CODES

ADOPTS WITH AMENDMENTS:

International Existing Building Code 2015 (IEBC 2015)

Introduction

The International Existing Building Code® (IEBC®) is a comprehensive code with the goal of addressing all aspects of work taking place in existing buildings and providing user-friendly methods and tools for regulation and improvement of such buildings. This resource document is included within the cover of the IEBC with that goal in mind and as a step towards accomplishing that goal.

In the process of repair and alteration of existing buildings, based on the nature and the extent of the work, the IEBC might require certain upgrades in the fire-resistance rating of building elements, at which time it becomes critical for the designers and the code officials to be able to determine the fire-resistance rating of the existing building elements as part of the overall evaluation for the assessment of the need for improvements. This resource document provides a guideline for such an evaluation for fire-resistance ratings of archaic materials that are not typically found in the modern model building codes.

Resource A is only a guideline and is not intended to be a document for specific adoption as it is not written in the format or language of ICC's International Codes and is not subject to the code development process.

PURPOSE

The Guideline on Fire Ratings of Archaic Materials and Assemblies focuses upon the fire-related performance of archaic construction. "Archaic"encompasses construction typical of an earlier time, generally prior to 1950. "Fire-related performance"includes fire resistance, flame spread, smoke production and degree of combustibility.

The purpose of this guideline is to update the information which was available at the time of original construction, for use by architects, engineers and code officials when evaluating the fire safety of a rehabilitation project. In addition, information relevant to the evaluation of general classes of materials and types of construction is presented for those cases when documentation of the fire performance of a particular archaic material or assembly cannot be found.

It has been assumed that the building materials and their fastening, joining and incorporation into the building structure are sound mechanically. Therefore, some determination must be made that the original manufacture, the original construction practice, and the rigors of aging and use have not weakened the building. This assessment can often be difficult because process and quality control was not good in many industries, and variations among locally available raw materials and manufacturing techniques often resulted in a product which varied widely in its strength and durability. The properties of iron and steel, for example, varied widely, depending on the mill and the process used.

There is nothing inherently inferior about archaic materials or construction techniques. The pressures that promote fundamental change are most often economic or technological matters not necessarily related to concerns for safety. The high cost of labor made wood lath and plaster uneconomical. The high cost of land and the congestion of the cities provided the impetus for high-rise construction. Improved technology made it possible. The difficulty with archaic materials is not a question of suitability, but familiarity.

Code requirements for the fire performance of key building elements (e.g., walls, floor/ceiling assemblies, doors, shaft enclosures) are stated in performance terms: hours of fire resistance. It matters not whether these elements were built in 1908 or 1980, only that they provide the required degree of fire resistance. The level of performance will be defined by the local community, primarily through the enactment of a building or rehabilitation code. This guideline is only a tool to help evaluate the various building elements, regardless of what the level of performance is required to be.

The problem with archaic materials is simply that documentation of their fire performance is not readily available. The application of engineering judgment is more difficult because building officials may not be familiar with the materials or construction method involved. As a result, either a full-scale fire test is required or the archaic construction in question removed and replaced. Both alternatives are time consuming and wasteful.

This guideline and the accompanying appendix are designed to help fill this information void. By providing the necessary documentation, there will be a firm basis for the continued acceptance of archaic materials and assemblies.

1 FIRE-RELATED PERFORMANCE OF ARCHAIC MATERIALS AND ASSEMBLIES

FIGURE 1 PRELIMINARY EVALUATION FIELD NOTES

BUILDING ELEMENT MATERIALS THICKNESS CONDITION NOTES
Exterior Bearing Walls
Interior Bearing Walls
Exterior Nonbearing Walls
Interior Nonbearing
Walls or Partitions:
A
B
Structural Frame:
Columns
Beams
Other
Floor/Ceiling
Structural System
Spanning
Roofs
Doors (including frame and hardware):
a) Enclosed vertical exitway
b) Enclosed horizontal exitway
c) Other


1.1 FIRE PERFORMANCE MEASURES

This guideline does not specify the level of performance required for the various building components. These requirements are controlled by the building occupancy and use and are set forth in the local building or rehabilitation code.

The fire resistance of a given building element is established by subjecting a sample of the assembly to a "standard"fire test which follows a "standard"time-temperature curve. This test method has changed little since the 1920s. The test results tabulated in the Appendix have been adjusted to reflect current test methods.

The current model building codes cite other fire-related properties not always tested for in earlier years: flame spread, smoke production, and degree of combustibility. However, they can generally be assumed to fall within well defined values because the principal combustible component of archaic materials is cellulose. Smoke production is more important today because of the increased use of plastics. However, the early flame spread tests, developed in the early 1940s, also included a test for smoke production.

"Plastics,"one of the most important classes of contemporary materials, were not found in the review of archaic materials. If plastics are to be used in a rehabilitated building, they should be evaluated by contemporary standards. Information and documentation of their fire-related properties and performance is widely available.

Flame spread, smoke production and degree of combustibility are discussed in detail below. Test results for eight common species of lumber, published in an Underwriter's Laboratories' report (104), are noted in the following table:

TUNNEL TEST RESULTS FOR EIGHT SPECIES OF LUMBER

SPECIES OF LUMBER FLAME
SPREAD
FUEL
CONTRIBUTED
SMOKE
DEVELOPED
Western White Pine 75 50-60 50
Northern White Pine 120-215 120-140 60-65
Ponderosa Pine 80-215 120-135 100-110
Yellow Pine 180-190 130-145 275-305
Red Gum 140-155 125-175 40-60
Yellow Birch 105-110 100-105 45-65
Douglas Fir 65-100 50-80 10-100


Flame Spread

The flame spread of interior finishes is most often measured by the ASTM E 84 "tunnel test."This test measures how far and how fast the flames spread across the surface of the test sample. The resulting flame spread rating (FSR) is expressed as a number on a continuous scale where cementasbestos board is 0 and red oak is 100. (Materials with a flame spread greater than red oak have an FSR greater than 100.) The scale is divided into distinct groups or classes. The most commonly used flame spread classifications are: Class I or A*, with a 0-25 FSR; Class II or B, with a 26-75 FSR; and Class III or C, with a 76-200 FSR. The NFPA Life Safety Code also has a Class D (201-500 FSR) and Class E (over 500 FSR) interior finish.

These classifications are typically used in modern building codes to restrict the rate of fire spread. Only the first three classifications are normally permitted, though not all classes of materials can be used in all places throughout a building. For example, the interior finish of building materials used in exits or in corridors leading to exits is more strictly regulated than materials used within private dwelling units.

In general, inorganic archaic materials (e.g., bricks or tile) can be expected to be in Class I. Materials of whole wood are mostly Class II. Whole wood is defined as wood used in the same form as sawn from the tree. This is in contrast to the contemporary reconstituted wood products such as plywood, fiberboard, hardboard, or particle board. If the organic archaic material is not whole wood, the flame spread classification could be well over 200 and thus would be particularly unsuited for use in exits and other critical locations in a building. Some plywoods and various wood fiberboards have flame spreads over 200. Although they can be treated with fire retardants to reduce their flame spread, it would be advisable to assume that all such products have a flame spread over 200 unless there is information to the contrary.

Smoke Production

The evaluation of smoke density is part of the ASTM E 84 tunnel test. For the eight species of lumber shown in the table above, the highest levels are 275-305 for Yellow Pine, but most of the others are less smoky than red oak which has an index of 100. The advent of plastics caused substantial increases in the smoke density values measured by the tunnel test. The ensuing limitation of the smoke production for wall and ceiling materials by the model building codes has been a reaction to the introduction of plastic materials. In general, cellulosic materials fall in the 50-300 range of smoke density which is below the general limitation of 450 adopted by many codes.

Degree of Combustibility

The model building codes tend to define "noncombustibility"on the basis of having passed ASTM E 136 or if the material is totally inorganic. The acceptance of gypsum wallboard as noncombustible is based on limiting paper thickness to not over 1/8 inch and a 0-50 flame spread rating by ASTM E 84. At times there were provisions to define a Class I or A material (0-25 FSR) as noncombustible, but this is not currently recognized by most model building codes.

If there is any doubt whether or not an archaic material is noncombustible, it would be appropriate to send out samples for evaluation. If an archaic material is determined to be noncombustible according to ASTM E 136, it can be expected that it will not contribute fuel to the fire.

* Some codes are Roman numerals, others use letters.

1.2 COMBUSTIBLE CONSTRUCTION TYPES

One of the earliest forms of timber construction used exterior load-bearing masonry walls with columns and/or wooden walls supporting wooden beams and floors in the interior of the building. This form of construction, often called "mill"or "heavy timber"construction, has approximately 1 hour fire resistance. The exterior walls will generally contain the fire within the building.

With the development of dimensional lumber, there was a switch from heavy timber to "balloon frame"construction. The balloon frame uses load-bearing exterior wooden walls which have long timbers often extending from foundation to roof. When longer lumber became scarce, another form of construction, "platform"framing, replaced the balloon framing. The difference between the two systems is significant because platform framing is automatically fire-blocked at every floor while balloon framing commonly has concealed spaces that extend unblocked from basement to attic. The architect, engineer, and code official must be alert to the details of construction and the ease with which fire can spread in concealed spaces.

2 BUILDING EVALUATION

A given rehabilitation project will most likely go through several stages. The preliminary evaluation process involves the designer in surveying the prospective building. The fire resistance of existing building materials and construction systems is identified; potential problems are noted for closer study. The final evaluation phase includes: developing design solutions to upgrade the fire resistance of building elements, if necessary; preparing working drawings and specifications; and the securing of the necessary code approvals.

FIGURE 2 PRELIMINARY EVALUATION WORKSHEET

BUILDING ELEMENT REQUIRED FIRE
RESISTANCE
REQUIRED
FLAME SPREAD
ESTIMATED FIRE
RESISTANCE
ESTIMATED
FLAME SPREAD
METHOD OF
UPGRADING
ESTIMATED
UPGRADED
PROTECTION
NOTES
Exterior Bearing
Walls
Interior Bearing
Walls
Exterior Nonbearing
Walls
Interior
Nonbearing
Walls or Partitions:
A
B
Structural Frame:
Columns
Beams
Other
Floor/Ceiling
Structural System
Spanning
Roofs
Doors (including frame and
hardware):
a) Enclosed vertical exitway
b) Enclosed horizontal
exitway
c) Others


2.1 PRELIMINARY EVALUATION

A preliminary evaluation should begin with a building survey to determine the existing materials, the general arrangement of the structure and the use of the occupied spaces, and the details of construction. The designer needs to know "what is there" before a decision can be reached about what to keep and what to remove during the rehabilitation process. This preliminary evaluation should be as detailed as necessary to make initial plans. The fire-related properties need to be determined from the applicable building or rehabilitation code, and the materials and assemblies existing in the building then need to be evaluated for these properties. Two work sheets are shown below to facilitate the preliminary evaluation.

Two possible sources of information helpful in the preliminary evaluation are the original building plans and the building code in effect at the time of original construction. Plans may be on file with the local building department or in the offices of the original designers (e.g., architect, engineer) or their successors. If plans are available, the investigator should verify that the building was actually constructed as called for in the plans, as well as incorporate any later alterations or changes to the building. Earlier editions of the local building code should be on file with the building official. The code in effect at the time of construction will contain fire performance criteria. While this is no guarantee that the required performance was actually provided, it does give the investigator some guidance as to the level of performance which may be expected. Under some code administration and enforcement systems, the code in effect at the time of construction also defines the level of performance that must be provided at the time of rehabilitation.

Figure 1 illustrates one method for organizing preliminary field notes. Space is provided for the materials, dimensions, and condition of the principal building elements. Each floor of the structure should be visited and the appropriate information obtained. In practice, there will often be identical materials and construction on every floor, but the exception may be of vital importance. A schematic diagram should be prepared of each floor showing the layout of exits and hallways and indicating where each element described in the field notes fits into the structure as a whole. The exact arrangement of interior walls within apartments is of secondary importance from a fire safety point of view and need not be shown on the drawings unless these walls are required by code to have a fire resistance rating.

The location of stairways and elevators should be clearly marked on the drawings. All exterior means of escape (e.g., fire escapes) should be identified.1

The following notes explain the entries in Figure 1.

Exterior Bearing Walls: Many old buildings utilize heavily constructed walls to support the floor/ceiling assemblies at the exterior of the building. There may be columns and/or interior bearing walls within the structure, but the exterior walls are an important factor in assessing the fire safety of a building.

The field investigator should note how the floor/ceiling assemblies are supported at the exterior of the building. If columns are incorporated in the exterior walls, the walls may be considered nonbearing.

Interior Bearing Walls: It may be difficult to determine whether or not an interior wall is load bearing, but the field investigator should attempt to make this determination. At a later stage of the rehabilitation process, this question will need to be determined exactly. Therefore, the field notes should be as accurate as possible.

Exterior Nonbearing Walls:The fire resistance of the exterior walls is important for two reasons. These walls (both bearing and nonbearing) are depended upon to: a) contain a fire within the building of origin; or b) keep an exterior fire outside the building. It is therefore important to indicate on the drawings where any openings are located as well as the materials and construction of all doors or shutters. The drawings should indicate the presence of wired glass, its thickness and framing, and identify the materials used for windows and door frames. The protection of openings adjacent to exterior means of escape (e.g., exterior stairways, fire escapes) is particularly important. The ground floor drawing should locate the building on the property and indicate the precise distances to adjacent buildings.

Interior Nonbearing Walls (Partitions):A partition is a "wall that extends from floor to ceiling and subdivides space within any story of a building."(48) Figure 1 has two categories (A & B) for Interior Nonbearing Walls (Partitions) which can be used for different walls, such as hallway walls as compared to inter-apartment walls. Under some circumstances there may be only one type of wall construction; in others, three or more types of wall construction may occur.

The field investigator should be alert for differences in function as well as in materials and construction details. In general, the details within apartments are not as important as the major exit paths and exit stairways. The preliminary field investigation should attempt to determine the thickness of all walls. A term introduced below called "thickness design"will depend on an accurate (± 1/4 inch) determination. Even though this initial field survey is called "preliminary," the data generated should be as accurate and complete as possible.

The field investigator should note the exact location from which observations are recorded. For instance, if a hole is found through a wall enclosing an exit stairway which allows a cataloguing of the construction details, the field investigation notes should reflect the location of the "find."At the preliminary stage it is not necessary to core every wall; the interior details of construction can usually be determined at some location.

Structural Frame: There may or may not be a complete skeletal frame, but usually there are columns, beams, trusses, or other like elements. The dimensions and spacing of the structural elements should be measured and indicated on the drawings. For instance, if there are 10-inch square columns located on a 30-foot square grid throughout the building, this should be noted. The structural material and cover or protective materials should be identified wherever possible. The thickness of the cover materials should be determined to an accuracy of ± 1/4 inch. As discussed above, the preliminary field survey usually relies on accidental openings in the cover materials rather than a systematic coring technique.

Floor/Ceiling Structural Systems: The span between supports should be measured. If possible, a sketch of the cross-section of the system should be made. If there is no location where accidental damage has opened the floor/ceiling construction to visual inspection, it is necessary to make such an opening. An evaluation of the fire resistance of a floor/ceiling assembly requires detailed knowledge of the materials and their arrangement. Special attention should be paid to the cover on structural steel elements and the condition of suspended ceilings and similar membranes.

Roofs: The preliminary field survey of the roof system is initially concerned with water-tightness. However, once it is apparent that the roof is sound for ordinary use and can be retained in the rehabilitated building, it becomes necessary to evaluate the fire performance. The field investigator must measure the thickness and identify the types of materials which have been used. Be aware that there may be several layers of roof materials.

Doors: Doors to stairways and hallways represent some of the most important fire elements to be considered within a building. The uses of the spaces separated largely controls the level of fire performance necessary. Walls and doors enclosing stairways or elevator shafts would normally require a higher level of performance than between the bedroom and bath. The various uses are differentiated in Figure 1.

Careful measurements of the thickness of door panels must be made, and the type of core material within each door must be determined. It should be noted whether doors have self-closing devices; the general operation of the doors should be checked. The latch should engage and the door should fit tightly in the frame. The hinges should be in good condition. If glass is used in the doors, it should be identified as either plain glass or wired glass mounted in either a wood or steel frame.

Materials: The field investigator should be able to identify ordinary building materials. In situations where an unfamiliar material is found, a sample should be obtained. This sample should measure at least 10 cubic inches so that an ASTM E 136 fire test can be conducted to determine if it is combustible.

Thickness: The thickness of all materials should be measured accurately since, under certain circumstances, the level of fire resistance is very sensitive to the material thickness.

Condition: The method of attaching the various layers and facings to one another or to the supporting structural element should be noted under the appropriate building element. The "secureness"of the attachment and the general condition of the layers and facings should be noted here.

Notes: The "Notes"column can be used for many purposes, but it might be a good idea to make specific references to other field notes or drawings.

After the building survey is completed, the data collected must be analyzed. A suggested work sheet for organizing this information is given below as Figure 2.

The required fire resistance and flame spread for each building element are normally established by the local building or rehabilitation code. The fire performance of the existing materials and assemblies should then be estimated, using one of the techniques described below. If the fire performance of the existing building element(s) is equal to or greater than that required, the materials and assemblies may remain. If the fire performance is less than required, then corrective measures must be taken.

The most common methods of upgrading the level of protection are to either remove and replace the existing building element(s) or to repair and upgrade the existing materials and assemblies. Other fire protection measures, such as automatic sprinklers or detection and alarm systems, also could be considered, though they are beyond the scope of this guideline. If the upgraded protection is still less than that required or deemed to be acceptable, additional corrective measures must be taken. This process must continue until an acceptable level of performance is obtained.

2.2 FIRE RESISTANCE OF EXISTING BUILDING ELEMENTS

The fire resistance of the existing building elements can be estimated from the tables and histograms contained in the Appendix. The Appendix is organized first by type of building element: walls, columns, floor/ceiling assemblies, beams, and doors. Within each building element, the tables are organized by type of construction (e.g., masonry, metal, wood frame), and then further divided by minimum dimensions or thickness of the building element.

A histogram precedes every table that has 10 or more entries. The X-axis measures fire resistance in hours; the Yaxis shows the number of entries in that table having a given level of fire resistance. The histograms also contain the location of each entry within that table for easy cross-referencing.

The histograms, because they are keyed to the tables, can speed the preliminary investigation. For example, Table 1.3.2, Wood Frame Walls 4" to Less Than 6" Thick, contains 96 entries. Rather than study each table entry, the histogram shows that every wall assembly listed in that table has a fire resistance of less than 2 hours. If the building code required the wall to have 2 hours fire resistance, the designer, with a minimum of effort, is made aware of a problem that requires closer study.

Suppose the code had only required a wall of 1 hour fire resistance. The histogram shows far fewer complying elements (19) than noncomplying ones (77). If the existing assembly is not one of the 19 complying entries, there is a strong possibility the existing assembly is deficient. The histograms can also be used in the converse situation. If the existing assembly is not one of the smaller number of entries with a lower than required fire resistance, there is a strong possibility the existing assembly will be acceptable.

At some point, the existing building component or assembly must be located within the tables. Otherwise, the fire resistance must be determined through one of the other techniques presented in the guideline. Locating the building component in the Appendix Tables not only guarantees the accuracy of the fire resistance rating, but also provides a source of documentation for the building official.

2.3 EFFECTS OF PENETRATIONS IN FIRE RESISTANT ASSEMBLIES

There are often many features in existing walls or floor/ceiling assemblies which were not included in the original certification or fire testing. The most common examples are pipes and utility wires passed through holes poked through an assembly. During the life of the building, many penetrations are added, and by the time a building is ready for rehabilitation it is not sufficient to just consider the fire resistance of the assembly as originally constructed. It is necessary to consider all penetrations and their relative impact upon fire performance. For instance, the fire resistance of the corridor wall may be less important than the effect of plain glass doors or transoms. In fact, doors are the most important single class of penetrations.

A fully developed fire generates substantial quantities of heat and excess gaseous fuel capable of penetrating any holes which might be present in the walls or ceiling of the fire compartment. In general, this leads to a severe degradation of the fire resistance of those building elements and to a greater potential for fire spread. This is particularly applicable to penetrations located high in a compartment where the positive pressure of the fire can force the unburned gases through the penetration.

Penetrations in a floor/ceiling assembly will generally completely negate the barrier qualities of the assembly and will lead to rapid spread of fire to the space above. It will not be a problem, however, if the penetrations are filled with noncombustible materials strongly fastened to the structure. The upper half of walls are similar to the floor/ceiling assembly in that a positive pressure can reasonably be expected in the top of the room, and this will push hot and/or burning gases through the penetration unless it is completely sealed.

Building codes require doors installed in fire resistive walls to resist the passage of fire for a specified period of time. If the door to a fully involved room is not closed, a large plume of fire will typically escape through the doorway, preventing anyone from using the space outside the door while allowing the fire to spread. This is why door closers are so important. Glass in doors and transoms can be expected to rapidly shatter unless constructed of listed or approved wire glass in a steel frame. As with other building elements, penetrations or nonrated portions of doors and transoms must be upgraded or otherwise protected.

Table 5.1 in Section V of the Appendix contains 41 entries of doors mounted in sound tightfitting frames. Part 3.4 below outlines one procedure for evaluating and possibly upgrading existing doors.

3 FINAL EVALUATION AND DESIGN SOLUTION

The final evaluation begins after the rehabilitation project has reached the final design stage and the choice is made to keep certain archaic materials and assemblies in the rehabilitated building. The final evaluation process is essentially a more refined and detailed version of the preliminary evaluation. The specific fire resistance and flame spread requirements are determined for the project. This may involve local building and fire officials reviewing the preliminary evaluation as depicted in Figures 1 and 2 and the field drawings and notes. When necessary, provisions must be made to upgrade existing building elements to provide the required level of fire performance.

There are several approaches to design solutions that can make possible the continued use of archaic materials and assemblies in the rehabilitated structure. The simplest case occurs when the materials and assembly in question are found within the Appendix Tables and the fire performance properties satisfy code requirements. Other approaches must be used, though, if the assembly cannot be found within the Appendix or the fire performance needs to be upgraded. These approaches have been grouped into two classes: experimental and theoretical.


FIGURE 3 MODIFICATION DETAILS

3.1. THE EXPERIMENTAL APPROACH

If a material or assembly found in a building is not listed in the Appendix Tables, there are several other ways to evaluate fire performance. One approach is to conduct the appropriate fire test(s) and thereby determine the fire-related properties directly. There are a number of laboratories in the United States which routinely conduct the various fire tests. A current list can be obtained by writing the Center for Fire Research, National Bureau of Standards, Washington, D.C. 20234.

The contract with any of these testing laboratories should require their observation of specimen preparation as well as the testing of the specimen. A complete description of where and how the specimen was obtained from the building, the transportation of the specimen, and its preparation for testing should be noted in detail so that the building official can be satisfied that the fire test is representative of the actual use.

The test report should describe the fire test procedure and the response of the material or assembly. The laboratory usually submits a cover letter with the report to describe the provisions of the fire test that were satisfied by the material or assembly under investigation. A building official will generally require this cover letter, but will also read the report to confirm that the material or assembly complies with the code requirements. Local code officials should be involved in all phases of the testing process.

The experimental approach can be costly and time consuming because specimens must be taken from the building and transported to the testing laboratory. When a load bearing assembly has continuous reinforcement, the test specimen must be removed from the building, transported, and tested in one piece. However, when the fire performance cannot be determined by other means, there may be no alternative to a full-scale test.

A "nonstandard"small-scale test can be used in special cases. Sample sizes need only be 10-25 square feet (0.93-2.3 m2), while full-scale tests require test samples of either 100 or 180 square feet (9.3 or 17 m2) in size. This small-scale test is best suited for testing nonload-bearing assemblies against thermal transmission only.

1. The "thermal"fire endurance is the time at which the average temperature on the unexposed side of a construction exceeds its initial value by 250° when the other side is exposed to the "standard"fire specified by ASTM Test Method E-19.

3.2 THE THEORETICAL APPROACH

There will be instances when materials and assemblies in a building undergoing rehabilitation cannot be found in the Appendix Tables. Even where test results are available for more or less similar construction, the proper classification may not be immediately apparent. Variations in dimensions, loading conditions, materials, or workmanship may markedly affect the performance of the individual building elements, and the extent of such a possible effect cannot be evaluated from the tables.

Theoretical methods being developed offer an alternative to the full-scale fire tests discussed above. For example, Section 4302(b) of the 1979 edition of the Uniform Building Code specifically allows an engineering design for fire resistance in lieu of conducting full-scale tests. These techniques draw upon computer simulation and mathematical modeling, thermodynamics, heat-flow analysis, and materials science to predict the fire performance of building materials and assemblies.

One theoretical method, known as the "Ten Rules of Fire Endurance Ratings,"was published by T. Z. Harmathy in the May, 1965 edition of Fire Technology. (35) Harmathy's Rules provide a foundation for extending the data within the Appendix Tables to analyze or upgrade current as well as archaic building materials or assemblies.

HARMATHY'S TEN RULES

Rule 1: The "thermal"1fire endurance of a construction consisting of a number of parallel layers is greater than the sum of the "thermal"fire endurances characteristic of the individual layers when exposed separately to fire.

The minimum performance of an untested assembly can be estimated if the fire endurance of the individual components is known. Though the exact rating of the assembly cannot be stated, the endurance of the assembly is greater than the sum of the endurance of the components.

When a building assembly or component is found to be deficient, the fire endurance can be upgraded by providing a protective membrane. This membrane could be a new layer of brick, plaster, or drywall. The fire endurance of this membrane is called the "finish rating."Appendix Tables 1.5.1 and 1.5.2 contain the finish ratings for the most commonly employed materials. (See also the notes to Rule 2).

The test criteria for the finish rating is the same as for the thermal fire endurance of the total assembly: average temperature increases of 250°F (121°C) above ambient or 325°F (163°C) above ambient at any one place with the membrane being exposed to the fire. The temperature is measured at the interface of the assembly and the protective membrane.

Rule 2: The fire endurance of a construction does not decrease with the addition of further layers.

Harmathy notes that this rule is a consequence of the previous rule. Its validity follows from the fact that the additional layers increase both the resistance to heat flow and the heat capacity of the construction. This, in turn, reduces the rate of temperature rise at the unexposed surface.

This rule is not just restricted to "thermal"performance but affects the other fire test criteria: direct flame passage, cotton waste ignition, and load bearing performance. This means that certain restrictions must be imposed on the materials to be added and on the loading conditions. One restriction is that a new layer, if applied to the exposed surface, must not produce additional thermal stresses in the construction, i.e., its thermal expansion characteristics must be similar to those of the adjacent layer. Each new layer must also be capable of contributing enough additional strength to the assembly to sustain the added dead load. If this requirement is not fulfilled, the allowable live load must be reduced by an amount equal to the weight of the new layer. Because of these limitations, this rule should not be applied without careful consideration.

Particular care must be taken if the material added is a good thermal insulator. Properly located, the added insulation could improve the "thermal"performance of the assembly. Improperly located, the insulation could block necessary thermal transmission through the assembly, thereby subjecting the structural elements to greater temperatures for longer periods of time, and could cause premature structural failure of the supporting members.

Rule 3: The fire endurance of constructions containing continuous air gaps or cavities is greater than the fire endurance of similar constructions of the same weight, but containing no air gaps or cavities.

By providing for voids in a construction, additional resistances are produced in the path of heat flow. Numerical heat flow analyses indicate that a 10 to 15 percent increase in fire endurance can be achieved by creating an air gap at the midplane of a brick wall. Since the gross volume is also increased by the presence of voids, the air gaps and cavities have a beneficial effect on stability as well. However, constructions containing combustible materials within an air gap may be regarded as exceptions to this rule because of the possible development of burning in the gap.

There are numerous examples of this rule in the tables. For instance:

Table 1.1.4; Item W-8-M-82: Cored concrete masonry, nominal 8 inch thick wall with one unit in wall thickness and with 62 percent minimum of solid material in each unit, load bearing (80 PSI). Fire endurance: 21/2 hours.

Table 1.1.5; Item W-10-M-11: Cored concrete mansonry, nominal 10 inch thick wall with two units in wall thickness and a 2-inch (51 mm) air space, load bearing (80 PSI). The units are essentially the same as item W-8-M-82. Fire endurance: 31/2 hours.

These walls show 1 hour greater fire endurance by the addition of the 2-inch (51 mm) air space.

Rule 4: The farther an air gap or cavity is located from the exposed surface, the more beneficial is its effect on the fire endurance.

Radiation dominates the heat transfer across an air gap or cavity, and it is markedly higher where the temperature is higher.

The air gap or cavity is thus a poor insulator if it is located in a region which attains high temperatures during fire exposure.

Some of the clay tile designs take advantage of these factors. The double cell design, for instance, ensures that there is a cavity near the unexposed face. Some floor/ceiling assemblies have air gaps or cavities near the top surface and these enhance their thermal performance.

Rule 5: The fire endurance of a construction cannot be increased by increasing the thickness of a completely enclosed air layer.

Harmathy notes that there is evidence that if the thickness of the air layer is larger than about 1/2 inch (12.7 mm), the heat transfer through the air layer depends only on the temperature of the bounding surfaces, and is practically independent of the distance between them. This rule is not applicable if the air layer is not completely enclosed, i.e., if there is a possibility of fresh air entering the gap at an appreciable rate.

Rule 6: Layers of materials of low thermal conductivity are better utilized on that side of the construction on which fire is more likely to happen.

As in Rule 4, the reason lies in the heat transfer process, though the conductivity of the solid is much less dependent on the ambient temperature of the materials. The low thermal conductor creates a substantial temperature differential to be established across its thickness under transient heat flow conditions. This rule may not be applicable to materials undergoing physico-chemical changes accompanied by significant heat absorption or heat evolution.

Rule 7: The fire endurance of asymmetrical constructions depends on the direction of heat flow.

This rule is a consequence of Rules 4 and 6, as well as other factors. This rule is useful in determining the relative protection of corridors and walls enclosing an exit stairway from the surrounding spaces. In addition, there are often situations where a fire is more likely, or potentially more severe, from one side or the other.

Rule 8: The presence of moisture, if it does not result in explosive spalling, increases the fire endurance.

The flow of heat into an assembly is greatly hindered by the release and evaporation of the moisture found within cementitious materials such as gypsum, portland cement, or magnesium oxychloride. Harmathy has shown that the gain in fire endurance may be as high as 8 percent for each percent (by volume) of moisture in the construction. It is the moisture chemically bound within the construction material at the time of manufacture or processing that leads to increased fire endurance. There is no direct relationship between the relative humidity of the air in the pores of the material and the increase in fire endurance.

Under certain conditions there may be explosive spalling of low permeability cementitious materials such as dense concrete. In general, one can assume that extremely old concrete has developed enough minor cracking that this factor should not be significant.

Rule 9: Load-supporting elements, such as beams, girders and joists, yield higher fire endurances when subjected to fire endurance tests as parts of floor, roof, or ceiling assemblies than they would when tested separately.

One of the fire endurance test criteria is the ability of a load-supporting element to carry its design load. The element will be deemed to have failed when the load can no longer be supported.

Failure usually results for two reasons. Some materials, particularly steel and other metals, lose much of their structural strength at elevated temperatures. Physical deflection of the supporting element, due to decreased strength or thermal expansion, causes a redistribution of the load forces and stresses throughout the element. Structural failure often results because the supporting element is not designed to carry the redistributed load.

Roof, floor, and ceiling assemblies have primary (e.g., beams) and secondary (e.g., floor joists) structural members. Since the primary load-supporting elements span the largest distances, their deflection becomes significant at a stage when the strength of the secondary members (including the roof or floor surface) is hardly affected by the heat. As the secondary members follow the deflection of the primary load-supporting element, an increasingly larger portion of the load is transferred to the secondary members.

When load-supporting elements are tested separately, the imposed load is constant and equal to the design load throughout the test. By definition, no distribution of the load is possible because the element is being tested by itself. Without any other structural members to which the load could be transferred, the individual elements cannot yield a higher fire endurance than they do when tested as parts of a floor, roof orceiling assembly.

Rule 10: The load-supporting elements (beams, girders, joists, etc.) of a floor, roof, or ceiling assembly can be replaced by such other load-supporting elements which, when tested separately, yielded fire endurances not less than that of the assembly.

This rule depends on Rule 9 for its validity. A beam or girder, if capable of yielding a certain performance when tested separately, will yield an equally good or better performance when it forms a part of a floor, roof, or ceiling assembly. It must be emphasized that the supporting element of one assembly must not be replaced by the supporting element of another assembly if the performance of this latter element is not known from a separate (beam) test. Because of the load-reducing effect of the secondary elements that results from a test performed on an assembly, the performance of the supsupporting element alone cannot be evaluated by simple arithmetic. This rule also indicates the advantage of performing separate fire tests on primary load-supporting elements.

1. Reproduced from the May 1065 Fire Technology (Vol. 1, No. 2). Copyright National Fire Protection Association, Boston. Reproduced by permission.

ILLUSTRATION OF HARMATHY'S RULES

Harmathy provided one schematic figure which illustrated his Rules.1 It should be useful as a quick reference to assist in applying his Rules.

EXAMPLE APPLICATION OF HARMATHY'S RULES

The following examples, based in whole or in part upon those presented in Harmathy's paper (35), show how the Rules can be applied to practical cases.

Example 1

Problem

A contractor would like to keep a partition which consists of a 33/4 inch (95 mm) thick layer of red clay brick, a 11/4 inch (32 mm) thick layer of plywood, and a 3/8 inch (9.5 mm) thick layer of gypsum wallboard, at a location where 2-hour fire endurance is required. Is this assembly capable of providing a 2-hour protection?

Solution

(1) This partition does not appear in the Appendix Tables.

(2) Bricks of this thickness yield fire endurances of approximately 75 minutes (Table 1.1.2, Item W-4-M- 2).

(3) The 11/4 inch (32 mm) thick plywood has a finish rating of 30 minutes.

(4) The 3/8 inch (9.5 mm) gypsum wallboard has a finish rating of 10 minutes.

(5) Using the recommended values from the tables and applying Rule 1, the fire endurance (FI) of the assembly is larger than the sum of the individual layers, or

FI > 75 + 30 + 10 = 115 minutes

Discussion

This example illustrates how the Appendix Tables can be utilized to determine the fire resistance of assemblies not explicitly listed.

Example 2

Problem

(1) A number of buildings to be rehabilitated have the same type of roof slab which is supported with different structural elements.

(2) The designer and contractor would like to determine whether or not this roof slab is capable of yielding a 2-hour fire endurance. According to a rigorous interpretation of ASTM E 119, however, only the roof assembly, including the roof slab as well as the cover and the supporting elements, can be subjected to a fire test. Therefore, a fire endurance classification cannot be issued for the slabs separately.

(3) The designer and contractor believe this slab will yield a 2-hour fire endurance even without the cover, and any beam of at least 2-hour fire endurance will provide satisfactory support. Is it possible to obtain a classification for the slab separately?

Solution

(1) The answer to the question is yes.

(2) According to Rule 10 it is not contrary to common sense to test and classify roofs and supporting elements separately. Furthermore, according to Rule 2, if the roof slabs actually yield a 2-hour fire endurance, the endurance of an assembly, including the slabs, cannot be less than 2 hours.

(3) The recommended procedure would be to review the tables to see if the slab appears as part of any tested roof or floor/ceiling assembly. The supporting system can be regarded as separate from the slab specimen, and the fire endurance of the assembly listed in the table is at least the fire endurance of the slab. There would have to be an adjustment for the weight of the roof cover in the allowable load if the test specimen did not contain a cover.

(4) The supporting structure or element would have to have at least a 2-hour fire endurance when tested separately.

Discussion

If the tables did not include tests on assemblies which contained the slab, one procedure would be to assemble the roof slabs on any convenient supporting system (not regarded as part of the specimen) and to subject them to a load which, besides the usually required superimposed load, includes some allowances for the weight of the cover.

Example 3

Problem

A steel-joisted floor and ceiling assembly is known to have yielded a fire endurance of 1 hour and 35 minutes. At a certain location, a 2-hour endurance is required. What is the most economical way of increasing the fire endurance by at least 25 minutes?


Solution

(1) The most effective technique would be to increase the ceiling plaster thickness. Existing coats of paint would have to be removed and the surface properly prepared before the new plaster could be applied. Other materials (e.g., gypsum wallboard) could also be considered.

(2) There may be other techniques based on other principles, but an examination of the drawings would be necessary.

Discussion

(1) The additional plaster has at least three effects:

a) The layer of plaster is increased and thus there is a gain of fire endurance (Rule 1).

b) There is a gain due to shifting the air gap farther from the exposed surface (Rule 4).

c) There is more moisture in the path of heat flow to the structural elements (Rules 7 and 8).

(2) The increase in fire endurance would be at least as large as that of the finish rating for the added thickness of plaster. The combined effects in (1) above would further increase this by a factor of 2 or more, depending upon the geometry of the assembly.

Example 4

Problem

The fire endurance of item W-10-M-l in Table 1.1.5 is 4 hours. This wall consists of two 33/4 inch (95 mm) thick layers of structural tiles separated by a 2-inch (51 mm) air gap and 3/4 inch (19 mm) portland cement plaster or stucco on both sides. If the actual wall in the building is identical to item W-10-M-1 except that it has a 4-inch (102 mm) air gap, can the fire endurance be estimated at 5 hours?

Solution

The answer to the question is no for the reasons contained in Rule 5.

Example 5

Problem

In order to increase the insulating value of its precast roof slabs, a company has decided to use two layers of different concretes. The lower layer of the slabs, where the strength of the concrete is immaterial (all the tensile load is carried by the steel reinforcement), would be made with a concrete of low strength but good insulating value. The upper layer, where the concrete is supposed to carry the compressive load, would remain the original high strength, high thermal conductivity concrete. How will the fire endurance of the slabs be affected by the change?

Solution

The effect on the thermal fire endurance is beneficial:

(1) The total resistance to heat flow of the new slabs has been increased due to the replacement of a layer of high thermal conductivity by one of low conductivity.

(2) The layer of low conductivity is on the side more likely to be exposed to fire, where it is more effectively utilized according to Rule 6. The layer of low thermal conductivity also provides better protection for the steel reinforcement, thereby extending the time before reaching the temperature at which the creep of steel becomes significant.

1. Cover: the protective layer or membrane of material which slows the flow of heat to the structural elements.

3.3 "THICKNESS DESIGN"STRATEGY

The "thickness design"strategy is based upon Harmathy's Rules 1 and 2. This design approach can be used when the construction materials have been identified and measured, but the specific assembly cannot be located within the tables. The tables should be surveyed again for thinner walls of like material and construction detail that have yielded the desired or greater fire endurance. If such an assembly can be found, then the thicker walls in the building have more than enough fire resistance. The thickness of the walls thus becomes the principal concern.

This approach can also be used for floor/ceiling assemblies, except that the thickness of the cover1 and the slab become the central concern. The fire resistance of the untested assembly will be at least the fire resistance of an assembly listed in the table having a similar design but with less cover and/or thinner slabs. For other structural elements (e.g., beams and columns), the element listed in the table must also be of a similar design but with less cover thickness.

3.4 EVALUATION OF DOORS

A separate section on doors has been included because the process for evaluation presented below differs from those suggested previously for other building elements. The impact of unprotected openings or penetrations in fire resistant assemblies has been detailed in Part 2.3 above. It is sufficient to note here that openings left unprotected will likely lead to failure of the barrier under actual fire conditions.

For other types of building elements (e.g., beams, columns), the Appendix Tables can be used to establish a minimum level of fire performance. The benefit to rehabilitation is that the need for a full-scale fire test is then eliminated. For doors, however, this cannot be done. The data contained in Appendix Table 5.1, Resistance of Doors to Fire Exposure, can only provide guidance as to whether a successful fire test is even feasible.

For example, a door required to have 1 hour fire resistance is noted in the tables as providing only 5 minutes. The likelihood of achieving the required 1 hour, even if the door is upgraded, is remote. The ultimate need for replacement of the doors is reasonably clear, and the expense and time needed for testing can be saved. However, if the performance documented in the table is near or in excess of what is being required, then a fire test should be conducted. The test documentation can then be used as evidence of compliance with the required level of performance.

The table entries cannot be used as the sole proof of performance of the door in question because there are too many unknown variables which could measurably affect fire performance. The wood may have dried over the years; coats of flammable varnish could have been added. Minor deviations in the internal construction of a door can result in significant differences in performance. Methods of securing inserts in panel doors can vary. The major non-destructive method of analysis, an x-ray, often cannot provide the necessary detail. It is for these, and similar reasons, that a fire test is still felt to be necessary.

It is often possible to upgrade the fire performance of an existing door. Sometimes, "as is"and modified doors are evaluated in a single series of tests when failure of the unmodified door is expected. Because doors upgraded after an initial failure must be tested again, there is a potential savings of time and money.

The most common problems encountered are plain glass, panel inserts of insufficient thickness, and improper fit of a door in its frame. The latter problem can be significant because a fire can develop a substantial positive pressure, and the fire will work its way through otherwise innocent-looking gaps between door and frame.

One approach to solving these problems is as follows. The plain glass is replaced with approved or listed wire glass in a steel frame. The panel inserts can be upgraded by adding an additional layer of material. Gypsum wallboard is often used for this purpose. Intumescent paint applied to the edges of the door and frame will expand when exposed to fire, forming an effective seal around the edges. This seal, coupled with the generally even thermal expansion of a wood door in a wood frame, can prevent the passage of flames and other fire gases. Figure 3 below illustrates these solutions.

Because the interior construction of a door cannot be determined by a visual inspection, there is no absolute guarantee that the remaining doors are identical to the one(s) removed from the building and tested. But the same is true for doors constructed today, and reason and judgment must be applied. Doors that appear identical upon visual inspection can be weighed. If the weights are reasonably close, the doors can be assumed to be identical and therefore provide the same level of fire performance. Another approach is to fire test more than one door or to dismantle doors selected at random to see if they had been constructed in the same manner. Original building plans showing door details or other records showing that doors were purchased at one time or obtained from a single supplier can also be evidence of similar construction.

More often though, it is what is visible to the eye that is most significant. The investigator should carefully check the condition and fit of the door and frame, and for frames out of plumb or separating from the wall. Door closers, latches, and hinges must be examined to see that they function properly and are tightly secured. If these are in order and the door and frame have passed a full-scale test, there can be a reasonable basis for allowing the existing doors to remain.

4 SUMMARY

This section summarizes the various approaches and design solutions discussed in the preceding sections of the guideline. The term "structural system"includes: frames, beams, columns, and other structural elements. "Cover"is a protective layer(s) of materials or membrane which slows the flow of heat to the structural elements. It cannot be stressed too strongly that the fire endurance of actual building elements can be greatly reduced or totally negated by removing part of the cover to allow pipes, ducts, or conduits to pass through the element. This must be repaired in the rehabilitation process.

The following approaches shall be considered equivalent.

4.1
The fire resistance of a building element can be established from the Appendix Tables. This is subject to the following limitations:

The building element in the rehabilitated building shall be constructed of the same materials with the same nominal dimensions as stated in the tables.

All penetrations in the building element or its cover for services such as electricity, plumbing, and HVAC shall be packed with noncombustible cementitious materials and so fixed that the packing material will not fall out when it loses its water of hydration.

The effects of age and wear and tear shall be repaired so that the building element is sound and the original thickness of all components, particularly covers and floor slabs, is maintained.

This approach essentially follows the approach taken by model building codes. The assembly must appear in a table either published in or accepted by the code for a given fire resistance rating to be recognized and accepted.

4.2
The fire resistance of a building element which does not explicitly appear in the Appendix Tables can be established if one or more elements of same design but different dimensions have been listed in the tables. For walls, the existing element must be thicker than the one listed. For floor/ceiling assemblies, the assembly listed in the table must have the same or less cover and the same or thinner slab constructed of the same material as the actual floor/ceiling assembly. For other structural elements, the element listed in the table must be of a similar design but with less cover thickness. The fire resistance in all instances shall be the fire resistance recommended in the table. This is subject to the following limitations:

The actual element in the rehabilitated building shall be constructed of the same materials as listed in the table. Only the following dimensions may vary from those specified: for walls, the overall thickness must exceed that specified in the table; for floor/ceiling assemblies, the thickness of the cover and the slab must be greater than, or equal to, that specified in the table; for other structural elements, the thickness of the cover must be greater than that specified in the table.

All penetrations in the building element or its cover for services such as electricity, plumbing, or HVAC shall be packed with noncombustible cementitious materials and so fixed that the packing material will not fall out when it loses its water of hydration.

The effects of age and wear and tear shall be repaired so that the building element is sound and the original thickness of all components, particularly covers and floor slabs, is maintained.

This approach is an application of the "thickness design"concept presented in Part 3.3 of the guideline. There should be many instances when a thicker building element was utilized than the one listed in the Appendix Tables. This guideline recognizes the inherent superiority of a thicker design. Note: "thickness design"for floor/ceiling assemblies and structural elements refers to cover and slab thickness rather than total thickness.

The "thickness design"concept is essentially a special case of Harmathy's Rules (specifically Rules 1 and 2). It should be recognized that the only source of data is the Appendix Tables. If other data are used, it must be in connection with the approach below.

4.3
The fire resistance of building elements can be established by applying Harmathy's Ten Rules of Fire Resistance Ratings as set forth in Part 3.2 of the guideline. This is subject to the following limitations:

The data from the tables can be utilized subject to the limitations in 4.2 above.

Test reports from recognized journals or published papers can be used to support data utilized in applying Harmathy's Rules.

Calculations utilizing recognized and well established computational techniques can be used in applying Harmathy's Rules. These include, but are not limited to, analysis of heat flow, mechanical properties, deflections, and load bearing capacity.

APPENDIX

INTRODUCTION

The fire-resistance tables that follow are a part of Resource A and provide a tabular form of assigning fire-resistance ratings to various archaic building elements and assemblies.

These tables for archaic materials and assemblies do for archaic materials what Tables 721.1(1-3) of the International Building Code® do for more modern building elements and assemblies. The fire resistance tables of Resource A should be used as described in the "Purpose and Procedure" that follows the table of contents for these tables.

RESOURCE A TABLE OF CONTENTS

Purpose and Procedure 175
Section I‒Walls
1.1.1 Masonry 0 in. - 4 in. thick 176
1.1.2 Masonry 4 in. - 6 in. thick 179
1.1.3 Masonry 6 in. - 8 in. thick 186
1.1.4 Masonry 8 in. - 10 in. thick 191
1.1.5 Masonry 10 in. - 12 in. thick 199
1.1.6 Masonry 12 in. - 14 in. thick 203
1.1.7 Masonry 14 in. or more thick 209
1.2.1 Metal Frame 0 in. - 4 in. thick 212
1.2.2 Metal Frame 4 in. - 6 in. thick 216
1.2.3 Metal Frame 6 in. - 8 in. thick 218
1.2.4 Metal Frame 8 in. - 10 in. thick 219
1.3.1 Wood Frame 0 in. - 4 in. thick 220
1.3.2 Wood Frame 4 in. - 6 in. thick 221
1.3.3 Wood Frame 6 in. - 8 in. thick 229
1.4.1 Miscellaneous Materials 0 in. - 4 in. thick 229
1.4.2 Miscellaneous Materials 4 in. - 6 in. thick 230
1.5.1 Finish Ratings‒Inorganic Materials Thickness 231
1.5.2 Finish Ratings‒Organic Materials Thickness 232
Section II‒Columns
2.1.1 Reinforced Concrete Min. Dim. 0 in. - 6 in. 233
2.1.2 Reinforced Concrete Min. Dim. 10 in. - 12 in. 234
2.1.3 Reinforced Concrete Min. Dim. 12 in. - 14 in. 237
2.1.4 Reinforced Concrete Min. Dim. 14 in. - 16 in. 238
2.1.5 Reinforced Concrete Min. Dim. 16 in. - 18 in. 239
2.1.6 Reinforced Concrete Min. Dim. 18 in. - 20 in. 241
2.1.7 Reinforced Concrete Min. Dim. 20 in. - 22 in. 242
2.1.8 Hexagonal Reinforced Concrete Diameter‒12 in. - 14 in. 243
2.1.9 Hexagonal Reinforced Concrete Diameter‒14 in. - 16 in. 244
2.1.10 Hexagonal Reinforced Concrete Diameter‒16 in. - 18 in. 244
2.1.11 Hexagonal Reinforced Concrete Diameter‒20 in. - 22 in. 244
2.2 Round Cast Iron Columns Minimum Dimension 245
2.3 Steel‒Gypsum Encasements Minimum Area of Solid Material 246
2.4 Timber Minimum Dimension 247
2.5.1.1 Steel/Concrete Encasements Minimum Dimension less than 6 in. 247
2.5.1.2 Steel/Concrete Encasements Minimum Dimension 6 in. - 8 in. 248
2.5.1.3 Steel/Concrete Encasements Minimum Dimension 8 in. - 10 in. 249
2.5.1.4 Steel/Concrete Encasements Minimum Dimension 10 in. - 12 in. 251
2.5.1.5 Steel/Concrete Encasements Minimum Dimension 12 in. - 14 in. 255
2.5.1.6 Steel/Concrete Encasements Minimum Dimension 14 in. - 16 in. 257
2.5.1.7 Steel/Concrete Encasements Minimum Dimension 16 in. - 18 in. 259
2.5.2.1 Steel/Brick and Block Encasements Minimum Dimension 10 in. - 12 in. 259
2.5.2.2 Steel/Brick and Block Encasements Minimum Dimension 12 in. - 14 in. 260
2.5.2.3 Steel/Brick and Block Encasements Minimum Dimension 14 in. - 16 in. 260
2.5.3.1 Steel/Plaster Encasements Minimum Dimension 6 in. - 8 in. 261
2.5.3.2 Steel/Plaster Encasements Minimum Dimension 8 in. - 10 in. 261
2.5.4.1 Steel/Miscellaneous Encasements Minimum Dimension 6 in. - 8 in. 261
2.5.4.2 Steel/Miscellaneous Encasements Minimum Dimension 8 in. - 10 in. 262
2.5.4.3 Steel/Miscellaneous Encasements Minimum Dimension 10 in. - 12 in. 262
2.5.4.4 Steel/Miscellaneous Encasements Minimum Dimension 12 in. - 14 in. 262
Section III‒Floor/Ceiling Assemblies
3.1 Reinforced Concrete Assembly thickness 263
3.2 Steel Structural Elements Membrane thickness 269
3.3 Wood Joist Membrane thickness 275
3.4 Hollow Clay Tile with Reinforced Concrete Membrane thickness 279
Section IV‒Beams
4.1.1 Reinforced Concrete Depth‒10 in. - 12 in. 282
4.1.2 Reinforced Concrete Depth‒12 in. - 14 in. 285
4.1.3 Reinforced Concrete Depth‒14 in. - 16 in. 287
4.2.1 Reinforced Concrete/Unprotected Depth‒10 in. - 12 in. 288
4.2.2 Steel/Concrete Protection Depth‒10 in. - 12 in. 288
Section V‒Doors
5.1 Resistance of Doors to Fire Exposure Thickness 289


PURPOSE AND PROCEDURE

The tables and histograms which follow are to be used only within the analytical framework detailed in the main body of this guideline.

Histograms precede any table with 10 or more entries. The use and interpretation of these histograms is explained in Part 2 of the guideline. The tables are in a format similar to that found in the model building codes. The following example, taken from an entry in Table 1.1.2, best explains the table format.

1. Item Code: The item code consists of a four place series in the general form w-x-y-z in which each member of the series denotes the following:

w = Type of building element (e.g., W=Walls; F=Floors, etc.)
x = The building element thickness rounded down to the nearest 1-inch increment (e.g., 45/8 inches is rounded off to 4 inches)
y = The general type of material from which the building element is constructed (e.g., M=Masonry; W=Wood, etc.)
z = The item number of the particular building element in a given table


The item code shown in the example W-4-M-50 denotes the following:

W = Wall, as the building element
4 = Wall thickness in the range of 4 inches (102 mm) to less than 5 inches (127 mm)
M = Masonry construction
50 = The 50th entry in Table 1.1.2


2. The specific name or heading of this column identifies the dimensions which, if varied, has the greatest impact on fire resistance. The critical dimension for walls, the example here, is thickness. It is different for other building elements (e.g., depth for beams; membrane thickness for some floor/ceiling assemblies). The table entry is the named dimension of the building element measured at the time of actual testing to within ±1/8inch (3.2 mm) tolerance. The thickness tabulated includes facings where facings are a part of the wall construction.

3. Construction Details: The construction details provide a brief description of the manner in which the building element was constructed.

4. Performance: This heading is subdivided into two columns. The column labeled "Load" will either list the load that the building element was subjected to during the fire test or it will contain a note number which will list the load and any other significant details. If the building element was not subjected to a load during the test, this column will contain "n/a," which means "not applicable."

The second column under performance is labeled "Time" and denotes the actual fire endurance time observed in the fire test.

5. Reference Number: This heading is subdivided into three columns: Pre-BMS-92; BMS-92; and Post-BMS-92. The table entry under this column is the number in the Bibliography of the original source reference for the test data.

6. Notes: Notes are provided at the end of each table to allow a more detailed explanation of certain aspects of the test. In certain tables the notes given to this column have also been listed under the "Construction Details" and/or "Load" columns.

7. Rec Hours: This column lists the recommended fire endurance rating, in hours, of a building element. In some cases, the recommended fire endurance will be less than that listed under the "Time" column. In no case is the "Rec Hours" greater than given in the "Time" column.

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-4-M-50 45/8 Core: structural clay tile, See notes
12, 16, 21; Facings on unexposed
side only, see note 18
N/A 25 min. 1 3, 4, 24 1/3


SECTION I - WALLS

FIGURE 1.1.1 MASONRY WALLS 0″ TO LESS THAN 4″ THICK


FIRE RESISTANCE RATING (HOURS)

TABLE 1.1.1 MASONRY WALLS 0″ TO LESS THAN 4″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-2-M-1 21/4 Solid partition; 3/4 ″ gypsum plank- 10″ ×1'6″ ; 3/4
plus gypsum plaster each side.
N/A 1 hr.
22 min.
7 1 11/4
W-3-M-2 3″ Concrete block (18″ × 9″ × 3″ ) of fuel ash, portland cement and plasticizer; cement/sand mortar. N/A 2 hrs. 7 2, 3 2
W-2-M-3 2″ Solid gypsum block wall; No facings N/A 1 hr. 1 4 1
W-3-M-4 3″ Solid gypsum blocks, laid in 1:3 sanded gypsum mortar. N/A 1 hr. 1 4 1
W-3-M-5 3″ Magnesium oxysulfate wood fiber blocks;2″ thick,
laid in portland cement-lime mortar; Facings: 1/2
of 1:3 sanded gypsum plaster on both sides.
N/A 1 hr. 1 4 1
W-3-M-6 3″ Magnesium oxysulfate bound wood fiber blocks;3″ thick; laid in portland cement-lime mortar; Facings: 1/2″ of 1:3 sanded gypsum plaster on both sides. N/A 2 hrs. 1 4 2


(continued)

TABLE 1.1.1‒continued MASONRY WALLS 0″ TO LESS THAN 4″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-3-M-7 3″ Clay tile; Ohio fire clay; single cell thick; Face plaster: 5/8″ (both sides) 1:3 sanded gypsum; Design "E," Construction "A." N/A 1 hr.
6 min.
0 2 5, 6, 7,11, 12,39 1
W-3-M-8 3″ Clay tile; Illinois surface clay; single cell thick; Face plaster: 5/8″ (both sides) 1:3 sanded gypsum; Design "A," Construction "E." N/A 1 hr.
1 min
2 5, 8, 9,11, 12,39 1
W-3-M-9 3″ Clay tile; Illinois surface clay; single cell thick;
No face plaster; Design "A," Construction "C."
N/A 25 min. 2 5, 10, 11,12, 39 1/3
W-3-M-10 7/8 8″ × 47/8″ glass blocks; weight 4 lbs. each; portland cement-lime mortar; horizontal mortar joints reinforced with metal lath. N/A 15 min. 1 4 1/4
W-3-M-11 3″ Core: structural clay tile; see Notes 14, 18, 13;
No facings.
N/A 10 min. 1 5, 11, 26 1/6
W-3-M-12 3″ Core: structural clay tile; see Notes 14, 19, 23;
No facings.
N/A 20 min. 1 5, 11, 26 1/3
W-3-M-13 35/8 Core: structural clay tile; see Notes 14, 18, 23; Facings: unexposed side; see Note 20. N/A 20 min. 1 5, 11, 26 1/3
W-3-M-14 35/8 Core: structural clay tile; see Notes 14, 19, 23; Facings: unexposed side only; see Note 20. N/A 20 min. 1 5, 11, 26 1/3
W-3-M-15 35/8 Core: clay structural tile; see Notes 14, 18, 23; Facings: side exposed to fire; see Note 20. N/A 30 min. 1 5, 11, 26 1/2
W-3-M-16 35/8 Core: clay structural tile; see Notes 14, 19, 23; Facings: side exposed to fire; see Note 20. N/A 45 min. 1 5, 11, 26 3/4
W-2-M-17 2″ 2″ thick solid gypsum blocks; see Note 27. N/A 1 hr. 1 27 1
W-3-M-18 3″ Core: 3″ thick gypsum blocks 70% solid; see
Note 2; No facings.
N/A 1 hr. 1 27 1
W-3-M-19 3″ Core: hollow concrete units; see Notes 29, 35,
36, 38; No facings.
N/A 1 hr. 1 27 1
W-3-M-20 3″ Core: hollow concrete units; see Notes 28, 35,
36, 37,38; No facings.
N/A 1 hr. 1 1
W-3-M-21 31/2 Core: hollow concrete units; see Notes 28, 35,
36, 37, 38; Facings: one side; see Note 37.
N/A 11/2 hrs. 1 11/2
W-3-M-22 31/2 Core: hollow concrete units; see Notes 29, 35,
36, 38; Facings: one side, see Note 37.
N/A 11/4 hrs. 1 11/4

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, °C = [(°F) - 32]/1.8.
Notes:
1. Failure mode‒flame thru.
2. Passed 2-hour fire test (Grade "C" fire res. - British).
3. Passed hose stream test.
4. Tested at NBS under ASA Spec. No. A2-1934. As nonload bearing partitions.
5. Tested at NBS under ASA Spec. No. 42-1934 (ASTM C 19-33) except that hose stream testing where carried was run on test specimens exposed for full test duration, not for a reduced period as is contemporarily done.
6. Failure by thermal criteria‒maximum temperature rise 325°F.
7. Hose stream failure.
8. Hose stream‒pass.
9. Specimen removed prior to any failure occurring.
10. Failure mode‒collapse.
11. For clay tile walls, unless the source or density of the clay can be positively identified or determined, it is suggested that the lowest hourly rating for the fire endurance of a clay tile partition of that thickness be followed. Identified sources of clay showing longer fire endurance can lead to longer time recommendations.
12. See appendix for construction and design details for clay tile walls.
13. Load: 80 psi for gross wall area.
14. One cell in wall thickness.
15. Two cells in wall thickness.
16. Double shells plus one cell in wall thickness.
17. One cell in wall thickness, cells filled with broken tile, crushed stone, slag cinders or sand mixed with mortar.
18. Dense hard-burned clay or shale tile.
19. Medium-burned clay tile.
20. Not less than 5/8 inch thickness of 1:3 sanded gypsum plaster.
21. Units of not less than 30 percent solid material.
22. Units of not less than 40 percent solid material.
23. Units of not less than 50 percent solid material.
24. Units of not less than 45 percent solid material.
25. Units of not less than 60 percent solid material.
26. All tiles laid in portland cement-lime mortar.
27. Blocks laid in 1:3 sanded gypsum mortar voids in blocks not to exceed 30 percent.
28. Units of expanded slag or pumice aggregate.
29. Units of crushed limestone, blast furnace, slag, cinders and expanded clay or shale.
30. Units of calcareous sand and gravel. Coarse aggregate, 60 percent or more calcite and dolomite.
31. Units of siliceous sand and gravel. Ninety percent or more quartz, chert or flint.
32. Unit at least 49 percent solid.
33. Unit at least 62 percent solid.
34. Unit at least 65 percent solid.
35. Unit at least 73 percent solid.
36. Ratings based on one unit and one cell in wall thickness.
37. Minimum of 1/2 inch‒1:3 sanded gypsum plaster.
38. Nonload bearing.
39. See Clay Tile Partition Design Construction drawings, below.


FIGURE 1.1.2 MASONRY WALLS 4″ TO LESS THAN 6″ THICK


TABLE 1.1.2 MASONRY WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-4-M-1 4″ Solid 3″ thick, gypsum blocks laid in 1:3 sanded gypsum mortar; Facings:1/2″ of 1:3 sanded gypsum plaster (both sides). N/A 2 hrs. 1 1 2
W-4-M-2 4″ Solid clay or shale brick. N/A 1 hr.
15 min
1 1, 2 11/4
W-4-M-3 4″ Concrete; No facings. N/A 1 hr.
30 min.
1 1 11/2
W-4-M-4 4″ Clay tile; Illinois surface clay; single cell thick; No face plaster; Design "B," Construction "C." N/A 25 min. 2 3-7, 36 1/3
W-4-M-5 4″ Solid sand-lime brick. N/A 1 hr.
45 min.
1 1 13/4
W-4-M-6 4″ Solid wall; 3″ thick block; 1/2″ plaster each side; 173/4″ ×83/4″ × 4″ "Breeze Blocks"; portland cement/sand mortar N/A 1 hr.
52 min.
7 2 13/4
W-4-M-7 4″ Concrete (4020 psi); Reinforcement: vertical 3/8″ ; horizontal 1/4″ ; 6″ × 6″ grid. N/A 2 hrs.
10 min.
7 2 2
W-4-M-8 4″ Concrete wall (4340 psi crush); reinforcement 1/4″ diameter rebar on 8″ centers (vertical and horizontal). N/A 1 hr.
40 min.
7 2 12/3


(continued)

TABLE 1.1.2‒continued MASONRY WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-4-M-9 43/16 43/16″ × 25/8″ cellular fletton brick (1873 psi) with 1/2″ sand mortar; bricks are U-shaped yielding hollow cover (approx. 2″ × 4″ ) in final cross-section configuration. N/A 1 hr.
25 min.
7 2 11/3
W-4-M-10 41/4 41/4″ × 21/2″ fletton (1831 psi) brick in 1/2″ sand mortar. N/A 1 hr.
53 min
7 2 13/4
W-4-M-11 41/4 41/4″ × 21/2″ London stock (683 psi) brick; 1/2″ grout. N/A 1 hr.
52 min.
7 2 13/4
W-4-M-12 41/2 41/4″ × 21/2″ Leicester red, wire-cut brick (4465 psi) in 1/2″ sand mortar. N/A 1 hr.
56 min.
7 6 13/4
W-4-M-13 41/4 41/4″ × 21/2″ stairfoot brick (7527 psi) 1/2″ sand mortar. N/A 1 hr.
37 min.
7 2 11/2
W-4-M-14 41/4 41/4″ × 21/2″ sand-lime brick (2603 psi) 1/2″ sand mortar. N/A 2 hrs.
6 min.
7 2 2
W-4-M-15 41/4 41/4″ × 21/2″ concrete brick (2527 psi) 1/2″ sand mortar. N/A 2 hrs.
10 min.
7 2 2
W-4-M-16 41/2 4″ thick clay tile; Ohio fire clay; single cell thick; No plaster exposed face; 1/2″ 1:2 gypsum back face; Design "F," Construction "S." N/A 31 min. 2 3-6, 36 1/2
W-4-M-17 41/2 4″ thick clay tile; Ohio fire clay; single cell thick; Plaster exposed face; 1/2″ 1:2 sanded gypsum; Back Face:none; Construction "S," Design "F." 80 psi 50 min. 2 3-5, 8, 36 3/4
W-4-M-18 41/2 Core: solid sand-lime brick; 1/2″ sanded gypsum plaster facings on both sides. 80 psi 3 hrs. 1 1, 11 3
W-4-M-19 41/2 Core: solid sand-lime brick; 1/2″ sanded gypsum plaster facings on both sides. 80 psi 2 hrs.
30 min.
1 1, 11 21/2
W-4-M-20 41/2 Core: concrete brick 1/2″ of 1:3 sanded gypsum plaster facings on both sides. 80 psi 2 hrs. 1 1, 11 2
W-4-M-21 41/2 Core: solid clay or shale brick; 1/2″ thick, 1:3 sanded gypsum plaster facings on fire sides. 80 psi 1 hr.
45 min.
1 1, 2, 11 13/4
W-4-M-22 43/4 4″ thick clay tile; Ohio fire clay; single cell thick; cells filled with cement and broken tile concrete; Plaster on exposed face; none on unexposed face; 3/4″ 1:3 sanded gypsum; Design "G," Construction "E." N/A 1 hr.
48 min.
2 2, 3-5, 9, 36 13/4
W-4-M-23 43/4 thick clay tile; Ohio fire clay; single cell thick; cells filled with cement and broken tile concrete; No plaster exposed faced; 3/4″ neat gypsum plaster on unexposed face; Design "G,"″ Construction "E." N/A 2 hrs.
14 min.
2 2, 3-5, 9, 36 2
W-5-M-24 5″ 3″ × 13″ air space; 1″ thick metal reinforced concrete facings on both sides; faces connected with wood splines. 2,250 lbs./ ft. 45 min. 1 1 3/4
W-5-M-25 5″ Core: 3″ thick void filled with "nondulated" mineral wool weighing 10 lbs./ft.3; 1″ thick metal reinforced concrete facings on both sides. 2,250 lbs./ ft. 2 hrs. 1 1 2
W-5-M-26 5″ Core: solid clay or shale brick; 1/2″ thick, 1:3 sanded gypsum plaster facings on both sides 40 psi 2 hrs.
30 min.
1 1, 2, 11 21/2
W-5-M-27 5″ Core: solid 4″ thick gypsum blocks, laid in 1:3 sanded gypsum mortar; 1/2″ of 1:3 sanded gypsum plaster facings on both sides. N/A 3 hrs. 1 1 3


(continued)

TABLE 1.1.2‒continued MASONRY WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-5-M-28 5″ Core: 4″ thick hollow gypsum blocks with 30% voids; blocks laid in 1:3 sanded gypsum mortar; No facings. N/A 4 hrs. 1 1 4
W-5-M-29 5″ Core: concrete brick; 1/2″ of 1:3 sanded gypsum plaster facings on both sides. 160 psi 3 hrs. 1 1 3
W-5-M-30 51/4 4″ thick clay tile; Illinois surface clay; double cell thick; Plaster: 5/8″ sanded gypsum 1:3 both faces; Design "D," Construction "S." N/A 2 hrs.
53 min.
2 2-5, 9,36 23/4
W-5-M-31 51/4 4″ thick clay tile; New Jersey fire clay; double cell thick; Plaster: 5/8″ sanded gypsum 1:3 both faces; Design "D," Construction "S." N/A 1 hr.
52 min.
2 2-5, 9,36 13/4
W-5-M-32 51/4 4″ thick clay tile; New Jersey fire clay; single cell thick; Plaster: 5/8″ sanded gypsum 1:3 both faces; Design "D," Construction "S." N/A 1 hr.
34 min.
2 2 2-5, 9,36 11/2
W-5-M-33 51/4 4″ thick clay tile; New Jersey fire clay; single cell thick; Face plaster: 5/8″ both sides; 1:3 sanded gypsum; Design "B," Construction "S." N/A 50 min. 2 3-5, 8,36 3/4
W-5-M-34 51/4 4″ thick clay tile; Ohio fire clay; single cell thick; Face plaster: 5/8″ both sides; 1:3 sanded gypsum; Design "B," Construction "A." N/A 1 hr.
19 min.
2 2-5, 9,36 11/4
W-5-M-35 51/4 4″ thick clay tile; Illinois surface clay; single cell thick; Face plaster: 5/8″ both sides; 1:3 sanded gypsum; Design "B," Construction "S." N/A 1 hr.
59 min.
2 2-5, 10 36 13/4
W-5-M-36 4″ Core: structural clay tile; see Notes 12, 16, 21; No facings. N/A 15 min. 1 3, 4, 24 1/4
W-4-M-37 4″ Core: structural clay tile; see Notes 12, 17, 21; No facings. N/A 25 min. 1 3, 4, 24 1/3
W-4-M-38 4″ Core: structural clay tile; see Notes 12, 16, 20; No facings. N/A 10 min. 1 3, 4, 24 1/6
W-4-M-39 4″ Core: structural clay tile; see Notes 12, 17, 20; No facings. N/A 20 min. 1 3, 4, 24 1/3
W-4-M-40 4″ Core: structural clay tile; see Notes 13, 16, 23; No facings. N/A 30 min. 1 3, 4, 24 1/2
W-4-M-41 4″ Core: structural clay tile; see Notes 13, 17, 23; No facings. N/A 35 min. 1 3, 4, 24 1/2
W-4-M-42 4″ Core: structural clay tile; see Notes 13, 16, 21; No facings. N/A 25 min. 1 3, 4, 24 1/3
W-4-M-43 4″ Core: structural clay tile; see Notes 13, 17, 21; No facings. N/A 30 min. 1 3, 4, 24 1/2
W-4-M-44 4″ Core: structural clay tile; see Notes 15, 16, 20; No facings N/A 1 hr.
15 min.
1 3, 4, 24 11/4
W-4-M-45 4″ Core: structural clay tile; see Notes 15, 17, 20; No facings. N/A 1 hr.
15 min.
1 3, 4, 24 11/4
W-4-M-46 4″ Core: structural clay tile; see Notes 14, 16, 22; No facings. N/A 20 min. 1 3, 4, 24 1/3
W-4-M-47 4″ Core: structural clay tile; see Notes 14, 17, 22; No facings. N/A 25 min. 1 3, 4, 24 1/3
W-4-M-48 41/4 Core: structural clay tile; see Notes 12, 16, 21; Facings: both sides; see Note 18. N/A 45 min. 1 3, 4, 24 3/4


(continued)

TABLE 1.1.2‒continued MASONRY WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-4-M-49 41/4 Core: structural clay tile; see Notes 12, 17, 21, Facings: both sides; see Note 18. N/A 1 hr. 1 3, 4, 24 1
W-4-M-50 45/8 Core: structural clay tile; see Notes 12, 16, 21;
Facings: unexposed side only; see Note 18.
N/A 25 min. 1 3, 4, 24 1/3
W-4-M-51 45/8 Core: structural clay tile; see Notes 12, 17, 21;
Facings: unexposed side only; see Note 18.
N/A 30 min. 1 3, 4, 24 1/2
W-4-M-52 45/8 Core: structural clay tile; see Notes 12, 16, 21;
Facings: unexposed side only; see Note 18.
N/A 45 min. 1 3, 4, 24 3/4
W-4-M-53 45/8 Core: structural clay tile; see Notes 12, 17, 21;
Facings: fire side only; see Note 18.
N/A 1 hr. 1 3, 4, 24 1
W-4-M-54 45/8 Core: structural clay tile; see Notes 12, 16, 20;
Facings: unexposed side; see Note 18.
N/A 20 min. 1 3, 4, 24 1/3
W-4-M-55 45/8 Core: structural clay tile; see Notes 12, 17, 20;
Facings: exposed side; see Note 18.
N/A 25 min. 1 3, 4, 24 1/3
W-4-M-56 45/8 Core: structural clay tile; see Notes 12, 16, 20;
Facings: fire side only; see Note 18.
N/A 30 min. 1 3, 4, 24 1/2
W-4-M-57 45/8 Core: structural clay tile; see Notes 12, 17, 20;
Facings: fire side only; see Note 18.
N/A 45 min. 1 3, 4, 24 3/4
W-4-M-58 45/8 Core: structural clay tile; see Notes 13, 16, 23;
Facings: unexposed side only; see Note 18.
N/A 40 min. 1 3, 4, 24 2/3
W-4-M-59 45/8 Core: structural clay tile; see Notes 13, 17, 23;
Facings: unexposed side only; see Note 18.
N/A 1 hr. 1 3, 4, 24 1
W-4-M-60 45/8 Core: structural clay tile; see Notes 13, 16, 23;
Facings: fire side only; see Note 18.
N/A 1 hr.
15 min.
1 3, 4, 24 11/4
W-4-M-61 45/8 Core: structural clay tile; see Notes 13, 17, 23;
Facings: fire side only; see Note 18.
N/A 1 hr.
30 min.
1 3, 4, 24 11/2
W-4-M-62 45/8 Core: structural clay tile; see Notes 13, 16, 21;
Facings: unexposed side only; see Note 18.
N/A 35 min. 1 3, 4, 24 1/2
W-4-M-63 45/8 Core: structural clay tile; see Notes 13, 17, 21;
Facings: unexposed face only; see Note 18.
N/A 45 min. 1 3, 4, 24 3/4
W-4-M-64 45/8 Core: structural clay tile; see Notes 13, 16, 23;
Facings: exposed face only; see Note 18.
N/A 1 hr. 1 3, 4, 24 1
W-4-M-65 45/8 Core: structural clay tile; see Notes 13, 17, 21;
Facings: exposed side only; see Note 18.
N/A 1 hr.
15 min.
1 3, 4, 24 11/4
W-4-M-66 45/8 Core: structural clay tile; see Notes 15, 17, 20;
Facings: unexposed side only; see Note 18
N/A 1 hr.
30 min.
1 3, 4, 24 11/2
W-4-M-67 45/8 Core: structural clay tile; see Notes 15, 16, 20;
Facings: exposed side only; see Note 18.
N/A 1 hr.
45 min.
1 3, 4, 24 13/4
W-4-M-68 45/8 Core: structural clay tile; see Notes 15, 17, 20;
Facings: exposed side only; see Note 18.
N/A 1 hr.
45 min.
1 3, 4, 24 13/4
W-4-M-69 45/8 Core: structural clay tile; see Notes 15, 16, 20;
Facings: unexposed side only; see Note 18.
N/A 1 hr.
30 min.
1 3, 4, 24 13/4
W-4-M-70 45/8 Core: structural clay tile; see Notes 14, 16, 22;
Facings: unexposed side only; see Note 18.
N/A 30 min. 1 3, 4, 24 1/2


(continued)

TABLE 1.1.2‒continued MASONRY WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-4-M-71 45/8 Core: structural clay tile; see Notes 14, 17, 22;
Facings: exposed side only; see Note 18.
N/A 35 min. 1 3, 4, 24 1/2
W-4-M-72 45/8 Core: structural clay tile; see Notes 14, 16, 22;
Facings: fire side of wall only; see Note 18.
N/A 45 min. 1 3, 4, 24 3/4
W-4-M-73 45/8 Core: structural clay tile; see Notes 14, 17, 22;
Facings: fire side of wall only; see Note 18.
N/A 1 hr. 1 3, 4, 24 1
W-4-M-74 51/4 Core: structural clay tile; see Notes 12, 16, 21;
Facings: both sides; see Note 18.
N/A 1 hr. 1 3, 4, 24 1
W-5-M-75 51/4 Core: structural clay tile; see Notes 12, 17, 21;
Facings: both sides; see Note 18
N/A 1 hr.
15 min.
1 3, 4, 24 11/4
W-5-M-76 51/4 Core: structural clay tile; see Notes 12, 16, 20;
Facings: both sides; see Note 18.
N/A 45 min. 1 3, 4, 24 3/4
W-5-M-77 51/4 Core: structural clay tile; see Notes 12, 17, 20;
Facings: both sides; see Note 18.
N/A 1 hr. 1 3, 4, 24 1
W-5-M-78 51/4 Core: structural clay tile; see Notes 13, 16, 23;
Facings: both sides of wall; see Note 18.
N/A 1 hr.
30 min.
1 3, 4, 24 11/2
W-5-M-79 51/4 Core: structural clay tile; see Notes 13, 17, 23;
Facings: both sides of wall; see Note 18.
N/A 2 hrs. 1 3, 4, 24 2
W-5-M-80 51/4 Core: structural clay tile; see Notes 13, 16, 21; Facings: both sides of wall; see Note 18. N/A 1 hr.
15 min.
1 3, 4, 24 11/4
W-5-M-81 51/4 Core: structural clay tile; see Notes 13, 16, 21; Facings: both sides of wall; see Note 18. N/A 1 hr.
30 min.
1 3, 4, 24 11/2
W-5-M-82 51/4 Core: structural clay tile; see Notes 15, 16, 20; Facings: both sides; see Note 18. N/A 2 hrs.
30 min.
1 3, 4, 24 21/2
W-5-M-83 51/4 Core: structural clay tile; see Notes 15, 17, 20; Facings: both sides; see Note 18. N/A 2 hrs.
30 min.
1 3, 4, 24 21/2
W-5-M-84 51/4 Core: structural clay tile; see Notes 14, 16, 22; Facings: both sides of wall; see Note 18. N/A 1 hr.
15 min.
1 3, 4, 24 11/4
W-5-M-85 51/4 Core: structural clay tile; see Notes 14, 17, 22; Facings: both sides of wall; see Note 18. N/A 1 hr.
30 min.
1 3, 4, 24 11/2
W-4-M-86 4″ Core: 3″ thick gypsum blocks 70% solid; see
Note 26; Facings: both sides; see Note 25.
N/A 2 hrs. 1 2
W-4-M-87 4″ Core: hollow concrete units; see Notes 27, 34,
35; No facings.
N/A 1 hr.
30 min.
1 11/2
W-4-M-88 4″ Core: hollow concrete units; see Notes 28, 33,
35; No facings.
N/A 1 hr. 1 1
W-4-M-89 4″ Core: hollow concrete units; see Notes 28, 34,
35; Facings: both sides; see Note 25.
N/A 1 hr.
45 min.
1 13/4
W-4-M-90 4″ Core: hollow concrete units; see Notes 27, 34,
35; Facings: both sides; see Note 25.
N/A 2 hrs. 1 2
W-4-M-91 4″ Core: hollow concrete units; see Notes 27, 32,
35; No facings.
N/A 1 hr.
15 min.
1 11/4
W-4-M-92 4″ Core: hollow concrete units; see Notes 28, 34,
35; No facings.
N/A 1 hr.
15 min.
1 11/4
W-4-M-93 4″ Core: hollow concrete units; see Notes 29, 32,
35; No facings.
N/A 20 min. 1 1/3


(continued)

TABLE 1.1.2‒continued MASONRY WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
W-4-M-94 4″ Core: hollow concrete units; see Notes 30, 34, 35; No facings. N/A 15 min. 1 1/4
W-4-M-95 41/2 Core: hollow concrete units; see Notes 27, 34, 35; Facings: one side only; see Note 25. N/A 2 hrs. 1 2
W-4-M-96 41/2 Core: hollow concrete units; see Notes 27, 32, 35; Facings: one side only; see Note 25. N/A 1 hr.
45 min.
1 13/4
W-4-M-97 41/2 Core: hollow concrete units; see Notes 28, 33, 35; Facings: one side; see Note 25. N/A 1 hr.
30 min.
1 11/2
W-4-M-98 41/2 Core: hollow concrete units; see Notes 28, 34, 35; Facings: one side only; see Note 25. N/A 1 hr.
45 min.
1 13/4
W-4-M-99 41/2 Core: hollow concrete units; see Notes 29, 32, 35; Facings: one side; see Note 25. N/A 30 min. 1 1/2
W-4-M-100 41/2 Core: hollow concrete units; see Notes 30, 34, 35; Facings: one side; see Note 25. N/A 20 min. 1 1/3
W-5-M-101 5″ Core: hollow concrete units; see Notes 27, 34, 35; Facings: both sides; see Note 25. N/A 2 hrs.
30 min.
1 21/2
W-5-M-102 5″ Core: hollow concrete units; see Notes 27, 32, 35; Facings: both sides; see Note 25. N/A 2 hrs.
30 min.
1 21/2
W-5-M-103 5″ Core: hollow concrete units; see Notes 28, 33, 35; Facings: both sides; see Note 25. N/A 2 hrs. 1 2
W-5-M-104 5″ Core: hollow concrete units; see Notes 28, 31, 35; Facings: both sides; see Note 25. N/A 2 hrs. 1 2
W-5-M-105 5″ Core: hollow concrete units; see Notes 29, 32, 35; Facings: both sides; see Note 25. N/A 1 hr.
45 min.
1 13/4
W-5-M-106 5″ Core: hollow concrete units; see Notes 30, 34, 35; Facings: both sides; see Note 25. N/A 1 hr. 1 1
W-5-M-107 5″ Core: 5″ thick solid gypsum blocks; see
Note 26; No facings.
N/A 4 hrs. 1 4
W-5-M-108 5″ Core: 4″ thick hollow gypsum blocks; see
Note 26; Facings: both sides; see Note 25.
N/A 3 hrs. 1 3
W-5-M-109 4″ Concrete with 4″ × 4″ No. 6 welded wire mesh at wall center. 100 psi 45 min. 43 2 3/4
W-4-M-110 4″ Concrete with 4″ × 4″ No. 6 welded wire mesh at wall center. N/A 1 hr.
15 min.
43 2 11/4

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Tested as NBS under ASA Spec. No. A 2-1934.
2. Failure mode‒maximum temperature rise.
3. Treated at NBS under ASA Spec. No. 42-1934 (ASTM C 19-53) except that hose stream testing where carried out was run on test specimens exposed for full test duration, not for or reduced period as is contemporarily done.
4. For clay tile walls, unless the source the clay can be positively identified, it is suggested that the most pessimistic hour rating for the fire endurance of a clay tile partition of that thickness to be followed. Identified sources of clay showing longer fire endurance can lead to longer time recommendations.
5. See appendix for construction and design details for clay tile walls.
6. Failure mode‒flame thru or crack formation showing flames.
7. Hole formed at 25 minutes; partition collapsed at 42 minutes or removal from furnace.
8. Failure mode‒collapse.
9. Hose stream pass.
10. Hose stream hole formed in specimen.
11. Load: 80 psi for gross wall cross sectional area.
12. One cell in wall thickness.
13. Two cells in wall thickness.
14. Double cells plus one cell in wall thickness.
15. One cell in wall thickness, cells filled with broken tile, crushed stone, slag, cinders or sand mixed with mortar.
16. Dense hard-burned clay or shale tile.
17. Medium-burned clay tile.
18. Not less than 5/8 inch thickness of 1:3 sanded gypsum plaster.
19. Units of not less than 30 percent solid material.
20. Units of not less than 40 percent solid material.
21. Units of not less than 50 percent solid material.
22. Units of not less than 45 percent solid material.
23. Units of not less than 60 percent solid material.
24. All tiles laid in portland cement-lime mortar.
25. Minimum 1/2 inch‒1:3 sanded gypsum plaster.
26. Laid in 1:3 sanded gypsum mortar. Voids in hollow units not to exceed 30 percent.
27. Units of expanded slag or pumice aggregate.
28. Units of crushed limestone, blast furnace slag, cinders and expanded clay or shale.
29. Units of calcareous sand and gravel. Coarse aggregate, 60 percent or more calcite and dolomite.
30. Units of siliceous sand and gravel. Ninety percent or more quartz, chert or flint.
31. Unit at least 49 percent solid.
32. Unit at least 62 percent solid.
33. Unit at least 65 percent solid.
34. Unit at least 73 percent solid.
35. Ratings based on one unit and one cell in wall thickness.
36. See Clay Tile Partition Design Construction drawings, below.


FIGURE 1.1.3 MASONRY WALLS 6″ TO LESS THAN 8″ THICK

TABLE 1.1.3 MASONRY WALLS 6″ TO LESS THAN 8″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-6-M-1 6″ Core: 5″ thick, solid gypsum blocks laid in 1:3
sanded gypsum mortar; 1/2″ of 1:3 sanded
gypsum plaster facings on both sides.
N/A 6 hrs. 1 6
W-6-M-2 6″ 6″ clay tile; Ohio fire clay; single cell thick; No
plaster; Design "C," Construction "A."
N/A 17 min. 2 1, 3, 4, 6, 55 1/4
W-6-M-3 6″ 6″ clay tile; Illinois surface clay; double cell
thick; No plaster; Design "E," Construction "C."
N/A 45 min. 2 1-4, 7, 55 3/4
W-6-M-4 6″ 6″ clay tile; New Jersey fire clay; double cell
thick; No plaster; Design "E," Construction "S."
N/A 1 hr.
1 min.
2 1-4, 8, 55 1
W-7-M-5 71/4 6″ clay tile; Illinois surface clay; double cell
thick; Plaster: 5/8″ ‒1:3 sanded gypsum both faces; Design "E," Construction "A."
N/A 1 hr.
41 min.
2 1-4, 55 12/3
W-7-M-6 71/4 6″ clay tile; New Jersey fire clay; double cell
thick; Plaster: 5/8″ ‒1:3 sanded gypsum both faces; Design "E," Construction "S."
N/A 2 hrs.
23 min.
2 1-4, 9, 55 21/3
W-7-M-7 71/4 6″ clay tile; Ohio fire clay; single cell
thick; Plaster: 5/8″ sanded gypsum; 1:3 both
faces; Design "C," Construction "A."
N/A 1 hr.
54 min.
2 1-4, 9, 55 23/4
W-7-M-8 71/4 6″ clay tile; Illinois surface clay; single cell
thick; Plaster: 5/8″ sanded gypsum 1:3 both faces;
Design "C," Construction "S."
N/A 2 hrs. 2 1, 3, 4, 9, 10, 55 2
W-7-M-8a 71/4 6″ clay tile; Illinois surface clay; single cell
thick; Plaster: 5/8″ sanded gypsum 1:3 both faces;
Design "C," Construction "E."
N/A 1 hr.
23 min
2 1-4, 9, 10, 55 13/4


(continued)

TABLE 1.1.3‒continued MASONRY WALLS 6″ TO LESS THAN 8″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-6-M-9 6″ Core: structural clay tile; see Notes 12, 16, 20;
No facings.
N/A 20 min. 1 3, 5, 24 1/3
W-6-M-10 6″ Core: structural clay tile; see Notes 12, 17, 20;
No facings.
N/A 25 min. 1 3, 5, 24 1/3
W-6-M-11 6″ Core: structural clay tile; see Notes 12, 16, 19;
No facings.
N/A 15 min. 1 3, 5, 24 1/4
W-6-M-12 6″ Core: structural clay tile; see Notes 12, 17, 19;
No facings.
N/A 20 min. 1 3, 5, 24 1/3
W-6-M-13 6″ Core: structural clay tile; see Notes 13, 16, 22;
No facings.
N/A 45 min. 1 3, 5, 24 3/4
W-6-M-14 6″ Core: structural clay tile; see Notes 13, 17, 22;
No facings.
N/A 1 hr. 1 3, 5, 24 1
W-6-M-15 6″ Core: structural clay tile; see Notes 15, 17, 19;
No facings.
N/A 2 hrs. 1 3, 5, 24 2
W-6-M-16 6″ Core: structural clay tile; see Notes 15, 16, 19;
No facings.
N/A 2 hrs. 1 3, 5, 24 2
W-6-M-17 6″ Cored concrete masonry; see Notes 12, 34, 36, 38, 41;
No facings.
80 psi 3 hrs.
30 min.
1 5, 25 31/2
W-6-M-18 6″ Cored concrete masonry; see Notes 12, 33, 36, 38, 41;
No facings.
80 psi 3 hrs. 1 5, 25 3
W-6-M-19 61/2 Cored concrete masonry; see Notes 12, 34, 36, 38, 41; Facings: side 1; see Note 35. 80 psi 4 hrs. 1 5, 25 4
W-6-M-20 61/2 Cored concrete masonry; see Notes 12, 33, 36, 38, 41; Facings: side 1; see Note 35. 80 psi 4 hrs. 1 5, 25 4
W-6-M-21 6 5/8 Core: structural clay tile; see Notes 12, 16, 20; Facings: unexposed face only; see Note 18. N/A 30 min. 1 3, 5, 24 1/2
W-6-M-22 6 5/8 Core: structural clay tile; see Notes 12, 17, 20; Facings: unexposed face only; see Note 18. N/A 40 min. 1 3, 5, 24 2/3
W-6-M-23 6 5/8 Core: structural clay tile; see Notes 12, 16, 20; Facings: exposed face only; see Note 18. N/A 1 hr. 1 3, 5, 24 1
W-6-M-24 6 5/8 Core: structural clay tile; see Notes 12, 17, 20; Facings: exposed face only; see Note 18. N/A 1 hr.
5 min.
1 3, 5, 24 1
W-6-M-25 6 5/8 Core: structural clay tile; see Notes 12, 16, 19; Facings: unexposed side only; see Note 18. N/A 25 min. 1 3, 5, 24 1/3
W-6-M-26 6 5/8 Core: structural clay tile; see Notes 12, 7, 19; Facings: unexposed face only; see Note 18. N/A 30 min. 1 3, 5, 24 1/2
W-6-M-27 6 5/8 Core: structural clay tile; see Notes 12, 16, 19; Facings: exposed side only; see Note 18. N/A 1 hr. 1 3, 5, 24 1
W-6-M-28 6 5/8 Core: structural clay tile; see Notes 12, 17, 19; Facings: fire side only; see Note 18. N/A 1 hr. 1 3, 5, 24 1
W-6-M-29 6 5/8 Core: structural clay tile; see Notes 13, 16, 22; Facings: unexposed side only; see Note 18. N/A 1 hr. 1 3, 5, 24 1
W-6-M-30 6 5/8 Core: structural clay tile; see Notes 13, 17, 22; Facings: unexposed side only; see Note 18. N/A 1 hr.
15 min.
1 3, 5, 24 11/4
W-6-M-31 6 5/8 Core: structural clay tile; see Notes 13, 16, 22; Facings: fire side only; see Note 18. N/A 1 hr.
15 min.
1 3, 5, 24 11/4
W-6-M-32 6 5/8 Core: structural clay tile; see Notes 13, 17, 22; Facings: fire side only; see Note 18. N/A 1 hr.
30 min.
1 3, 5, 24 11/2


(continued)

TABLE 1.1.3‒continued MASONRY WALLS 6″ TO LESS THAN 8″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-6-M-33 65/8 Core: structural clay tile; see Notes 15, 16, 19;
Facings: unexposed side only; see Note 18.
N/A 2 hrs.
30 min.
1 3, 5, 24 21/2
W-6-M-34 65/8 Core: structural clay tile; see Notes 15, 17, 19;
Facings: unexposed side only; see Note 18.
N/A 2 hrs.
30 min.
1 3, 5, 24 21/2
W-6-M-35 65/8 Core: structural clay tile; see Notes 15, 16, 19;
Facings: fire side only; see Note 18.
N/A 2 hrs.
30 min.
1 3, 5, 24 21/2
W-6-M-36 65/8 Core: structural clay tile; see Notes 15, 17, 19;
Facings: fire side only; see Note 18.
N/A 2 hrs.
30 min.
1 3, 5, 24 21/2
W-6-M-37 7″ Cored concrete masonry; see Notes 12, 34, 36,
38, 41; see Note 35 for facings on both sides.
80 psi 5 hrs. 1 5, 25 5
W-6-M-38 7″ Cored concrete masonry; see Notes 12, 33, 36,
38, 41; see Note 35 for facings.
80 psi 5 hrs. 1 5, 25 5
W-6-M-39 71/4 Core: structural clay tile; see Notes 12, 16, 20;
Facings: both sides; see Note 18.
N/A 1 hr.
15 min.
1 3, 5, 24 11/4
W-6-M-40 71/4 Core: structural clay tile; see Notes 12, 17, 20;
Facings: both sides; see Note 18.
N/A 1 hr.
30 min.
1 3, 5, 24 11/2
W-6-M-41 71/4 Core: structural clay tile; see Notes 12, 16, 19;
Facings: both sides; see Note 18.
N/A 1 hr.
15 min.
1 3, 5, 24 11/4
W-6-M-42 71/4 Core: structural clay tile; see Notes 12, 17, 19;
Facings: both sides; see Note 18.
N/A 1 hr.
30 min.
1 3, 5, 24 11/2
W-7-M-43 71/4 Core: structural clay tile; see Notes 13, 16, 22;
Facings: both sides of wall; see Note 18.
N/A 1 hr.
30 min.
1 3, 5, 24 11/2
W-7-M-44 71/4 Core: structural clay tile; see Notes 13, 17, 22;
Facings: both sides of wall; see Note 18.
N/A 2 hrs. 1 3, 5, 24 11/2
W-7-M-45 71/4 Core: structural clay tile; see Notes 15, 16, 19;
Facings: both sides; see Note 18.
N/A 3 hrs.
30 min.
1 3, 5, 24 31/2
W-7-M-46 71/4 Core: structural clay tile; see Notes 15, 17, 19;
Facings: both sides; see Note 18.
N/A 3 hrs.
30 min.
1 3, 5, 24 31/2
W-6-M-47 6″ Core: 5″ thick solid gypsum blocks; see Note 45;
Facings: both sides; see Note 45.
N/A 6 hrs. 1 6
W-6-M-48 6″ Core: hollow concrete units; see Notes 47, 50, 54;
No facings.
N/A 1 hr.
15 min.
1 11/4
W-6-M-49 6″ Core: hollow concrete units; see Notes 46, 50, 54;
No facings.
N/A 1 hr.
30 min.
1 11/2
W-6-M-50 6″ Core: hollow concrete units; see Notes 46, 41, 54;
No facings.
N/A 2 hrs. 1 2
W-6-M-51 6″ Core: hollow concrete units; see Notes 46, 53, 54;
No facings.
N/A 3 hrs. 1 3
W-6-M-52 6″ Core: hollow concrete units; see Notes 47, 53, 54;
No facings.
N/A 2 hrs.
30 min.
1 21/2
W-6-M-53 6″ Core: hollow concrete units; see Notes 47, 51, 54;
No facings.
N/A 1 hr.
30 min.
1 11/2
W-6-M-54 61/2 Core: hollow concrete units; see Notes 46, 50, 54;
Facings: one side only; see Note 35.
N/A 2 hrs. 1 2
W-6-M-55 61/2 Core: hollow concrete units; see Notes 4, 51, 54;
Facings: one side; see Note 35.
N/A 2 hrs.
30 min.
1 21/2
W-6-M-56 61/2 Core: hollow concrete units; see Notes 46, 53, 54;
Facings: one side; see Note 35.
N/A 4 hrs. 1 4


(continued)

TABLE 1.1.3‒continued MASONRY WALLS 6″ TO LESS THAN 8″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-6-M-57 61/2 Core: hollow concrete units; see Notes 47, 53, 54;
Facings: one side; see Note 35.
N/A 3 hrs. 1 3
W-6-M-58 61/2 Core: hollow concrete units; see Notes 47, 51, 54;
Facings: one side; see Note 35.
N/A 2 hrs. 1 2
W-6-M-59 61/2 Core: hollow concrete units; see Notes 47, 50, 54;
Facings: one side; see Note 35.
N/A 1 hr.
45 min.
1 13/4
W-7-M-60 7″ Core: hollow concrete units; see Notes 46, 53, 54;
Facings: both sides; see Note 35.
N/A 5 hrs. 1 5
W-7-M-61 7″ Core: hollow concrete units; see Notes 46, 51, 54;
Facings: both sides; see Note 35.
N/A 3 hrs.
30 min.
1 31/2
W-7-M-62 7″ Core: hollow concrete units; see Notes 46, 50, 54;
Facings: both sides; see Note 35.
N/A 2 hrs.
30 min.
1 21/2
W-7-M-63 7″ Core: hollow concrete units; see Notes 47, 53, 54;
Facings: both sides; see Note 35.
N/A 4 hrs. 1 4
W-7-M-64 7″ Core: hollow concrete units; see Notes 47, 51, 54;
Facings: both sides; see Note 35.
N/A 2 hrs.
30 min.
1 21/2
W-7-M-65 7″ Core: hollow concrete units; see Notes 47, 50, 54;
Facings: both sides; see Note 35.
N/A 2 hrs. 1 2
W-6-M-66 6″ Concrete wall with 4″ × 4″ No. 6 wire fabric (welded)
near wall center for reinforcement.
N/A 2 hrs.
30 min.
43 2 21/2

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Tested at NBS under ASA Spec. No. 43-1934 (ASTM C 19-53) except that hose stream testing where carried out was run on test specimens exposed for full test duration, not for a reduced period as is contemporarily done.
2. Failure by thermal criteria‒maximum temperature rise.
3. For clay tile walls, unless the source or density of the clay can be positively identified or determined, it is suggested that the lowest hourly rating for the fire endurance of a clay tile partition of that thickness be followed. Identified sources of clay showing longer fire endurance can lead to longer time recommendations.
4. See Note 55 for construction and design details for clay tile walls.
5. Tested at NBS under ASA Spec. No. A2-1934.
6. Failure mode‒collapse.
7. Collapsed on removal from furnace at 1 hour 9 minutes.
8. Hose stream‒failed.
9. Hose stream‒passed.
10. No end point met in test.
11. Wall collapsed at 1 hour 28 minutes.
12. One cell in wall thickness.
13. Two cells in wall thickness.
14. Double shells plus one cell in wall thickness.
15. One cell in wall thickness, cells filled with broken tile, crushed stone, slag, cinders or sand mixed with mortar.
16. Dense hard-burned clay or shale tile.
17. Medium-burned clay tile.
18. Not less than 5/8 inch thickness of 1:3 sanded gypsum plaster.
19. Units of not less than 30 percent solid material.
20. Units of not less than 40 percent solid material.
21. Units of not less than 50 percent solid material.
22. Units of not less than 45 percent solid material.
23. Units of not less than 60 percent solid material.
24. All tiles laid in portland cement-lime mortar.
25. Load: 80 psi for gross cross sectional area of wall.
26. Three cells in wall thickness.
27. Minimum percent of solid material in concrete units = 52.
28. Minimum percent of solid material in concrete units = 54.
29. Minimum percent of solid material in concrete units = 55.
30. Minimum percent of solid material in concrete units = 57.
31. Minimum percent of solid material in concrete units = 62.
32. Minimum percent of solid material in concrete units = 65.
33. Minimum percent of solid material in concrete units = 70.
34. Minimum percent of solid material in concrete units = 76.
35. Not less than 1/2 inch of 1:3 sanded gypsum plaster.
36. Noncombustible or no members framed into wall.
37. Combustible members framed into wall.
38. One unit in wall thickness.
39. Two units in wall thickness.
40. Three units in wall thickness.
41. Concrete units made with expanded slag or pumice aggregates.
42. Concrete units made with expanded burned clay or shale, crushed limestone, air cooled slag or cinders.
43. Concrete units made with calcareous sand and gravel. Coarse aggregate, 60 percent or more calcite and dolomite.
44. Concrete units made with siliceous sand and gravel. Ninety percent or more quartz, chert or flint.
45. Laid in 1:3 sanded gypsum mortar.
46. Units of expanded slag or pumice aggregate.
47. Units of crushed limestone, blast furnace, slag, cinder and expanded clay or shale.
48. Units of calcareous sand and gravel. Coarse aggregate, 60 percent or more calcite and dolomite.
49. Units of siliceous sand and gravel. Ninety percent or more quartz, chert or flint.
50. Unit minimum 49 percent solid.
51. Unit minimum 62 percent solid.
52. Unit minimum 65 percent solid.
53. Unit minimum 73 percent solid.
54. Ratings based on one unit and one cell in wall section.
55. See Clay Tile Partition Design Construction drawings, below.


FIGURE 1.1.4 MASONRY WALLS 8″ TO LESS THAN 10″ THICK

TABLE 1.1.4 MASONRY WALLS 8″ TO LESS THAN 10″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-8-M-1 8″ Core: clay or shale structural tile; Units in wall
thickness: 1; Cells in wall thickness: 2; Minimum
% solids in units: 40.
80 psi 1 hr.
15 min.
1 1, 20 11/4
W-8-M-2 8″ Core: clay or shale structural tile; Units in wall
thickness: 1; Cells in wall thickness: 2; Minimum
% solids in units: 40; No facings; Result for wall
with combustible members framed into interior.
80 psi 45 min. 1 1, 20 3/4
W-8-M-3 8″ Core: clay or shale structural tile; Units in wall thickness: 1; Cells in wall thickness: 2; Minimum
% solids in units: 43.
80 psi 1 hr.
30 min.
1 1, 20 11/2
W-8-M-4 8″ Core: clay or shale structural tile; Units in wall
thickness: 1; Cells in wall thickness: 2; Minimum
% solids in units: 43; No facings; Combustible members framed into wall.
80 psi 45 min. 1 1, 20 3/4
W-8-M-5 8″ Core: clay or shale structural tile; No facings. See
Notes
1 hr.
30 min.
1 1, 2, 5, 10, 18, 20, 21 11/2
W-8-M-6 8″ Core: clay or shale structural tile; No facings. See
Notes
45 min. 1 1, 2, 5, 10,19, 20, 21 3/4


(continued)

TABLE 1.1.4‒continued MASONRY WALLS 8″ TO LESS THAN 10″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-8-M-7 8″ Core: clay or shale structural tile; No facings See
Notes
2 hrs. 1 1, 2, 5, 13, 18, 20, 21 2
W-8-M-8 8″ Core: clay or shale structural tile; No facings. See
Notes
1 hr.
45 min.
1 1, 2, 5, 13, 19, 20, 21 11/4
W-8-M-9 8″ Core: clay or shale structural tile; No facings. See
Notes
1 hr.
15 min.
1 1, 2, 6, 9, 18, 20, 21 13/4
W-8-M-10 8″ Core: clay or shale structural tile; No facings. See
Notes
45 min. 1 1, 2, 6, 9, 19, 20, 21 3/4
W-8-M-11 8″ Core: clay or shale structural tile; No facings. See
Notes
2 hrs. 1 1, 2, 6, 10, 18, 20, 21 2
W-8-M-12 8″ Core: clay or shale structural tile; No facings. See
Notes
45 min. 1 1, 2, 6, 10, 19, 20, 21 3/4
W-8-M-13 8″ Core: clay or shale structural tile; No facings. See
Notes
2 hrs.
30 min.
1 1, 3, 6, 12, 18, 20, 21 21/2
W-8-M-14 8″ Core: clay or shale structural tile; No facings. See
Notes
1 hr. 1 1, 2, 6, 12, 19, 20, 21 1
W-8-M-15 8″ Core: clay or shale structural tile; No facings. See
Notes
3 hrs. 1 1, 2, 6, 16, 18, 20, 21 3
W-8-M-16 8″ Core: clay or shale structural tile; No facings. See
Notes
1 hr.
15 min.
1 1, 2, 6, 16, 19, 20, 21 11/4
W-8-M-17 8″ Cored clay or shale brick; Units in wall thickness:
1; Cells in wall thickness: 1; Minimum % solids:
70; No facings.
See
Notes
2 hrs.
30 min.
1 1, 44 21/2
W-8-M-18 8″ Cored clay or shale brick; Units in wall thickness:
2; Cells in wall thickness: 2; Minimum % solids: 87; No facings.
See
Notes
5 hrs. 1 1, 45 5
W-8-M-19 8″ Core: solid clay or shale brick; No facings. See
Notes
5 hrs. 1 1, 22, 45 5
W-8-M-20 8″ Core: hollow rolok of clay or shale. See
Notes
2 hrs.
30 min.
1 1, 22, 45 21/2
W-8-M-21 8″ Core: hollow rolok bak of clay or shale; No facings. See
Notes
4 hrs. 1 1, 45 4
W-8-M-22 8″ Core: concrete brick; No facings. See
Notes
6 hrs. 1 1, 45 6
W-8-M-23 8″ Core: sand-lime brick; No facings. See
Notes
7 hrs. 1 1, 45 7
W-8-M-24 8″ Core: 4″ , 40% solid clay or shale structural tile; 1 side 4″ brick facing. See Notes 3 hrs.
30 min.
1 1, 20 31/2
W-8-M-25 8″ Concrete wall (3220 psi); Reinforcing vertical rods 1″ from each face and 1″ diameter;
horizontal rods 5/8″ diameter.
22,200 lbs./ft. 6 hrs. 7 6
W-8-M-26 8″ Core: sand-line brick; 1/2″ of 1:3 sanded gypsum plaster facings on one side. See
Notes
9 hrs. 1 1, 45 9
W-8-M-27 81/2 Core: sand-line brick; 1/2″ of 1:3 sanded gypsum plaster facings on one side. See
Notes
8 hrs. 1 1, 45 8
W-8-M-28 81/2 Core: concrete; 1/2″ of 1:3 sanded gypsum plaster facings on one side. See
Notes
7 hrs. 1 1, 45 7


(continued)

TABLE 1.1.4‒continued MASONRY WALLS 8″ TO LESS THAN 10″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-8-M-29 81/2 Core: hollow rolok of clay or shale; 1/2″ of 1:3 sanded gypsum plaster facings on one side. See
Notes
3 hrs. 1 1, 45 3
W-8-M-30 81/2 Core: solid clay or shale brick 1/2″ thick, 1:3 sanded gypsum plaster facings on one side. See
Notes
6 hrs. 1 1, 22, 45, 6
W-8-M-31 81/2 Core: cored clay or shale brick; Units in wall thickness: 1; Cells in wall thickness: 1; Minimum % solids: 70; 1/2″ of 1:3 sanded gypsum plaster facings on both sides. See
Notes
4 hrs. 1 1, 44 4
W-8-M-32 81/2 Core: cored clay or shale brick; Units in wall thickness: 2; Cells in wall thickness: 2; Minimum % solids: 87; 1/2″ of 1:3 sanded gypsum plaster facings on one side. See
Notes
6 hrs. 1 1, 45 6
W-8-M-33 81/2 Core: hollow rolok bak of clay or shale; 1/2″ of 1:3 sanded gypsum plaster facings on one side. See
Notes
5 hrs. 1 1, 45 5
W-8-M-34 85/8 Core: clay or shale structural tile; Units in wall thickness: 1; Cells in wall thickness: 2; Minimum % solids in units: 40; 5/8″ of 1:3 sanded gypsum plaster facings on one side. See
Notes
2 hrs. 1 1, 20 21 2
W-8-M-35 85/8 Core: clay or shale structural tile; Units in wall thickness: 1; Cells in wall thickness: 2; Minimum % solids in units: 40; Exposed face: 5/8″ of 1:3 sanded gypsum plaster. See
Notes
1 hr.
30 min.
1 1, 20, 21 11/2
W-8-M-36 85/8 Core: clay or shale structural tile; Units in wall thickness: 1; Cells in wall thickness: 2; Minimum % solids in units: 43; 5/8″ of 1:3 sanded gypsum plaster facings on one side. See
Notes
2 hrs. 1, 20,21 2
W-8-M-37 85/8 Core: clay or shale structural tile; Units in wall thickness: 1; Cells in wall thickness: 2; Minimum % solids in units: 43; 5/8″ of 1:3 sanded gypsum plaster of the exposed face only. See
Notes
1 hr.
30 min.
1 1, 20, 21 11/2
W-8-M-38 85/8 Core: clay or shale structural tile; Facings: side 1; see Note 17. See
Notes
2 hrs. 1 1, 2, 5, 10, 18, 20, 21 2
W-8-M-39 85/8 Core: clay or shale structural tile; Facings:
exposed side only; see Note 17.
See
Notes
1 hr.
30 min.
1 1, 2, 5, 10, 19, 20, 21 11/2
W-8-M-40 85/8 Core: clay or shale structural tile; Facings:
exposed side only; see Note 17.
See
Notes
3 hrs. 1 1, 2, 5, 13, 18, 20, 21 3
W-8-M-41 85/8 Core: clay or shale structural tile; Facings:
exposed side only; see Note 17.
See
Notes
2 hrs. 1 1, 2, 5, 13, 19, 20, 21 2
W-8-M-42 85/8 Core: clay or shale structural tile; Facings: side 1; see Note 17. See Notes 2 hrs.
30 min.
1 1, 2, 9, 18, 20, 21 21/2
W-8-M-43 85/8 Core: clay or shale structural tile; Facings:
exposed side only; see Note 17.
See Notes 1 hr.
30 min.
1 1, 2, 6, 9, 19, 20, 21 11/2


(continued)

TABLE 1.1.4‒continued MASONRY WALLS 8″ TO LESS THAN 10″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-8-M-44 85/8 Core: clay or shale structural tile; Facings: side 1,
see Note 17; side 2, none.
See
Notes
3 hrs. 1 1, 2,
10, 18,
20, 21
3
W-8-M-45 85/8 Core: clay or shale structural tile; Facings: fire side
only; see Note 17.
See
Notes
1 hr.
30 min.
1 1, 2, 6,
10, 19,
20, 21
11/2
W-8-M-46 85/8 Core: clay or shale structural tile; Facings: side 1,
see Note 17; side 2, none.
See
Notes
3 hrs.
30 min.
1 1, 2, 6,
12, 18,
20, 21
31/2
W-8-M-47 85/8 Core: clay or shale structural tile; Facings: exposed
side only; see Note 17.
See
Notes
1 hr.
45 min.
1 1, 2, 6,
12, 19,
20, 21
13/4
W-8-M-48 85/8 Core: clay or shale structural tile; Facings: side 1,
see Note 17; side 2, none.
See
Notes
4 hrs. 1 1, 2, 6,
16, 18,
20, 21
4
W-8-M-49 85/8 Core: clay or shale structural tile; Facings: fire side
only; see Note 17.
See
Notes
2 hrs. 1 1, 2, 6,
16, 19,
20, 21
2
W-8-M-50 85/8 Core: 4″ , 40% solid clay or shale clay structural tile;
4″ brick plus 5/8″ of 1:3 sanded gypsum plaster
facings on one side.
See
Notes
4 hrs. 1 1, 20 4
W-8-M-51 83/4 83/4″ × 21/2″ and 4″ × 21/2″ cellular fletton (1873 psi)
single and triple cell hollow brick set in 1/2″ sand
mortar in alternate courses.
3.6 tons/ft. 6 hrs. 7 23, 29 6
W-8-M-52 83/4 83/4″ thick cement brick (2527 psi) with P.C. and sand
mortar.
3.6 tons/ft. 6 hrs. 7 23, 24 6
W-8-M-53 83/4 83/4″ × 21/2″ fletton brick (1831 psi) in 1/2″ sand
mortar.
3.6 tons/ft. 6 hrs. 7 23, 24 6
W-8-M-54 83/4 83/4″ × 21/2″ London stock brick (683 psi) in 1/2″ P.C.-
sand mortar.
7.2 tons/ft. 6 hrs. 7 23, 24 6
W-9-M-55 9″ 9″ × 21/2″ Leicester red wire-cut brick (4465 psi) in
1/2″ P.C.- sand mortar.
6.0 tons/ft. 6 hrs. 7 23, 24 6
W-9-M-56 9″ 9″ × 3″ sand-lime brick (2603 psi) in 1/2″ P.C.- sand
mortar.
3.6 tons/ft. 6 hrs. 7 23, 24 6
W-9-M-57 9″ 2 layers 27/8″ fletton brick (1910 psi) with 31/4″ air
space; Cement and sand mortar.
1.5 tons/ft. 32 min. 7 23, 25 1/3
W-9-M-58 9″ 9″ × 3″ stairfoot brick (7527 psi) in 1/2″ sand-cement
mortar.
7.2 tons/ft. 6 hrs. 7 23, 24 6
W-9-M-59 9″ Core: solid clay or shale brick; 1/2″ thick; 1:3 sanded
gypsum plaster facings on both sides.
See
Notes
7 hrs. 1 1, 22, 45 7
W-9-M-60 9″ Core: concrete brick; 1/2″ of 1:3 sanded
gypsum plaster facings on both sides.
See
Notes
8 hrs. 1 1, 45 8
W-9-M-61 9″ Core: hollow rolok of clay or shale; 1/2″ of 1:3 sanded
gypsum plaster facings on both sides.
See
Notes
4 hrs. 1 1, 45 4
W-9-M-62 9″ Cored clay or shale brick; Units in wall thickness: 1;
Cells in wall thickness: 1; Minimum % solids: 70; 1/2
of 1:3 sanded gypsum plaster facings on one side.
See
Notes
3 hrs. 1 1, 44 3


(continued)

TABLE 1.1.4‒continued MASONRY WALLS 8″ TO LESS THAN 10″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-9-M-63 9″ Cored clay or shale brick; Units in wall thickness:
2; Cells in wall thickness: 2; Minimum % solids:
87; 1/2″ of 1:3 sanded gypsum plaster facings on
both sides.
See
Notes
7 hrs. 1 1, 45 7
W-9-M-64 9-10″ Core: cavity wall of clay or shale brick;
No facings.
See
Notes
5 hrs. 1 1, 45 5
W-9-M-65 9-10″ Core: cavity construction of clay or shale brick;
1/2″ of 1:3 sanded gypsum plaster facings on one
side.
See
Notes
6 hrs. 1 1, 45 6
W-9-M-66 9-10″ Core: cavity construction of clay or shale brick;
1/2″ of 1:3 sanded gypsum plaster facings on both
sides.
See
Notes
7 hrs. 1 1, 45 7
W-9-M-67 91/4 Core: clay or shale structural tile; Units in wall
thickness: 1; Cells in wall thickness: 2; Minimum
% solids in units: 40; 5/8″ of 1:3 sanded gypsum
plaster facings on both sides.
See
Notes
3 hrs. 1 1, 20,
21
3
W-9-M-68 91/4 Core: clay or shale structural tile; Units in wall
thickness: 1; Cells in wall thickness: 2; Minimum
% solids in units: 43; 5/8″ of 1:3 sanded gypsum
plaster facings on both sides.
See
Notes
3 hrs. 1 1, 20,
21
3
W-9-M-69 91/4 Core: clay or shale structural tile; Facings: sides 1
and 2; see Note 17.
See
Notes
3 hrs. 1 1, 2, 5,
10, 18,
20, 21
3
W-9-M-70 91/4 Core: clay or shale structural tile; Facings: sides 1
and 2; see Note 17.
See
Notes
4 hrs. 1 1, 2, 5,
13, 18,
20, 21
4
W-9-M-71 91/4 Core: clay or shale structural tile; Facings: sides 1
and 2; see Note 17.
See
Notes
3 hrs.
30 min.
1 1, 2, 6,
9, 18,
20, 21
31/2
W-9-M-72 91/4 Core: clay or shale structural tile; Facings: sides 1
and 2; see Note 17.
See
Notes
4 hrs. 1 1, 2, 6,
10, 18,
20, 21
4
W-9-M-73 91/4 Core: clay or shale structural tile; Facings: sides 1
and 2; see Note 17.
See
Notes
4 hrs. 1 1, 2, 6,
12, 18,
20, 21
4
W-9-M-74 91/4 Core: clay or shale structural tile; Facings: sides 1
and 2; see Note 17.
See
Notes
5 hrs. 1 1, 2, 6,
16, 18,
20, 21
5
W-9-M-75 8″ Cored concrete masonry; see Notes 2, 19, 26, 34,
40; No facings.
80 psi 1 hr.
30 min.
1 1, 20 11/2
W-8-M-76 8″ Cored concrete masonry; see Notes 2, 18, 26, 34,
40; No facings
80 psi 4 hrs. 1 1, 20 4
W-8-M-77 8″ Cored concrete masonry; see Notes 2, 19, 26, 31,
40; No facings.
80 psi 1 hr.
15 min.
1 1, 20 11/4
W-8-M-78 8″ Cored concrete masonry; see Notes 2, 18, 26, 31,
40; No facings.
80 psi 3 hrs. 1 1, 20 3
W-8-M-79 8″ Cored concrete masonry; see Notes 2, 19, 26, 36,
42; No facings.
80 psi 1 hr.
30 min.
1 1, 20 11/2


(continued)

TABLE 1.1.4‒continued MASONRY WALLS 8″ TO LESS THAN 10″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-8-M-80 8″ Cored concrete masonry; see Notes 2, 18, 26, 36, 41;
No facings.
80 psi 3 hrs. 1 1, 20 3
W-8-M-81 8″ Cored concrete masonry; see Notes 2, 19, 26, 34, 41;
No facings.
80 psi 1 hr. 1 1, 20 1
W-8-M-82 8″ Cored concrete masonry; see Notes 2, 18, 26, 34, 41;
No facings.
80 psi 2 hrs.
30 min.
1 1, 20 21/2
W-8-M-83 8″ Cored concrete masonry; see Notes 2, 19, 26, 29, 41;
No facings.
80 psi 45 min. 1 1, 20 3/4
W-8-M-84 8″ Cored concrete masonry; see Notes 2, 18, 26, 29, 41;
No facings.
80 psi 2 hrs. 1 1, 20 2
W-8-M-85 81/2 Cored concrete masonry; see Notes 3, 18, 26, 34, 41;
Facings: 21/4″ brick.
80 psi 4 hrs. 1 1, 20 4
W-8-M-86 8″ Cored concrete masonry; see Notes 3, 18, 26, 34, 41;
Facings: 33/4″ brick face.
80 psi 5 hrs. 1 1, 20 5
W-8-M-87 8″ Cored concrete masonry; see Notes 2, 19, 26, 30, 43;
No facings.
80 psi 12 min. 1 1, 20 1/5
W-8-M-88 8″ Cored concrete masonry; see Notes 2, 18, 26, 30, 43;
No facings.
80 psi 12 min. 1 1, 20 1/5
W-8-M-89 81/2 Cored concrete masonry; see Notes 2, 19, 26, 34, 40;
Facings: fire side only; see Note 38.
80 psi 2 hrs. 1 1, 20 2
W-8-M-90 81/2 Cored concrete masonry; see Notes 2, 18, 26, 34, 40;
Facings: side 1; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-8-M-91 81/2 Cored concrete masonry; see Notes 2, 19, 26, 31, 40;
Facings: fire side only; see Note 38.
80 psi 1 hr.
45 min.
1 1, 20 13/4
W-8-M-92 81/2 Cored concrete masonry; see Notes 2, 18, 26, 31, 40;
Facings: one side; see Note 38.
80 psi 4 hrs. 1 1, 20 4
W-8-M-93 81/2 Cored concrete masonry; see Notes 2, 19, 26, 36, 41;
Facings: fire side only; see Note 38.
80 psi 2 hrs. 1 1, 20 2
W-8-M-94 81/2 Cored concrete masonry; see Notes 2, 18, 26, 36, 41;
Facings: fire side only; see Note 38.
80 psi 4 hrs. 1 1, 20 4
W-8-M-95 81/2 Cored concrete masonry; see Notes 2, 19, 26, 34, 41;
Facings: fire side only; see Note 38.
80 psi 1 hr.
30 min.
1 1, 20 11/2
W-8-M-96 81/2 Cored concrete masonry; see Notes 2, 18, 26, 34, 41;
Facings: one side; see Note 38.
80 psi 3 hrs. 1, 20 3
W-8-M-97 81/2 Cored concrete masonry; see Notes 2, 19, 26, 29, 41;
Facings: fire side only; see Note 38.
80 psi 1 hr.
30 min.
1 1, 20 11/2
W-8-M-98 81/2 Cored concrete masonry; see Notes 2, 18, 26, 29, 41;
Facings: one side; see Note 38.
80 psi 2 hrs.
30 min.
1 1, 20 21/2
W-8-M-99 81/2 Cored concrete masonry; see Notes 3, 19, 23, 27, 41;
No facings.
80 psi 1 hr.
15 min.
1 1, 20 11/4


(continued)

TABLE 1.1.4‒continued MASONRY WALLS 8″ TO LESS THAN 10″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-8-M-100 81/2 Cored concrete masonry; see Notes 3, 18, 23, 27, 41;
No facings.
80 psi 3 hrs.
30 min.
1 1, 20 31/2
W-8-M-101 81/2 Cored concrete masonry; see Notes 3, 18, 26, 34, 41;
Facings: 33/4″ brick face; one side only; see Note 38.
80 psi 6 hrs. 1 1, 20 6
W-8-M-102 81/2 Cored concrete masonry; see Notes 2, 19, 26, 30, 43;
Facings: fire side only; see Note 38.
80 psi 30 min. 1 1, 20 1/2
W-8-M-103 81/2 Cored concrete masonry; see Notes 2, 18, 26, 30, 43;
Facings: one side only; see Note 38.
80 psi 12 min. 1 1, 20 1/5
W-8-M-104 9″ Cored concrete masonry; see Notes 2, 18, 26, 34, 40;
Facings: both sides; see Note 38.
80 psi 6 hrs. 1 1, 20 6
W-8-M-105 9″ Cored concrete masonry; see Notes 2, 18, 26, 31, 40;
Facings: both sides; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-8-M-106 9″ Cored concrete masonry; see Notes 2, 18, 26, 36, 41;
Facings: both sides of wall; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-8-M-107 9″ Cored concrete masonry; see Notes 2, 18, 26, 34, 41;
Facings: both sides; see Note 38.
80 psi 4 hrs. 1 1, 20 4
W-8-M-108 9″ Cored concrete masonry; see Notes 2, 18, 26, 29, 41;
Facings: both sides; see Note 38.
80 psi 3 hrs.
30 min.
1 1, 20 31/2
W-8-M-109 9″ Cored concrete masonry; see Notes 3, 19, 23, 27, 40;
Facings: fire side only; see Note 38.
80 psi 1 hr.
45 min.
1 1, 20 13/4
W-8-M-110 9″ Cored concrete masonry; see Notes 3, 18, 23, 27, 41;
Facings: one side only; see Note 38.
80 psi 4 hrs. 1 1, 20 4
W-8-M-111 9″ Cored concrete masonry; see Notes 3, 18, 26, 34, 41;
21/4″ brick face on one side only; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-8-M-112 9″ Cored concrete masonry; see Notes 2, 18, 26, 30, 43;
Facings: both sides; see Note 38.
80 psi 30 min. 1 1, 20 1/2
W-9-M-113 91/2 Cored concrete masonry; see Notes 3, 18, 23, 27, 41;
Facings: both sides; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-8-M-114 8″ 200 psi 5 hrs. 43 22 5

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Tested at NBS under ASA Spec. No. 43-1934 (ASTM C 19-53).
2. One unit in wall thickness.
3. Two units in wall thickness.
4. Two or three units in wall thickness.
5. Two cells in wall thickness.
6. Three or four cells in wall thickness.
7. Four or five cells in wall thickness.
8. Five or six cells in wall thickness.
9. Minimum percent of solid materials in units = 40%.
10. Minimum percent of solid materials in units = 43%.
11. Minimum percent of solid materials in units = 46%.
12. Minimum percent of solid materials in units = 48%.
13. Minimum percent of solid materials in units = 49%.
14. inimum percent of solid materials in units = 45%.
15. Minimum percent of solid materials in units = 51%.
16. Minimum percent of solid materials in units = 53%.
17. Not less than 5/8 inch thickness of 1:3 sanded gypsum plaster.
18. Noncombustible or no members framed into wall.
19. Combustible members framed into wall.
20. Load: 80 psi for gross cross-sectional area of wall.
21. Portland cement-lime mortar.
22. Failure mode thermal.
23. British test.
24. Passed all criteria.
25. Failed by sudden collapse with no preceding signs of impending failure.
26. One cell in wall thickness.
27. Two cells in wall thickness.
28. Three cells in wall thickness.
29. Minimum percent of solid material in concrete units = 52.
30. Minimum percent of solid material in concrete units = 54.
31. Minimum percent of solid material in concrete units = 55.
32. Minimum percent of solid material in concrete units = 57.
33. Minimum percent of solid material in concrete units = 60.
34. Minimum percent of solid material in concrete units = 62.
35. Minimum percent of solid material in concrete units = 65.
36. Minimum percent of solid material in concrete units = 70.
37. Minimum percent of solid material in concrete units = 76.
38. Not less than 1/2inch of 1:3 sanded gypsum plaster.
39. Three units in wall thickness.
40. Concrete units made with expanded slag or pumice aggregates.
41. Concrete units made with expanded burned clay or shale, crushed limestone, air cooled slag or cinders.
42. Concrete units made with calcareous sand and gravel. Coarse aggregate, 60 percent or more calcite and dolomite.
43. Concrete units made with siliceous sand and gravel. Ninety percent or more quartz, chert and dolomite.
44. Load: 120 psi for gross cross-sectional area of wall.
45. Load: 160 psi for gross cross-sectional area of wall.


FIGURE 1.1.5 MASONRY WALLS 10″ TO LESS THAN 12″ THICK



TABLE 1.1.5 MASONRY WALLS 10″ TO LESS THAN 12″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-10-M-1 10″ Core: two 33/4″ , 40% solid clay or shale structural tiles
with 2″ air space between; Facings:3/4″ portland
cement plaster on stucco on both sides.
80 psi 4 hrs. 1 1, 20 4
W-10-M-2 10″ Core: cored concrete masonry, 2″ air cavity; see Notes
3, 19, 27, 34, 40; No facings.
80 psi 1 hr.
30 min.
1 1, 20 11/2
W-10-M-3 10″ Cored concrete masonry; see Notes 3, 18, 27, 34, 40;
No facings.
80 psi 4 hrs. 1 1, 20 4
W-10-M-4 10″ Cored concrete masonry; see Notes 2, 19, 26, 34, 40;
No facings.
80 psi 2 hrs. 1 1, 20 2
W-10-M-5 10″ Cored concrete masonry; see Notes 2, 18, 26, 33, 40;
No facings.
80 psi 5 hrs. 1 1, 20 5
W-10-M-6 10″ Cored concrete masonry; see Notes 2, 19, 26, 33, 41;
No facings.
80 psi 1 hr.
30 min.
1 1, 20 11/2
W-10-M-7 10″ Cored concrete masonry; see Notes 2, 18, 26, 33, 41;
No facings.
80 psi 4 hrs. 1 1, 20 4
W-10-M-8 10″ Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 19, 27, 34, 42; No facings.
80 psi 1 hr.
15 min.
1 1, 20 11/4


(continued)

TABLE 1.1.5‒continued MASONRY WALLS 10″ TO LESS THAN 12″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-10-M-9 10″ Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 18, 27, 34, 42; No facings.
80 psi 1 hr.
15 min.
1 1, 20 11/4
W-10-M-10 10″ Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 19, 27, 34, 41; No facings.
80 psi 1 hr.
15 min.
1 1, 20 11/4
W-10-M-11 10″ Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 18, 27, 34, 41; No facings.
80 psi 3 hrs.
30 min.
1 1, 20 31/2
W-10-M-12 10″ 9″ thick concrete block (113/4″ × 9″ × 41/4″ ) with two 2″
thick voids included; 3/8″ P.C. plaster 1/8″ neat gypsum.
N/A 1 hr.
53 min.
7 23, 44 13/4
W-10-M-13 10″ Holly clay tile block wall - 81/2″ block with two 3″
voids in each 81/2″ section;3/4″ gypsum plaster - each
face.
N/A 2 hrs.
42 min.
7 23, 25 21/2
W-10-M-14 10″ Two layers 41/4″ brick with 11/2″ air space; No ties sand
cement mortar.(Fletton brick - 1910 psi).
N/A 6 hrs. 7 23, 24 6
W-10-M-15 10″ Two layers 41/4″ thick Fletton brick (1910 psi);
11/2″ air space; Ties: 18″ o.c. vertical; 3' o.c. horizontal.
N/A 6 hrs. 7 23, 24 6
W-10-M-16 101/2 Cored concrete masonry; 2″ air cavity; see Notes 3, 19,
27, 34, 40; Facings: fire side only; see Note 38.
80 psi 2 hrs. 1 1, 20 2
W-10-M-17 101/2 Cored concrete masonry; see Notes 3, 18, 27, 34, 40;
Facings: side 1 only; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-10-M-18 101/2 Cored concrete masonry; see Notes 2, 19, 26, 33, 40;
Facings: fire side only; see Note 38.
80 psi 2 hrs.
30 min.
1 1, 20 21/2
W-10-M-19 101/2 Cored concrete masonry; see Notes 2, 18, 26, 33, 40;
Facings: one side; see Note 38.
80 psi 6 hrs. 1 1, 20 6
W-10-M-20 101/2 Cored concrete masonry; see Notes 2, 19, 26, 33, 41;
Facings: fire side of wall only; see Note 38.
80 psi 2 hrs. 1 1, 20 2
W-10-M-21 101/2 Cored concrete masonry; see Notes 2, 18, 26, 33, 41;
Facings: one side only; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-10-M-22 101/2 Cored concrete masonry (cavity type 2″ air space); see
Notes 3,19, 27, 34, 42; Facings: fire side only; see Note 38.
80 psi 1 hr.
45 min.
1 1, 20 13/4
W-10-M-23 101/2 Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 18, 27, 34, 42; Facings: one side only; see Note 38.
80 psi 1 hr.
15 min.
1 1, 20 11/4
W-10-M-24 101/2 Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 19, 27, 34, 41; Facings: fire side only; see Note 38.
80 psi 2 hrs. 1 1, 20 2
W-10-M-25 101/2 Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 18, 27, 34, 41; Facings: one side only; see Note 38.
80 psi 4 hrs. 1 1, 20 4
W-10-M-26 105/8 Core: 8″ , 40% solid tile plus 2″ furring tile; 5/8″ sanded
gypsum plaster between tile types; Facings: both sides
3/4″ portland cement plaster or stucco.
80 psi 5 hrs. 1 1, 20 5


(continued)

TABLE 1.1.5‒continued MASONRY WALLS 10″ TO LESS THAN 12″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-
BMS-92
W-10-M-27 105/8 Core: 8″ , 40% solid tile plus 2″ furring tile; 5/8″ sanded
gypsum plaster between tile types; Facings: one side
3/4″ portland cement plaster or stucco.
80 psi 3 hrs. 30 min. 1 1, 20 31/2
W-11-M-28 11″ Cored concrete masonry; see Notes 3, 18, 27, 34, 40;
Facings: both sides; see Note 38.
80 psi 6 hrs. 1 1, 20 6
W-11-M-29 11″ Cored concrete masonry; see Notes 2, 18, 26, 33, 40;
Facings: both sides; see Note 38.
80 psi 7 hrs. 1 1, 20 7
W-11-M-30 11″ Cored concrete masonry; see Notes 2, 18, 26, 33, 41;
Facings: both sides of wall; see Note 38.
80 psi 6 hrs. 1 1, 20 6
W-11-M-31 11″ Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 18, 27, 34, 42; Facings: both sides; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-11-M-32 11″ Cored concrete masonry (cavity type 2″ air space); see
Notes 3, 18, 27, 34, 41; Facings: both sides; see Note 38.
80 psi 5 hrs. 1 1, 20 5
W-11-M-33 11″ Two layers brick (41/2″ Fletton, 2,428 psi) 2″ air space;
galvanized ties; 18″ o.c.- horizontal; 3' o.c.- vertical.
3 tons/ft. 6 hrs. 7 23, 24 6

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Tested at NBS - ASA Spec. No. A2-1934.
2. One unit in wall thickness.
3. Two units in wall thickness.
4. Two or three units in wall thickness.
5. Two cells in wall thickness.
6. Three or four cells in wall thickness.
7. Four or five cells in wall thickness.
8. Five or six cells in wall thickness.
9. Minimum percent of solid materials in units = 40%.
10. Minimum percent of solid materials in units = 43%.
11. Minimum percent of solid materials in units = 46%.
12. Minimum percent of solid materials in units = 48%.
13. Minimum percent of solid materials in units = 49%.
14. Minimum percent of solid materials in units = 45%.
15. Minimum percent of solid materials in units = 51%.
16. Minimum percent of solid materials in units = 53%.
17. Not less than 5/8 inch thickness of 1:3 sanded gypsum plaster.
18. Noncombustible or no members framed into wall.
19. Combustible members framed into wall.
20. Load: 80 psi for gross cross sectional area of wall.
21. Portland cement-lime mortar.
22. Failure mode‒thermal.
23. British test.
24. Passed all criteria.
25. Failed by sudden collapse with no preceding signs of impending failure.
26. One cell in wall thickness.
27. Two cells in wall thickness.
28. Three cells in wall thickness.
29. Minimum percent of solid material in concrete units = 52%.
30. Minimum percent of solid material in concrete units = 54%.
31. Minimum percent of solid material in concrete units = 55%.
32. Minimum percent of solid material in concrete units = 57%.
33. Minimum percent of solid material in concrete units = 60%.
34. Minimum percent of solid material in concrete units = 62%.
35. Minimum percent of solid material in concrete units = 65%.
36. Minimum percent of solid material in concrete units = 70%.
37. Minimum percent of solid material in concrete units = 76%.
38. Not less than 1/2 inch of 1:3 sanded gypsum plaster.
39. Three units in wall thickness.
40. Concrete units made with expanded slag or pumice aggregates.
41. Concrete units made with expanded burned clay or shale, crushed limestone, air cooled slag or cinders.
42. Concrete units made with calcareous sand and gravel. Coarse aggregate, 60 percent or more calcite and dolomite.


FIGURE 1.1.6 MASONRY WALLS 12″ TO LESS THAN 14″ THICK



TABLE 1.1.6 MASONRY WALLS 12″ TO LESS THAN 14″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST- BMS-92
W-12-M-1 12″ Core: solid clay or shale brick;
No facings.
N/A 12 hrs. 1 1 12
W-12-M-2 12″ Core: solid clay or shale brick;
No facings.
160 psi 10 hrs. 1 1, 44 10
W-12-M-3 12″ Core: hollow rolok of clay or shale;
No facings.
160 psi 5 hrs. 1 1, 44 5
W-12-M-4 12″ Core: hollow rolok bak of clay or shale;
No facings.
160 psi 10 hrs. 1 1, 44 10
W-12-M-5 12″ Core: concrete brick; No facings. 160 psi 13 hrs. 1 1, 44 13
W-12-M-6 12″ Core: sand-lime brick; No facings. N/A 14 hrs. 1 1 14
W-12-M-7 12″ Core: sand-lime brick; No facings. 160 psi 10 hrs. 1 1, 44 10
W-12-M-8 12″ Cored clay or shale brick; Units in wall
thickness: 1; Cells in wall thickness: 2;
Minimum % solids: 70; No facings.
120 psi 5 hrs. 1 1, 45 5
W-12-M-9 12″ Cored clay or shale brick; Units in wall
thickness: 3; Cells in wall thickness: 3;
Minimum % solids: 87; No facings.
160 psi 10 hrs. 1 1, 44 10
W-12-M-10 12″ Cored clay or shale brick; Units in wall
thickness: 3; Cells in wall thickness: 3;
Minimum % solids: 87; No facings.
N/A 11 hrs. 1 1 11


(continued)

TABLE 1.1.6‒continued MASONRY WALLS 12″ TO LESS THAN 14″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-
92
BMS-92 POST-
BMS-92
W-12-M-11 12″ Core: clay or shale structural tile; see
Notes 2, 6, 9, 18; No facings.
80 psi 2 hrs. 1 1, 20 21/2
W-12-M-12 12″ Core: clay or shale structural tile; see
Notes 2, 4, 9, 19; No facings.
80 psi 2 hrs. 1 1, 20 2
W-12-M-13 12″ Core: clay or shale structural tile; see
Notes 2, 6, 14, 19; No facings.
80 psi 3 hrs. 1 1, 20 3
W-12-M-14 12″ Core: clay or shale structural tile; see
Notes 2, 6, 14, 18; No facings.
80 psi 2 hrs.
30 min.
1 1, 20 21/2
W-12-M-15 12″ Core: clay or shale structural tile; see
Notes 2, 4, 13, 18; No facings.
80 psi 3 hrs.
30 min.
1 1, 20 31/2
W-12-M-16 12″ Core: clay or shale structural tile; see
Notes 2, 4, 13, 19; No facings.
80 psi 3 hrs. 1 1, 20 3
W-12-M-17 12″ Core: clay or shale structural tile; see
Notes 3, 6, 9, 18; No facings.
80 psi 3 hrs.
30 min.
1 1, 20 31/2
W-12-M-18 12″ Core: clay or shale structural tile; see
Notes 3, 6, 9, 19; No facings.
80 psi 2 hrs. 1 1, 20 2
W-12-M-19 12″ Core: clay or shale structural tile; see
Notes 3, 6, 14, 18; No facings.
80 psi 4 hrs. 1 1, 20 4
W-12-M-20 12″ Core: clay or shale structural tile; see
Notes 3, 6, 14, 19; No facings.
80 psi 2 hrs.
30 min.
1 1, 20 21/2
W-12-M-21 12″ Core: clay or shale structural tile; see
Notes 3, 6, 16, 18; No facings.
80 psi 5 hrs. 1 1, 20 5
W-12-M-22 12″ Core: clay or shale structural tile; see
Notes 3, 6, 16, 19; No facings.
80 psi 3 hrs. 1 1, 20 3
W-12-M-23 12″ Core: 8″ , 70% solid clay or shale struc
tural tile; 4″ brick facings on one side.
80 psi 10 hrs. 1 1, 20 10
W-12-M-24 12″ Core: 8″ , 70% solid clay or shale struc
tural tile; 4″ brick facings on one side.
N/A 11 hrs. 1 1 11
W-12-M-25 12″ Core: 8″ , 40% solid clay or shale struc
tural tile; 4″ brick facings on one side.
80 psi 6 hrs. 1 1, 20 6
W-12-M-26 12″ Cored concrete masonry; see Notes 1, 9,
15, 16, 20; No facings.
80 psi 2 hrs. 1 1, 20 2
W-12-M-27 12″ Cored concrete masonry; see Notes 2,
18, 26, 34, 41; No facings.
80 psi 5 hrs. 1 1, 20 5
W-12-M-28 12″ Cored concrete masonry; see Notes 2,
19, 26, 31, 41; No facings.
80 psi 1 hr.
30 min.
1 1, 20 11/2
W-12-M-29 12″ Cored concrete masonry; see Notes 2,
18, 26, 31, 41; No facings.
80 psi 4 hrs. 1 1, 20 4
W-12-M-30 12″ Cored concrete masonry; see Notes 3,
19, 27, 31, 43; No facings.
80 psi 2 hrs. 1 1, 20 2
W-12-M-31 12″ Cored concrete masonry; see Notes 3,
18, 27, 31, 43; No facings.
80 psi 5 hrs. 1 1, 20 5
W-12-M-32 12″ Cored concrete masonry; see Notes 2,
19, 26, 32, 43; No facings.
80 psi 25 min. 1 1, 20 1/3
W-12-M-33 12″ Cored concrete masonry; see Notes 2,
18, 26, 32, 43; No facings.
80 psi 25 min. 1 1, 20 1/3


(continued)

TABLE 1.1.6‒continued MASONRY WALLS 12″ TO LESS THAN 14″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST- BMS-92
W-12-M-34 121/2 Core: solid clay or shale brick; 1/2″ of 1:3
sanded gypsum plaster facings on one side.
160
psi
10 hrs. 1 1, 44 10
W-12-M-35 121/2 Core: solid clay or shale brick; 1/2″ of 1:3
sanded gypsum plaster facings on one side.
N/A 13 hrs. 1 1 13
W-12-M-36 121/2 Core: hollow rolok of clay or shale; 1/2″ of
1:3 sanded gypsum plaster facings on one side.
160
psi
6 hrs. 1 1, 44 6
W-12-M-37 121/2 Core: hollow rolok bak of clay or shale; 1/2
of 1:3 sanded gypsum plaster facings on one side.
160
psi
10 hrs. 1 1, 44 10
W-12-M-38 121/2 Core: concrete; 1/2″ of 1:3 sanded gypsum
plaster facings on one side.
160
psi
14 hrs. 1 1, 44 14
W-12-M-39 121/2 Core: sand-lime brick; 1/2″ of 1:3 sanded
gypsum plaster facings on one side.
160
psi
10 hrs. 1 1, 44 10
W-12-M-40 121/2 Core: sand-lime brick; 1/2″ of 1:3 sanded
gypsum plaster facings on one side.
N/A 15 hrs. 1 1 15
W-12-M-41 121/2 Cored clay or shale brick; Units in wall
thickness: 1; Cells in wall thickness: 2;
Minimum % solids: 70; 1/2″ of 1:3 sanded
gypsum plaster facings on one side.
120
psi
6 hrs. 1 1, 45 6
W-12-M-42 121/2 Cored clay or shale brick; Units in wall
thickness: 3; Cells in wall thickness: 3;
Minimum % solids: 87; 1/2″ of 1:3 sanded
gypsum plaster facings on one side.
160
psi
10 hrs. 1 1, 44 10
W-12-M-43 121/2 Cored clay or shale brick; Units in wall
thickness: 3; Cells in wall thickness: 3;
Minimum % solids: 87; 1/2″ of 1:3 sanded
gypsum plaster facings on one side.
N/A 12 hrs. 1 1 12
W-12-M-44 121/2 Cored concrete masonry; see Notes 2, 19,
26, 34, 41; Facings: fire side only; see Note
38.
80 psi 2 hrs.
30 min.
1 1, 20 21/2
W-12-M-45 121/2 Cored concrete masonry; see Notes 2, 18,
26, 34, 39, 41; Facings: one side only; see
Note 38.
80 psi 6 hrs. 1 1, 20 6
W-12-M-46 121/2 Cored concrete masonry; see Notes 2, 19,
26, 31, 41; Facings: fire side only; see
Note 38.
80 psi 2 hrs. 1 1, 20 2
W-12-M-47 121/2 Cored concrete masonry; see Notes 2, 18,
26, 31, 41; Facings: one side of wall only; see
Note 38.
80 psi 5 hrs. 1 1, 20 5
W-12-M-48 121/2 Cored concrete masonry; see Notes 3, 19,
27, 31, 43; Facings: fire side only; see
Note 38.
80 psi 2 hrs.
30 min.
1 1, 20 21/2
W-12-M-49 121/2 Cored concrete masonry; see Notes 3, 18,
27, 31, 43; Facings: one side only; see
Note 38.
80 psi 6 hrs. 1 1, 20 6
W-12-M-50 121/2 Cored concrete masonry; see Notes 2, 19,
26, 32, 43; Facings: fire side only; see
Note 38.
80 psi 2 hrs.
30 min.
1 1, 20 21/2


(continued)

TABLE 1.1.6‒continued MASONRY WALLS 12″ TO LESS THAN 14″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-12-M-51 121/2 Cored concrete masonry; see Notes 2, 18,
26, 32, 43; Facings: one side only; see Note
38.
80 psi 25 min. 1 1, 20 1/3
W-12-M-52 125/8 Clay or shale structural tile; see Notes 2, 6,
9, 18; Facings: side 1, see Note 17; side 2,
none.
80 psi 3 hrs.
30 min.
1 1, 20 31/2
W-12-M-53 125/8 Clay or shale structural tile; see Notes 2, 6,
9, 19; Facings: fire side only; see Note 17.
80 psi 3 hrs. 1 1, 20 3
W-12-M-54 125/8 Clay or shale structural tile; see Notes 2, 6,
14, 19; Facings: side 1, see Note 17; side 2,
none.
80 psi 4 hrs. 1 1, 20 4
W-12-M-55 125/8 Clay or shale structural tile; see Notes 2, 6,
14, 18; Facings: exposed side only; see Note
17.
80 psi 3 hrs.
30 min.
1 1, 20 31/2
W-12-M-56 125/8 Clay or shale structural tile; see Notes 2, 4,
13, 18; Facings: side 1, see Note 17; side 2,
none.
80 psi 4 hrs. 1 1, 20 4
W-12-M-57 125/8 Clay or shale structural tile; see Notes 1, 4,
13, 19; Facings: fire side only; see Note 17.
80 psi 4 hrs. 1 1, 20 4
W-12-M-58 125/8 Clay or shale structural tile; see Notes 3, 6,
9, 18; Facings: side 1, see Note 17; side 2,
none.
80 psi 4 hrs. 1 1, 20 4
W-12-M-59 125/8 Clay or shale structural tile; see Notes 3, 6,
9, 19; Facings: fire side only; see Note 17.
80 psi 3 hrs. 1 1, 20 3
W-12-M-60 125/8 Clay or shale structural tile; see Notes 3, 6,
14, 18; Facings: side 1, see Note 17; side 2,
none.
80 psi 5 hrs. 1 1, 20 5
W-12-M-61 125/8 Clay or shale structural tile; see Notes 3, 6,
14, 19; Facings: fire side only; see Note 17.
80 psi 3 hrs.
30 min.
1 1, 20 31/2
W-12-M-62 125/8 Clay or shale structural tile; see Notes 3, 6,
16, 18; Facings: side 1, see Note 17; side 2,
none.
80 psi 6 hrs. 1 1, 20 6
W-12-M-63 125/8 Clay or shale structural tile; see Notes 3, 6,
16, 19; Facings: fire side only; see Note 17.
80 psi 4 hrs. 1 1, 20 4
W-12-M-64 125/8 Core: 8″ , 40% solid clay or shale structural
tile; Facings: 4″ brick plus 5/8″ of 1:3 sanded
gypsum plaster on one side.
80 psi 7 hrs. 1 1, 20 7
W-13-M-65 13″ Core: solid clay or shale brick; 1/2″ of 1:3
sanded gypsum plaster facings on both sides.
160 psi 12 hrs. 1 1, 44 12
W-13-M-66 13″ Core: solid clay or shale brick; 1/2″ of 1:3
sanded gypsum plaster facings on both sides.
N/A 15 hrs. 1 1, 20 15
W-13-M-67 13″ Core: solid clay or shale brick; 1/2″ of 1:3
sanded gypsum plaster facings on both sides.
N/A 15 hrs. 1 1 15
W-13-M-68 13″ Core: hollow rolok of clay or shale; 1/2″ of 1:3
sanded gypsum plaster facings on both sides.
80 psi 7 hrs. 1 1, 20 7
W-13-M-69 13″ Core: concrete brick; 1/2″ of
1:3 sanded gypsum plaster facings on both
sides.
160 psi 16 hrs. 1 1, 44 16


(continued)

TABLE 1.1.6‒continued MASONRY WALLS 12″ TO LESS THAN 14″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-13-M-70 13″ Core: sand-lime brick; 1/2″ of 1:3 sanded gypsum plaster facings on both sides. 160 psi 12 hrs. 1 1, 44 12
W-13-M-71 13″ Core: sand-lime brick; 1/2″ of 1:3 sanded gypsum plaster facings on both sides. N/A 17 hrs. 1 1 17
W-13-M-72 13″ Cored clay or shale brick; Units in wall thickness: 1; Cells in wall thickness: 2;
Minimum % solids: 70; 1/2″ of 1:3 sanded gypsum plaster facings on both sides.
120 psi 7 hrs. 1 1, 45 7
W-13-M-73 13″ Cored clay or shale brick; Units in wall thickness: 3; Cells in wall thickness: 3;
Minimum % solids: 87; 1/2″ of 1:3 sanded gypsum plaster facings on both sides.
160 psi 12 hrs. 1 1, 44 12
W-13-M-74 13″ Cored clay or shale brick; Units in wall thickness: 3; Cells in wall thickness: 2;
Minimum % solids: 87; 1/2″ of 1:3 sanded gypsum plaster facings on both sides.
N/A 14 hrs. 1 1 14
W-13-M-75 13″ Cored concrete masonry; see Notes 18, 23, 28, 39, 41; No facings. 80 psi 7 hrs. 1 1, 20 7
W-13-M-76 13″ Cored concrete masonry; see Notes 19, 23, 28, 39, 41; No facings. 80 psi 4 hrs. 1 1, 20 4
W-13-M-77 13″ Cored concrete masonry; see Notes 3, 18, 27, 31, 43; Facings: both sides; see Note 38. 80 psi 6 hrs. 1 1, 20 6
W-13-M-78 13″ Cored concrete masonry; see Notes 2, 18, 26, 31, 41; Facings: both sides; see Note 38. 80 psi 6 hrs. 1 1, 20 6
W-13-M-79 13″ Cored concrete masonry; see Notes 2, 18, 26, 34, 41; Facings: both sides of wall; see Note 38. 80 psi 7 hrs. 1 1, 20 7
W-13-M-80 131/4 Core: clay or shale structural tile; see Notes 2, 6, 9, 18; Facings: both sides; see Note 17. 80 psi 4 hrs. 1 1, 20 4
W-13-M-82 131/4 Core: clay or shale structural tile; see Notes 2, 4, 13, 18; Facings: both sides; see Note 17. 80 psi 6 hrs. 1 1, 20 6
W-13-M-83 131/4 Core: clay or shale structural tile; see Notes 3, 6, 9, 18; Facings: both sides; see Note 17. 80 psi 6 hrs. 1 1, 20 6
W-13-M-84 131/4 Core: clay or shale structural tile; see Notes 3, 6, 14, 18; Facings: both sides; see Note 17. 80 psi 6 hrs. 1 1, 20 6
W-13-M-85 131/4 Core: clay or shale structural tile; see Notes 3, 6, 16, 18; Facings: both sides; see Note 17. 80 psi 7 hrs. 1 1, 20 7


(continued)

TABLE 1.1.6‒continued MASONRY WALLS 12″ TO LESS THAN 14″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-13-M-86 131/2 Cored concrete masonry; see Notes 18, 23, 28, 39, 41; Facings: one side only; see Note 38. 80 psi 8 hrs. 1 1, 20 8
W-13-M-87 131/2 Cored concrete masonry; see Notes 19, 23, 28, 39, 41; Facings: fire side only; see Note 38. 80 psi 5 hrs. 1 1, 20 5

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Tested at NBS - ASA Spec. No. A2-1934.
2. One unit in wall thickness.
3. Two units in wall thickness.
4. Two or three units in wall thickness.
5. Two cells in wall thickness.
6. Three or four cells in wall thickness.
7. Four or five cells in wall thickness.
8. Five or six cells in wall thickness.
9. Minimum percent of solid materials in units = 40%.
10. Minimum percent of solid materials in units = 43%.
11. Minimum percent of solid materials in units = 46%.
12. Minimum percent of solid materials in units = 48%.
13. Minimum percent of solid materials in units = 49%.
14. Minimum percent of solid materials in units = 45%.
15. Minimum percent of solid materials in units = 51%.
16. Minimum percent of solid materials in units = 53%.
17. Not less than 5/8 inch thickness of 1:3 sanded gypsum plaster.
18. Noncombustible or no members framed into wall.
19. Combustible members framed into wall.
20. Load: 80 psi for gross area.
21. Portland cement-lime mortar.
22. Failure mode-thermal.
23. British test.
24. Passed all criteria.
25. Failed by sudden collapse with no preceding signs of impending failure.
26. One cell in wall thickness.
27. Two cells in wall thickness.
28. Three cells in wall thickness.
29. Minimum percent of solid material in concrete units = 52%.
30. Minimum percent of solid material in concrete units = 54%.
31. Minimum percent of solid material in concrete units = 55%.
32. Minimum percent of solid material in concrete units = 57%.
33. Minimum percent of solid material in concrete units = 60%.
34. Minimum percent of solid material in concrete units = 62%.
35. Minimum percent of solid material in concrete units = 65%.
36. Minimum percent of solid material in concrete units = 70%.
37. Minimum percent of solid material in concrete units = 76%.
38. Not less than 1/2 inch of 1:3 sanded gypsum plaster.
39. Three units in wall thickness.
40. Concrete units made with expanded slag or pumice aggregates.
41. Concrete units made with expanded burned clay or shale, crushed limestone, air cooled slag or cinders.
42. Concrete units made with calcareous sand and gravel. Coarse aggregate, 60 percent or more calcite and dolomite.
43. Concrete units made with siliceous sand and gravel. Ninety percent or more quartz, chert or flint.
44. Load: 160 psi of gross wall cross sectional area.
45. Load: 120 psi of gross wall cross sectional area.


FIGURE 1.1.7 MASONRY WALLS 14″ OR MORE THICK



TABLE 1.1.7 MASONRY WALLS 14″ OR MORE THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-BMS-92
W-14-M-1 14″ Core: cored masonry; see Notes 18, 28, 33, 39, 41; Facings: both sides; see Note 38. 80 psi 9 hrs. 1 1, 20 9
W-16-M-2 16″ Core: clay or shale structural tile; see Notes 4, 7, 9, 19; No facings. 80 psi 5 hrs. 1 1, 20 5
W-16-M-3 16″ Core: clay or shale structural tile; see Notes 4, 7, 9, 19; No facings. 80 psi 4 hrs. 1 1, 20 4
W-16-M-4 16″ Core: clay or shale structural tile; see Notes 4, 7, 10, 18; No facings. 80 psi 6 hrs. 1 1, 20 6
W-16-M-5 16″ Core: clay or shale structural tile; see Notes 4, 7, 10, 19; No facings. 80 psi 4 hrs. 1 1, 20 4
W-16-M-6 16″ Core: clay or shale structural tile; see Notes 4, 7, 11, 18; No facings. 80 psi 7 hrs. 1 1, 20 7
W-16-M-7 16″ Core: clay or shale structural tile; see Notes 4, 7, 11, 19; No facings. 80 psi 5 hrs. 1 1, 20 5
W-16-M-8 16″ Core: clay or shale structural tile; see Notes 4, 8, 13, 18; No facings. 80 psi 8 hrs. 1 1, 20 8
W-16-M-9 16″ Core: clay or shale structural tile; see Notes 4, 8, 13, 19; No facings. 80 psi 5 hrs. 1 1, 20 5


(continued)

TABLE 1.1.7‒continued MASONRY WALLS 14″ OR MORE THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-
BMS-92
BMS-92 POST-BMS-92
W-16-M-10 16″ Core: clay or shale structural tile; see Notes 4, 8, 15, 18; No facings. 80 psi 9 hrs. 1 1, 20 9
W-16-M-11 16″ Core: clay or shale structural tile; see Notes 3, 7, 14, 18; No facings. 80 psi 6 hrs. 1 1, 20 6
W-16-M-12 16″ Core: clay or shale structural tile; see Notes 4, 8, 16, 18; No facings. 80 psi 10 hrs. 1 1, 20 10
W-16-M-13 16″ Core: clay or shale structural tile; see Notes 4, 6, 16, 19; No facings. 80 psi 7 hrs. 1 1, 20 7
W-16-M-14 165/8 Core: clay or shale structural tile; see Notes 4, 7, 9, 18; Facings: side 1, see Note 17; side 2, none. 80 psi 6 hrs. 1 1, 20 6
W-16-M-15 165/8 Core: clay or shale structural tile; see Notes 4, 7, 9, 19; Facings: fire side only; see Note 17. 80 psi 5 hrs. 1 1, 20 5
W-16-M-16 165/8 Core: clay or shale structural tile; see Notes 4, 7, 10, 18; Facings: side 1, see Note 17; side 2, none. 80 psi 7 hrs. 1 1, 20 7
W-16-M-17 165/8 Core: clay or shale structural tile; see Notes 4, 7, 10, 19; Facings: fire side only; see Note 17. 80 psi 5 hrs. 1 1, 20 5
W-16-M-18 165/8 Core: clay or shale structural tile; see Notes 4, 7, 11, 18; Facings: side 1, see Note 17; side 2, none. 80 psi 5 hrs. 1 1, 20 5
W-16-M-19 165/8 Core: clay or shale structural tile; see Notes 4, 7, 11, 19; Facings: fire side only; see Note 17. 80 psi 6 hrs. 1 1, 20 6
W-16-M-20 165/8 Core: clay or shale structural tile; see Notes 4, 8, 13, 18; Facings: sides 1 and 2; see Note 17. 80 psi 11 hrs. 1 1, 20 11
W-16-M-21 165/8 Core: clay or shale structural tile; see Notes 4, 8, 13 18; Facings: side 1, see Note 17; side 2, none. 80 psi 9 hrs. 1 1, 20 9
W-16-M-22 165/8 Core: clay or shale structural tile; see Notes 4, 8, 13, 19; Facings: fire side only; see Note 17. 80 psi 6 hrs. 1 1, 20 6
W-16-M-23 165/8 Core: clay or shale structural tile; see Notes 4, 8, 15, 18; Facings: side 1, see Note 17; side 2, none. 80 psi 10 hrs. 1 1, 20 10
W-16-M-24 165/8 Core: clay or shale structural tile; see Notes 4, 8, 15, 19; Facings: fire side only; see Note 17. 80 psi 7 hrs. 1 1, 20 7
W-16-M-25 165/8 Core: clay or shale structural tile; see Notes 4, 6, 16, 18; Facings: side 1, see Note 17; side 2, none. 80 psi 11 hrs. 1 1, 20 11
W-16-M-26 165/8 Core: clay or shale structural tile; see Notes 4, 6, 16, 19; Facings: fire side only; see Note 17. 80 psi 8 hrs. 1 1, 20 8


(continued)

TABLE 1.1.7‒continued MASONRY WALLS 14″ OR MORE THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-17-M-27 171/4 Core: clay or shale structural tile; see Notes 4, 7, 9, 18; Facings: sides 1 and 2; see Note 17. 80 psi 8 hrs. 1 1, 20 8
W-17-M-28 171/4 Core: clay or shale structural tile; see Notes 4, 7, 10, 18; Facings: sides 1 and 2; see Note 17. 80 psi 9 hrs. 1 1, 20 9
W-17-M-29 171/4 Core: clay or shale structural tile; see Notes 4, 7, 11, 18; Facings: sides 1 and 2; see Note 17. 80 psi 10 hrs. 1 1, 20 10
W-17-M-30 171/4 Core: clay or shale structural tile; see Notes 4, 8, 15, 18; Facings: sides 1 and 2; see Note 17. 80 psi 12 hrs. 1 1, 20 12
W-17-M-31 171/4 Core: clay or shale structural tile; see Notes 4, 6, 16, 18; Facings: sides 1 and 2; see Note 17. 80 psi 13 hrs. 1 1, 20 13

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1 Tested at NBS - ASA Spec. No. A2-1934.
2. One unit in wall thickness.
3. Two units in wall thickness.
4. Two or three units in wall thickness.
5. Two cells in wall thickness.
6. Three or four cells in wall thickness.
7. Four or five cells in wall thickness.
8. Five or six cells in wall thickness.
9. Minimum percent of solid materials in units = 40%.
10. Minimum percent of solid materials in units = 43%.
11. Minimum percent of solid materials in units = 46%.
12. Minimum percent of solid materials in units = 48%.
13. Minimum percent of solid materials in units = 49%.
14. Minimum percent of solid materials in units = 45%.
15. Minimum percent of solid materials in units = 51%.
16. Minimum percent of solid materials in units = 53%.
17. Not less than 5/8 inch thickness of 1:3 sanded gypsum plaster.
18. Noncombustible or no members framed into wall.
19. Combustible members framed into wall.
20. Load: 80 psi for gross area.
21. Portland cement-lime mortar.
22. Failure mode‒thermal.
23. British test.
24. Passed all criteria.
25. Failed by sudden collapse with no preceding signs of impending failure.
26. One cell in wall thickness.
27. Two cells in wall thickness.
28. Three cells in wall thickness.
29. Minimum percent of solid material in concrete units = 52%.
30. Minimum percent of solid material in concrete units = 54%.
31. Minimum percent of solid material in concrete units = 55%.
32. Minimum percent of solid material in concrete units = 57%.
33. Minimum percent of solid material in concrete units = 60%.
34. Minimum percent of solid material in concrete units = 62%.
35. Minimum percent of solid material in concrete units = 65%.
36. Minimum percent of solid material in concrete units = 70%.
37. Minimum percent of solid material in concrete units = 76%.
38. Not less than 1/2 inch of 1:3 sanded gypsum plaster.
39. Three units in wall thickness.
40. Concrete units made with expanded slag or pumice aggregates.
41. Concrete units made with expanded burned clay or shale, crushed limestone, air cooled slag or cinders.
42. Concrete units made with calcareous sand and gravel. Coarse aggregate, 60 percent or more calcite and dolomite.
43. Concrete units made with siliceous sand and gravel. Ninety percent or more quartz, chert or flint.


FIGURE 1.2.1 METAL FRAME WALLS 0″ TO LESS THAN 4″ THICK



TABLE 1.2.1 METAL FRAME WALLS 0″ TO LESS THAN 4″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-3-Me-1 3″ Core: steel channels having three rows of
4″ × 1/8″ staggered slots in web; core filled with heat expanded vermiculite weighing 1.5 lbs./ft.2 of wall area; Facings: sides 1 and 2, 18 gage steel, spot welded to core.
N/A 25 min. 1 1/3
W-3-Me-2 3″ Core: steel channels having three rows of
4″ × 1/8″ staggered slots in web; core filled with heat expanded vermiculite weighing 2 lbs./ft.2 of wall area; Facings: sides 1 and 2, 18 gage steel, spot welded to core.
N/A 30 min. 1 1/2
W-3-Me-3 21/2 Solid partition: 3/8″ tension rods (vertical) 3' o.c. with metal lath; Scratch coat: cement/sand/lime plaster; Float coats: cement/sand/lime plaster; Finish coats: neat gypsum plaster. N/A 1 hr. 7 1 1
W-2-Me-4 2″ Solid wall: steel channel per Note 1; 2″ thickness of 1:2; 1:3 portland cement on metal lath. N/A 30 min. 1 1/2


(continued)

TABLE 1.2.1‒continued METAL FRAME WALLS 0″ TO LESS THAN 4″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-2-Me-5 2″ Solid wall: steel channel per Note 1; 2″ thickness of neat gypsum plaster on metal lath. N/A 1 hr.
45 min.
1 13/4
W-2-Me-6 2″ Solid wall: steel channel per Note 1; 2″ thickness of 1:11/2; 1:11/2 gypsum plaster on metal lath. N/A 1 hr.
30 min.
1 11/2
W-2-Me-7 2″ Solid wall: steel channel per Note 2; 2″ thickness of 1:1; 1:1 gypsum plaster on metal lath. N/A 1 hr. 1 1
W-2-Me-8 2″ Solid wall: steel channel per Note 1; 2″ thickness of 1:2; 1:2 gypsum plaster on metal lath. N/A 45 min. 1 3/4
W-2-Me-9 21/4 Solid wall: steel channel per Note 2; 21/4″ thickness of 1:2; 1:3 portland cement on metal lath. N/A 30 min. 1 1/2
W-2-Me-10 21/4 Solid wall: steel channel per Note 2; 21/4″ thickness of neat gypsum plaster on metal lath. N/A 2 hrs. 1 2
W-2-Me-11 21/4 Solid wall: steel channel per Note 2; 21/4″ thickness of 1:1/2; 1:1/2 gypsum plaster on metal lath. N/A 1 hr.
45 min.
1 13/4
W-2-Me-12 21/4 Solid wall: steel channel per Note 2; 21/4″ thickness of 1:1; 1:1 gypsum plaster on metal lath. N/A 1 hr.
15 min.
1 11/4
W-2-Me-13 21/4 Solid wall: steel channel per Note 2; 21/4″ thickness of 1:2; 1:2 gypsum plaster on metal lath. N/A 1 hr. 1 1
W-2-Me-14 21/2 Solid wall: steel channel per Note 1; 21/2″ thickness of 4.5:1:7; 4.5:1:7 portland cement, sawdust and sand sprayed on wire mesh; see Note 3. N/A 1 hr. 1 1
W-2-Me-15 21/2 Solid wall: steel channel per Note 2; 21/2″ thickness of 1:4; 1:4 portland cement sprayed on wire mesh; see Note 3. N/A 20 min. 1 1/3
W-2-Me-16 21/2 Solid wall: steel channel per Note 2; 21/2″ thickness of 1:2; 1:3 portland cement on metal lath. N/A 30 min. 1 1/2
W-2-Me-17 21/2 Solid wall: steel channel per Note 2; 21/2″ thickness of neat gypsum plaster on metal lath. N/A 2 hrs.
30 min.
1 21/2
W-2-Me-18 21/2 Solid wall: steel channel per Note 2; 21/2″ thickness of 1:1/2; 1:1/2 gypsum plaster on metal lath. N/A 2 hrs. 1 2
W-2-Me-19 21/2 Solid wall: steel channel per Note 2; 21/2″ thickness of 1:1; 1:1 gypsum plaster on metal lath. N/A 1 hr.
30 min.
1 11/2


(continued)

TABLE 1.2.1‒continued METAL FRAME WALLS 0″ TO LESS THAN 4″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-2-Me-20 21/2 Solid wall: steel channel per Note 2; 21/2
thickness of 1:2; 1:2 gypsum plaster on
metal lath.
N/A 1 hr. 1 1
W-2-Me-21 21/2 Solid wall: steel channel per Note 2; 21/2
thickness of 1:2; 1:3 gypsum plaster on
metal lath.
N/A 1 hr. 1 1
W-3-Me-22 3″ Core: steel channel per Note 2; 1:2; 1:2
gypsum plaster on 3/4″ soft asbestos lath;
plaster thickness 2″ .
N/A 45 min. 1 3/4
W-3-Me-23 31/2 Solid wall: steel channel per Note 2; 21/2
thickness of 1:2; 1:2 gypsum plaster on 3/4
asbestos lath.
N/A 1 hr. 1 1
W-3-Me-24 31/2 Solid wall: steel channel per Note 2; lath
over and 1:21/2; 1:21/2 gypsum plaster on 1″
magnesium oxysulfate wood fiberboard;
plaster thickness 21/2
N/A 1 hr. 1 1
W-3-Me-25 31/2 Core: steel studs; see Note 4; Facings: 3/4
thickness of 1:1/30:2; 1:1/30: 3 portland cement
and asbestos fiber plaster.
N/A 45 min. 1 3/4
W-3-Me-26 31/2 Core: steel studs; see Note 4; Facings: both
sides 3/4″ thickness of 1:2; 1:3 portland
cement.
N/A 30 min. 1 1/2
W-3-Me-27 31/2 Core: steel studs; see Note 4; Facings: both
sides 3/4″ thickness of neat gypsum plaster.
N/A 1 hr. 30 min. 1 11/2
W-3-Me-28 31/2 Core: steel studs; see Note 4; Facings: both
sides 3/4″ thickness of 1:1/2; 1:1/2 gypsum
plaster.
N/A 1 hr. 15 min. 1 11/4
W-3-Me-29 31/2 Core: steel studs; see Note 4; Facings: both
sides 3/4″ thickness of 1:2; 1:2 gypsum plaster.
N/A 1 hr. 1 1
W-3-Me-30 31/2 Core: steel studs; see Note 4; Facings: both
sides3/4″ thickness of 1:2; 1:3 gypsum
plaster.
N/A 45 min. 1 3/4
W-3-Me-31 33/4 Core: steel studs; see Note 4; Facings: both
sides 7/8″ thickness of 1:1/30: 2; 1:1/30: 3
portland cement and asbestos fiber plaster.
N/A 1 hr. 1 1
W-3-Me-32 33/4 Core: steel studs; see Note 4; Facings: both
sides 7/8″ thickness of 1:2; 1:3 portland cement.
N/A 45 min. 1 3/4
W-3-Me-33 33/4 Core: steel studs; see Note 4; Facings: both
sides 7/8″ thickness of neat gypsum plaster.
N/A 2 hrs. 1 2
W-3-Me-34 33/4 Core: steel studs; see Note 4; Facings: both
sides 7/8″ thickness of 1:1/2; 1:1/2″ gypsum
plaster.
N/A 1 hr. 30 min. 1 11/2


(continued)

TABLE 1.2.1‒continued METAL FRAME WALLS 0″ TO LESS THAN 4″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-3-Me-35 33/4 Core: steel studs; see Note 4; Facings: both
sides 7/8″ thickness of 1:2; 1:2 gypsum plaster.
N/A 1 hr.
15 min.
1 11/4
W-3-Me-36 33/4 Core: steel; see Note 4; Facings: 7/8″ thickness
of 1:2; 1:3 gypsum plaster on both sides.
N/A 1 hr. 1 1

For SI: 1 inch = 25.4 mm.
Notes:
1. Failure mode‒local temperature rise‒back face.
2. Three-fourths inch or 1 inch channel framing‒hot-rolled or strip-steel channels.
3. Reinforcement is 4-inch square mesh of No. 6 wire welded at intersections (no channels).
4. Ratings are for any usual type of nonload-bearing metal framing providing 2 inches (or more) air space.
General Note:
The construction details of the wall assemblies are as complete as the source documentation will permit. Data on the method of attachment of facings and the gauge of steel studs was provided when known. The cross-sectional area of the steel stud can be computed, thereby permitting a reasoned estimate of actual loading conditions. For load-bearing assemblies, the maximum allowable stress for the steel studs has been provided in the table "Notes."More often, it is the thermal properties of the facing materials, rather than the specific gauge of the steel, that will determine the degree of fire resistance. This is particularly true for nonbearing wall assemblies.


FIGURE 1.2.2 METAL FRAME WALLS 4″ TO LESS THAN 6″ THICK


TABLE 1.2.2 METAL FRAME WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-5-Me-1 51/2 3″ cavity with 16 ga. channel studs (31/2″ o.c.)
of 1/2″ × 1/2″ channel and 3″ spacer; Metal lath
on ribs with plaster (three coats) 3/4″ over face
of lath; Plaster (each side): scratch coat,
cement/lime/sand with hair; float coat, cement/
lime/sand; finish coat, neat gypsum.
N/A 1 hr.
11 min.
7 1 1
W-4-Me-2 4″ Core: steel studs; see Note 2; Facings: both
sides 1″ thickness of neat gypsum plaster.
N/A 2 hrs.
30 min.
1 21/2
W-4-Me-3 4″ Core: steel studs; see Note 2; Facings: both
sides 1″ thickness of 1:1/2; 1:1/2 gypsum plaster.
N/A 2 hrs. 1 2
W-4-Me-4 4″ Core: steel; see Note 2; Facings: both
sides 1″ thickness of 1:2; 1:3 gypsum plaster.
N/A 1 hr.
15 min.
1 11/4
W-4-Me-5 41/2 Core: lightweight steel studs 3″ in depth; Facings:
both sides 3/4″ thick sanded gypsum plaster,
1:2 scratch coat, 1:3 brown coat applied
on metal lath.
See Note
4
45 min. 1 5 3/4


(continued)

TABLE 1.2.2‒continued METAL FRAME WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-4-Me-6 41/2 Core: lightweight steel studs 3″ in depth;
Facings: both sides 3/4″ thick neat gypsum
plaster on metal lath.
See Note 4 1 hr.
30 min.
1 5 11/2
W-4-Me-7 41/2 Core: lightweight steel studs 3″ in depth;
Facings: both sides 3/4″ thick sanded
gypsum plaster, 1:2 scratch and brown coats
applied on metal lath.
See Note 4 1 hr. 1 5 1
W-4-Me-8 43/4 Core: lightweight steel studs 3″ in depth;
Facings: both sides 7/8″ thick sanded
gypsum plaster, 1:2 scratch coat, 1:3 brown
coat, applied on metal lath.
See Note 4 1 hr. 1 5 1
W-4-Me-9 43/4 Core: lightweight steel studs 3″ in depth;
Facings: both sides 7/8″ thick sanded
gypsum plaster, 1:2 scratch and 1:3 brown
coats applied on metal lath.
See Note 4 1 hr.
15 min.
1 5 11/4
W-5-Me-10 5″ Core: lightweight steel studs 3″ in depth;
Facings: both sides 1″ thick neat gypsum
plaster on metal lath.
See Note 4 2 hrs. 1 5 2
W-5-Me-11 5″ Core: lightweight steel studs 3″ in depth;
Facings: both sides 1″ thick neat gypsum
plaster on metal lath.
See Note 4 2 hrs.
30 min.
1 5, 6 21/2

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Failure mode‒local back face temperature rise.
2. Ratings are for any usual type of nonbearing metal framing providing a minimum 2 inches air space.
3. Facing materials secured to lightweight steel studs not less than 3 inches deep.
4. Rating based on loading to develop a maximum stress of 7270 psi for net area of each stud.
5. Spacing of steel studs must be sufficient to develop adequate rigidity in the metal-lath or gypsum-plaster base.
6. As per Note 4 but load/stud not to exceed 5120 psi.
General Note:
The construction details of the wall assemblies are as complete as the source documentation will permit. Data on the method of attachment of facings and the gauge of steel studs was provided when known. The cross sectional area of the steel stud can be computed, thereby permitting a reasoned estimate of actual loading conditions. For load-bearing assemblies, the maximum allowable stress for the steel studs has been provided in the table "Notes."More often, it is the thermal properties of the facing materials, rather than the specific gauge of the steel, that will determine the degree of fire resistance. This is particularly true for nonbearing wall assemblies.


TABLE 1.2.3 METAL FRAME WALLS 6″ TO LESS THAN 8″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-6-Me-1 65/8 On one side of 1″ magnesium oxysulfate
wood fiberboard sheathing attached to steel
studs (see Notes 1 and 2), 1″ air space, 33/4
brick secured with metal ties to steel frame
every fifth course; Inside facing of 7/8″ 1:2
sanded gypsum plaster on metal lath secured
directly to studs; Plaster side exposed to fire.
See
Note 2
1 hr.
45 min.
1 1 13/4
W-6-Me-2 65/8 On one side of 1″ magnesium oxysulfate
wood fiberboard sheathing attached to steel
studs (see Notes 1 and 2), 1″ air space, 33/4
brick secured with metal ties to steel frame
every fifth course; Inside facing of 7/8″ 1:2
sanded gypsum plaster on metal lath secured
directly to studs; Brick face exposed to fire.
See Note 2 4 hrs. 1 1 4
W-6-Me-3 65/8 On one side of 1″ magnesium oxysulfate
wood fiberboard sheathing attached to steel
studs (see Notes 1 and 2), 1″ air space, 33/4
brick secured with metal ties to steel frame
every fifth course; Inside facing of 7/8″ vermiculite
plaster on metal lath secured
directly to studs; Plaster side exposed to fire.
See Note 2 2 hrs. 1 1 2

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Lightweight steel studs (minimum 3 inches deep) used. Stud spacing dependent on loading, but in each case, spacing is to be such that adequate rigidity is provided to the metal lath plaster base.
2. Load is such that stress developed in studs is not greater than 5120 psi calculated from net stud area.
General Note:
The construction details of the wall assemblies are as complete as the source documentation will permit. Data on the method of attachment of facings and the gauge of steel studs was provided when known. The cross sectional area of the steel stud can be computed, thereby permitting a reasoned estimate of actual loading conditions. For load-bearing assemblies, the maximum allowable stress for the steel studs has been provided in the table "Notes."More often, it is the thermal properties of the facing materials, rather than the specific gauge of the steel, that will determine the degree of fire resistance. This is particularly true for nonbearing wall assemblies.


TABLE 1.2.4 METAL FRAME WALLS 8″ TO LESS THAN 10″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-9-Me-1 91/16 On one side of 1/2″ wood fiberboard sheathing
next to studs, 3/4″ air space formed with 3/4″ ×
15/8″ wood strips placed over the fiberboard
and secured to the studs, paper backed wire
lath nailed to strips 33/4″ brick veneer held in
place by filling a 3/4″ space between the brick
and paper backed lath with mortar; Inside facing
of 3/4″ neat gypsum plaster on metal lath
attached to 5/16″ plywood strips secured to
edges of steel studs; Rated as combustible
because of the sheathing; See Notes 1 and 2;
Plaster exposed.
See
Note 2
1 hr.
45 min.
1 1 13/4
W-9-Me-2 91/16 Same as above with brick exposed. See Note 2 4 hrs. 1 1 4
W-8-Me-3 81/2 On one side of paper backed wire lath attached
to studs and 33/4″ brick veneer held in place by
filling a 1″ space between the brick and lath
with mortar; Inside facing of 1″ paper-
enclosed mineral wool blanket weighing 0.6
lb./ft.2 attached to studs, metal lath or paper
backed wire lath laid over the blanket and
attached to the studs, 3/4″ sanded gypsum plaster
1:2 for the scratch coat and 1:3 for the brown coat; See Notes 1 and 2; Plaster face
exposed.
See Note 2 4 hrs. 1 1 4
W-8-Me-4 81/2 Same as above with brick exposed. See Note 2 5 hrs. 1 1 5

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Lightweight steel studs ≥ 3 inches in depth. Stud spacing dependent on loading, but in any case, the spacing is to be such that adequate rigidity is provided to the metal-lath plaster base.
2. Load is such that stress developed in studs is ≤ 5120 psi calculated from the net area of the stud.
General Note:
The construction details of the wall assemblies are as complete as the source documentation will permit. Data on the method of attachment of facings and the gauge of steel studs was provided when known. The cross sectional area of the steel stud can be computed, thereby permitting a reasoned estimate of actual loading conditions. For load-bearing assemblies, the maximum allowable stress for the steel studs has been provided in the table "Notes."More often, it is the thermal properties of the facing materials, rather than the specific gauge of the steel, that will determine the degree of fire resistance. This is particularly true for nonbearing wall assemblies.


TABLE 1.3.1 WOOD FRAME WALLS 0″ TO LESS THAN 4″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-3-W-1 33/4 Solid wall: 21/4″ wood-wool slab core; 3/4
gypsum plaster each side.
N/A 2 hrs. 7 1, 6 2
W-3-W-2 37/8 2 × 4 stud wall; 3/16″ thick cement asbestos
board on both sides of wall.
360 psi
net area
10 min. 1 2-5 1/6
W-3-W-3 37/8 Same as W-3-W-2 but stud cavities filled
with 1 lb./ft.2 mineral wool batts.
360 psi net area 40 min. 1 2-5 2/3

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
Notes:
1. Achieved "Grade C"fire resistance (British).
2. Nominal 2 × 4 wood studs of No. 1 common or better lumber set edgewise, 2 × 4 plates at top and bottom and blocking at mid height of wall.
3. All horizontal joints in facing material backed by 2 × 4 blocking in wall.
4. Load: 360 psi of net stud cross sectional area.
5. Facings secured with 6d casing nails. Nail holes predrilled and 0.02 inch to 0.03 inch smaller than nail diameter.
6. The wood-wool core is a pressed excelsior slab which possesses insulating properties similar to cellulosic insulation.


FIGURE 1.3.2 WOOD FRAME WALLS 4″ TO LESS THAN 6″ THICK


TABLE 1.3.2 WOOD FRAME WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-4-W-1 4″ 2″ × 4″ stud wall; 3/16″ CAB; no
insulation; Design A.
35 min. 10 min. 4 1-10 1/6
W-4-W-2 41/8 2″ × 4″ stud wall; 3/16″ CAB; no
insulation; Design A.
38 min. 9 min. 4 1-10 1/6
W-4-W-3 43/4 2″ × 4″ stud wall; 3/16″ CAB and 3/8
gypsum board face (both sides);
Design B.
62 min. 64 min. 4 1-10 1
W-5-W-4 5″ 2″ × 4″ stud wall; 3/16″ CAB and 1/2
gypsum board (both sides);
Design B.
79 min. Greater
than
90 min.
4 1-10 1
W-4-W-5 43/4 2″ × 4″ stud wall; 3/16″ CAB and 3/8
gypsum board (both sides);
Design B.
45 min. 45 min. 4 1-12
W-5-W-6 5″ 2″ × 4″ stud wall; 3/16″ CAB and 1/2
gypsum board face (both sides);
Design B.
45 min. 45 min. 4 1-10, 12,
13
W-4-W-7 4″ 2″ × 4″ stud wall; 3/16″ CAB face; 31/2
mineral wool insulation; Design C.
40 min. 42 min. 4 1-10 2/3
W-4-W-8 4″ 2″ × 4″ stud wall; 3/16″ CAB face; 31/2
mineral wool insulation; Design C.
46 min. 46 min. 4 1-10, 43 2/3
W-4-W-9 4″ 2″ × 4″ stud wall; 3/16″ CAB face; 31/2
mineral wool insulation; Design C.
30 min. 30 min. 4 1-10, 12,
14


(continued)

TABLE 1.3.2‒continued WOOD FRAME WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-4-W-10 41/8 2″ × 4″ stud wall; 3/16″ CAB face; 31/2
mineral wool insulation; Design C.
30 min. 4 1-8, 12,
14
W-4-W-11 43/4 2″ × 4″ stud wall; 3/16″ CAB face; 3/8″ gypsum
strips over studs; 51/2″ mineral wool
insulation; Design D.
79 min. 79 min. 4 1-10 1
W-4-W-12 43/4 2″ × 4″ stud wall; 3/16″ CAB face; 3/8″ gypsum
strips at stud edges; 71/2″ mineral
wool insulation; Design D.
82 min. 82 min. 4 1-10 1
W-4-W-13 43/4 2″ × 4″ stud wall; 3/16″ CAB face; 3/8″ gypsum
board strips over studs; 51/2″ mineral
wool insulation; Design D.
30 min. 30 min. 4 1-12
W-4-W-14 43/4 2″ × 4″ stud wall; 3/16″ CAB face; 3/8″ gypsum
board strips over studs; 7″ mineral
wool insulation; Design D.
30 min. 30 min. 4 1-12
W-5-W-15 51/2 2″ × 4″ stud wall; Exposed face: CAB shingles
over 1″ × 6″ ; Unexposed face: 1/8
CAB sheet; 7/16″ fiberboard (wood); Design
E.
34 min. 4 1-10 1/2
W-5-W-16 51/2 2″ × 4″ stud wall; Exposed face: 1/8″ CAB
sheet; 7/16″ fiberboard; Unexposed face:
CAB shingles over 1″ × 6″ ; Design E.
32 min. 33 min. 4 1-10 1/2
W-5-W-17 51/2 2″ × 4″ stud wall; Exposed face: CAB shingles
over 1″ × 6″ ; Unexposed face:1/8
CAB sheet; gypsum at stud edges; 31/2
mineral wood insulation; Design F.
51 min. 4 1-10 3/4
W-5-W-18 51/2 2″ × 4″ stud wall; Exposed face: 1/8″ CAB
sheet; gypsum board at stud edges; Unexposed
face: CAB shingles over 1″ × 6″ ;
31/2″ mineral wool insulation; Design F.
42 min. 4 1-10 2/3
W-5-W-19 55/8 2″ × 4″ stud wall; Exposed face: CAB shingles
over 1″ × 6″ ; Unexposed face: 1/8
CAB sheet; gypsum board at stud edges;
51/2″ mineral wool insulation; Design G.
74 min. 85 min. 4 1-10 1
W-5-W-20 55/8 2″ × 4″ stud wall; Exposed face: 1/8″ CAB
sheet; gypsum board at 3/16″ stud edges; 7/16
fiberboard; Unexposed face: CAB shingles
over 1″ × 6″ ; 51/2″ mineral wool insulation;
Design G.
79 min. 85 min. 4 1-10 11/4
W-5-W-21 55/8 2″ × 4″ stud wall; Exposed face: CAB shingles
1″ × 6″ sheathing; Unexposed face:
CAB sheet; gypsum board at stud edges;
51/2″ mineral wool insulation; Design G.
38 min. 38 min. 4 1-10, 12,
14
W-5-W-22 55/8 2″ × 4″ stud wall; Exposed face: CAB
sheet; gypsum board at stud edges; Unexposed
face: CAB shingles 1″ × 6″ sheathing; 51/2″ mineral wool insulation; Design
G.
38 min. 38 min. 4 1-12
W-6-W-23 6″ 2″ × 4″ stud wall; 16″ o.c.; 1/2″ gypsum
board each side; 1/2″ gypsum plaster each
side.
N/A 60 min. 7 15 1


(continued)

TABLE 1.3.2‒continued WOOD FRAME WALLS 4″ TO LESS THAN 6″ THICK.

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-6-W-24 6″ 2″ × 4″ stud wall; 16″ o.c.; 1/2″ gypsum
board each side; 1/2″ gypsum plaster each
side.
N/A 68 min. 7 16 1
W-6-W-25 67/8 2″ × 4″ stud wall; 18″ o.c.; 3/4″ gypsum
plank each side; 3/16″ gypsum plaster each
side.
N/A 80 min. 7 15 11/3
W-5-W-26 51/8 2″ × 4″ stud wall; 16″ o.c.; 3/8″ gypsum
board each side; 3/16″ gypsum plaster each
side.
N/A 37 min. 7 15 1/2
W-5-W-27 53/4 2″ × 4″ stud wall; 16″ o.c.; 3/8″ gypsum lath
each side; 1/2″ gypsum plaster each side.
N/A 52 min. 7 15 3/4
W-5-W-28 5″ 2″ × 4″ stud wall; 16″ o.c.; 1/2″ gypsum
board each side.
N/A 37 min. 7 16 1/2
W-5-W-29 5″ 2″ × 4″ stud wall; 1/2″ fiberboard both sides
14% M.C. with F.R. paint at 35 gm./ft.2.
N/A 28 min. 7 15 1/3
W-4-W-30 43/4 2″ × 4″ stud wall; Fire side: 1/2″ (wood)
fiberboard; Back side: 1/4″ CAB; 16″ o.c.
N/A 17 min. 7 15, 16 1/4
W-5-W-31 51/8 2″ × 4″ stud wall; 16″ o.c.; 1/2″ fiberboard
insulation with 1/32″ asbestos (both sides of
each board).
N/A 50 min. 7 16 3/4
W-4-W-32 41/4 2″ × 4″ stud wall; 3/8″ thick gypsum
wallboard on both faces; insulated cavities.
See Note 23 25 min. 1 17, 18,
23
1/3
W-4-W-33 41/2 2″ × 4″ stud wall; 1/2″ thick gypsum
wallboard on both faces.
See Note 17 40 min. 1 17, 23 1/3
W-4-W-34 41/2 2″ × 4″ stud wall; 1/2″ thick gypsum
wallboard on both faces; insulated cavities.
See Note 17 45 min. 1 17, 18,
23
3/4
W-4-W-35 41/2 2″ × 4″ stud wall; 1/2″ thick gypsum
wallboard on both faces; insulated cavities.
N/A 1 hr. 1 17, 18,
24
1
W-4-W-36 41/2 2″ × 4″ stud wall; 1/2″ thick, 1.1 lbs./ft.2
wood fiberboard sheathing on
both faces.
See Note 23 15 min. 1 17, 23 1/4
W-4-W-37 41/2 2″ × 4″ stud wall; 1/2″ thick, 0.7 lb./ft.2
wood fiberboard sheathing on both faces.
See Note 23 10 min. 1 17, 23 1/6
W-4-W-38 41/2 2″ × 4″ stud wall; 1/2″ thick, flameproofed
1.6 lbs./ft.2 wood fiberboard sheathing on both faces.
See Note 23 30 min. 1 17, 23 1/2
W-4-W-39 41/2 2″ × 4″ stud wall; 1/2″ thick gypsum
wallboard on both faces; insulated cavities.
See Note 23 1 hr. 1 17, 18,
23
1
W-4-W-40 41/2 2″ × 4″ stud wall; 1/2″ thick, 1:2; 1:3
gypsum plaster on wood lath on both faces.
See Note 23 30 min. 1 17, 21,
23
1/2
W-4-W-41 41/2 2″ × 4″ stud wall; 1/2″ , 1:2; 1:3
gypsum plaster on wood lath on both faces; insulated cavities.
See Note 23 1 hr. 1 17, 18,
21, 24
1


(continued)

TABLE 1.3.2‒continued WOOD FRAME WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-4-W-42 41/2 2″ × 4″ stud wall; 1/2″ , 1:5; 1:7.5 lime
plaster on wood lath on both wall faces.
See
Note 23
30 min. 1 17, 21,
23
1/2
W-4-W-43 41/2 2″ × 4″ stud wall; 1/2″ thick 1:5; 1:7.5 lime
plaster on wood lath on both faces;
insulated cavities.
See
Note 23
45 min. 1 17, 18,
21, 23
3/4
W-4-W-44 45/8 2″ × 4″ stud wall; 3/16″ thick cement-asbestos
over 3/8″ thick gypsum board on both
faces.
See
Note 23
1 hr. 1 23, 25,
26, 27
1
W-4-W-45 45/8 2″ × 4″ stud wall; studs faced with 4″ wide
strips of 3/8″ thick gypsum board; 3/16″ thick
gypsum cement-asbestos board on both
faces; insulated cavities.
See
Note 23
1 hr. 1 23, 25,
27, 28
1
W-4-W-46 45/8 Same as W-4-W-45 but nonload bearing. N/A 1 hr.
15 min.
1 24, 28 11/4
W-4-W-47 47/8 2″ × 4″ stud wall; 3/16″ thick cement-asbestos
board over 1/2″ thick gypsum sheathing
on both faces.
See
Note 23
1 hr.
15 min.
1 23, 25,
26, 27
11/4
W-4-W-48 47/8 Same as W-4-W-47 but nonload bearing. N/A 1 hr.
30 min.
1 24, 27 11/2
W-5-W-49 5″ 2″ × 4″ stud wall; Exterior face: 3/4″ wood
sheathing; asbestos felt 14 lbs./100 ft.2 and
5/32″ cement-asbestos shingles; Interior
face: 4″ wide strips of 3/8″ gypsum board
over studs; wall faced with 3/16″ thick
cement-asbestos board.
See
Note 23
40 min. 1 18, 23,
25, 26,
29
2/3
W-5-W-50 5″ 2″ × 4″ stud wall; Exterior face: as per W-
5-W-49; Interior face: 9/16″ composite
board consisting of 7/16″ thick wood fiberboard
faced with 1/8″ thick cement-asbestos
board; Exterior side exposed to fire.
See
Note 23
30 min. 1 23, 25,
26, 30
1/2
W-5-W-51 5″ Same as W-5-W-50 but interior side
exposed to fire.
See
Note 23
30 min. 1 23, 25,
26
1/2
W-5-W-52 5″ Same as W-5-W-49 but exterior side
exposed to fire.
See
Note 23
45 min. 1 18, 23,
25, 26
3/4
W-5-W-53 5″ 2″ × 4″ stud wall; 3/4″ thick T&G wood
boards on both sides.
See
Note 23
20 min. 1 17, 23 1/3
W-5-W-54 5″ Same as W-5-W-53 but with insulated
cavities.
See
Note 23
35 min. 1 17, 18,
23
1/2
W-5-W-55 5″ 2″ × 4″ stud wall; 3/4″ thick T&G wood
boards on both sides with 30 lbs./100 ft.2
asbestos; paper, between studs and boards.
See
Note 23
45 min. 1 17, 23 3/4
W-5-W-56 5″ 2″ × 4″ stud wall; 1/2″ thick, 1:2; 1:3 gypsum
plaster on metal lath on both sides of wall.
See
Note 23
45 min. 1 17, 21,
34
3/4


(continued)

TABLE 1.3.2‒continued WOOD FRAME WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-5-W-57 5″ 2″ × 4″ stud wall; 3/4″ thick 2:1:8; 2:1:12
lime and Keene's cement plaster over
metal lath on both sides of wall.
See
Note 23
45 min. 1 17, 21,
23
1/2
W-5-W-58 5″ 2″ × 4″ stud wall; 3/4″ thick 2:1:8; 2:1:10
lime portland cement plaster over metal
lath on both sides of wall.
See
Note 23
30 min. 1 17, 21, 23 1/2
W-5-W-59 5″ 2″ × 4″ stud wall; 3/4″ thick 1:5; 1:7.5 lime
plaster on metal lath on both sides of wall.
See
Note 23
30 min. 1 17, 21,
23
1/2
W-5-W-60 5″ 2″ × 4″ stud wall; 3/4″ thick 1:1/30:2; 1:1/30:
3 portland cement, asbestos fiber plaster
on metal lath on both sides of wall.
See
Note 23
45 min. 1 17, 21,
23
3/4
W-5-W-61 5″ 2″ × 4″ stud wall; 3/4″ thick 1:2; 1:3
portland cement plaster on metal lath on
both sides of wall.
See
Note 23
30 min. 1 17, 21,
23
1/2
W-5-W-62 5″ 2″ × 4″ stud wall; 3/4″ thick neat gypsum
plaster on metal lath on both sides of wall.
N/A 1 hr.
30 min.
1 17, 22,
24
11/2
W-5-W-63 5″  2″ × 4″ stud wall; 3/4″ thick neat gypsum
plaster on metal lath on both sides of wall.
See
Note 23
1 hr.
30 min.
1 17, 21,
23
11/2
W-5-W-64 5″ 2″ × 4″ stud wall; 3/4″ thick 1:2; 1:2 gypsum
plaster on metal lath on both sides of
wall; insulated cavities.
See
Note 23
1 hr.
30 min.
1 17, 18,
21, 23
11/2
W-5-W-65 5″ 2″ × 4″ stud wall; same as W-5-W-64 but
cavities not insulated.
See
Note 23
1 hr. 1 17, 21,
23
1
W-5-W-66 5″ 2″ × 4″ stud wall; 3/4″ thick 1:2; 1:3
gypsum plaster on metal lath on both sides
of wall; insulated cavities.
See
Note 23
1 hr.
15 min.
1 17, 18,
21, 23
11/4
W-5-W-67 51/16 Same as W-5-W-49 except cavity insulation
of 1.75 lbs./ft.2 mineral wool bats;
rating applies when either wall side
exposed to fire.
See
Note 23
1 hr.
15 min.
1 23, 26,
25
11/4
W-5-W-68 51/4 2″ × 4″ stud wall, 7/8″ thick 1:2; 1:3
gypsum plaster on metal lath on both sides
of wall; insulated cavities.
See
Note 23
1 hr.
30 min.
1 17, 18,
21, 23
11/2
W-5-W-69 51/4 2″ × 4″ stud wall; 7/8″ thick neat gypsum
plaster applied on metal lath on both sides
of wall.
N/A 1 hr.
45 min.
1 17, 22,
24
13/4
W-5-W-70 51/4 2″ × 4″ stud wall; 1/2″ thick neat gypsum
plaster on 3/8″ plain gypsum lath on both
sides of wall.
See
Note 23
1 hr. 1 17, 22,
23
1
W-5-W-71 51/4 2″ × 4″ stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster on 3/8″ thick plain gypsum
lath with 13/4″ × 13/4″ metal lath pads
nailed 8″ o.c. vertically and 16″ o.c.
horizontally on both sides of wall.
See
Note 23
1 hr. 1 17, 21,
23
1
W-5-W-72 51/4 2″ × 4″ stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster on 3/8″ perforated gypsum
lath, one 3/4″ diameter hole or larger per
16″ square of lath surface, on both sides of
wall.
See
Note 23
1 hr. 1 17, 21,
23
1


(continued)

TABLE 1.3.2‒continued WOOD FRAME WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-5-W-73 51/4 2″ × 4″ stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster on 3/8″ gypsum lath (plain,
indented or perforated) on both sides of
wall.
See Note 23 45 min. 1 17, 21,
23
3/4
W-5-W-74 51/4 2″ × 4″ stud wall; 7/8″ thick of 1:2; 1:3 gypsum
plaster over metal lath on both sides
of wall.
See Note 23 1 hr. 1 17, 21,
23
1
W-5-W-75 51/4 2″ × 4″ stud wall; 7/8″ thick of 1:1/30:2; 1:
1/30:3 portland cement, asbestos plaster
applied over metal lath on both sides of
wall.
See Note 23 1 hr. 1 17, 21,
23
1
W-5-W-76 51/4 2″ × 4″ stud wall; 7/8″ thick of 1:2; 1:3
portland cement plaster over metal lath on
both sides of wall.
See Note 23 45 min. 1 17, 21,
23
3/4
W-5-W-77 51/2 2″ × 4″ stud wall; 1″ thick neat gypsum
plaster over metal lath on both sides of
wall; nonload bearing.
N/A 2 hrs. 1 17, 22,
24
2
W-5-W-78 51/2 2″ × 4″ stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster on 1/2″ thick, 0.7 lb./ft.2
wood fiberboard on both sides of wall.
See Note 23 35 min. 1 17, 21,
23
1/2
W-4-W-79 43/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over wood lath on both
sides of wall; mineral wool insulation.
N/A 1 hr. 43 21, 31,
35,38
1
W-4-W-80 43/4 Same as W-4-W-79 but uninsulated. N/A 35 min. 43 21, 31,
35
1/2
W-4-W-81 43/4 2″ × 4″ wood stud wall; 1/2″ thick of 3:1:8;
3:1:12 lime, Keene’s cement, sand plaster
over wood lath on both sides of wall;
mineral wool insulation.
N/A 1 hr. 43 21, 31, 35, 40 1
W-4-W-82 43/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:61/4; 1:61/4
lime Keene’s cement plaster over
wood lath on both sides of wall;
mineral wool insulation.
N/A 30 min. 43 21, 31,
35, 40
1/2
W-4-W-83 43/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:5;
1:7.5 lime plaster over wood lath on both
sides of wall.
N/A 30 min. 43 21, 31,
35
1/2
W-5-W-84 51/8 2″ × 4″ wood stud wall; 11/16″ thick of 1:5;
1:7.5 lime plaster over wood lath on both
sides of wall; mineral wool insulation.
N/A 45 min. 43 21, 31,
35, 39
3/4
W-5-W-85 51/4 2″ × 4″ wood stud wall; 3/8″ thick of 1:5;
1:7 lime plaster over wood lath on both
sides of wall; mineral wool insulation.
N/A 40 min. 43 21, 31,
35, 40
2/3
W-5-W-86 51/4 2″ × 4″ wood stud wall; 1/2″ thick of 2:1:12
lime, Keene’s cement and sand scratch
coat; 1/2″ thick 2:1:18 lime, Keene's
cement and sand brown coat over wood
lath on both sides of wall; mineral wool
insulation.
N/A 1 hr. 43 21, 31,
35, 40
1
W-5-W-87 51/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2;
1:2 gypsum plaster over 3/8″ plaster board
on both sides of wall.
N/A 45 min. 43 21, 31 3/4


(continued)

TABLE 1.3.2‒continued WOOD FRAME WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-5-W-88 51/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over 3/8″ gypsum lath on
both sides of wall.
N/A 45 min. 43 21, 31 3/4
W-5-W-89 51/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over 3/8″ gypsum lath on
both sides of wall.
N/A 1 hr. 43 21, 31, 33 1
W-5-W-90 51/4 2″ × 4″ wood stud wall; 1/2″ thick neat plaster
over 3/8″ thick gypsum lath on both sides
of wall.
N/A 1 hr. 43 21, 22, 31 1
W-5-W-91 51/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over 3/8″ thick indented gypsum
lath on both sides of wall.
N/A 45 min. 43 21, 31 3/4
W-5-W-92 51/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over 3/8″ thick perforated
gypsum lath on both sides of wall.
N/A 45 min. 43 21, 31, 34 3/4
W-5-W-93 51/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over 3/8″ perforated gypsum
lath on both sides of wall.
N/A 1 hr. 43 21, 31 1
W-5-W-94 51/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over 3/8″ thick perforated gypsum lath on both sides of wall.
N/A 45 min. 43 21, 31, 34 3/4
W-5-W-95 51/2 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over 1/2″ thick wood fiberboard
plaster base on both sides of wall.
N/A 35 min. 43 21, 31, 36 1/2
W-5-W-96 53/4 2″ × 4″ wood stud wall; 1/2″ thick of 1:2; 1:2
gypsum plaster over 7/8″ thick flameproofed
wood fiberboard on both sides of wall.
N/A 1 hr. 43 21, 31, 37 1

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 pound per square foot = 47.9 N/m2.
Notes:
1. All specimens 8 feet or 8 feet 8 inches by 10 feet 4 inches, i.e. one-half of furnace size. See Note 42 for design cross section.
2. Specimens tested in tandem (two per exposure).
3. Test per ASA No. A2-1934 except where unloaded. Also, panels were of "half"size of furnace opening. Time value signifies a thermal failure time.
4. Two-inch by 4-inch studs: 16 inches on center.; where 10 feet 4 inches, blocking at 2-foot 4-inch height.
5. Facing 4 feet by 8 feet, cement-asbestos board sheets, 3/16 inch thick.
6. Sheathing (diagonal): 25/22 inch by 51/2 inch, 1 inch by 6 inches pine.
7. Facing shingles: 24 inches by 12 inches by 5/32 inch where used.
8. Asbestos felt: asphalt sat between sheathing and shingles.
9. Load: 30,500 pounds or 360 psi/stud where load was tested.
10. Walls were tested beyond achievement of first test end point. A load-bearing time in excess of performance time indicates that although thermal criteria were exceeded, load-bearing ability continued.
11. Wall was rated for one hour combustible use in original source.
12. Hose steam test specimen. See table entry of similar design above for recommended rating.
13. Rated one and one-fourth hour load bearing. Rated one and one-half hour nonload bearing.
14. Failed hose stream.
15. Test terminated due to flame penetration.
16. Test terminated‒local back face temperature rise.
17. Nominal 2-inch by 4-inch wood studs of No. 1 common or better lumber set edgewise. Two-inch by four-inch plates at top and bottom and blocking at mid height of wall.
18. Cavity insulation consists of rock wool bats 1.0 lb./ft.2 of filled cavity area.
19. Cavity insulation consists of glass wool bats 0.6 lb./ft.2 of filled cavity area.
20. Cavity insulation consists of blown-in forck wool 2.0 lbs./ft.2 of filled cavity area
21. Mix proportions for plastered walls as follows: first ratio indicates scratch coat mix, weight of dry plaster: dry sand; second ratio indicates brown coat mix.
22. "Neat"plaster is taken to mean unsanded wood-fiber gypsum plaster.
23. Load: 360 psi of net stud cross sectional area.
24. Rated as nonload bearing.
25. Nominal 2-inch by 4-inch studs per Note 17, spaced at 16 inches on center.
26. Horizontal joints in facing material supported by 2-inch by 4-inch blocking within wall.
27. Facings secured with 6d casing nails. Nail holes predrilled and were 0.02 to 0.03 inch smaller than nail diameter.
28. Cavity insulation consists of mineral wool bats weighing 2 lbs./ft.2 of filled cavity area.
29. Interior wall face exposed to fire.
30. Exterior wall faced exposed to fire.
31. Nominal 2-inch by 4-inch studs of yellow pine or Douglas-fir spaced 16 inches on center in a single row.
32. Studs as in Note 31 except double row, with studs in rows staggered.
33. Six roofing nails with metal-lath pads around heats to each 16-inch by 48-inch lath.
34. Areas of holes less than 23/4 percent of area of lath.
35. Wood laths were nailed with either 3d or 4d nails, one nail to each bearing, and the end joining broken every seventh course.
36. One-half-inch thick fiberboard plaster base nailed with 3d or 4d common wire nails spaced 4 to 6 inches on center.
37. Seven-eighths-inch thick fiberboard plaster base nailed with 5d common wire nails spaced 4 to 6 inches on center.
38. Mineral wood bats 1.05 to 1.25 lbs./ft.2 with waterproofed-paper backing.
39. Blown-in mineral wool insulation, 2.2 lbs./ft.2.
40. Mineral wool bats, 1.4 lbs./ft.2 with waterproofed-paper backing.
41. Mineral wood bats, 0.9 lb./ft.2.
42. See wall design diagram, below.
43. Duplicate specimen of W-4-W-7, tested simultaneously with W-4-W-7 in 18-foot test furnace.


TABLE 1.3.3 WOOD FRAME WALLS 6″ TO LESS THAN 8″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-6-W-1 61/4 2 × 4 stud wall; 1/2″ thick, 1:2; 1:2 gypsum
plaster on 7/8″ flameproofed wood fiberboard
weighing 2.8 lbs./ft.2 on both sides
of wall.
See Note 3 1 hr. 1 1-3 1
W-6-W-2 61/2 2 × 4 stud wall; 1/2″ thick, 1:3; 1:3 gypsum
plaster on 1″ thick magnesium oxysulfate
wood fiberboard on both sides
of wall.
See Note 3 45 min. 1 1-3 3/4
W-7-W-3 71/4 Double row of 2 × 4 studs, 1/2″ thick of 1:2;
1:2 gypsum plaster applied over 3/8″ thick
perforated gypsum lath on both sides of
wall; mineral wool insulation.
N/A 1 hr. 43 2, 4, 5 1
W-7-W-4 71/2 Double row of 2 × 4 studs, 5/8″ thick of 1:2;
1:2 gypsum plaster applied over 3/8″ thick
perforated gypsum lath over laid with 2″ ×
2″ , 16 gage wire fabric, on both sides of
wall.
N/A 1 hr.
15 min.
43 2, 4 11/4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 pound per square foot = 47.9 N/m2.
Notes:
1. Nominal 2-inch by 4-inch wood studs of No. 1 common or better lumber set edgewise. Two-inch by 4-inch plates at top and bottom and blocking at mid height of wall.
2. Mix proportions for plastered walls as follows: first ratio indicates scratch coat mix, weight of dry plaster: dry sand; second ratio indicates brown coat mix.
3. Load: 360 psi of net stud cross sectional area.
4. Nominal 2-inch by 4-inch studs of yellow pine of Douglas-fir spaced 16 inches in a double row, with studs in rows staggered.
5. Mineral wool bats, 0.19 lb./ft.2


TABLE 1.4.1 MISCELLANEOUS MATERIALS WALLS 0″ TO LESS THAN 4″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-3-Mi-1 37/8 Glass brick wall:(bricks 53/4″ × 53/4″ × 37/8″ )
1/4″ mortar bed, cement/lime/sand; mounted in
brick (9″ ) wall with mastic and 1/2″ asbestos
rope.
N/A 1 hr. 7 1, 2 1
W-3-Mi-2 3″ Core: 2″ magnesium oxysulfate wood-fiber
blocks; laid in portland cement-lime mortar;
Facings: on both sides; see Note 3.
N/A 1 hr. 1 3 1
W-3-Mi-3 37/8 Core: 8″ × 47/8″ glass blocks 37/8″ thick weighing
4 lbs. each; laid in portland cement-lime
mortar; horizontal mortar joints reinforced with
metal lath.
N/A 15 min. 1 1/4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN.
Notes:
1. No failure reached at 1 hour.
2. These glass blocks are assumed to be solid based on other test data available for similar but hollow units which show significantly reduced fire endurance.
3. Minimum of 1/2 inch of 1:3 sanded gypsum plaster required to develop this rating.


TABLE 1.4.2 MISCELLANEOUS MATERIALS WALLS 4″ TO LESS THAN 6″ THICK

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
W-4-Mi-1 4″ Core: 3″ magnesium oxysulfate wood-fiber
blocks; laid in portland cement mortar;

Facings: both sides; see Note 1.
N/A 2 hrs. 1 2

For SI: 1 inch = 25.4 mm.
Notes:
1. One-half inch sanded gypsum plaster. Voids in hollow blocks to be not more than 30 percent.


FIGURE 1.5.1 FINISH RATINGS‒INORGANIC MATERIALS



TABLE 1.5.1 FINISH RATINGS‒INORGANIC MATERIALS

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. F.R.
(MIN.)
FINISH RATING PRE-BMS-92 BMS-92 POST-BMS-92
F.R.-I-1 9/16 3/8″ gypsum wallboard faced with 3/16
cement-asbestos board.
20 minutes 1 1, 2 15
F.R.-I-2 11/16 1/2″ gypsum sheathing faced with 3/16
cement-asbestos board.
20 minutes 1 1, 2 20
F.R.-I-3 3/16 3/16″ cement-asbestos board over uninsulated
cavity.
10 minutes 1 1, 2 5
F.R.-I-4 3/16 3/16″ cement-asbestos board over insulated
cavities.
5 minutes 1 1, 2 5
F.R.-I-5 3/4 3/4″ thick 1:2; 1:3 gypsum plaster over paper
backed metal lath.
20 minutes 1 1, 2, 3 20
F.R.-I-6 3/4 3/4″ thick portland cement plaster on metal
lath.
10 minutes 1 1, 2 10
F.R.-I-7 3/4 3/4″ thick 1:5; 1:7.5 lime plaster on metal
lath.
10 minutes 1 1, 2 10
F.R.-I-8 1″ 1″ thick neat gypsum plaster on metal lath. 35 minutes 1 1, 2, 4 35
F.R.-I-9 3/4 3/4″ thick neat gypsum plaster on metal lath. 30 minutes 1 1, 2, 4 30


(continued)

TABLE 1.5.1‒continued FINISH RATINGS‒INORGANIC MATERIALS

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. F.R.
(MIN.)
FINISH RATING PRE-BMS-92 BMS-92 POST-BMS-92
F.R.-I-10 3/4 3/4″ thick 1:2; 1:2 gypsum plaster on metal
lath.
15 minutes 1 1, 2, 3 15
F.R.-I-11 1/2 Same as F.R.-1-7, except 1/2″ thick on wood
lath.
15 minutes 1 1, 2, 3 15
F.R.-I-12 1/2 1/2″ thick 1:2; 1:3 gypsum plaster on wood
lath.
15 minutes 1 1, 2, 3 15
F.R.-I-13 7/8 1/2″ thick 1:2; 1:2 gypsum plaster on 3/8

perforated gypsum lath.
30 minutes 1 1, 2, 3 30
F.R.-I-14 7/8 1/2″ thick 1:2; 1:2 gypsum plaster on 3/8
thick plain or indented gypsum plaster.
20 minutes 1 1, 2, 3 20
F.R.-I-15 3/8 3/8″ gypsum wallboard. 10 minutes 1 1, 2 10
F.R.-I-16 1/2 1/2″ gypsum wallboard. 15 minutes 1 1, 2 15

For SI: 1 inch = 25.4 mm,°C = [(°F) - 32]/1.8.
Notes:
1. The finish rating is the time required to obtain an average temperature rise of 250°F, or a single point rise of 325°F, at the interface between the material being rated and the substrate being protected.
2. Tested in accordance with the Standard Specifications for Fire Tests of Building Construction and Materials, ASA No. A2-1932.
3. Mix proportions for plasters as follows: first ratio, dry weight of plaster: dry weight of sand for scratch coat; second ratio, plaster: sand for brown coat.
4. Neat plaster means unsanded wood-fiber gypsum plaster.
General Note:
The finish rating of modern building materials can be found in the current literature.


TABLE 1.5.2 FINISH RATINGS‒ORGANIC MATERIALS

ITEM CODE THICKNESS CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. F.R.
(MIN.)
FINISH RATING PRE-BMS-92 BMS-92 POST-BMS-92
F.R.-O-1 9/16 7/16″ wood fiberboard faced with 1/8
cement-asbestos board.
15 minutes 1 1, 2 15
F.R.-O-2 29/32 3/4″ wood sheathing, asbestos felt weighing 14
lbs./100 ft.2 and 5/32″ cement-asbestos shingles.
20 minutes 1 1, 2 20
F.R.-O-3 11/2 1″ thick magnesium oxysulfate wood fiberboard
faced with 1:3; 1:3 gypsum plaster, 1/2
thick.
20 minutes 1 1, 2, 3 20
F.R.-O-4 1/2 1/2″ thick wood fiberboard. 5 minutes 1 1, 2 5
F.R.-O-5 1/2 1/2″ thick flameproofed wood fiberboard. 10 minutes 1 1, 2 10
F.R.-O-6 1″ 1/2″ thick wood fiberboard faced with 1/2″ thick
1:2; 1:2 gypsum plaster.
15 minutes 1 1, 2, 3 30
F.R.-O-7 13/8 7/8″ thick flameproofed wood fiberboard faced
with 1/2″ thick 1:2; 1:2 gypsum plaster.
30 minutes 1 1, 2, 3 30
F.R.-O-8 11/4 11/4″ thick plywood. 30 minutes 35 30

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 pound per square foot = 47.9 N/m2,°C = [(°F) - 32]/1.8.
Notes:
1. The finish rating is the time required to obtain an average temperature rise of 250°F, or a single point rise of 325°F, at the interface between the material being rated and he substrate being protected.
2. Tested in accordance with the Standard Specifications for Fire Tests of Building Construction and Materials, ASA No. A2-1932.
3. Plaster ratios as follows: first ratio is for scratch coat, weight of dry plaster: weight of dry sand; second ratio is for the brown coat.
General Note:
The finish rating of thinner materials, particularly thinner woods, have not been listed because the possible effects of shrinkage, warpage and aging cannot be predicted.


SECTION II COLUMNS

TABLE 2.1.1 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 0″ TO LESS THAN 6″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
C-6-RC-1 6″ 6″ × 6″ square columns; gravel aggregate
concrete (4030 psi); Reinforcement
: vertical, four 7/8″ rebars;
horizontal, 5/16″ ties at 6″ pitch; Cover:
1″ .
34.7 tons 62 min. 7 1, 2 1
C-6-RC-2 6″ 6″ × 6″ square columns; gravel aggregate
concrete (4200 psi); Reinforcement
: vertical, four 1/2″ rebars;
horizontal, 5/16″ ties at 6″ pitch; Cover:
1″ .
21 tons 69 min. 7 1, 2 1

Notes:
1. Collapse.
2. British Test


FIGURE 2.1.2 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 10″ TO LESS THAN 12″


TABLE 2.1.2 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST BMS-92
C-10-RC-1 10″ 10″ square columns; aggregate concrete
(4260 psi); Reinforcement:
vertical, four 11/4″ rebars; horizontal,
3/8″ ties at 6″ pitch; Cover: 11/4″ .
92.2
tons
1 hr.
2 min.
7 1 1
C-10-RC-2 10″ 10″ square columns; aggregate
concrete (2325 psi); Reinforcement: vertical,
four 1/2″ rebars; horizontal,
5/16″ ties at 6″ pitch; Cover: 1″ .
46.7
tons
1 hr.
52 min.
7 1 13/4
C-10-RC-3 10″ 10″ square columns; aggregate concrete
(5370 psi); Reinforcement: vertical, four 1/2
rebars; horizontal,5/16″ ties at 6″ pitch; Cover: 1″ .
46.5
tons
2 hrs. 7 2, 3, 11 2
C-10-RC-4 10″ 10″ square columns; aggregate concrete
(5206 psi); Reinforcement: vertical, four 1/2
rebars; horizontal, 5/16″ ties at 6″ pitch;
Cover: 1″ .
46.5
tons
2 hrs. 7 2, 7 2
C-10-RC-5 10″ 10″ square columns; aggregate concrete
(5674 psi); Reinforcement: vertical, four 1/2
rebars; horizontal, 5/16″ ties at 6″ pitch;
Cover: 1″ .
46.7
tons
2 hrs. 7 1 2


(continued)

TABLE 2.1.2—continued REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST- BMS-92
C-10-RC-6 10″ 10″ square columns; aggregate concrete
(5150 psi); Reinforcement: vertical, four
11/2″ rebars; horizontal, 5/16″ ties at 6″ pitch;
Cover: 1″ .
66
tons
1 hr.
43 min.
7 1 13/4
C-10-RC-7 10″ 10″ square columns; aggregate concrete
(5580 psi); Reinforcement: vertical, four
1/2″ rebars; horizontal, 5/16″ ties at 6″ pitch;
Cover: 11/8″ .
62.5
tons
1 hr.
38 min.
7 1 11/2
C-10-RC-8 10″ 10″ square columns; aggregate concrete (4080 psi); Reinforcement: vertical, four
11/8″ rebars; horizontal, 5/16″ ties at 6″ pitch;
Cover: 11/8″ .
72.8
tons
1 hr.
48 min.
7 1 13/4
C-10-RC-9 10″ 10″ square columns; aggregate concrete
(2510 psi); Reinforcement: vertical, four
1/2″ rebars; horizontal, 5/16″ ties at 6″ pitch;
Cover: 1″ .
51
tons
2 hrs.
16 min.
7 1 21/4
C-10-RC-10 10″ 10″ square columns; aggregate concrete
(2170 psi); Reinforcement: vertical, four
1/2″ rebars; horizontal, 5/16″ ties at 6″ pitch;
Cover: 1″ .
45
tons
2 hrs.
14 min.
7 12 21/4
C-10-RC-11 10″ 10″ square columns; gravel aggregate
concrete (4015 psi); Reinforcement:
vertical, four 1/2″ rebars; horizontal, 5/16″ ties
at 6″ pitch; Cover: 11/8″ .
46.5
tons
2 hrs.
6 min.
7 1 2
C-11-RC-12 11″ 11″ square columns; gravel aggregate
concrete (4150 psi); Reinforcement:
vertical, four 11/4″ rebars;
horizontal, 3/8″ ties at 71/2″ pitch; Cover: 11/2″ .
61
tons
1 hr.
23 min.
7 1 11/4
C-11-RC-13 11″ 11″ square columns; gravel aggregate
concrete (4380 psi); Reinforcement:
vertical, four 11/4″ rebars; horizontal,
3/8″ ties at 71/2″ pitch; Cover: 11/2″ .
61
tons
1 hr.
26 min.
7 1 11/4
C-11-RC-14 11″ 11″ square columns; gravel aggregate
concrete (4140 psi); Reinforcement:
vertical, four 11/4″ rebars; horizontal,
3/8″ ties at 71/2″ pitch; steel mesh around
reinforcement; Cover: 11/2″ .
61
tons
3 hrs.
9 min.
7 1 3
C-11-RC-15 11″ 11″ square columns; slag aggregate
concrete (3690 psi); Reinforcement:
vertical, four 11/4″ rebars; horizontal,
3/8″ ties at 71/2″ pitch; Cover: 11/2″ .
91
tons
2 hrs. 7 2, 3, 4, 5 2
C-11-RC-16 11″ 11″ square columns; limestone aggregate
concrete (5230 psi); Reinforcement:
vertical, four 11/4″ rebars; horizontal,
3/8″ ties at 71/2″ pitch; Cover: 11/2″ .
91.5
tons
3 hrs.
41 min.
7 1 31/2
C-11-RC-17 11″ 11″ square columns; limestone aggregate
concrete (5530 psi); Reinforcement:
vertical, four 11/4″ rebars; horizontal,
3/8″ ties at 71/2″ pitch; Cover: 11/2″ .
91.5
tons
3 hrs.
47 min.
7 1 31/2


(continued)

TABLE 2.1.2—continued REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST- BMS-92
C-11-RC-18 11″ 11″ square columns; limestone aggregate
concrete (5280 psi); Reinforcement:
vertical, four 11/4″ rebars; horizontal, 3/8
ties at 71/2″ pitch; Cover: 11/2″ .
91.5
tons
2 hrs. 7 2, 3, 4, 6 2
C-11-RC-19 11″ 11″ square columns; limestone aggregate
concrete (4180 psi); Reinforcement:
vertical, four 5/8″ rebars; horizontal, 3/8″ ties
at 7″ pitch; Cover: 11/2″ .
71.4
tons
2 hrs. 7 2, 7 2
C-11-RC-20 11″ 11″ square columns; gravel concrete (4530 psi);
Reinforcement: vertical, four 5/8
rebars; horizontal, 3/8″ ties at 7″ pitch;
Cover: 11/2″ with 1/2″ plaster.
58.8
tons
2 hrs. 7 2, 3, 9 11/4
C-11-RC-21 11″ 11″ square columns; gravel concrete (3520 psi);
Reinforcement: vertical, four 5/8
rebars; horizontal,3/8″ ties at 7″ pitch;
Cover: 11/2″ .
Variable 1 hr.
24 min.
7 1, 8 2
C-11-RC-22 11″ 11″ square columns; aggregate concrete
(3710 psi); Reinforcement: vertical, four 5/8
rebars; horizontal, 3/8″ ties at 7″ pitch;
Cover: 11/2″ .
58.8
tons
2 hrs. 7 2, 3, 10 2
C-11-RC-23 11″ 11″ square columns; aggregate concrete
(3190 psi); Reinforcement: vertical, four 5/8
rebars; horizontal,3/8″ ties at 7″ pitch;
Cover: 11/2″ .
58.8
tons
2 hrs. 7 2, 3, 10 2
C-11-RC-24 11″ 11″ square columns; aggregate concrete
(4860 psi); Reinforcement: vertical, four
5/8″ rebars; horizontal, 3/8″ ties at 7″ pitch;
Cover: 11/2″ .
86.1
tons
1 hr.
20 min.
7 1 11/3
C-11-RC-25 11″ 11″ square columns; aggregate concrete
(4850 psi); Reinforcement: vertical, four
5/8″ rebars; horizontal, 3/8″ ties at 7″ pitch;
Cover: 11/2″ .
58.8
tons
1 hr.
59 min.
7 1 13/4
C-11-RC-26 11″ 11″ square columns; aggregate concrete
(3834 psi); Reinforcement: vertical, four 5/8
rebars; horizontal, 5/16″ ties at 41/2″ pitch;
Cover: 11/2″ .
71.4
tons
53 min. 7 1 3/4

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Failure mode—collapse.
2. Passed 2 hour fire exposure.
3. Passed hose stream test.
4. Reloaded effectively after 48 hours but collapsed at load in excess of original test load.
5. Failing load was 150 tons.
6. Failing load was 112 tons.
7. Failed during hose stream test.
8. Range of load 58.8 tons (initial) to 92 tons (92 minutes) to 60 tons (80 minutes).
9. Collapsed at 44 tons in reload after 96 hours.
10. Withstood reload after 72 hours.
11. Collapsed on reload after 48 hours.


TABLE 2.1.3 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 12″ TO LESS THAN 14″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-12-RC-1 12″ 12″ square columns; gravel aggregate concrete
(2647 psi); Reinforcement: vertical, four 5/8
rebars; horizontal, 5/16″ ties at 41/2″ pitch;
Cover: 2″ .
78.2
tons
38 min. 1 7 1 1/2
C-12-RC-2 12″ Reinforced columns with 11/2″ concrete outside
of reinforced steel; Gross diameter or side of
column: 12″ ; Group I, Column A.
6 hrs. 1 2, 3 6
C-12-RC-3 12″ Description as per C-12-RC-2;
Group I, Column B.
4 hrs. 1 2, 3 4
C-12-RC-4 12″ Description as per C-12-RC-2;
Group II, Column A.
4 hrs. 1 2, 3 4
C-12-RC-5 12″ Description as per C-12-RC-2;
Group II, Column B.
2 hrs.
30 min.
1 2, 3 21/2
C-12-RC-6 12″ Description as per C-12-RC-2;
Group III, Column A.
3 hrs. 1 2, 3 3
C-12-RC-7 12″ Description as per C-12-RC-2;
Group III, Column B.
2 hrs. 1 2, 3 2
C-12-RC-8 12″ Description as per C-12-RC-2;
Group IV, Column A.
2 hrs. 1 2, 3 2
C-12-RC-9 12″ Description as per C-12-RC-2;
Group IV, Column B.
1 hr.
30 min.
1 2, 3 11/2

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 pound per square yard = 5.3 N/m2.
Notes:
1. Failure mode—unspecified structural.
2. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.
3. Groupings of aggregates and ties are the same as for structural steel columns protected solidly with concrete, the ties to be placed over the vertical reinforcing bars and the mesh where required, to be placed within 1 inch from the surface of the column.
Column A: working loads are assumed as carried by the area of the column inside of the lines circumscribing the reinforcing steel.
Column B: working loads are assumed as carried by the gross area of the column.


TABLE 2.1.4 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 14″ TO LESS THAN 16″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
C-14-RC-1 14″ 14″ square columns; gravel aggregate
concrete (4295 psi); Reinforcement:
vertical four 3/4″ rebars; horizontal:
1/4″ ties at 9″ pitch; Cover: 11/2
86
tons
1 hr.
22 min.
7 1 11/4
C-14-RC-2 14″ Reinforced concrete columns with 11/2
concrete outside reinforcing steel;
Gross diameter or side of column: 12″ ;
Group I, Column A.
7 hrs. 1 2, 3 7
C-14-RC-3 14″ Description as per C-14-RC-2;
Group II, Column B.
5 hrs. 1 2, 3 5
C-14-RC-4 14″ Description as per C-14-RC-2;
Group III, Column A.
5 hrs. 1 2, 3 5
C-14-RC-5 14″ Description as per C-14-RC-2;
Group IV, Column B.
3 hrs.
30 min.
1 2, 3 31/2
C-14-RC-6 14″ Description as per C-14-RC-2;
Group III, Column A.
4 hrs. 1 2, 3 4
C-14-RC-7 14″ Description as per C-14-RC-2;
Group III, Column B.
2 hrs.
30 min.
1 2, 3 21/2
C-14-RC-8 14″ Description as per C-14-RC-2;
Group IV, Column A.
2 hrs.
30 min.
1 2, 3 21/2
C-14-RC-9 14″ Description as per C-14-RC-2;
Group IV, Column B.
1 hr.
30 min.
1 2, 3 11/2

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 pound per square yard = 5.3 N/m2.
Notes:
1. Failure mode—main rebars buckled between links at various points.
2. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.
3. Groupings of aggregates and ties are the same as for structural steel columns protected solidly with concrete, the ties to be placed over the vertical reinforcing bars and the mesh where required, to be placed within 1 inch from the surface of the column.
Column A: working loads are assumed as carried by the area of the column inside of the lines circumscribing the reinforcing steel.
Column B: working loads are assumed as carried by the gross area of the column.


FIGURE 2.1.5 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 16″ TO LESS THAN 18″


TABLE 2.1.5 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 16″ TO LESS THAN 18″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-16-RC-1 16″ 16″ square columns; gravel aggregate concrete
(4550 psi); Reinforcement: vertical, eight 13/8
rebars; horizontal, 5/16″ ties at 6″ pitch 13/8
below column surface and 5/16″ ties at 6″ pitch
linking center rebars of each face forming a
smaller square in column cross section.
237
tons
1 hr 7 1, 2, 3 1
C-16-RC-2 16″ 16″ square columns; gravel aggregate concrete
(3360 psi); Reinforcement: vertical, eight 13/8
rebars; horizontal, 5/16″ ties at 6″ pitch; Cover:
13/8″ .
210
tons
2 hrs. 7 2, 4, 5,6 2
C-16-RC-3 16″ 16″ square columns; gravel aggregate concrete
(3980 psi); Reinforcement: vertical, four 7/8
rebars; horizontal,
3/8″ ties at 6″ pitch; Cover: 1″ .
123.5
tons
2 hrs. 7 2, 4, 7 2
C-16-RC-4 16″ Reinforced concrete columns with 11/2
concrete outside reinforcing steel;
Gross diameter or side of
column: 16″ ; Group I, Column A.
9 hrs. 1 8, 9 9
C-16-RC-5 16″ Description as per C-16-RC-4;
Group I, Column B.
6 hrs. 1 8, 9 6
C-16-RC-6 16″ Description as per C-16-RC-4;
Group II, Column A.
6 hrs. 1 8, 9 6


(continued)

TABLE 2.1.5—continued REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 16″ TO LESS THAN 18″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-16-RC-7 16″ Description as per C-16-RC-4;
Group II, Column B.
4 hrs. 1 8, 9 4
C-16-RC-8 16″ Description as per C-16-RC-4;
Group III, Column A.
5 hrs. 1 8, 9 5
C-16-RC-9 16″ Description as per C-16-RC-4;
Group III, Column B.
3 hrs.
30 min.
1 8, 9 31/2
C-16-RC-10 16″ Description as per C-16-RC-4;
Group IV, Column A.
3 hrs. 1 8, 9 3
C-16-RC-11 16″ Description as per C-16-RC-4;
Group IV, Column B.
2 hrs. 1 8, 9 2

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 pound per square yard = 5.3 N/m2.
Notes:
1. Column passed 1-hour fire test.
2. Column passed hose stream test.
3. No reload specified.
4. Column passed 2-hour fire test.
5. Column reloaded successfully after 24 hours.
6. Reinforcing details same as C-16-RC-1.
7. Column passed reload after 72 hours.
8. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.
9. Groupings of aggregates and ties are the same as for structural steel columns protected solidly with concrete, the ties to be placed over the vertical reinforcing bars and the mesh where required, to be placed within 1 inch from the surface of the column.
Column A: working loads are assumed as carried by the area of the column inside of the lines circumscribing the reinforcing steel.
Column B: working loads are assumed as carried by the gross area of the column.


TABLE 2.1.6 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 18″ TO LESS THAN 20″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
C-18-RC-1 18″ Reinforced concrete columns with 11/2
concrete outside reinforced steel; Gross
diameter or side of column: 18″ ; Group I,
Column A.
11 hrs. 1 1, 2 11
C-18-RC-2 18″ Description as per C-18-RC-1;
Group I, Column B.
8 hrs. 1 1, 2 8
C-18-RC-3 18″ Description as per C-18-RC-1;
Group II, Column A.
7 hrs. 1 1, 2 7
C-18-RC-4 18″ Description as per C-18-RC-1;
Group II, Column B.
5 hrs. 1 1, 2 5
C-18-RC-5 18″ Description as per C-18-RC-1;
Group III, Column A.
6 hrs. 1 1, 2 6
C-18-RC-6 18″ Description as per C-18-RC-1;
Group III, Column B.
4 hrs. 1 1, 2 4
C-18-RC-7 18″ Description as per C-18-RC-1;
Group IV, Column A.
3 hrs.
30 min.
1 1, 2 31/2
C-18-RC-8 18″ Description as per C-18-RC-1;
Group IV, Column B.
2 hrs.
30 min.
1 1, 2 21/2

For SI: 1 inch = 25.4 mm, 1 pound per square yard = 5.3 N/m2.
Notes:
1. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint and, tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.
2. Groupings of aggregates and ties are the same as for structural steel columns protected solidly with concrete, the ties to be placed over the vertical reinforcing bars and the mesh where required, to be placed within 1 inch from the surface of the column.
Column A: working loads are assumed as carried by the area of the column inside of the lines circumscribing the reinforcing steel.
Column B: working loads are assumed as carried by the gross area of the column.


FIGURE 2.1.7 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 20″ TO LESS THAN 22″


TABLE 2.1.7 REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 20″ TO LESS THAN 22″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-20-RC-1 20″ 20″ square columns; gravel aggregate
concrete (6690 psi); Reinforcement:
vertical, four 13/4″ rebars; horizontal,
3/8″ wire at 6″ pitch; Cover 13/4″ .
367
tons
2 hrs. 7 1, 2, 3 2
C-20-RC-2 20″ 20″ square columns; gravel aggregate concrete
(4330 psi); Reinforcement: vertical, four
13/4″ rebars; horizontal,
3/8″ ties at 6″ pitch; Cover 13/4″ .
327
tons
2 hrs. 7 1, 2, 4 2
C-20-RC-3 201/4 20″ square columns; gravel aggregate concrete
(4230 psi); Reinforcement: vertical, four
11/8″ rebars; horizontal,
3/8″ wire at 5″ pitch; Cover 11/8″ .
199
tons
2 hrs.
56 min.
7 5 23/4
C-20-RC-4 20″ Reinforced concrete columns with 11/2″ concrete outside of reinforcing steel; Gross
diameter or side of column: 20″ ; Group I, Column A.
12 hrs. 1 6, 7 12
C-20-RC-5 20″ Description as per C-20-RC-4;
Group I, Column B.
9 hrs. 1 6, 7 9


(continued)

TABLE 2.1.7—continued REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 20″ TO LESS THAN 22″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-20-RC-6 20″ Description as per C-20-RC-4;
Group II, Column A.
9 hrs. 1 6, 7 9
C-20-RC-7 20″ Description as per C-20-RC-4;
Group II, Column B.
6 hrs 1 6, 7 6
C-20-RC-8 20″ Description as per C-20-RC-4;
Group III, Column A.
7 hrs. 1 6, 7 7
C-20-RC-9 20″ Description as per C-20-RC-4;
Group III, Column B.
5 hrs. 1 6, 7 5
C-20-RC-10 20″ Description as per C-20-RC-4;
Group IV, Column A.
4 hrs. 1 6, 7 4
C-20-RC-11 20″ Description as per C-20-RC-4;
Group IV, Column B.
3 hrs. 1 6, 7 3

For SI: 1 inch = 25.4 mm, 1 pound per square yard = 5.3 N/m2, 1 ton = 8.896 kN.
Notes:
1. Passed 2-hour fire test.
2. Passed hose stream test.
3. Failed during reload at 300 tons.
4. Passed reload after 72 hours.
5. Failure mode—collapse.
6. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.
7. Groupings of aggregates and ties are the same as for structural steel columns protected solidly with concrete, the ties to be placed over the vertical reinforcing bars and the mesh where required, to be placed within 1 inch from the surface of the column.
Column A: working loads are assumed as carried by the area of the column inside of the lines circumscribing the reinforcing steel.
Column B: working loads are assumed as carried by the gross area of the column.


TABLE 2.1.8 HEXAGONAL REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 12″ TO LESS THAN 14″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-12-HRC-1 12″ 12″ hexagonal columns; gravel
aggregate concrete (4420 psi); Reinforcement: vertical, eight 1/2″ rebars; horizontal,
5/16″ helical winding at 11/2″ pitch; Cover: 1/2″ .
88 tons 58 min. 7 1 3/4
C-12-HRC-2 12″ 12″ hexagonal columns; gravel aggregate concrete (3460 psi); Reinforcement:
vertical, eight 1/2″ rebars; horizontal, 5/16″ helical winding at 11/2″ pitch; Cover: 1/2″ .
78.7
tons
1 hr. 7 2 1

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Failure mode—collapse.
2. Test stopped at 1 hour.


TABLE 2.1.9 HEXAGONAL REINFORCED CONCRETE COLUMNS MINIMUM DIMENSION 14″ TO LESS THAN 16″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-14-HRC-1 14″ 14″ hexagonal columns; gravel aggregate concrete (4970 psi); Reinforcement: vertical, eight 1/2″ rebars; horizontal, 5/16″ helical winding on 2″ pitch; Cover: 1/2″ . 90 tons 2 hrs. 7 1, 2, 3 2

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Withstood 2-hour fire test.
2. Withstood hose stream test.
3. Withstood reload after 48 hours.


TABLE 2.1.10 HEXAGONAL REINFORCED CONCRETE COLUMNS DIAMETER—16″ TO LESS THAN 18″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-16-HRC-1 16″ 16″ hexagonal columns; gravel concrete (6320 psi); Reinforcement: vertical, eight 5/8″ rebars; horizontal, 5/16″ helical winding on 3/4″ pitch; Cover: 1/2″ . 140
tons
1 hr.
55 min.
7 1 13/4
C-16-HRC-2 16″ 16″ hexagonal columns; gravel aggregate concrete (5580 psi); Reinforcement:
vertical, eight 5/8″ rebars; horizontal, 5/16″ helical winding on 13/4″ pitch; Cover: 1/2
124
tons
2 hrs. 7 2 2

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Failure mode—collapse.
2. Failed on furnace removal.


TABLE 2.1.11 HEXAGONAL REINFORCED CONCRETE COLUMNS DIAMETER—20″ TO LESS THAN 22″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-20-HRC-1 20″ 20″ hexagonal columns; gravel concrete (6080 psi); Reinforcement: vertical, 3/4″ rebars; horizontal, 5/6″ helical winding on
13/4″ pitch; Cover: 1/2″ .
211
tons
2 hrs. 7 1 2
C-20-HRC-2 20″ 20″ hexagonal columns; gravel concrete (5080 psi); Reinforcement: vertical, 3/4″ rebars; horizontal, 5/16″ wire on 13/4″ pitch; Cover: 1/2″ . 184
tons
2 hrs.
15 min.
7 2, 3, 4 21/4

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Column collapsed on furnace removal.
2. Passed 21/4-hour fire test.
3. Passed hose stream test.
4. Withstood reload after 48 hours.


TABLE 2.2 ROUND CAST IRON COLUMNS

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-7-CI-1 7″ O.D. Column: 0.6″ minimum metal thickness; unprotected. 30 min. 1 1/2
C-7-CI-2 7″ O.D. Column: 0.6″ minimum metal thickness concrete filled, outside unprotected. 45 min. 1 3/4
C-11-CI-3 11″ O.D. Column: 0.6″ minimum metal thickness; Protection: 11/2″ portland cement plaster on high ribbed metal lath, 1/2″ broken air space. 3 hrs. 1 3
C-11-CI-4 11″ O.D. Column: 0.6″ minimum metal thickness; Protection: 2″ concrete other than siliceous aggregate. 2 hrs.
30 min.
1 21/2
C-12-CI-5 12.5″ O.D. Column: 7″ O.D. 0.6″ minimum metal thickness; Protection: 2″ porous hollow tile,3/4″ mortar between tile and column, outside wire ties. 3 hrs. 1 3
C-7-CI-6 7.6″ O.D. Column: 7″ I.D., 3/10″ minimum metal thickness, concrete filled unprotected. 30 min. 1 1/2
C-8-CI-7 8.6″ O.D. Column: 8″ I.D., 3/10″ minimum metal thickness; concrete filled reinforced with four 31/2″ × 3/8″ angles, in fill; unprotected outside. 1 hr. 1 1

For SI: 1 inch = 25.4 mm.


FIGURE 2.3 STEEL COLUMNS-GYPSUM ENCASEMENTS


TABLE 2.3 STEEL COLUMNS—GYPSUM ENCASEMENTS

ITEM CODE MINIMUM AREA OF SOLID MATERIAL CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-SG-1 Steel protected with 3/4″ 1:3 sanded
gypsum or 1″ 1:21/2 portland cement plaster on wire or lath; one layer.
1 hr. 1 1
C-SG-2 Same as C-SG-1; two layers. 2 hrs.
30 min.
1 21/2
C-SG-3 130 in.2 2″ solid blocks with wire mesh in
horizontal joints; 1″ mortar on flange; reentrant space filled with block and mortar.
2 hrs. 1 2
C-SG-4 150 in.2 Same as C-130-SG-3 with 1/2″ sanded gypsum plaster. 5 hrs. 1 5
C-SG-5 130 in.2 2″ solid blocks with wire mesh in
horizontal joints; 1″ mortar on flange; reentrant space filled with gypsum concrete.
2 hrs.
30 min.
1 21/2
C-SG-6 150 in.2 Same as C-130-SG-5 with 1/2″ sanded gypsum plaster. 5 hrs. 1 5
C-SG-7 300 in.2 4″ solid blocks with wire mesh in
horizontal joints; 1″ mortar on flange; reentrant space filled with block and mortar.
4 hrs. 1 4


(continued)

TABLE 2.3—continued STEEL COLUMNS—GYPSUM ENCASEMENTS

ITEM CODE MINIMUM AREA OF SOLID MATERIAL CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-SG-8 300 in.2 Same as C-300-SG-7 with reentrant space filled with gypsum concrete. 5 hrs. 1 5
C-SG-9 85 in.2 2″ solid blocks with cramps at horizontal joints; mortar on flange only at horizontal joints; reentrant space not filled. 2 hrs.
30 min.
1 21/2
C-SG-10 105 in.2 Same as C-85-SG-9 with 1/2″ sanded gypsum plaster. 4 hrs. 1 4
C-SG-11 95 in.2 3″ hollow blocks with cramps at horizontal joints; mortar on flange only at horizontal joints; reentrant space not filled. 2 hrs.
30 min.
1 21/2
C-SG-12 120 in.2 Same as C-95-SG-11 with 1/2″ sanded gypsum plaster. 5 hrs. 1 5
C-SG-13 130 in.2 2″ neat fibered gypsum reentrant space filled poured solid and reinforced with 4″ × 4″ wire mesh 1/2″ sanded gypsum plaster. 7 hrs. 1 7

For SI: 1 inch = 25.4 mm, 1 square inch = 645 mm2.


TABLE 2.4 TIMBER COLUMNS MINIMUM DIMENSION

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-11-TC-1 11″ With unprotected steel plate cap. 30 min. 1 1, 2 1/2
C-11-TC-2 11″ With unprotected cast iron cap and pintle. 45 min. 1 1, 2 3/4
C-11-TC-3 11″ With concrete or protected steel or cast
iron cap.
1 hr.
15 min.
1 1, 2 11/4
C-11-TC-4 11″ With 3/8″ gypsum wallboard over column and over cast iron or steel cap. 1 hr.
15 min.
1 1, 2 11/4
C-11-TC-5 11″ With 1″ portland cement plaster on wire lath over column and over cast iron or steel cap; 3/8″ air space. 2 hrs. 1 1, 2 2

For SI: 1 inch = 25.4 mm, 1 square inch = 645 mm2.
Notes:
1. Minimum area: 120 square inches.
2. Type of wood: long leaf pine or Douglas fir.


TABLE 2.5.1.1 STEEL COLUMNS—CONCRETE ENCASEMENTS MINIMUM DIMENSION LESS THAN 6″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-5-SC-1 5″ 5″ × 6″ outer dimensions; 4″ × 3″ × 10 lbs."H" beam; Protection: gravel concrete (4900 psi) 6″ × 4″ - 13 SWG mesh. 12 tons 1 hr.
29 min.
7 1 11/4

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Failure mode—collapse.


TABLE 2.5.1.2 STEEL COLUMNS—CONCRETE ENCASEMENTS 6″ TO LESS THAN 8″ THICK

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-7-SC-1 7″ 7″ × 8″ column; 4″ × 3″ × 10 lbs."H" beam; Protection: brick filled concrete (6220 psi); 6″ × 4″ mesh - 13 SWG; 1″ below column surface. 12 tons 2 hrs.
46 min.
7 1 23/4
C-7-SC-2 7″ 7″ × 8″ column; 4″ × 3″ × 10 lbs."H" beam; Protection: gravel concrete (5140 psi); 6″ × 4″ 13 SWG mesh 1″ below surface. 12 tons 3 hrs.
1 min.
7 1 3
C-7-SC-3 7″ 7″ × 8″ column; 4″ × 3″ × 10 lbs."H" beam; Protection: concrete (4540 psi); 6″ × 4″ - 13 SWG mesh; 1″ below column surface. 12 tons 3 hrs.
9 min.
7 1 3
C-7-SC-4 7″ 7″ × 8″ column; 4″ × 3″ × 10 lbs."H" beam; Protection: gravel concrete (5520 psi); 4″ × 4″ mesh; 16 SWG. 12 tons 2 hrs.
50 min.
7 1 23/4

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Failure mode—collapse.


FIGURE 2.5.1.3 STEEL COLUMNS—CONCRETE ENCASEMENTS MINIMUM DIMENSION 8″ TO LESS THAN 10″


TABLE 2.5.1.3 STEEL COLUMNS—CONCRETE ENCASEMENTS MINIMUM DIMENSION 8″ TO LESS THAN 10″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-8-SC-1 81/2 81/2″ × 10″ column; 6″ × 41/2″ × 20 lbs.
"H" beam; Protection: gravel concrete
(5140 psi); 6″ × 4″ - 13 SWG mesh.
39 tons 3 hrs.
8 min.
7 1 3
C-8-SC-2 8″ 8″ × 10″ column; 8″ × 6″ × 35 lbs.
"I" beam; Protection: gravel concrete
(4240 psi); 6″ × 4″ - 13 SWG mesh;
1/2″ cover.
90 tons 2 hrs.
1 min.
7 1 2
C-8-SC-3 8″ 8″ × 10″ concrete encased column;
8″ × 6″ × 35 lbs."H" beam; protection: aggregate concrete (3750 psi); 4″ mesh - 16 SWG reinforcing 1/2″ below column surface.
90 tons 1 hr.
58 min.
7 1 13/4
C-8-SC-4 8″ 6″ × 6″ steel column; 2″ outside protection; Group I. 5 hrs. 1 2 5
C-8-SC-5 8″ 6″ × 6″ steel column; 2″ outside protection; Group II. 3 hrs.
30 min.
1 2 31/2
C-8-SC-6 8″ 6″ × 6″ steel column; 2″ outside protection; Group III. 2 hrs.
30 min.
1 2 21/2


(continued)

TABLE 2.5.1.3—continued STEEL COLUMNS—CONCRETE ENCASEMENTS MINIMUM DIMENSION 8″ TO LESS THAN 10″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-8-SC-7 8″ 6″ × 6″ steel column; 2″ outside protection; Group IV. 1 hr.
45 min.
1 2 13/4
C-9-SC-8 9″ 6″ × 6″ steel column; 3″ outside protection; Group I. 7 hrs. 1 2 7
C-9-SC-9 9″ 6″ × 6″ steel column; 3″ outside protection; Group II. 5 hrs. 1 2 5
C-9-SC-10 9″ 6″ × 6″ steel column; 3″ outside protection; Group III. 3 hrs.
30 min.
1 2 31/2
C-9-SC-11 9″ 6″ × 6″ steel column; 3″ outside protection; Group IV. 2 hrs.
30 min.
1 2 21/2

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 pound per square yard = 5.3 N/m2, 1 ton = 8.896 kN.
Notes:
1. Failure mode—collapse.
2. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.


FIGURE 2.5.1.4 STEEL COLUMNS—CONCRETE ENCASEMENTS MINIMUM DIMENSION 10″ TO LESS THAN 12″


TABLE 2.5.1.4 STEEL COLUMNS—CONCRETE ENCASEMENTS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-10-SC-1 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: gravel aggregate concrete (3640 psi); Mesh 6″ × 4″ 13 SWG, 1″ below column surface. 90 tons 3 hrs.
7 min.
7 1,2 3
C-10-SC-2 10″ 10″ × 16″ column; 8″ × 6″ × 35 lbs."H" beam; Protection: clay brick concrete (3630 psi); 6″ × 4″ mesh; 13 SWG, 1″ below column surface. 90 tons 4 hrs.
6 min.
7 2 4
C-10-SC-3 10″ 10″ × 12″ column; 8″ × 6″ × 35 lbs. "H" beam; Protection: crushed stone and sand concrete (3930 psi); 6″ × 4″ - 13 SWG mesh; 1″ below column surface. 90 tons 3 hrs.
17 min.
7 2 31/4
C-10-SC-4 10″ 10″ × 12″ column; 8″ × 6″ × 35 lbs. "H" beam; Protection: crushed basalt and sand concrete (4350 psi); 6″ × 4″ - 13 SWG mesh; 1″ below column surface. 90 tons 3 hrs.
22 min.
7 2 31/3
C-10-SC-5 10″ 10″ × 12″ column; 8″ × 6″ × 35 lbs. "H" beam; Protection: gravel aggregate concrete (5570 psi); 6″ × 4″ mesh; 13 SWG. 90 tons 3 hrs.
39 min.
7 2 31/2
C-10-SC-6 10″ 10″ × 16″ column; 8″ × 6″ × 35 lbs. "I" beam; Protection: gravel concrete (4950 psi); mesh; 6″ × 4″ 13 SWG 1″ below column surface. 90 tons 4 hrs.
32 min.
7 2 41/2


(continued)

TABLE 2.5.1.4—continued STEEL COLUMNS—CONCRETE ENCASEMENTS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-10-SC-7 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs. "H" beam; Protection: aggregate concrete (1370 psi); 6″ × 4″ mesh; 13 SWG reinforcing 1″ below column surface. 90 tons 2 hrs. 7 3, 4 2
C-10-SC-8 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" column; Protection: aggregate concrete (4000 psi); 13 SWG iron wire loosely around column at 6″ pitch about 2″ beneath column surface. 86 tons 3 hrs.
36 min.
7 2 31/2
C-10-SC-9 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: aggregate concrete (3290 psi); 2″ cover minimum. 86 tons 2 hrs.
8 min.
7 2 2
C-10-SC-10 10″ 10″ × 14″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" column; Protection: crushed brick filled concrete (5310 psi); 6″ × 4″ mesh; 13 SWG reinforcement 1″ below column surface. 90 tons 4 hrs.
28 min.
7 2 41/3
C-10-SC-11 10″ 10″ × 14″ concrete encased column; 8″ × 6″ × 35 lbs."H" beam; Protection: aggregate concrete (342 psi); 6″ × 4″ mesh; 13 SWG reinforcement 1″ below surface. 90 tons 1 hr.
2 min.
7 2 1
C-10-SC-12 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: aggregate concrete (4480 psi); four 3/8″ vertical bars at "H" beam edges with 3/16″ spacers at beam surface at 3' pitch and 3/16″ binders at 10″ pitch; 2″ concrete cover. 90 tons 3 hrs.
2 min.
7 2 3
C-10-SC-13 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: aggregate concrete (5070 psi); 6″ × 4″ mesh; 13 SWG reinforcing at 6″ beam sides wrapped and held by wire ties across (open) 8″ beam face; reinforcements wrapped in 6″ × 4″ mesh; 13 SWG throughout; 1/2″ cover to column surface. 90 tons 3 hrs.
59 min.
7 2 33/4
C-10-SC-14 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: aggregate concrete (4410 psi); 6″ × 4″ mesh; 13 SWG reinforcement 11/4″ below column surface; 1/2″ limestone cement plaster with 3/8″ gypsum plaster finish. 90 tons 2 hrs.
50 min.
7 2 23/4
C-10-SC-15 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: crushed clay brick filled concrete (4260 psi); 6″ × 4″ mesh; 13 SWG reinforcing 1″ below column surface. 90 tons 3 hrs.
54 min.
7 2 33/4
C-10-SC-16 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: limestone aggregate concrete (4350 psi); 6″ × 4″ mesh; 13 SWG reinforcing 1″ below column surface. 90 tons 3 hrs.
54 min.
7 2 33/4


(continued)

TABLE 2.5.1.4—continued STEEL COLUMNS—CONCRETE ENCASEMENTS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-10-SC-17 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: limestone aggregate concrete (5300 psi); 6″ × 4″ ; 13 SWG wire mesh 1″ below column surface. 90 tons 3 hrs. 7 4, 5 3
C-10-SC-18 10″ 10″ × 12″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: limestone aggregate concrete (4800 psi) with 6″ × 4″ ; 13 SWG mesh reinforcement 1″ below surface. 90 tons 3 hrs. 7 4, 5 3
C-10-SC-19 10″ 10″ × 14″ concrete encased steel column; 12″ × 8″ × 65 lbs."H" beam; Protection: aggregate concrete (3900 psi); 4″ mesh; 16 SWG reinforcing 1/2″ below column surface. 118 tons 2 hrs.
42 min.
7 2 2
C-10-SC-20 10″ 10″ × 14″ concrete encased steel column; 12″ × 8″ × 65 lbs."H" beam; Protection: aggregate concrete (4930 psi); 4″ mesh; 16 SWG reinforcing 1/2″ below column surface. 177 tons 2 hrs.
8 min.
7 2 2
C-10-SC-21 103/8 103/8″ × 123/8″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: aggregate concrete (835 psi) with 6″ × 4″ mesh; 13 SWG reinforcing 13/16″ below column surface; 3/16″ gypsum plaster finish. 90 tons 2 hrs. 7 3, 4 2
C-11-SC-22 11″ 11″ × 13″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam; Protection: ″ open texture″ brick filled concrete (890 psi) with 6″ × 4″ mesh; 13 SWG reinforcing 11/2″ below column surface; 3/8″ lime cement plaster; 1/8″ gypsum plaster finish. 90 tons 3 hrs. 7 6, 7 3
C-11-SC-23 11″ 11″ × 12″ column; 4″ × 3″ × 10 lbs."H" beam; gravel concrete (4550 psi); 6″ × 4″ - 13 SWG mesh reinforcing; 1″ below column surface. 12 tons 6 hrs. 7 7, 8 6
C-11-SC-24 11″ 11″ × 12″ column; 4″ × 3″ × 10 lbs."H" beam; Protection: gravel aggregate concrete (3830 psi); with 4″ × 4″ mesh; 16 SWG, 1″ below column surface. 16 tons 5 hrs.
32 min.
7 2 51/2
C-10-SC-25 10″ 6″ × 6″ steel column with 4″ outside protection; Group I. 9 hrs. 1 9 9
C-10-SC-26 10″ Description as per C-SC-25; Group II. 7 hrs. 1 9 7
C-10-SC-27 10″ Description as per C-10-SC-25; Group III. 5 hrs. 1 9 5
C-10-SC-28 10″ Description as per C-10-SC-25; Group IV. 3 hrs.
30 min.
1 9 31/2
C-10-SC-29 10″ 8″ × 8″ steel column with 2″ outside protection; Group I. 6 hrs. 1 9 6
C-10-SC-30 10″ Description as per C-10-SC-29; Group II. 4 hrs. 1 9 4
C-10-SC-31 10″ Description as per C-10-SC-29; Group III. 3 hrs. 1 9 3
C-10-SC-32 10″ Description as per C-10-SC-29; Group IV. 2 hrs. 1 9 2


(continued)

TABLE 2.5.1.4‒continued STEEL COLUMNS‒CONCRETE ENCASEMENTS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-11-SC-33 11″ 8″ × 8″ steel column with 3″ outside protection; Group I. 8 hrs. 1 9 8
C-11-SC-34 11″ Description as per C-10-SC-33; Group II. 6 hrs. 1 9 6
C-11-SC-35 11″ Description as per C-10-SC-33; Group III. 4 hrs. 1 9 4
C-11-SC-36 11″ Description as per C-10-SC-33; Group IV. 3 hrs. 1 9 3

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 pound per square yard = 5.3 N/m2, 1 ton = 8.896 kN.
Notes:
1. Tested under total restraint load to prevent expansion‒minimum load 90 tons.
2. Failure mode‒collapse.
3. Passed 2-hour fire test (Grade "C," British).
4. Passed hose stream test.
5. Column tested and passed 3-hour grade fire resistance (British).
6. Column passed 3-hour fire test.
7. Column collapsed during hose stream testing.
8. Column passed 6-hour fire test.
9. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.


FIGURE 2.5.1.5 STEEL COLUMNS‒CONCRETE ENCASEMENTS MINIMUM DIMENSION 12″ TO LESS THAN 14″



TABLE 2.5.1.5 STEEL COLUMNS‒CONCRETE ENCASEMENTS MINIMUM DIMENSION 12″ TO LESS THAN 14″

ITEM CODE MINIMUM DIMENSION CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-12-SC-1 12″ 12″ × 14″ concrete encased steel column; 8″ × 6″ × 35 lbs."H" beam;
Protection: aggregate concrete (4150 psi) with 4″ mesh; 16 SWG reinforcing
1″ below column surface.
120
tons
3 hrs.
24 min.
7 1 31/3
C-12-SC-2 12″ 12″ × 16″ concrete encased column;
8″ × 6″ × 35 lbs."H" beam; Protection: aggregate concrete (4300 psi) with
4″ mesh; 16 SWG reinforcing
1″ below column surface.
90 tons 2 hrs.
52 min.
7 1 23/4
C-12-SC-3 12″ 12″ × 16″ concrete encased steel column; 12″ × 8″ × 65 lbs."H" column;
Protection: gravel aggregate concrete (3550 psi) with 4″ mesh; 16 SWG reinforcement 1″ below column surface.
177 tons 2 hrs.
31 min.
7 1 21/2
C-12-SC-4 12″ 12″ × 16″ concrete encased column;
12″ × 8″ × 65 lbs."H" beam; Protection: aggregate concrete (3450 psi) with
4″ mesh; 16 SWG reinforcement
1″ below column surface.
118
tons
4 hrs.
4 min.
7 1 4


(continued)

TABLE 2.5.1.5 STEEL COLUMNS‒CONCRETE ENCASEMENTS MINIMUM DIMENSION 12″ TO LESS THAN 14″

ITEM
CODE
MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-12-SC-5 121/2 121/2″ × 14″ column; 6″ × 41/2″ × 20 lbs.
"H" beam; Protection: gravel aggregate concrete (3750 psi) with 4″ × 4″ mesh;
16 SWG reinforcing 1″ below column surface.
52 tons 4 hrs.
29 min.
7 1 41/3
C-12-SC-6 12″ 8″ × 8″ steel column; 2″ outside protection;
Group I.
11 hrs. 1 2 11
C-12-SC-7 12″ Description as per C-12-SC-6; Group II. 8 hrs. 1 2 8
C-12-SC-8 12″ Description as per C-12-SC-6; Group III. 6 hrs. 1 2 6
C-12-SC-9 12″ Description as per C-12-SC-6; Group IV. 4 hrs. 1 2 4
C-12-SC-
10
12″ 10″ × 10″ steel column; 2″ outside protection;
Group I.
7 hrs. 1 2 7
C-12-SC-
11
12″ Description as per C-12-SC-10; Group II. 5 hrs. 1 2 5
C-12-SC-
12
12″ Description as per C-12-SC-10; Group III. 4 hrs. 1 2 4
C-12-SC-
13
12″ Description as per C-12-SC-10; Group IV. 2 hrs.
30 min.
1 2 21/2
C-13-SC-
14
13″ 10″ × 10″ steel column; 3″ outside protection;
Group I.
10 hrs. 1 2 10
C-13-SC-
15
13″ Description as per C-12-SC-14; Group II. 7 hrs. 1 2 7
C-13-SC-
16
13″ Description as per C-12-SC-14; Group III. 5 hrs. 1 2 5
C-13-SC-
17
13″ Description as per C-12-SC-14; Group IV. 3 hrs.
30 min.
1 2 31/2

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 pound per square yard = 5.3 N/m2, 1 ton = 8.896 kN.
Notes:
1. Failure mode‒collapse.
2. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.


FIGURE 2.5.1.6 STEEL COLUMNS‒CONCRETE ENCASEMENTS MINIMUM DIMENSION 14″TO LESS THAN 16″



TABLE 2.5.1.6 STEEL COLUMNS‒CONCRETE ENCASEMENTS MINIMUM DIMENSION 14″ TO LESS THAN 16″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-14-SC-1 14″ 24″ × 16″ concrete encased steel column; 8″ ×
6″ × 35 lbs."H" column; Protection: aggregate
concrete (4240 psi); 4″ mesh - 16 SWG rein-
forcing 1″ below column surface.
90 tons 3 hrs.
40 min.
7 1 3
C-14-SC-2 14″ 14″ × 18″ concrete encased steel column; 12″
× 8″ × 65 lbs."H" beam; Protection: gravel
aggregate concrete (4000 psi) with 4″ - 16
SWG wire mesh reinforcement 1″ below column surface.
177
tons
3 hrs.
20 min.
7 1 3
C-14-SC-3 14″ 10″ × 10″ steel column; 4″ outside protection;
Group I.
12 hrs. 1 2 12
C-14-SC-4 14″ Description as per C-14-SC-3; Group II. 9 hrs. 1 2 9
C-14-SC-1 14″ 24″ × 16″ concrete encased steel column; 8″ ×
6″ × 35 lbs."H" column; Protection: aggregate
concrete (4240 psi); 4″ mesh - 16 SWG reinforcing 1″ below column surface.
90 tons 3 hrs.
40 min.
7 1 3


(continued)

TABLE 2.5.1.6‒continued STEEL COLUMNS‒CONCRETE ENCASEMENTS MINIMUM DIMENSION 14″ TO LESS THAN 16″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-14-SC-2 14″ 14″ × 18″ concrete encased steel column; 12″
× 8″ × 65 lbs."H" beam; Protection: gravel
aggregate concrete (4000 psi) with 4″-16
SWG wire mesh reinforcement 1″ below col-
umn surface.
177
tons
3 hrs.
20 min.
7 1 3
C-14-SC-3 14″ 10″ × 10″ steel column; 4″ outside
protection; Group I.
12 hrs. 1 2 12
C-14-SC-4 14″ Description as per C-14-SC-3;
Group II.
9 hrs. 1 2 9
C-14-SC-5 14″ Description as per C-14-SC-3;
Group III.
7 hrs. 1 2 7
C-14-SC-6 14″ Description as per C-14-SC-3;
Group IV.
5 hrs. 1 2 5
C-14-SC-7 14″ 12″ × 12″ steel column; 2″ outside
protection; Group I.
8 hrs. 1 2 8
C-14-SC-8 14″ Description as per C-14-SC-7;
Group II.
6 hrs. 1 2 6
C-14-SC-9 14″ Description as per C-14-SC-7; Group III. 5 hrs. 1 2 5
C-14-SC-10 14″ Description as per C-14-SC-7; Group IV 3 hrs. 1 2 3
C-15-SC-11 15″ 12″ × 12″ steel column; 3″ outside
protection; Group I.
11 hrs. 1 2 11
C-15-SC-12 15″ Description as per C-15-SC-11;
Group II.
8 hrs. 1 2 8
C-15-SC-13 15″ Description as per C-15-SC-11;
Group III.
6 hrs. 1 2 6
C-15-SC-14 15″ Description as per C-15-SC-11;
Group IV.
4 hrs. 1 2 4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 pound per square yard = 5.3 N/m2, 1 ton = 8.896 kN.
Notes:
1. Collapse.
2. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.


TABLE 2.5.1.7 STEEL COLUMNS‒CONCRETE ENCASEMENTS MINIMUM DIMENSION 16″ TO LESS THAN 18″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-16-SC-13 16″ 12″ × 12″ steel column; 4″ outside protection; Group I. 14 hrs. 1 1 14
C-16-SC-2 16″ Description as per C-16-SC-1; Group II. 10 hrs. 1 1 10
C-16-SC-3 16″ Description as per C-16-SC-1;
Group III.
8 hrs. 1 1 8
C-16-SC-4 16″ Description as per C-16-SC-1;
Group IV.
5 hrs. 1 1 5

For SI: 1 inch = 25.4 mm.
Notes:
1. Group I: includes concrete having calcareous aggregate containing a combined total of not more than 10 percent of quartz, chert and flint for the coarse aggregate.
Group II: includes concrete having trap-rock aggregate applied without metal ties and also concrete having cinder, sandstone or granite aggregate, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group III: includes concrete having cinder, sandstone or granite aggregate tied with No. 5 gage steel wire, wound spirally over the column section on a pitch of 8 inches, or equivalent ties, and concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, if held in place with wire mesh or expanded metal having not larger than 4-inch mesh, weighing not less than 1.7 lbs./yd.2, placed not more than 1 inch from the surface of the concrete.
Group IV: includes concrete having siliceous aggregates containing a combined total of 60 percent or more of quartz, chert and flint, and tied with No. 5 gage steel wire wound spirally over the column section on a pitch of 8 inches, or equivalent ties.


TABLE 2.5.2.1 STEEL COLUMNS‒BRICK AND BLOCK ENCASEMENTS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-10-SB-1 101/2 101/2″ × 13″ brick encased steel columns; 8″ ×
6″ × 35 lbs."H" beam; Protection. Fill of broken brick and mortar; 2″ brick on edge; joints
broken in alternate courses; cement-sand
grout; 13 SWG wire reinforcement in every
third horizontal joint.
90 tons 3 hrs.
6 min.
7 1 3
C-10-SB-2 101/2 101/2″ × 13″ brick encased steel columns; 8″ ×
6″ × 35 lbs."H" beam; Protection: 2″ brick;
joints broken in alternate courses; cement-
sand grout; 13 SWG iron wire reinforcement
in alternate horizontal joints.
90 tons 2 hrs. 7 2, 3, 4 2
C-10-SB-3 10″ 10″ × 12″ block encased columns;
8″ × 6″ × 35 lbs."H" beam; Protection: 2″
foamed slag concrete blocks;
13 SWG wire at each horizontal joint; mortar
at each joint.
90 tons 2 hrs. 7 5 2
C-10-SB-4 101/2 101/2″ × 12″ block encased steel columns; 8″ ×
6″ × 35 lbs."H" beam; Protection: gravel
aggregate concrete fill (unconsolidated) 2″
thick hollow clay tiles with mortar at edges.
86 tons 56 min. 7 1 3/4
C-10-SB-5 101/2 101/2″ × 12″ block encased steel columns; 8″ ×
6″ × 35 lbs."H" beam; Protection: 2″ hollow
clay tiles with mortar at edges.
86 tons 22 min. 7 1 1/4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Failure mode‒collapse.
2. Passed 2-hour fire test (Grade "C"- British).
3. Passed hose stream test.
4. Passed reload test.
5. Passed 2-hour fire exposure but collapsed immediately following hose stream test.


TABLE 2.5.2.2 STEEL COLUMNS‒BRICK AND BLOCK ENCASEMENTS MINIMUM DIMENSION 12″ TO LESS THAN 14″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-12-SB-1 12″ 12″ × 15″ brick encased steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection:
25/8″ thick brick; joints broken in alternate
courses; cement-sand grout; fill of broken
brick and mortar.
90 tons 1 hr.
49 min.
7 1 13/4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Failure mode‒collapse.


TABLE 2.5.2.3 STEEL COLUMNS‒BRICK AND BLOCK ENCASEMENTS MINIMUM DIMENSION 14″ TO LESS THAN 16″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-15-SB-1 15″ 15″ × 17″ brick encased steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection: 41/2
thick brick; joints broken in alternate courses;
cement-sand grout; fill of broken brick and
mortar.
45 tons 6 hrs. 7 1 6
C-15-SB-2 15″ 15″ × 17″ brick encased steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection.
Fill of broken brick and mortar; 41/2″ brick;
joints broken in alternate courses; cement-sand
grout.
86 tons 6 hrs. 7 2, 3, 4 6
C-15-SB-3 15″ 15″ × 18″ brick encased steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection: 41/2
brick work; joints alternating;
cement-sand grout.
90 tons 4 hrs. 7 5, 6 4
C-15-SB-4 14″ 14″ × 16″ block encased steel columns; 8″ × 6″
× 35 lbs."H" beam; Protection:
4″ thick foam slag concrete blocks;
13 SWG wire reinforcement in each horizontal
joint; mortar in joints.
90 tons 5 hrs.
52 min.
7 7 43/4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Only a nominal load was applied to specimen.
2. Passed 6-hour fire test (Grade "A"- British).
3. Passed (6 minute) hose stream test.
4. Reload not specified.
5. Passed 4-hour fire exposure.
6. Failed by collapse between first and second minute of hose stream exposure.
7. Mode of failure-collapse.


TABLE 2.5.3.1 STEEL COLUMNS‒PLASTER ENCASEMENTS MINIMUM DIMENSION 6″ TO LESS THAN 8″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-7-SP-1 71/2 71/2″ × 91/2″ plaster protected steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection: 24
SWG wire metal lath;
11/4″ lime plaster.
90 tons 57 min. 7 1 3/4
C-7-SP-2 77/8 77/8″ × 10″ plaster protected steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection:
3/8″ gypsum bal wire wound with 16 SWG wire
helically wound at 4″ pitch;
1/2″ gypsum plaster.
90 tons 1 hr.
13 min.
7 1 1
C-7-SP-3 71/4 71/4″ × 93/8″ plaster protected steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection:
3/8″gypsum board; wire helically wound
16 SWG at 4″ pitch;
1/4″ gypsum plaster finish.
90 tons 1 hr.
14 min.
7 1 1

Notes:
1. Failure mode‒collapse.


TABLE 2.5.3.2 STEEL COLUMNS‒PLASTER ENCASEMENTS MINIMUM DIMENSION 8″ TO LESS THAN 10″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-8-SP-1 8″ 8″ × 10″ plaster protected steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection:
24 SWG wire lath; 1″ gypsum plaster.
86 tons 1 hr.
23 min.
7 1 11/4
C-8-SP-2 81/2 81/2″ × 101/2″ plaster protected steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection: 24
SWG metal lath wrap; 11/4″ gypsum plaster.
90 tons 1 hr.
36 min.
7 1 11/2
C-9-SP-3 9″ 9″ × 11″ plaster protected steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection:
24 SWG metal lath wrap; 1/8″ M.S. ties at 12″
pitch wire netting 11/2″ × 22 SWG between first
and second plaster coats; 11/2″ gypsum plaster.
90 tons 1 hr.
33 min.
7 1 11/2
C-8-SP-4 83/4 83/4″ × 103/4″ plaster protected steel columns;
8″ × 6″ × 35 lbs."H" beam; Protection: 3/4″ gyp-
sum board; wire wound spirally (#16 SWG) at
11/2″ pitch; 1/2″ gypsum plaster.
90 tons 2 hrs. 7 2, 3, 4 2

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Failure mode‒collapse.
2. Passed 2 hour fire exposure test (Grade "C"- British).
3. Passed hose stream test.


TABLE 2.5.4.1 STEEL COLUMNS‒MISCELLANEOUS ENCASEMENTS MINIMUM DIMENSION 6″ TO LESS THAN 8″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-7-SM-1 75/8 75/8″× 91/2″ (asbestos plaster) protected steel
columns; 8″ × 6″ × 35 lbs."H" beam;
Protection: 20 gage 1/2″ metal lath; 9/16″ asbestos
plaster (minimum).
90 tons 1 hr.
52 min.
7 1 13/4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Failure mode‒collapse.


TABLE 2.5.4.2 STEEL COLUMNS‒MISCELLANEOUS ENCASEMENTS MINIMUM DIMENSION 8″ TO LESS THAN 10″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-9-SM-1 95/8 95/8″ × 113/8″ asbestos slab and cement plaster
protected columns; 8″ × 6″ × 35 lbs."H" beam;
Protection: 1″ asbestos slab; wire wound; 5/8
plaster.
90 tons 2 hrs. 7 1, 2 2

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Passed 2 hour fire exposure test.
2. Collapsed during hose stream test.


TABLE 2.5.4.3 STEEL COLUMNS‒MISCELLANEOUS ENCASEMENTS MINIMUM DIMENSION 10″ TO LESS THAN 12″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-11-SM-1 111/2 111/2″ × 131/2″ wood wool and plaster protected
steel columns; 8″ × 6″ × 35 lbs."H" beam;
Protection: wood-wool-cement paste as fill
and to 2″ cover over beam; 3/4″ gypsum plaster
finish.
90 tons 2 hrs. 7 1, 2, 3 2
C-10-SM-1 10″ 10″ × 12″ asbestos protected steel columns; 8″
× 6″ × 35 lbs."H" beam; Protection: sprayed
on asbestos paste to 2″ cover over column.
90 tons 4 hrs. 7 2, 3, 4 4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Passed 2 hour fire exposure (Grade "C" - British).
2. Passed hose stream test.
3. Passed reload test.
4. Passed 4 hour fire exposure test.


TABLE 2.5.4.4 STEEL COLUMNS‒MISCELLANEOUS ENCASEMENTS MINIMUM DIMENSION 12″ TO LESS THAN 14″

ITEM CODE MINIMUM
DIMENSION
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
C-12-SM-1 12″ 12″ × 141/4″ cement and asbestos protected
columns; 8″ × 6″ × 35 lbs."H" beam; Protec-
tion: fill of asbestos packing pieces 1″ thick
1'3″ o.c.; cover of 2″ molded asbestos inner
layer; 1″ molded asbestos outer layer; held in
position by 16 SWG nichrome wire ties; wash
of refractory cement on outer surface.
86 tons 4 hrs.
43 min.
7 1, 2, 3 42/3

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Passed 4 hour fire exposure (Grade "B"- British).
2. Passed hose stream test.
3. Passed reload test.


SECTION III FLOOR/CEILING ASSEMBLIES

FIGURE 3.1 FLOOR/CEILING ASSEMBLIES‒REINFORCED CONCRETE



TABLE 3.1 FLOOR/CEILING ASSEMBLIES‒REINFORCED CONCRETE

ITEM CODE ASSEMBLY
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-3-RC-1 33/4 33/4 ″thick floor; 31/4″ (5475 psi) concrete
deck; 1/2″plaster under deck; 3/8″main rein-
forcement bars at 51/2″ pitch with 7/8″ con-
crete cover; 3/8″ main reinforcement bars at
41/2″ pitch perpendicular with 1/2″ concrete
cover; 13'1″ span restrained.
195 psf 24 min. 7 1, 2 1/3
F/C-3-RC-2 31/4 31/4″ deep (3540 psi) concrete deck; 3/8″ main
reinforcement bars at 51/2″ pitch with 7/8
cover; 3/8″main reinforcement bars at 41/2
pitch perpendicular with 1/2″ cover; 13'1″
span restrained.
195 psf 2 hrs. 7 1, 3, 4 2


(continued)

TABLE 3.1‒continued FLOOR/CEILING ASSEMBLIES‒REINFORCED CONCRETE

ITEM CODE ASSEMBLY
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-3-RC-3 31/4 31/4″deep (4175 psi) concrete deck; 3/8
main reinforcement bars at 51/2″ pitch with
7/8″ cover; 3/8″ main reinforcement bars at
41/2″ pitch perpendicular with 1/2″ cover;
13'1″ span restrained.
195 psf 31 min. 7 1, 5 1/2
F/C-3-RC-4 31/4 31/4″ deep (4355 psi) concrete deck;
3/8″ main reinforcement bars at 51/2″ pitch
with 7/8″ cover; 3/8″ main reinforcement
bars at 41/2″ pitch perpendicular with 1/2
cover; 13'1″ span restrained.
195 psf 41 min. 7 1, 5, 6 1/2
F/C-3-RC-5 31/4 31/4″ thick (3800 psi) concrete deck; 3/8
main reinforcement bars at 51/2″ pitch with
7/8″ cover; 3/8″ main reinforcement bars at
41/2″ pitch perpendicular with 1/2″ cover;
13'1″ span restrained.
195 psf 1 hr.
5 min.
7 1, 5 1
F/C-4-RC-6 41/4 41/4 ″ thick; 31/4 ″ (4000 psi) concrete deck;
1″ sprayed asbestos lower surface; 3/8
main reinforcement bars at 57/8″ pitch with
7/8″ concrete cover; 3/8″ main reinforce-
ment bars at 41/2″ pitch perpendicular with
1/2″ concrete cover; 13'1″ span restrained.
195 psf 4 hrs. 7 1, 7 4
F/C-4-RC-7 4″ 4″ (5025 psi) concrete deck; 1/4 ″ reinforce-
ment bars at 71/2″ pitch with 3/4″ cover; 3/8
main reinforcement bars at 33/4″ pitch per-
pendicular with 1/2″cover; 13'1″ span
restrained.
140 psf 1 hr.
16 min.
7 1, 2 11/4
F/C-4-RC-8 4″ 4″ thick (4905 psi) deck; 1/4 ″ reinforcement
bars at 71/2″ pitch with 7/8″ cover; 3/8″ main
reinforcement bars at 33/4″ pitch perpen-
dicular with 1/2″ cover; 13'1″ span
restrained.
100 psf 1 hr.
23 min.
7 1, 2 11/3
F/C-4-RC-9 4″ 4″ deep (4370 psi);1/4 ″ reinforcement bars
at 6″ pitch with 3/4″ cover; 1/4 ″ main rein-
forcement bars at 4″ pitch perpendicular
with 1/2″cover; 13'1″ span restrained.
150 psf 2 hrs. 7 1, 3 2
F/C-4-RC-10 4″ 4″ thick (5140 psi) deck; 1/4 ″ reinforcement
bars at 71/2″ pitch with 7/8″ cover; 3/8″ main
reinforcement bars at 33/4″ pitch perpen-
dicular with 1/2″ cover; 13'1″ span
restrained.
140 psf 1 hr.
16 min.
7 1, 5 11/4
F/C-4-RC-11 4″ 4″ thick (4000 psi) concrete deck; 3″ × 11/2
× 4 lbs. R.S.J.; 2″6″ C.R.S.; flush with top
surface; 4″ × 6″ x 13 SWG mesh reinforce-
ment 1″ from bottom of slab; 6'6″ span
restrained.
150 psf 2 hrs. 7 1, 3 2


(continued)

TABLE 3.1‒continued FLOOR/CEILING ASSEMBLIES‒REINFORCED CONCRETE

ITEM CODE ASSEMBLY
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-4-RC-12 4″ 4″ deep (2380 psi) concrete deck;
3″ × 11/2″ × 4 lbs. R.S.J.; 2″6″ C.R.S.; flush
with top surface; 4″ × 6″ x 13 SWG mesh
reinforcement 1″ from bottom surface;
6'6″ span restrained.
150 psf 1 hr.
3 min.
7 1, 2 1
F/C-4-RC-13 41/2 41/2″ thick (5200 psi) deck; 1/4 ″ reinforce-
ment bars at 71/4 ″ pitch with 7/8″ cover; 3/8
main reinforcement bars at 33/4″ pitch per-
pendicular with 1/2″ cover; 13'1″ span
restrained.
140 psf 2 hrs. 7 1, 3 2
F/C-4-RC-14 41/2 41/2″deep (2525 psi) concrete deck; 1/4
reinforcement bars at 71/2″ pitch with 7/8
cover; 3/8″ main reinforcement bars at 33/8
pitch perpendicular with 1/2″ cover; 13'1″
span restrained.
150 psf 42 min. 7 1, 5 2/3
F/C-4-RC-15 41/2 41/2″ deep (4830 psi) concrete deck;
11/2″ × No. 15 gauge wire mesh; 3/8″ rein-
forcement bars at 15″ pitch with 1″ cover;
1/2″ main reinforcement bars at 6″ pitch
perpendicular with 1/2″ cover; 12' span
simply supported.
75 psf 1 hr.
32 min.
7 1, 8 11/2
F/C-4-RC-16 41/2 41/2″ deep (4595 psi) concrete deck; 1/4
reinforcement bars at 71/2″ pitch with 7/8
cover; 3/8″ main reinforcement bars at 31/2
pitch perpendicular with 1/2″ cover; 12'
span simply supported.
75 psf 1 hr.
20 min.
7 1, 8 11/3
F/C-4-RC-17 41/2 41/2″ deep (3625 psi) concrete deck; 1/4
reinforcement bars at 71/2″ pitch with 7/8
cover; 3/8″ main reinforcement bars at 31/2
pitch perpendicular with 1/2″ cover; 12'
span simply supported.
75 psf 35 min. 7 1, 8 1/2
F/C-4-RC-18 41/2 41/2″ deep (4410 psi) concrete deck; 1/4
reinforcement bars at 71/2″ pitch with 7/8
cover; 3/8″ main reinforcement bars at 31/2
pitch perpendicular with 1/2″ cover; 12'
span simply supported.
85 psf 1 hr.
27 min.
7 1, 8 11/3
F/C-4-RC-19 41/2 41/2″ deep (4850 psi) deck; 3/8″ reinforce-
ment bars at 15″ pitch with 1″ cover; 1/2
main reinforcement bars at 6″ pitch per-
pendicular with 1/2″ cover; 12' span simply
supported.
75 psf 2 hrs.
15 min.
7 1, 9 11/4
F/C-4-RC-20 41/2 41/2″ deep (3610 psi) deck; 1/4″ reinforce-
ment bars at 71/2″ pitch with 7/8″ cover; 3/8
main reinforcement bars at 31/2″ pitch per-
pendicular with 1/2″ cover; 12' span simply
supported.
75 psf 1 hr.
22 min.
7 1, 8 11/3


(continued)

TABLE 3.1‒continued FLOOR/CEILING ASSEMBLIES‒REINFORCED CONCRETE

ITEM CODE ASSEMBLY
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-5-RC-21 5″ 5″ deep; 41/2″ (5830 psi) concrete deck; 1/2
plaster finish bottom of slab; 1/4″ reinforce-
ment bars at 71/2″ pitch with 7/8″ cover; 3/8
main reinforcement bars at 31/2″ pitch per-
pendicular with 1/2″ cover; 12' span simply
supported.
69 psf 2 hrs. 7 1, 3 2
F/C-5-RC-22 5″ 41/2″ (5290 psi) concrete deck; 1/2″ plaster
finish bottom of slab; 1/4 ″reinforcement
bars at 71/2″ pitch with 7/8″ cover; 3/8″ main
reinforcement bars at 31/2″ pitch perpen-
dicular with 1/2″ cover; 12' span simply
supported.
No load 2 hrs.
28 min.
7 1, 10,
11
21/4
F/C-5-RC-23 5″ 5″ (3020 psi) concrete deck; 3″ × 11/2″ × 4
lbs. R.S.J.; 2' C.R.S. with 1″ cover on bot-
tom and top flanges; 8' span restrained.
172 psf 1 hr.
24 min.
7 1, 2,
12
11/2
F/C-5-RC-24 51/2 5″ (5180 psi) concrete deck; 1/2″ retarded
plaster underneath slab; 1/4 ″ reinforcement
bars at 71/2″ pitch with 13/8″ cover; 3/8
main reinforcement bars at 31/2″ pitch per-
pendicular with 1″ cover; 12' span simply
supported.
60 psf 2 hrs.
48 min.
7 1, 10 23/4
F/C-6-RC-25 6″ 6″ deep (4800 psi) concrete deck; 1/4 ″ rein-
forcement bars at 71/2″ pitch with 7/8″ cover; 3/8
main reinforcement bars at 31/2″ pitch per-
pendicular with 7/8″ cover; 13'1″
span restrained.
195 psf 4 hrs. 7 1, 7 4
F/C-6-RC-26 6″ 6″ (4650 psi) concrete deck; 1/4 ″ reinforce-
ment bars at 71/2″ pitch with 7/8″ cover; 3/8
main reinforcement bars at 31/2″ pitch per-
pendicular with 1/2″ cover; 13'1″ span
restrained.
195 psf 2 hrs.
23 min.
7 1, 2 21/4
F/C-6-RC-27 6″ 6″ deep (6050 psi) concrete deck; 1/4 ″ rein-
forcement bars at 71/2″ pitch 7/8″ cover; 3/8
reinforcement bars at 31/2″ pitch perpen-
dicular with 1/2″ cover; 13'1″ span
restrained.
195 psf 3 hrs.
30 min.
7 1, 10 31/2
F/C-6-RC-28 6″ 6″ deep (5180 psi) concrete deck; 1/4″rein-
forcement bars at 8″ pitch 3/4″ cover; 1/4
reinforcement bars at 51/2″ pitch perpen-
dicular with 1/2″ cover; 13'1″ span
restrained.
150 psf 4 hrs. 7 1, 7 4
F/C-6-RC-29 6″ 6″ thick (4180 psi) concrete deck; 4″ × 3″
× 10 lbs. R.S.J.; 2' 6″ C.R.S. with 1″ cover
on both top and bottom flanges; 13'1″ span
restrained.
160 psf 3 hrs.
48 min.
7 1, 10 33/4
F/C-6-RC-30 6″ 6″ thick (3720 psi) concrete deck; 4″ × 3″
× 10 lbs. R.S.J.; 2' 6″ C.R.S. with 1″ cover
on both top and bottom flanges; 12' span
simply supported.
115 psf 29 min. 7 1, 5,
13
1/4


(continued)

TABLE 3.1‒continued FLOOR/CEILING ASSEMBLIES‒REINFORCED CONCRETE

ITEM CODE ASSEMBLY
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-6-RC-31 6″ 6″ deep (3450 psi) concrete deck; 4″ ×
13/4″ × 5 lbs. R.S.J.; 2' 6″ C.R.S. with 1″
cover on both top and bottom flanges; 12'
span simply supported.
25 psf 3 hrs.
35 min.
7 1, 2 31/2
F/C-6-RC-32 6″ 6″ deep (4460 psi) concrete deck; 4″ ×
13/4″ × 5 lbs. R.S.J.; 2' C.R.S.; with 1″
cover on both top and bottom flanges; 12'
span simply supported.
60 psf 4 hrs.
30 min.
7 1, 10 41/2
F/C-6-RC-33 6″ 6″ deep (4360 psi) concrete deck; 4″ × 13/4
× 5 lbs. R.S.J.; 2' C.R.S.; with 1″ cover on
both top and bottom flanges; 13'1″ span
restrained.
60 psf 2 hrs. 7 1, 3 2
F/C-6-RC-34 61/4 61/4 ″ thick; 43/4″ (5120 psi) concrete core;
1″ T&G board flooring; 1/2″ plaster under-
coat; 4″ × 3″ × 10 lbs. R.S.J.; 3' C.R.S.
flush with top surface concrete; 12' span
simply supported; 2″ × 1'3″ clinker con-
crete insert.
100 psf 4 hrs. 7 1, 7 4
F/C-6-RC-35 61/4 43/4″ (3600 psi) concrete core; 1″ T&G
board flooring; 1/2″ plaster undercoat; 4″ ×
3″ × 10 lbs. R.S.J.; 3' C.R.S.; flush with
top surface concrete; 12' span simply sup-
ported; 2″ × 1'3″ clinker concrete insert.
100 psf 2 hrs.
30 min.
7 1, 5 21/2
F/C-6-RC-36 61/4 43/4″ (2800 psi) concrete core; 1″ T&G
board flooring; 1/2″ plaster undercoat; 4″ ×
3″ × 10 lbs. R.S.J.; 3' C.R.S.; flush with
top surface concrete; 12″ span simply sup-
ported; 2″ × 1'3″ clinker concrete insert.
80 psf 4 hrs. 7 1, 7 4
F/C-7-RC-37 7″ (3640 psi) concrete deck; 1/4″ reinforce-
ment bars at 6″ pitch with 11/2″ cover; 1/4
reinforcement bars at 5″ pitch perpendicu-
lar with 11/2″ cover; 13'1″ span restrained.
169 psf 6 hrs. 7 1, 14 6
F/C-7-RC-38 7″ (4060 psi) concrete deck; 4″ × 3″ × 10 lbs.
R.S.J.; 2' 6″ C.R.S. with 11/2″ cover on
both top and bottom flanges; 4″ × 6″ × 13
SWG mesh reinforcement 11/2″ from bot-
tom of slab; 13'1″ span restrained.
175 psf 6 hrs. 7 1, 14 6
F/C-7-RC-39 71/4 53/4″(4010 psi) concrete core; 1″ T&G
board flooring; 1/2″ plaster undercoat; 4″ ×
3″ × 10 lbs. R.S.J.; 2' 6″ C.R.S.; 1″ down
from top surface of concrete; 12' simply
supported span; 2″ × 1' 3″ clinker concrete
insert.
95 psf 2 hrs. 7 1, 3 2
F/C-7-RC-40 71/4 53/4″ (3220 psi) concrete core; 1″ T&G
flooring; 1/2″ plaster undercoat; 4″ × 3″ ×
10 lbs. R.S.J.; 2'6″ C.R.S.; 1″ down from
top surface of concrete; 12' simply sup-
ported span; 2″ × 1'3″ clinker concrete
insert.
95 psf 4 hrs. 7 1, 7 4


(continued)

TABLE 3.1‒continued FLOOR/CEILING ASSEMBLIES‒REINFORCED CONCRETE

ITEM CODE ASSEMBLY
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-7-RC-41 10″
(21/4″ Slab)
Ribbed floor, see Note 15 for details; slab
21/2″ deep (3020 psi); 1/4″ reinforcement
bars at 6″ pitch with 3/4″ cover; beams 71/2
deep × 5″ wide; 24″ C.R.S.; 5/8″ reinforce-
ment bars two rows 1/2″ vertically apart
with 1″ cover; 13'1″ span restricted.
195 psf 1 hr.
4 min.
7 1, 2,
15
1
F/C-5-RC-42 51/2 Composite ribbed concrete slab assembly;
see Note 17 for details.
See
Note 16
2 hrs. 43 16, 17 2
F/C-3-RC-43 3″ 2500 psi concrete; 5/8″ cover; fully
restrained at test.
See
Note 16
30 min. 43 16 1/2
F/C-3-RC-44 3″ 2000 psi concrete; 5/8″ cover; free or partial
restraint at test.
See
Note 16
45 min. 43 16 3/4
F/C-4-RC-45 4″ 2500 psi concrete; 5/8″ cover; fully
restrained at test.
See
Note 16
40 min. 43 16 2/3
F/C-4-RC-46 4″ 2000 psi concrete; 3/4″ cover; free or partial
restraint at test.
See
Note 16
1 hr.
15 min.
43 16 11/4
F/C-5-RC-47 5″ 2500 psi concrete; 3/4″ cover; fully
restrained at test.
See
Note 16
1 hr. 43 16 1
F/C-5-RC-48 5″ 2000 psi concrete; 3/4″ cover; free or partial
restraint at test.
See
Note 16
1 hr.
30 min.
43 16 11/2
F/C-6-RC-49 6″ 2500 psi concrete; 1″ cover; fully
restrained at test.
See
Note 16
1 hr.
30 min.
43 16 11/2
F/C-6-RC-50 6″ 2000 psi concrete; 1″ cover; free or partial
restraint at test.
See
Note 16
2 hrs. 43 16 2

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound per square inch = 0.00689 MPa, 1 pound per square foot = 47.9 N/m2.
Notes :
1. British test.
2. Failure mode‒local back face temperature rise.
3. Tested for Grade "C" (2 hour) fire resistance
4. Collapse imminent following hose stream.
5. Failure mode‒flame thru.
6. Void formed with explosive force and report.
7. Achieved Grade "B" (4 hour) fire resistance (British).
8. Failure mode‒collapse.
9. Test was run to 2 hours, but specimen was partially supported by the furnace at 11/4 hours.
10. Failure mode‒average back face temperature.
11. Recommended endurance for nonload bearing performance only.
12. Floor maintained load bearing ability to 2 hours at which point test was terminated.
13. Test was run to 3 hours at which time failure mode 2 (above) was reached in spite of crack formation at 29 minutes.
14. Tested for Grade "A" (6 hour) fire resistance.
15.
16. Load unspecified.
17. Total assembly thickness 51/2 inches. Three-inch thick blocks of molded excelsior bonded with portlandcement used as inserts with 21/2-inch cover (concrete) above blocks and 3/4-inch gypsum plaster below. Nine-inch wide ribs containing reinforcing steel of unspecified size interrupted 20-inch wide segments of slab composite (i.e., plaster, excelsior blocks, concrete cover).


FIGURE 3.2 FLOOR/CEILING ASSEMBLIES‒STEEL STRUCTURAL ELEMENTS



TABLE 3.2 FLOOR/CEILING ASSEMBLIES‒STEEL STRUCTURAL ELEMENTS

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-S-1 0″ 10' × 13'6″; S.J. 103 - 24″ o.c.; Deck: 2″
concrete; Membrane: none.
145 psf 7 min. 3 1, 2, 3,
8
0
F/C-S-2 0″ 10'× 13'6″ ; S.J. 103 - 24″ o.c.; Deck: 2″
concrete; Membrane: none
145 psf 7 min. 3 1, 2, 3,
8
0
F/C-S-3 1/2 10' × 13' 6″ ; S.J. 103 - 24″ o.c.; Deck: 2″
concrete 1:2:4; Membrane: furring 12″ o.c.;
Clips A, B, G; No extra reinforcement;
1/2″ plaster - 1.5:2.5.
145 psf 1 hr.
15 min.
3 2, 3, 8 11/4
F/C-S-4 1/2 10' × 13' 6″ ; S.J. 103 - 24″ o.c.; Deck: 2″
concrete 1:2:4; Membrane: furring 16″ o.c.;
Clips D, E, F, G; Diagonal wire reinforcement;
1/2″ plaster - 1.5:2.5.
145 psf 2 hrs.
46 min.
3 3, 8 23/4
F/C-S-5 1/2 10' × 13'6″ ; S.J. 103 - 24″ o.c.; Deck: 2″
concrete 1:2:4; Membrane: furring 16″ o.c.;
Clips A, B, G; No extra reinforcement;
1/2″ plaster - 1.5:2.5.
145 psf 1 hr.
4 min.
3 2, 3, 8 1
F/C-S-6 1/2 10' × 13'6″; S.J. 103 - 24″ o.c.; Deck: 2″
concrete 1:2:4; Membrane: furring 16″ o.c.;
Clips D, E, F, G; Hexagonal mesh
reinforcement; 1/2″ plaster.
145 psf 3 hrs.
28 min.
3 2, 3, 8 21/3


(continued)

TABLE 3.2‒continued FLOOR/CEILING ASSEMBLIES‒STEEL STRUCTURAL ELEMENTS

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-S-7 1/2 10'× 13'6″ ; S.J. 103 - 24″ o.c.; Deck: 4 lbs.
rib lath; 6″ × 6″ - 10 × 10 ga. reinforcement; 2″
deck gravel concrete; Membrane: furring 16″
o.c.; Clips C, E; Reinforcement: none; 1/2
plaster - 1.5:2.5 mill mix.
N/A 55 min. 3 5, 8 3/4
F/C-S-8 1/2 Spec. 9' × 4'4″; S.J. 103 bar joists - 18″ o.c.;
Deck: 4 lbs. rib lath base; 6″ × 6″ - 10 × 10 ga.
reinforcement; 2″ deck 1:2:4 gravel concrete;
Membrane: furring, 3/4″ C.R.S., 16″ o.c.; Clips
C, E; Reinforcement: none; 1/2″ plaster -
1.5:2.5 mill mix.
300 psf 1 hr.
10 min.
3 2, 3, 8 1
F/C-S-9 5/8 10' × 13'6″; S.J. 103 - 24″ o.c.; Deck: 2″ con-
crete 1:2:4; Membrane: furring 12″ o.c.; Clips
A, B, G; Extra "A" clips reinforcement; 5/8
plaster - 1.5:2; 1.5:3.
145 psf 3 hrs. 3 6, 8 3
F/C-S-10 5/8 18' × 13'6″ ; Joists, S.J. 103 - 24″ o.c.; Deck: 4
lbs. rib lath; 6″ × 6″ - 10 × 10 ga. reinforce-
ment; 2″ deck 1:2:3.5 gravel concrete; Mem-
brane: furring, spacing 16″ o.c.; Clips C, E;
Reinforcement: none; 5/8″ plaster - 1.5:2.5 mill
mix.
145 psf 1 hr.
25 min.
3 2, 3, 8 11/3
F/C-S-11 5/8 10'× 13'6″; S.J. 103 - 24″ o.c.; Deck: 2″ con-
crete 1:2:4; Membrane: furring 12″ o.c.; Clips
D, E, F, G; Diagonal wire reinforcement; 5/8
plaster - 1.5:2; 0.5:3.
145 psf 3 hrs.
15 min.
3 2, 4, 8 31/4
F/C-S-12 5/8 10' × 13'6″; Joists, S.J. 103 - 24″ o.c.; Deck:
3.4 lbs. rib lath; 6″ × 6″ - 10 × 10 ga. reinforce-
ment; 2″ deck 1:2:4 gravel concrete; Mem-
brane: furring 16″ o.c.; Clips D, E, F, G;
Reinforcement: none; 5/8″ plaster - 1.5:2.5.
145 psf 1 hr. 3 7, 8 1
F/C-S-13 3/4 Spec. 9' × 4'4″; S.J. 103 - 18″ o.c.; Deck: 4 lbs.
rib lath; 6″ × 6″ - 10 × 10 ga. reinforcement; 2″
deck 1:2:4 gravel concrete; Membrane: fur-
ring, 3/4″ C.R.S., 16″ o.c.; Clips C, E; Rein-
forcement: none; 3/4″ plaster - 1.5:2.5 mill mix.
300 psf 1 hr.
56 min.
3 3, 8 13/4
F/C-S-14 7/8 Floor finish: 1″ concrete; plate cont. weld; 4″
- 7.7 lbs. "I" beams; Ceiling: 1/4″ rods 12″ o.c.;
7/8″ gypsum sand plaster.
105 psf 1 hr.
35 min.
6 2, 4, 9,
10
11/2
F/C-S-15 1″ Floor finish: 11/2″ L.W. concrete; 1/2″ limestone
cement; plate cont. weld; 5″ - 10 lbs. "I"
beams; Ceiling: 1/4″ rods 12″ o.c. tack welded
to beams metal lath; 1″ P. C. plaster.
165 psf 3 hrs.
20 min.
6 4, 9, 11 31/3
F/C-S-16 1″ 10' × 13'6″ ; S.J. 103 - 24″ o.c.; Deck: 2″ con-
crete 1:2:4; Membrane: furring 12″ o.c.; Clips
D, E, F, G; Hexagonal mesh reinforcement; 1″
thick plaster - 1.5:2; 1.5:3.
145 psf 4 hrs.
26 min.
3 2, 4, 8 41/3
F/C-S-17 1″ 10' × 13'6″ ; Joists - S.J. 103 - 24″ o.c.; Deck:
3.4 lbs. rib lath; 6″ × 6″ - 10 × 10 ga. reinforce-
ment; 2″ deck 1:2:4 gravel concrete; Mem-
brane: furring 16″ o.c.; Clips D, E, F, G; 1″
plaster.
145 psf 1 hr.
42 min.
3 2, 4, 8 12/3


(continued)

TABLE 3.2‒continued FLOOR/CEILING ASSEMBLIES‒STEEL STRUCTURAL ELEMENTS

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-S-18 11/8 10' × 13'6″ ; S. J. 103 - 24″ o.c.; Deck: 2″ con-
crete 1:2:4; Membrane: furring 12″ o.c.; Clips
C, E, F, G; Diagonal wire reinforcement; 11/8
plaster.
145 psf 2 hrs.
44 min.
3 2, 4, 8 22/3
F/C-S-19 11/8 10' × 13'6″ ; Joists - S.J. 103 - 24″ o.c.; Deck:
11/2″ gypsum concrete over; 1/2″gypsum
board; Membrane: furring 12″ o.c.; Clips D, E,
F, G; 11/8″plaster - 1.5:2; 1.5:3.
145 psf 1 hr.
40 min.
3 2, 3, 8 12/3
F/C-S-20 11/8 21/2″ cinder concrete; 1/2″ topping; plate 6″
welds 12″ o.c.; 5″ - 18.9 lbs. "H" center; 5″ -
10 lbs."I" ends; 1″ channels 18″ o.c.; 11/8
gypsum sand plaster.
150 psf 3 hrs.
43 min.
6 2, 4, 9,
11
32/3
F/C-S-21 11/4 10' × 13'6″ ; Joists - S.J. 103 - 24″ o.c.; Deck:
11/2″ gypsum concrete over; 1/2″ gypsum board
base; Membrane: furring 12″ o.c.; Clips D, E,
F, G; 11/4″ plaster - 1.5:2; 1.5:3.
145 psf 1 hr.
48 min.
3 2, 3, 8 12/3
F/C-S-22 11/4 Floor finish: 11/2″ limestone concrete; 1/2″ sand
cement topping; plate to beams 31/2″; 12″ o.c.
welded; 5″ - 10 lbs. "I" beams; 1″ channels
18″ o.c.; 11/4″ wood fiber gypsum sand plaster
on metal lath.
292 psf 2 hrs.
45 min.
6 2, 4, 9,
10
23/4
F/C-S-23 11/2 21/2″ L.W. (gas exp.) concrete; Deck: 1/2″ top-
ping; plate 61/4 ″ welds 12″ o.c.; Beams: 5″ -
18.9 lbs. "H" center; 5″ - 10 lbs. "I" ends;
Membrane: 1″ channels 18″ o.c.; 11/2″ gypsum
sand plaster.
150 psf 4 hrs.
42 min.
6 2, 4, 9 42/3
F/C-S-24 11/2 Floor finish: 11/2″ limestone concrete; 1/2
cement topping; plate 31/2″- 12″ o.c. welded;
5″ - 10 lbs. "I" beams; Ceiling: 1″ channels
18″ o.c.; 11/2″ gypsum plaster.
292 psf 2 hrs.
34 min.
6 2, 4, 9,
10
21/2
F/C-S-25 11/2 Floor finish: 11/2″ gravel concrete on exp.
metal; plate cont. weld; 4″ - 7.7 lbs. "I"
beams; Ceiling: 1/4 ″ rods 12″ o.c. welded to
beams; 11/2″ fiber gypsum sand plaster.
70 psf 1 hr.
24 min.
6 2, 4, 9,
10
11/3
F/C-S-26 21/2 Floor finish: bare plate; 61/4″ welding - 12″
o.c.; 5″ - 18.9 lbs. "H" girders (inner); 5″ - 10
lbs "I" girders (two outer); 1″ channels 18″
o.c.; 2″ reinforced gypsum tile; 1/2″ gypsum
sand plaster.
122 psf 1 hr. 6 7, 9, 11 1
F/C-S-27 21/2 Floor finish: 2″ gravel concrete; plate to
beams 31/2″ - 12″ o.c. welded; 4″ - 7.7 lbs. "I"
beams; 2″ gypsum ceiling tiles; 1/2″ 1:3 gyp-
sum sand plaster.
105 psf 2 hrs.
31 min.
6 2, 4, 9,
10
21/2
F/C-S-28 21/2 Floor finish: 11/2″gravel concrete; 1/2″gypsum
asphalt; plate continuous weld;4″ - 7.7 lbs. "I"
beams; 12″ - 31.8 lbs. "I" beams - girder at 5″
from one end; 1″ channels 18″ o.c.; 2″ rein-
forcement gypsum tile; 1/2″ 1:3 gypsum sand
plaster.
200 psf 4 hrs.
55 min.
6 2, 4, 9,
11
42/3


(continued)

TABLE 3.2‒continued FLOOR/CEILING ASSEMBLIES‒STEEL STRUCTURAL ELEMENTS

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-S-29 3/4 Floor: 2″ reinforced concrete or 2″ precast
reinforced gypsum tile; Ceiling: 3/4″portland
cement-sand plaster 1:2 for scratch coat and
1:3 for brown coat with 15 lbs. hydrated lime
and 3 lbs. of short asbestos fiber bag per
cement or 3/4″ sanded gypsum plaster 1:2 for
scratch coat and 1:3 for brown coat.
See
Note 12
1 hr.
30 min.
1 12, 13,
14
11/2
F/C-S-30 3/4 Floor: 21/4″ reinforced concrete or 2″ rein-
forced gypsum tile; the latter with 1/4″ mortar
finish; Ceiling: 3/4″ sanded gypsum plaster;
1:2 for scratch coat and 1:3 for brown coat.
See
Note 12
2 hrs. 1 12, 13,
14
2
F/C-S-31 3/4 Floor: 21/2″ reinforced concrete or 2″ rein-
forced gypsum tile; the latter with 1/4″ mortar
finish; Ceiling: 1″ neat gypsum plaster or 3/4
gypsum-vermiculite plaster, ratio of gypsum
to fine vermiculite 2:1 to 3:1.
See
Note 12
2 hrs.
30 min.
1 12, 13,
14
21/2
F/C-S-32 3/4 Floor: 21/2″reinforced concrete or 2″ rein-
forced gypsum tile; the latter with 1/2″ mortar
finish; Ceiling: 1″ neat gypsum plaster or 3/4
gypsum-vermiculite plaster, ratio of gypsum
to fine vermiculite 2:1 to 3:1.
See
Note 12
3 hrs. 1 12, 13,
14
3
F/C-S-33 1″ Floor: 21/2″ reinforced concrete or 2″ rein-
forced gypsum slabs; the latter with 1/2″ mor-
tar finish; Ceiling: 1″ gypsum-vermiculite
plaster applied on metal lath and ratio 2:1 to
3:1 gypsum to vermiculite by weight.
See
Note 12
4 hrs. 1 12, 13,
14
4
F/C-S-34 21/2 Floor: 2″ reinforced concrete or 2″ precast
reinforced portland cement concrete or gyp-
sum slabs; precast slabs to be finished with
1/4″ mortar top coat; Ceiling: 2″ precast rein-
forced gypsum tile, anchored into beams
with metal ties or clips and covered with 1/2
1:3 sanded gypsum plaster.
See
Note 12
4 hrs. 1 12, 13,
14
4
F/C-S-35 1″ Floor: 1:3:6 portland cement, sand and gravel
concrete applied directly to the top of steel
units and 11/2″ thick at top of cells, plus
1/2″ 1:21/2″ cement-sand finish, total thick-
ness at top of cells, 2″ ; Ceiling: 1″ neat
gypsum plaster, back of lath 2″ or more from
underside of cellular steel.
See
Note 15
3 hrs. 1 15, 16,
17, 18
3
F/C-S-36 1″ Floor: same as F/C-S-35; Ceiling: 1″ gyp-
sum-vermiculite plaster (ratio of gypsum to
vermiculite 2:1 to 3:1), the back of lath 2″ or
more from under-side of cellular steel.
See
Note 15
4 hrs. 1 15, 16,
17, 18
4
F/C-S-37 1″ Floor: same as F/C-S-35; Ceiling: 1″ neat
gypsum plaster; back of lath 9″ or more from
underside of cellular steel.
See
Note 15
4 hrs. 1 15, 16,
17, 18
4
F/C-S-38 1″ Floor: same as F/C-S-35; Ceiling: 1″ gyp-
sum-vermiculite plaster (ratio of gypsum to
vermiculite 2:1 to 3:1), the back of lath being
9″ or more from underside of cellular steel.
See
Note 15
5 hrs. 1 15, 16,
17,18
5


(continued)

TABLE 3.2‒continued FLOOR/CEILING ASSEMBLIES‒STEEL STRUCTURAL ELEMENTS

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-S-39 3/4 Floor: asbestos paper 14 lbs./100 ft.2 cemented
to steel deck with waterproof linoleum
cement, wood screeds and 7/8″ wood floor;
Ceiling: 3/4″ sanded gypsum plaster 1:2 for
scratch coat and 1:3 for brown coat.
See
Note 19
1 hr. 1 19, 20,
21, 22
1
F/C-S-40 3/4 Floor: 11/2″, 1:2:4 portland cement concrete;
Ceiling: 3/4″ sanded gypsum plaster 1:2 for
scratch coat and 1:3 for brown coat.
See
Note 19
1 hr.
30 min.
1 19, 20,
21, 22
11/2
F/C-S-41 3/4 Floor: 2″, 1:2:4 portland cement concrete;
Ceiling: 3/4″ sanded gypsum plaster, 1:2 for
scratch coat and 1:3 for brown coat.
See
Note 19
2 hrs. 1 19, 20,
21, 22
2
F/C-S-42 1″ Floor: 2″, 1:2:4 portland cement concrete;
Ceiling: 1″ portland cement-sand plaster with
10 lbs. of hydrated lime for @ bag of cement
1:2 for scratch coat and 1:21/2″ for brown coat.
See
Note 19
2 hrs. 1 19, 20,
21, 22
2
F/C-S-43 11/2 Floor: 2″, 1:2:4 portland cement concrete;
Ceiling: 11/2″, 1:2 sanded gypsum plaster on
ribbed metal lath.
See
Note 19
2 hrs.
30 min.
1 19, 20,
21, 22
21/2
F/C-S-44 11/8 Floor: 2″, 1:2:4 portland cement concrete;
Ceiling: 11/8″, 1:1 sanded gypsum plaster.
See
Note 19
2 hrs.
30 min.
1 19, 20,
21, 22
21/2
F/C-S-45 1″ Floor: 21/2″, 1:2:4 portland cement concrete;
Ceiling: 1″, 1:2 sanded gypsum plaster.
See
Note 19
2 hrs.
30 min.
1 19, 20,
21, 22
21/2
F/C-S-46 3/4 Floor: 21/2″, 1:2:4 portland cement concrete;
Ceiling: 1″ neat gypsum plaster or 3/4″gyp-
sum-vermiculite plaster, ratio of gypsum to
vermiculite 2:1 to 3:1.
See
Note 19
3 hrs. 1 19, 20,
21, 22
3
F/C-S-47 11/8 Floor: 21/2″, 1:2:4 portland cement, sand and
cinder concrete plus 1/2″, 1:21/2″ cement-sand
finish; total thickness 3″; Ceiling: 11/8″,
1:1 sanded gypsum plaster.
See
Note 19
3 hrs. 1 19, 20,
21, 22
3
F/C-S-48 11/8 Floor: 21/2″, gas expanded portland cement-
sand concrete plus 1/2″, 1:2.5 cement-sand fin-
ish; total thickness 3″; Ceiling: 11/8″ ,
1:1 sanded gypsum plaster.
See
Note 19
3 hrs.|
30 min.
1 19, 20,
21, 22
31/2
F/C-S-49 1″ Floor: 21/2″, 1:2:4 portland cement concrete;
Ceiling: 1″ gypsum- vermiculite plaster; ratio
of gypsum to vermiculite 2:1 to 3:1.
See
Note 19
4 hrs. 1 19, 20,
21, 22
4
F/C-S-50 21/2 Floor: 2″, 1:2:4 portland cement concrete;
Ceiling: 2″ interlocking gypsum tile supported
on upper face of lower flanges of beams,
1/2″ 1:3 sanded gypsum plaster.
See
Note 19
2 hrs. 1 19, 20,
21, 22
2
F/C-S-51 21/2 Floor: 2″, 1:2:4 portland cement concrete;
Ceiling: 2″ precast metal reinforced gypsum
tile, 1/2″ 1:3 sanded gypsum plaster (tile
clipped to channels which are clipped to
lower flanges of beams).
See Note 19 4 hrs. 1 19, 20,
21, 22
4

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound per square inch = 0.00689 MPa, 1 pound per square foot = 47.9 N/m2.
Notes:
1. No protective membrane over structural steel.
2. Performance time indicates first endpoint reached only several tests were continued to points where other failures occurred.
3. Load failure.
4. Thermal failure.
5. This is an estimated time to load bearing failure. The same joist and deck specimen was used for a later test with different membrane protection.
6. Test stopped at 3 hours to reuse specimen; no endpoint reached.
7. Test stopped at 1 hour to reuse specimen; no endpoint reached.
8. All plaster used = gypsum.
9. Specimen size - 18 feet by 131/2 inches. Floor deck - base material - 1/4-inch by 18-foot steel plate welded to "I" beams.
10. "I" beams - 24 inches o.c.
11. "I" beams - 48 inches o.c.
12. Apply to open web joists, pressed steel joists or rolled steel beams, which are not stressed beyond 18,000 lbs./in.2 in flexure for open-web pressed or light rolled joists, and 20,000 lbs./in.2 for American standard or heavier rolled beams.
13. Ratio of weight of portland cement to fine and coarse aggregates combined for floor slabs shall not be less than 1:61/2.
14. Plaster for ceiling shall be applied on metal lath which shall be tied to supports to give the equivalent of single No. 18 gage steel wires 5 inches o.c.
15. Load: maximum fiber stress in steel not to exceed 16,000 psi.
16. Prefabricated units 2 feet wide with length equal to the span, composed of two pieces of No. 18 gage formed steel welded together to give four longitudinal cells.
17. Depth not less than 3 inches and distance between cells no less than 2 inches.
18. Ceiling: metal lath tied to furring channels secured to runner channels hung from cellular steel.
19. Load: rolled steel supporting beams and steel plate base shall not be stressed beyond 20,000 psi in flexure. Formed steel (with wide upper flange) construction shall not be stressed beyond 16,000 psi.
20. Some type of expanded metal or woven wire shall be embedded to prevent cracking in concrete flooring.
21. Ceiling plaster shall be metal lath wired to rods or channels which are clipped or welded to steel construction. Lath shall be no smaller than 18 gage steel wire and not more than 7 inches o.c.
22. The securing rods or channels shall be at least as effective as single 3/16-inch rods with 1-inch of their length bent over the lower flanges of beams with the rods or channels tied to this clip with 14 gage iron wire.


FIGURE 3.3 FLOOR/CEILING ASSEMBLIES‒WOOD JOIST



TABLE 3.3 FLOOR/CEILING ASSEMBLIES‒WOOD JOIST

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-W-1 3/8 12″ clear span - 2″ × 9″ wood joists; 18″ o.c.;
Deck: 1″ T&G; Filler: 3″ of ashes on 1/2″ boards
nailed to joist sides 2″ from bottom; 2″ air space;
Membrane: 3/8″ gypsum board.
60 psf 36 min. 7 1, 2 1/2
F/C-W-2 1/2 12″ clear span - 2″ × 7″ joists; 15″ o.c.; Deck: 1″
nominal lumber; Membrane: 1/2″ fiber board.
60 psf 22 min. 7 1, 2, 3 1/4
F/C-W-3 1/2 12″ clear span - 2″ × 7″ wood joists; 16″ o.c.;
2″ × 11/2″ bridging at center; Deck: 1″ T&G;
Membrane: 1/2″ fiber board; 2 coats "distemper"
paint.
30 psf 28 min. 7 1, 3, 15 1/3
F/C-W-4 3/16 12″ clear span - 2″ × 7″ wood joists; 16″ o.c.; 2″
× 11/2″ bridging at center span; Deck: 1″ nominal
lumber; Membrane: 1/2″ fiber board under 3/16
gypsum plaster.
30 psf 32 min. 7 1, 2 1/2
F/C-W-5 5/8 As per previous F/C-W-4 except membrane is
5/8″ lime plaster.
70 psf 48 min. 7 1, 2 3/4
F/C-W-6 5/8 As per previous F/C-W-5 except membrane is
5/8″ gypsum plaster on 22 gage 3/8″ metal lath.
70 psf 49 min. 7 1, 2 3/4


(continued)

TABLE 3.3‒continued FLOOR/CEILING ASSEMBLIES‒WOOD JOIST

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-W-7 1/2 As per previous F/C-W-6 except membrane is
1/2″ fiber board under 1/2″ gypsum plaster.
60 psf 43 min. 7 1, 2, 3 2/3
F/C-W-8 1/2 As per previous F/C-W-7 except membrane is
1/2″ gypsum board.
60 psf 33 min. 7 1, 2, 3 1/2
F/C-W-9 9/16 12″ clear span - 2″ × 7″ wood joists; 15″ o.c.;
2″ × 11/2″ bridging at center; Deck: 1″ nominal
lumber; Membrane: 3/8″ gypsum board;
3/16″ gypsum plaster.
60 psf 24 min. 7 1, 2, 3 1/3
F/C-W-10 5/8 As per F/C-W-9 except membrane is 5/8
gypsum plaster on wood lath.
60 psf 27 min. 7 1, 2, 3 1/3
F/C-W-11 7/8 12″ clear span - 2″ × 9″ wood joists; 15″ o.c.;
2″ × 11/2″ bridging at center span; Deck: 1″
T&G; Membrane: original ceiling joists have
3/8″ plaster on wood lath; 4″ metal hangers
attached below joists creating 15″ chases filled
with mineral wool and closed with 7/8″ plaster
(gypsum) on 3/8″ S.W.M. metal lath to form new
ceiling surface.
75 psf 1 hr.
10 min.
7 1, 2 1
F/C-W-12 7/8 12″ clear span - 2″ × 9″wood joists; 15″ o.c.;
2″ × 11/2″ bridging at center; Deck: 1″ T&G;
Membrane: 3″ mineral wood below joists;
3″ hangers to channel below joists; 7/8″ gypsum
plaster on metal lath attached to channels.
75 psf 2 hrs. 7 1, 4 2
F/C-W-13 7/8 12″ clear span - 2″ × 9″wood joists; 16″ o.c.;
2″ × 11/2″bridging at center span; Deck: 1″
T&G on 1″ bottoms on 3/4″ glass wool strips on
3/4″ gypsum board nailed to joists; Membrane:
3/4″ glass wool strips on joists; 3/8″ perforated
gypsum lath; 1/2″ gypsum plaster.
60 psf 41 min. 7 1, 3 2/3
F/C-W-14 7/8 12″ clear span - 2″ × 9″ wood joists; 15″ o.c.;
Deck: 1″ T&G; Membrane: 3″ foam concrete in
cavity on 1/2″ boards nailed to joists; wood lath
nailed to 1″ × 11/4″ straps 14 o.c. across joists;
7/8″ gypsum plaster.
60 psf 1 hr.
40 min.
7 1, 5 12/3
F/C-W-15 7/8 12″ clear span - 2″ × 9″wood joists; 18″ o.c.;
Deck: 1″ T&G; Membrane: 2″ foam concrete
on 1/2″ boards nailed to joist sides 2″ from joist
bottom; 2″ air space; 1″ × 11/4″ wood straps 14″
o.c. across joists; 7/8″ lime plaster on wood lath.
60 psf 53 min. 7 1, 2 3/4
F/C-W-16 7/8 12″ clear span -2″ × 9″ wood joists;
Deck: 1″ T&G; Membrane: 3″ ashes on 1/2
boards nailed to joist sides 2″ from joist bottom;
2″ air space; 1″ × 11/4″ wood straps 14″ o.c.;
7/8″ gypsum plaster on wood lath.
60 psf 28 min. 7 1, 2 1/3
F/C-W-17 7/8 As per previous F/C-W-16 but with lime plaster
mix.
60 psf 41 min. 7 1, 2 2/3
F/C-W-18 7/8 12″ clear span - 2″ × 9″ wood joists; 18″ o.c.;
2″ × 11/2″ bridging at center; Deck: 1″ T&G;
Membrane: 7/8″ gypsum plster on wood lath.
60 psf 36 min. 7 1, 2 1/2
F/C-W-19 7/8 As per previous F/C-W-18 except with lime
plaster membrane and deck is 1″ nominal
boards (plain edge).
60 psf 19 min. 7 1, 2 1/4


(continued)

TABLE 3.3‒continued FLOOR/CEILING ASSEMBLIES‒WOOD JOIST

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-W-20 7/8 As per F/C-W-19, except deck is 1″ T&G
boards.
60 psf 43 min. 7 1, 2 2/3
F/C-W-21 1″ 12″ clear span - 2″ × 9″wood joists; 16″
o.c.; 2″ × 11/2″ bridging at center; Deck: 1″
T&G; Membrane: 3/8″ gypsum base board;
5/8″ gypsum plaster.
70 psf 29 min. 7 1, 2 1/3
F/C-W-22 11/8 12″ clear span - 2″ × 9″ wood joists; 16″
o.c.; 2″ × 2″ wood bridging at center;
Deck: 1″ T&G; Membrane: hangers, chan-
nel with 3/8″ gypsum baseboard affixed
under 3/4″gypsum plaster.
60 psf 1 hr. 7 1, 2, 3 1
F/C-W-23 3/8 Deck: 1″ nominal lumber; Joists: 2″ × 7″;
15″ o.c.; Membrane: 3/8″ plasterboard with
plaster skim coat.
60 psf 111/2 min. 12 2, 6 1/6
F/C-W-24 1/2 Deck: 1″ T&G lumber; Joists: 2″ × 9″; 16″
o.c.; Membrane: 1/2″ plasterboard.
60 psf 18 min. 12 2, 7 1/4
F/C-W-25 1/2 Deck: 1″ T&G lumber; Joists: 2″ × 7″; 16″
o.c.; Membrane: 1/2″ fiber insulation board.
30 psf 8 min. 12 2, 8 2/15
F/C-W-26 1/2 Deck: 1″ nominal lumber; Joists: 2″ × 7″;
15″ o.c.; Membrane: 1/2″ fiber insulation
board.
60 psf 8 min. 12 2, 9 2/15
F/C-W-27 5/8 Deck: 1″ nominal lumber; Joists: 2″ × 7″;
15″ o.c.; Membrane: 5/8″ gypsum plaster on
wood lath.
60 psf 17 min. 12 2, 10 1/4
F/C-W-28 5/8 Deck: 1″ T&G lumber; Joists: 2″ × 9″; 16″
o.c.; Membrane: 1/2″ fiber insulation board;
1/2″ plaster.
60 psf 20 min. 12 2, 11 1/3
F/C-W-29 No
Membrane
Exposed wood joists. See
Note 13
15 min. 1 1, 12,
13, 14
1/4
F/C-W-30 3/8 Gypsum wallboard: 3/8″ or 1/2″ with 11/2
No. 15 gage nails with 3/16″ heads spaced
6″centers with asbestos paper applied with
paperhangers' paste and finished with
casein paint.
See
Note 13
25 min. 1 1, 12,
13, 14
1/2
F/C-W-31 1/2 Gypsum wallboard: 1/2″ with 13/4″ No. 12
gage nails with 1/2″ heads, 6″ o.c., and
finished with casein paint.
See
Note 13
25 min. 1 1, 12,
13, 14
1/2
F/C-W-32 1/2 Gypsum wallboard: 1/2″with 11/2″ No. 12
gage nails with 1/2″ heads, 18″ o.c., with
asbestos paper applied with paperhangers'
paste and secured with 11/2″ No. 15 gage
nails with 3/16″ heads and finished with
casein paint; combined nail spacing 6″ o.c.
See
Note 13
30 min. 1 1, 12,
13, 14
1/2
F/C-W-33 3/8 Gypsum wallboard: two layers 3/8″ secured
with 11/2″ No. 15 gage nails with 3/8″ heads,
6″ o.c.
See
Note 13
30 min. 1 1, 12,
13, 14
1/2
F/C-W-34 1/2 Perforated gypsum lath: 3/8″, plastered with
11/8″ No. 13 gage nails with 5/16″ heads, 4″
o.c.; 1/2″ sanded gypsum plaster.
See
Note 13
30 min. 1 1, 12,
13, 14
1/2
F/C-W-35 1/2 Same as F/C-W-34, except with 11/8
No. 13 gage nails with 3/8″ heads, 4″ o.c.
See
Note 13
45 min. 1 1, 12,
13, 14
3/4


(continued)

TABLE 3.3‒continued FLOOR/CEILING ASSEMBLIES‒WOOD JOIST

ITEM
CODE
MEMBRANE
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-W-36 1/2 Perforated gypsum lath: 3/8″ , nailed with
11/8″No. 13 gage nails with 3/8″ heads, 4″
o.c.; joints covered with 3″ strips of metal
lath with 13/4″ No. 12 nails with 1/2″ heads,
5″ o.c.; 1/2″ sanded gypsum plaster.
See
Note 13
1 hr. 1 1, 12,
13, 14
1
F/C-W-37 1/2 Gypsum lath: 3/8″and lower layer of 3/8
perforated gypsum lath nailed with 13/4
No. 13 nails with 5/16″ heads, 4″ o.c.; 1/2
sanded gypsum plaster or 1/2″ portland
cement plaster.
See
Note 13
45 min. 1 1, 12,
13, 14
3/4
F/C-W-38 3/4 Metal lath: nailed with 11/4″ No. 11 nails
with 3/8″ heads or 6d common driven 1″
and bent over, 6″ o.c.; 3/4″ sanded gypsum
plaster.
See
Note 13
45 min. 1 1, 12,
13, 14
3/4
F/C-W-39 3/4 Same as F/C-W-38, except nailed with
11/2″ No. 11 barbed roof nails with 7/16
heads, 6″ o.c.
See
Note 13
1 hr. 1 1, 12,
13, 14
1
F/C-W-40 3/4 Same as F/C-W-38, except with lath nailed
to joists with additional supports for lath
27″ o.c.; attached to alternate joists and
consisting of two nails driven 11/4″, 2″
above bottom on opposite sides of the
joists, one loop of No. 18 wire slipped over
each nail; the ends twisted together below
lath.
See
Note 13
1 hr.
15 min.
1 1, 12,
13, 14
11/4
F/C-W-41 3/4 Metal lath: nailed with 11/2″ No. 11 barbed
roof nails with 7/16″ heads, 6 o.c., with 3/4
portland cement plaster for scratch coat
and 1:3 for brown coat, 3 lbs. of asbestos
fiber and 15 lbs. of hydrated lime/94 lbs.
bag of cement.
See
Note 13
1 hr. 1 1, 12,
13, 14
1
F/C-W-42 3/4 Metal lath: nailed with 8d, No. 111/2 gage
barbed box nails, 21/2″ driven, 11/4″ on
slant and bent over, 6″ o.c.; 3/4″ sanded
gypsum plaster, 1:2 for scratch coat and
1:3 for below coat.
See
Note 13
1 hr. 1 1, 12,
13, 14
1

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound per square inch = 0.00689 MPa, 1 pound per square foot = 47.9 N/m2.
Notes:
1. Thickness indicates thickness of first membrane protection on ceiling surface.
2. Failure mode‒flame thru.
3. Failure mode‒collapse.
4. No endpoint reached at termination of test.
5. Failure imminent‒test terminated.
6. Joist failure‒11.5 minutes; flame thru‒13 minutes; collapse‒24 minutes.
7. Joist failure‒17 minutes; flame thru‒18 minutes; collapse‒33 minutes.
8. Joist failure‒18 minutes; flame thru‒8 minutes; collapse‒30 minutes.
9. Joist failure‒12 minutes; flame thru‒8 minutes; collapse‒22 minutes.
10. Joist failure‒11 minutes; flame thru‒17 minutes; collapse‒27 minutes.
11. Joist failure‒17 minutes; flame thru‒20 minutes; collapse‒43 minutes.
12. Joists: 2-inch by 10-inch southern pine or Douglas fir; No. 1 common or better. Subfloor: 3/4-inch wood sheating diaphragm of asbestos
paper, and finish of tongue-and-groove wood flooring.
13. Loadings: not more than 1,000 psi maximum fiber stress in joists.
14. Perforations in gypsum lath are to be not less than 3/4-inch diameter with one perforation for not more than 16/in.2 diameter.
15. "Distemper" is a British term for a water-based paint such as white wash or calcimine.


FIGURE 3.4 FLOOR/CEILING ASSEMBLIES‒HOLLOW CLAY TILE WITH REINFORCED CONCRETE



TABLE 3.4 FLOOR/CEILING ASSEMBLIES‒HOLLOW CLAY TILE WITH REINFORCED CONCRETE

ITEM
CODE
ASSEMBLY
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-HT-1 6″ Cover: 11/2″ concrete (6080 psi); three cell
hollow clay tiles, 12″ × 12″ × 4″; 31/4″ concrete
between tiles including two 1/2″ rebars with 3/4
concrete cover; 1/2″ plaster cover, lower.
75 psf 2 hrs.
7 min.
7 1, 2, 3 2
F/C-HT-2 6″ Cover: 11/2″ concrete (5840 psi); three cell
hollow clay tiles, 12″ × 12″ × 4″; 31/4″ concrete
between tiles including two 1/2″ rebars each
with 1/2″ concrete cover and 5/8″ filler tiles
between hollow tiles; 1/2″ plaster cover, lower.
61 psf 3 hrs.
23 min.
7 3, 4, 6 31/3
F/C-HT-3 6″ Cover: 11/2″concrete (6280 psi); three cell
hollow clay tiles, 12″ × 12″ × 4″; 31/4″ concrete
between tiles including two 1/2″ rebars with 1/2
cover; 1/2″ plaster cover, lower.
122 psf 2 hrs. 7 1, 3, 5,
8
2
F/C-HT-4 6″ Cover: 11/2″ concrete (6280 psi); three cell
hollow clay tiles, 12″ × 12″ × 4″; 31/4″ concrete
between tiles including two 1/2″ rebars with 3/4
cover; 1/2″ plaster cover, lower.
115 psf 2 hrs.
23 min.
7 1, 3, 7 21/3
F/C-HT-5 6″ Cover: 11/2″ concrete (6470 psi); three cell
hollow clay tiles, 12″ × 12″ × 4″; 31/4″ concrete
between tiles including two 1/2″ rebars with 1/2
cover; 1/2″ plaster cover, lower.
122 psf 2 hrs. 7 1, 3, 5,
8
2


(continued)

TABLE 3.4‒continued FLOOR/CEILING ASSEMBLIES‒HOLLOW CLAY TILE WITH REINFORCED CONCRETE

ITEM
CODE
ASSEMBLY
THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
F/C-HT-6 8″ Floor cover: 11/2″ gravel cement (4300 psi);
three cell, 12″ × 12″ × 6″ ; 31/2″ space between
tiles including two 1/2″ rebars with 1″ cover
from concrete bottom; 1/2″ plaster cover, lower.
165 psf 4 hrs. 7 1, 3, 9,
10
4
F/C-HT-7 9″ (nom.) Deck: 7/8″T&G on 2″ × 11/2″ bottoms
(18″ o.c.) 11/2″ concrete cover (4600 psi); three
cell hollow clay tiles, 12″ × 12″ × 4″; 3″
concrete between tiles including one 3/4″ rebar
3/4″ from tile bottom; 3/4″ plaster cover.
95 psf 2 hrs.
26 min.
7 4, 11,
12, 13
21/3
F/C-HT-8 9″ (nom.) Deck: 7/8″ T&G on 2″ × 11/2″ bottoms (18″
o.c.) 11/2″ concrete cover (3850 psi); three cell
hollow clay tiles, 12″ × 12″ × 4″;
3″ concrete between tiles including
one 3/4″ rebar 3/4″ from tile bottoms;
1/2″ plaster cover.
95 psf 3 hrs.
28 min.
7 4, 11,
12, 13
F/C-HT-9 9″(nom.) Deck: 7/8″ T&G on 2″ × 11/2″ bottoms (18″
o.c.) 11/2″ concrete cover (4200 psi); three cell
hollow clay tiles, 12″ × 12″ × 4″;
3″ concrete between tiles including
one 3/4″ rebar 3/4″ from tile bottoms;
1/2″ plaster cover.
95 psf 2 hrs.
14 min.
7 3, 5, 8,
11
F/C-HT-10 51/2 Fire clay tile (4″ thick); 11/2″ concrete cover;
for general details, see Note 15.
See
Note 14
1 hr. 43 15 1
F/C-HT-11 8″ Fire clay tile (6″ thick); 2″ cover. See
Note 14
1 hr. 43 15 1
F/C-HT-12 51/2 Fire clay tile (4″ thick); 11/2″ cover;
5/8″ gypsum plaster, lower.
See
Note 14
1 hr.
30 min.
43 15 11/2
F/C-HT-13 8″ Fire clay tile (6″ thick); 2″ cover;
5/8″gypsum plaster, lower.
See
Note 14
2 hrs. 43 15 11/2

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound per square inch = 0.00689 MPa, 1 pound per square foot = 47.9 N/m2.

Notes:


1. A generalized cross section of this floor type follows:
2. Failure mode - structural.
3. Plaster: base coat‒lime-cement-sand; top coat‒gypsum (neat).
4. Failure mode‒collapse.
5. Test stopped before any endpoints were reached.
6. A generalized cross section of this floor type follows:


7. Failure mode‒thermal‒back face temperature rise.
8. Passed hose stream test.
9. Failed hose stream test.


10. Test stopped at 4 hours before any endpoints were reached.
11. A generalized cross section of this floor type follows:
12. Plaster: base coat‒retarded hemihydrate gypsum-sand; second coat‒neat gypsum.
13. Concrete in Item 7 is P.C. based but with crushed brick aggregates while in Item 8 river sand and river gravels are used with the P.C.
14. Load - unspecified.
15. The 12-inch by 12-inch fire-clay tiles were laid end to end in rows spaced 21/2 inches or 4 inches apart. The reinforcing steel was placed between these rows and the concrete cast around them and over the tile to form the structural floor.


SECTION IV BEAMS

TABLE 4.1.1 REINFORCED CONCRETE BEAMS DEPTH 10″ TO LESS THAN 12″

ITEM CODE DEPTH CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
B-11-RC-1 11″ 24″ wide × 11″ deep reinforced concrete "T"
beam (3290 psi); Details: see Note 5 figure.
8.8 tons 4 hrs.
2 min.
7 1, 2, 14 4
B-10-RC-2 10″ 24″ wide × 10″ deep reinforced concrete "T"
beam (4370 psi); Details: see Note 6 figure.
8.8 tons 1 hr.
53 min.
7 1, 3 13/4
B-10-RC-3 101/2 24″ wide × 101/2″ deep reinforced concrete
"T" beam (4450 psi); Details: see Note 7 figure.
8.8 tons 2 hrs.
40 min.
7 1, 3 22/3
B-11-RC-4 11″ 24″ wide × 11″ deep reinforced concrete "T"
beam (2400 psi); Details: see Note 8 figure.
8.8 tons 3 hrs.
32 min.
7 1, 3, 14 31/2
B-11-RC-5 11″ 24″ wide × 11″ deep reinforced concrete "T"
beam (4250 psi); Details: see Note 9 figure.
8.8 tons 3 hrs.
3 min.
7 1, 3, 14 3
B-11-RC-6 11″ Concrete flange: 4″ deep × 2″ wide (4895
psi) concrete; Concrete beam: 7″ deep × 61/2
wide beam; "I" beam reinforcement; 10″ ×
41/2″ × 25 lbs. R.S.J.; 1″ cover on flanges;
Flange reinforcement: 3/8″ diameter bars at
6″ pitch parallel to "T"; 1/4″ diameter bars
perpendicular to "T"; Beam reinforcement:
4″ × 6″ wire mesh No. 13 SWG; Span: 11″
restrained; Details: see Note 10 figure.
10 tons 6 hrs. 7 1, 4 6
B-11-RC-7 11″ Concrete flange: 6″ deep × 1″ 61/2″ wide
(3525 psi) concrete; Concrete beam: 5″ deep
× 8″ wide precast concrete blocks 83/4″ long;
"I" beam reinforcement; 7″ × 4″ × 16 lbs.
R.S.J.; 2″ cover on bottom; 11/2″ cover on
top; Flange reinforcement: two rows 1/2
diameter rods parallel to "T"; Beam
reinforcement: 1/8″ wire mesh perpendicular
to 1″ ; Span: 1″ 3″ simply supported;
Details: see Note 11 figure.
3.9 tons 4 hrs. 7 1, 2 4
B-11-RC-8 11″ Concrete flange: 4″ deep × 2″ wide (3525
psi) concrete; Concrete beam 7″ deep × 41/2
wide; (scaled from drawing); "I" beam
reinforcement; 10″ × 41/2″ × 25 lbs.
R.S.J.; no concrete cover on bottom; Flange
reinforcement: 3/8″ diameter bars at 6 pitch
parallel to "T"; 1/4″ diameter bars
perpendicular to "T"; Span: 11″ restricted.
10 tons 4 hrs. 7 1, 2, 12 4
B-11-RC-9 111/2 24″ wide × 111/2″ deep reinforced concrete
"T" beam (4390 psi); Details: see Note 12
figure.
8.8 tons 3 hrs.
24 min.
7 1, 3 31/3

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Load concentrated at mid span.
2. Achieved 4 hour performance (Class "B," British).
3. Failure mode‒collapse.
4. Achieved 6 hour performance (Class "A," British).
5.
6.
7.
8.
9.
10.
11.
12.
13.
14. The different performances achieved by B-11-RC-1, B-11-RC-4 and B-11-RC-5 are attributable to differences in concrete aggregate compositions reported in the source document but unreported in this table. This demonstrates the significance of material composition in addition to other details.


TABLE 4.1.2 REINFORCED CONCRETE BEAMS DEPTH 12″ TO LESS THAN 14″

ITEM
CODE
DEPTH CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
B-12-RC-1 12″ 12″ × 8″ section; 4160 psi aggregate concrete; Reinforcement: 4-7/8″ rebars at corners; 1″ below each surface; 1/4″ stirrups 10″ o.c. 5.5 tons 2 hrs. 7 1 2
B-12-RC-2 12″ Concrete flange: 4″ deep × 2″ wide (3045 psi) concrete at 35 days; Concrete beam: 8″ deep; "I" beam reinforcement: 10″ × 41/2″ × 25 lbs. R.S.J.; 1″ cover on flanges; Flange reinforcement: 3/8″ diameter bars at 6″ pitch parallel to "T"; 1/4″ diameter bars perpendicular to "T"; Beam reinforcement: 4″ × 6″ wire mesh No. 13 SWG; Span: 10″ 3″ simply supported. 10 tons 4 hrs. 7 2, 3, 5 4
B-13-RC-3 13″ Concrete flange: 4″ deep × 2″ wide (3825 psi) concrete at 46 days; Concrete beam: 9″ deep × 81/2″ wide; (scaled from drawing); "I" beam reinforcement: 10″ × 41/2″ × 25 lbs. R.S.J.; 3″ cover on bottom flange; 1″ cover on top flange; Flange reinforcement: 3/8″ diameter bars at 6″ pitch parallel to "T"; 1/4″ diameter bars perpendicular to "T"; Beam reinforcement: 4″ × 6″ wire mesh No. 13 SWG; Span: 11″ restrained. 10 tons 6 hrs. 7 2, 3, 6,
8, 9
4
B-12-RC-4 12″ Concrete flange: 4″ deep × 2″ wide (3720 psi) concrete at 42 days; Concrete beam: 8″ deep × 81/2″ wide; (scaled from drawing); "I" beam reinforcement: 10″ × 41/2″ × 25 lbs. R.S.J.; 2″ cover bottom flange; 1″ cover top flange; Flange reinforcement: 3/8″ diameter bars at 6″ pitch parallel to "T"; 1/4″ diameter bars perpendicular to "T"; Beam reinforcement: 4″ × 6″ wire mesh No. 13 SWG; Span: 11″ restrained. 10 tons 6 hrs. 7 1, 3, 4,
7, 8, 9
4

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Qualified for 2 hour use. (Grade "C," British) Test included hose stream and reload at 48 hours.
2. Load concentrated at mid span.
3. British test.
4. British test‒qualified for 6 hour use (Grade "A").
5.
6.
7.
8. See Table 4.1.3, Note 5.
9. Hourly rating based upon B-12-RC-2 above.


TABLE 4.1.3 REINFORCED CONCRETE BEAMS DEPTH 14″ TO LESS THAN 16″

ITEM
CODE
DEPTH CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92
B-15-RC-1 15″ Concrete flange: 4″ deep × 2″ wide (3290 psi) concrete; Concrete beam: 10″ deep × 81/2″ wide; "I" beam reinforcement: 10″ × 41/2″ × 25 lbs. R.S.J.; 4″ cover on bottom flange; 1″ cover on top flange; Flange reinforcement: 3/8″ diameter bars at 6″ pitch parallel to "T"; 1/4″ diameter bars perpendicular to "T"; Beam reinforcement: 4″ × 6″ wire mesh No. 13 SWG; Span: 11″ restrained. 10 tons 6 hrs. 7 1, 2, 3
5, 6
4
B-15-RC-2 15″ Concrete flange: 4″ deep × 2″ wide (4820 psi) concrete; Concrete beam: 10″ deep × 81/2″ wide; "I" beam reinforcement: 10″ × 41/2″ × 25 lbs. R.S.J.; 1″ cover over wire mesh on bottom flange; 1″ cover on top flange; Flange reinforcement: 3/8″ diameter bars at 6″ pitch parallel to "T"; 1/4″ diameter bars perpendicular to "T"; Beam reinforcement: 4″ × 6″ wire mesh No. 13 SWG; Span: 11″ restrained. 10 tons 6 hrs. 7 1, 2, 4,
5, 6
4

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Load concentrated at mid span.
2. Achieved 6 hour fire rating (Grade "A," British).
3.
4.
5. Section 43.147 of the 1979 edition of the Uniform Building Code Standards provides:
"A restrained condition in fire tests, as used in this standard, is one in which expansion at the supports of a load-carrying element resulting from the effects of the fire is resisted by forces external to the element. An unrestrained condition is one in which the load-carrying element is free to expand and rotate at its support."
"Restraint in buildings is defined as follows: Floor and roof assemblies and individual beams in buildings shall be considered restrained when the surrounding or supporting structure is capable of resisting the thermal expansion throughout the range of anticipated elevated temperatures. Construction not complying . . . is assumed to be free to rotate and expand and shall be considered as unrestrained."
"Restraint may be provided by the lateral stiffness of supports for floor and roof assemblies and intermediate beams forming part of the assembly. In order to develop restraint, connections must adequately transfer thermal thrusts to such supports. The rigidity of adjoining panels or structures shall be considered in assessing the capability of a structure to resist therm expansion."
Because it is difficult to determine whether an existing building's structural system is capable of providing the required restraint, the lower hourly ratings of a similar but unrestrained assembly have been recommended.
6. Hourly rating based upon Table 4.2.1, Item B-12-RC-2.


TABLE 4.2.1 REINFORCED CONCRETE BEAMS‒UNPROTECTED DEPTH 10″ TO LESS THAN 12″

ITEM
CODE
DEPTH CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST-BMS-92
B-SU-1 10″ 10″ × 41/2″ × 25 lbs. "I" beam. 10 tons 39 min. 7 1 1/3

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.
Notes:
1. Concentrated at mid span.


TABLE 4.2.2 STEEL BEAMS‒CONCRETE PROTECTION DEPTH 10″ TO LESS THAN 12″

ITEM CODE DEPTH CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC. HOURS
LOAD TIME PRE- BMS-92 BMS-92 POST- BMS-92
B-SC-1 10″ 10″ × 8″ rectangle; aggregate concrete (4170 psi) with 1″ top cover and 2″ bottom cover;
No. 13 SWG iron wire loosely wrapped at approximately 6″ pitch about 7″ × 4″ × 16 lbs. "I" beam.
3.9 tons 3 hrs.
46 min.
7 1, 2, 3 33/4
B-SC-1 10″ 10″ × 8″ rectangle; aggregate concrete (3630 psi) with 1″ top cover and 2″ bottom cover;
No. 13 SWG iron wire loosely wrapped at approximately 6″ pitch about 7″ × 4″ × 16 lbs. "I" beam.
5.5 tons 5 hrs.
26 min.
7 1, 4, 5,
6, 7
33/4

For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
1. Load concentrated at mid span.
2. Specimen 10-foot 3-inch clear span simply supported.
3. Passed Grade "C" fire resistance (British) including hose stream and reload.
4. Specimen 11-foot clear span‒restrained.
5. Passed Grade "B" fire resistance (British) including hose stream and reload.
6. See Table 4.1.3, Note 5.
7. Hourly rating based upon B-SC-1 above.


SECTION V DOORS

FIGURE 5.1 RESISTANCE OF DOORS TO FIRE EXPOSURE



TABLE 5.1 RESISTANCE OF DOORS TO FIRE EXPOSURE

ITEM CODE DOOR
MINIMUM THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
(MIN.)
EFFECTIVE
BARRIER
EDGE FLAMING PRE- BMS-92 BMS-92 POST- BMS-92
D-1 3/8 Panel door; pine perimeter (13/8″); painted (enamel). 5 min.
10 sec.
N/A 90 1, 2 5
D-2 3/8 As above, with two coats U.L. listed intumescent coating. 5 min.
30 sec.
5 min. 90 1, 2, 7 5
D-3 3/8 As D-1, with standard primer and flat interior paint. 5 min.
55 sec.
N/A 90 1, 3, 4 5
D-4 25/8 As D-1, with panels covered each side with 1/2″ plywood; edge grouted with sawdust filled plaster; door faced with 1/8″ hardboard each side; paint see (5). 11 min.
15 sec.
3 min.
45 sec.
90 1, 2, 5,
7
10


(continued)

TABLE 5.1‒continued RESISTANCE OF DOORS TO FIRE EXPOSURE

ITEM CODE DOOR
MINIMUM THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
(MIN.)
EFFECTIVE
BARRIER
EDGE FLAMING PRE- BMS-92 BMS-92 POST- BMS-92
D-5 3/8 As D-1, except surface protected with glass fiber reinforced intumescent fire retardant coating. 16 min. N/A 90 1, 3, 4,
7
15
D-6 15/8 Door detail: As D-4, except with 1/8″ cement asbestos board facings with aluminum foil; door edges protected by sheet metal. 17 min. 10 min.
15 sec.
90 1, 3, 4 15
D-7 15/8 Door detail with 1/8″ hardboard cover each side as facings; glass fiber reinforced intumescent coating applied. 20 min. N/A 90 1, 3, 4,
7
20
D-8 15/8 Door detail same as D-4; paint was glass reinforced epoxy intumescent. 26 min. 24 min.
45 sec.
90 1, 3, 4,
6, 7
25
D-9 15/8 Door detail same as D-4 with facings of 1/8″ cement asbestos board. 29 min. 3 min.
15 sec.
90 1, 2 5
D-10 15/8 As per D-9. 31 min.
30 sec.
7 min.
20 sec.
90 1, 3, 4 6
D-11 15/8 As per D-7; painted with epoxy intumescent coating including glass fiber roving. 36 min.
25 sec.
N/A 90 1, 3, 4 35
D-12 15/8 As per D-4 with intumescent fire retardant paint. 37 min.
30 sec.
24 min.
40 sec.
90 1, 3, 4 30
D-13 11/2
(nom.)
As per D-4, except with 24 ga. galvanized sheet metal facings. 39 min. 39 min. 90 1, 3, 4 39
D-14 15/8 As per D-9. 41 min.
30 sec.
17 min.
20 sec.
90 1, 3, 4,
6
20
D-15 Class C steel fire door. 60 min. 58 min. 90 7, 8 60
D-16 Class B steel fire door. 60 min. 57 min. 90 7, 8 60
D-17 13/4 Solid core flush door; core staves laminated to facings but not each other; Birch plywood facings 1/2″ rebate in door frame for door; 3/32″ clearance between door and wood frame. 15 min. 13 min. 37 11 13


(continued)

TABLE 5.1‒continued RESISTANCE OF DOORS TO FIRE EXPOSURE

ITEM CODE DOOR
MINIMUM THICKNESS
CONSTRUCTION DETAILS PERFORMANCE REFERENCE NUMBER NOTES REC.
(MIN.)
EFFECTIVE
BARRIER
EDGE FLAMING PRE- BMS-92 BMS-92 POST- BMS-92
D-18 13/4 As per D-17. 14 min. 13 min. 37 11 13
D-19 13/4 Door same as D-17, except with 16 ga. steel; 3/32″ door frame clearance. 12 min. 37 9, 11 10
D-20 13/4 As per D-19. 16 min. 37 10, 11 10
D-21 13/4 Doors as per D-17; intumescent paint applied to top and side edges. 26 min. 37 11 25
D-22 13/4 Door as per D-17, except with 1/2″ × 1/8″ steel
strip set into edges of door at top and side facing stops;
matching strip on stop.
18 min. 6 min. 37 11 18
D-23 13/4 Solid oak door. 36 min. 22 min. 15 13 25
D-24 17/8 Solid oak door. 45 min. 35 min. 15 13 35
D-25 17/8 Solid teak door. 58 min. 34 min. 15 13 35
D-26 17/8 Solid (pitch) pine door. 57 min. 36 min. 15 13 35
D-27 17/8 Solid deal (pine) door. 57 min. 30 min. 15 13 30
D-28 17/8 Solid mahogany door. 49 min. 40 min. 15 13 45
D-29 17/8 Solid poplar door. 24 min. 3 min. 15 13, 14 5
D-30 17/8 Solid oak door. 40 min. 33 min. 15 13 35
D-31 17/8 Solid walnut door. 40 min. 15 min. 15 13 20
D-32 25/8 Solid Quebec pine. 60 min. 60 min. 15 13 60
D-33 25/8 Solid pine door. 55 min. 39 min. 15 13 40
D-34 25/8 Solid oak door. 69 min. 60 min. 15 13 60
D-35 25/8 Solid teak door. 65 min. 17 min. 15 13 60
D-36 11/2 Solid softwood door. 23 min. 8.5 min. 15 13 10
D-37 3/4 Panel door. 8 min. 7.5 min. 15 13 5
D-38 5/16 Panel door. 5 min. 5 min. 15 13 5
D-39 3/4 Panel door, fire retardant treated. 171/2min. 3 min. 15 13 8
D-40 3/4 Panel door, fire retardant treated. 81/2min. 81/2min. 15 13 8
D-41 3/4 Panel door, fire retardant treated. 163/4min. 111/2min. 15 13 8

For SI: 1 inch = 25.4 mm, 1 foot = 305 mm.
Notes:
1. All door frames were of standard lumber construction.
2. Wood door stop protected by asbestos millboard.
3. Wood door stop protected by sheet metal.
4. Door frame protected with sheet metal and weather strip.
5. Surface painted with intumescent coating.
6. Door edge sheet metal protected.
7. Door edge intumescent paint protected.
8. Formal steel frame and door stop.
9. Door opened into furnace at 12 feet.
10. Similar door opened into furnace at 12 feet.
11. The doors reported in these tests represent the type contemporaries used as 20-minute solid-core wood doors. The test results demonstrate the necessity of having wall anchored metal frames, minimum cleaners possible between door, frame and stops. They also indicate the utility of long throw latches and the possible use of intumescent paints to seal doors to frames in event of a fire.
12. Minimum working clearance and good latch closure are absolute necessities for effective containment for all such working door assemblies.
13. Based on British tests.
14. Failure at door-frame interface.


BIBLIOGRAPHY

1. Central Housing Committee on Research, Design, and Construction; Subcommittee on Fire Resistance Classifications, "Fire-Resistance Classifications of Building Constructions," Building Materials and Structures, Report BMS 92, National Bureau of Standards, Washington, Oct. 1942. (Available from NTIS No. COM-73-10974)

2. Foster, H. D., Pinkston, E. R., and Ingberg, S. H., "Fire Resistance of Structural Clay Tile Partitions," Building Materials and Structures, Report BMS 113, National Bureau of Standards, Washington, Oct. 1948.

3. Ryan, J. V., and Bender, E.W., "Fire Endurance of Open-Web Steel-Joist Floors with Concrete Slabs and Gypsum Ceilings," Building Materials and Structures, Report BMS 141, National Bureau of Standards, Washington, Aug. 1954.

4. Mitchell, N. D., "Fire Tests of Wood-Framed Walls and Partitions with Asbestos-Cement Facings," Building Materials and Structures, Report BMS 123, National Bureau of Standards, Washington, May 1951.

5. Robinson, H. E., Cosgrove, L. A., and Powell, F. J., "Thermal Resistance of Airspace and Fibrous Insulations Bounded by Reflective Surfaces," Building Materials and Structures, Report BMS 151, National Bureau of Standards, Washington, Nov. 1957.

6. Shoub, H., and Ingberg, S. H., "Fire Resistance of Steel Deck Floor Assemblies," Building Science Series, 11, National Bureau of Standards, Washington, Dec. 1967.

7. Davey, N., and Ashton, L. A., "Investigations on Building Fires, Part V: Fire Tests of Structural Elements," National Building Studies, Research Paper, No. 12, Dept. of Scientific and Industrial Research (Building Research Station), London, 1953.

8. National Board of Fire Underwriters, Fire Resistance Ratings of Beam, Girder, and Truss Protections, Ceiling Constructions, Column Protections, Floor and Ceiling Constructions, Roof Constructions, Walls and Partitions, New York, April 1959.

9. Mitchell, N.D., Bender, E.D., and Ryan, J.V., "Fire Resistance of Shutters for Moving-Stairway Openings," Building Materials and Structures, Report BMS 129, National Bureau of Standards, Washington, March 1952.

10. National Board of Fire Underwriters, National Building Code; an Ordinance Providing for Fire Limits, and Regulations Governing the Construction, Alteration, Equipment, or Removal of Buildings or Structures, New York, 1949.

11. Department of Scientific and Industrial Research and of the Fire Offices' Committee, Joint Committee of the Building Research Board, "Fire Gradings of Buildings, Part I: General Principles and Structural Precautions," Post-War Building Studies, No. 20, Ministry of Works, London, 1946.

12. Lawson, D. I., Webster, C. T., and Ashton, L. A., "Fire Endurance of Timber Beams and Floors," National Building Studies, Bulletin, No. 13, Dept. of Scientific and Industrial Research and Fire Offices' Committee (Joint Fire Research Organization), London, 1951.

13. Parker, T. W., Nurse, R. W., and Bessey, G. E., "Investigations on Building Fires. Part I: The Estimation of the Maximum Temperature Attained in Building Fires from Examination of the Debris, and Part II: The Visible Change in Concrete or Mortar Exposed to High Temperatures," National Building Studies, Technical Paper, No. 4, Dept. of Scientific and Industrial Research (Building Research Station), London, 1950.

14. Bevan, R. C., and Webster, C. T., "Investigations on Building Fires, Part III: Radiation from Building Fires," National Building Studies, Technical Paper, No. 5, Dept. of Scientific and Industrial Research (Building Research Station), London, 1950.

15. Webster, D. J., and Ashton, L. A., "Investigations on Building Fires, Part IV: Fire Resistance of Timber Doors," National Building Studies, Technical Paper, No. 6, Dept. of Scientific and Industrial Research (Building Research Station), London, 1951.

16. Kidder, F. E., Architects' and Builders' Handbook: Data for Architects, Structural Engineers, Contractors, and Draughtsmen, comp. by a Staff of Specialists and H. Parker, editor-in-chief, 18th ed., enl., J. Wiley, New York, 1936.

17. Parker, H., Gay, C. M., and MacGuire, J. W., Materials and Methods of Architectural Construction, 3rd ed., J. Wiley, New York, 1958.

18. Diets, A. G. H., Dwelling House Construction, The MIT Press, Cambridge, 1971.

19. Crosby, E. U., and Fiske, H. A., Handbook of Fire Protection, 5th ed., The Insurance Field Company, Louisville, Ky., 1914.

20. Crosby, E. U., Fiske, H. A., and Forster, H.W., Handbook of Fire Protection, 8th ed., R. S. Moulton, general editor, National Fire Protection Association, Boston, 1936.

21. Kidder, F. E., Building Construction and Superintendence, rev. and enl., by T. Nolan, W. T. Comstock, New York, 1909-1913, 2 vols.

22. National Fire Protection Association, Committee on Fire-Resistive Construction, The Baltimore Conflagration, 2nd ed., Chicago, 1904.

23. Przetak, L., Standard Details for Fire-Resistive Building Construction, McGraw-Hill Book Co., New York, 1977.

24. Hird, D., and Fischl, C. F., "Fire Hazard of Internal Linings," National Building Studies, Special Report, No. 22, Dept. of Scientific and Industrial Research and Fire Offices' Committee (Joint Fire Research Organization), London, 1954.

25. Menzel, C. A., Tests of the Fire-Resistance and Strength of Walls Concrete Masonry Units, Portland Cement Association, Chicago, 1934.

26. Hamilton, S. B., "A Short History of the Structural Fire Protection of Buildings Particularly in England," National Building Studies, Special Report, No. 27, Dept. of Scientific and Industrial Research (Building Research Station), London, 1958.

27. Sachs, E. O., and Marsland, E., "The Fire Resistance of Doors and Shutters being Tabulated Results of Fire Tests Conducted by the Committee," Journal of the British Fire Prevention Committee, No. VII, London, 1912.

28. Egan, M. D., Concepts in Building Firesafety, J. Wiley, New York, 1978.

29. Sachs, E. O., and Marsland, E., "The Fire Resistance of Floors being Tabulated Results of Fire Tests Conducted by the Committee," Journal of the British Fire Prevention Committee, No. VI, London, 1911.

30. Sachs, E. O., and Marsland, E., "The Fire Resistance of Partitions being Tabulated Results of Fire Tests Conducted by the Committee," Journal of the British Fire Prevention Committee, No. IX, London, 1914.

31. Ryan, J. V., and Bender, E. W., "Fire Tests of Precast Cellular Concrete Floors and Roofs," National Bureau of Standards Monograph, 45, Washington, April 1962.

32. Kingberg, S. H., and Foster, H. D., "Fire Resistance of Hollow Load-Bearing Wall Tile," National Bureau of Standards Research Paper, No. 37, (Reprint from NBS Journal of Research, Vol. 2) Washington, 1929.

33. Hull, W. A., and Ingberg, S. H., "Fire Resistance of Concrete Columns," Technologic Papers of the Bureau of Standards, No. 272, Vol. 18, Washington, 1925, pp. 635-708.

34. National Board of Fire Underwriters, Fire Resistance Ratings of Less than One Hour, New York, Aug. 1956.

35. Harmathy, T. Z., "Ten Rules of Fire Endurance Rating," Fire Technology, Vol. 1, May 1965, pp. 93-102.

36. Son, B. C., "Fire Endurance Test on a Steel Tubular Column Protected with Gypsum Board," National Bureau of Standards, NBSIR, 73-165, Washington, 1973.

37. Galbreath, M., "Fire Tests of Wood Door Assemblies," Fire Study, No. 36, Div. of Building Research, National Research Council Canada, Ottawa, May 1975.

38. Morris, W. A., "An Investigation into the Fire Resistance of Timber Doors," Fire Research Note, No. 855, Fire Research Station, Boreham Wood, Jan. 1971.

39. Hall, G. S., "Fire Resistance Tests of Laminated Timber Beams," Timber Association Research Report, WR/RR/1, High Sycombe, July 1968.

40. Goalwin, D. S., "Fire Resistance of Concrete Floors," Building Materials and Structures, Report BMS 134, National Bureau of Standards, Washington, Dec. 1952.

41. Mitchell, N. D., and Ryan, J. V., "Fire Tests of Steel Columns Encased with Gypsum Lath and Plaster," Building Materials and Structures, Report BMS 135, National Bureau of Standards, Washington, April 1953.

42. Ingberg, S. H., "Fire Tests of Brick Walls," Building Materials and Structures, Report BMS 143, National Bureau of Standards, Washington, Nov. 1954.

43. National Bureau of Standards, "Fire Resistance and Sound-Insulation Ratings for Walls, Partitions, and Floors," Technical Report on Building Materials, 44, Washington, 1944.

44. Malhotra, H. L., "Fire Resistance of Brick and Block Walls," Fire Note, No. 6, Ministry of Technology and Fire Offices' Committee Joint Fire Research Organization, London, HMSO, 1966.

45. Mitchell, N. D., "Fire Tests of Steel Columns Protected with Siliceous Aggregate Concrete," Building Materials and Structures, Report BMS 124, National Bureau of Standards, Washington, May 1951.

46. Freitag, J. K., Fire Prevention and Fire Protection as Applied to Building Construction; a Handbook of Theory and Practice, 2nd ed., J. Wiley, New York, 1921.

47. Ingberg, S. H., and Mitchell, N. D., "Fire Tests of Wood and Metal-Framed Partition," Building Materials and Structures, Report BMS 71, National Bureau of Standards, Washington, 1941.

48. Central Housing Committee on Research, Design, and Construction, Subcommittee on Definitions, "A Glossary of Housing Terms," Building Materials and Structures, Report BMS 91, National Bureau of Standards, Washington, Sept. 1942.

49. Crosby, E. U., Fiske, H. A., and Forster, H.W., Handbook of Fire Protection, 7th ed., D. Van Nostrand Co., New York 1924.

50. Bird, E. L., and Docking, S. J., Fire in Buildings, A. & C. Black, London, 1949.

51. American Institute of Steel Construction, Fire Resistant Construction in Modern Steel-Framed Buildings, New York, 1959.

52. Central Dockyard Laboratory, "Fire Retardant Paint Tests‒a Critical Review," CDL Technical Memorandum, No. P87/73, H. M. Naval Base, Portsmouth, Dec. 1973.

53. Malhotra, H. L., "Fire Resistance of Structural Concrete Beams," Fire Research Note, No. 741, Fire Research Station, Borehamwood, May 1969.

54. Abrams, M. S., and Gustaferro, A. H., "Fire Tests of Poke-Thru Assemblies," Research and Development Bulletin, 1481-1, Portland Cement Association, Skokie, 1971.

55. Bullen, M. L., "A Note on the Relationship between Scale Fire Experiments and Standard Test Results," Building Research Establishment Note, N51/75, Borehamwood, May 1975.

56. The America Fore Group of Insurance Companies, Research Department, Some Characteristic Fires in Fire Resistive Buildings, Selected from twenty years record in the files of the N.F.P.A. "Quarterly," New York, c. 1933.

57. Spiegelhalter, F., "Guide to Design of Cavity Barriers and Fire Stops," Current Paper, CP 7/77, Building Research Establishment, Borehamwood, Feb. 1977.

58. Wardle, T. M. "Notes on the Fire Resistance of Heavy Timber Construction," Information Series, No. 53, New Zealand Forest Service, Wellington, 1966.

59. Fisher, R. W., and Smart, P. M. T., "Results of Fire Resistance Tests on Elements of Building Construction," Building Research Establishment Report, G R6, London, HMSO, 1975.

60. Serex, E. R., "Fire Resistance of Alta Bates Gypsum Block Non-Load Bearing Wall," Report to Alta Bates Community Hospital, Structural Research Laboratory Report, ES-7000, University of Calif., Berkeley, 1969.

61. Thomas, F. G., and Webster, C. T., "Investigations on Building Fires, Part VI: The Fire Resistance of Reinforced Concrete Columns," National Building Studies, Research Paper, No. 18, Dept. of Scientific and Industrial Research (Building Research Station), London, HMSO, 1953.

62. Building Research Establishment, "Timber Fire Doors," Digest, 220, Borehamwood, Nov. 1978.

63. Massachusetts State Building Code; Recommended Provisions, Article 22: Repairs, Alterations, Additions, and Change of Use of Existing Buildings, Boston, Oct. 23, 1978.

64. Freitag, J. K., Architectural Engineering; with Especial Reference to High Building Construction, Including Many Examples of Prominent Office Buildings, 2nd ed., rewritten, J. Wiley, New York, 1906.

65. Architectural Record, Sweet's Indexed Catalogue of Building Construction for the Year 1906, New York, 1906.

66. Dept. of Commerce, Building Code Committee, "Recommended Minimum Requirements for Fire Resistance in Buildings," Building and Housing, No. 14, National Bureau of Standards, Washington, 1931.

67. British Standards Institution, "Fire Tests on Building Materials and Structures," British Standards, 476, Pt. 1, London, 1953.

68. Löberg-Holm, K., "Glass," The Architectural Record, Oct. 1930, pp. 345-357.

69. Structural Clay Products Institute, "Fire Resistance," Technical Notes on Brick and Tile Construction, 16 rev., Washington, 1964.

70. Ramsey, C. G., and Sleeper, H. R., Architectural Graphic Standards for Architects, Engineers, Decorators, Builders, and Draftsmen, 3rd ed., J. Wiley, New York, 1941.

71. Underwriters' Laboratories, Fire Protection Equipment List, Chicago, Jan. 1957.

72. Underwriters' Laboratories, Fire Resistance Directory; with Hourly Ratings for Beams, Columns, Floors, Roofs, Walls, and Partitions, Chicago, Jan. 1977.

73. Mitchell, N. D., "Fire Tests of Gunite Slabs and Partitions," Building Materials and Structures, Report BMS 131, National Bureau of Standards, Washington, May 1952.

74. Woolson, I. H., and Miller, R. P., "Fire Tests of Floors in the United States," Proceedings International Association for Testing Materials, VIth Congress, New York, 1912, Section C, pp. 36-41.

75. Underwriters' Laboratories, "An Investigation of the Effects of Fire Exposure upon Hollow Concrete Building Units, Conducted for American Concrete Institute, Concrete Products Association, Portland Cement Association, Joint Submittors," Retardant Report, No. 1555, Chicago, May 1924.

76. Dept. of Scientific & Industrial Research and of the Fire Offices' Committee, Joint Committee of the Building Research Board, "Fire Gradings of Buildings. Part IV: Chimneys and Flues," Post-War Building Studies, No. 29, London, HMSO, 1952.

77. National Research Council of Canada. Associate Committee on the National Building Code, Fire Performance Ratings, Suppl. No. 2 to the National Building Code of Canada, Ottawa, 1965.

78. Associated Factory Mutual Fire Insurance Companies, The National Board of Fire Underwriters, and the Bureau of Standards, Fire Tests of Building Columns; an Experimental Investigation of the Resistance of Columns, Loaded and Exposed to Fire or to Fire and Water, with Record of Characteristic Effects, Jointly Conducted at Underwriters. Laboratories, Chicago, 1917-19.

79. Malhotra, H. L., "Effect of Age on the Fire Resistance of Reinforced Concrete Columns," Fire Research Memorandum, No. 1, Fire Research Station, Borehamwood, April 1970.

80. Bond, H., ed., Research on Fire; a Description of the Facilities, Personnel and Management of Agencies Engaged in Research on Fire, a Staff Report, National Fire Protection Association, Boston, 1957.

81. California State Historical Building Code, Draft, 1978.

82. Fisher, F. L., et al., "A Study of Potential Flashover Fires in Wheeler Hall and the Results from a Full Scale Fire Test of a Modified Wheeler Hall Door Assembly," Fire Research Laboratory Report, UCX 77-3; UCX-2480, University of Calif., Dept. of Civil Eng., Berkeley, 1977.

83. Freitag, J. K., The Fireproofing of Steel Buildings, 1st ed., J. Wiley, New York, 1906.

84. Gross, D., "Field Burnout Tests of Apartment Dwellings Units," Building Science Series, 10, National Bureau of Standards, Washington, 1967.

85. Dunlap, M. E., and Cartwright, F. P., "Standard Fire Tests for Combustible Building Materials," Proceedings of the American Society for Testing Materials, vol. 27, Philadelphia, 1927, pp. 534-546.

86. Menzel, C. A., "Tests of the Fire Resistance and Stability of Walls of Concrete Masonry Units," Proceedings of the American Society for Testing Materials, vol. 31, Philadelphia, 1931, pp. 607-660.

87. Steiner, A. J., "Method of Fire-Hazard Classification of Building Materials," Bulletin of the American Society for Testing and Materials, March 1943, Philadelphia, 1943, pp. 19-22.

88. Heselden, A. J. M., Smith, P. G., and Theobald, C. R., "Fires in a Large Compartment Containing Structural Steelwork; Detailed Measurements of Fire Behavior," Fire Research Note, No. 646, Fire Research Station, Borehamwood, Dec. 1966.

89. Ministry of Technology and Fire Offices' Committee Joint Fire Research Organization, "Fire and Structural Use of Timber in Buildings; Proceedings of the Symposium Held at the Fire Research Station, Borehamwood, Herts on 25th October, 1967," Symposium, No. 3, London, HMSO, 1970.

90. Shoub, H., and Gross, D., "Doors as Barriers to Fire and Smoke," Building Science Series, 3, National Bureau of Standards, Washington, 1966.

91. Ingberg, S. H., "The Fire Resistance of Gypsum Partitions," Proceedings of the American Society for Testing and Materials, vol. 25, Philadelphia, 1925, pp. 299-314.

92. Ingberg, S.H., "Influence of Mineral Composition of Aggregates on Fire Resistance of Concrete," Proceedings of the American Society for Testing and Materials, vol. 29, Philadelphia, 1929, pp. 824-829.

93. Ingberg, S. H., "The Fire Resistive Properties of Gypsum," Proceedings of the American Society for Testing and Materials, vol. 23, Philadelphia, 1923, pp. 254-256.

94. Gottschalk, F.W., "Some Factors in the Interpretation of Small-Scale Tests for Fire-Retardant Wood," Bulletin of the American Society for Testing and Materials, October 1945, pp. 40-43.

95. Ministry of Technology and Fire Offices' Committee Joint Fire Research Organization, "Behaviour of Structural Steel in Fire; Proceedings of the Symposium Held at the Fire Research Station Borehamwood, Herts on 24th January, 1967," Symposium, No. 2, London, HMSO, 1968.

96. Gustaferro, A. H., and Martin, L. D., Design for Fire Resistance of Pre-cast Concrete, prep. for the Prestressed Concrete Institute Fire Committee, 1st ed., Chicago, PCI, 1977.

97. "The Fire Endurance of Concrete; a Special Issue," Concrete Construction, vol. 18, no. 8, Aug. 1974, pp. 345-440.

98. The British Constructional Steelwork Association, "Modern Fire Protection for Structural Steelwork," Publication, No. FPl, London, 1961.

99. Underwriters' Laboratories, "Fire Hazard Classification of Building Materials," Bulletin, No. 32, Sept. 1944, Chicago, 1959.

100. Central Housing Committee on Research, Design, and Construction, Subcommittee on Building Codes, "Recommended Building Code Requirements for New Dwelling Construction with Special Reference to War Housing; Report," Building Materials and Structures, Report BMS 88, National Bureau of Standards, Washington, Sept. 1942.

101. De Coppet Bergh, D., Safe Building Construction; a Treatise Giving in Simplest Forms Possible Practical and Theoretical Rules and Formulae Used in Construction of Buildings and General Instruction, new ed., thoroughly rev. Macmillan Co., New York, 1908.

102. Cyclopedia of Fire Prevention and Insurance; a General Reference Work on Fire and Fire Losses, Fireproof Construction, Building Inspection..., prep. by architects, engineers, underwriters and practical insurance men. American School of Correspondence, Chicago, 1912.

103. Setchkin, N. P., and Ingberg, S. H., "Test Criterion for an Incombustible Material," Proceedings of the American Society for Testing Materials, vol. 45, Philadelphia, 1945, pp. 866-877.

104. Underwriters' Laboratories, "Report on Fire Hazard Classification of Various Species of Lumber," Retardant, 3365, Chicago, 1952.

105. Steingiser, S., "A Philosophy of Fire Testing," Journal of Fire & Flammability, vol. 3, July 1972, pp. 238-253.

106. Yuill, C. H., Bauerschlag, W. H., and Smith, H. M., "An Evaluation of the Comparative Performance of 2.4.1 Plywood and Two-Inch Lumber Roof Decking under Equivalent Fire Exposure," Fire Protection Section, Final Report, Project No. 717A-3-211, Southwest Research Institute, Dept. of Structural Research, San Antonio, Dec. 1962.

107. Ashton, L. A., and Smart, P.M. T., Sponsored Fire-Resistance Tests on Structural Elements, London, Dept. of Scientific and Industrial Research and Fire Offices. Committee, London, 1960.

108. Butcher, E. G., Chitty, T. B., and Ashton, L. A., "The Temperature Attained by Steel in Building Fires," Fire Research Technical Paper, No. 15, Ministry of Technology and Fire Offices. Committee, Joint Fire Research Organization, London, HMSO, 1966.

109. Dept. of the Environment and Fire Offices' Committee, Joint Fire Research Organization, "Fire-Resistance Requirements for Buildings‒a New Approach; Proceedings of the Symposium Held at the Connaught Rooms, London, 28 September 1971," Symposium, No. 5, London, HMSO, 1973.

110. Langdon Thomas, G. J., "Roofs and Fire," Fire Note, No. 3, Dept. of Scientific and Industrial Research and Fire Offices' Committee, Joint Fire Research Organization, London, HMSO, 1963.

111. National Fire Protection Association and the National Board of Fire Underwriters, Report on Fire the Edison Phonograph Works, Thomas A. Edison, Inc., West Orange, N.J., December 9, 1914, Boston, 1915.

112. Thompson, J. P., Fire Resistance of Reinforced Concrete Floors, Portland Cement Association, Chicago, 1963.

113. Forest Products Laboratory, "Fire Resistance Tests of Plywood Covered Wall Panels," Information reviewed and reaffirmed, Forest Service Report, No. 1257, Madison, April 1961.

114. Forest Products Laboratory, "Charring Rate of Selected Woods‒Transverse to Grain," Forest Service Research Paper, FLP 69, Madison, April 1967.

115. Bird, G. I., "Protection of Structural Steel Against Fire," Fire Note, No. 2, Dept. of Scientific and Industrial Research and Fire Offices' Committee, Joint Fire Research Organization, London, HMSO, 1961.

116. Robinson, W. C., The Parker Building Fire, Underwriters' Laboratories, Chicago, c. 1908.

117. Ferris, J. E., "Fire Hazards of Combustible Wallboards," Commonwealth Experimental Building Station Special Report, No. 18, Sydney, Oct. 1955.

118. Markwardt, L. J., Bruce, H. D., and Freas, A. D., "Brief Description of Some Fire-Test Methods Used for Wood and Wood Base Materials," Forest Service Report, No. 1976, Forest Products Laboratory, Madison, 1976.

119. Foster, H. D., Pinkston, E. R., and Ingberg, S. H., "Fire Resistance of Walls of Gravel-Aggregate Concrete Masonry Units," Building Materials and Structures, Report, BMS 120, National Bureau of Standards, Washington, March 1951.

120. Foster, H. D., Pinkston, E.R., and Ingberg, S. H., "Fire Resistance of Walls of Lightweight-Aggregate Concrete Masonry Units," Building Materials and Structures, Report BMS 117, National Bureau of Standards, Washington, May 1950.

121. Structural Clay Products Institute, "Structural Clay Tile Fireproofing," Technical Notes on Brick & Tile Construction, vol. 1, no. 11, San Francisco, Nov. 1950.

122. Structural Clay Products Institute, "Fire Resistance Ratings of Clay Masonry Walls‒I," Technical Notes on Brick & Tile Construction, vol. 3, no. 12, San Francisco, Dec. 1952.

123. Structural Clay Products Institute, "Estimating the Fire Resistance of Clay Masonry Walls‒II," Technical Notes on Brick & Tile Construction, vol. 4, no. 1, San Francisco, Jan. 1953.

124. Building Research Station, "Fire: Materials and Structures," Digest, No. 106, London, HMSO, 1958.

125. Mitchell, N. D., "Fire Hazard Tests with Masonry Chimneys," NFPA Publication, No. Q-43-7, Boston, Oct. 1949.

126. Clinton Wire Cloth Company, Some Test Data on Fireproof Floor Construction Relating to Cinder Concrete, Terra Cotta and Gypsum, Clinton, 1913.

127. Structural Engineers Association of Southern California, Fire Ratings Subcommittee, "Fire Ratings, a Report," part of Annual Report, Los Angeles, 1962, pp. 30-38.

128. Lawson, D. I., Fox, L. L., and Webster, C. T., "The Heating of Panels by Flue Pipes," Fire Research, Special Report, No. 1, Dept. of Scientific and Industrial Research and Fire Offices' Committee, London, HMSO, 1952.

129. Forest Products Laboratory, "Fire Resistance of Wood Construction," Excerpt from 'Wood Handbook‒Basic Information on Wood as a Material of Construction with Data for its Use in Design and Specification,' Dept. of Agriculture Handbook, No. 72, Washington, 1955, pp. 337-350.

130. Goalwin, D. S., "Properties of Cavity Walls," Building Materials and Structures, Report BMS 136, National Bureau of Standards, Washington, May 1953.

131. Humphrey, R. L., "The Fire-Resistive Properties of Various Building Materials," Geological Survey Bulletin, 370, Washington, 1909.

132. National Lumber Manufacturers Association, "Comparative Fire Test on Wood and Steel Joists," Technical Report, No. 1, Washington, 1961.

133. National Lumber Manufacturers Association, "Comparative Fire Test of Timber and Steel Beams," Technical Report, No. 3, Washington, 1963.

134. Malhotra, H. L., and Morris, W. A., "Tests on Roof Construction Subjected to External Fire," Fire Note, No. 4, Dept. of Scientific and Industrial Research and Fire Offices' Committee, Joint Fire Research Organization, London, HMSO, 1963.

135. Brown, C. R., "Fire Tests of Treated and Untreated Wood Partitions," Research Paper, RP 1076, part of Journal of Research of the National Bureau of Standards, vol. 20, Washington, Feb. 1938, pp. 217-237.

136. Underwriters' Laboratories, "Report on Investigation of Fire Resistance of Wood Lath and Lime Plaster Interior Finish," Publication, SP. 1.230, Chicago, Nov. 1922.

137. Underwriters' Laboratories, "Report on Interior Building Construction Consisting of Metal Lath and Gypsum Plaster on Wood Supports," Retardant, No. 1355, Chicago, 1922.

138. Underwriters' Laboratories, "An Investigation of the Effects of Fire Exposure upon Hollow Concrete Building Units," Retardant, No. 1555, Chicago, May 1924.

139. Moran, T. H., "Comparative Fire Resistance Ratings of Douglas Fir Plywood," Douglas Fir Plywood Association Laboratory Bulletin, 57-A, Tacoma, 1957.

140. Gage Babcock & Association, "The Performance of Fire-Protective Materials under Varying Conditions of Fire Severity," Report 6924, Chicago, 1969.

141. International Conference of Building Officials, Uniform Building Code (1979 ed.), Whittier, CA, 1979.

142. Babrauskas, V., and Williamson, R. B., "The Historical Basis of Fire Resistance Testing, Part I and Part II," Fire Technology, vol. 14, no. 3 & 4, Aug. & Nov. 1978, pp. 184-194, 205, 304-316.

143. Underwriters' Laboratories, "Fire Tests of Building Construction and Materials," 8th ed., Standard for Safety, UL263, Chicago, 1971.

144. Hold, H. G., Fire Protection in Buildings, Crosby, Lockwood, London, 1913.

145. Kollbrunner, C. F., "Steel Buildings and Fire Protection in Europe," Journal of the Structural Division, ASCE, vol. 85, no. ST9, Proc. Paper 2264, Nov. 1959, pp. 125-149.

146. Smith, P., "Investigation and Repair of Damage to Concrete Caused by Formwork and Falsework Fire," Journal of the American Concrete Institute, vol. 60, Title no. 60-66, Nov. 1963, pp. 1535-1566.

147. "Repair of Fire Damage," 3 parts, Concrete Construction, March-May, 1972.

148. National Fire Protection Association, National Fire Codes; a Compilation of NFPA Codes, Standards, Recommended Practices and Manuals, 16 vols., Boston, 1978.

149. Ingberg, S. H. "Tests of Severity of Building Fires," NFPA Quarterly, vol. 22, no. 1, July 1928, pp. 43-61.

150. Underwriters' Laboratories, "Fire Exposure Tests of Ordinary Wood Doors," Bulletin of Research, no. 6, Dec. 1938, Chicago, 1942.

151. Parson, H., "The Tall Building under Test of Fire," Red Book, no. 17, British Fire Prevention Committee, London, 1899.

152. Sachs, E. O., "The British Fire Prevention Committee Testing Station," Red Book, no. 13, British Fire Prevention Committee, London, 1899.

153. Sachs, E. O., "Fire Tests with Unprotected Columns," Red Book, no. 11, British Fire Prevention Committee, London, 1899.

154. British Fire Prevention Committee, "Fire Tests with Floors a Floor by the Expended Metal Company," Red Book, no. 14, London, 1899.

155. Engineering News, vol. 56, Aug. 9, 1906, pp. 135-140.

156. Engineering News, vol. 36, Aug. 6, 1896, pp. 92-94.

157. Bauschinger, J., Mittheilungen de Mech.-Tech. Lab. der K. Tech. Hochschule, Müchen, vol. 12, 1885.

158. Engineering News, vol. 46, Dec. 26, 1901, pp. 482-486, 489-490.

159. The American Architect and Building News, vol. 31, March 28, 1891, pp. 195-201.

160. British Fire Prevention Committee, First International Fire Prevention Congress, Official Congress Report, London, 1903.

161. American Society for Testing Materials, Standard Specifications for Fire Tests of Materials and Construction (C19-18), Philadelphia, 1918.

162. International Organization for Standardization, Fire Resistance Tests on Elements of Building Construction (R834), London, 1968.

163. Engineering Record, vol. 35, Jan. 2, 1897, pp. 93-94; May 29, 1897, pp. 558-560; vol. 36, Sept. 18, 1897, pp. 337-340; Sept. 25, 1897, pp. 359-363; Oct. 2, 1897, pp. 382-387; Oct. 9, 1897, pp. 402-405.

164. Babrauskas, Vytenis, "Fire Endurance in Buildings," PhD Thesis. Fire Research Group, Report, No. UCB FRG 76-16, University of California, Berkeley, Nov. 1976.

165. The Institution of Structural Engineers and The Concrete Society, Fire Resistance of Concrete Structures, London, Aug. 1975.
Resources