Heads up: There are no amended sections in this chapter.

CALIFORNIA EXISTING BUILDING CODE — MATRIX ADOPTION TABLE
CHAPTER 3A — PROVISIONS FOR ALL COMPLIANCE METHODS

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user.
See Chapter 1 for state agency authority and building applications.)

Adopting AgencyBSCBSC-
CG
SFMHCDDSAOSHPDBSCCDPHAGRDWRCECCASLSLC
121/ACACSSSS/CC11R2345
Adopt Entire ChapterX
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter / Section

The state agency does not adopt sections identified with the following symbol:

The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

The provisions of this chapter shall control the alteration, repair, addition, and change of occupancy of existing structures for applications listed in Sections 1.10.1 [OSHPD 1] regulated by the Office of Statewide Health Planning and Development (OSHPD).

California Energy Commission, State Fire Marshal and DSA-AC requirements for existing structures shall be enforced by the Office of Statewide Health Planning and Development (OSHPD).

Repairs shall comply with the requirements of Chapter 4A.

The alteration, addition or change of occupancy of all existing buildings or structures shall comply with one of the methods or categories listed in Section 301A.3.1, 301A.3.2 or 301A.3.3 Section 303A.3.2 applies to all methods or categories. Sections 301A.3.1 through 301A.3.3 shall not be applied in combination with each other, except when permitted by the enforcement agency.

Exception: Subject to the approval of the enforcement agency, alterations complying with the laws in existence at the time the building or the affected portion of the building was built shall be considered in compliance with the provisions of this code. New structural members added as part of the alteration shall comply with the California Building Code.

Alterations, additions and changes of occupancy complying with Chapter 5A of this code for existing buildings or structures shall be considered in compliance with the provisions of this code.
Alterations, additions and changes of occupancy to existing buildings or structures designed in accordance with the Pre-1973 building code complying with Section 303A.3.1 and the applicable requirements herein shall be considered in compliance with the provisions of this code.
Alterations, additions and changes of occupancy to existing buildings or structures complying with Sections 303A.3.4 and 303A.3.5 of this code shall be considered in compliance with the provisions of this code.

Structures moved into or within the jurisdiction shall comply with the provisions of the California Building Code for new structures.

Accessibility requirements for existing buildings shall comply with the California Building Code, Part 2 Volume 1 Chapter 11B, Section 201 "Existing Buildings and Facilities."
Peer review requirements shall comply with California Building Code Section 1617A.1.41.
Earthquake monitoring instrumentation of existing buildings shall comply with Section 306A.
Compliance alternatives for services/systems and utilities shall comply with Section 307A.
The provisions of Section 302A apply to all alterations, repairs, additions, relocations of structures and changes of occupancy regardless of compliance method.
The code official shall have the authority to require the elimination of conditions deemed dangerous.

Alterations, repairs, additions and changes of occupancy to, or relocation of, existing buildings and structures shall comply with the provisions for alterations, repairs, additions and changes of occupancy or relocation, respectively, in the California Fire Code, California Mechanical Code, California Plumbing Code, and California Electrical Code. Where provisions of the other codes conflict with provisions of this chapter, the provisions of this chapter shall take precedence.

Materials and equipment already in use in a building in compliance with requirements or approvals in effect at the time of their erection or installation shall be permitted to remain in use unless determined by the building official to be unsafe in accordance with California Building Code Section 116.

Where the existing seismic force-resisting system is a type that can be designated ordinary or is a welded steel moment frame constructed under a permit issued prior to October 25, 1994, values of R, Ω0, and Cd for the existing seismic force-resisting system shall be those specified by this code for an ordinary system unless it is demonstrated that the existing system will provide performance equivalent to that of a detailed, intermediate or special system.

Except as otherwise required or permitted by this code, materials and equipment permitted by the applicable code for new construction shall be used. Like materials shall be permitted for repairs and alterations, provided no hazard to life, health or property is created. Hazardous materials shall not be used where the code for new construction would not permit their use in building of similar occupancy, purpose, and location.

New structural members and connections shall comply with the detailing provisions of the California Building Code for new buildings of similar structure, purpose and location.

Exception: Where alternative design criteria are specifically permitted.

Where determining the appropriate application of the referenced sections of this code, the occupancy and use of a building shall be determined in accordance with Chapter 3 of the California Building Code.
Buildings and structures, and parts thereof, shall be maintained in a safe and sanitary condition. Devices or safeguards which are required by this code shall be maintained in conformance with the code edition under which they were installed. The owner or the owner's designated agent shall be responsible for the maintenance of buildings and structures. To determine compliance with this subsection, the building official shall have the authority to require a building or structure to be re-inspected. The requirements of this chapter shall not provide the basis for removal or abrogation of fire protection and safety systems and devices in existing structures.
The design loads and other information pertinent to the structural design required by California Building Code Section 1603A shall be included in the drawings. In addition to the information required by California Building Code Section 1603A.1.5, the drawings shall show the ground motion hazard used for the retrofit or rehabilitation as either a percentage of the California Building Code prescribed ground motion for new hospital buildings, or ASCE 41 seismic hazard designation, or a probability of exceedance in a specified time period, or a return period for exceedance of the specified ground motion.
Where an addition or alteration does not result in increased design live load, existing gravity loadcarrying structural elements shall be permitted to be evaluated and designed for live loads approved prior to the addition or alteration. If the approved live load is less than that required by Section 1607A of the California Building Code, the area designated for the nonconforming live load shall be posted with placards of approved design indicating the approved live load. Where the addition or alteration results in increased design live load, the live load required by Section 1607A of the California Building Code shall be used.
Where an alteration or addition changes the potential snow drift effects on an adjacent building, the code official is authorized to enforce Section 7.12 of ASCE 7.

Provisions of this section shall apply to hospital buildings which were originally designed to pre-1973 building codes and not designated as SPC 3 or higher in accordance with Chapter 6 of the California Administrative Code.

Incidental and minor structural additions shall be permitted, provided the additions meet the California Building Code for new construction using importance factor, Ie, equal to or greater than 1.0. Alterations, or repair to existing gravity and lateral force-resisting systems shall be made to conform to the requirements of Section 503A or Chapter 4A respectively using importance factor, Ie, equal to or greater than 1.0.

  1. Nonstructural components. Component importance factor, Ip, shall be permitted to be 1.0.

    Exception: Components required for lifesafety purposes after an earthquake, including emergency and standby power systems, mechanical smoke removal systems, fire protection sprinkler systems, fire alarm control panels, and egress stairways shall have a component importance factor (Ip) of 1.5.

Notwithstanding any other requirements of this code, existing general acute care hospitals shall comply with the seismic evaluation requirements specified in Chapter 6, of the California Administrative Code, when applicable. Seismic retrofit to comply with requirements specified in Chapter 6 of the California Administrative Code shall be permitted to be in accordance with these provisions. When load combinations which do not include seismic forces are required, the new building provisions of this code shall be applicable.

Nonconforming hospital buildings satisfying the following requirements and one of Sections 501A.3.1, 501A.3.2 or 303A.3.4.5, but not a combination thereof, shall be considered to satisfy the requirements of SPC-4D.

  1. Approval of construction documents based on building characterization in accordance with the California Administrative Code (CAC) Chapter 6 Section 2.1.2.1, material properties in accordance with the CAC Chapter 6 Section 2.1.2.2 and Section 303A.5.3 of this code, and a complete rational structural analysis shall be required.
  2. Where the SPC-4D upgrade involves construction, a building permit prior to construction shall be required.
  3. Where multiple building permits are used to upgrade a building to SPC-4D, a complete rational structural analysis to justify compliance with SPC-4D, for the building in its final configuration, shall be submitted as part of the construction documents submittal to the Office for the last project.
  4. Where the SPC-4D upgrade involves construction, buildings shall be assigned to SPC-4D after all projects required for SPC-4D are closed in compliance.
Except for the modifications as set forth in Sections 303A.3.4 and 303A.3.5, all additions, alterations, repairs and seismic retrofit to existing structures or portions thereof shall be permitted to be designed in accordance with the provisions of ASCE 41. When load combinations which do not include seismic forces are required, the new building code provisions of this code shall be applicable. Required building performance objectives under ASCE 41 shall be as follows:
  1. Immediate Occupancy (IO) Structural Performance Level (S-1) as defined in Section 2.3.1.1 at Basic Safety Earthquake 1N (BSE-1N) Seismic Hazard Level; and
  2. Life Safety (LS) Structural Performance Level (S-3) as defined in Section 2.3.1.3 at Basic Safety Earthquake 2N (BSE-2N) Seismic Hazard Level; and
  3. The nonstructural components shall satisfy the requirements of this code for new construction.

    Exception: Performance objectives for upgrading nonconforming hospital buildings to SPC-4D and for incidental or minor alterations or repairs of SPC-4D buildings shall be in accordance with Section 303A.3.4.5 of this code.

  1. Life Safety Structural Performance (S-3) Level as defined in ASCE 41 Section 2.3.1.3 at the Basic Safety Earthquake 1E (BSE-1E) Seismic Hazard Level; and
  2. Collapse Prevention (CP) Building Performance Level (5-D) in accordance with Section 2.3.3.4 at the Basic Safety Earthquake 2E (BSE-2E) Seismic Hazard Level; and
  3. The nonstructural components shall satisfy the requirements of Position Retention Nonstructural Performance Level (N-B) in accordance with ASCE 41 Section 2.3.2.2 at BSE-1E Seismic Hazard Level.
  1. Operational Building Performance Level of (1-A) as defined in Section 2.3.3.1 at Basic Safety Earthquake 1N (BSE-1N) Seismic Hazard Level; and
  2. Life Safety (LS) Building Performance Level (S-3) as defined in Section 2.3.1.3 at Basic Safety Earthquake 2N (BSE-2N) Seismic Hazard Level.

Structures shall be considered to comply with SPC 2 requirements of Table 2.5.3, Chapter 6 of the California Administrative Code, when all of the following are satisfied:

  1. Life Safety Structural Performance Level (S-3) in accordance with Section 2.3.1.3 of ASCE 41 at BSE-1E; and
  2. Items identified in Chapter 6, Article 10 of the California Administrative Code satisfying the requirements of Position Retention nonstructural Performance Level (N-B) in accordance with Section 2.3.2.2 at BSE-1E.

Structures shall be deemed to comply with the SPC-4D requirements of Table 2.5.3, Chapter 6 of the California Administrative Code, when all of the following are satisfied:

  1. Damage control Structural Performance Level (S-2) in accordance with Section 2.3.1.2.1 of ASCE 41 at BSE-1E; and
  2. Collapse Prevention Structural Performance Level (S-5) in accordance with Section 2.3.1.5 of ASCE 41 at BSE-2E; and
  3. Items identified in Chapter 6, Article 10 of the California Administrative Code satisfy the requirements of Position Retention Nonstructural Performance Level (N-B) in accordance with Section 2.3.2.2 at BSE-1E.
Exception: ASCE 41-13 § 7.2.13.2 Separation
Exemptions: Add the following exemption:
  1. Seismic separation is deemed to comply with SPC-4D requirements and a pounding analysis is not required where either A) or B) apply:
    1. The adjacent building was constructed using the 1989 or later edition of the California Building Code.
    2. The adjacent building meets the SPC building separation requirements in accordance with the California Administrative Code (CAC), Chapter 6, Section 3.4 and all the following are met:
      1. Where the structural resisting system of the adjacent building is different, the mass of the more flexible building is no greater than 50 percent of the mass of the stiffer building.
      2. The adjacent building does not have any of the following structural deficiencies as defined in CAC, Chapter 6, Article 3:
        1. Load path (3.1)
        2. Weak story (3.3.1)
        3. Soft story (3.3.2)
        4. Vertical discontinuity (3.3.5) or
        5. Torsion (3.3.6)

