ADOPTS WITHOUT AMENDMENTS:

NFPA 70, 2014

Heads up: There are no amended sections in this chapter.
This article covers general requirements, applications, and construction specifications for flexible cords and flexible cables.
Flexible cords and flexible cables shall comply with this article and with the applicable provisions of other articles of this Code.
Flexible cords and cables and their associated fittings shall be suitable for the conditions of use and location.
Flexible cords and flexible cables shall conform to the description in Table 400.4. The use of flexible cords and flexible cables other than those in Table 400.4 shall require permission by the authority having jurisdiction.

Table 400.4 Flexible Cords and Cables (See 400.4.)

Trade
Name
Type Letter Voltage AWG or kcmil Number of
Conductors
Insulation AWG or kcmil Nominal Insulation Thickness Braid on
Each
Conductor
Outer
Covering
Use
mm mils
Lamp
cord
C 300
600
18-16
15-10
2 or
more
Thermoset or
thermoplastic
18-16
15-10
0.76
1.14
30
45
Cotton None Pendant
or portable
Dry
locations
Not
hard
usage
Elevator
cable
E1,2,3,4 300 or
600
20-2 2 or more Thermoset 20-16
15-12
12-10
8-2
0.51
0.76
1.14
1.52
20
30
45
60
Cotton Three cotton;
outer one
flame-retardant
& moisture-resistant
Elevator
lighting
and
control
Unclassified
locations
 
            20-16
15-12
12-10
8-2
0.51
0.76
1.14
1.52
20
30
45
60
Flexible
nylon
jacket
       
Elevator
cable
EO1,2,4 300 or
600
20-2 2 or more Thermoset 20-16
15-12
12-10
8-2
0.51
0.76
1.14
1.52
20
30
45
60
Cotton Three cotton;
outer one
flame-retardant
& moisture-resistant
Elevator
lighting
and
control
Unclassified
locations
 
                    One cotton
and a neoprene
jacket.
  Hazardous
(classified)
locations
 
Elevator
cable
ETP2,4 300 or
600
            Rayon Thermoplastic Hazardous
(classified)
locations
   
  ETT2,4 300 or
600
            None One cotton
or equivalent
and a thermoplastic
jacket
     
Electric
vehicle
cable
EV5,6 600 18-500 2 or more
plus grounding
conductor(s),
plus optional
hybrid data,
signal
communications
and optical
fiber cables
Thermoset with
optional nylon
18-15
14-10
8-2
1-4/0
250-500
0.76
(0.51)
1.14
(0.76)
1.52
(1.14)
2.03
(1.52)
2.41
(1.90)
30
(20)
45
(30)
60
(45)
80
(60)
95
(75)
Optional Oil-resistant
thermoset
Electric
vehicle
charging
Wet
locations
Extra-hard
usage
  EVJ5,6 300 18-12     18-12 0.76
(0.51)
30
(20)
        Hard
usage
  EVE5,6 600 18-500 2 or more
plus grounding
conductor(s),
plus optional
hybrid data,
signal
communications
and optical
fiber cables
Thermoplastic
elastomer with
optional nylon
18-15
14-10
8-2
1-4/0
250-500
0.76
(0.51)
1.14
(0.76)
1.52
(1.14)
2.03
(1.52)
2.41
(1.90)
30
(20)
45
(30)
60
(45)
80
(60)
95
(75)
  Oil-resistant
thermoplastic
elastomer
    Extra-hard
usage
  EVJE5,6 300 18-12     18-12 0.76
(0.51)
30
(20)
        Hard
usage
  EVT5,6 600 18-500 2 or more
plus grounding
conductor(s),
plus optional
hybrid data,
signal
communications
and optical
fiber
cables
Thermoplastic
with optional
nylon
18-15
14-10
8-2
1-4/0
250-500
0.76
(0.51)
1.14
(0.76)
1.52
(1.14)
2.03
(1.52)
2.41
(1.90)
30
(20)
45
(30)
60
(45)
80
(60)
95
(75)
Optional Oil-resistant
thermoplastic
Electric
vehicle
charging
Wet
locations
Extra-hard
usage
  EVJT5,6 300 18-12     18-12 0.76
(0.51)
30
(20)
        Hard
usage
Portable
power
cord
G 2000 12-500 2-6 plus
grounding
conductor(s)
Thermoset 12-2
1-4/0
250-500
1.52
2.03
2.41
60
80
95
  Oil-resistant
thermoset
Portable and extra-hard usage
  G-GC7 2000 12-500 3-6 plus
grounding
conductors
and 1
ground
check
conductor
Thermoset 12-2
1-4/0
250-500
1.52
2.03
2.41
60
80
95
  Oil-resistant
thermoset
     
Heater
cord
HPD 300 18-12 2, 3, or 4 Thermoset 18-16
15-12
0.38
0.76
15
30
None Cotton or
rayon
Portable
heaters
Dry locations Not hard
usage
Parallel
Heater
cord
HPN8 300 18-12 2 or 3 Oil-resistant
thermoset
18-16
15
14
12
1.14
1.52
2.41
45
60
95
None Oil-resistant
thermoset
Portable Damp locations Not hard
usage
Thermoset
jacketed
heater
cords
HSJ 300 18-12 2, 3 or 4 Thermoset 18-16
15-12
0.76
1.14
30
45
None Cotton and
thermoset
Portable or
portable
heater
Damp locations Hard
usage
  HSJO 300 18-12             Cotton and
oil-resistant
thermoset
  Damp and
wet locations
 
  HSJOW9 300 18-12                 Damp locations  
  HSJOO 300 18-12   Oil-resistant
thermoset
               
  HSJOOW9 300 18-12                 Damp and
wet locations
 
Non-integral
parallel cords
NISP-1 300 20-18 2 or 3 Thermoset 20-18 0.38 15 None Thermoset Pendant
or portable
Damp locations Not hard
usage
  NISP-2 300 18-16     18-16 0.76 30          
  NISPE-18 300 20-18   Thermoplastic
elastomer
20-18 0.38 15   Thermoplastic
elastomer
     
  NISPE-28 300 18-16     18-16 0.76 30          
  NISPT-18 300 20-18   Thermoplastic 20-18 0.38 15   Thermoplastic      
  NISPT-28 300 18-16     18-16 0.76 30          
Twisted
portable
cord
PD 300
600
18-16
14-10
2 or more Thermoset or
thermoplastic
18-16
15-10
0.76
1.14
30
45
Cotton Cotton or
rayon
Pendant
or portable
Dry locations Not hard
usage
Portable
power
cord
PPE7 2000 12-500 1-6 plus
optional
grounding
conductor(s)
Thermoset
elastomer
12-2
1-4/0
250-500
1.52
2.03
2.41
60
80
95
  Oil-resistant
thermoplastic
elastomer
Portable, extra-hard usage
Hard
service
cord
S7 600 18-2 2 or more Thermoset 18-15
14-10
8-2
0.76
1.14
1.52
30
45
60
None Thermoset Pendant
or portable
Damp locations Extra-hard
usage
Flexible stage
and lighting
power cords
SC7,10 600 8-250 1 or more Thermoset 8-2
1-4/0
250
1.52
2.03
2.41
60
80
95
  Thermoset Portable, extra-hard usage
  SCE7,10 600     Thermoplastic
elastomer
        Thermoplastic
elastomer
     
  SCT7,10 600     Thermoplastic         Thermoplastic      
Hard
service cord
SE7 600 18-2 2 or more Thermoplastic
elastomer
18-15
14-9
8-2
0.76
1.14
1.52
30
45
60
None Thermo
plastic
elastomer
Pendant
or portable
Damp location Extra-hard
usage
  SEW7,9 600                   Damp and
wet locations
 
  SEO7 600               Oil-resistant
thermoplastic
elastomer
  Damp and
locations
 
  SEOW7,9 600                   Damp and
wet locations
 
  SEOO7 600     Oil-resistant
thermoplastic
elastomer
            Damp and
locations
 
  SEOOW7,9 600                   Damp and
wet locations
 
Junior
hard service
cord
SJ 300 18-10 2-6 Thermoset 18-11
10
0.76
1.14
30
45
None Thermoset Pendant
or portable
Damp location Extra-hard
usage
  SJE 300     Thermoplastic
elastomer
        Thermoplastic
elastomer
     
  SJEW9 300                   Damp and
wet locations
 
  SJEO 300               Oil-resistant
thermoplastic
elastomer
  Damp locations  
  SJEOW9 300                   Damp and
wet locations
 
  SJEOO 300     Oil-resistant
thermoplastic
elastomer
            Damp
locations
 
  SJEOOW9 300                   Damp and wet locations  
  SJO 300     Thermoset         Oil-resistant
thermoset
  Damp locations  
  SJOW9 300                   Damp and
wet locations
 
  SJOO 300     Oil-resistant
thermoset
            Damp locations  
  SJOOW9 300                   Damp and
wet locations
 
  SJT 300     Thermoplastic         Thermoplastic   Damp locations  
  SJTW9 300                   Damp and wet locations  
  SJTO 300       18-12
10
0.76
1.14
30
45
  Oil-resistant
thermoplastic
  Damp locations  
  SJTOW9 300                   Damp and
wet locations
 
  SJTOO 300     Oil-resistant
thermoplastic
            Damp locations  
  SJTOOW9 300                   Damp and
wet locations
 
Hard
service cord
SO7 600 18-2 2 or more Thermoset 18-15 0.76 30 None Oil-resistant
Thermoset
Pendant
or portable
Damp location Extra-hard
usage
  SOW7,9 600                   Damp and wet locations  
  SOO7 600     Oil-resistant
thermoset
14-9
8-2
1.14
1.52
45
60
      Damp locations  
  SOOW7,9 600                   Damp and wet locations  
All thermoset
parallel cord
SP-1 300 20-18 2 or 3 Thermoset 20-18 0.76 30 None None Pendant or
portable
Damp location Not hard
usage
  SP-2 300 18-16     18-16 1.14 45          
  SP-3 300 18-10     18-16
15,14
12
10
1.52
2.03
2.41
2.80
60
80
95
110
    Refrigerators,
room air
conditioners,
and as
permitted
in 422.16(B)
   
All elastomer
(thermoplastic)
parallel cord
SPE-18 300 20-18 2 or 3 Thermoplastic
elastomer
20-18 0.76 30 None None Pendant
or portable
Damp location Not hard
usage
  SPE-28 300 18-16     18-16 1.14 45          
  SPE-38 300 18-10     18-16
15
14
12
10
1.52
2.03
2.41
2.80
60
80
95
110
    Refrigerators,
room air
conditioners,
and as
permitted
in 422.16(B)
   
All
thermoplastic
parallel cord
SPT-1 300 20-18 2 or 3 Thermoplastic 20-18 0.76 30 None None Pendant or
portable
Damp location Not hard
usage
  SPT-1W9 300   2               Damp and
wet locations
 
  SPT-2 300 18-16 2 or 3   18-16 1.14 45       Damp and locations  
  SPT-2W9 300   2               Damp and
wet locations
 
  SPT-3 300 18-10 2 or 3   18-16
15
14
12
10
1.52
2.03
2.41
2.80
60
80
95
110
    Refrigerators,
room air
conditioners,
and as
permitted
in 422.16(B)
Damp locations Not hard
usage
Range,
dryer cord
SRD 300 10-4 3 or 4 Thermoset 10-4 1.14 45 None Thermoset Portable Damp location Range,
dryer
  SRDE 300 10-4 3 or 4 Thermoplastic
elastomer
      None Thermoplastic
elastomer
     
  SRDT 300 10-4 3 or 4 Thermoplastic       None Thermoplastic      
Hard
service cord
ST7 600 18-2 2 or more Thermoplastic 18-15
14-9
8-2
0.76
1.14
1.52
30
45
60
None Thermoplastic Pendant or
portable
Damp location Extra-hard
usage
  STW7,9 600                   Damp and
wet locations
 
  STO7 600               Oil-resistant
thermoplastic
  Damp locations  
  STWO7,9 600                   Damp and
wet locations
 
  STOO7 600     Oil-resistant
thermoplastic
            Damp locations  
  STOOW7 600                   Damp and
wet locations
 
Vacuum
cleaner cord
SV 300 18-16 2 or 3 Thermoset 18-16 0.38 15 None Thermoset Pendant or
portable
Damp location Not hard
usage
  SVE 300     Thermoplastic
elastomer
        Thermoplastic
elastomer
     
  SVEO 300               Oil-resistant
thermoplastic
elastomer
     
  SVEOO 300     Oil-resistant
thermoplastic
elastomer
               
  SVO 300     Thermoset         Oil-resistant
thermoset
     
  SVOO 300     Oil-resistant
thermoset
        Oil-resistant
thermoset
     
  SVT 300     Thermoplastic         Thermoplastic      
  SVTO 300     Thermoplastic         Oil-resistant
thermoplastic
     
  SVTOO 300     Oil-resistant
thermoplastic
               
Parallel
tinsel cord
TPT11 300 27 2 Thermoplastic 27 0.76 30 None Thermoplastic Attached to
an appliance
Damp locations Not hard
usage
Jacketed
tinsel cord
TST11 300 27 2 Thermoplastic 27 0.38 15 None Thermoplastic Attached to
an appliance
Damp locations Not hard
usage
Portable
power cable
W7 2000 12-500
501-1000
1-6
1
Thermoset 12-2
1-4/0
250-500
501-1000
1.52
2.03
2.41
2.80
60
80
95
110
  Oil-resistant
thermoset
Portable, extra-hard usage

Notes:

All types listed in Table 400.4 shall have individual conductors twisted together, except for Types HPN, SP-1, SP-2, SP-3, SPE-1, SPE-2, SPE-3, SPT-1, SPT-2, SPT-3, SPT-1W, SPT-2W, TPT, NISP-1, NISP-2, NISPT-1. NISPT-2, NISPE-1, NISPE-2, and three-conductor parallel versions of SRD, SRDE, and SRDT.

The individual conductors of all cords, except those of heat-resistant cords, shall have a thermoset or thermoplastic insulation, except that the equipment grounding conductor, where used, shall be in accordance with 400.23(B).

1Rubber-filled or varnished cambric tapes shall be permitted as a substitute for the inner braids.

2Elevator traveling cables for operating control and signal circuits shall contain nonmetallic fillers as necessary to maintain concentricity. Cables shall have steel supporting members as required for suspension by 620.41. In locations subject to excessive moisture or corrosive vapors or gases, supporting members of other materials shall be permitted. Where steel supporting members are used, they shall run straight through the center of the cable assembly and shall not be cabled with the copper strands of any conductor.

In addition to conductors used for control and signaling circuits, Types E, EO, ETP, and ETT elevator cables shall be permitted to incorporate in the construction one or more 20 AWG telephone conductor pairs, one or more coaxial cables, or one or more optical fibers. The 20 AWG conductor pairs shall be permitted to be covered with suitable shielding for telephone, audio, or higher frequency communications circuits; the coaxial cables consist of a center conductor, insulation, and a shield for use in video or other radio frequency communications circuits. The optical fiber shall be suitably covered with flame-retardant thermoplastic. The insulation of the conductors shall be rubber or thermoplastic of a thickness not less than specified for the other conductors of the particular type of cable. Metallic shields shall have their own protective covering. Where used, these components shall be permitted to be incorporated in any layer of the cable assembly but shall not run straight through the center.

3Insulations and outer coverings that meet the requirements as flame retardant, limited smoke, and are so listed, shall be permitted to be marked for limited smoke after the Code type designation.

4Elevator cables in sizes 20 AWG through 14 AWG are rated 300 volts, and sizes 10 AWG through 2 AWG are rated 600 volts. 12 AWG is rated 300 volts with a 0.76 mm (30 mil) insulation thickness and 600 volts with a 1.14 mm (45 mil) insulation thickness.

5Conductor size for Types EV, EVJ, EVE, EVJE, EVT, and EVJT cables apply to nonpower-limited circuits only. Conductors of power-limited (data, signal, or communications) circuits may extend beyond the stated AWG size range. All conductors shall be insulated for the same cable voltage rating.

6Insulation thickness for Types EV, EVJ, EVEJE, EVT, and EVJT cables of nylon construction is indicated in parentheses.

7Types G, G-GC, S, SC, SCE, SCT, SE, SEO, SEOO, SEW, SEOW, SEOOW, SO, SOO, SOW, SOOW, ST, STO, STOO, STW, STOW, STOOW, PPE, and W shall be permitted for use on theater stages, in garages, and elsewhere where flexible cords are permitted by this Code.

8The third conductor in Type HPN shall be used as an equipment grounding conductor only. The insulation of the equipment grounding conductor for Types SPE-1, SPE-2, SPE-3, SPT-1, SPT-2, SPT-3, NISPT-1, NISPT-2, NISPE-1, and NISPE-2 shall be permitted to be thermoset polymer.

9Cords that comply with the requirements for outdoor cords and are so listed shall be permitted to be designated as weather and water resistant with the suffix "W" after the Code type designation. Cords with the "W" suffix are suitable for use in wet locations and are sunlight resistant.

10The required outer covering on some single-conductor cables may be integral with the insulation.

11Types TPT and TST shall be permitted in lengths not exceeding 2.5 m (8 ft) where attached directly, or by means of a special type of plug, to a portable appliance rated at 50 watts or less and of such nature that extreme flexibility of the cord is essential.

Table 400.5(A)(1) provides the allowable ampacities, and Table 400.5(A)(2) provides the ampacities for flexible cords and cables with not more than three current-carrying conductors. These tables shall be used in conjunction with applicable end-use product standards to ensure selection of the proper size and type. Where cords and cables are used in ambient temperatures other than 30°C (86°F), the temperature correction factors from Table 310.15(B)(2)(a) that correspond to the temperature rating of the cord or cable shall be applied to the ampacity in Table 400.5(A)(1) and Table 400.5(A)(2). Cords and cables rated 105°C shall use correction factors in the 90°C column of Table 310.15(B)(2)(a) for temperature correction. Where the number of current-carrying conductors exceeds three, the allowable ampacity or the ampacity of each conductor shall be reduced from the three-conductor rating as shown in Table 400.5(A)(3).

Informational Note: See Informative Annex B, Table B.310.15(B)(2)(H), for adjustment factors for more than three current-carrying conductors in a raceway or cable with load diversity.

A neutral conductor that carries only the unbalanced current from other conductors of the same circuit shall not be required to meet the requirements of a current-carrying conductor.

In a 3-wire circuit consisting of two phase conductors and the neutral conductor of a 4-wire, 3-phase, wye-connected system, a common conductor carries approximately the same current as the line-to-neutral currents of the other conductors and shall be considered to be a current-carrying conductor.

On a 4-wire, 3-phase, wye circuit where more than 50 percent of the load consists of nonlinear loads, there are harmonic currents present in the neutral conductor and the neutral conductor shall be considered to be a current-carrying conductor.

An equipment grounding conductor shall not be considered a current-carrying conductor.

Where a single conductor is used for both equipment grounding and to carry unbalanced current from other conductors, as provided for in 250.140 for electric ranges and electric clothes dryers, it shall not be considered as a current-carrying conductor.

Table 400.5(A)(1) Allowable Ampacity for Flexible Cords and Cables [Based on Ambient Temperature of 30°C (86°F). See 400.13 and Table 400.4.

Copper Conductor Size (AWG) Thermoplastic Types TPT, TST Thermoset Types C, E, EO, PD, S, SJ, SJO, SJOW, SJOO, SJOOW, SO, SOW, SOO, SOOW, SP-1, SP-2, SP-3, SRD, SV, SVO, SVOO, NISP-1, NISP-2 Types HPD, HPN, HSJ, HSJO, HSJOW, HSJOO, HSJOOW
Thermoplastic Types ETP, ETT, NISPE-1, NISPE-2, NISPT-1,
NISPT-2, SE, SEW, SEO, SEOO, SEOW, SEOOW, SJE, SJEW, SJEO, SJEOO, SJEOW, SJEOOW, SJT, SJTW, SJTO, SJTOW, SJTOO,
SJTOOW, SPE-1, SPE-2, SPE-3, SPT-1, SPT-1W, SPT-2, SPT-2W, SPT-3, ST, STW, SRDE, SRDT, STO, STOW, STOO, STOOW, SVE, SVEO, SVEOO, SVT, SVTO, SVTOO
    Column Aa Column Bb  
27c 0.5
20 5d e
18 7 10 10
17 9 12 13
16 10 13 15
15 12 16 17
14 15 18 20
13 17 21
12 20 25 30
11 23 27
10 25 30 35
9 29 34
8 35 40
6 45 55
4 60 70
2 80 95

aThe allowable currents under Column A apply to three-conductor cords and other multiconductor cords connected to utilization equipment so that only three-conductors are current-carrying.

bThe allowable currents under Column B apply to two-conductor cords and other multiconductor cords connected to utilization equipment so that only two conductors are current-carrying.

cTinsel cord.

dElevator cables only.

e7amperes for elevator cables only; 2 amperes for other types.

Table 400.5(A)(2) Ampacity of Cable Types SC, SCE, SCT, PPE, G, G-GC, and W. [Based on Ambient Temperature of 30°C (86°F). See Table 400.4.]

Copper Conductor Size (AWG or kcmil) Temperature Rating of Cable
60°C (140°F) 75°C (167°F) 90°C (194°F)
D1 E2 F3 D1 E2 F3 D1 E2 F3
12 31 26 37 31 42 35
10 44 37 52 43 59 49
8 60 55 48 70 65 57 80 74 65
6 80 72 63 95 88 77 105 99 87
4 105 96 84 125 115 101 140 130 114
3 120 113 99 145 135 118 165 152 133
2 140 128 112 170 152 133 190 174 152
1 165 150 131 195 178 156 220 202 177
1/0 195 173 151 230 207 181 260 234 205
2/0 225 199 174 265 238 208 300 271 237
3/0 260 230 201 310 275 241 350 313 274
4/0 300 265 232 360 317 277 405 361 316
250 340 296 259 405 354 310 455 402 352
300 375 330 289 445 395 346 505 449 393
350 420 363 318 505 435 381 570 495 433
400 455 392 343 545 469 410 615 535 468
500 515 448 392 620 537 470 700 613 536
600 575 690 780
700 630 755 855
750 655 785 885
800 680 815 920
900 730 870 985
1000 780 935 1055

1The ampacities under subheading D shall be permitted for single-conductor Types SC, SCE, SCT, PPE, and W cable only where the individual conductors are not installed in raceways and are not in physical contact with each other except in lengths not to exceed 600 mm (24 in.) where passing through the wall of an enclosure.

2The ampacities under subheading E apply to two-conductor cables and other multiconductor cables connected to utilization equipment so that only two conductors are current-carrying.

3The ampacities under subheading F apply to three-conductor cables and other multiconductor cables connected to utilization equipment so that only three conductors are current-carrying.

Table 400.5(A)(3) Adjustment Factors for More Than Three Current-Carrying Conductors in a Flexible Cord or Cable

Number of Conductors Percent of Value in Table 400.5(A)(1)
and Table 400.5(A)(2)
4-6 80
7-9 70
10-20 50
21-30 45
31-10 40
41 and above 35
In no case shall conductors be associated together in such a way with respect to the kind of circuit, the wiring method used, or the number of conductors such that the limiting temperature of the conductors is exceeded.
Under engineering supervision, conductor ampacities shall be permitted to be calculated in accordance with 310.15(C).
Flexible cords and cables shall be marked by means of a printed tag attached to the coil reel or carton. The tag shall contain the information required in 310.120(A). Types S, SC, SCE, SCT, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, STOO, SEW, SEOW, SEOOW, SJEW, SJEOW, SJEOOW, SJOW, SJTW, SJTOW, SJTOOW, SOW, SOOW, STW, STOW, and STOOW flexible cords and G, G-GC, PPE, and W flexible cables shall be durably marked on the surface at intervals not exceeding 610 mm (24 in.) with the type designation, size, and number of conductors. Required markings on tags, cords, and cables shall also include the maximum operating temperature of the flexible cord or cable.
Flexible cords and cable types listed in Table 400.4 shall be permitted to be surface marked to indicate special characteristics of the cable materials. These markings include, but are not limited to, markings for limited smoke, sunlight resistance, and so forth.
Flexible cords and cables shall be used only for the following:
  1. Pendants.
  2. Wiring of luminaires.
  3. Connection of portable luminaires, portable and mobile signs, or appliances.
  4. Elevator cables.
  5. Wiring of cranes and hoists.
  6. Connection of utilization equipment to facilitate frequent interchange.
  7. Prevention of the transmission of noise or vibration.
  8. Appliances where the fastening means and mechanical connections are specifically designed to permit ready removal for maintenance and repair, and the appliance is intended or identified for flexible cord connection.
  9. Connection of moving parts.
  10. Where specifically permitted elsewhere in this Code.
  11. Between an existing receptacle outlet and an inlet, where the inlet provides power to an additional single receptacle outlet. The wiring interconnecting the inlet to the single receptacle outlet shall be a Chapter 3 wiring method. The inlet, receptacle outlet, and Chapter 3 wiring method, including the flexible cord and fittings, shall be a listed assembly specific for this application.
Where used as permitted in 400.7(A)(3), (A)(6), and (A)(8), each flexible cord shall be equipped with an attachment plug and shall be energized from a receptacle outlet or cord connector body.

Exception: As permitted in 368.56.

Unless specifically permitted in 400.7, flexible cords and cables shall not be used for the following:
  1. As a substitute for the fixed wiring of a structure
  2. Where run through holes in walls, structural ceilings, suspended ceilings, dropped ceilings, or floors
  3. Where run through doorways, windows, or similar openings
  4. Where attached to building surfaces

    Exception to (4): Flexible cord and cable shall be permitted to be attached to building surfaces in accordance with the provisions of 368.56(B)

  5. Where concealed by walls, floors, or ceilings or located above suspended or dropped ceilings
  6. Where installed in raceways, except as otherwise permitted in this Code
  7. Where subject to physical damage
Flexible cord shall be used only in continuous lengths without splice or tap where initially installed in applications permitted by 400.7(A). The repair of hard-service cord and junior hard-service cord (see Trade Name column in Table 400.4) 14 AWG and larger shall be permitted if conductors are spliced in accordance with 110.14(B) and the completed splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced.
Flexible cords and cables shall be connected to devices and to fittings so that tension is not transmitted to joints or terminals.

Exception: Listed portable single-pole devices that are intended to accommodate such tension at their terminals shall be permitted to be used with single-conductor flexible cable.

Informational Note: Some methods of preventing pull on a cord from being transmitted to joints or terminals include knotting the cord, winding with tape, and using support or strain-relief fittings.

Flexible cords used in show windows and showcases shall be Types S, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO, SJOO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, STOO, SEW, SEOW, SEOOW, SJEW, SJEOW, SJEOOW, SJOW, SJOOW, SJTW, SJTOW, SJTOOW, SOW, SOOW, STW, STOW, or STOOW.

Exception No. 1: For the wiring of chain-supported luminaires.

Exception No. 2: As supply cords for portable luminaires and other merchandise being displayed or exhibited.

Flexible cords not smaller than 18 AWG, and tinsel cords or cords having equivalent characteristics of smaller size approved for use with specific appliances, shall be considered as protected against overcurrent in accordance with 240.5.
Flexible cords and cables shall be protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures.

In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, flexible cords and cables shall be permitted to be installed in aboveground raceways that are no longer than 15 m (50 ft) to protect the flexible cord or cable from physical damage. Where more than three current-carrying conductors are installed within the raceway, the allowable ampacity shall be reduced in accordance with Table 400.5(A)(3).

II Construction Specifications

Flexible cords shall be examined and tested at the factory and labeled before shipment.
The individual conductors of a flexible cord or cable shall have flexible stranding and shall not be smaller than the sizes specified in Table 400.4.
The nominal thickness of insulation for conductors of flexible cords and cables shall not be less than specified in Table 400.4.
One conductor of flexible cords that is intended to be used as a grounded circuit conductor shall have a continuous marker that readily distinguishes it from the other conductor or conductors. The identification shall consist of one of the methods indicated in 400.22(A) through (F).
A braid finished to show a white or gray color and the braid on the other conductor or conductors finished to show a readily distinguishable solid color or colors.
A tracer in a braid of any color contrasting with that of the braid and no tracer in the braid of the other conductor or conductors. No tracer shall be used in the braid of any conductor of a flexible cord that contains a conductor having a braid finished to show white or gray.

Exception: In the case of Types C and PD and cords having the braids on the individual conductors finished to show white or gray. In such cords, the identifying marker shall be permitted to consist of the solid white or gray finish on one conductor, provided there is a colored tracer in the braid of each other conductor.

A white or gray insulation on one conductor and insulation of a readily distinguishable color or colors on the other conductor or conductors for cords having no braids on the individual conductors.

For jacketed cords furnished with appliances, one conductor having its insulation colored light blue, with the other conductors having their insulation of a readily distinguishable color other than white or gray.

Exception: Cords that have insulation on the individual conductors integral with the jacket.

The insulation shall be permitted to be covered with an outer finish to provide the desired color.

A white or gray separator on one conductor and a separator of a readily distinguishable solid color on the other conductor or conductors of cords having insulation on the individual conductors integral with the jacket.
One conductor having the individual strands tinned and the other conductor or conductors having the individual strands untinned for cords having insulation on the individual conductors integral with the jacket.
One or more ridges, grooves, or white stripes located on the exterior of the cord so as to identify one conductor for cords having insulation on the individual conductors integral with the jacket.
A conductor intended to be used as an equipment grounding conductor shall have a continuous identifying marker readily distinguishing it from the other conductor or conductors. Conductors having a continuous green color or a continuous green color with one or more yellow stripes shall not be used for other than equipment grounding conductors. Cords or cables consisting of integral insulation and a jacket without a nonintegral grounding conductor shall be permitted to be green. The identifying marker shall consist of one of the methods in 400.23(A) or (B).
A braid finished to show a continuous green color or a continuous green color with one or more yellow stripes.
For cords having no braids on the individual conductors, an insulation of a continuous green color or a continuous green color with one or more yellow stripes.
Where a flexible cord is provided with an equipment grounding conductor and equipped with an attachment plug, the attachment plug shall comply with 250.138(A) and (B).

III Portable Cables Over 600 Volts, Nominal

Part III applies to single and multiconductor portable cables used to connect mobile equipment and machinery.
The conductors shall be 12 AWG copper or larger and shall employ flexible stranding.
An equipment grounding conductor(s) shall be provided in cables with three or more conductors. The total area shall not be less than that of the size of the equipment grounding conductor required in 250.122.
All shields shall be connected to an equipment grounding conductor.
Equipment grounding conductors shall be connected in accordance with Parts VI and VII of Article 250.
The minimum bending radii for portable cables during installation and handling in service shall be adequate to prevent damage to the cable.
Connectors used to connect lengths of cable in a run shall be of a type that locks firmly together. Provisions shall be made to prevent opening or closing these connectors while energized. Suitable means shall be used to eliminate tension at connectors and terminations.
Portable cables shall not contain splices unless the splices are of the permanent molded, vulcanized types in accordance with 110.14(B). Terminations on portable cables rated over 600 volts, nominal, shall be accessible only to authorized and qualified personnel.
This article covers general requirements and construction specifications for fixture wires.
Fixture wires shall comply with this article and also with the applicable provisions of other articles of this Code.

Informational Note: For application in luminaires, see Article 410.

Fixture wires shall be of a type listed in Table 402.3, and they shall comply with all requirements of that table. The fixture wires listed in Table 402.3 are all suitable for service at 600 volts, nominal, unless otherwise specified.

Informational Note: Thermoplastic insulation may stiffen at temperatures colder than -10°C (+14°F), requiring that care be exercised during installation at such temperatures. Thermoplastic insulation may also be deformed at normal temperatures where subjected to pressure, requiring that care be exercised during installation and at points of support.

Table 402.3 Fixture Wires

Name Type Letter Insulation AWG Thickness of Insulation Outer Covering Maximum Operating Temperature Application Provisions
mm mils
Heat-resistant rubber- covered fixture wire — flexible stranding FFH-2 Heat-resistant rubber 18-16 0.76 30 Nonmetallic covering 75°C
167°F
Fixture wiring
  Cross-linked synthetic polymer 18-16 0.76 30      
ECTFE — solid or 7-strand HF Ethylene chlorotrifluoroethylene 18-14 0.38 15 None 150°C
302°F
Fixture wiring
ECTFE — flexible stranding HFF Ethylene chlorotrifluoroethylene 18-14 0.38 15 None 150°C
302°F
Fixture wiring
Tape insulated fixture wire — solid or 7-strand KF-1 Aromatic polyimide tape 18-10 0.14 5.5 None 200°C
392°F
Fixture wiring— limited to 300 volts
KF-2 Aromatic polyimide tape 18-10 0.21 8.4 None 200°C
392°F
Fixture wiring
Tape insulated fixture wire — flexible stranding KFF-1 Aromatic polyimide tape 18-10 0.14 5.5 None 200°C
392°F
Fixture wiring— limited to 300 volts
KFF-2 Aromatic polyimide tape 18-10 0.21 8.4 None 200°C
392°F
Fixture wiring
Perfluoroalkoxy— solid or 7-strand (nickel or nickel-coated copper) PAF Perfluoroalkoxy 18-14 0.51 20 None 250°C
482°F
Fixture wiring (nickel or nickel-coated copper)
Perfluoro-alkoxy — flexible stranding PAFF Perfluoroalkoxy 18-14 0.51 20 None 150°C
302°F
Fixture wiring
Fluorinated ethylene propylene fixture wire —solid or 7-strand PF Fluorinated ethylene propylene 18-14 0.51 20 None 200°C
392°F
Fixture wiring
Fluorinated ethylene propylene fixture wire — flexible stranding PFF Fluorinated ethylene propylene 18-14 0.51 20 None 150°C
302°F
Fixture wiring
Fluorinated ethylene propylene fixture wire — solid or 7-strand PGF Fluorinated ethylene propylene 18-14 0.36 14 Glass braid 200°C
392°F
Fixture wiring
Fluorinated ethylene propylene fixture wire — flexible stranding PGFF Fluorinated ethylene propylene 18-14 0.36 14 Glass braid 150°C
302°F
Fixture wiring
Extruded polytetrafluoroethylene — solid or 7-strand (nickel or nickel-coated copper) PTF Extruded polytetrafluoroethylene 18-14 0.51 20 None 250°C
482°F
Fixture wiring (nickel or nickel-coated copper)
Extruded polytetrafluoroethylene — flexible stranding 26-36 (AWG silver or nickelcoated copper) PTFF Extruded polytetrafluoroethylene 18-14 0.51 20 None 150°C
302°F
Fixture wiring (silver or nickel-coated copper)
Heat-resistant rubber- covered fixture wire — solid or 7-strand RFH-1 Heat-resistant rubber 18 0.38 15 Nonmetallic covering 75°C
167°F
Fixture wiring — limited to 300 volts
RFH-2 Heat-resistant rubber Cross-linked synthetic polymer 18-16 0.76 30 None or non-metallic covering 75°C
167°F
Fixture wiring
Heat-resistant cross-linked synthetic polymer-insulated fixture wire — solid or 7-strand RFHH-2* Cross-linked synthetic polymer 18-16 0.76 30 None or non-metallic covering 90°C
194°F
Fixture wiring
RFHH-3*   18-16 1.14 45      
Silicone insulated fixture wire — solid or 7-strand SF-1 Silicone rubber 18 0.38 15 Nonmetallic covering 200°C
392°F
Fixture wiring — limited to 300 volts
SF-2 Silicone rubber 18-12
10
0.76
1.14
30
45
Nonmetallic covering 200°C
392°F
Fixture wiring
Silicone insulated fixture wire —flexible stranding SFF-1 Silicone rubber 18 0.38 15 Nonmetallic covering 150°C
302°F
Fixture wiring — limited to 300 volts
SF-2 Silicone rubber 18-12
10
0.76
1.14
30
45
Nonmetallic covering 150°C
302°F
Fixture wiring
Thermoplastic covered fixture wire — solid or 7-strand TF* Thermoplastic 18-16 0.76 30 None 60°C
140°F
Fixture wiring
Thermoplastic covered fixture wire — flexible stranding TFF* Thermoplastic 18-16 0.76 30 None 60°C
140°F
Fixture wiring
Heat-resistant thermoplastic covered fixture wire — solid or 7-strand TFN* Thermoplastic 18-16 0.38 15 Nylon jacketed or equivalent 90°C
194°F
Fixture wiring
Heat-resistant thermoplastic covered fixture wire — flexible stranded TFFN* Thermoplastic 18-16 0.38 15 Nylon jacketed or equivalent 90°C
194°F
Fixture wiring
Cross-linked polyolefin insulated fixture wire — solid or 7-strand XF* Cross-linked polyolefin 18-14
12-10
0.76
1.14
30
45
None 150°C
302°F
Fixture wiring — limited to 300 volts
Cross-linked polyolefin insulated fixture wire — flexible stranded XFF* Cross-linked polyolefin 18-14
12-10
0.76
1.14
30
45
None 150°C
302°F
Fixture wiring — limited to 300 volts
Modified ETFE — solid or 7-strand ZF Modified ethylene tetrafluoroethylene 18-14 0.38 15 None 150°C
302°F
Fixture wiring
Flexible stranding ZFF Modified ethylene tetrafluoroethylene 18-14 0.38 15 None 150°C
302°F
Fixture wiring
High temp. modified ETFE— solid or 7-strand ZHF Modified ethylene tetrafluoroethylene 18-14 0.38 15 None 200°C
392°F
Fixture wiring

*Insulations and outer coverings that meet the requirements of flame retardant, limited smoke, and are so listed, shall be permitted to be marked for limited smoke after the Code type designation.

The allowable ampacity of fixture wire shall be as specified in Table 402.5.

No conductor shall be used under such conditions that its operating temperature exceeds the temperature specified in Table 402.3 for the type of insulation involved.

Informational Note: See 310.15(A)(3) for temperature limitation of conductors.

 

Table 402.5 Allowable Ampacity for Fixture Wires
Size (AWG) Allowable Ampacity
18 6
16 8
14 17
12 23
10 28
Fixture wires shall not be smaller than 18 AWG.
The number of fixture wires permitted in a single conduit or tubing shall not exceed the percentage fill specified in Table 1, Chapter 9.
Fixture wires that are intended to be used as grounded conductors shall be identified by one or more continuous white stripes on other than green insulation or by the means described in 400.22(A) through (E).
Thermoplastic insulated fixture wire shall be durably marked on the surface at intervals not exceeding 610 mm (24 in.). All other fixture wire shall be marked by means of a printed tag attached to the coil, reel, or carton.
Fixture wire types listed in Table 402.3 shall be permitted to be surface marked to indicate special characteristics of the cable materials. These markings include, but are not limited to, markings for limited smoke, sunlight resistance, and so forth.
Fixture wires shall be permitted (1) for installation in luminaires and in similar equipment where enclosed or protected and not subject to bending or twisting in use, or (2) for connecting luminaires to the branch-circuit conductors supplying the luminaires.
Fixture wires shall not be used as branch-circuit conductors except as permitted elsewhere in this Code.
Overcurrent protection for fixture wires shall be as specified in 240.5.

I Installation

The provisions of this article apply to all switches, switching devices, and circuit breakers used as switches operating at 1000 volts and below, unless specifically referenced elsewhere in this Code for higher voltages.
Three-way and four-way switches shall be wired so that all switching is done only in the ungrounded circuit conductor. Where in metal raceways or metal-armored cables, wiring between switches and outlets shall be in accordance with 300.20(A).

Exception: Switch loops shall not require a grounded conductor.

Switches or circuit breakers shall not disconnect the grounded conductor of a circuit.

Exception: A switch or circuit breaker shall be permitted to disconnect a grounded circuit conductor where all circuit conductors are disconnected simultaneously, or where the device is arranged so that the grounded conductor cannot be disconnected until all the ungrounded conductors of the circuit have been disconnected.

The grounded circuit conductor for the controlled lighting circuit shall be provided at the location where switches control lighting loads that are supplied by a grounded general-purpose branch circuit for other than the following:
  1. Where conductors enter the box enclosing the switch through a raceway, provided that the raceway is large enough for all contained conductors, including a grounded conductor
  2. Where the box enclosing the switch is accessible for the installation of an additional or replacement cable without removing finish materials
  3. Where snap switches with integral enclosures comply with 300.15(E)
  4. Where a switch does not serve a habitable room or bathroom
  5. Where multiple switch locations control the same lighting load such that the entire floor area of the room or space is visible from the single or combined switch locations
  6. Where lighting in the area is controlled by automatic means
  7. Where a switch controls a receptacle load

Informational Note: The provision for a (future) grounded conductor is to complete a circuit path for electronic lighting control devices.

Switches and circuit breakers shall be of the externally operable type mounted in an enclosure listed for the intended use. The minimum wire-bending space at terminals and minimum gutter space provided in switch enclosures shall be as required in 312.6.

Exception No. 1: Pendant- and surface-type snap switches and knife switches mounted on an open-face switchboard or panelboard shall be permitted without enclosures.

Exception No. 2: Switches and circuit breakers installed in accordance with 110.27(A)(1), (A)(2), (A)(3), or (A)(4) shall be permitted without enclosures.

Enclosures shall not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to other switches or overcurrent devices, unless the enclosure complies with 312.8.
A surface-mounted switch or circuit breaker shall be enclosed in a weatherproof enclosure or cabinet that shall comply with 312.2.
A flush-mounted switch or circuit breaker shall be equipped with a weatherproof cover.
Switches shall not be installed within tubs or shower spaces unless installed as part of a listed tub or shower assembly.
Time switches, flashers, and similar devices shall be of the enclosed type or shall be mounted in cabinets or boxes or equipment enclosures. Energized parts shall be barriered to prevent operator exposure when making manual adjustments or switching.

Exception: Devices mounted so they are accessible only to qualified persons shall be permitted without barriers, provided they are located within an enclosure such that any energized parts within 152 mm (6.0 in.) of the manual adjustment or switch are covered by suitable barriers.

Single-throw knife switches shall be placed so that gravity will not tend to close them. Single-throw knife switches, approved for use in the inverted position, shall be provided with an integral mechanical means that ensures that the blades remain in the open position when so set.
Double-throw knife switches shall be permitted to be mounted so that the throw is either vertical or horizontal. Where the throw is vertical, integral mechanical means shall be provided to hold the blades in the open position when so set.
Single-throw knife switches and switches with butt contacts shall be connected such that their blades are de-energized when the switch is in the open position. Bolted pressure contact switches shall have barriers that prevent inadvertent contact with energized blades. Single-throw knife switches, bolted pressure contact switches, molded case switches, switches with butt contacts, and circuit breakers used as switches shall be connected so that the terminals supplying the load are de-energized when the switch is in the open position.

Exception: The blades and terminals supplying the load of a switch shall be permitted to be energized when the switch is in the open position where the switch is connected to circuits or equipment inherently capable of providing a backfeed source of power. For such installations, a permanent sign shall be installed on the switch enclosure or immediately adjacent to open switches with the following words or equivalent: WARNING — LOAD SIDE TERMINALS MAY BE ENERGIZED BY BACKFEED. The warning sign or label shall comply with 110.21(B).

General-use and motor-circuit switches, circuit breakers, and molded case switches, where mounted in an enclosure as described in 404.3, shall clearly indicate whether they are in the open (off) or closed (on) position.

Where these switch or circuit breaker handles are operated vertically rather than rotationally or horizontally, the up position of the handle shall be the closed (on) position.

Exception No. 1: Vertically operated double-throw switches shall be permitted to be in the closed (on) position with the handle in either the up or down position.

Exception No. 2: On busway installations, tap switches employing a center-pivoting handle shall be permitted to be open or closed with either end of the handle in the up or down position. The switch position shall be clearly indicating and shall be visible from the floor or from the usual point of operation.

All switches and circuit breakers used as switches shall be located so that they may be operated from a readily accessible place. They shall be installed such that the center of the grip of the operating handle of the switch or circuit breaker, when in its highest position, is not more than 2.0 m (6 ft 7 in.) above the floor or working platform.

Exception No. 1: On busway installations, fused switches and circuit breakers shall be permitted to be located at the same level as the busway. Suitable means shall be provided to operate the handle of the device from the floor.

Exception No. 2: Switches and circuit breakers installed adjacent to motors, appliances, or other equipment that they supply shall be permitted to be located higher than 2.0 m (6 ft 7 in.) and to be accessible by portable means.

Exception No. 3: Hookstick operable isolating switches shall be permitted at greater heights.

A snap switch shall not be grouped or ganged in enclosures with other snap switches, receptacles, or similar devices, unless they are arranged so that the voltage between adjacent devices does not exceed 300 volts, or unless they are installed in enclosures equipped with identified, securely installed barriers between adjacent devices.
A multipole, general-use snap switch shall not be permitted to be fed from more than a single circuit unless it is listed and marked as a two- circuit or three-circuit switch.

Informational Note: See 210.7 for disconnect requirements where more than one circuit supplies a switch.

Faceplates provided for snap switches mounted in boxes and other enclosures shall be installed so as to completely cover the opening and, where the switch is flush mounted, seat against the finished surface.
Snap switches, including dimmer and similar control switches, shall be connected to an equipment grounding conductor and shall provide a means to connect metal faceplates to the equipment grounding conductor, whether or not a metal faceplate is installed. Snap switches shall be considered to be part of an effective ground-fault current path if either of the following conditions is met:
  1. The switch is mounted with metal screws to a metal box or metal cover that is connected to an equipment grounding conductor or to a nonmetallic box with integral means for connecting to an equipment grounding conductor.
  2. An equipment grounding conductor or equipment bonding jumper is connected to an equipment grounding termination of the snap switch.

Exception No. 1 to (B): Where no means exists within the snap-switch enclosure for connecting to the equipment grounding conductor, or where the wiring method does not include or provide an equipment grounding conductor, a snap switch without a connection to an equipment grounding conductor shall be permitted for replacement purposes only. A snap switch wired under the provisions of this exception and located within 2.5 m (8 ft) vertically, or 1.5 m (5 ft) horizontally, of ground or exposed grounded metal objects shall be provided with a faceplate of nonconducting noncombustible material with nonmetallic attachment screws, unless the switch mounting strap or yoke is nonmetallic or the circuit is protected by a ground-fault circuit interrupter.

Exception No. 2 to (B): Listed kits or listed assemblies shall not be required to be connected to an equipment grounding conductor if all of the following conditions are met:

  1. The device is provided with a nonmetallic faceplate that cannot be installed on any other type of device,
  2. The device does not have mounting means to accept other configurations of faceplates,
  3. The device is equipped with a nonmetallic yoke, and
  4. All parts of the device that are accessible after installation of the faceplate are manufactured of nonmetallic materials.

Exception No. 3 to (B): A snap switch with integral nonmetallic enclosure complying with 300.15(E) shall be permitted without a connection to an equipment grounding conductor.

Metal faceplates shall be of ferrous metal not less than 0.76 mm (0.030 in.) in thickness or of nonferrous metal not less than 1.02 mm (0.040 in.) in thickness. Faceplates of insulating material shall be noncombustible and not less than 2.54 mm (0.100 in.) in thickness, but they shall be permitted to be less than 2.54 mm (0.100 in.) in thickness if formed or reinforced to provide adequate mechanical strength.
Snap switches used with open wiring on insulators shall be mounted on insulating material that separates the conductors at least 13 mm (1/2 in.) from the surface wired over.
Flush-type snap switches mounted in boxes that are set back of the finished surface as permitted in 314.20 shall be installed so that the extension plaster ears are seated against the surface. Flush-type snap switches mounted in boxes that are flush with the finished surface or project from it shall be installed so that the mounting yoke or strap of the switch is seated against the box. Screws used for the purpose of attaching a snap switch to a box shall be of the type provided with a listed snap switch, or shall be machine screws having 32 threads per inch or part of listed assemblies or systems, in accordance with the manufacturer's instructions.
A hand-operable circuit breaker equipped with a lever or handle, or a power-operated circuit breaker capable of being opened by hand in the event of a power failure, shall be permitted to serve as a switch if it has the required number of poles.

Informational Note: See the provisions contained in 240.81 and 240.83.

Metal enclosures for switches or circuit breakers shall be connected to an equipment grounding conductor as specified in Part IV of Article 250. Metal enclosures for switches or circuit breakers used as service equipment shall comply with the provisions of Part V of Article 250. Where nonmetallic enclosures are used with metal raceways or metal-armored cables, provision shall be made for connecting the equipment grounding conductor(s).

Except as covered in 404.9(B), Exception No. 1, nonmetallic boxes for switches shall be installed with a wiring method that provides or includes an equipment grounding conductor.

Knife switches rated at over 1200 amperes at 250 volts or less, and at over 1000 amperes at 251 to 1000 volts, shall be used only as isolating switches and shall not be opened under load.
To interrupt currents over 1200 amperes at 250 volts, nominal, or less, or over 600 amperes at 251 to 600 volts, nominal, a circuit breaker or a switch of special design listed for such purpose shall be used.
Knife switches of ratings less than specified in 404.13(A) and (B) shall be considered general-use switches.

Informational Note: See the definition of General-Use Switch in Article 100.

Motor-circuit switches shall be permitted to be of the knife-switch type.

Informational Note: See the definition of a Motor-Circuit Switch in Article 100.

Snap switches shall be used within their ratings and as indicated in 404.14(A) through (F).

Informational Note No. 1: For switches on signs and outline lighting, see 600.6.

Informational Note No. 2: For switches controlling motors, see 430.83, 430.109, and 430.110.

A form of general-use snap switch suitable only for use on ac circuits for controlling the following:
  1. Resistive and inductive loads not exceeding the ampere rating of the switch at the voltage applied
  2. Tungsten-filament lamp loads not exceeding the ampere rating of the switch at 120 volts
  3. Motor loads not exceeding 80 percent of the ampere rating of the switch at its rated voltage
A form of general-use snap switch suitable for use on either ac or dc circuits for controlling the following:
  1. Resistive loads not exceeding the ampere rating of the switch at the voltage applied.
  2. Inductive loads not exceeding 50 percent of the ampere rating of the switch at the applied voltage. Switches rated in horsepower are suitable for controlling motor loads within their rating at the voltage applied.
  3. Tungsten-filament lamp loads not exceeding the ampere rating of the switch at the applied voltage if T-rated.
Snap switches rated 20 amperes or less directly connected to aluminum conductors shall be listed and marked CO/ALR.
Snap switches rated 347 volts ac shall be listed and shall be used only for controlling the loads permitted by (D)(1) and (D)(2).
Noninductive loads other than tungsten-filament lamps not exceeding the ampere and voltage ratings of the switch.
Inductive loads not exceeding the ampere and voltage ratings of the switch. Where particular load characteristics or limitations are specified as a condition of the listing, those restrictions shall be observed regardless of the ampere rating of the load.

The ampere rating of the switch shall not be less than 15 amperes at a voltage rating of 347 volts ac. Flush-type snap switches rated 347 volts ac shall not be readily interchangeable in box mounting with switches identified in 404.14(A) and (B).

General-use dimmer switches shall be used only to control permanently installed incandescent luminaires unless listed for the control of other loads and installed accordingly.
Where a snap switch is used to control cord- and plug-connected equipment on a general-purpose branch circuit, each snap switch controlling receptacle outlets or cord connectors that are supplied by permanently connected cord pendants shall be rated at not less than the rating of the maximum permitted ampere rating or setting of the overcurrent device protecting the receptacles or cord connectors, as provided in 210.21(B).

Informational Note: See 210.50(A) and 400.7(A)(1) for equivalency to a receptacle outlet of a cord connector that is supplied by a permanently connected cord pendant.

Exception: Where a snap switch is used to control not more than one receptacle on a branch circuit, the switch shall be permitted to be rated at not less than the rating of the receptacle.

II Construction Specifications

Switches shall be marked with the current, voltage, and, if horsepower rated, the maximum rating for which they are designed.
Where in the off position, a switching device with a marked OFF position shall completely disconnect all ungrounded conductors to the load it controls.
Auxiliary contacts of a renewable or quick-break type or the equivalent shall be provided on all knife switches rated 600 to 1000 volts and designed for use in breaking current over 200 amperes.
A fused switch shall not have fuses in parallel except as permitted in 240.8.
The wire-bending space required by 404.3 shall meet Table 312.6(B) spacings to the enclosure wall opposite the line and load terminals.
This article covers the rating, type, and installation of receptacles, cord connectors, and attachment plugs (cord caps).

Child Care Facility. A building or structure, or portion thereof, for educational, supervisory, or personal care services for more than four children 7 years old or less.

Receptacles shall be listed and marked with the manufacturer's name or identification and voltage and ampere ratings.
Receptacles and cord connectors shall be rated not less than 15 amperes, 125 volts, or 15 amperes, 250 volts, and shall be of a type not suitable for use as lampholders.

Informational Note: See 210.21(B) for receptacle ratings where installed on branch circuits.

Receptacles rated 20 amperes or less and designed for the direct connection of aluminum conductors shall be marked CO/ALR.
Receptacles incorporating an isolated grounding conductor connection intended for the reduction of electrical noise (electromagnetic interference) as permitted in 250.146(D) shall be identified by an orange triangle located on the face of the receptacle.
Isolated ground receptacles installed in nonmetallic boxes shall be covered with a nonmetallic faceplate.

Exception: Where an isolated ground receptacle is installed in a nonmetallic box, a metal faceplate shall be permitted if the box contains a feature or accessory that permits the effective grounding of the faceplate.

All nonlocking-type, 125-volt,15- and 20-ampere receptacles that are controlled by an automatic control device, or that incorporate control features that remove power from the outlet for the purpose of energy management or building automation, shall be marked with the symbol shown in Figure 406.3(E) and located on the controlled receptacle outlet where visible after installation.

Figure 406.3(E) Controlled Receptacle Marking Symbol.

Exception: The marking is not required for receptacles controlled by a wall switch that provide the required room lighting outlets as permitted by 210.70.

Receptacle outlets shall be located in branch circuits in accordance with Part III of Article 210. General installation requirements shall be in accordance with 406.4(A) through (F).
Except as provided in 406.4(D), receptacles installed on 15- and 20-ampere branch circuits shall be of the grounding type. Grounding-type receptacles shall be installed only on circuits of the voltage class and current for which they are rated, except as provided in Table 210.21(B)(2) and Table 210.21(B)(3).
Receptacles and cord connectors that have equipment grounding conductor contacts shall have those contacts connected to an equipment grounding conductor.

Exception No. 1: Receptacles mounted on portable and vehicle-mounted generators in accordance with 250.34.

Exception No. 2: Replacement receptacles as permitted by 406.4(D).

The equipment grounding conductor contacts of receptacles and cord connectors shall be grounded by connection to the equipment grounding conductor of the circuit supplying the receptacle or cord connector.

Informational Note: For installation requirements for the reduction of electrical noise, see 250.146(D).

The branch-circuit wiring method shall include or provide an equipment grounding conductor to which the equipment grounding conductor contacts of the receptacle or cord connector are connected.

Informational Note No. 1: See