[P] 2901.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this chapter and the South Carolina Plumbing Code shall govern the erection, installation, alteration, repairs, relocation, replacement, addition to, use or maintenance of plumbing equipment and systems. Toilet and bathing rooms shall be constructed in accordance with Section 1210. Plumbing systems and equipment shall be constructed, installed and maintained in accordance with the South Carolina Plumbing Code. Private sewage disposal systems shall conform to the International Private Sewage Disposal Code.

[P] 2902.1 Minimum Number of Fixtures

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Plumbing fixtures shall be provided in the minimum number as shown in Table 2902.1 based on the actual use of the building or space. Uses not shown in Table 2902.1 shall be considered individually by the code official. The number of occupants shall be determined by this code.
[P] TABLE 2902.1
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa
(See Sections 2902.1.1 and 2902.2)
No. CLASSIFICATION OCCUPANCY DESCRIPTION WATER CLOSETS
(URINALS SEE
SECTION 419.2 OF
THE SOUTH CAROLINA PLUMBING CODE)
LAVATORIES BATHTUBS/
SHOWERS
DRINKING
FOUNTAINS
(SEE SECTION
410 OF THE
SOUTH CAROLINA PLUMBING CODE)
OTHER
Male Female Male Female
1 Assembly A-1d Theaters and other
buildings for the per-
forming arts and motion
pictures
1 per 125 1 per 65 1 per 200 1 per 500 1 service
sink
A-2d Nightclubs, bars, tav-
erns, dance halls and
buildings for similar
purposes
1 per 40 1 per 40 1 per 75 1 per 500 1 service
sink
Restaurants, banquet
halls and food courts
1 per 75 1 per 75 1 per 200 1 per 500 1 service
sink
A-3d Auditoriums without
permanent seating, art
galleries, exhibition
halls, museums, lecture
halls, libraries, arcades
and gymnasiums
1 per 125 1 per 65 1 per 200 1 per 500 1 service
sink
Passenger terminals and
transportation facilities
1 per 500 1 per 500 1 per 750 1 per 1,000 1 service
sink
Places of worship and
other religious services
1 per 150 1 per 75 1 per 200 1 per 1,000 1 service
sink
A-4 Coliseums, arenas,
skating rinks,
pools and tennis
courts for indoor
sporting events and
activities
1 per 75 for
the first
1,500 and 1
per 120 for
the remain-
der excee-
ding 1,500
1 per 40 for
the first
1,520 and 1
per 60 for
the remain-
der exceed-
ing 1,520
1 per
200
1 per
150
1 per 1,000 1 service sink
A-5 Stadiums, amusement
parks, bleachers and
grandstands for
outdoor sporting
events and
activities
1 per 75 for
the first
1,500 and 1
per 120 for
the remain-
der exceed-
ing 1,500
1 per 40 for
the first
1,520 and 1
per 60 for
the remain-
der exceed-
ing 1,520
1 per
200
1 per
150
1 per 1,000 1 service sink
2 Business B Buildings for the
transaction of business,
professional services,
other services
involving merchandise,
office buildings,
banks, light
industrial and similar
uses
1 per 25 for the first 50
and 1 per 50 for the
remainder exceeding 50
1 per 40 for the
first 80 and 1 per
80 for the
remainder
exceeding 80
1 per 100 1 service sinke
3 Educational E Educational
facilities
1 per 50 1 per 50 1 per 100 1 service sink
4 Factory and industrial F-1 and F-2 Structures in which
occupants are
engaged in work
fabricating, assembly
or processing
of products or materials
1 per 100 1 per 100 See Sec-
tion 411 of
the South Carolina Plumbing Code
1 per 400 1 service sink
5 Institutional I-1 Residential care 1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
I-2 Hospitals, ambulatory
nursing home
care recipientb
1 per roomc 1 per roomc 1 per 15 1 per 100 1 service sink
Employees, other
than residential
careb
1 per 25 1 per 35 1 per 100
Visitors, other than
residential care
1 per 75 1 per 100 1 per 500
I-3 Prisonsb 1 per cell 1 per cell 1 per 15 1 per 100 1 service sink
I-3 Reformatories,
detention centers
and correctional centersb
1 per 15 1 per 15 1 per 15 1 per 100 1 service sink
Employeesb 1 per 25 1 per 35 1 per 100
I-4 Adult day care and
child day care
1 per 15 1 per 15 1 1 per 100 1 service sink
6 Mercantile M Retail stores, service
stations,
shops, salesrooms,
markets and shopping
centers
1 per 500 1 per 750 1 per 1,000 1 service sinke
7 Residential R-1 Hotels, motels,
boarding houses
(transient)
1 per sleeping
unit
1 per sleeping
unit
1 per sleeping
unit
1 service sink
R-2 Dormitories, fraternities,
sororities
and boarding
houses (not transient)
1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
R-2 Apartment house 1 per dwelling
unit
1 per dwelling
unit
1 per
dwelling
unit
1 kitchen sink
per dwelling
unit; 1 automatic
clothes washer connection
per 20 dwelling units
R-3 One- and two-family
dwellings and
lodging houses
with five or fewer
guest rooms
1 per dwelling
unit
1 per 10 1 per
dwelling
unit
1 kitchen sink
per dwelling
unit; 1 automatic
clothes washer connection
per dwelling unit
R-3 Congregate living
facilities with 16 or
fewer persons
1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
R-4 Congregate living
facilities with 16 or
fewer persons
1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
8 Storage S-1
S-2
Structures for the
storage of goods,
warehouses, store-
houses and freight
depots, low and
moderate hazard
1 per 100 1 per 100 See Section
411
of the
South Carolina Plumbing Code
1 per 1,000 1 service sink

a. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by this code.
b. Toilet facilities for employees shall be separate from facilities for inmates or care recipients.
c. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted, provided that each patient sleeping unit has direct access to the toilet room and provisions for privacy for the toilet room user are provided.
d. The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required.
e. For business and mercantile occupancies with an occupant load of 15 or fewer, service sinks shall not be required.
To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 2902.1. Fractional numbers resulting from applying the fixture ratios of Table 2902.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall first be summed and then rounded up to the next whole number.
Exception: The total occupant load shall not be required to be divided in half where approved statistical data indicate a distribution of the sexes of other than 50 percent of each sex.
Fixtures located within family or assisted-use toilet and bathing rooms required by Section 1109.2.1 are permitted to be included in the number of required fixtures for either the male or female occupants in assembly and mercantile occupancies.
Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Exceptions:
  1. Separate facilities shall not be required for dwelling units and sleeping units.
  2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or fewer.
  3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or less.
Where a building or tenant space requires a separate toilet facility for each sex and each toilet facility is required to have only one water closet, two family or assisted-use toilet facilities shall be permitted to serve as the required separate facilities. Family or assisted-use toilet facilities shall not be required to be identified for exclusive use by either sex as required by Section 2902.4.
Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902.1 for all users. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
Exception: Public toilet facilities shall not be required in:
  1. Open or enclosed parking garages where there are no parking attendants.
  2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet (28 m2).

[P] 2902.3.1 Access

ILLUSTRATION
The route to the public toilet facilities required by Section 2902.3 shall not pass through kitchens, storage rooms or closets. Access to the required facilities shall be from within the building or from the exterior of the building. Routes shall comply with the accessibility requirements of this code. The public shall have access to the required toilet facilities at all times that the building is occupied.
In occupancies other than covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).
Exception: The location and maximum distances of travel to required employee facilities in factory and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum distance of travel are approved.
In covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 300 feet (91 mm). In mall buildings, the required facilities shall be based on total square footage (m2) within a covered mall building or within the perimeter line of an open mall building, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The maximum distance of travel to central toilet facilities in mall buildings shall be measured from the main entrance of any store or tenant space. In mall buildings, where employees' toilet facilities are not provided in the individual store, the maximum distance of travel shall be measured from the employees' work area of the store or tenant space.
Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities. Required facilities shall be free of charge.
Where a toilet room is provided for the use of multiple occupants, the egress door for the room shall not be lockable from the inside of the room. This section does not apply to family or assisted-use toilet rooms.
Toilet rooms shall not open directly into a room used for the preparation of food for service to the public.
Required public facilities shall be provided with signs that designate the sex as required by Section 2902.2. Signs shall be readily visible and located near the entrance to each toilet facility. Signs for accessible toilet facilities shall comply with Section 1111.
Directional signage indicating the route to the required public toilet facilities shall be posted in a lobby, corridor, aisle or similar space, such that the sign can be readily seen from the main entrance to the building or tenant space.
Drinking fountains shall not be required to be located in individual tenant spaces provided that public drinking fountains are located within a distance of travel of 500 feet (152 m) of the most remote location in the tenant space and not more than one story above or below the tenant space. Where the tenant space is in a covered or open mall, such distance shall not exceed 300 feet (91 440 mm). Drinking fountains shall be located on an accessible route.
Drinking fountains shall not be required for an occupant load of 15 or fewer.