Structures shall be considered to comply with SPC 5 requirements of Table 2.5.3, Chapter 6 of the California Administrative Code where all of the following are satisfied:

  1. Immediate Occupancy structural Performance Level (S-1) in accordance with Section 2.3.1.1 of ASCE 41 at BSE-1N;
  2. Life Safety Performance Level S-3 in accordance with Section 2.3.1.3 of ASCE 41 at BSE-2N; and
  3. Items identified in Chapter 6, Article 10 of the California Administrative Code, satisfying the requirements of Operational Nonstructural Performance Level (N-A) in accordance with Section 2.3.2.1 of ASCE 41 at BSE-1N.

Operational Nonstructural Performance Level (N-A) and Position Retention Nonstructural Performance Level (N-B) of ASCE 41 at BSE-1N shall be considered equivalent to NPC 3/NPC 2 requirements respectively of Table 11.1, Chapter 6 of the California Administrative Code. For NPC 3/NPC 2, only components listed in Table 11.1, Chapter 6 of the California Administrative Code for NPC 3/NPC 2 need to satisfy the requirements specified above.

Exception: Evaluation procedure of Article 11, Chapter 6 of the California Administrative Code shall be used for seismic evaluation of NPC 2, NPC 3, NPC 4 or NPC 4D and NPC 5, where specific procedure is not outlined in ASCE 41. Administrative and permitting provisions outlined in Article 11, Chapter 6 of the California Administrative Code shall apply.

Nonstructural components for Operational Nonstructural Performance Level (N-A) in Section 2.3.2.1 or NPC-4/NPC 4D shall satisfy the requirements of the California Building Code for new construction. Nonstructural components for NPC-5 shall satisfy Operational Performance Level N-A/NPC-4/NPC 4D and California Building Code Section 1617A.1.40 Items 1 & 2.
The text of ASCE 41 shall be modified as indicated in Sections 303A.5.1 through 303A.5.14.

Modify ASCE 41 Section 1.1 with the following:

Seismic evaluations shall be performed for performance objective specified in Section 303A.3.4 of this code (CEBC) using procedure of this standard (ASCE 41) as follows:

  1. Structural components shall be evaluated in accordance with Tier 3 systematic evaluations procedure in Chapter 6.
  2. Nonstructural components shall be evaluated in accordance with Chapter 13.

Exception: For general acute care hospitals, seismic evaluation shall be permitted to be in accordance with Chapter 6 of the California Administrative Code (CAC) when required by provisions of that chapter.

Modify ASCE 41 Section 6.2 with the following:

Data Collection Requirements. The extent of data collection shall be at Comprehensive level for all structures, including structures upgraded to SPC-4D. A testing program for materials properties shall be approved by the enforcement agent prior to commencement of material testing work. Previously approved material test results shall be permitted to be used to satisfy part of the comprehensive data collection requirements.

Exception: Data collection at Usual level shall be permitted for structures with SPC-2 or lower target performance objective.

Tension testing of reinforcing bars shall be in accordance with ASTM A615. All test specimens shall be the full section of the bar as rolled (8-in. gage length) and shall not be reduced.

At test sample locations, structural members, slabs and walls shall be repaired to a state that is equivalent to their original condition.

For buildings built under an OSHPD permit based on the 1976 or later edition of the CBC, where materials properties are shown on design drawings and original materials test data are available, no materials testing shall be required when approved by the enforcement agent.

Modify ASCE 41 Section 7.3.2.1 with the following:

Nonlinear Static Procedure. If higher mode effects are significant and building is taller than 75 feet above the base, the Nonlinear Dynamic Procedure shall be used.

Modify ASCE 41 Section 7.5.1 with the following:

Acceptance Criteria — Drift Limitations. The interstory drift ratio shall not exceed the drift limits for Risk Category IV buildings in ASCE 7 Table 12.12-1 due to forces corresponding to BSE-1E or BSE-1N, as applicable.

Exception: Larger interstory drift ratios shall be permitted where justified by rational analysis that both structural and nonstructural elements can tolerate such drift and approved by the enforcement agent.

Modify ASCE 41 Section 7.5.1.4 by the following:

Material Properties. Expected material properties are not permitted to be determined by multiplying lower bound values by the assumed factors specified in Chapters 8 through 12 and shall be based exclusively on materials tests.

Modify ASCE 41 Section 8.4 with the following:

Foundation Strength and Stiffness. Foundation and soil strength shall be used to evaluate potential overturning, uplift and sliding for fixed base assumptions, and stiffness for flexible base assumptions, including deformations associated with those actions.

Replace ASCE 41 Section 8.4.1.1 as follows:

Prescriptive Expected Capacities. Not permitted by OSHPD.

Modify ASCE 41 Section 8.5.1 with the following:

The product of RRSbsa x RRSe, shall not be less than 0.7.

The combined effect of kinematic interaction and foundation damping shall meet the following:

  1. The site specific response spectrum modified for soil-structure interaction effects shall not be taken as less than 80 percent of the spectral acceleration as determined from a site-specific response spectrum in accordance with ASCE 7 Section 21.3, or
  2. The site specific response spectrum modified for soil-structure interaction effects shall not be taken as less than 70 percent of the spectral acceleration as determined from the design response spectrum and MCER response spectrum in accordance with ASCE 7 Sections 11.4.5 and 11.4.6 respectively.

    Exception: For the seismic retrofit of existing nonconforming buildings, design ground motion shall be consistent with performance objectives in Section 303A.3.4.

Modify ASCE 41 Section 8.6 with the following:

Seismic Earth Pressure. Where the grade difference from one side of the building to another exceeds one-half story height, the seismic increment of earth pressure shall be added to the gravity lateral earth pressure to evaluate the building overturning and sliding stability and the lateral force-resisting system below grade in combination with the building seismic forces.

Modify ASCE 41 Section 10.7.1.1 with the following:

Monolithic Reinforced Concrete Shear Walls and Wall Segments. For nonlinear procedures, shear walls or wall segments with axial loads greater than 0.35 Po shall be included in the model as primary elements with appropriate strength and stiffness degrading properties assigned to those components subject to the approval of the enforcement agent. For linear procedures, the effects of deformation compatibility shall be investigated using momentcurvature section analyses and cyclic testing results of similar components to determine whether strengthening is necessary to maintain the gravity load-carrying capacity of that component.

Horizontal wall segments or spandrels reinforced similar to vertical wall segments or piers shall be classified as wall segments, not shear wall coupling beams, in Tables 10-19 through 10-22.

Modify ASCE 41 Section 11.1 by the following:

Scope: Unreinforced masonry walls (including unreinforced infill walls) and partitions are not permitted for General Acute Care (GAC) hospital buildings.

Modify ASCE 41 Section 14.1 by the following:

Scope: For buildings located in Seismic Design Category F, verification of the interstory lateral displacements, the strength adequacy of the seismic force-resisting system and anchorage to the foundation shall be accomplished using the Nonlinear Dynamic Procedure.

Not permitted by OSHPD.
Where used, in-situ load tests shall be conducted in accordance with Section 1708A of the California Building Code.

Accessibility requirements for existing buildings shall comply with the California Building Code, Part 2 Volume 1 Chapter 11B.

A facility that is constructed or altered to be accessible shall be maintained accessible during occupancy.
An alteration of an existing facility shall not impose a requirement for greater accessibility than that which would be required for new construction. Alterations shall not reduce or have the effect of reducing accessibility of a facility or portion of a facility.

Existing buildings that undergo a change of group or occupancy shall comply with this section.

Exception: Type B dwelling or sleeping units required by Section 1107A of the California Building Code are not required to be provided in existing buildings and facilities undergoing a change of occupancy in conjunction with alterations where the work area is 50 percent or less of the aggregate area of the building.

Where a portion of the building is changed to a new occupancy classification, any alterations shall comply with Sections 305A.6, 305A.7 and 305A.8.

Where an entire building undergoes a change of occupancy, it shall comply with Section 305A.4.1 and shall have all of the following accessible features:

  1. Not fewer than one accessible building entrance.
  2. Not fewer than one accessible route from an accessible building entrance to primary function areas.
  3. Signage complying with Section 1111A of the California Building Code.
  4. Accessible parking, where parking is being provided.
  5. Not fewer than one accessible passenger loading zone, where loading zones are provided.
  6. Not fewer than one accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance.

Where it is technically infeasible to comply with the new construction standards for any of these requirements for a change of group or occupancy, Items 1 through 6 shall conform to the requirements to the maximum extent technically feasible.

Exception: The accessible features listed in Items 1 through 6 are not required for an accessible route to Type B units.

Provisions for new construction shall apply to additions. An addition that affects the accessibility to, or contains an area of, a primary function shall comply with the requirements in Section 305A.7.

A facility that is altered shall comply with the applicable provisions in Chapter 11 of the California Building Code, unless technically infeasible. Where compliance with this section is technically infeasible, the alteration shall provide access to the maximum extent technically feasible.

Exceptions:

  1. The altered element or space is not required to be on an accessible route, unless required by Section 305A.7.
  2. Accessible means of egress required by Chapter 10 of the California Building Code are not required to be provided in existing facilities.
  3. The alteration to Type A individually owned dwelling units within a Group R-2 occupancy shall be permitted to meet the provision for a Type B dwelling unit.
  4. Type B dwelling or sleeping units required by Section 1107A of the California Building Code are not required to be provided in existing buildings and facilities undergoing alterations where the work area is 50 percent or less of the aggregate area of the building.

Where an alteration affects the accessibility to, or contains an area of primary function, the route to the primary function area shall be accessible. The accessible route to the primary function area shall include toilet facilities and drinking fountains serving the area of primary function.

Exceptions:

  1. The costs of providing the accessible route are not required to exceed 20 percent of the costs of the alterations affecting the area of primary function.
  2. This provision does not apply to alterations limited solely to windows, hardware, operating controls, electrical outlets and signs.
  3. This provision does not apply to alterations limited solely to mechanical systems, electrical systems, installation or alteration of fire protection systems and abatement of hazardous materials.
  4. This provision does not apply to alterations undertaken for the primary purpose of increasing the accessibility of a facility.
  5. This provision does not apply to altered areas limited to Type B dwelling and sleeping units.
The provisions of Sections 305A.8.1 through 305A.8.15 shall apply to alterations to existing buildings and facilities.
Where an alteration includes alterations to an entrance that is not accessible, and the facility has an accessible entrance, the altered entrance is not required to be accessible unless required by Section 305A.7. Signs complying with Section 1111A of the California Building Code shall be provided.
Altered elements of existing elevators shall comply with ASME A17.1 and ICC A117.1. Such elements shall also be altered in elevators programmed to respond to the same hall call control as the altered elevator.
Platform (wheelchair) lifts complying with ICC A117.1 and installed in accordance with ASME A18.1 shall be permitted as a component of an accessible route.
Where an escalator or stairway is added where none existed previously and major structural modifications are necessary for installation, an accessible route shall be provided between the levels served by the escalator or stairways in accordance with Section 1104A.4 of the California Building Code.
Where slopes steeper than allowed by Section 1012.2 of the California Building Code are necessitated by space limitations, the slope of ramps in or providing access to existing facilities shall comply with Table 305A.8.5.

TABLE 305A.8.5
RAMPS
SLOPE MAXIMUM RISE
Steeper than 1:10 but not steeper than 1:8 3 inches
Steeper than 1:12 but not steeper than 1:10 6 inches
For SI: 1 inch = 25.4 mm.
Where Group I-1, I-2, I-3, R-1, R-2 or R-4 dwelling or sleeping units are being altered or added, the requirements of Section 1107A of the California Building Code for Accessible units apply only to the quantity of spaces being altered or added.
Where more than 20 Group R-2 dwelling or sleeping units are being altered or added, the requirements of Section 1107A of the California Building Code for Type A units apply only to the quantity of the spaces being altered or added.
Where four or more Group I-1, I-2, R-1, R-2, R-3 or R-4 dwelling or sleeping units are being added, the requirements of Section 1107A of the California Building Code for Type B units apply only to the quantity of the spaces being added. Where Group I-1, I-2, R-1, R-2, R-3 or R-4 dwelling or sleeping units are being altered and where the work area is greater than 50 percent of the aggregate area of the building, the requirements of Section 1107A of the California Building Code for Type B units apply only to the quantity of the spaces being altered.
In alterations, accessible wheelchair spaces are not required to be located within the defined area of raised jury boxes or witness stands and shall be permitted to be located outside these spaces where the ramp or lift access restricts or projects into the required means of egress.
Where it is technically infeasible to alter existing toilet and bathing rooms to be accessible, an accessible family or assisted-use toilet or bathing room constructed in accordance with Section 1109A.2.1 of the California Building Code is permitted. The family or assisted-use toilet or bathing room shall be located on the same floor and in the same area as the existing toilet or bathing rooms. At the inaccessible toilet and bathing rooms, directional signs indicating the location of the nearest family or assisted-use toilet room or bathing room shall be provided. These directional signs shall include the California Symbol of Accessibility and sign characters shall meet the visual character requirements in accordance with ICC A117.1.
In assembly and mercantile occupancies, where additional toilet fixtures are added, not fewer than one accessible family or assisted-use toilet room shall be provided where required by Section 1109A.2.1 of the California Building Code. In recreational facilities, where additional bathing rooms are being added, not fewer than one family or assisted-use bathing room shall be provided where required by Section 1109A.2.1 of the California Building Code.
Where it is technically infeasible to provide accessible dressing, fitting or locker rooms at the same location as similar types of rooms, one accessible room on the same level shall be provided. Where separate-sex facilities are provided, accessible rooms for each sex shall be provided. Separate-sex facilities are not required where only unisex rooms are provided.
Operable parts of replacement fuel dispensers shall be permitted to be 54 inches (1370 mm) maximum, measuring from the surface of the vehicular way where fuel dispensers are installed on existing curbs.
The maximum height of thresholds at doorways shall be 3/4 inch (19.1 mm). Such thresholds shall have beveled edges on each side.
Where the structural or operational characteristics of an amusement ride are altered to the extent that the amusement ride's performance differs from that specified by the manufacturer or the original design, the amusement ride shall comply with requirements for new construction in Section 1110A.4.8 of the California Building Code.

These provisions shall apply to facilities designated as historic structures that undergo alterations or a change of occupancy, unless technically infeasible. Where compliance with the requirements for accessible routes, entrances or toilet rooms would threaten or destroy the historic significance of the facility, as determined by the authority having jurisdiction, the alternative requirements of Sections 305A.9.1 through 305A.9.4 for that element shall be permitted.

Exception: Type B dwelling or sleeping units required by Section 1107A of the California Building Code are not required to be provided in historic buildings.

Not fewer than one accessible route from a site arrival point to an accessible entrance shall be provided.
An accessible route from an accessible entrance to public spaces on the level of the accessible entrance shall be provided.

Not fewer than one main entrance shall be accessible.

Exception: If a public entrance cannot be made accessible, an accessible entrance that is unlocked while the building is occupied shall be provided; or, a locked accessible entrance with a notification system or remote monitoring shall be provided.

Signs complying with Section 1111A of the California Building Code shall be provided at the public entrance and the accessible entrance.

Where toilet rooms are provided, not fewer than one accessible family or assisted-use toilet room complying with Section 1109A.2.1 of the California Building Code shall be provided.
All owners of existing structures, selected by the enforcement agency for the installation of earthquakerecording instruments, shall provide space for the installation and access to such instruments. Location of said instruments shall be determined by the enforcement agency. The enforcement agency shall make arrangements to provide, maintain, and service the instruments. Data shall be the property of the enforcement agency, but copies of individual records shall be made available to the public on request and the payment of an appropriate fee.

The provisions of this section are intended to maintain or increase the current degree of public safety, health and general welfare in existing buildings while permitting repair, alteration, addition and change of occupancy without requiring full compliance with California Building Code Chapters 2 through 33, or Sections 302A.3, and 502A through 506A, except where compliance with other provisions of this code is specifically required in this section.

Services/systems and utilities that originate in and pass through or under buildings and are necessary to the operation of the hospital buildings shall meet the structural requirements of this section. Examples of services/systems and utilities include but are not limited to normal power; emergency power; nurse call; fire alarm; communication and data systems; space-heating systems; process load systems; cooling systems; domestic hot and cold water systems; means of egress systems; fire-suppression systems; building drain and sewer systems; and medical gas systems that support basic and supplemental services.

After January 1, 2030, services/systems and utilities for acute care hospital buildings shall not originate in or pass through or under a nonhospital or hospital building unless it has approved performance categories of SPC-3 or higher and NPC-5.

Services/systems and utilities that are necessary to the operation of the hospital buildings shall meet the structural requirements of this section, based upon the approved Structural Performance Category (SPC) of the building receiving the services/systems and utilities.

Services from a conforming building shall be permitted to serve a nonconforming building with prior approval of the Office. The services/systems and utilities in the nonconforming building shall be equipped with fail safe valves, switches, or other equivalent devices that allow the nonconforming building to be isolated from the conforming building.

Exception: Remodel projects that use available existing services/systems and utilities are exempted from the requirements of this section. The enforcing agency shall be permitted to exempt minor addition, minor alteration, and minor remodel projects and projects to upgrade existing services/systems and utilities from the requirements of this section.

Services/systems and utilities for new hospital buildings and additions, alterations or remodels to existing conforming buildings shall originate in hospital buildings that are conforming or have approved performance categories of SPC-3 or higher, and NPC-4/NPC-4D or higher. The services/systems and utilities shall not pass through or under buildings that do not have approved performance categories of SPC-2 or higher and NPC-4/NPC-4D or higher.

Exceptions:

Services/systems and utilities shall be permitted to pass through or under buildings that have approved nonstructural performance categories of NPC-3 or higher or NPC-2, provided that the building has an approved extension to the NPC-3 deadline. The services/systems and utilities feeding the new building addition, alteration, or remodel shall conform to the new building provisions of this code and shall be deemed by OSHPD to be free of adverse seismic interactions that could be caused by potential failure of overhead or adjacent components.

Services/systems and utilities for additions, alterations, or remodels of SPC-2 hospital buildings shall be permitted to originate in and pass through or under SPC-2 or higher buildings that have an approved nonstructural performance category of NPC-3 or higher.

Exception: Services/systems and utilities shall be permitted to pass through or under buildings that have approved nonstructural performance categories of NPC-2, provided that the building has an approved extension to the NPC-3 deadline. Services/systems and utilities feeding the addition, alteration or remodel shall conform to the nonstructural bracing requirements for new buildings.

Services/systems and utilities for alterations or remodels of SPC-1 hospital buildings shall be permitted to originate in and pass through or under SPC-1 or higher buildings that have an approved nonstructural performance category of NPC-2 or higher.
When services/systems and utilities for new buildings, additions, alterations, or remodels pass through or under hospital buildings which would not otherwise require evaluation for an SPC rating, such buildings shall be evaluated in accordance with the requirements of Section 1.3, Chapter 6, of the California Administrative Code, to determine the appropriate ratings, or shall be shown to meet the structural requirements of these regulations for new hospital buildings. The services/systems and utilities feeding the new building addition, alteration, or remodel shall conform with new building provisions of this code and shall be deemed by OSHPD to be free of adverse seismic interactions that could be caused by potential failure of overhead or adjacent components.

Services/systems and utilities for conforming acute care hospital buildings shall be permitted to pass through or under a building that has been removed from acute care hospital service until January 1, 2030, if the building removed from service meets the performance requirements of Section 307A.1.1.1.1. Services/systems and utilities for nonconforming nonacute care hospital buildings shall be permitted to pass through or under a building that has been removed from acute care hospital service only if the building removed from service meets the performance requirements of Section 307A.1.1.1.2.

Exception: Service/system and utilities for acute care hospital buildings may pass through or under the buildings that have been removed from acute care service and which do not meet the performance requirements of Section 307A.1.1.1.1 or Section 307A.1.1.1.2, provided all the following are met:

  1. The building removed from acute care service remains under the jurisdiction of OSHPD.
  2. The service/system and utilities only support acute care services in SPC-1 or SPC-2 buildings, and where no critical care areas occur.
  3. The SPC-1 or SPC-2 buildings supported by the service/system and utilities meet the nonstructural requirements of NPC-2, as defined in the CAC, Part 1, Article 11, Table 11.1 and are served with essential power from a conforming building or source which does not pass through or under a building removed from acute care services.
  4. The SPC-2 buildings supported by the service/system and utilities are removed from acute care service no later than January 1, 2026.
Services/systems and utilities shall originate in and only pass through or under buildings that are under the jurisdiction of the Office of Statewide Health Planning and Development (OSHPD).
Means of egress through existing buildings shall be in accordance with the California Building Code, except as modified in this section.

Means of egress shall comply with the requirements of Sections 308A.1.1.1 and 308A.1.1.2.

Exception: The enforcing agency shall be permitted to exempt minor additions, minor alterations and minor remodel projects from these requirements.

Means of egress for hospital buildings shall comply with the requirements of Sections 308A.1.1.1.1 through 308A.1.1.1.6.

Means of egress for new hospital buildings and additions to existing conforming hospital buildings shall only pass through buildings that are conforming or comply with the requirements of SPC-3 or higher, and NPC-4/NPC-4D or higher.

Exception: Existing means of egress that pass through hospital buildings that have approved nonstructural performance categories NPC-3, or NPC-2, if the building has an approved extension to the NPC-3 deadline, shall be permitted to remain for the duration of extension. The nonstructural components in the path of egress shall be braced in accordance with the new building provisions of this code.

Means of egress for additions to existing SPC-2 hospital buildings shall only pass through hospital buildings that have approved performance categories of SPC-2 or higher and NPC-4/NPC-4D or higher.

Exception: The means of egress shall be permitted to pass through hospital buildings that have approved nonstructural performance categories of NPC-3, or NPC-2 if the building has an approved extension to the NPC-3 deadline. Nonstructural components in the path of egress shall be braced in accordance with the new building provisions of this code.

Means of egress for remodels of existing SPC-3 or higher hospital buildings shall only pass through hospital buildings that have approved performance categories of SPC-2 or higher and NPC-4 /NPC-4D or higher.

Exception: The means of egress shall be permitted to pass through hospital buildings that have approved nonstructural performance categories of NPC-3, or NPC-2 if the building has an approved extension to the NPC-3 deadline. Nonstructural components in the path of egress shall be braced in accordance with the new building provisions of this code.

Means of egress for remodels of existing SPC-1 hospital buildings shall only pass through hospital buildings that have approved performance categories of SPC-1 or higher and NPC-2 or higher.

Exception: Means of egress for acute care service spaces for hospitals licensed pursuant to subdivision (a) of Section 1250 of the Health and Safety Code shall comply with the requirements of Section 308A.1.1.1.2.

Hospital buildings that would not otherwise require evaluation for an SPC rating, which are used as a part of the means of egress for hospital buildings, shall be evaluated in accordance with the requirements of Section 1.3, Chapter 6, of the California Administrative Code to determine the appropriate rating, or shall meet the structural requirements of these regulations for conforming hospital buildings. Means of egress shall be in accordance with the requirements of Sections 308A.1.1.1.1 through 308A.1.1.1.4.

The means of egress for acute care hospitals shall be permitted to pass through buildings that are removed from hospital service only if the buildings remain under the jurisdiction of OSHPD, and only until January 1, 2030, subject to the following:

  1. Egress for conforming hospital buildings shall be permitted to pass through buildings that have been removed from acute care hospital service that comply with the requirements of Section 308A.1.1.1.1 or 308A.1.1.1.3.
  2. Egress for nonconforming hospital buildings shall be permitted to pass through buildings that have been removed from acute care hospital service that comply with the requirements of Section 308A.1.1.1.2 or 308A.1.1.1.4.

After January 1, 2030, the means of egress for acute care hospital buildings shall only pass through hospital buildings that have approved performance categories of SPC-3 or higher and NPC-5.

Means of egress shall only pass through buildings that are under the jurisdiction of the Office of Statewide Health Planning and Development (OSHPD).
The provisions of this section shall apply when hospital SPC or freestanding buildings are being removed from general acute care service, including when freestanding buildings are removed from OSHPD jurisdiction. Removal of these buildings shall satisfy the requirements of this section and the California Building Standards Code. OSHPD approval of construction documents and a building permit are required for removal.

An SPC-1 hospital building without an approved delay in compliance requirements in accordance with the California Administrative Code (CAC) Chapter 6 Section 1.5.2 or past the extension date granted in accordance with the CAC Chapter 6 Section 1.5.2 shall not be issued a building permit until a project to remove the subject SPC-1 building from general acute care services has been approved, permitted, and closed in compliance by the Office.

Exception: Building permits for seismic compliance, maintenance and repair shall be permitted to be issued.

The following words and terms are applicable to this section only:

BUILDING. The area included within surrounding exterior walls or any combination of exterior walls and fire walls (as described in California Building Code Sections 202 and 706) exclusive of vent shafts and courts. Areas of the building not provided with surrounding walls shall be included in the building area if such areas are included within the horizontal projection of the roof or floor above. A building may consist of one or more adjacent SPC buildings.

GENERAL ACUTE CARE SERVICE. Means basic and supplemental services, as defined in California Building Code Section 1224.3, provided in a general acute care building, as defined in California Building Code Section 202 and the California Administrative Code, Chapter 6, Section 1.2.

STRUCTURAL SEPARATION. Means a building separation in accordance with the California Building Code.

In order to establish that one or more SPC buildings are eligible for removal from general acute care service, the hospital owner shall submit construction documents showing that after the SPC buildings are removed from general acute care service:

  1. All basic acute care services or supplemental services on the hospital's license are provided in SPC buildings satisfying the requirements for SPC-2, SPC-3, SPC-4, SPC-4D, or SPC-5.

    Exception: If the hospital includes SPC-1 buildings that are not being removed from general acute care service, and these SPC-1 buildings have an approved extension to the SPC-2 deadline, basic acute care services or supplemental services on the hospital's license are permitted to remain in these SPC buildings for the duration of their extension or until these SPC-1 buildings are removed from general acute care service, whichever comes first.

  2. All basic acute care services or supplemental services on the hospital's license are provided in SPC buildings satisfying the requirements for NPC-3, NPC-4/NPC-4D, or NPC-5.

    Exception: Services shall be permitted to be located in SPC buildings satisfying the requirements of NPC-2 if the SPC buildings have an approved extension to NPC-3 deadline.

  3. The hospital complies with all egress requirements, including occupant load, number of required exits and travel distance to exits, and provides evidence that no egress from any acute care hospital building passes through the SPC buildings removed from general acute care service, SPC-1 buildings, or through buildings not under OSHPD jurisdiction.

    Exceptions:

    1. If the SPC building has an approved extension to the SPC-2 deadline, existing egress through the SPC-1 building shall be permitted for the duration of the extension or until the SPC-1 building is removed from general acute care service, whichever comes first.
    2. When permitted by Section 308A.1.1.1.6.
  4. No SPC building removed from general acute care service is used as a smoke compartment for any acute care hospital building. Buildings not under OSHPD jurisdiction shall not be used as a smoke compartment for any acute care hospital building.
  5. Structural separation, fire barriers and fire walls shall satisfy the requirements of the California Building Standards Code.

    Exception: An SPC seismic separation in accordance with the California Administrative Code Chapter 6 Section 3.4 shall be deemed to satisfy the building structural/seismic separation requirement in this section for SPC buildings that will remain under OSHPD jurisdiction.

  6. If the SPC building removed from general acute care service shares a common fire alarm system with the acute care hospital, the main fire alarm control panel shall be located in an acute care hospital building. The SPC building removed from general acute care service shall be in a separate zone monitored by the main fire alarm control panel. Flexible connections shall be provided for conduits/conductors crossing structural or SPC seismic separation joints. If the intent is to place the SPC building under local jurisdiction, the building shall satisfy Section 309A.5.1.

    Exception: Flexible connections for fire alarm conduits/conductors crossing seismic separation joints between an SPC building removed from general acute care service and adjacent SPC-1 or SPC-2 buildings may be omitted, provided the fire alarm in the adjacent SPC-1 and SPC-2 buildings have no connection to any SPC-3, SPC-4, SPC-4D, and SPC-5 buildings providing general acute care service.

  7. If the SPC building removed from general acute care service shares the fire sprinkler system with the acute care hospital, an isolation valve with a tamper switch shall be provided to isolate the portion of the system serving the SPC building removed from acute care service. Flexible connections shall be provided in piping that crosses structural or SPC seismic separation joints. The fire sprinkler system shall not originate in the SPC building removed from general acute care service. If the intent is to place the building under local jurisdiction, the building shall satisfy Section 309A.5.1.

    Exception: Flexible connections for seismic separation joints and fail safe shutoff valves, and disconnects for utilities between an SPC building removed from general acute care service and adjacent SPC-1 or SPC-2 buildings may be omitted, provided utilities in the adjacent SPC-1 and SPC-2 buildings have no connection to any SPC-3, SPC-4, SPC-4D, and SPC-5 buildings providing general acute care service.

  8. Patient access as required by California Building Code Section 1224.4.7.5 does not pass through an SPC building removed from general acute care service or through buildings that are not under the jurisdiction of OSHPD.
  9. The primary accessible entrance to the hospital is not through an SPC building removed from general acute care service or through buildings that are not under the jurisdiction of OSHPD.
  10. No utilities servicing acute care hospital buildings originate in or pass through, over, or under, an SPC building removed from general acute care service, except as permitted by Section 307A.1.1.1.5, or a building not under OSHPD jurisdiction.
  11. If utilities originating in an acute care hospital building feed an SPC building removed from general acute care hospital service, fail safe shutoff valves and/or disconnects shall be provided that permit isolation of the SPC building removed from general acute care service from the hospital utilities. Flexible connections shall be provided for all utilities crossing structural or SPC seismic separation joints.

    Exception: Flexible connections for seismic separation joints and fail safe shutoff valves, and disconnects for utilities between an SPC building removed from general acute care service and adjacent SPC-1 or SPC-2 buildings may be omitted, provided utilities in the adjacent SPC-1 and SPC-2 buildings have no connection to any SPC-3, SPC-4, SPC-4D, and SPC-5 buildings providing general acute care service.

SPC and freestanding buildings removed from acute care service while remaining under the jurisdiction of OSHPD shall be subject to the provisions of Section 309.3.
Except as provided by Section 309A.5.3, at the hospital's discretion, a building removed from general acute care service shall be permitted to be placed under the jurisdiction of the local enforcement agency. To be eligible for a change in jurisdiction, the building removed from general acute care service shall satisfy the requirements of Section 309A.5.1.

For a building removed from general acute care service to be eligible for a change in jurisdiction to the local enforcing agency, all the following criteria shall be satisfied:

  1. The building removed from general acute care service shall be freestanding, as defined in the California Administrative Code, Section 7-111.
  2. Any hospital support services located in the building removed from general acute care service, including administrative services, central sterile supply, storage, morgue and autopsy, employee dressing rooms and lockers, janitorial and housekeeping service, and laundry, shall be in excess of the minimum requirements for licensure and operation. Prior approval by the California Department of Public Health shall be obtained by hospital to locate these services in the building removed from general acute care service.
  3. Services/systems and utilities (e.g., power, emergency power, communication/data/nurse-call systems, space-heating systems, fire alarm system, firesprinkler system, medical gas & plumbing systems) shall be separate and independent from those serving any buildings under OSHPD jurisdiction.
  4. If the building being transferred to the jurisdiction of the local enforcing agency is adjacent to a building under OSHPD jurisdiction and fire-resistive construction separations are required, they shall be located in the building under OSHPD jurisdiction.
The owner of the building shall be responsible for bringing the building into compliance with all requirements of the new authority having jurisdiction. If a building requires modification to become eligible for removal from OSHPD jurisdiction, the construction project shall be closed with compliance by OSHPD prior to the change in jurisdiction. All occupancy separation, setback, and allowable area requirements shall be enforced.

The following freestanding buildings shall remain under OSHPD jurisdiction:

  1. Any building in which basic and/or supplementary services are provided for a general acute care hospital, acute psychiatric hospital, and general acute care hospital providing only acute medical rehabilitation center services.
  2. Any building which provides required patient access, egress, or smoke compartment for a Building under OSHPD's jurisdiction.
  3. Any building in which services under OSHPD jurisdiction are provided, including skilled nursing services, intermediate care services, acute psychiatric services, and distinct part skilled nursing or intermediate care services.
  4. Any building providing central plant or utility services to a building under OSHPD jurisdiction.
  5. Any building through which utilities pass through, over or under, to serve a building under OSHPD jurisdiction.
Vacated spaces intended to remain vacant while under the jurisdiction of OSHPD shall be subject to the provisions of Section 309.3.5.
Demolition of SPC buildings to be removed from general acute care services shall be permitted when buildings remaining under OSHPD's jurisdiction, after demolition, satisfy the requirements of the California Building Standards Code and demolition activity does not impair the operation and/or safety of any buildings that remain under the OSHPD's jurisdiction. Demolition shall be in accordance with California Building Code Section 3303.
The requirements of this section and Section 309A shall apply to buildings removed from general acute care services that remain under OSHPD jurisdiction.
Non-GAC buildings shall conform to the requirements of Section 1.10.1 [OSHPD 1R].

Application and enforcement of freestanding buildings removed from general acute care services but remaining under OSHPD jurisdiction shall be in accordance with Section 1.10.1 [OSHPD 1R].

Freestanding hospital-owned clinics shall be permitted to be under the jurisdiction of OSHPD in accordance with the California Administrative Code Sections 7-2104, 7-2105, and 7-2106.

All access points into SPC-1 buildings/non-GAC buildings from general acute care buildings shall prominently display signage at entrances/corridors, on each floor with access into the SPC-1 building stating "NO GENERAL ACUTE CARE SERVICES BEYOND THIS POINT."
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING