ADOPTS WITH AMENDMENTS:

International Building Code 2018 (IBC 2018)

Heads up: There are no amended sections in this chapter.

Chapter 31 Special Construction

AMENDMENT
This section has been amended at the state or city level.
CALIFORNIA BUILDING CODE — MATRIX ADOPTION TABLE
CHAPTER 31— SPECIAL CONSTRUCTION

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5
Adopt entire chapter X X X X X X
Adopt entire chapter as
amended (amended
sections listed below)
X X X X
Adopt only those
sections that are
listed below
X X X X
Chapter / Section
3101 X
3102.1 X
3102.3.1 X
3103 X
3104 X
3104.2, Exception 2 X X
3105 X
3106 X
3109
3109.1 X X
3109.2 X
3110 X
3111 X
3111.1.1 X X
3111.1.1, Exception X X
3111.3 X X X X
3112.2 X
3112.3, Exception X X
3113
3113.1 X X
3113.1.1 X X
3113.2, Exception X X
3113.3, Exception X X
3113.4, Exception X X
The state agency does not adopt sections identified with the following symbol:
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.



User notes:
About this chapter: Chapter 31 provides regulations for unique buildings and building elements. Those include buildings such as membrane structures, greenhouses and relocatable buildings. Special elements include pedestrian walkways and tunnels, awnings, canopies and marquees, vehicular gates and solar energy systems.

Code development reminder: Code change proposals to sections preceded by the designation [BS] will be considered by the IBC—Structural Code Development Committee during the 2019 (Group B) Code Development Cycle. See explanation on page ix.


The provisions of this chapter shall govern special building construction including membrane structures, temporary structures, pedestrian walkways and tunnels, automatic vehicular gates, awnings and canopies, marquees, signs, towers, antennas, relocatable buildings, swimming pool enclosures and safety devices, and solar energy systems.

3102.1 General

AMENDMENT
This section has been amended at the state or city level.
The provisions of Sections 3102.1 through 3102.8 shall apply to air-supported, air-inflated, membrane-covered cable, membrane-covered frame and tensile membrane structures, collectively known as membrane structures, erected for a period of 180 days or longer. Those erected for a shorter period of time shall comply with the California Fire Code. Membrane structures covering water storage facilities, water clarifiers, water treatment plants, sewage treatment plants, greenhouses and similar facilities not used for human occupancy are required to meet only the requirements of Sections 3102.3.1 and 3102.7. Membrane structures erected on a building, balcony, deck or other structure for any period of time shall comply with this section.
Tensile membrane structures and air-supported structures, including permanent and temporary structures, shall be designed and constructed in accordance with ASCE 55. The provisions in Sections 3102.3 through 3102.6 shall apply.
Noncombustible membrane structures shall be classified as Type IIB construction. Noncombustible frame or cable-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IIB construction. Heavy timber frame-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IV construction. Other membrane structures shall be classified as Type V construction.
Exception: Plastic less than 30 feet (9144 mm) above any floor used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.

3102.3.1 Membrane and Interior Liner Material

AMENDMENT
This section has been amended at the state or city level.

Membranes and interior liners shall be either noncombustible as set forth in Section 703.5 shall be flame resistant in accordance with the provisions set forth in CCR, Title 19, Division 1, Chapter 8. Tops and sidewalls shall be made either from fabric that has been flame resistant treated with an approved exterior chemical process by an approved application concern, or from inherently flame resistant fabric approved and listed by the State Fire Marshal (see CCR, Title 19, Division 1, Chapter 8).

Exception: Plastic less than 20 mil (0.5 mm) in thickness used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.

The area of a membrane structure shall not exceed the limitations specified in Section 506.

Membrane structures shall not exceed one story nor shall such structures exceed the height limitations in feet specified in Section 504.3.

Exception: Noncombustible membrane structures serving as roofs only.

Membrane structures shall be permitted to be utilized as specified in this section as a portion of buildings of other types of construction. Height and area limits shall be as specified for the type of construction and occupancy of the building.
A noncombustible membrane shall be permitted for use as the roof or as a skylight of any building or atrium of a building of any type of construction provided that the membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery.
A membrane meeting the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 shall be permitted to be used as the roof or as a skylight on buildings of Type IIB, III, IV and V construction, provided that the membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery.
The structure shall be designed and constructed to sustain dead loads; loads due to tension or inflation; live loads including wind, snow or flood and seismic loads and in accordance with Chapter 16.
For membrane-covered frame structures, the membrane shall not be considered to provide lateral restraint in the calculation of the capacities of the frame members.
Air-supported and air-inflated structures shall be provided with primary and auxiliary inflation systems to meet the minimum requirements of Sections 3102.8.1 through 3102.8.3.
The inflation system shall consist of one or more blowers and shall include provisions for automatic control to maintain the required inflation pressures. The system shall be so designed as to prevent overpressurization of the system.
In addition to the primary inflation system, in buildings larger than 1,500 square feet (140 m2) in area, an auxiliary inflation system shall be provided with sufficient capacity to maintain the inflation of the structure in case of primary system failure. The auxiliary inflation system shall operate automatically when there is a loss of internal pressure and when the primary blower system becomes inoperative.

Blower equipment shall meet all of the following requirements:

  1. Blowers shall be powered by continuous-rated motors at the maximum power required for any flow condition as required by the structural design.
  2. Blowers shall be provided with inlet screens, belt guards and other protective devices as required by the building official to provide protection from injury.
  3. Blowers shall be housed within a weather-protecting structure.
  4. Blowers shall be equipped with backdraft check dampers to minimize air loss when inoperative.
  5. Blower inlets shall be located to provide protection from air contamination. The location of inlets shall be approved.

3102.8.2 Standby Power

ILLUSTRATION
Wherever an auxiliary inflation system is required, an approved standby power-generating system shall be provided. The system shall be equipped with a suitable means for automatically starting the generator set upon failure of the normal electrical service and for automatic transfer and operation of all of the required electrical functions at full power within 60 seconds of such service failure. Standby power shall be capable of operating independently for not less than 4 hours.
A system capable of supporting the membrane in the event of deflation shall be provided for in air-supported and air-inflated structures having an occupant load of 50 or more or where covering a swimming pool regardless of occupant load. The support system shall be capable of maintaining membrane structures used as a roof for Type I construction not less than 20 feet (6096 mm) above floor or seating areas. The support system shall be capable of maintaining other membranes not less than 7 feet (2134 mm) above the floor, seating area or surface of the water.

3103.1 General

AMENDMENT
This section has been amended at the state or city level.
The provisions of Sections 3103.1 through 3103.4 shall apply to structures erected for a period of less than 180 days. Tents, umbrella structures and other membrane structures erected for a period of less than 180 days shall comply with the California Fire Code. Those erected for a longer period of time shall comply with applicable sections of this code.

3103.1.1 Conformance

AMENDMENT
This section has been amended at the state or city level.
Temporary structures and uses shall conform to the structural strength, fire safety, means of egress, accessibility, light, ventilation and sanitary requirements of this code as necessary to ensure public health, safety and general welfare. See Section 106A.1.7 for permit requirements.
Temporary structures that cover an area greater than 120 square feet (11.16 m2), including connecting areas or spaces with a common means of egress or entrance that are used or intended to be used for the gathering together of 10 or more persons, shall not be erected, operated or maintained for any purpose without obtaining a permit from the building official.
A permit application and construction documents shall be submitted for each installation of a temporary structure. The construction documents shall include a site plan indicating the location of the temporary structure and information delineating the means of egress and the occupant load.
Temporary structures shall be located in accordance with the requirements of Table 602 based on the fire-resistance rating of the exterior walls for the proposed type of construction.

3103.4 Means of Egress

ILLUSTRATION
Temporary structures shall conform to the means of egress requirements of Chapter 10 and shall have an exit access travel distance of 100 feet (30 480 mm) or less.
This section shall apply to connections between buildings such as pedestrian walkways or tunnels, located at, above or below grade level, that are used as a means of travel by persons. The pedestrian walkway shall not contribute to the building area or the number of stories or height of connected buildings.
Pedestrian walkways shall be designed and constructed in accordance with Sections 3104.2 through 3104.9. Tunnels shall be designed and constructed in accordance with Sections 3104.2 and 3104.10.

3104.2 Separate Structures

AMENDMENT
This section has been amended at the state or city level.

Buildings connected by pedestrian walkways or tunnels shall be considered to be separate structures.


Exceptions:

  1. Buildings that are on the same lot and considered as portions of a single building in accordance with Section 503.1.2.
  2. [DSA-AC and HCD 1-AC] For purposes of accessibility in residential facilities as required by Chapters 11A and 11B, structurally connected buildings, buildings connected by stairs, walkways, or roofs, and buildings with multiple wings shall be considered one structure.

The pedestrian walkway shall be of noncombustible construction.

Exceptions:

  1. Combustible construction shall be permitted where connected buildings are of combustible construction.
  2. Fire-retardant-treated wood, in accordance with Section 603.1, Item 1.3, shall be permitted for the roof construction of the pedestrian walkway where connected buildings are not less than Type I or II construction.
Only materials and decorations approved by the building official shall be located in the pedestrian walkway.

The connection of a pedestrian walkway to a building shall comply with Section 3104.5.1, 3104.5.2, 3104.5.3 or 3104.5.4.

Exception: Buildings that are on the same lot and considered as portions of a single building in accordance with Section 503.1.2.

3104.5.1 Fire Barriers

ILLUSTRATION
Pedestrian walkways shall be separated from the interior of the building by not less than 2-hour fire barriers constructed in accordance with Section 707 and Sections 3104.5.1.1 through 3104.5.1.3.
Exterior walls of buildings connected to pedestrian walkways shall be 2-hour fire-resistance rated. This protection shall extend not less than 10 feet (3048 mm) in every direction surrounding the perimeter of the pedestrian walkway.
Openings in exterior walls required to be fire-resistance rated in accordance with Section 3104.5.1.1 shall be equipped with opening protectives providing a not less than 3/4-hour fire protection rating in accordance with Section 716.
The fire barrier shall be supported by construction as required by Section 707.5.1.

The wall separating the pedestrian walkway and the building shall comply with Section 3104.5.2.1 or 3104.5.2.2 where:

  1. The distance between the connected buildings is more than 10 feet (3048 mm).
  2. The pedestrian walkway and connected buildings are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, and the roof of the walkway is not more than 55 feet (16 764 mm) above grade connecting to the fifth, or lower, story above grade plane, of each building.

Exception: Open parking garages need not be equipped with an automatic sprinkler system.

The wall shall be capable of resisting the passage of smoke.
The wall shall be constructed of a tempered, wired or laminated glass and doors separating the interior of the building from the pedestrian walkway. The glass shall be protected by an automatic sprinkler system in accordance with Section 903.3.1.1 that, when actuated, shall completely wet the entire surface of interior sides of the wall or glass. Obstructions shall not be installed between the sprinkler heads and the wall or glass. The glass shall be in a gasketed frame and installed in such a manner that the framing system will deflect without breaking (loading) the glass before the sprinkler operates.

Where the distance between the connected buildings is more than 10 feet (3048 mm), the walls at the intersection of the pedestrian walkway and each building need not be fire-resistance rated provided that both sidewalls of the pedestrian walkway are not less than 50 percent open with the open area uniformly distributed to prevent the accumulation of smoke and toxic gases. The roof of the walkway shall be located not more than 40 feet (12 160 mm) above grade plane, and the walkway shall only be permitted to connect to the third or lower story of each building.

Exception: Where the pedestrian walkway is protected with a sprinkler system in accordance with Section 903.3.1.1, the roof of the walkway shall be located not more than 55 feet (16 764 mm) above grade plane and the walkway shall only be permitted to connect to the fifth or lower story of each building.

Where exterior walls of connected buildings are required by Section 705 to have a fire-resistance rating greater than 2 hours, the walls at the intersection of the pedestrian walkway and each building need not be fire-resistance rated provided:

  1. The pedestrian walkway is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
  2. The roof of the walkway is not located more than 55 feet (16 764 mm) above grade plane and the walkway connects to the fifth, or lower, story above grade plane of each building.
Access shall be provided at all times to a pedestrian walkway that serves as a required exit.
The unobstructed width of pedestrian walkways shall be not less than 36 inches (914 mm). The total width shall be not greater than 30 feet (9144 mm).

3104.9 Exit Access Travel

ILLUSTRATION

The length of exit access travel shall be 200 feet (60 960 mm) or less.

Exceptions:

  1. Exit access travel distance on a pedestrian walkway equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall be 250 feet (76 200 mm) or less.
  2. Exit access travel distance on a pedestrian walkway constructed with both sides not less than 50 percent open shall be 300 feet (91 440 mm) or less.
  3. Exit access travel distance on a pedestrian walkway constructed with both sides not less than 50 percent open, and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, shall be 400 feet (122 m) or less.
Separation between the tunneled walkway and the building to which it is connected shall be not less than 2-hour fire-resistant construction and openings therein shall be protected in accordance with Section 716.
Awnings and canopies shall comply with the requirements of Sections 3105.2 and 3105.3 and other applicable sections of this code.
Awnings and canopies shall be designed and constructed to withstand wind or other lateral loads and live loads as required by Chapter 16 with due allowance for shape, open construction and similar features that relieve the pressures or loads. Structural members shall be protected to prevent deterioration. Awnings shall have frames of noncombustible material, fire-retardant-treated wood, heavy timber complying with Section 2304.11, or 1-hour construction with combustible or noncombustible covers and shall be either fixed, retractable, folding or collapsible.

3105.3 Awnings and Canopy Materials

AMENDMENT
This section has been amended at the state or city level.

Awnings and canopies shall be provided with an approved covering that complies with one of the following:

  1. The fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.
  2. Has a flame spread index not greater than 25 when tested in accordance with ASTM E84 or UL 723.
  3. Meets all of the following criteria when tested in accordance with NFPA 286:

    1. 3.1. During the 40 kW exposure, flames shall not spread to the ceiling.
    2. 3.2. Flashover, as defined in NFPA 286, shall not occur.
    3. 3.3. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
    4. 3.4. The peak heat release rate throughout the test shall not exceed 800 kW.
     All fabrics and all interior decorative fabrics or materials shall be flame resistant in accordance with the provisions set forth in CCR, Title 19, Division 1, Chapter 8. Tops and sidewalls shall be made either from fabric that has been flame resistant treated with an approved exterior chemical process by an approved application concern, or from inherently flame resistant fabric approved and listed by the State Fire Marshal (see CCR, Title 19, Division 1, Chapter 8).

Exception: The fire propagation performance and flame spread index requirements shall not apply to awnings installed on detached one- and two-family dwellings.

Marquees shall comply with Sections 3106.2 through 3106.5 and other applicable sections of this code.
The height or thickness of a marquee measured vertically from its lowest to its highest point shall be not greater than 3 feet (914 mm) where the marquee projects more than two-thirds of the distance from the lot line to the curb line, and shall be not greater than 9 feet (2743 mm) where the marquee is less than two-thirds of the distance from the lot line to the curb line.
Where the roof or any part thereof is a skylight, the skylight shall comply with the requirements of Chapter 24. Every roof and skylight of a marquee shall be sloped to downspouts that shall conduct any drainage from the marquee in such a manner so as not to spill over the sidewalk.
Every marquee shall be so located as not to interfere with the operation of any exterior standpipe, and such that the marquee does not obstruct the clear passage of stairways or exit discharge from the building or the installation or maintenance of street lighting.
A marquee shall be supported entirely from the building and constructed of noncombustible materials. Marquees shall be designed as required in Chapter 16. Structural members shall be protected to prevent deterioration.

3107.1 General

AMENDMENT
This section has been amended at the state or city level.
Except as otherwise provided herein, all signs placed upon or attached to any building, structure or property shall comply with this chapter and shall be installed under a valid sign permit.

The electrical portion of the sign shall be constructed in accordance with the requirements of the Electrical Code, and an electrical permit shall be obtained in accordance with that code.

Plans shall be filed with the application for a permit for any sign. When required, computations shall be provided.

3107.1.1 Exempt Signs

AMENDMENT
This section has been amended at the state or city level.
The following signs are exempt from the requirements of this code:
  1. Signs painted on structures. However, such signs must comply with the San Francisco Planning Code, and an application shall be filed with the Department.
  2. Bulletin boards for public, charitable or religious institutions, when such boards are located on the premises of said institutions.
  3. Real estate signs advertising the sale, rental or lease of the premises on which they are maintained, which do not exceed 15 square feet (1.39 m2) in size, and which are mounted flush to the building.
  4. Professional occupation signs denoting only the name and profession of an occupant in a commercial building, public institutional building or dwelling house, and not exceeding 3 square feet (0.278 m2) in area for each occupant.

3107.1.2 Prohibitions

AMENDMENT
This section has been amended at the state or city level.
The following prohibitions apply to signs:
  1. No signs shall be erected, relocated or maintained so as to block any exits or required windows. No sign shall be attached to a standpipe, gutter drain, stairway or fire escape, or interfere with the function or operation of any standpipe or fire escape. No roof sign shall be located within 6 feet (1.829 m) of a standpipe outlet.
  2. No sign shall be increased in size, altered in shape or changed by the addition of other signs or advertising matter not specifically allowed by the provisions of this code and the San Francisco Planning Code.
  3. No wall sign shall extend across or in front of any window or other exterior opening located above the first story of a building, except as approved by the Building Official.
  4. No wall sign erected on a wall adjacent to and facing a street, public space or yard shall project above the parapet walls.
Exceptions:
  1. On a building located on a corner lot, a wall sign may project a maximum of 7 feet (2.134 m) above the roof line on only one street.
  2. On any frontage, signs not more than 10 feet (3.048 m) long for any 40-foot (12.19 m) frontage and occupying no more than 25 percent of the lot frontage may project a maximum of 7 feet (2.134 m) above the roof line.

3107.1.3 Permit Number on Sign

AMENDMENT
This section has been amended at the state or city level.
Every sign shall have the permit number clearly painted and maintained on its face or edge, and of such size and location as to be legible from the sidewalk level, ground level or an easily accessible location. Electric signs may have an approved metal tag attached to them instead of painted characters.

3107.1.4 Revocable Permits

AMENDMENT
This section has been amended at the state or city level.
The permit for any sign over public property may be revoked. A permit granted under Chapter 1A and this chapter for a sign over public property shall not be construed to create any perpetual right but is a revocable license which may be terminated by revocation by the Board of Supervisors.

3107.1.5 Existing Signs

AMENDMENT
This section has been amended at the state or city level.
This chapter shall not render unlawful the existence or maintenance of any sign erected or maintained by a lawful permit issued prior to the adoption of this ordinance.
Exception: Signs for which lawful permits were issued and which, due to a sidewalk narrowing or street widening project, no longer conform to the requirements of Section 3107.3 shall be altered to conform not later than 90 days following completion of such project.

3107.2 Definitions

AMENDMENT
This section has been amended at the state or city level.
For the purposes of this chapter, certain terms are defined as follows:

APPROVED PLASTIC is a plastic material found to be suitable functionally for the purpose for which it is intended and which complies with the requirements of Chapter 26. For outdoor signs, the approval of the plastic shall be based upon considerations of flame spread value only. For indoor signs, the approval shall be based upon flame spread and smoke density values.

AREA OF A SIGN is that area of exposed vertical surface which is included within a rectangle enclosing all the features of the sign. In cases of an irregular sign, it is the sum of the areas of the enclosing rectangles estimated to the nearest 5 square feet (0.465 m2).

BUSINESS SIGN is a sign which directs attention to a business, commodity, service, industry or other activity which is sold, offered or conducted on the premises upon which such sign is located, or to which it is affixed.

SIGN is any structure, part thereof, or device or inscription which is located upon, attached to or painted, projected or represented on the exterior of any building or structure, including an awning, canopy, marquee or similar appendage, or affixed to the glass on the outside or inside of a window so as to be seen from the outside of the building, and which displays or includes any numeral, letter, word, model, banner, emblem, insignia, symbol, device, light, trademark or other representation used as, or in the nature of, an announcement, advertisement or designation by or of any person, firm, group, organization, place, commodity, product, service, business, profession, enterprise or industry. A sign includes the support, uprights and framework of the display.

3107.3 Height, Projection, and Location

AMENDMENT
This section has been amended at the state or city level.
Height, projection and location of all signs shall be as specified in Article 6 of the San Francisco Planning Code. No sign shall project past the curbline of any street, alley or public way.

The minimum vertical clearance of signs over public sidewalks shall be 10 feet (3.048 m). Additionally, signs or portions within the outer one- third of a sidewalk shall have 12-foot (3.658 m) clearance, and when within 2 feet (0.61 m) of the curbline shall have 14-foot (4.267 m) clearance.

Roof signs shall be not less than 5 feet (1.524 m) above the roof. Supports shall be spaced at least 6 feet (1.829 m) apart.

3107.4 Design

AMENDMENT
This section has been amended at the state or city level.
The design shall make allowances for the effects of corrosion and lack of maintenance.

No anchor or support of any sign shall be connected to, or suspended by, an unbraced parapet wall, unless such wall is designed in accordance with the requirements for parapet walls specified in Chapter 16.

Fasteners and braces shall be of noncombustible construction, except that stringers for attachment of roof signs may be of 6-inch (152.4 mm) minimum dimension redwood or approved preservative-treated lumber.

3107.5 Construction

AMENDMENT
This section has been amended at the state or city level.

3107.5.1 General

AMENDMENT
This section has been amended at the state or city level.
All signs shall be constructed of noncombustible materials except that approved plastics may be used in sign facings as described in Section 3107.5.2. All ferrous metal and all fastenings used in construction or installation, excluding stainless steel, shall be hot-dipped galvanized, porcelain-enameled or otherwise protected in an approved manner against corrosion.

Aluminum may only be used for minor internal members, such as stiffeners and closures, and for sign faces and nonstructural trim. The minimum thickness shall be 0.0299 inch (0.76 mm).

Steel shapes or plates used for primary support shall be not less than 3/16 inch (4.76 mm) in thickness. Sheet metal formed integrally with the sign face or used as cabinet cover shall be not less than 0.0239 inch (24 gauge). Secondary support members not formed integrally with the design face shall be not less than 0.1046 (12 gauge) inch.

The minimum material thickness requirements in this section pertain to the base metal before application of protective covering and need not apply to signs located inside a building.

3107.5.2 Plastics

AMENDMENT
This section has been amended at the state or city level.
Where plastics are included in a sign, the application to install a sign shall set forth the manufacturer's trade name, or the common name of the plastic material to be used in the sign, thickness of plastic, aspect ratio, corrugation type, if any, and span. The plastic employed in the signs shall be identified as set forth in Chapter 26 with the manufacturer's trade name, or with the common name of the plastic material.

Plastic sign facing shall conform to the provisions of this section. Plastic sign faces, formed or flat, letters and decorations shall be of sufficient thickness or so formed or supported that they will withstand all loads required by this code.

Plastic facing shall be mounted in a metal frame. Proper provision shall be made for the difference in thermal expansion between plastic members and the frame.

3107.5.3 Electric Plastic Signs

AMENDMENT
This section has been amended at the state or city level.
Every electric sign containing approved plastics shall comply with the minimum requirements set forth in the Standard for Electric Signs, UL No. 48. The attachment of Underwriters Laboratories label, or other approved laboratory per the Electrical Code, shall be sufficient proof that a sign has complied with the requirements of the Electrical Code.

3107.5.4 Wood-Faced Signs

AMENDMENT
This section has been amended at the state or city level.
Projecting signs with wood facing or backing are permitted on any building.

Plywood used for signs shall be exterior grade and not less than 5/8-inch (15.88 mm) thickness. Lumber shall be not less than 1-inch (25.4 mm) nominal and shall be finished to provide a weather- resistant finish.

3107.6 Ground Signs

AMENDMENT
This section has been amended at the state or city level.

3107.6.1 Height

AMENDMENT
This section has been amended at the state or city level.
The maximum height of a ground sign constructed with wood supports shall be 30 feet (9.14 m), as measured from the top of the sign to the sidewalk in front of the sign or the existing ground under the sign, whichever is higher.

3107.6.2 Design and Construction

AMENDMENT
This section has been amended at the state or city level.
The design and construction of wood signs shall comply with Chapters 16 and 23 of this code. All wood within 12 inches of the ground shall be pressure-treated wood.

3107.7 Removal of Business Signs

AMENDMENT
This section has been amended at the state or city level.
It shall be unlawful for any person to allow any business sign to remain posted more than 180 days after the activity for which the business sign has been posted has ceased operation on the premises if such person (1) owns, leases or rents the property on which the sign is posted, or (2) owns or operates such business, service, industry or other activity.
Towers shall be designed and constructed in accordance with the provisions of TIA-222. Towers shall be designed for seismic loads; exceptions related to seismic design listed in Section 2.7.3 of TIA-222 shall not apply. In Section 2.6.6.2 of TIA 222, the horizontal extent of Topographic Category 2, escarpments, shall be 16 times the height of the escarpment.
Exception: Single free-standing poles used to support antennas not greater than 75 feet (22 860 mm), measured from the top of the pole to grade, shall not be required to be noncombustible.
Towers shall be located such that guy wires and other accessories shall not cross or encroach on any street or other public space, or over above-ground electric utility lines, or encroach on any privately owned property without the written consent of the owner of the encroached-upon property, space or above-ground electric utility lines. Towers shall be equipped with climbing and working facilities in compliance with TIA-222. Access to the tower sites shall be limited as required by applicable OSHA, FCC and EPA regulations.

3109.1 General

AMENDMENT
This section has been amended at the state or city level.
The design and construction of swimming pools, spas and hot tubs shall comply with the International Swimming Pool and Spa Code. [DSA-SS and DSA-SS/CC] Swimming pools utilized for public school purposes shall also be designed, constructed and inspected in accordance with this code.

3109.2 California Swimming Pool Safety Act (Statewide)

AMENDMENT
This section has been amended at the state or city level.
The following text in this section contains the statutory language in the Swimming Pool Safety Act (HS Code, §§ 115920 — 115929) that is required to be duplicated and published in California Code of Regulations, Title 24. As such, the section numbers reflect those within the Health and Safety Code.

115920. This act shall be known and may be cited as the Swimming Pool Safety Act.

(Added by Stats. 1996, Ch. 925, Sec. 3.5. Effective January 1, 1997.)

115921. As used in this article the following terms have the following meanings:
  1. "Swimming pool" or "pool" means any structure intended for swimming or recreational bathing that contains water over 18 inches deep. "Swimming pool" includes in-ground and aboveground structures and includes, but is not limited to, hot tubs, spas, portable spas, and nonportable wading pools.
  2. "Public swimming pool" means a swimming pool operated for the use of the general public with or without charge, or for the use of the members and guests of a private club. Public swimming pool does not include a swimming pool located on the grounds of a private single-family home.
  3. "Enclosure" means a fence, wall, or other barrier that isolates a swimming pool from access to the home.
  4. "Approved safety pool cover" means a manually or power-operated safety pool cover that meets all of the performance standards of the American Society for Testing and Materials (ASTM), in compliance with standard F1346-91.
  5. "Exit alarms" means devices that make audible, continuous alarm sounds when any door or window, that permits access from the residence to the pool area that is without any intervening enclosure, is opened or is left ajar. Exit alarms may be battery operated or may be connected to the electrical wiring of the building.
  6. "ANSI/APSP performance standard" means a standard that is accredited by the American National Standards Institute (ANSI) and published by the Association of Pool and Spa Professionals (APSP).
  7. "Suction outlet" means a fitting or fixture typically located at the bottom or on the sides of a swimming pool that conducts water to a recirculating pump.
[Amended by Stats. 2012, Ch. 679, Sec. 1. (AB 2114) Effective January 1, 2013.]

115922.
  1. Except as provided in Section 115925, when a building permit is issued for the construction of a new swimming pool or spa or the remodeling of an existing swimming pool or spa at a private single-family home, the respective swimming pool or spa shall be equipped with at least two of the following seven drowning prevention safety features:
    1. An enclosure that meets the requirements of Section 115923 and isolates the swimming pool or spa from the private single-family home.
    2. Removable mesh fencing that meets American Society for Testing and Materials (ASTM) Specifications F2286 standards in conjunction with a gate that is self-closing and self-latching and can accommodate a key lockable device.
    3. An approved safety pool cover, as defined in subdivision (d) of Section 115921.
    4. Exit alarms on the private single-family home's doors that provide direct access to the swimming pool or spa. The exit alarm may cause either an alarm noise or a verbal warning, such as a repeating notification that "the door to the pool is open."
    5. A self-closing, self-latching device with a release mechanism placed no lower than 54 inches above the floor on the private single-family home's doors providing direct access to the swimming pool or spa.
    6. An alarm that, when placed in a swimming pool or spa, will sound upon detection of accidental or unauthorized entrance into the water. The alarm shall meet and be independently certified to the ASTM Standard F2208 "Standard Safety Specification for Residential Pool Alarms," which includes surface motion, pressure, sonar, laser, and infrared type alarms. A swimming protection alarm feature designed for individual use, including an alarm attached to a child that sounds when the child exceeds a certain distance or becomes submerged in water, is not a qualifying drowning prevention safety feature.
    7. Other means of protection, if the degree of protection afforded is equal to or greater than that afforded by any of the features set forth above and has been independently verified by an approved testing laboratory as meeting standards for those features established by the ASTM or the American Society of Mechanical Engineers (ASME).
  2. Before the issuance of a final approval for the completion of permitted construction or remodeling work, the local building code official shall inspect the drowning safety prevention features required by this section and, if no violations are found, shall give final approval.
[Amended by Stats. 2017, Ch. 670, Sec. 4. (SB 442) Effective January 1, 2018.]

115923. An enclosure shall have all of the following characteristics:
  1. Any access gates through the enclosure open away from the swimming pool, and are self-closing with a self-latching device placed no lower than 60 inches above the ground.
  2. A minimum height of 60 inches.
  3. A maximum vertical clearance from the ground to the bottom of the enclosure of two inches.
  4. Gaps or voids, if any, do not allow passage of a sphere equal to or greater than four inches in diameter.
  5. An outside surface free of protrusions, cavities, or other physical characteristics that would serve as handholds or footholds that could enable a child below the age of five years to climb over.
(Added by Stats. 1996, Ch. 925, Sec. 3.5. Effective January 1, 1997.)

115924.
  1. Any person entering into an agreement to build a swimming pool or spa, or to engage in permitted work on a pool or spa covered by this article, shall give the consumer notice of the requirements of this article.
  2. Pursuant to existing law, the Department of Health Services shall have available on the department's Web site, commencing January 1, 2007, approved pool safety information available for consumers to download. Pool contractors are encouraged to share this information with consumers regarding the potential dangers a pool or spa poses to toddlers. Additionally, pool contractors may provide the consumer with swimming pool safety materials produced from organizations such as the United States Consumer Product Safety Commission, Drowning Prevention Foundation, California Coalition for Children's Safety & Health, Safe Kids Worldwide, Association of Pool and Spa Professionals, or the American Academy of Pediatrics.
(Amended by Stats. 2006, Ch. 478, Sec. 3. Effective January 1, 2007.)

115925. The requirements of this article do not apply to any of the following:
  1. Public swimming pools.
  2. Hot tubs or spas with locking safety covers that comply with the American Society for Testing and Materials (ASTM F1346).
  3. An apartment complex, or any residential setting other than a single-family home.
[Amended by Stats. 2017, Ch. 670, Sec. 5. (SB 442) Effective January 1, 2018.]

115926. This article does not apply to any facility regulated by the State Department of Social Services even if the facility is also used as the private residence of the operator. Pool safety in those facilities shall be regulated pursuant to regulations adopted therefor by the State Department of Social Services.

(Added by Stats. 1996, Ch. 925, Sec. 3.5. Effective January 1, 1997.)

115927. Notwithstanding any other provision of law, this article shall not be subject to further modification or interpretation by any regulatory agency of the state, this authority being reserved exclusively to local jurisdictions, as provided for in subdivision (e) of Section 115922 and subdivision (c) of Section 115924.

(Added by Stats. 1996, Ch. 925, Sec. 3.5. Effective January 1, 1997.)

115928. Whenever a building permit is issued for the construction of a new swimming pool or spa, the pool or spa shall meet all of the following requirements:
    1. The suction outlets of the pool or spa for which the permit is issued shall be equipped to provide circulation throughout the pool or spa as prescribed in paragraphs (2) and (3).
    2. The swimming pool or spa shall either have at least two circulation suction outlets per pump that shall be hydraulically balanced and symmetrically plumbed through one or more "T" fittings, and that are separated by a distance of at least three feet in any dimension between the suction outlets, or be designed to use alternatives to suction outlets, including, but not limited to, skimmers or perimeter overflow systems to conduct water to the recirculation pump.
    3. The circulation system shall have the capacity to provide a complete turnover of pool water, as specified in Section 3124B of Chapter 31B of the California Building Standards Code (Title 24 of the California Code of Regulations).
  1. Suction outlets shall be covered with antientrapment grates, as specified in the ANSI/APSP-16 performance standard or successor standard designated by the federal Consumer Product Safety Commission, that cannot be removed except with the use of tools. Slots or openings in the grates or similar protective devices shall be of a shape, area, and arrangement that would prevent physical entrapment and would not pose any suction hazard to bathers.
  2. Any backup safety system that an owner of a new swimming pool or spa may choose to install in addition to the requirements set forth in subdivisions (a) and (b) shall meet the standards as published in the document, "Guidelines for Entrapment Hazards: Making Pools and Spas Safer," Publication Number 363, March 2005, United States Consumer Product Safety Commission.
[Amended by Stats. 2012, Ch. 679, Sec. 2. (AB 2114) Effective January 1, 2013.]

115928.5. Whenever a building permit is issued for the remodel or modification of an existing swimming pool, toddler pool, or spa, the permit shall require that the suction outlet or suction outlets of the existing swimming pool, toddler pool, or spa be upgraded so as to be equipped with antientrapment grates, as specified in the ANSI/APSP-16 performance standard or a successor standard designated by the federal Consumer Product Safety Commission.

[Amended by Stats. 2012, Ch. 679, Sec. 3. (AB 2114) Effective January 1, 2013.]

115929.
  1. The Legislature encourages a private entity, in consultation with the Epidemiology and Prevention for Injury Control Branch of the department, to produce an informative brochure or booklet, for consumer use, explaining the child drowning hazards of, possible safety measures for, and appropriate drowning hazard prevention measures for, home swimming pools and spas, and to donate the document to the department.
  2. The Legislature encourages the private entity to use existing documents from the United States Consumer Product Safety Commission on pool safety.
  3. If a private entity produces the document described in subdivisions (a) and (b) and donates it to the department, the department shall review and approve the brochure or booklet.
  4. Upon approval of the document by the department, the document shall become the property of the state and a part of the public domain. The department shall place the document on its Web site in a format that is readily available for downloading and for publication. The department shall review the document in a timely and prudent fashion and shall complete the review within 18 months of receipt of the document from a private entity.
(Added by Stats. 2003, Ch. 422, Sec. 3. Effective January 1, 2004.)
Automatic vehicular gates shall comply with the requirements of Sections 3110.2 and 3110.3 and other applicable sections of this code.
Vehicular gates intended for automation shall be designed, constructed and installed to comply with the requirements of ASTM F2200.
Vehicular gate openers, where provided, shall be listed in accordance with UL 325.
Solar energy systems shall comply with the requirements of this section.

3111.1.1 Wind Resistance

AMENDMENT
This section has been amended at the state or city level.
Rooftop-mounted photovoltaic panels and modules and solar thermal collectors shall be designed in accordance with Section 1609.

Exception: [DSA-SS, DSA-SS/CC, HCD-1, HCD-2] Rooftop-mounted photovoltaic panels and modules and solar thermal collectors shall be designed in accordance with Section 1510.7 of this code.
Roof structures that provide support for solar energy systems shall be designed in accordance with Section 1607.13.5.

3111.2 Solar Thermal Systems

AMENDMENT
This section has been amended at the state or city level.
Solar thermal systems shall be designed and installed in accordance with Section 2606.12, the California Plumbing Code, the California Mechanical Code and the California Fire Code.
Solar thermal systems and components shall be listed and labeled in accordance with ICC 900/SRCC 300 and ICC 901/SRCC 100.

3111.3 Photovoltaic Solar Energy Systems

AMENDMENT
This section has been amended at the state or city level.
[DSA-SS, DSA-SS/CC, HCD-1, and HCD-2] Photovoltaic solar energy systems shall be designed and installed in accordance with this section, the California Fire Code, California Electrical Code, the manufacturer's installation instructions and Section 1512 of this code.
Photovoltaic panels and modules shall be listed and labeled in accordance with UL 1703. Inverters shall be listed and labeled in accordance with UL 1741. Systems connected to the utility grid shall use inverters listed for utility interaction.
Rooftop-mounted photovoltaic systems shall have a fire classification in accordance with Section 1505.9. Building-integrated photovoltaic systems shall have a fire classification in accordance with Section 1505.8.
Building-integrated photovoltaic systems that serve as roof coverings shall be designed and installed in accordance with Section 1507.18.

3111.3.4 Access and Pathways

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Roof access, pathways and spacing requirements shall be provided in accordance with Section 1204 of the California Fire Code.

3111.3.5 Ground-Mounted Photovoltaic Systems

AMENDMENT
This section has been amended at the state or city level.
Ground-mounted photovoltaic systems shall be designed and installed in accordance with Chapter 16 and the California Fire Code.
Ground-mounted photovoltaic systems shall be subject to the fire separation distance requirements determined by the local jurisdiction.
The provisions of this section shall apply to greenhouses that are designed and used for the cultivation, maintenance, or protection of plants.

3112.2 Accessibility. [HCD 1]

AMENDMENT
This section has been amended at the state or city level.
Greenhouses accessory to covered multifamily dwellings, as defined in Chapter 2, used as a common use facility, shall be on an accessible route in accordance with Chapter 11A.

3112.3 Structural Design

AMENDMENT
This section has been amended at the state or city level.
Greenhouses shall comply with the structural design requirements for greenhouses in Chapter 16.

Exception: [DSA-SS and DSA-SS/CC] Greenhouses considered to be school buildings shall comply with the structural design requirements in Chapter 16A and in accordance with Part 1, California Administrative Code, Title 24, C.C.R.
Glass and glazing used in greenhouses shall comply with Section 2405.
Light-transmitting plastics shall be permitted in lieu of plain glass in greenhouses and shall comply with Section 2606.
Greenhouses that are membrane structures shall comply with Section 3102.
Plastic films used in greenhouses shall comply with Section 3102.3.

3113.1 General

AMENDMENT
This section has been amended at the state or city level.

The provisions of this section shall apply to relocatable buildings. Relocatable buildings manufactured after the effective date of this code shall comply with the applicable provisions of this code [DSA-SS and DSA-SS/CC] as enforced by the enforcement agency.

Exception: This section shall not apply to manufactured housing used as dwellings.



[HCD] The provisions of Section 3113 are not applicable to commercial modulars, manufactured homes, mobilehomes, multi-unit manufactured housing, and special purpose commercial modulars as defined in Health and Safety Code Sections 18001.8, 18007, 18008, 18008.7 and 18012.5, respectively. These structures are subject to installation/reinstallation requirements specified in the Mobilehome Parks Act (Health and Safety Code Section 18200 et seq.) and the California Code of Regulations, Title 25, Division 1, Chapter 2. Manufactured homes must meet unit identification (data plate) and certification label requirements as specified in the Code of Federal Regulations, Title 24, Subtitle B, Chapter XX, Part 3280 and Health and Safety Code Section 18032. Commercial modulars and special purpose commercial modulars must meet identification requirements in the California Code of Regulations, Title 25, Division 1, Chapter 3, Subchapter 2.

3113.1.1 Compliance

AMENDMENT
This section has been amended at the state or city level.
A newly constructed relocatable building shall comply with the requirements of this code for new construction [DSA-SS and DSA-SS/CC] as enforced by the enforcement agency. An existing relocatable building that is undergoing alteration, addition, change of occupancy or relocation shall comply with Chapter 14 of the California Existing Building Code.

Exception: [DSA-SS and DSA-SS/CC] An existing relocatable public school building that is undergoing alteration, addition or change of occupancy shall comply with Chapter 3 of the California Existing Building Code.

3113.2 Supplemental Information

AMENDMENT
This section has been amended at the state or city level.

Supplemental information specific to a relocatable building shall be submitted to the authority having jurisdiction. It shall, as a minimum, include the following in addition to the information required by Section 105:


Exception: [DSA-SS and DSA-SS/CC] Supplemental information specific to a relocatable building shall be submitted to the enforcement agency. It shall, as a minimum, include the following in addition to the information required by Section 1603A:
  1. Manufacturer's name and address.
  2. Date of manufacture.
  3. Serial number of module.
  4. Manufacturer's design drawings.
  5. Type of construction in accordance with Section 602.
  6. Design loads including: roof live load, roof snow load, floor live load, wind load and seismic site class, use group and design category.
  7. Additional building planning and structural design data.
  8. Site-built structure or appurtenance attached to the relocatable building.

3113.3 Manufacturer's Data Plate

AMENDMENT
This section has been amended at the state or city level.

Each relocatable module shall have a data plate that is permanently attached on or adjacent to the electrical panel, and shall include the following information:

  1. Occupancy group.
  2. Manufacturer's name and address.
  3. Date of manufacture.
  4. Serial number of module.
  5. Design roof live load, design floor live load, snow load, wind and seismic design.
  6. Approved quality assurance agency or approved inspection agency.
  7. Codes and standards of construction.
  8. Envelope thermal resistance values.
  9. Electrical service size.
  10. Fuel-burning equipment and size.
  11. Special limitations if any.
Exception: [DSA-SS and DSA-SS/CC] Each relocatable module shall have two metal identification labels permanently attached to the structure as enforced by the enforcement agency.

3113.4 Inspection Agencies

AMENDMENT
This section has been amended at the state or city level.
The building official is authorized to accept reports of inspections conducted by approved inspection agencies during off-site construction of the relocatable building, and to satisfy the applicable requirements of Sections 110.3 through 110.3.11.1.

Exception: [DSA-SS and DSA-SS/CC] Each relocatable module shall be inspected during construction and installation at the project site by project inspectors acceptable to the enforcement agency in accordance with Part 1, California Administrative Code, Title 24, C.C.R.

Section 3114 Woodburning Appliances

AMENDMENT
This section has been amended at the state or city level.

3114.1 Woodburning Appliances

AMENDMENT
This section has been amended at the state or city level.
All woodburning appliances installed in new buildings or woodburning appliances being added, reconstructed or replaced in existing buildings shall comply with this section.

Gas fireplaces shall be exempt from the requirements of this section. However, the conversion of a gas fireplace to burn wood shall constitute the installation of a woodburning appliance and shall be subject to the requirements of this section.

3114.2 Definitions

AMENDMENT
This section has been amended at the state or city level.
The definitions set forth in this section shall govern the application and interpretation of this section.

BAY AREA AIR QUALITY MANAGEMENT DISTRICT means the air quality agency for the San Francisco Bay Area established pursuant to California Health and Safety Code Section 40200.

EPA means the United States Environmental Protection Agency.

EPA CERTIFIED WOOD HEATER means any wood heater that meets the standards in Title 40, Part 60, Subpart AAA, Code of Federal Regulations in effect at the time of installation and is certified and labeled pursuant to those regulations.

FIREPLACE means any permanently installed masonry or factory-built appliance that burns wood, except a pellet-fueled wood heater, designed to be used with an air-to-fuel ratio greater than or equal to 35 to one.

GARBAGE means all solid, semisolid and liquid wastes generated from residential, commercial and industrial sources, including trash, refuse, rubbish, industrial wastes, asphaltic products, manure, vegetable or animal solids and semisolid wastes, and other discarded solid and semisolid wastes.

GAS FIREPLACE means any device designed to burn natural gas in a manner that simulates the appearance of a woodburning fireplace.

PAINTS means all exterior and interior house and trim paints, enamels, varnishes, lacquers, stains, primers, sealers, undercoatings, roof coatings, wood preservatives, shellacs, and other paints or paint-like products.

PAINT SOLVENTS means all original solvents sold or used to thin paints or to clean up painting equipment.

PELLET-FUELED WOOD HEATER means any appliance that burns wood and operates exclusively on wood pellets.

RECONSTRUCTION means the complete rebuilding of the woodburning appliance such that all or a substantial portion of its parts are new. It does not include repairs made to the appliance in order to make it safer or more efficient.

SOLID FUEL means wood or any other nongaseous or nonliquid fuel.

TREATED WOOD means wood of any species that has been chemically impregnated, painted or similarly modified to improve resistance to insects or weathering. It does not include products such as Duraflame or Presto logs that are specifically designed and sold to be burned in a woodburning appliance.

WASTE PETROLEUM PRODUCTS means any petroleum product other than gaseous fuels that has been refined from crude oil and has been used, and as a result of use has been contaminated with physical or chemical impurities.

WOODBURNING APPLIANCE means fireplace, wood heater, or pellet-fueled wood heater or any similar device burning any solid fuel used for aesthetic or space-heating purposes.

WOOD HEATER means a stove that burns wood.

3114.3 Unauthorized Appliances Prohibited

AMENDMENT
This section has been amended at the state or city level.
No person shall install a woodburning appliance that is not one of the following:
  1. A pellet-fueled wood heater;
  2. An EPA-certified wood heater; or
  3. A fireplace certified by the Northern Sonoma Air Pollution Control District.
Exceptions:
  1. Woodburning appliances that are designed primarily for food preparation in new or existing restaurants or bakeries.
  2. Historic woodburning appliances installed in historic structures, as determined by the Building Official of the Department of Building Inspection in consultation with the Director of the Department of Planning.

3114.4 Prohibited Fuels

AMENDMENT
This section has been amended at the state or city level.
The following fuels are prohibited from use in a woodburning appliance:
  1. Garbage;
  2. Treated wood;
  3. Plastic products;
  4. Rubber products;
  5. Waste petroleum products;
  6. Paints or paint solvents;
  7. Coal;
  8. Glossy or colored paper;
  9. Particle board; or
  10. Saltwater driftwood.

3114.5 Certification

AMENDMENT
This section has been amended at the state or city level.
Any person who plans to install a woodburning appliance must submit documentation to the Building Official demonstrating that the appliance is a pellet-fueled wood heater, a certified wood heater, or a fireplace certified by Northern Sonoma Air Pollution Control District.

NOTE: Ordinance 13-02, adopted 1-14-2002, which amended Section 3102.8, contained the following findings:
  1. In 1982, the State Air Resources Board (ARB) adopted a particulate matter (PM10) Ambient Air Quality Standard (AAQS). Levels for the PM10 AAQS were selected pursuant to California Code of Regulations Title 17 Section 70200 to protect the health of people who are sensitive to exposure to fine particles.
  2. Research indicates that wood smoke is a significant contributor to PM10 levels that pose significant health risks.
  3. The City and County of San Francisco desires to lessen the risk to life and property from air pollution from woodburning appliances.
  4. The City and County of San Francisco finds that the proposed regulation will significantly reduce the increases in particulate emissions from future installation and construction activities.
  5. The City and County of San Francisco finds a need exists to adopt regulations which apply to woodburning combustion emissions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING