ADOPTS WITH AMENDMENTS:

International Existing Building Code 2015 (IEBC 2015)

Heads up: There are no amended sections in this chapter.
An addition to a building or structure shall comply with the International Codes as adopted for new construction without requiring the existing building or structure to comply with any requirements of those codes or of these provisions, except as required by this chapter. Where an addition impacts the existing building or structure, that portion shall comply with this code.
An addition shall not create or extend any nonconformity in the existing building to which the addition is being made with regard to accessibility, structural strength, fire safety, means of egress, or the capacity of mechanical, plumbing, or electrical systems.
Any repair or alteration work within an existing building to which an addition is being made shall comply with the applicable requirements for the work as classified in Chapter 5.

1102.1 Height Limitations

AMENDMENT
This section has been amended at the state or city level.
No addition shall increase the height of an existing building beyond that permitted under the applicable provisions of Chapter 5 of the South Carolina Building Code for new buildings.

1102.2 Area Limitations

AMENDMENT
This section has been amended at the state or city level.
No addition shall increase the area of an existing building beyond that permitted under the applicable provisions of Chapter 5 of the South Carolina Building Code for new buildings unless fire separation as required by the South Carolina Building Code is provided.

Exception: In-filling of floor openings and nonoccupiable appendages such as elevator and exit stairway shafts shall be permitted beyond that permitted by the South Carolina Building Code.

1102.3 Fire Protection Systems

AMENDMENT
This section has been amended at the state or city level.
Existing fire areas increased by the addition shall comply with Chapter 9 of the South Carolina Building Code.

1103.1 Compliance With the International South Carolina Building Code

AMENDMENT
This section has been amended at the state or city level.
Additions to existing buildings or structures are new construction and shall comply with the South Carolina Building Code.

1103.2 Additional Gravity Loads

AMENDMENT
This section has been amended at the state or city level.
Existing structural elements supporting any additional gravity loads as a result of additions shall comply with the South Carolina Building Code.
Exceptions:
  1. Structural elements whose stress is not increased by more than 5 percent.
  2. Buildings of Group R occupancy with no more than five dwelling units or sleeping units used solely for residential purposes where the existing building and the addition comply with the conventional light-frame construction methods of the South Carolina Building Code or the provisions of the South Carolina Residential Code.

1103.3 Lateral Force-Resisting System

AMENDMENT
This section has been amended at the state or city level.
The lateral force-resisting system of existing buildings to which additions are made shall comply with Sections 1103.3.1, 1103.3.2 and 1103.3.3.
Exceptions:
  1. Buildings of Group R occupancy with no more than five dwelling or sleeping units used solely for residential purposes where the existing building and the addition comply with the conventional light-frame construction methods of the South Carolina Building Code or the provisions of the South Carolina Residential Code.
  2. Any existing lateral load-carrying structural element whose demand-capacity ratio with the addition considered is not more than 10 percent greater than its demand-capacity ratio with the addition ignored shall be permitted to remain unaltered. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces and capacities shall account for the cumulative effects of additions and alterations since original construction. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations involving South Carolina Building Code-level seismic forces in accordance with Section 301.1.4.1.

1103.3.1 Vertical Addition

AMENDMENT
This section has been amended at the state or city level.
Any element of the lateral force-resisting system of an existing building subjected to an increase in vertical or lateral loads from the vertical addition shall comply with the South Carolina Building Code wind provisions and the South Carolina Building Code-level seismic forces specified in Section 301.1.4.1 of this code.

1103.3.2 Horizontal Addition

AMENDMENT
This section has been amended at the state or city level.
Where horizontal additions are structurally connected to an existing structure, all lateral force-resisting elements of the existing structure affected by such addition shall comply with the South Carolina Building Code wind provisions and the IBC-level seismic forces specified in Section 301.1.4.1 of this code.
Voluntary addition of structural elements to improve the lateral force-resisting system of an existing building shall comply with Section 807.6.

1103.4 Snow Drift Loads

AMENDMENT
This section has been amended at the state or city level.
Any structural element of an existing building subjected to additional loads from the effects of snow drift as a result of an addition shall comply with the South Carolina Building Code.
Exceptions:
  1. Structural elements whose stress is not increased by more than 5 percent.
  2. Buildings of Group R occupancy with no more than five dwelling units or sleeping units used solely for residential purposes where the existing building and the addition comply with the conventional light-frame construction methods of the South Carolina Building Code or the provisions of the South Carolina Residential Code.

1103.5 Flood Hazard Areas

AMENDMENT
This section has been amended at the state or city level.
Additions and foundations in flood hazard areas shall comply with the following requirements:
  1. For horizontal additions that are structurally interconnected to the existing building:
    1. If the addition and all other proposed work, when combined, constitute substantial improvement, the existing building and the addition shall comply with Section 1612 of the South Carolina Building Code, or Section R322 of the South Carolina Residential Code, as applicable.
    2. If the addition constitutes substantial improvement, the existing building and the addition shall comply with Section 1612 of the South Carolina Building Code, or Section R322 of the South Carolina Residential Code, as applicable.
  2. For horizontal additions that are not structurally interconnected to the existing building:
    1. The addition shall comply with Section 1612 of the South Carolina Building Code, or Section R322 of the South Carolina Residential Code, as applicable.
    2. If the addition and all other proposed work, when combined, constitute substantial improvement, the existing building and the addition shall comply with Section 1612 of the South Carolina Building Code, or Section R322 of the South Carolina Residential Code, as applicable.
  3. For vertical additions and all other proposed work that, when combined, constitute substantial improvement, the existing building shall comply with Section 1612 of the South Carolina Building Code, or Section R322 of the South Carolina Residential Code, as applicable.
  4. For a raised or extended foundation, if the foundation work and all other proposed work, when combined, constitute substantial improvement, the existing building shall comply with Section 1612 of the South Carolina Building Code, or Section R322 of the South Carolina Residential Code, as applicable.
  5. For a new foundation or replacement foundation, the foundation shall comply with Section 1612 of the South Carolina Building Code or Section R322 of the South Carolina Residential Code, as applicable.

1104.1 Smoke Alarms in Existing Portions of a Building

AMENDMENT
This section has been amended at the state or city level.
Where an addition is made to a building or structure of a Group R or I-1 occupancy, the existing building shall be provided with smoke alarms as required by Section 1103.8 of the South Carolina Fire Code or Section R314 of the South Carolina Residential Code as applicable.
Accessibility provisions for new construction shall apply to additions. An addition that affects the accessibility to, or contains an area of, primary function shall comply with the requirements of Sections 705, 806 and 906, as applicable.

1105.2 Accessible Dwelling Units and Sleeping Units

AMENDMENT
This section has been amended at the state or city level.
Where Group I-1, I-2, I-3, R-1, R-2 or R-4 dwelling or sleeping units are being added, the requirements of Section 1107 of the South Carolina Building Code for accessible units apply only to the quantity of spaces being added.

1105.3 Type A Dwelling or Sleeping Units

AMENDMENT
This section has been amended at the state or city level.
Where more than 20 Group R-2 dwelling or sleeping units are being added, the requirements of Section 1107 of the South Carolina Building Code for Type A units and Chapter 9 of the South Carolina Building Code for visible alarms apply only to the quantity of the spaces being added.

1105.4 Type B Dwelling or Sleeping Units

AMENDMENT
This section has been amended at the state or city level.
Where four or more Group I-1, I-2, R-1, R-2, R-3 or R-4 dwelling or sleeping units are being added, the requirements of Section 1107 of the South Carolina Building Code for Type B units and Chapter 9 of the South Carolina Building Code for visible alarms apply only to the quantity of spaces being added.

1106.1 Minimum Requirements

AMENDMENT
This section has been amended at the state or city level.
Additions to existing buildings shall conform to the energy requirements of the International Energy Conservation Code or South Carolina Residential Code as they relate to new construction.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING