. The provisions of 12.7.5.8 shall not apply to approved existing materials and methods of construction used to protect existing joints in fire barriers, unless otherwise required by Chapters 11 through 43 of NFPA 101. [101: 8.3.6.1]
Joints made within or at the perimeter of fire barriers shall be protected with a joint system that is capable of limiting the transfer of smoke. [101: 8.3.6.2]
Joints made within or between fire barriers shall be protected with a smoke-tight joint system that is capable of limiting the transfer of smoke. [101: 8.3.6.3]
Testing of the joint system in a fire barrier shall be representative of the actual installation suitable for the required engineering demand without compromising the fire resistance rating of the assembly or the structural integrity of the assembly. [101: 8.3.6.4]
Joints made within or between fire resistance-rated assemblies shall be protected with a joint system that is designed and tested to prevent the spread of fire for a time period equal to that of the assembly in which the joint is located. Such materials, systems, or devices shall be tested as part of the assembly in accordance with the requirements of ASTM E 1966, Standard Test Method for Fire-Resistive Joint Systems, or ANSI/UL 2079, Standard for Tests for Fire Resistance of Building Joint Systems. [101: 8.3.6.5]
All joint systems shall be tested at their maximum joint width in accordance with the requirements of ASTM E 1966 or ANSI/UL 2079, under a minimum positive pressure differential of 0.01 in. water column (2.5 N/m2) for a time period equal to that of the assembly. All test specimens shall comply with the minimum height or length required by the standard. Wall assemblies shall be subjected to a hose stream test in accordance with ASTM E 119 or ANSI/UL 263. [101: 8.3.6.6]
Voids created between the fire resistance-rated floor assembly and the exterior curtain wall shall be protected with a perimeter joint system that is designed and tested in accordance with ASTM E 2307, Standard Test Method for Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multistory Apparatus. [101: 8.3.6.7.1]
The perimeter joint system shall have an F rating equal to the fire resistance rating of the floor assembly. [101: 8.3.6.7.2]
Where required elsewhere in this Code, smoke partitions shall be provided to limit the transfer of smoke. [101: 8.4.1]

12.8.2 Continuity

ILLUSTRATION
The following shall apply to smoke partitions:
  1. They shall extend from the floor to the underside of the floor or roof deck above, through any concealed spaces, such as those above suspended ceilings, and through interstitial structural and mechanical spaces.
  2. *They shall be permitted to extend from the floor to the underside of a monolithic or suspended ceiling system where the following conditions are met:
    1. The ceiling system forms a continuous membrane.
    2. A smoke-tight joint is provided between the top of the smoke partition and the bottom of the suspended ceiling.
    3. The space above the ceiling is not used as a plenum.
  3. Smoke partitions enclosing hazardous areas shall be permitted to terminate at the underside of a monolithic or suspended ceiling system where the following conditions are met:
    1. The ceiling system forms a continuous membrane.
    2. A smoke-tight joint is provided between the top of the smoke partition and the bottom of the suspended ceiling.
    3. Where the space above the ceiling is used as a plenum, return grilles from the hazardous area into the plenums are not permitted. [101: 8.4.2]
Doors in smoke partitions shall comply with 12.8.3.2 through 12.8.3.5. [101: 8.4.3.1]
Doors shall comply with the provisions of 7.2.1 of NFPA 101. [101: 8.4.3.2]
Doors shall not include louvers. [101: 8.4.3.3]
Door clearances shall be in accordance with NFPA 80. [101: 8.4.3.4]
Doors shall be self-closing or automatic-closing in accordance with 14.5.4. [101: 8.4.3.5]
The provisions of 12.8.4 shall govern the materials and methods of construction used to protect through-penetrations and membrane penetrations of smoke partitions. [101: 8.4.4]
Penetrations for cables, cable trays, conduits, pipes, tubes, vents, wires, and similar items to accommodate electrical, mechanical, plumbing, and communications systems that pass through a smoke partition shall be protected by a system or material that is capable of limiting the transfer of smoke. [101: 8.4.4.1]
Where designs take transmission of vibrations into consideration, any vibration isolation shall meet one of the following conditions:
  1. It shall be provided on either side of the smoke partition.
  2. It shall be designed for the specific purpose. [101: 8.4.4.2]

12.8.5 Joints

ILLUSTRATION
The provisions of 12.8.5 shall govern the materials and methods of construction used to protect joints in between and at the perimeter of smoke partitions or, where smoke partitions meet other smoke partitions, the floor or roof deck above, or the outside walls. The provisions of 12.8.5 shall not apply to approved existing materials and methods of construction used to protect existing joints in smoke partitions, unless otherwise required by Chapters 11 through 43 of NFPA 101. [101: 8.4.5.1]
Joints made within or at the perimeter of smoke partitions shall be protected with a joint system that is capable of limiting the transfer of smoke. [101: 8.4.5.2]
The provisions of 12.8.6 shall govern the materials and methods of construction used to protect air-transfer openings in smoke partitions. [101: 8.4.6.1]
Air-transfer openings in smoke partitions shall be provided with approved smoke dampers designed and tested in accordance with the requirements of ANSI/UL 555S, Standard for Smoke Dampers, to limit the transfer of smoke. [101: 8.4.6.2]
Smoke damper leakage ratings shall be not less than Class II. Elevated temperature ratings shall be not less than 250°F (140°C). [101: 8.4.6.3]
Dampers in air-transfer openings shall close upon detection of smoke by approved smoke detectors installed in accordance with NFPA 72, National Fire Alarm and Signaling Code and Section 13.7. [101: 8.4.6.4]
Where required by Chapters 11 through 43 of NFPA 101, smoke barriers shall be provided to subdivide building spaces for the purpose of restricting the movement of smoke. [101: 8.5.1]

12.9.2* Continuity

ILLUSTRATION
Smoke barriers required by NFPA 101 shall be continuous from an outside wall to an outside wall, from a floor to a floor, or from a smoke barrier to a smoke barrier, or by use of a combination thereof. [101: 8.5.2.1]
Smoke barriers required by NFPA 101 shall be continuous through all concealed spaces, such as those found above a ceiling, including interstitial spaces. [101: 8.5.2.2]
A smoke barrier required for an occupied space below an interstitial space shall not be required to extend through the interstitial space, provided that the construction assembly forming the bottom of the interstitial space provides resistance to the passage of smoke equal to that provided by the smoke barrier. [101: 8.5.2.3]
A fire barrier shall be permitted to be used as a smoke barrier, provided that it meets the requirements of Section 12.9. [101: 8.5.3]
Doors in smoke barriers shall close the opening, leaving only the minimum clearance necessary for proper operation, and shall be without louvers or grilles. For other than previously approved existing doors, the clearance under the bottom of the doors shall be a maximum of 3/4 in. (19 mm). [101: 8.5.4.1]
Where required by Chapters 11 through 43 of NFPA 101, doors in smoke barriers that are required to be smoke leakage-rated shall comply with the requirements of 8.2.2.5 of NFPA 101. [101: 8.5.4.2]
Latching hardware shall be required on doors in smoke barriers unless specifically exempted by Chapters 11 through 43 of NFPA 101. [101: 8.5.4.3]
Doors in smoke barriers shall be self-closing or automatic-closing in accordance with 14.5.4 and shall comply with the provisions of 7.2.1 of NFPA 101. [101: 8.5.4.4]
Fire window assemblies shall comply with 12.7.3. [101: 8.5.4.5]
The provisions of 12.9.5 shall govern the materials and methods of construction used to protect ducts and air-transfer openings in smoke barriers. [101: 8.5.5.1]
Where a smoke barrier is penetrated by a duct or air-transfer opening, a smoke damper designed and tested in accordance with the requirements of ANSI/UL 555S shall be installed. [101: 8.5.5.2.1]
Where a smoke barrier is also constructed as a fire barrier, a combination fire/smoke damper designed and tested in accordance with the requirements of ANSI/UL 555 and ANSI/UL 555S shall be installed. [101: 8.5.5.2.2]
Smoke dampers shall not be required under any of the following conditions:
  1. Where specifically exempted by provisions in Chapters 11 through 43 of NFPA 101
  2. Where ducts or air-transfer openings are part of an engineered smoke control system and the smoke damper will interfere with the operation of a smoke control system
  3. Where the air in ducts continues to move and the air-handling system installed is arranged to prevent recirculation of exhaust or return air under fire emergency conditions
  4. Where the air inlet or outlet openings in ducts are limited to a single smoke compartment
  5. Where ducts penetrate floors that serve as smoke barriers
  6. Where ducts penetrate smoke barriers forming a communicating space separation in accordance with 8.6.6(4)(a) of NFPA 101 [101: 8.5.5.3]
Air-conditioning, heating, ventilating ductwork, and related equipment, including smoke dampers and combination fire and smoke dampers, shall be installed in accordance with NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems; NFPA 90B, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems; NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives; or NFPA 80, Standard for Fire Doors and Other Opening Protectives, as applicable. [101: 8.5.5.4.1]
Smoke dampers and combination fire and smoke dampers required by this code shall be inspected, tested, and maintained in accordance with NFPA 105. [101: 8.5.5.4.2]
The equipment specified in 12.9.5.4.1 shall be installed in accordance with the requirements of 12.9.5, the manufacturer's installation instructions, and the equipment listing. [101: 8.5.5.4.3]
Access to the dampers shall be provided for inspection, testing, and maintenance. [101: 8.5.5.5.1]
Smoke and combination fire and smoke dampers in new construction shall be provided with an approved means of access, as follows:
  1. The means of access shall be large enough to allow inspection and maintenance of the damper and its operating parts.
  2. The access shall not affect the integrity of fire resistance-rated assemblies or smoke barrier continuity.
  3. The access openings shall not reduce the fire resistance rating of the assembly.
  4. Access doors in ducts shall be tight-fitting and suitable for the required duct construction.
  5. Access and maintenance shall comply with the requirements of the mechanical code. [101: 8.5.5.5.2]
Access points to fire and smoke dampers in new construction shall be permanently identified by one of the following:
  1. A label having letters not less than 1/2 in. (13 mm) in height and reading as one of the following:
    1. FIRE/SMOKE DAMPER
    2. SMOKE DAMPER
    3. FIRE DAMPER
  2. Symbols as approved by the AHJ [101: 8.5.5.5.3]
Smoke damper leakage ratings shall be not less than Class II. Elevated temperature ratings shall be not less than 250°F (140°C). [101: 8.5.5.6]
Required smoke dampers in ducts penetrating smoke barriers shall close upon detection of smoke by approved smoke detectors in accordance with NFPA 72, unless one of the following conditions exists:
  1. The ducts penetrate smoke barriers above the smoke barrier doors, and the door release detector actuates the damper.
  2. Approved smoke detector installations are located within the ducts in existing installations. [101: 8.5.5.7.1]
Where a duct is provided on one side of the smoke barrier, the smoke detectors on the duct side shall be in accordance with 12.9.5.7.1. [101: 8.5.5.7.2]
Required smoke dampers in air-transfer openings shall close upon detection of smoke by approved smoke detectors in accordance with NFPA 72. [101: 8.5.5.7.3]
The provisions of 12.9.6 shall govern the materials and methods of construction used to protect through-penetrations and membrane penetrations of smoke barriers. [101: 8.5.6.1]
Penetrations for cables, cable trays, conduits, pipes, tubes, vents, wires, and similar items to accommodate electrical, mechanical, plumbing, and communications systems that pass through a wall, floor, or floor/ceiling assembly constructed as a smoke barrier, or through the ceiling membrane of the roof/ceiling of a smoke barrier assembly, shall be protected by a system or material capable of restricting the transfer of smoke. [101: 8.5.6.2]
Where a smoke barrier is also constructed as a fire barrier, the penetrations shall be protected in accordance with the requirements of 12.7.5 to limit the spread of fire for a time period equal to the fire resistance rating of the assembly and 12.9.6 to restrict the transfer of smoke, unless the requirements of 12.9.6.4 are met. [101: 8.5.6.3]
Where sprinklers penetrate a single membrane of a fire resistance-rated assembly in buildings equipped throughout with an approved automatic fire sprinkler system, noncombustible escutcheon plates shall be permitted, provided that the space around each sprinkler penetration does not exceed 1/2 in. (13 mm), measured between the edge of the membrane and the sprinkler. [101: 8.5.6.4]
Where the penetrating item uses a sleeve to penetrate the smoke barrier, the sleeve shall be securely set in the smoke barrier, and the space between the item and the sleeve shall be filled with a listed system or with a material capable of restricting the transfer of smoke. [101: 8.5.6.5]
Where designs take transmission of vibrations into consideration, any vibration isolation shall meet one of the following conditions:
  1. It shall be provided on either side of the smoke barrier.
  2. It shall be designed for the specific purpose. [101: 8.5.6.6]
The provisions of 12.9.7 shall govern the materials and methods of construction used to protect joints in between and at the perimeter of smoke barriers or, where smoke barriers meet other smoke barriers, the floor or roof deck above, or the outside walls. The provisions of 12.9.7 shall not apply to approved existing materials and methods of construction used to protect existing joints in smoke barriers, unless otherwise required by Chapters 11 through 43 of NFPA 101. [101: 8.5.7.1]
Joints made within or at the perimeter of smoke barriers shall be protected with a joint system that is capable of limiting the transfer of smoke. [101: 8.5.7.2]
Joints made within or between smoke barriers shall be protected with a smoke-tight joint system that is capable of limiting the transfer of smoke. [101: 8.5.7.3]
Smoke barriers that are also constructed as fire barriers shall be protected with a joint system that is designed and tested to resist the spread of fire for a time period equal to the required fire resistance rating of the assembly and restrict the transfer of smoke. [101: 8.5.7.4]
Testing of the joint system in a smoke barrier that also serves as fire barrier shall be representative of the actual installation. [101: 8.5.7.5]
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING