Heads up: There are no amended sections in this chapter.

CALIFORNIA EXISTING BUILDING CODE — MATRIX ADOPTION TABLE
CHAPTER 4 — REPAIRS

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user.
See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD   BSCC DPH AGR DWR CEC CA SL SLC
1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5
Adopt Entire Chapter                         X                    
Adopt Entire Chapter as amended (amended sections listed below)       X X           X X   X X                
Adopt only those sections that are listed below X   X                                        
Chapter / Section                                              
401.1      X               X X   X X                
401.1.1 X                                            
401.2     X                                        
401.3 X                                            
402     X                                        
402.2       X X                                    
402.3       X X                                    
403     X                                        
404     X                                        
405.2.1405.2.4.1                                              
405.2.3.1      X                                        
405.2.5 X                                            
406                                      
407                                              
407.1       X X                                    
408.1       X X                                    
408.2       X X                                    

The state agency does not adopt sections identified with the following symbol:

The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.



User note:

About this chapter: Chapter 4 provides requirements for repairs of existing buildings. The provisions define conditions under which repairs may be made using materials and methods like those of the original construction or the extent to which repairs must comply with requirements for new buildings.

Repairs shall comply with the requirements of this chapter. Repairs to historic buildings need only comply with Chapter 12. [OSHPD 1R, 2, 4 & 5] Repairs to historic buildings not adopted by OSHPD shall comply with the requirements in the California Building Code, Sections 1224.2, 1225.2, 1226.2, 1227.2 and 1228.2 for functional requirements.

[BSC] For state-owned buildings, including those owned by the University of California and the California State University and the Judicial Council, the requirements of Sections 405.2.1 and 405.2.3 are replaced by the requirements of Sections 317 through 322.

The work shall not make the building less complying than it was before the repair was undertaken.
In flood hazard areas, repairs that constitute substantial improvement shall require that the building comply with Section 1612 of the California Building Code, or Section R322 of the California Residential Code, as applicable.

Replacement glazing in hazardous locations shall comply with the safety glazing requirements of the California Building Code or California Residential Code as applicable.

Exception: Glass block walls, louvered windows and jalousies repaired with like materials.

[HCD] Existing materials shall comply with Section 302.4.
[HCD] New and replacement materials used for repairs shall comply with Section 302.5.
Repairs shall be done in a manner that maintains the level of fire protection provided.
Repairs shall be done in a manner that maintains the level of protection provided for the means of egress.
Structural repairs shall be in compliance with this section and Section 401.2.

[BS] 405.2 Repairs to Damaged Buildings

AMENDMENT
This section has been amended at the state or city level.
Repairs to damaged buildings shall comply with this section. Unless otherwise approved by the Building Official, all structural damage shall be repaired. Repairs to buildings or structures which have sustained substantial structural damage to lateral force resisting elements shall comply with the minimum lateral force design requirements of Section 303.4 or with the code under which the building or structure was designed, whichever is more restrictive.

     Damage may be caused by events or a combination of events, including, but not limited to, fire, explosion, structural pest or wood-destroying organism attack, earthquake, wind storm, vehicular impact, ground subsidence or failure, or the collapse or dislodgement of any portion of any adjacent building or structure. The removal or alteration of structural elements as part of the work described in an approved building permit application shall not be considered to be "damage."
Unless otherwise required by this section, for damage less than substantial structural damage, the damaged elements shall be permitted to be restored to their predamage condition.
Structural components whose damage was caused by or related to snow load effects shall be repaired, replaced or altered to satisfy the requirements of Section 1608 of the California Building Code.

405.2.1.2 Other Damage

AMENDMENT
This section has been amended at the state or city level.
For damage less than substantial structural damage that is not Disproportionate Earthquake Damage, repairs shall be allowed that restore the building to its predamage state, based on material properties and design strengths applicable at the time of original construction. New structural members and connections used for this repair shall comply with the detailing provisions of this code for new buildings of similar structure, purpose and location.

[BS] 405.2.2 Disproportionate Earthquake Damage

AMENDMENT
This section has been amended at the state or city level.
A building assigned to Seismic Design Category D, E or F that has sustained disproportionate earthquake damage shall be subject to the requirements for buildings with substantial structural damage to vertical elements of the lateral force-resisting system.

     Permit applications for required rehabilitation work shall be submitted to the Department within one year after the earthquake, and the work shall be completed as specified in Table B of San Francisco Building Code Section 106A.4.4.

A building that has sustained substantial structural damage to the vertical elements of its lateral force-resisting system shall be evaluated in accordance with Section 405.2.3.1, and either repaired in accordance with Section 405.2.3.2 or repaired and retrofitted in accordance with Section 405.2.3.3, depending on the results of the evaluation.

Exceptions:

  1. Buildings assigned to Seismic Design Category A, B or C whose substantial structural damage was not caused by earthquake need not be evaluated or retrofitted for load combinations that include earthquake effects.
  2. One- and two-family dwellings need not be evaluated or retrofitted for load combinations that include earthquake effects.

[BS] 405.2.3.1 Evaluation

AMENDMENT
This section has been amended at the state or city level.
The building shall be evaluated by a registered design professional, and the evaluation findings shall be submitted to the code official within 60 days of completion of the evaluation. The evaluation shall establish whether the damaged building, if repaired to its predamage state, would comply with the provisions of this code for wind and earthquake loads. Evaluation for earthquake loads shall be required if the substantial structural damage was caused by or related to earthquake effects or if the building is in Seismic Design Category C, D, E or F.

     Wind loads for this evaluation shall be those prescribed in San Francisco Building Code Section 1609. Earthquake loads for this evaluation, if required, shall be according to section 303.4
.
If the evaluation establishes that the building in its predamage condition complies with the provisions of Section 405.2.3.1, then the damaged elements shall be permitted to be restored to their predamage condition.
If the evaluation does not establish that the building in its predamage condition complies with the provisions of Section 405.2.3.1, then the building shall be retrofitted to comply with the provisions of this section. The wind loads for the repair and retrofit shall be those required by the building code in effect at the time of original construction, unless the damage was caused by wind, in which case the wind loads shall be in accordance with the California Building Code. The seismic loads for this retrofit design shall be those required by the building code in effect at the time of original construction, but not less than the reduced seismic forces.
Gravity load-carrying components that have sustained substantial structural damage shall be rehabilitated to comply with the applicable provisions for dead and live loads in the California Building Code. Snow loads shall be considered if the substantial structural damage was caused by or related to snow load effects. Undamaged gravity load-carrying components that receive dead, live or snow loads from rehabilitated components shall also be rehabilitated if required to comply with the design loads of the rehabilitation design.

Regardless of the level of damage to vertical elements of the lateral force-resisting system, if substantial structural damage to gravity load-carrying components was caused primarily by wind or seismic effects, then the building shall be evaluated in accordance with Section 405.2.3.1 and, if noncompliant, retrofitted in accordance with Section 405.2.3.3.

Exceptions:

  1. Buildings assigned to Seismic Design Category A, B, or C whose substantial structural damage was not caused by earthquake need not be evaluated or retrofitted for load combinations that include earthquake effects.
  2. One- and two-family dwellings need not be evaluated or retrofitted for load combinations that include earthquake effects.
In flood hazard areas, buildings that have sustained substantial damage shall be brought into compliance with Section 1612 of the California Building Code, or Section R322 of the California Residential Code, as applicable.

[OSHPD 1R, 2, 4 & 5] Not adopted by OSHPD. Existing electrical wiring and equipment undergoing repair shall be in accordance with Title 24 Part 3 California Electrical Code (CEC).

Existing electrical wiring and equipment undergoing repair shall be allowed to be repaired or replaced with like material.
Replacement of electrical receptacles shall comply with the applicable requirements of Section 406.4(D) of NFPA 70.
Plug fuses of the Edison-base type shall be used for replacements only where there is no evidence of over fusing or tampering per applicable requirements of Section 240.51(B) of NFPA 70.
For replacement of nongrounding-type receptacles with groundingtype receptacles and for branch circuits that do not have an equipment grounding conductor in the branch circuitry, the grounding conductor of a grounding-type receptacle outlet shall be permitted to be grounded to any accessible point on the grounding electrode system or to any accessible point on the grounding electrode conductor in accordance with Section 250.130(C) of NFPA 70.
Receptacles in patient bed locations of Group I-2 that are not "hospital grade" shall be replaced with "hospital grade" receptacles, as required by NFPA 99 and Article 517 of NFPA 70.
Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers and outlet or junction boxes that are part of the existing branch circuit for these appliances shall be permitted to be grounded to the grounded circuit conductor in accordance with Section 250.140 of NFPA 70.
Existing mechanical systems undergoing repair shall not make the building less complying than it was before the damaged occurred. [HCD 1 & HCD 2] Existing mechanical systems undergoing repair shall comply with the California Mechanical Code.
Plumbing materials and supplies shall not be used for repairs that are prohibited in the California Plumbing Code. [HCD 1 & HCD 2] Existing plumbing systems undergoing repair shall comply with the California Plumbing Code and Division 4.3 of the CALGreen Code, as applicable.
The maximum water consumption flow rates and quantities for all replaced water closets shall be 1.28 gallons (4.8 L) per flushing cycle.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING