ADOPTS WITHOUT AMENDMENTS:

UPC 2021

Heads up: There are no amended sections in this chapter.
This appendix provides general guidelines for the sizing of storm water drainage systems based on maximum rates of rainfall for various cities. The rainfall rates in Table D 101.1 shall be permitted to be used for design unless higher values are established locally.

TABLE D 101.1
MAXIMUM RATES OF RAINFALL FOR VARIOUS CITIES*
STATES AND CITIES STORM DRAINAGE 60-MINUTE DURATION, 100-YEAR RETURN
inches per hour gallons per minute per square foot
ALABAMA
Birmingham 3.7 0.038
Huntsville 3.3 0.034
Mobile 4.5 0.047
Montgomery 3.8 0.039
     
ALASKA
Aleutian Islands 1.0 0.010
Anchorage 0.6 0.006
Bethel 0.8 0.008
Fairbanks 1.0 0.010
Juneau 0.6 0.006
     
ARIZONA
Flagstaff 2.3 0.024
Phoenix 2.2 0.023
Tucson 3.0 0.031
     
ARKANSAS
Eudora 3.8 0.039
Ft. Smith 3.9 0.041
Jonesboro 3.5 0.036
Little Rock 3.7 0.038
     
CALIFORNIA
Eureka 1.5 0.016
Lake Tahoe 1.3 0.014
Los Angeles 2.0 0.021
Lucerne Valley 2.5 0.026
Needles 1.5 0.016
Palmdale 3.0 0.031
Redding 1.5 0.016
San Diego 1.5 0.016
San Francisco 1.5 0.016
San Luis Obispo 1.5 0.016
     
COLORADO
Craig 1.5 0.016
Denver 2.2 0.023
Durango 1.8 0.019
Stratton 3.0 0.031
     
CONNECTICUT
Hartford 2.8 0.029
New Haven 3.0 0.031
     
DELAWARE
Dover 3.5 0.036
Rehobeth Beach 3.6 0.037
     
DISTRICT OF COLUMBIA
Washington 4.0 0.042
     
FLORIDA
Daytona Beach 4.0 0.042
Ft. Myers 4.0 0.042
Jacksonville 4.3 0.045
Melbourne 4.0 0.042
Miami 4.5 0.047
Palm Beach 5.0 0.052
Tampa 4.2 0.044
Tallahassee 4.1 0.043
     
GEORGIA
Atlanta 3.5 0.036
Brunswick 4.0 0.042
Macon 3.7 0.038
Savannah 4.0 0.042
Thomasville 4.0 0.042
     
HAWAII
Rainfall rates in the Hawaiian Islands vary from 11/2 inches per hour to 8 inches per hour, depending on location and elevation. Consult local data.
     
IDAHO
Boise 1.0 0.010
Idaho Falls 1.2 0.012
Lewiston 1.0 0.010
Twin Falls 1.1 0.011
     
ILLINOIS
Chicago 2.7 0.028
Harrisburg 3.1 0.032
Peoria 2.9 0.030
Springfield 3.0 0.031
     
INDIANA
Evansville 3.0 0.031
Indianapolis 2.8 0.029
Richmond 2.7 0.028
South Bend 2.7 0.028
     
IOWA
Council Bluffs 3.7 0.038
Davenport 3.0 0.031
Des Moines 3.4 0.035
Sioux City 3.6 0.037
     
KANSAS
Goodland 3.5 0.036
Salina 3.8 0.039
Topeka 3.8 0.039
Wichita 3.9 0.041
     
KENTUCKY
Bowling Green 2.9 0.030
Lexington 2.9 0.030
Louisville 2.8 0.029
Paducah 3.0 0.031
     
LOUISIANA
Monroe 3.8 0.039
New Orleans 4.5 0.047
Shreveport 4.0 0.042
     
MAINE
Bangor 2.2 0.023
Kittery 2.4 0.025
Millinocket 2.0 0.021
     
MARYLAND
Baltimore 3.6 0.037
Frostburg 2.9 0.030
Ocean City 3.7 0.038
     
MASSACHUSETTS
Adams 2.6 0.027
Boston 2.7 0.028
Springfield 2.7 0.028
     
MICHIGAN
Detroit 2.5 0.026
Grand Rapids 2.6 0.027
Kalamazoo 2.7 0.028
Sheboygan 2.1 0.022
Traverse City 2.2 0.023
     
MINNESOTA
Duluth 2.6 0.027
Grand Forks 2.5 0.026
Minneapolis 3.0 0.031
Worthington 3.4 0.035
     
MISSISSIPPI
Biloxi 4.5 0.047
Columbus 3.5 0.036
Jackson 3.8 0.039
     
MISSOURI
Independence 3.7 0.038
Jefferson City 3.4 0.035
St. Louis 3.2 0.033
Springfield 3.7 0.038
     
MONTANA
Billings 1.8 0.019
Glendive 2.5 0.026
Great Falls 1.8 0.019
Missoula 1.3 0.014
     
NEBRASKA
Omaha 3.6 0.037
North Platte 3.5 0.036
Scotts Bluff 2.8 0.029
     
NEVADA
Las Vegas 1.5 0.016
Reno 1.2 0.012
Winnemucca 1.0 0.010
     
NEW HAMPSHIRE
Berlin 2.2 0.023
Manchester 2.5 0.026
     
NEW JERSEY
Atlantic City 3.4 0.035
Paterson 3.0 0.031
Trenton 3.2 0.033
     
NEW MEXICO
Albuquerque 2.0 0.021
Carlsbad 2.6 0.027
Gallup 2.1 0.022
     
NEW YORK
Binghamton 2.4 0.025
Buffalo 2.3 0.024
New York City 3.1 0.032
Schenectady 2.5 0.026
Syracuse 2.4 0.025
     
NORTH CAROLINA
Asheville 3.2 0.033
Charlotte 3.4 0.035
Raleigh 4.0 0.042
Wilmington 4.4 0.046
     
NORTH DAKOTA
Bismarck 2.7 0.028
Fargo 2.9 0.030
Minot 2.6 0.027
     
OHIO
Cincinnati 2.8 0.029
Cleveland 2.4 0.025
Columbus 2.7 0.028
Toledo 2.6 0.027
Youngstown 2.4 0.025
     
OKLAHOMA
Boise City 3.4 0.035
Muskogee 4.0 0.042
Oklahoma City 4.1 0.043
     
OREGON
Medford 1.3 0.014
Ontario 1.0 0.010
Portland 1.3 0.014
     
PENNSYLVANIA
Erie 2.4 0.025
Harrisburg 2.9 0.030
Philadelphia 3.2 0.033
Pittsburgh 2.5 0.026
Scranton 2.8 0.029
     
RHODE ISLAND
Newport 3.0 0.031
Providence 2.9 0.030
     
SOUTH CAROLINA
Charleston 4.1 0.043
Columbia 3.5 0.036
Greenville 3.3 0.034
     
SOUTH DAKOTA
Lemmon 2.7 0.028
Rapid City 2.7 0.028
Sioux Falls 3.4 0.035
     
TENNESSEE
Knoxville 3.1 0.032
Memphis 3.5 0.036
Nashville 3.0 0.031
     
TEXAS
Corpus Christi 4.6 0.048
Dallas 4.2 0.044
El Paso 2.0 0.021
Houston 4.6 0.048
Lubbock 3.3 0.034
San Antonio 4.4 0.046
     
UTAH
Bluff 2.0 0.021
Cedar City 1.5 0.016
Salt Lake City 1.3 0.014
     
VERMONT
Bennington 2.5 0.026
Burlington 2.3 0.024
Rutland 2.4 0.025
     
VIRGINIA
Charlottesville 3.4 0.035
Norfolk 4.0 0.042
Richmond 4.0 0.042
Roanoke 3.3 0.034
     
WASHINGTON
Seattle 1.0 0.010
Spokane 1.0 0.010
Walla Walla 1.0 0.010
     
WEST VIRGINIA
Charleston 2.9 0.030
Martinsburg 3.0 0.031
Morgantown 2.7 0.028
     
WISCONSIN
Green Bay 2.5 0.026
Lacrosse 2.9 0.030
Milwaukee 2.7 0.028
Wausau 2.5 0.026
     
WYOMING
Casper 1.9 0.020
Cheyenne 2.5 0.026
Evanston 1.3 0.014
Rock Springs 1.4 0.015
For SI units: 1 inch per hour = 25.4 mm/h, 1 gallon per minute per square foot = 0.679 [(L/s)/m2]
* The rainfall rates in this table are based on U.S. Weather Bureau Technical Paper No. 40, Chart 14: 100-Year 60-Minute Rainfall (inches).
Storm drainage systems shall be permitted to be sized by storm water flow rates, using the gallons per minute per square foot [(L/s)/m2] of rainfall listed in Table D 101.1 for the local area. Multiplying the listed gallons per minute per square foot [(L/s)/m2] by the roof area being drained (in square feet) (m2) by each inlet produces the gallons per minute (gpm) (L/s) of required flow for sizing each drain inlet. The flow rates shall be permitted to be added to determine the flows in each of the drainage systems. Required pipe sizes for various flow rates are listed in Table 1103.1 and Table 1103.2.
Storm drainage systems shall be permitted to be sized using the roof area served by each of the drainage systems. Maximum allowable roof areas with various rainfall rates are listed in Table 1103.1 and Table 1103.2, along with the required pipe sizes. By using this method, it shall be permitted to interpolate between two listed rainfall rate columns (inches per hour) (mm/h). To determine the allowable roof area for a listed pipe size at a listed slope, divide the allowable square feet (m2) of the roof for a 1 inch per hour (in/h) (25.4 mm/h) rainfall rate by the listed rainfall rate for the local area. For example, the allowable roof area for a 6 inch (150 mm) drain at 1/8 inch per foot (10.4 mm/m) slope with a rainfall rate of 3.2 in/h (81 mm/h) is 21 400/3.2 = 6688 square feet (621.3 m2).
Table D 104.1 lists the discharge capacity of rectangular roof scuppers of various widths with various heads of water. The maximum allowable level of water on the roof shall be obtained from the registered design professional, based on the design of the roof.

TABLE D 104.1
DISCHARGE FROM RECTANGULAR SCUPPERS (gallons per minute)1, 2, 3, 4
WATER HEAD
(inches)
WIDTH OF SCUPPER (inches)
6 12 18 24 30 36
1/2 6 13 19 25 32 38
1 17 35 53 71 89 107
11/2 31 64 97 130 163 196
2 98 149 200 251 302
21/2 136 207 278 349 420
3 177 271 364 458 551
31/2 339 457 575 693
4 412 556 700 844
For SI units: 1 inch = 25.4 mm, 1 gallon per minute = 0.06 L/s
Notes:
1 Table D 104.1 is based on discharge over a rectangular weir with end contractions.
2 The head is the depth of water above the bottom of the scupper opening.
3 The height of the scupper opening shall be not less than two times the design head.
4 Coordinate the allowable head of water with the structural design of the roof.
Linked Resources
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Code Compare
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Bookmarks
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Amendment Styling
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More