Heads up: There are no suggested sections in this chapter.
Heads up: There are no amended sections in this chapter.

The provisions of this chapter shall govern the design, installation, repair and maintenance of septic tanks, treatment tanks and holding tanks.

Septic tanks shall be fabricated or constructed of welded steel, monolithic concrete, fiberglass or an approved material. Tanks shall be water tight and fabricated to constitute an individual structure, and shall be designed and constructed to withstand anticipated loads. The design of prefabricated septic tanks shall be approved. Plans for site-constructed concrete tanks shall be approved prior to construction.

Septic tanks shall have not less than two compartments. The inlet compartment shall be not less than two-thirds of the total capacity of the tank, not less than a 500-gallon (1893 L) liquid capacity and not less than 3 feet (914 mm) wide and 5 feet (1524 mm) long. The secondary compartment of a septic tank shall have not less than a capacity of 250 gallons (946 L) and not more than one-third of the total capacity. The secondary compartment of septic tanks having a capacity more than 1,500 gallons (5678 L) shall be not less than 5 feet (1524 mm) long.

The liquid depth shall be not less than 30 inches (762 mm) and a maximum average of 6 feet (1829 mm). The total depth shall be not less than 8 inches (203 mm) greater than the liquid depth.

Rectangular tanks shall be constructed with the longest dimensions parallel to the direction of the flow.

Cylindrical tanks shall be not less than 48 inches (1219 mm) in diameter.

The inlet and outlet on all tanks or tank compartments shall be provided with open-end coated sanitary tees or baffles made of approved materials constructed to distribute flow and retain scum in the tank or compartments. The inlet and outlet openings on all tanks shall contain a stop or other provision that will prevent the insertion of the sewer piping beyond the inside wall of the tank. The tees or baffles shall extend not less than 6 inches (152 mm) above the liquid level, not less than 9 inches (229 mm) below the liquid level, and not greater than one-third the liquid depth below the liquid level. Not less than 2 inches (51 mm) of clear space shall be provided above the top of the baffles or tees. The bottom of the outlet opening shall be not less than 2 inches (51 mm) below the bottom of the inlet.
Each compartment of a tank shall be provided with not fewer than one manhole opening located over the inlet or outlet opening, and such opening shall be not less than 24 inches (610 mm) square or 24 inches (610 mm) in diameter. Where the inlet compartment of a septic tank exceeds 12 feet (3658 mm) in length, an additional manhole shall be provided over the baffle wall. Manholes shall terminate not greater than 6 inches (152 mm) below the ground surface. Manholes shall be of the same material as the tank. Steel tanks shall have not less than a 2-inch (51 mm) collar for the manhole extensions permanently welded to the tank. The manhole extension on fiberglass tanks shall be of the same material as the tank and an integral part of the tank. The collar shall be not less than 2 inches (51 mm) high.
Manhole risers shall be provided with a fitted, water-tight cover of concrete, steel, cast iron or other approved material capable of withstanding all anticipated loads. Manhole covers terminating above grade shall have an approved locking device.
An inspection opening shall be provided over either the inlet or outlet baffle of every treatment tank. The opening shall be not less than 4 inches (102 mm) in diameter with a tight-fitting cover. Inspection pipes terminating above ground shall be not less than 6 inches (152 mm) above finished grade. Inspection pipes approved for terminating below grade shall be not more than 2 inches (51 mm) below finished grade, and the location shall be permanently recorded.
The capacity of a septic tank or other treatment tank shall be based on the number of persons using the building to be served or on the volume and type of waste, whichever is greater. The minimum liquid capacity shall be 750 gallons (2839 L). Where the required capacity is to be provided by more than one tank, the minimum capacity of any tank shall be 750 gallons (2839 L). The installation of more than four tanks in series is prohibited.

The minimum liquid capacity for one- and two-family dwellings shall be in accordance with Table 802.7.1.

TABLE 802.7.1

SEPTIC TANK CAPACITY FOR ONE- AND TWO-FAMILY DWELLINGS

NUMBER OF BEDROOMSSEPTIC TANK (gallons)
1750
2750
31,000
41,200
51,425
61,650
71,875
82,100

For SI: 1 gallon = 3.785 L.

For buildings, the liquid capacity shall be increased above the 750-gallon (2839 L) minimum as established in Table 802.7.1. In buildings with kitchen or laundry waste, the tank capacity shall be increased to receive the anticipated volume for a 24-hour period from the kitchen or laundry or both. The liquid capacities established in Table 802.7.2 do not include employees.

Exception: One- or two-family dwellings.

TABLE 802.7.2

ADDITIONAL CAPACITY FOR OTHER BUILDINGS

BUILDING CLASSIFICATIONCAPACITY (gallons)
Apartment buildings (per bedroom—includes automatic clothes washer)150
Assembly halls (per person—no kitchen)2
Bars and cocktail lounges (per patron space)9
Beauty salons (per station—includes customers)140
Bowling centers (per lane)125
Bowling centers with bar (per lane)225
Camp, day use only—no meals served (per person)15
Campgrounds and camping resorts (per camp space)100
Campground sanitary dump stations (per camp space) (omit camp spaces with sewer connection)5
Camps, day and night (per person)40
Car washes (per car handwash)50
Catch basins—such as for garages and motor-fuel-dispensing facilities (per basin)100
Catch basins—truck washing (per truck)100
Places of religious worship—no kitchen (per person)3
Places of religious worship—with kitchen (per person)7.5
Condominiums (per bedroom—includes automatic clothes washer)150
Dance halls (per person)3
Dining halls—kitchen and toilet waste—with dishwasher, food waste grinder or both (per meal served)11
Dining halls—kitchen waste only (per meal served)3
Drive-in restaurants—all paper service (per car space)15
Drive-in restaurants—all paper service, inside seating (per seat)15
Drive-in theaters (per car space)5
Employees—in all buildings, per employee—total all shifts20
Floor drains (per drain)50
Hospitals (per bed space)200
Hotels or motels and tourist rooming houses100
Labor camps, central bathhouses (per employee)30
Medical office buildings, clinics and dental offices
Doctors, nurses, medical staff (per person)
Office personnel (per person)
Patients (per person)
75
20
10
Mobile home parks, homes with bathroom groups (per site)300
Motor-fuel-dispensing facilities10
Nursing and rest homes—without laundry (per bed space)100
Outdoor sports facilities (toilet waste only—per person)5
Parks, toilet waste (per person—75 persons per acre)5
Parks, with showers and toilet waste (per person—75 persons per acre)10
Restaurants—dishwasher or food waste grinder or both (per seat)3
Restaurants—kitchen and toilet wastes (per seating space)30
Restaurants—kitchen waste only—without dishwasher and food waste grinder (per seat)9
Restaurants—toilet waste only (per seat)21
Restaurants (24-hour)—dishwasher or food waste grinder (per seat)6
Restaurants (24 hour)—kitchen and toilet waste (per seating space)60
Retail stores—customers1.5
Schools (per classroom—25 pupils per classroom)450
Schools with meals served (per classroom—25 pupils per classroom)600
Schools with meals served and showers provided (per classroom)750
Self-service laundries (toilet waste only, per machine)
Automatic clothes washers—such as for apartments and service buildings, (per machine)
50

300
Showers—public (per shower taken)15
Swimming pool bathhouses (per person)10

For SI: 1 gallon = 3.785 L.

Septic and other treatment tanks shall be located with a horizontal distance not less than specified in Table 802.8 between various elements. Tanks installed in ground water shall be securely anchored. A 3-inch-thick (76 mm) compacted bedding shall be provided for all septic and other treatment tank installations. The bedding material shall be sand, gravel, granite, limerock or other noncorrosive materials of such size that the material passes through a 0.5-inch (12.7 mm) screen.

TABLE 802.8

MINIMUM HORIZONTAL SEPARATION DISTANCES FOR TREATMENT TANKS

ELEMENTDISTANCE (feet)
Building5
Cistern25
Foundation wall5
Lake, high water mark25
Lot line2
Pond25
Reservoir25
Spring50
Stream or watercourse25
Swimming pool15
Water service5
Well25

For SI: 1 foot = 304.8 mm.

The backfill material for steel and fiberglass tanks shall be specified for bedding and shall be tamped into place without causing damage to the coating. The backfill for concrete tanks shall be soil material, which shall pass a 4-inch (102 mm) screen and be tamped into place.
Joints on concrete risers and manhole covers shall be tongue-and-groove or shiplap type and sealed water tight using neat cement, mortar or bituminous compound. Joints on steel risers shall be welded or flanged and bolted and water tight. Steel manhole extensions shall be bituminous coated both inside and outside. Methods of attaching fiberglass risers shall be water tight and approved.
Dosing or pumping chambers shall be fabricated or constructed of welded steel, monolithic concrete, glass fiber-reinforced polyester or other approved materials. Manholes for dosing or pumping chambers shall terminate not less than 4 inches (102 mm) above the ground surface. Dosing or pumping chambers shall be water tight, and materials and construction specifications shall meet the same criteria specified for septic tanks in this chapter.

The working capacity of the dosing or pumping chamber shall be sized to permit automatic discharge of the total daily sewage flow with discharge occurring not more than four times per 24 hours. Minimum capacity of a dosing chamber shall be 500 gallons (1893 L) and a space shall be provided between the bottom of the pump and floor of the dosing or pumping chamber. A dosing chamber shall have a 1-day holding capacity located above the high-water alarm for one- and two-family dwellings based on 100 gallons (379 L) per day per bedroom, or in the case of other buildings, in accordance with Section 802.7. Minimum pump chamber sizes are indicated for one- and two-family dwellings in Table 802.11.1. Where the total developed length of distribution piping exceeds 1,000 feet (305 m), the dosing or pumping chamber shall have two siphons or pumps dosing alternately and serving one-half of the soil absorption system.

TABLE 802.11.1

PUMP CHAMBER SIZES

NUMBER OF BEDROOMSMINIMUM PUMPING CHAMBER SIZE
(gallons)
1500
2500
3750
4750
51,000

For SI: 1 gallon = 3.785 L.

The design of other treatment tanks shall be approved on an individual basis. The capacity, sizing and installation of the tank shall be in accordance with this section except as otherwise approved. Where a treatment tank is preceded by a conventional septic tank, credit shall be given for the capacity of the septic tank.
Septic tanks and other treatment tanks shall be cleaned whenever the sludge and scum occupy one-third of the tank's liquid capacity.
Septage shall be disposed of at an approved location.
Products for chemical restoration or chemical restoration procedures for private sewage disposal systems shall not be used unless approved.
The installation of a holding tank shall not be approved where the site can accommodate the installation of any other private sewage disposal system specified in this code. A pumping and maintenance schedule for each holding tank installation shall be submitted to the code official.

The minimum liquid capacity of a holding tank for one- and two-family dwellings shall be in accordance with Table 805.2. Other buildings shall have a minimum 5-day holding capacity, but not less than 2,000 gallons (7570 L). Sizing shall be in accordance with Table 802.7.2. Not more than four holding tanks shall be installed in series.

TABLE 805.2

MINIMUM LIQUID CAPACITY OF HOLDING TANKS

NUMBER OF
BEDROOMS
TANK CAPACITY
(gallons)
12,000
22,000
32,000
42,500
53,000
63,500
74,000
84,500

For SI: 1 gallon = 3.785 L.

Holding tanks shall be constructed of welded steel, monolithic concrete, glass-fiber-reinforced polyester or other approved materials.
Tanks shall be located in accordance with Section 802.8, except the tanks shall be not less than 20 feet (6096 mm) from any part of a building. Holding tanks shall be located so the servicing manhole is located not less than 10 feet (3048 mm) from an all-weather access road or drive.
A high-water warning device shall be installed to activate 1 foot (305 mm) below the inlet pipe. This device shall be either an audible or an approved illuminated alarm. The electrical junction box, including warning equipment junctions, shall be located outside the holding tank or housed in waterproof, explosionproof enclosures. Electrical relays or controls shall be located outside the holding tank.
Each tank shall be provided with either a manhole not less than 24 inches (610 mm) square or with a manhole having a 24-inch (610 mm) inside diameter extending not less than 4 inches (102 mm) above ground. Finished grade shall be sloped away from the manhole to divert surface water from the manhole. Each manhole cover shall have an effective locking device. Service ports in manhole covers shall be not less than 8 inches (203 mm) in diameter and shall be 4 inches (102 mm) above finished grade level. The service port shall have an effective locking cover or a brass cleanout plug.
The outlet shall be sealed where an approved septic tank is installed to serve as a holding tank. Removal of the inlet and outlet baffle shall not be prohibited.
Each tank shall be provided with a vent not less than 2 inches (51 mm) in diameter and shall extend not less than 12 inches (305 mm) above finished grade, terminating with a return bend fitting or approved vent cap.
Analyzing code differences
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING