ADOPTS WITH AMENDMENTS:

International Fire Code 2018 (IFC 2018)

Part I — Administrative

Part II — General Safety Provisions

Part III — Building and Equipment Design Features

Part IV — Special Occupancies and Operations

Part V — Hazardous Materials

Part VI — Referenced Standards

Part VII — Appendices

Heads up: There are no amended sections in this chapter.
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance or legislation of the jurisdiction.

The procedure for determining fire-flow requirements for buildings or portions of buildings hereafter constructed shall be in accordance with this appendix. This appendix does not apply to structures other than buildings.

For the purpose of this appendix, certain terms are defined as follows:

FIRE FLOW. The flow rate of a water supply, measured at 20 pounds per square inch (psi) (138 kPa) residual pressure, that is available for fire fighting.

FIRE-FLOW CALCULATION AREA. The floor area, in square feet (m2), used to determine the required fire flow.

The fire code official is authorized to reduce the fire-flow requirements for isolated buildings or a group of buildings in rural areas or small communities where the development of full fire-flow requirements is impractical.
The fire code official is authorized to increase the fire-flow requirements where conditions indicate an unusual susceptibility to group fires or conflagrations. An increase shall be not more than twice that required for the building under consideration.
For information regarding water supplies for fire-fighting purposes in rural and suburban areas in which adequate and reliable water supply systems do not exist, the fire code official is authorized to utilize NFPA 1142 or the International Wildland-Urban Interface Code.
The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections of the roof of a building, except as modified in Section B104.3.
Portions of buildings that are separated by fire walls without openings, constructed in accordance with the International Building Code, are allowed to be considered as separate fire-flow calculation areas.

The fire-flow calculation area of buildings constructed of Type IA and Type IB construction shall be the area of the three largest successive floors.

Exception: Fire-flow calculation area for open parking garages shall be determined by the area of the largest floor.

The minimum fire-flow and flow duration requirements for one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Tables B105.1(1) and B105.1(2).

TABLE B105.1(1)

REQUIRED FIRE FLOW FOR ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES

FIRE-FLOW CALCULATION AREA
(square feet)
AUTOMATIC SPRINKLER SYSTEM
(Design Standard)
MINIMUM FIRE FLOW
(gallons per minute)
FLOW DURATION
(hours)
0—3,600No automatic sprinkler system1,0001
3,601 and greaterNo automatic sprinkler systemValue in
Table B105.1(2)
Duration in Table B105.1(2)
at the required fire-flow rate
0—3,600Section 903.3.1.3 of the International Fire Code or5001/2
3,601 and greaterSection 903.3.1.3 of the International Fire Code or1/2 value in
Table B105.1(2)
1

For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m.

TABLE B105.1(2)

REFERENCE TABLE FOR TABLES B105.1(1) AND B105.2

FIRE-FLOW CALCULATION AREA (square feet)FIRE-FLOW
(gallons per minute)b
FLOW DURATION
(hours)
Type IA and IBaType IIA and IIIAaType IV and V-AaType IIB and IIIBaType V-Ba
0-22,7000-12,7000-8,2000-5,9000-3,6001,5002
22,701-30,20012,701-17,0008,201-10,9005,901-7,9003,601-4,8001,750
30,201-38,70017,001-21,80010,901-12,9007,901-9,8004,801-6,2002,000
38,701-48,30021,801-24,20012,901-17,4009,801-12,6006,201-7,7002,250
48,301-59,00024,201-33,20017,401-21,30012,601-15,4007,701-9,4002,500
59,001-70,90033,201-39,70021,301-25,50015,401-18,4009,401-11,3002,750
70,901-83,70039,701-47,10025,501-30,10018,401-21,80011,301-13,4003,0003
83,701-97,70047,101-54,90030,101-35,20021,801-25,90013,401-15,6003,250
97,701-112,70054,901-63,40035,201-40,60025,901-29,30015,601-18,0003,500
112,701-128,70063,401-72,40040,601-46,40029,301-33,50018,001-20,6003,750
128,701-145,90072,401-82,10046,401-52,50033,501-37,90020,601-23,3004,0004
145,901-164,20082,101-92,40052,501-59,10037,901-42,70023,301-26,3004,250
164,201-183,40092,401-103,10059,101-66,00042,701-47,70026,301-29,3004,500
183,401-203,700103,101-114,60066,001-73,30047,701-53,00029,301-32,6004,750
203,701-225,200114,601-126,70073,301-81,10053,001-58,60032,601-36,0005,000
225,201-247,700126,701-139,40081,101-89,20058,601-65,40036,001-39,6005,250
247,701-271,200139,401-152,60089,201-97,70065,401-70,60039,601-43,4005,500
271,201-295,900152,601-166,50097,701-106,50070,601-77,00043,401-47,4005,750
295,901-Greater166,501-Greater106,501-115,80077,001-83,70047,401-51,5006,000
115,801-125,50083,701-90,60051,501-55,7006,250
125,501-135,50090,601-97,90055,701-60,2006,500
135,501-145,80097,901-106,80060,201-64,8006,750
145,801-156,700106,801-113,20064,801-69,6007,000
156,701-167,900113,201-121,30069,601-74,6007,250
167,901-179,400121,301-129,60074,601-79,8007,500
179,401-191,400129,601-138,30079,801-85,1007,750
191,401-Greater138,301-Greater85,101-Greater8,000

For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa.

  1. Types of construction are based on the International Building Code.
  2. Measured at 20 psi residual pressure.

The minimum fire-flow and flow duration for buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Tables B105.2 and B105.1(2).

TABLE B105.2

REQUIRED FIRE FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES

AUTOMATIC SPRINKLER SYSTEM
(Design Standard)
MINIMUM FIRE FLOW
(gallons per minute)
FLOW DURATION
(hours)
No automatic sprinkler systemValue in Table B105.1(2)Duration in Table B105.1(2)
Section 903.3.1.1 of the International Fire Code25% of the value in Table B105.1(2)aDuration in Table B105.1(2) at the reduced flow rate
Section 903.3.1.2 of the International Fire Code25% of the value in Table B105.1(2)bDuration in Table B105.1(2) at the reduced flow rate

For SI: 1 gallon per minute = 3.785 L/m.

  1. The reduced fire flow shall be not less than 1,000 gallons per minute.
  2. The reduced fire flow shall be not less than 1,500 gallons per minute.

For buildings equipped with an approved automatic sprinkler system, the water supply shall be capable of providing the greater of:

  1. The automatic sprinkler system demand, including hose stream allowance.
  2. The required fire flow.
ICC IBC—18International Building CodeB104.2
ICC IWUIC—18International WildlandUrban Interface CodeB103.3
ICC IRC—18International Residential CodeTable B105.1(1)
NFPA 1142—17Standard on Water Supplies for Suburban and Rural Fire FightingB103.3
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING