Heads up:
There are no amended sections in this chapter.
Mechanical equipment and systems serving the heating, cooling, ventilating, or refrigeration needs of new buildings shall comply with the requirements of this section as described in Section 6.2.
Mechanical equipment and systems serving the heating, cooling, ventilating, or refrigeration needs of additions to existing buildings shall comply with the requirements of this section as described in Section 6.2.
Exception to 6.1.1.2
Exceptions to 6.1.1.3
Compliance shall not be required
- for equipment that is being modified or repaired but not replaced, provided that such modifications and/or repairs will not result in an increase in the annual energy consumption of the equipment using the same energy type;
- where a replacement or alteration of equipment requires extensive revisions to other systems, equipment, or elements of a building, and such replaced or altered equipment is a like-for-like replacement;
- for a refrigerant change of existing equipment;
- for the relocation of existing equipment; or
- for ducts and piping where there is insufficient space or access to meet these requirements.
New HVACR equipment as a direct replacement of existing HVACR equipment shall comply with the following sections as applicable for the equipment being replaced:
- 6.3, "Simplified Approach Option for HVAC Systems"
- 6.4.1, "Equipment Efficiencies, Verification, and Labeling Requirements"
- 6.4.3.1, "Zone Thermostatic Controls"
- 6.4.3.2, "Set-Point Overlap Restrictions"
- 6.4.3.3, "Off-Hour Controls" except for Section 6.4.3.3.4, "Zone Isolation"
- 6.4.3.4, "Ventilation System Controls"
- 6.4.3.7, "Freeze Protection and Snow/Ice Melting Systems"
- 6.4.3.8, "Ventilation Controls for High-Occupancy Areas" only for single-zone equipment
- 6.4.3.9, "Heated or Cooled Vestibules"
- 6.4.5, "Walk-In Coolers and Walk-In Freezers"
- 6.5.1.1, "Air Economizers" for units located outdoors
- 6.5.1.3, "Integrated Economizer Control"
- 6.5.1.4, "Economizer Heating System Impact"
- 6.5.3.1.3, "Fan Efficiency"
- 6.5.3.2.1, "Supply Fan Airflow Control"
- 6.5.3.6, "Fractional Horsepower Kilowatt Fan Motors"
- 6.5.4.1, "Boiler Turndown"
- 6.5.4.3, "Chiller and Boiler Isolation"
- 6.5.5.2, "Fan Speed Control"
New cooling systems installed to serve previously uncooled spaces shall comply with this section as described in Section 6.2.
Alterations to existing cooling systems shall not decrease economizer capability unless the system complies with Section 6.5.1.
New and replacement piping shall comply with Section 6.4.4.1.
Climate zones shall be determined in accordance with Section 5.1.4.
Mechanical equipment and systems providing heating, cooling, ventilating, or refrigeration shall comply with Section 6.2.1 and Section 6.2.2.
Mechanical equipment and systems shall comply with Section 6.1, "General"; Section 6.4, "Mandatory Provisions"; Section 6.7, "Submittals"; and Section 6.8, "Minimum Equipment Efficiency Tables."
- Section 6.3, "Simplified Approach Building Compliance Path for HVAC Systems" Exception to 6.2.2(a)When compliance is shown using Section 6.2.2(a), compliance with Section 6.4 is not required.
- Section 6.5, "Prescriptive Compliance Path" Exception to 6.2.2(b)HVAC systems only serving the heating, cooling, or ventilating needs of a computer room with IT equipment load greater than 10 kW shall be permitted to comply with Section 6.4, "Mandatory Provisions" and Section 6.6, "Alternative Compliance Path."
The simplified approach is an optional path for compliance when the following conditions are met:
- The building is two stories or fewer in height.
- Gross floor area is less than 25,000 ft2.
- Each HVAC system in the building complies with the requirements listed in Section 6.3.2.
The HVAC system must meet all of the following criteria:
- The system serves a single HVAC zone.
- The equipment must meet the variable flow requirements of Section 6.5.3.2.1.
- Cooling (if any) shall be provided by a unitary packaged or split-system air conditioner that is either air cooled or evaporatively cooled, with efficiency meeting the requirements shown in Table 6.8.1-1 (air conditioners), Table 6.8.1-2 (heat pumps), or Table 6.8.1-4 (packaged terminal and room air conditioners and heat pumps) for the applicable equipment category.
- The system shall have an air economizer meeting the requirements of Sections 6.5.1 and 6.4.3.12.
- Heating (if any) shall be provided by a unitary packaged or split-system heat pump that meets the applicable efficiency requirements shown in Table 6.8.1-2 (heat pumps) or Table 6.8.1-4 (packaged terminal and room air conditioners and heat pumps), a fuel-fired furnace that meets the applicable efficiency requirements shown in Table 6.8.1-5 (furnaces, duct furnaces, and unit heaters), an electric resistance heater, or a baseboard system connected to a boiler that meets the applicable efficiency requirements shown in Table 6.8.1-6 (boilers).
- The system shall meet the exhaust air energy recovery requirements of Section 6.5.6.1.
- The system shall be controlled by a manual changeover or dual set-point thermostat.
- If a heat pump equipped with auxiliary internal electric resistance heaters is installed, controls shall be provided that prevent supplemental heater operation when the heating load can be met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation is permitted during outdoor coil defrost cycles. The heat pump must be controlled by either (1) a digital or electronic thermostat designed for heat pump use that energizes auxiliary heat only when the heat pump has insufficient capacity to maintain set point or to warm up the space at a sufficient rate or (2) a multistage space thermostat and an outdoor air thermostat wired to energize auxiliary heat only on the last stage of the space thermostat and when outdoor air temperature is less than 40°F. Exception to 6.3.2(h)Heat pumps that comply with the following:
- Have a minimum efficiency regulated by NAECA.
- Meet the requirements in Table 6.8.1-2.
- Include all usage of internal electric resistance heating.
- The system controls shall not permit reheat or any other form of simultaneous heating and cooling for humidity control.
- Systems serving spaces other than hotel/motel guest rooms, and other than those requiring continuous operation, which have both a cooling or heating capacity greater than 15,000 Btu/h and a supply fan motor power greater than 0.75 hp, shall be provided with a time clock that (1) can start and stop the system under different schedules for seven different day types per week, (2) is capable of retaining programming and time setting during a loss of power for a period of at least ten hours, (3) includes an accessible manual override that allows temporary operation of the system for up to two hours, (4) is capable of and configured with temperature setback down to 55°F during off hours, and (5) is capable of capable of and configured with temperature setup to 90°F during off hours.
- Systems serving hotel/motel guest rooms shall comply with Section 6.4.3.3.5.
- Except for piping within manufacturers' units, HVAC piping shall be insulated in accordance with Tables 6.8.3-1 and 6.8.3-2. Insulation exposed to weather shall be suitable for outdoor service, e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation.
- Ductwork and plenums shall be insulated in accordance with Table 6.8.2 and shall be sealed in accordance with Section 6.4.4.2.1.
- Construction documents shall require a ducted system to be air balanced in accordance with industry accepted procedures.
- Outdoor air intake and exhaust systems shall meet the requirements of Section 6.4.3.4.
- Where separate heating and cooling equipment serves the same temperature zone, thermostats shall be interlocked to prevent simultaneous heating and cooling.
- Systems with a design supply air capacity greater than 10,000 cfm shall have optimum start controls.
- The system shall comply with the demand control ventilation requirements in Section 6.4.3.8, occupied-standby controls in Section 6.5.3.8, and the ventilation design requirements in Section 6.5.3.7.
- The system complies with the door switch requirements in Section 6.5.10.
Equipment shown in Tables 6.8.1-1 through 6.8.1-20 shall have a minimum performance at the specified rating conditions when tested in accordance with the specified test procedure. Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy all stated requirements unless otherwise exempted by footnotes in the table. Equipment covered under the Federal Energy Policy Act of 1992 (EPACT) shall have no minimum efficiency requirements for operation at minimum capacity or other than standard rating conditions. Equipment used to provide service water-heating functions as part of a combination system shall satisfy all stated requirements for the appropriate space heating or cooling category.
Tables are as follows:
- Table 6.8.1-1, "Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Efficiency Requirements"
- Table 6.8.1-2, "Electrically Operated Air-Cooled Unitary Heat Pumps—Minimum Efficiency Requirements"
- Table 6.8.1-3, "Water-Chilling Packages—Minimum Efficiency Requirements" (See Section 6.4.1.2 for water-cooled centrifugal water-chilling packages that are designed to operate at nonstandard conditions.)
- Table 6.8.1-4, "Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air Conditioner Heat Pumps—Minimum Efficiency Requirements"
- Table 6.8.1-5, "Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit Heaters—Minimum Efficiency Requirements"
- Table 6.8.1-6, "Gas- and Oil-Fired Boilers—Minimum Efficiency Requirements"
- Table 6.8.1-7, "Performance Requirements for Heat-Rejection Equipment—Minimum Efficiency Requirements"
- Table 6.8.1-8, "Electrically Operated Variable-Refrigerant-Flow Air Conditioners—Minimum Efficiency Requirements"
- Table 6.8.1-9, "Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements
- Table 6.8.1-10, "Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms"
- Table 6.8.1-11, "Commercial Refrigerators, Commercial Freezers, and Refrigeration—Minimum Efficiency Requirements"
- Table 6.8.1-12, "Vapor-Compression-Based Indoor Pool Dehumidifiers—Minimum Efficiency Requirements"
- Table 6.8.1-13, "Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, without Energy Recovery—Minimum Efficiency Requirements"
- Table 6.8.1-14, "Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, with Energy Recovery—Minimum Efficiency Requirements"
- Table 6.8.1-15, "Electrically Operated Water-Source Heat Pumps—Minimum Efficiency Requirements"
- Table 6.8.1-16, "Heat Pump and Heat Recovery Chiller Packages—Minimum Efficiency Requirement"
- Table 6.8.1-17, "Ceiling-Mounted Computer-Room Air Conditioners—Minimum Efficiency Requirements"
- Table 6.8.1-18, "Walk-In Cooler and Freezer Display Door Efficiency Requirements"
- Table 6.8.1-19, "Walk-In Cooler and Freezer Nondisplay Door Efficiency Requirements"
- Table 6.8.1-20, "Walk-In Cooler and Freezer Refrigeration System Efficiency Requirements"
Equipment not designed for operation at AHRI Standard 550/590 test conditions of 44.00°F leaving and 54.00°F entering chilled-fluid temperatures, and with 85.00°F entering and 94.30°F leaving condenser-fluid temperatures, shall have maximum full-load kW/ton (FL) and part-load rating requirements adjusted using the following equations:
FLadj = FL/Kadj
PLVadj = IPLV.IP/Kadj
Kadj = A × B
where
FL | = | full-load kW/ton kW/ton value from Table 6.8.1-3 |
FLadj | = | maximum full-load kW/ton rating, adjusted for nonstandard conditions |
IPLV.IP | = | IPLV.IP value from Table 6.8.1-3 |
PLVadj | = | maximum NPLV rating, adjusted for nonstandard conditions |
A | = | 0.00000014592 × (LIFT)4 — 0.0000346496 × (LIFT)3 + 0.00314196 × (LIFT)2 — 0.147199 × (LIFT) + 3.93073 |
B | = | 0.0015 × LvgEvap + 0.934 |
LIFT | = | LvgCond — LvgEvap |
LvgCond | = | full-load condenser leaving fluid temperature (°F) |
LvgEvap | = | full-load evaporator leaving temperature (°F) |
The FLadj and PLVadj values are only applicable for centrifugal chillers meeting all of the following full-load design ranges:
• 36.00°F ≤ LvgEvap ≤ 60.00°F
• LvgCond ≤ 115.00°F
• 20.00°F ≤ LIFT ≤ 80.00°F
Manufacturers shall calculate the FLadj and PLVadj before determining whether to label the chiller per Section 6.4.1.5. Compliance with 90.1-2007, 2010, 2013, 2016 or combinations thereof, shall be labeled on chillers within the scope of the standard.
Centrifugal chillers designed to operate outside of these ranges are not covered by this standard.
Example (Section 6.4.1.2.1)
Path A 600-ton centrifugal chiller Table 6.8.1-3:
FL | = | 0.5600 kW/ton |
IPLV.IP | = | 0.5000 kW/ton |
LvgCond | = | 91.16°F |
LvgEvap | = | 42.00°F |
LIFT | = | 91.16 — 42 = 49.16°F |
A | = | 0.00000014592 × (49.16)4 — 0.0000346496 × (49.16)3 + 0.00314196 × (49.16)2 — 0.147199 × (49.16) + 3.93073 = 1.02331 |
B | = | 0.0015 × 42.00 + 0.934 = 0.99700 |
Kadj | = | 1.02331 × 0.99700 = 1.02024 |
FLadj | = | 0.5600/1.02024 = 0.5489 kW/ton |
PLVadj | = | 0.5000/1.02024 = 0.4901 kW/ton |
Equipment with an evaporator leaving fluid temperature higher than 32.00°F and water-cooled positive displacement chilling packages with a condenser leaving fluid temperature below 115.00°F shall show compliance with Table 6.8.1-3 when tested or certified with water at standard rating conditions, per the referenced test procedure.
Large-diameter ceiling fans shall be rated in accordance with 10 CFR 430 Appendix U or AMCA 230. The following data shall be provided:
- Blade span (blade tip diameter)
- Rated airflow and power consumption at the maximum speed See Informative Appendix F for the U.S. Department of Energy requirements for U.S. applications.
The data provided shall meet one of the following requirements:
- It is determined by an independent laboratory.
- It is included in a database published by USDOE.
- It is certified under a program meeting the requirements of Section 6.4.1.5. Exception to 6.4.1.3.1Ceiling fans not covered in the scope of 10 CFR Part 430.
Equipment efficiency information supplied by manufacturers shall be verified by one of the following:
- Equipment covered under EPACT shall comply with U.S. Department of Energy certification requirements.
- If a certification program exists for a covered product, and it includes provisions for verification and challenge of equipment efficiency ratings then the product shall be listed in the certification program.
- If a certification program exists for a covered product, and it includes provisions for verification and challenge of equipment efficiency ratings, but the product is not listed in the existing certification program, the ratings shall be verified by an independent laboratory test report.
- If no certification program exists for a covered product, the equipment efficiency ratings shall be supported by data furnished by the manufacturer.
- Where components such as indoor or outdoor coils from different manufacturers are used, the system designer shall specify component efficiencies whose combined efficiency meets the minimum equipment efficiency requirements in Section 6.4.1.
Mechanical equipment that is not covered by the U.S. National Appliance Energy Conservation Act (NAECA) of 1987 shall carry a permanent label installed by the manufacturer stating that the equipment complies with the requirements of Standard 90.1.
Nonstandard-size packaged terminal air conditioners and heat pumps with existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in.2 shall be factory labeled as follows: Manufactured for nonstandard-size applications only: Not to be installed in new construction projects.
Pump differential pressure (head) for the purpose of sizing pumps shall be determined in accordance with generally accepted engineering standards and handbooks acceptable to the adopting authority. The pressure drop through each device and pipe segment in the critical circuit at design conditions shall be calculated.
The supply of heating and cooling energy to each zone shall be individually controlled by thermostatic controls responding to temperature within the zone. For the purposes of this section, a dwelling unit shall be permitted to be considered a single zone.
Exceptions to 6.4.3.1.1
Independent perimeter systems that are designed to offset only building envelope loads shall be permitted to serve one or more zones also served by an interior system, provided that
- the perimeter system includes at least one thermostatic control zone for each building exposure having walls facing only one orientation for 50 contiguous feet or more and
- the perimeter system heating and cooling supply is controlled by thermostatic controls located within the zones served by the system. Exterior walls and semiexterior walls are considered to have different orientations if the exposures they face differ by more than 45 degrees.
Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of at least 5°F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
Exceptions to 6.4.3.1.2
- Thermostats that require manual changeover between heating and cooling modes.
- Special occupancy or special applications where wide temperature ranges are not acceptable (such as retirement homes, process applications, museums, some areas of hospitals) and are approved by the authority having jurisdiction.
Where heating and cooling to a zone are controlled by separate zone thermostatic controls located within the zone, means (such as limit switches; mechanical stops; or, for DDC systems, software programming) shall be provided to prevent the heating set point from exceeding the cooling set point, minus any applicable proportional band.
Exceptions to 6.4.3.3
- HVAC systems intended to operate continuously.
- HVAC systems having a design heating capacity and cooling capacity less than 15,000 Btu/h that are equipped with readily accessible manual on/off controls.
HVAC systems shall be equipped with at least one of the following:
- Controls that can start and stop the system under different time schedules for seven different day types per week, are capable of retaining programming and time setting during loss of power for a period of at least ten hours, and include an accessible manual override or equivalent function that allows temporary operation of the system for up to two hours.
- An occupancy sensor that is capable of shutting the system off when no occupant is sensed for a period of up to 30 minutes.
- A manually operated timer capable of being adjusted to operate the system for up to two hours.
- An interlock to a security system that shuts the system off when the security system is activated. Exception to 6.4.3.3.1Residential occupancies may use controls that can start and stop the system under two different time schedules per week.
Heating systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the system as required to maintain zone temperatures above an adjustable heating set point at least 10°F below the occupied heating set point. Cooling systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the mechanical cooling system as required to maintain zone temperatures below an adjustable cooling set point at least 5°F above the occupied cooling set point or to prevent high space humidity levels.
Individual heating and cooling systems with setback controls and DDC shall have optimum start controls. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied set point, the outdoor temperature, and the amount of time prior to scheduled occupancy. Mass radiant floor slab systems shall incorporate floor temperature into the optimum start algorithm.
HVAC systems serving zones that are intended to operate or be occupied nonsimultaneously shall be divided into isolation areas. Zones may be grouped into a single isolation area provided it does not exceed 25,000 ft2 of conditioned floor area nor include more than one floor. Each isolation area shall be equipped with isolation devices capable of and configured to automatically shut off the supply of conditioned air and outdoor air to and exhaust air from the area. Each isolation area shall be controlled independently by a device meeting the requirements of Section 6.4.3.3.1. For central systems and plants, controls and devices shall be provided to allow stable system and equipment operation for any length of time while serving only the smallest isolation area served by the system or plant.
Exceptions to 6.4.3.3.4
Isolation devices and controls are not required for
- exhaust air and outdoor air connections to isolation zones when the fan system to which they connect is 5000 cfm and smaller;
- exhaust airflow from a single isolation zone of less than 10% of the design airflow of the exhaust system to which it connects; or
- zones intended to operate continuously or intended to be inoperative only when all other zones are inoperative.
HVAC systems serving hotel guest rooms shall be capable of and configured with three modes of temperature control.
- Rented and unoccupied. Within 20 minutes of all occupants leaving the guest room, HVAC set points shall be automatically raised by at least 4°F from the occupant set point in the cooling mode and automatically lowered by at least 4°F from the occupant set point in the heating mode.
- Unrented and unoccupied. HVAC set points shall be automatically reset to 80°F or higher in the cooling mode and to 60°F or lower in the heating mode. The HVAC set points in the unrented and unoccupied guest room modes shall be initiated within 16 hours of the guest room being continuously unoccupied or within 20 minutes of the guest room being continuously unoccupied where a networked guest room control system indicates the guest room is unrented.
- Occupied. HVAC set points shall return to their occupied set points once occupancy is sensed.
Exceptions to 6.4.3.3.5.1
- A networked guest room control system shall be permitted to return the thermostat set points to their default occupied set points 60 minutes prior to the time the room is scheduled to be occupied.
- Cooling for humidity control shall be permitted during rented and unoccupied or unrented and unoccupied periods.
Within 20 minutes of all occupants leaving the guest room, ventilation and exhaust fans shall automatically be turned off, or isolation devices serving each guest room shall automatically shut off the supply of outdoor air to the guest room and shut off exhaust air from the guest room.
Exception to 6.4.3.3.5.2
Guest room ventilation systems shall be permitted to have an automatic daily preoccupancy purge cycle that provides daily outdoor air ventilation during unrented periods at the design ventilation rate for 60 minutes or at a rate and duration equivalent to one air change.
Card key card controls shall be permitted to be used to indicate occupancy.
Stair and elevator shaft vents shall be equipped with motorized dampers that are capable of and configured to automatically close during normal building operation and are interlocked to open as required by fire and smoke detection systems.
All outdoor air intake and exhaust systems shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use. Outdoor air and exhaust/relief dampers shall be capable of and configured to automatically shut off during preoccupancy building warm-up, cooldown, and setback, except when the supply of outdoor air reduces energy costs or when outdoor air must be supplied to meet code requirements.
Exceptions to 6.4.3.4.2
- Nonmotorized (gravity back draft) dampers are acceptable for exhaust and relief in buildings less than three stories in height and for outdoor air intakes and exhaust and relief dampers in buildings of any height located in Climate Zones 0, 1, 2, and 3. Nonmotorized dampers for outdoor air intakes must be protected from direct exposure to wind.
- Nonmotorized dampers are acceptable in systems with a design outdoor air intake or exhaust capacity of 300 cfm or less.
- Dampers are not required in ventilation or exhaust systems serving unconditioned spaces.
- Dampers are not required in exhaust systems serving Type 1 kitchen exhaust hoods.
- Dampers are not required in systems intended to operate continuously.
Where outdoor air supply and exhaust/relief dampers are required by Section 6.4.3.4.1, they shall have a maximum leakage rate as indicated in Table 6.4.3.4.3.
Table 6.4.3.4.3 Maximum Damper Leakagea,b, cfm per ft2 at 1.0 in. water
Climate Zone | Outdoor Air Intake | Exhaust/Relief | ||
---|---|---|---|---|
Nonmotorizeda | Motorized | Nonmotorizedc | Motorized | |
0, 1, 2 | ||||
Any height | 20 | 4 | 20 | 4 |
3 | ||||
Any height | 20 | 10 | 20 | 10 |
4, 5B, 5C | ||||
Fewer than three stories | 20d | 10 | 20 | 10 |
Three or more stories | 20d | 10 | 20d | 10 |
5A, 6, 7, 8 | ||||
Fewer than three stories | 20d | 4 | 20 | 4 |
Three or more stories | 20d | 4 | 20d | 4 |
- When tested in accordance with AMCA Standard 500-D.
- Dampers smaller than 12 in. in height, width, or diameter need not be tested but shall be of the same design and construction as the smallest tested damper meeting the listed leakage rate requirement.
- Nonmotorized dampers smaller than 24 in. in height, width, or diameter may have a leakage rate of 40 cfm/ft2.
- Where allowed by Section 6.4.3.4.2, Exception 2.
Fans with motors greater than 0.75 hp shall have automatic controls complying with Section 6.4.3.3.1 that are capable of and configured to shut off fans when not required.
Exception to 6.4.3.4.4
HVAC systems intended to operate continuously.
Enclosed parking garage ventilation systems shall automatically detect contaminant levels and stage fans or modulate fan airflow rates to 50% or less of design capacity, provided acceptable contaminant levels are maintained.
Exceptions to 6.4.3.4.5
- Garages less than 30,000 ft2 with ventilation systems that do not use mechanical cooling or mechanical heating.
- Garages that have a garage area to ventilation system motor nameplate horsepower ratio that exceeds 1500 ft2/hp and do not use mechanical cooling or mechanical heating.
- Where not permitted by the authority having jurisdiction.
Heat pumps equipped with internal electric resistance heaters shall have controls that prevent supplemental heater operation when the heating load can be met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation is permitted during outdoor coil defrost cycles.
Exception to 6.4.3.5
Heat pumps whose minimum efficiency is regulated by NAECA and whose ratings meet the requirements shown in Table 6.8.1-2 and include all usage of internal electric resistance heating.
Humidistatic controls shall not use mechanical cooling to reduce the humidity below the lower of a dew point of 55°F or relative humidity of 60% in the coldest zone served by the system.
Exception to 6.4.3.6.1 and 6.4.3.6.2
Systems serving zones where specific humidity levels are required, such as museums and hospitals, and approved by the authority having jurisdiction or required by accreditation standards, and where humidistatic controls are capable of and configured to maintain a dead band of at least 10% relative humidity where no active humidification or dehumidification takes place.
Systems serving zones where humidity levels are required to be maintained with precision of not more than ±5% relative humidity to comply with applicable codes or accreditation standards or as approved by the authority having jurisdiction.
Lower humidity is permitted when operating mechanical cooling for temperature control.
Humidistatic controls shall not use fossil fuel or electricity to produce relative humidity above 30% in the warmest zone served by the system.
Exception to 6.4.3.6.1 and 6.4.3.6.2
Systems serving zones where specific humidity levels are required, such as museums and hospitals, and approved by the authority having jurisdiction or required by accreditation standards, and where humidistatic controls are capable of and configured to maintain a dead band of at least 10% relative humidity where no active humidification or dehumidification takes place.
Systems serving zones where humidity levels are required to be maintained with precision of not more than ±5% relative humidity to comply with applicable codes or accreditation standards or as approved by the authority having jurisdiction.
Where a zone is served by a system or systems with both humidification and dehumidification capability, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided capable of and configured to prevent simultaneous operation of humidification and dehumidification equipment.
Systems serving zones where humidity levels are required to be maintained with precision of not more than ±5% relative humidity to comply with applicable codes or accreditation standards or as approved by the authority having jurisdiction.
Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls capable of and configured to shut off the systems when outdoor air temperatures are above 40°F or when the conditions of the protected fluid will prevent freezing. Snow and ice melting systems shall include automatic controls capable of and configured to shut off the systems when the pavement temperature is above 50°F and no precipitation is falling, and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F so that the potential for snow or ice accumulation is negligible.
Demand control ventilation (DCV) is required for spaces larger than 500 ft2 and with a design occupancy for ventilation of ≥25 people per 1000 ft2 of floor area and served by systems with one or more of the following:
- Air economizer
- Automatic modulating control of outdoor air damper
- Design outdoor airflow greater than 3000 cfm
Exceptions to 6.4.3.8
- Systems with exhaust air energy recovery complying with, and where required by, Section 6.5.6.1.
- Multiple-zone systems without DDC of individual zones communicating with a central control panel.
- Systems with a design outdoor airflow less than 750 cfm.
- Spaces where >75% of the space design outdoor airflow is required for makeup air that is exhausted from the space or transfer air that is required for makeup air that is exhausted from other spaces.
- Spaces with one of the following occupancy categories as defined in ASHRAE Standard 62.1: correctional cells, daycare sickrooms, science labs, barbers, beauty and nail salons, and bowling alley seating.
Heating for vestibules and for air curtains with integral heating shall include automatic controls capable of and configured to shut off the heating system when outdoor air temperatures are above 45°F. Vestibule heating and cooling systems shall be controlled by a thermostat in the vestibule capable of and configured to limit heating to a maximum of 60°F and cooling to a minimum of 85°F.
Exception to 6.4.3.9
Heating or cooling provided by site-recovered energy or by transfer air that would otherwise be exhausted.
Direct digital control shall be required as follows.
DDC shall be provided in the applications and qualifications listed in Table 6.4.3.10.1.
Exception to 6.4.3.10.1
DDC is not required for systems using the simplified approach to compliance in accordance with Section 6.3.
Table 6.4.3.10.1 DDC Applications and Qualifications
Building Status | Application | Qualifications |
---|---|---|
New building | Air-handling system and all zones served by the system | Individual systems supplying more than three zones and with fan system bhp of 10 hp and larger |
Chilled-water plant and all coils and terminal units served by the system | Individual plants supplying more than three zones and with design cooling capacity of 300,000 Btu/h and larger | |
Hot-water plant and all coils and terminal units served by the system | Individual plants supplying more than three zones and with design heating capacity of 300,000 Btu/h and larger | |
Alteration or addition | Zone terminal unit such as VAV box | Where existing zones served by the same air-handling, chilled-water, or hot-water system have DDC |
Air-handling system or fan coil | Where existing air-handling systems and fan coils served by the same chilled- or hot-water plant have DDC | |
New air-handling system and all new zones served by the system | Individual systems with fan system bhp of 10 hp and larger and supplying more than three zones and more than 75% of zones are new | |
New or upgraded chilled-water plant | Where all chillers are new and plant design cooling capacity is 300,000 Btu/h and larger | |
New or upgraded hot-water plant | Where all boilers are new and plant design heating capacity is 300,000 Btu/h and larger |
Where DDC is required by Section 6.4.3.10.1, the DDC system shall be capable of and configured with all of the following, as required, to provide the control logic required in Section 6.5:
- Monitoring zone and system demand for fan pressure, pump pressure, heating, and cooling
- Transferring zone and system demand information from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers
- Automatically detecting those zones and systems that may be excessively driving the reset logic and generate an alarm or other indication to the system operator
- Readily allowing operator removal of zones from the reset algorithm
Where DDC is required by Section 6.4.3.10.1 for new buildings, the DDC system shall be capable of trending and graphically displaying input and output points.
For electric-motor-driven chilled-water plants in new buildings, or for new plants in existing buildings, measurement devices shall be installed and shall measure the electric energy use and efficiency of the chilled-water plant for
- water-cooled chilled-water plants larger than 1500 tons peak cooling capacity for Climate Zones 5 through 8, 3C, and 4C, and larger than 1000 tons peak cooling capacity for all other zones; and
- air-cooled chilled-water plants larger than 860 tons peak cooling capacity for Climate Zones 5 through 8, 3C, and 4C, and larger than 570 tons peak cooling capacity for all other zones.
The efficiency shall be calculated in kW/ton (see Informative Appendix E).
The electrical energy use efficiency shall be trended every 15 minutes and graphically displayed and include hourly, daily, monthly, and annual data. The system shall maintain all data collected for a minimum of 36 months.
Air-cooled direct-expansion cooling units listed in Tables 6.8.1-1 and 6.8.1-2, where an air economizer is installed in accordance with Section 6.5.1, shall include a fault detection and diagnostics (FDD) system complying with the following:
- The following temperature sensors shall be permanently installed to monitor system operation:
- Outdoor air
- Supply air
- Return air, where required for economizer control
- The system shall have the capability of displaying the value of each sensor.
- The FDD system or unit controls shall be capable of and configured to provide system status by indicating the following:
- Free cooling available
- Economizer enabled
- Compressor enabled
- Heating enabled
- Mixed-air low-limit cycle active
- The FDD system or unit controls shall have provisions to manually initiate each operating mode so that the operation of compressors, economizers, fans, and the heating system can be independently tested and verified.
- The FDD system shall be capable of and configured to detect the following faults:
- Air temperature sensor failure/fault
- Not economizing when the unit should be economizing
- Economizing when the unit should not be economizing
- Damper not modulating
- Excess outdoor air
- The FDD system shall be capable of and configured to report faults to a fault management application or DDC system accessible by operating or service personnel, or annunciated locally on zone thermostats.
Insulation required by this section shall be installed in accordance with industry-accepted standards (see Informative Appendix E). These requirements do not apply to HVAC equipment. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance and wind, but not limited to the following:
- Insulation exposed to weather shall be suitable for outdoor service, e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material.
- Insulation covering chilled-water piping, refrigerant suction piping, or cooling ducts located outside the conditioned space shall include a vapor retardant located outside the insulation (unless the insulation is inherently vapor retardant), all penetrations and joints of which shall be sealed.
All supply and return ducts and plenums installed as part of an HVAC air distribution system shall be thermally insulated in accordance with Table 6.8.2.
Exceptions to 6.4.4.1.2
- Factory-installed plenums, casings, or ductwork furnished as a part of HVAC equipment tested and rated in accordance with Section 6.4.1.
- Ducts or plenums located in heated spaces, semiheated spaces, or cooled spaces.
- For runouts less than 10 ft in length to air terminals or air outlets, the rated R-value of insulation need not exceed R-3.5.
- Backs of air outlets and outlet plenums exposed to unconditioned space or indirectly conditioned space with face areas exceeding 5 ft2 need not exceed R-2; those 5 ft2 or smaller need not be insulated.
Exceptions to 6.4.4.1.3
- Factory-installed piping within HVAC equipment tested and rated in accordance with Section 6.4.1.
- Piping that conveys fluids having a design operating temperature range between 60°F and 105°F, inclusive.
- Piping that conveys fluids that have not been heated or cooled through the use of fossil fuels or electricity (such as roof and condensate drains, domestic cold-water supply, and natural gas piping).
- Where heat gain or heat loss will not increase energy use (such as liquid refrigerant piping).
- In piping 1 in. or less, insulation is not required for strainers, control valves, and balancing valves.
All thermally ineffective panel surfaces of sensible heating panels, including U-bends and headers, shall be insulated with a minimum of R-3.5. Adjacent building envelope insulation counts toward this requirement.
The bottom surfaces of floor structures incorporating radiant heating shall be insulated with a minimum of R-3.5. Adjacent building envelope insulation counts toward this requirement.
Exception to 6.4.4.1.5
Ductwork and all plenums with pressure class ratings shall be constructed to Seal Class A. Openings for rotating shafts shall be sealed with bushings or other devices that seal off air leakage. Pressure-sensitive tape shall not be used as the primary sealant unless it has been certified to comply with UL-181A or UL-181B by an independent testing laboratory, and the tape is used in accordance with that certification. All connections shall be sealed, including but not limited to spin-ins, taps, other branch connections, access doors, access panels, and duct connections to equipment. Sealing that would void product listings is not required. Spiral lock seams need not be sealed. All duct pressure class ratings shall be designated in the design documents.
Ductwork that is designed to operate at static pressures in excess of 3 in. of water and all ductwork located outdoors shall be leak-tested according to industry-accepted test procedures (see Informative Appendix E). Representative sections totaling no less than 25% of the total installed duct area for the designated pressure class shall be tested. All sections shall be selected by the building owner or the designated representative of the building owner. Positive pressure leakage testing is acceptable for negative pressure ductwork. The maximum permitted duct leakage shall be
Lmax = CLP0.65
where
Lmax | = | maximum permitted leakage, cfm per 100 ft2 of duct surface area |
CL | = | 4, duct leakage class, cfm per 100 ft2 of duct surface area per in. of water0.65 |
P | = | test pressure, which shall be equal to the design duct pressure class rating, in. of water |
Site-assembled or site-constructed walk-in coolers and walk-in freezers shall conform to the following requirements:
- Shall be equipped with automatic door closers that firmly close walk-in doors that have been closed to within 1 in. of full closure. Exception to 6.4.5(a)Doors wider than 3 ft 9 in. or taller than 7 ft.
- Doorways shall have strip doors (curtains), spring-hinged doors, or other method of minimizing infiltration when doors are open.
- Walk-in coolers shall contain wall, ceiling, and door insulation of at least R-25 and at least R-32 for walk-in freezers. Exception to 6.4.5(c)Glazed portions of doors or structural members.
- Walk-in freezers shall contain floor insulation of at least R-28.
- Evaporator fan motors that are less than 1 hp and less than 460 V shall use electronically commutated motors (brushless direct-current motors) or three-phase motors.
- Lights shall use light sources with an efficacy of 40 lm/W or more, including ballast losses (if any). Light sources with lower may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people.
- Transparent reach-in doors for walk-in freezers, and windows in walk-in freezer doors, shall be of triple-pane glass, either filled with inert gas or with heat-reflective treated glass or vacuum insulating glazing. Informative Note to 6.4.5(g)For applications in the U.S., alternate innovative component technologies (e.g., vacuum insulating glazing for transparent reach-in doors) are allowable only if the manufacturer has obtained a waiver from USDOE.
- Transparent reach-in doors for walk-in coolers, and windows in walk-in cooler doors, shall be double-pane glass with heat-reflective treated glass and gas filled, or triple-pane glass, either filled with inert gas or with heat-reflective treated glass or vacuum insulating glazing. Informative Note to 6.4.5(h)For applications in the U.S., alternate innovative component technologies (e.g., vacuum insulating glazing for transparent reach-in doors) are allowable only if the manufacturer has obtained a waiver from USDOE.
- Antisweat heaters without antisweat heater controls shall have a total door rail, glass, and frame heater power draw of ≤7.1 W/ft2 of door opening for walk-in freezers and 3.0 W/ft2 of door opening for walk-in coolers.
- Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
- Condenser fan motors that are less than 1 hp shall use electronically commutated motors, permanent split-capacitor-type motors, or three-phase motors.
- All walk-in freezers shall incorporate temperature-based defrost termination control with a time limit default. The defrost cycle shall terminate first on an upper temperature limit breach and second upon a time limit breach. Exception to 6.4.5(l)Walk-in coolers and walk-in freezers combined in a single enclosure greater than 3000 ft2.
- Doors in walk-in coolers and walk-in freezers shall meet the requirements of Tables 6.8.1-18 and 6.8.1-19. Walk-in cooler and walk-in freezer refrigeration systems, except for walk-in process cooling refrigeration systems as defined in 10 CFR 431.302, shall meet the requirements of Table 6.8.1-20.
- All refrigerated display cases shall conform to Section 6.4.1.1 and Table 6.8.1-11.
- Lighting in refrigerated display cases and glass doors installed on walk-in coolers and walk-in freezers shall be controlled by one of the following:
- Automatic time-switch controls to turn off lights during nonbusiness hours: Timed overrides for display cases or walk-in coolers and walk-in freezers may be used to turn the lights on for up to one hour and shall automatically time out to turn the lights off.
- Motion sensor controls on each display case or walk-in door section that reduce lighting power by at least 50% within three minutes after the area within the sensor range is vacated.
- All low-temperature display cases shall incorporate temperature-based defrost termination control with a time-limit default. The defrost cycle shall terminate first on an upper temperature limit breach and second on a time limit breach.
- Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
Plate-type liquid-to-liquid heat exchangers shall be rated in accordance with AHRI 400. Section 12 contains a complete specification of the referenced test procedure.
Each cooling system shall include either an air economizer or fluid economizer meeting the requirements of Sections 6.5.1.1 through 6.5.1.5.
Exceptions to 6.5.1
Economizers are not required for the following systems:
- Individual fan-cooling units with a supply capacity less than the minimum listed in Table 6.5.1-1.
- Chilled-water cooling systems without a fan or that use induced airflow, where the total capacity of these systems is less than 1,000,000 Btu/h in Climate Zones 0, 1B, and 2 through 4; less than 1,400,000 Btu/h in Climate Zones 5 through 8; or any size in Climate Zone 1A.
- Systems that include nonparticulate air treatment as required by Section 6.2.1 in Standard 62.1.
- In hospitals and ambulatory surgery centers, where more than 75% of the air designed to be supplied by the system is to spaces that are required to be humidified above 35°F dewpoint temperature to comply with applicable codes or accreditation standards; in all other buildings, where more than 25% of the air designed to be supplied by the system is to spaces that are designed to be humidified above 35°F dew-point temperature to satisfy process application needs. This exception does not apply to computer rooms.
- Systems that include a condenser heat recovery system with a minimum capacity as defined in Section 6.5.6.2.2.
- Systems that serve residential spaces where the system capacity is less than five times the requirement listed in Table 6.5.1-1.
- Systems that serve spaces whose sensible cooling load at design conditions, excluding transmission and infiltration loads, is less than or equal to transmission and infiltration losses at an outdoor temperature of 60°F.
- Systems expected to operate fewer than 20 hours per week.
- Where the use of outdoor air for cooling will affect supermarket open refrigerated casework systems.
- For comfort cooling where the cooling efficiency meets or exceeds the efficiency improvement requirements in Table 6.5.1-2.
- Systems primarily serving computer rooms where
- the total design cooling load of all computer rooms in the building is less than 3,000,000 Btu/h and the building in which they are located is not served by a centralized chilled water plant;
- the room total design cooling load is less than 600,000 Btu/h and the building in which they are located is served by a centralized chilled water plant;
- the local water authority does not allow cooling towers; or
- less than 600,000 Btu/h of computer-room cooling equipment capacity is being added to an existing building.
- Dedicated systems for computer rooms, where a minimum of 75% of the design load serves
- those spaces classified as an essential facility,
- those spaces having a design of Tier IV as defined by ANSI/TIA-942,
- those spaces classified under NFPA 70 Article 708—Critical Operations Power Systems (COPS), or
- those spaces where core clearing and settlement services are performed such that their failure to settle pending financial transactions could present systemic risk as described in "The Interagency Paper on Sound Practices to Strengthen the Resilience of the U.S. Financial System" (April 7, 2003).
Table 6.5.1-1 Minimum Fan-Cooling Unit Size for which an Economizer Is Required
Climate Zone | Cooling Capacity for which an Economizer Is Required |
---|---|
0A, 0B, 1A, 1B | No economizer requirement |
2A, 2B, 3A, 4A, 5A, 6A, 3B, 3C, 4B, 4C, 5B, 5C, 6B, 7, 8 | ≥54,000 Btu/h |
Table 6.5.1-2 Eliminate Required Economizer for Comfort Cooling by Increasing Cooling Efficiency
Climate Zone | Efficiency Improvementa |
---|---|
2A | 17% |
2B | 21% |
3A | 27% |
3B | 32% |
3C | 65% |
4A | 42% |
4B | 49% |
4C | 64% |
5A | 49% |
5B | 59% |
5C | 74% |
6A | 56% |
6B | 65% |
7 | 72% |
8 | 77% |
a. If a unit is rated with an IPLV, IEER, or SEER, then to eliminate the required economizer, the minimum cooling efficiency of the HVAC unit must be increased by the percentage shown. If the HVAC unit is only rated with a full-load metric like EER cooling then these must be increased by the percentage shown.
Air economizer systems shall be capable of and configured to modulate outdoor air and return air dampers to provide up to 100% of the design supply air quantity as outdoor air for cooling.
Economizer controls shall be capable of and configured to sequence the dampers with the mechanical cooling equipment and shall not be controlled by only mixed-air temperature.
Exception to 6.5.1.1.2
The use of mixed-air temperature limit control shall be permitted for systems controlled from space temperature (such as single-zone systems).
All air economizers shall be capable of and configured to automatically reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy use. High-limit shutoff control types and associated set points for specific climate zones shall be chosen from Table 6.5.1.1.3.
Control Type | Allowed Only in Climate Zone at Listed Set Point | Required High-Limit Set Points (Economizer Off when): | |
---|---|---|---|
Equation | Description | ||
Fixed dry-bulb temperature | 0B, 1B, 2B, 3B, 3C, 4B, 4C, 5B, 5C, 6B, 7, 8 | TOA > 75°F | Outdoor air temperature exceeds 75°F |
5A, 6A | TOA > 70°F | Outdoor air temperature exceeds 70°F | |
0A, 1A, 2A, 3A, 4A, | TOA > 65°F | Outdoor air temperature exceeds 65°F | |
Differential dry-bulb temperature | 0B, 1B, 2B, 3B, 3C, 4B, 4C, 5A, 5B, 5C, 6A, 6B, 7, 8 | TOA > TRA | Outdoor air temperature exceeds return air temperature |
Fixed enthalpy with fixed dry-bulb temperature | All | hOA > 28 Btu/lba or TOA > 75°F |
Outdoor air enthalpy exceeds 28 Btu/lba of dry aira or outdoor air temperature exceeds 75°F |
Differential enthalpy with fixed dry-bulb temperature | All | hOA > hRA or TOA> 75°F |
Outdoor air enthalpy exceeds return air enthalpy or outdoor air temperature exceeds 75°F |
- At altitudes substantially different than sea level, the fixed enthalpy limit shall be set to the enthalpy value at 75°F and 50% rh. As an example, at approximately 6000 ft elevation, the fixed enthalpy limit is approximately 30.7 Btu/lb.
- Devices with selectable rather than adjustable set points shall be capable of being set to within 2°F and 2 Btu/lb of the set point listed.
Exhaust/relief, and outdoor air dampers shall meet the requirements of Table 6.4.3.4.3. Return dampers shall meet the requirements of motorized exhaust/relief dampers in Table 6.4.3.4.3.
Exception to 6.5.1.1.4
Exhaust/relief and outdoor air intake dampers on systems intended to operate continuously.
Systems shall provide a means to relieve excess outdoor air during air economizer operation to prevent overpressurizing the building. The relief air outlet shall be located so as to avoid recirculation into the building.
Outdoor air, return air, mixed air, and supply air sensors shall be calibrated within the following accuracies:
- Dry-bulb and wet-bulb temperatures shall be accurate to ±2°F over the range of 40°F to 80°F.
- Enthalpy and the value of a differential enthalpy sensor shall be accurate to ±3 Btu/lb over the range of 20 to 36 Btu/lb.
- Relative humidity shall be accurate to ±5% over the range of 20% to 80% rh.
Fluid economizer systems shall be capable of providing up to 100% of the expected system cooling load at outdoor air temperatures of 50°F dry bulb/45°F wet bulb and below.
Exceptions to 6.5.1.2.1
- Systems primarily serving computer rooms in which 100% of the expected system cooling load at the dry-bulb and wet-bulb temperatures listed in Table 6.5.1.2.1 is met with water-cooled fluid economizers.
- Systems primarily serving computer rooms in which 100% of the expected system cooling load at the dry-bulb temperatures listed in Table 6.5.1.2.1 is met with air-cooled fluid economizers.
- Systems where dehumidification requirements cannot be met using outdoor air temperatures of 50°F dry-bulb/45°F wet-bulb and where 100% of the expected system cooling load at 45°F dry-bulb/40°F wet-bulb is met with water-cooled fluid economizers.
Climate Zone | Water Cooled | Air Cooled | ||
---|---|---|---|---|
Dry Bulb, °F | Wet Bulb, °F | Dry Bulb, °F | ||
0 | A | NR | NR | NR |
0 | B | NR | NR | NR |
1 | A | NR | NR | NR |
1 | B | NR | NR | NR |
2 | A | 40.0 | 35.0 | 30.0 |
2 | B | 35.0 | 30.0 | 30.0 |
3 | A | 40.0 | 35.0 | 25.0 |
3 | B | 30.0 | 25.0 | 25.0 |
3 | C | 30.0 | 25.0 | 30.0 |
4 | A | 40.0 | 35.0 | 25.0 |
4 | B | 30.0 | 25.0 | 25.0 |
4 | C | 30.0 | 25.0 | 25.0 |
5 | A | 40.0 | 35.0 | 20.0 |
5 | B | 30.0 | 25.0 | 20.0 |
5 | C | 30.0 | 25.0 | 25.0 |
6 | A | 35.0 | 30.0 | 20.0 |
6 | B | 30.0 | 25.0 | 20.0 |
7 | 30.0 | 25.0 | 20.0 | |
8 | 30.0 | 25.0 | 20.0 |
NR—Not required
Precooling coils and fluid-to-water heat exchangers used as part of a fluid economizer system shall either have a water-side pressure drop of less than 15 ft of water, or a secondary loop shall be created so that the coil or heat exchanger pressure drop is not seen by the circulating pumps when the system is in the normal cooling (noneconomizer) mode.
Economizer systems shall be integrated with the mechanical cooling system and be capable of and configured to provide partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. Controls shall not false load the mechanical cooling systems by limiting or disabling the economizer or by any other means, such as hot-gas bypass, except at the lowest stage of mechanical cooling.
Units that include an air economizer shall comply with the following:
- Unit controls shall have the mechanical cooling capacity control interlocked with the air economizer controls such that the outdoor air damper is at the 100% open position when mechanical cooling is on, and the outdoor air damper does not begin to close to prevent coil freezing due to minimum compressor run time until the leaving air temperature is less than 45°F.
- DX units with a rated capacity no less than 65,000 Btu/h that control the capacity of the mechanical cooling directly based on occupied space temperature shall have a minimum of two stages of mechanical cooling capacity.
- All other DX units, including those that control space temperature by modulating the airflow to the space, shall comply with the requirements of Table 6.5.1.3.
Table 6.5.1.3 DX Cooling Stage Requirements for Modulating Airflow Units
Rating Capacity, Btu/h | Minimum Number of Mechanical Cooling Stages | Minimum Compressor Displacementa |
---|---|---|
≥65,000 and <240,000 | 3 | ≤35% of full load |
≥240,000 | 4 | ≤25% full load |
a. For mechanical cooling stage control that does not use variable compressor displacement the percent displacement shall be equivalent to the mechanical cooling capacity reduction evaluated at the full load rating conditions for the compressor.
Systems with hydronic cooling and humidification systems designed to maintain inside humidity at a dew-point temperature greater than 35°F shall use a fluid economizer if an economizer is required by Section 6.5.1.
Zone thermostatic control shall prevent
- reheating;
- recooling;
- mixing or simultaneously supplying air that has been previously mechanically heated and air that has been previously cooled, either by mechanical cooling or by economizer systems; and
- other simultaneous operation of heating and cooling systems to the same zone.
Exceptions to 6.5.2.1
- Zones for which the volume of air that is reheated, recooled, or mixed is less than the larger of the following:
- For systems without DDC, 30% of the zone design peak supply.
- For systems with DDC, the minimum primary airflow rate required to meet the Simplified Procedure ventilation requirements of ASHRAE Standard 62.1 for the zone, permitted to be the average airflow rate as allowed by ASHRAE Standard 62.1.
- Any higher rate that can be demonstrated, to the satisfaction of the authority having jurisdiction, to reduce overall system annual energy use by offsetting reheat/recool energy losses through a reduction in outdoor air intake for the system.
- The airflow rate required to comply with applicable codes or accreditation standards, such as pressure relationships or minimum air change rates.
- Zones with DDC that comply with all of the following:
- The airflow rate in dead band between heating and cooling does not exceed the larger of the following:
- The minimum primary airflow rate required to meet the Simplified Procedure ventilation requirements of ASHRAE Standard 62.1 for the zone, permitted to be the average airflow rate as allowed by ASHRAE Standard 62.1.
- Any higher rate that can be demonstrated, to the satisfaction of the authority having jurisdiction, to reduce overall system annual energy use by offsetting reheat/recool energy losses through a reduction in outdoor air intake.
- The airflow rate required to comply with applicable codes or accreditation standards, such as pressure relationships or minimum air change rates.
- The airflow rate that is reheated, recooled, or mixed shall be less than 50% of the zone design peak supply rate.
- The first stage of heating consists of modulating the zone supply air temperature set point up to a maximum set point while the airflow is maintained at the dead band flow rate.
- The second stage of heating consists of modulating the airflow rate from the dead band flow rate up to the heating maximum flow rate.
- The airflow rate in dead band between heating and cooling does not exceed the larger of the following:
- Laboratory exhaust systems that comply with Section 6.5.7.3.
- Zones where at least 75% of the energy for reheating or for providing warm air in mixing systems is provided from site-recovered energy (including condenser heat) or site-solar energy.
Where reheating is permitted by other parts of this standard, zones that have both supply and return/exhaust air openings greater than 6 ft above floor shall not supply heating air more than 20°F above the space temperature set point.
Exceptions to 6.5.2.1.1
- Laboratory exhaust systems that comply with Section 6.5.7.3.
- During preoccupancy building warm-up and setback.
Systems that use a common distribution system to supply both heated and chilled water are acceptable provided all of the following are met:
- The system is designed to allow a dead band between changeover from one mode to the other of at least 15°F outdoor air temperature.
- The system is designed to operate and is provided with controls that will allow operation in one mode for at least four hours before changing over to the other mode.
- Reset controls are provided that allow heating and cooling supply temperatures at the changeover point to be no more than 30°F apart.
Hydronic heat pumps connected to a common heat pump water loop with central devices for heat rejection (e.g., cooling tower) and heat addition (e.g., boiler) shall have the following:
- Controls that are capable of and configured to provide a heat pump water supply temperature dead band of at least 20°F between initiation of heat rejection and heat addition by the central devices (e.g., tower and boiler).
- For Climate Zones 3 through 8, if a closed-circuit cooling tower (fluid cooler) is used, either an automatic valve shall be installed to bypass all but a minimal flow of water around the tower (for freeze protection) or low-leakage positive closure dampers shall be provided. If an open-circuit cooling tower is used directly in the heat pump loop, an automatic valve shall be installed to bypass all heat pump water flow around the tower. If an open-circuit cooling tower is used in conjunction with a separate heat exchanger to isolate the tower from the heat pump loop then heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop.
Exception to 6.5.2.2.3
Where a system loop temperature optimization controller is used to determine the most efficient operating temperature based on real-time conditions of demand and capacity, dead bands of less than 20°F shall be allowed.
Where humidity controls are provided, such controls shall prevent reheating, mixing of hot and cold airstreams, or other means of simultaneous heating and cooling of the same airstream.
Exceptions to 6.5.2.3
- The system is capable of and configured to reduce supply air volume to 50% or less of the design airflow rate or the minimum outdoor air ventilation rate specified in ASHRAE Standard 62.1 or other applicable federal, state, or local code or recognized standard, whichever is larger, before simultaneous heating and cooling takes place.
- The individual fan cooling unit has a design cooling capacity of 65,000 Btu/h or less and is capable of and configured to unload to 50% capacity before simultaneous heating and cooling takes place.
- The individual mechanical cooling unit has a design cooling capacity of 40,000 Btu/h or less. An individual mechanical cooling unit is a single system comprising a fan or fans and a cooling coil capable of providing mechanical cooling.
- Systems serving spaces where specific humidity levels are required to satisfy process application needs, such as vivariums; museums; surgical suites; pharmacies; and buildings with refrigerating systems, such as supermarkets, refrigerated warehouses, and ice arenas, and where the building includes site-recovered energy or site-solar energy that provide energy equal to at least 75% of the annual energy for reheating or for providing warm air in mixing systems. This exception does not apply to computer rooms.
- At least 90% of the annual energy for reheating or for providing warm air in mixing systems is provided from site-recovered energy (including condenser heat) or site-solar energy.
- Systems where the heat added to the airstream is the result of the use of a desiccant system, and 75% of the heat added by the desiccant system is removed by a heat exchanger, either before or after the desiccant system, with energy recovery.
Humidifiers with preheating jackets mounted in the airstream shall be provided with an automatic valve to shut off preheat when humidification is not required.
Humidification system dispersion-tube hot surfaces in the airstreams of ducts or air-handling units shall be insulated with a product with an insulating value of at least R-0.5.
Exception to 6.5.2.4.2
Systems where mechanical cooling, including economizer operation, does not occur simultaneously with humidification.
Preheat coils shall have controls that stop their heat output whenever mechanical cooling, including economizer operation, is occurring.
Units that provide ventilation air to multiple zones and operate in conjunction with zone heating and cooling systems shall not use heating or heat recovery to warm supply air above 60°F when representative building loads or outdoor air temperature indicate that the majority of zones require cooling.
Each HVAC system having a total fan system motor nameplate horsepower exceeding 5 hp at fan system design conditions shall not exceed the allowable fan system motor nameplate horsepower (Option 1) or fan system bhp (Option 2) as shown in Table 6.5.3.1-1. This includes supply fans, return/relief fans, exhaust fans, and fan-powered terminal units associated with systems providing heating or cooling capability that operate at fan system design conditions. Single-zone VAV systems shall comply with the constant-volume fan power limitation.
Exceptions to 6.5.3.1.1
- Hospital, vivarium, and laboratory systems that use flow control devices on exhaust and/or return to maintain space pressure relationships necessary for occupant health and safety or environmental control may use variable-volume fan power limitation.
- Individual exhaust fans with motor nameplate horsepower of 1 hp or less.
Table 6.5.3.1-1 Fan Power Limitationa
Limit | Constant Volume | Variable Volume | |
---|---|---|---|
Option 1: Fan system motor nameplate hp | Allowable motor nameplate hp | hp ≤ cfmS × 0.0011 | hp ≤ cfmS × 0.0015 |
Option 2: Fan system bhp | Allowable fan system bhp | bhp ≤ cfmS × 0.00094 + A | bhp ≤ cfmS × 0.0013 + A |
a. where
cfmS | = | maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute |
hp | = | maximum combined motor nameplate horsepower |
bhp | = | maximum combined fan-brake horsepower |
A | = | sum of (PD × cfmD/4131) |
where | ||
PD | = | each applicable pressure drop adjustment from Table 6.5.3.1-2 in in. of water |
cfmD | = | the design airflow through each applicable device from Table 6.5.3.1-2 in cubic feet per minute |
Table 6.5.3.1-2 Fan Power Limitation Pressure Drop Adjustment
Device | Adjustment |
---|---|
Credits | |
Return or exhaust systems required by code or accreditation standards to be fully ducted, or systems required to maintain air pressure differentials between adjacent rooms. | 0.5 in. of water (2.15 in. of water for laboratory and vivarium systems) |
Return and/or exhaust airflow control devices | 0.5 in. of water |
Exhaust filters, scrubbers, or other exhaust treatment | The pressure drop of device calculated at fan system design condition |
Particulate Filtration Credit: MERV 9 through 12 | 0.5 in. of water |
Particulate Filtration Credit: MERV 13 through 15 | 0.9 in. of water |
Particulate Filtration Credit: MERV 16 and greater and electronically enhanced filters | Pressure drop calculated at 2× clean filter pressure drop at fan system design condition |
Carbon and other gas-phase air cleaners | Clean filter pressure drop at fan system design condition |
Biosafety cabinet | Pressure drop of device at fan system design condition |
Energy recovery device, other than coil runaround loop | For each airstream [(2.2 × Enthalpy Recovery Ratio) — 0.5] in. of water |
Coil runaround loop | 0.6 in. of water for each airstream |
Evaporative humidifier/cooler in series with another cooling coil | Pressure drop of device at fan system design condition |
Sound attenuation section (fans serving spaces with design background noise goals below NC35) | 0.15 in. of water |
Exhaust system serving fume hoods | 0.35 in. of water |
Laboratory and vivarium exhaust systems in high-rise buildings | 0.25 in. of water/100 ft of vertical duct exceeding 75 ft |
Deductions | |
Systems without central cooling device | —0.6 in. of water |
Systems without central heating device | —0.3 in. of water |
Systems with central electric resistance heat | —0.2 in. of water |
- For each fan less than 6 bhp, the selected fan motor shall be no larger than the first available motor with a nameplate rating greater than 1.5 times the bhp.
- For each fan 6 bhp and larger, the selected fan motor shall be no larger than the first available motor with a nameplate rating greater than 1.3 times the bhp.
The bhp must be indicated on the design documents to allow for compliance verification by the building official.
Exceptions to 6.5.3.1.2
- Motors equipped with electronic speed control devices to vary the fan airflow as a function of load.
- Systems complying with Section 6.5.3.1.1, Option 1.
- Fans with motor nameplate horsepower of less than 1 hp.
- Fans with a fan nameplate electrical input power of less than 0.89 kW.
Each fan and fan array shall have a fan energy index (FEI) of 1.00 or higher. Each fan and fan array used for a variable-air-volume system that meets the requirements of Section 6.5.3.2.1 shall have an FEI of 0.95 or higher. The FEI for fan arrays shall be calculated in accordance with AMCA 208 Annex C.
Exceptions to 6.5.3.1.3
- Fans that are not embedded fans with a motor nameplate horsepower of less than 1.0 hp or with a fan nameplate electrical input power of less than 0.89 kW.
- Embedded fans and fan arrays with a combined motor nameplate horsepower of 5 hp or less or with a fan system electrical input power of 4.1 kW or less.
- Embedded fans that are part of equipment listed under Section 6.4.1.1.
- Embedded fans included in equipment bearing a third-party-certified seal for air or energy performance of the equipment package.
- Ceiling fans.
- Fans used for moving gases at temperatures above 482°F.
- Fans used for operation in explosive atmospheres.
- Reversible fans used for tunnel ventilation.
- Fans outside the scope of AMCA 208.
- Fans that are intended to only operate during emergency conditions.
Each cooling system listed in Table 6.5.3.2.1 shall be designed to vary the supply fan airflow as a function of load and shall comply with the following requirements:
- DX and chilled-water cooling units that control the capacity of the mechanical cooling directly based on space temperature shall have a minimum of two stages of fan control. Low or minimum speed shall not exceed 66% of full speed. At low or minimum speed, the fan system shall draw no more than 40% of the fan power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation.
- All other units, including DX cooling units and chilled-water units that control the space temperature by modulating the airflow to the space, shall have modulating fan control. Minimum speed shall not exceed 50% of full speed. At minimum speed, the fan system shall draw no more than 30% of the power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation.
- Units that include an air economizer to meet the requirements of Section 6.5.1 shall have a minimum of two speeds of fan control during economizer operation.
Exceptions to 6.5.3.2.1
- Modulating fan control is not required for chilled-water and evaporative cooling units with <1 hp fan motors if the units are not used to provide ventilation air and if the indoor fan cycles with the load.
- If the volume of outdoor air required to meet the ventilation requirements of Standard 62.1 at low speed exceeds the air that would be delivered at the speed defined in Section 6.5.3.2.1(a) or 6.5.3.2.1(b) then the minimum speed shall be selected to provide the required ventilation air.
Table 6.5.3.2.1 Fan Airflow Control
Cooling System Type | Fan Motor Size, hp | Mechanical Cooling Capacity, Btu/h |
---|---|---|
DX cooling | Any | ≥65,000 |
Chilled-water and evaporative cooling | ≥1/4 | Any |
Static pressure sensors used to control VAV fans shall be located such that the controller set point is no greater than 1.2 in. of water. If this results in the sensor being located downstream of major duct splits, sensors shall be installed in each major branch to ensure that static pressure can be maintained in each.
Exception to 6.5.3.2.2
Systems complying with Section 6.5.3.2.3.
For multiple-zone VAV systems having a total fan system motor nameplate horsepower exceeding 5 hp with DDC of individual zones reporting to the central control panel, static pressure set point shall be reset based on the zone requiring the most pressure; i.e., the set point is reset lower until one zone damper is nearly wide open. Controls shall provide the following:
Return and relief fans used to meet Section 6.5.1.1.5 shall comply with all of the following:
- Relief air rate shall be controlled to maintain building pressure either directly, or indirectly through differential supply-return airflow tracking. Systems with constant speed or multispeed supply fans shall also be allowed to control the relief system based on outdoor air damper position.
- Fans shall have variable-speed control or other devices that will result in total return/relief fan system demand of no more than 30% of total design power at 50% of total design fan flow.
Exceptions to 6.5.3.2.4
- Return or relief fans with total motor size less than or equal to 0.5 hp.
- Staged relief fans with a minimum of four stages.
Multiple-zone VAV systems with DDC of individual zone boxes reporting to a central control panel shall include means to automatically reduce outdoor air intake flow below design rates in response to changes in system ventilation efficiency as defined by Appendix A of ASHRAE Standard 62.1.
Exceptions to 6.5.3.3
- VAV systems with zonal transfer fans that recirculate air from other zones without directly mixing it with outdoor air, dual-duct dual-fan VAV systems, and VAV systems with fan-powered terminal units.
- Systems where total design exhaust airflow is more than 70% of total design outdoor air intake flow requirements.
Multiple zone HVAC systems shall include controls that are capable of and configured to automatically reset the supply air temperature in response to representative building loads, or to outdoor air temperature. The controls shall reset the supply air temperature at least 25% of the difference between the design supply air temperature and the design room air temperature. Controls that adjust the reset based on zone humidity are allowed in Climate Zones 0B, 1B, 2B, 3B, 3C, and 4 through 8. HVAC zones that are expected to experience relatively constant loads shall have maximum airflow designed to accommodate the fully reset supply air temperature.
HVAC zones that are expected to experience relatively constant loads typically include electronic equipment rooms and interior zones.
Exceptions to 6.5.3.5
- Systems in Climate Zones 0A, 1A, and 3A with less than 3000 cfm of design outdoor air.
- Systems in Climate Zone 2A with less than 10,000 cfm of design outdoor air.
- Systems in Climate Zones 0A, 1A, 2A, and 3A with at least 80% outdoor air and employing exhaust air energy recovery complying with Section 6.5.6.1.
- Systems that prevent reheating, recooling, or mixing of heated and cooled supply air.
- Systems in which at least 75% of the energy for reheating (on an annual basis) is from site recovered energy or site-solar energy.
In Climate Zones 0A, 1A, 2A, and 3A, the system design shall allow supply air temperature reset while dehumidification is provided. When dehumidification control is active, air economizers shall be locked out.
Examples of HVAC systems that can allow supply air temperature reset while dehumidifying include cooling of outdoor air with a separate cooling coil, bypassing return air around the cooling coil, a dedicated outdoor air system, and series energy recovery.
Motors for fans that are 1/12 hp or greater and less than 1 hp shall be electronically commutated motors or shall have a minimum motor efficiency of 70% when rated in accordance with DOE 10 CFR 431. These motors shall also have the means to adjust motor speed for either balancing or remote control. Belt-driven fans may use sheave adjustments for airflow balancing in lieu of a varying motor speed.
Exceptions to 6.5.3.6
- Motors in the airstream within fan-coils and terminal units that operate only when providing heating to the space served.
- Motors installed in space conditioning equipment certified under Section 6.4.1.
- Motors covered by Table 10.8-3 or Table 10.8-4.
The required minimum outdoor air rate is the larger of the minimum outdoor air rate or the minimum exhaust air rate required by Standard 62.1, Standard 170, or applicable codes or accreditation standards. Outdoor air ventilation systems shall comply with one of the following:
- Design minimum system outdoor air provided shall not exceed 135% of the required minimum outdoor air rate.
- Dampers, ductwork, and controls shall be provided that allow the system to supply no more than the required minimum outdoor air rate with a single set-point adjustment.
- The system includes exhaust air energy recovery complying with Section 6.5.6.1.
Zones serving only rooms that are required to have automatic partial OFF or automatic full OFF lighting controls per Section 9.4.1.1, where the ASHRAE Standard 62.1 occupancy category permits ventilation air to be reduced to zero when the space is in occupied-standby mode, and when using the Ventilation Rate Procedure, shall meet the following within five (5) minutes of all rooms in that zone entering occupied-standby mode.
Boiler systems with design input of at least 1,000,000 Btu/h shall comply with the turndown ratio specified in Table 6.5.4.1.
The system turndown requirement shall be met through the use of multiple single-input boilers, one or more modulating boilers, or a combination of single-input and modulating boilers.
Table 6.5.4.1 Boiler Turndown
Boiler System Design Input, Btu/h | Minimum Turndown Ratio |
---|---|
≥1,000,000 and ≤5,000,000 | 3 to 1 |
>5,000,000 and ≤10,000,000 | 4 to 1 |
>10,000,000 | 5 to 1 |
Chilled- and hot-water distribution systems that include three or more control valves designed to modulate or step open and close as a function of load shall be designed for variable fluid flow and shall be capable of and configured to reduce pump flow rates to no more than the larger of 25% of the design flow rate or the minimum flow required by the heating/cooling equipment manufacturer for the proper operation of equipment. Individual or parallel pumps serving variable-flow heating-water or chilled-water systems, where the nameplate horsepower of the motor or combined parallel motors is at least the power shown in Table 6.5.4.2, shall have controls or devices that will result in pump motor demand of no more than 30% of design wattage at 50% of design water flow. The controls or devices shall be controlled as a function of desired flow or to maintain a minimum required differential pressure. Differential pressure shall be measured at or near the most remote heat exchanger or the heat exchanger requiring the greatest differential pressure. The differential pressure set point shall be no more than 110% of that required to achieve design flow through the heat exchanger. Where differential pressure control is used to comply with this section and DDC systems are used, the set point shall be reset downward based on valve positions until one valve is nearly wide open.
Exceptions to 6.5.4.2
- Differential pressure set-point reset is not required where valve position is used to comply with Section 6.5.4.4.
- Variable-pump flow control is not required on heating-water pumps where more than 50% of annual heat is generated by an electric boiler.
- Variable flow is not required for primary pumps in a primary/secondary system.
- Variable flow is not required for a coil pump provided for freeze protection.
- Variable flow is not required for heat recovery coil runaround loops.
Chilled-Water Pumps in These Climate Zones | Heating Water Pumps in These Climate Zones | Motor Nameplate Horsepower |
---|---|---|
0A, 0B, 1A, 1B, 2B | NR | ≥2 hp |
2A, 3B | NR | ≥3 hp |
3A, 3C, 4A, 4B | 7, 8 | ≥5 hp |
4C, 5A, 5B, 5C, 6A, 6B | 3C, 5A, 5C, 6A, 6B | ≥7.5 hp |
4A, 4C, 5B | ≥10 hp | |
7, 8 | 4B | ≥15 hp |
2A, 2B, 3A, 3B | ≥25 hp | |
1B | ≥100 hp | |
0A, 0B, 1A | ≥200 hp |
When a chilled-water plant includes more than one chiller, provisions shall be made so that all fluid flow through the chiller is automatically shut off when the chiller is shut down. Chillers piped in series for the purpose of increased temperature differential shall be considered as one chiller. Where constant-speed chilled-water or condenser water pumps are used to serve multiple chillers, the number of pumps shall be no less than the number of chillers and staged on and off with the chillers.
When a boiler plant includes more than one boiler, provisions shall be made so that the flow through the boiler is automatically shut off when the boiler is shut down. Where constant-speed hot-water pumps are used to serve multiple boilers, the number of pumps shall be no less than the number of boilers and staged on and off with the boilers.
Chilled- and hot-water systems with a design capacity exceeding 300,000 Btu/h supplying chilled or heated water to comfort conditioning systems shall include controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature. Where DDC is used to control valves, the set point shall be reset based on valve positions until one valve is nearly wide open or set-point limits of the system equipment or application have been reached.
Exceptions to 6.5.4.4
- Where chilled-water supply is already cold, such as chilled water supplied from a district cooling or thermal energy storage system, such that blending would be required to achieve the reset chilled-water supply temperature.
- Where a specific temperature is required for a process application.
- Water temperature reset is not required where valve position is used to comply with Section 6.5.4.2.
Each hydronic heat pump and water-cooled unitary air conditioner shall have a two-position automatic valve interlocked to shut off water flow when the compressor is off.
Exception to 6.5.4.5.1
Units employing a fluid economizer.
Hydronic heat pumps and water-cooled unitary air conditioners having a total pump system power exceeding 5 hp shall have controls and/or devices (such as variable-speed control) that will result in pump motor demand of no more than 30% of design wattage at 50% of design water flow.
All chilled-water and condenser-water piping shall be designed such that the design flow rate in each piping segment shall not exceed the values listed in Table 6.5.4.6 for the appropriate total annual hours of operation. Piping size selections for systems that operate under variable flow conditions (e.g., modulating two-way control valves at coils) and that contain variable-speed pump motors are allowed to be made from the "Variable Flow/Variable Speed" columns. All others shall be made from the "Other" columns.
Exceptions to 6.5.4.6
- Design flow rates exceeding the values in Table 6.5.4.6 are allowed in specific sections of piping if the piping in question is not in the critical circuit at design conditions and is not predicted to be in the critical circuit during more than 30% of operating hours.
- Piping systems that have equivalent or lower total pressure drop than the same system constructed with standard weight steel pipe with piping and fittings sized per Table 6.5.4.6.
Operating Hours/Year | ≤2000 Hours/Year | >2000 and ≤4400 Hours/Year | >4400 Hours/Year | |||
---|---|---|---|---|---|---|
Nominal Pipe Size, in. | Other | Variable Flow/Variable Speed | Other | Variable Flow/Variable Speed | Other | Variable Flow/Variable Speed |
2 1/2 | 120 | 180 | 85 | 130 | 68 | 110 |
3 | 180 | 270 | 140 | 210 | 110 | 170 |
4 | 350 | 530 | 260 | 400 | 210 | 320 |
5 | 410 | 620 | 310 | 470 | 250 | 370 |
6 | 740 | 1100 | 570 | 860 | 440 | 680 |
8 | 1200 | 1800 | 900 | 1400 | 700 | 1100 |
10 | 1800 | 2700 | 1300 | 2000 | 1000 | 1600 |
12 | 2500 | 3800 | 1900 | 2900 | 1500 | 2300 |
Maximum velocity for pipes over 14 to 24 in. in size | 8.5 ft/s | 13.0 ft/s | 6.5 ft/s | 9.5 ft/s | 5.0 ft/s | 7.5 ft/s |
Chilled-water cooling coils shall be selected to provide a 15°F or higher temperature difference between leaving and entering water temperatures and a minimum of 57°F leaving water temperature at design conditions.
Exceptions to 6.5.4.7
- Chilled-water cooling coils that have an air-side pressure drop exceeding 0.70 in. of water when rated at 500 fpm face velocity and dry conditions (no condensation).
- Individual fan-cooling units with a design supply airflow rate 5000 cfm and less.
- Constant-air-volume systems.
- Coils selected at the maximum temperature difference allowed by the chiller.
- Passive coils (no mechanically supplied airflow).
- Coils with design entering chilled-water temperatures of 50°F and higher.
- Coils with design entering air dry-bulb temperatures of 65°F and lower.
New buildings with gas hot-water boiler systems for space heating with a total system input of at least 1,000,000 Btu/h but not more than 10,000,000 Btu/h shall comply with Sections 6.5.4.8.1 and 6.5.4.8.2.
Exceptions to 6.5.4.8
- Where 25% of the annual space heating requirement is provided by on-site renewable energy, site-recovered energy, or heat recovery chillers.
- Space heating boilers installed in individual dwelling units.
- Where 50% or more of the design heating load is served using perimeter convective heating, radiant ceiling panels, or both.
- Individual gas boilers with input capacity less than 300,000 Btu/h shall not be included in the calculations of the total system input or total system efficiency.
Gas hot-water boilers shall have a minimum thermal efficiency (Et) of 90% when rated in accordance with the test procedures in Table 6.8.1-6. Systems with multiple boilers are allowed to meet this requirement if the space-heating input provided by equipment with thermal efficiency (Et) above and below 90% provides an input capacity-weighted average thermal efficiency of at least 90%. For boilers rated only for combustion efficiency, the calculation for the input capacity-weighted average thermal efficiency shall use the combustion efficiency value.
The hot-water distribution system shall be designed to meet all of the following:
- Coils and other heat exchangers shall be selected so that at design conditions the hot-water return temperature entering the boilers is 120°F or less.
- Under all operating conditions, the water temperature entering the boiler is 120°F or less, or the flow rate of supply hot water that recirculates directly into the return system, such as by three-way valves or minimum flow bypass controls, shall be no greater than 20% of the design flow of the operating boilers.
Section 6.5.5 applies to heat-rejection equipment used in comfort cooling systems, such as air-cooled condensers, dry coolers, open-circuit cooling towers, closed-circuit cooling towers, and evaporative condensers.
Exception to 6.5.5.1
Heat-rejection devices whose energy use is included in the equipment efficiency ratings listed in Tables 6.8.1-1 through 6.8.1-4, Tables 6.8.1-8 through 6.8.1-14, and Tables 6.8.1-16, 6.8.1-17, and 6.8.1-20.
The fan system on a heat-rejection device powered by an individual motor or an array of motors with a connected power, including the motor service factor, totaling 5 hp or more shall have controls and/or devices (such as variable-speed control) that shall result in fan motor demand of no more than 30% of design wattage at 50% of the design airflow and that shall automatically modulate the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat-rejection device.
Exceptions to 6.5.5.2.1
- Condenser fans serving multiple refrigerant or fluid cooling circuits.
- Condenser fans serving flooded condensers.
Multicell heat-rejection equipment with variable-speed fan drives shall
- operate the maximum number of fans allowed that comply with the manufacturer's requirements for all system components and
- control all fans to the same fan speed required for the instantaneous cooling duty, as opposed to staged (on/off) operation. Minimum fan speed shall comply with the minimum allowable speed of the fan drive system per the manufacturer's recommendations.
Centrifugal fan open-circuit cooling towers with a combined rated capacity of 1100 gpm or greater at 95°F condenser water return, 85°F condenser water supply, and 75°F outdoor air wet-bulb temperature shall meet the energy efficiency requirement for axial fan open-circuit cooling towers listed in Table 6.8.1-7.
Exception to 6.5.5.3
Centrifugal open-circuit cooling towers that are ducted (inlet or discharge) or require external sound attenuation.
Open-circuit cooling towers used on water-cooled chiller systems that are configured with multiple- or variable-speed condenser water pumps shall be designed so that all open-circuit cooling tower cells can be run in parallel with the larger of
- the flow that is produced by the smallest pump at its minimum expected flow rate or
- 50% of the design flow for the cell.
Nontransient dwelling units shall be provided with outdoor air energy recovery ventilation systems. For nontransient dwelling units, energy recovery systems shall result in an enthalpy recovery ratio of at least 50% at cooling design condition and at least 60% at heating design condition. The energy recovery system shall provide the required enthalpy recovery ratio at both heating and cooling design conditions, unless one mode is not required for the climate zone by the exceptions below.
Exceptions to 6.5.6.1.1
- Nontransient dwelling units in Climate Zone 3C.
- Nontransient dwelling units with no more than 500 ft2 of conditioned floor area in Climate Zone 0, 1, 2, 3, 4C, and 5C.
- Enthalpy recovery ratio requirements at heating design condition in Climate Zones 0, 1, and 2.
- Enthalpy recovery ratio requirements at cooling design condition in Climate Zones 4, 5, 6, 7, 8.
Each fan system serving spaces other than nontransient dwelling units shall have an energy recovery system where the design supply fan airflow rate exceeds the value listed in Tables 6.5.6.1.2-1 and 6.5.6.1.2-2, based on the climate zone and percentage of outdoor air at design airflow conditions. Table 6.5.6.1.2-1 shall be used for all ventilation systems that operate less than 8000 hours per year, and Table 6.5.6.1.2-1 shall be used for all ventilation systems that operate 8000 or more hours per year.
For spaces other than nontransient dwelling units, energy recovery systems shall result in an enthalpy recovery ratio of at least 50%. The energy recovery system shall provide the required enthalpy recovery ratio at both heating and cooling design conditions, unless one mode is not required for the climate zone by the exceptions below. Provision shall be made to bypass or control the energy recovery system to permit air economizer operation as required by Section 6.5.1.1.
Exceptions to 6.5.6.1.2
- Laboratory systems meeting Section 6.5.7.3.
- Systems serving spaces that are not cooled and that are heated to less than 60°F.
- Heating energy recovery where more than 60% of the outdoor air heating energy is provided from site-recovered energy or site-solar energy in Climate Zones 5 through 8.
- Enthalpy recovery ratio requirements at heating design condition in Climate Zones 0, 1, and 2.
- Enthalpy recovery ratio requirements at cooling design condition in Climate Zones 3C, 4C, 5B, 5C, 6B, 7, and 8.
- Where the sum of the airflow rates exhausted and relieved within 20 ft of each other is less than 75% of the design outdoor airflow rate, excluding exhaust air that is
- Systems in Climate Zones 0 through 4 requiring dehumidification that employ series energy recovery and have a minimum SERR of 0.40.
- Systems expected to operate less than 20 hours per week at the outdoor air percentage covered by Table 6.5.6.1.2-1.
- Indoor pool dehumidifiers meeting Section 6.5.6.4.
Table 6.5.6.1.2-1 Exhaust Air Energy Recovery Requirements for Ventilation Systems Operating Less than 8000 Hours per Year
Climate Zone | % Outdoor Air at Full Design Airflow Rate | |||||||
---|---|---|---|---|---|---|---|---|
≥10% and <20% | ≥20% and <30% | ≥30% and < 40% | ≥40% and < 50% | ≥50% and < 60% | ≥60% and <70% | ≥70% and < 80% | ≥80% | |
Design Supply Fan Airflow Rate, cfm | ||||||||
3B, 3C, 4B, 4C, 5B | NR | NR | NR | NR | NR | NR | NR | NR |
0B, 1B, 2B,5C | NR | NR | NR | NR | ≥26000 | ≥12000 | ≥5000 | ≥4000 |
6B | ≥28,000 | ≥26,500 | ≥11000 | ≥5500 | ≥4500 | ≥3500 | ≥ 2500 | ≥1500 |
0A, 1A, 2A, 3A, 4A, 5A, 6A | ≥26,000 | ≥16,000 | ≥5500 | ≥4500 | ≥3500 | ≥2000 | ≥1000 | >120 |
7,8 | ≥4500 | ≥4000 | ≥2500 | ≥1000 | ≥140 | ≥120 | ≥100 | ≥80 |
NR—Not required
Table 6.5.6.1.2-2 Exhaust Air Energy Recovery Requirements for Ventilation Systems Operating Greater than or Equal to 8000 Hours per Year
Climate Zone | % Outdoor Air at Full Design Airflow Rate | |||||||
---|---|---|---|---|---|---|---|---|
≥10% and <20% | ≥20% and <30% | ≥30% and < 40% | ≥40% and < 50% | ≥50% and < 60% | ≥60% and <70% | ≥70% and < 80% | ≥80% | |
Design Supply Fan Airflow Rate, cfm | ||||||||
3C | NR | NR | NR | NR | NR | NR | NR | NR |
0B, 1B, 2B, 3B, 4C, 5C | NR | ≥19,500 | ≥9000 | ≥5000 | ≥4000 | ≥3000 | ≥1500 | ≥120 |
0A, 1A, 2A, 3A, 4B, 5B | ≥2500 | ≥2000 | ≥1000 | ≥500 | ≥140 | ≥120 | ≥100 | ≥80 |
4A, 5A, 6A, 6B, 7, 8 | ≥200 | ≥130 | ≥100 | ≥80 | ≥70 | ≥60 | ≥50 | ≥40 |
NR—Not required
The required heat recovery system shall have the capacity to provide the smaller of
- 60% of the peak heat-rejection load at design conditions or
- preheat of the peak service hot-water draw to 85°F.
Exceptions to 6.5.6.2.2
- Facilities that employ condenser heat recovery for space heating with a heat recovery design exceeding 30% of the peak water-cooled condenser load at design conditions.
- Facilities that provide 60% of their service water heating from site-solar energy or site-recovered energy or from other sources.
Where heating water is used for space heating, a condenser heat recovery system shall be installed, provided all of the following are true:
- The building is an acute inpatient hospital, where the building or portion of a building is used on a 24-hour basis for the inpatient medical, obstetric, or surgical care for patients.
- The total design chilled-water capacity for the acute inpatient hospital, either air cooled or water cooled, required at cooling design conditions exceeds 3,600,000 Btu/h of cooling.
- Simultaneous heating and cooling occurs above 60°F outdoor air temperature.
The required heat recovery system shall have a cooling capacity that is at least 7% of the total design chilled-water capacity of the acute inpatient hospital at peak design conditions.
Exceptions to 6.5.6.3
- Buildings that provide ≥ 60% of their reheat energy from on-site renewable energy or site-recovered energy.
- Buildings in Climate Zones 5C, 6B, 7, and 8.
An indoor pool dehumidifier serving a natatorium with a heated indoor pool over 500 ft2 in size shall include one of the following:
- An exhaust air sensible energy recovery system with a sensible energy recovery ratio of at least 50%
- A condenser heat recovery system capable of and configured to use 100% of the heat generated through dehumidification to heat the pool water when there is a pool water heating load
- An exhaust air energy recovery system that results in an enthalpy recovery ratio of at least 50%
Exception to 6.5.6.4
Natatoriums heated by on-site renewable energy or site recovered energy capable of and configured to provide at least 60% of the annual heating energy required.
Conditioned supply air delivered to any space with mechanical exhaust shall not exceed the greater of
- the supply flow required to meet the space heating or cooling load;
- the ventilation rate required by the authority having jurisdiction, the facility Environmental Health and Safety department, or ASHRAE Standard 62.1; or
- the mechanical exhaust flow minus the available transfer air from conditioned spaces or return air plenums on the same floor, not in different smoke or fire compartments, and that at their closest point are within 15 ft of each other. Available transfer air is that portion of outdoor ventilation air that
- is not required to satisfy other exhaust needs,
- is not required to maintain pressurization of other spaces, and
- is transferable according to applicable codes and standards and to the class of air recirculation limitations in ASHRAE Standard 62.1.
Exceptions to 6.5.7.1
- Biosafety level classified laboratories 3 or higher.
- Vivarium spaces.
- Spaces that are required by applicable codes and standards to be maintained at positive pressure relative to adjacent spaces. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy.
- Spaces where the demand for transfer air may exceed the available transfer airflow rate and where the spaces have a required negative pressure relationship. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy.
Replacement air introduced directly into the hood cavity of kitchen exhaust hoods shall not exceed 10% of the hood exhaust airflow rate.
If a kitchen/dining facility has a total kitchen hood exhaust airflow rate greater than 5000 cfm then each hood shall have an exhaust rate that complies with Table 6.5.7.2.2. If a single hood or hood section is installed over appliances with different duty ratings then the maximum allowable flow rate for the hood or hood section shall not exceed the Table 6.5.7.2.2 values for the highest appliance duty rating under the hood or hood section. Refer to ASHRAE Standard 154 for definitions of hood type, appliance duty, and net exhaust flow rate.
Exception to 6.5.7.2.2
At least 75% of all the replacement air is transfer air that would otherwise be exhausted.
Table 6.5.7.2.2 Maximum Net Exhaust Flow Rate, cfm per Linear Foot of Hood Length
Type of Hood | Light-Duty Equipment | Medium-Duty Equipment | Heavy-Duty Equipment | Extra-Heavy-Duty Equipment |
---|---|---|---|---|
Wall-mounted canopy | 140 | 210 | 280 | 385 |
Single island | 280 | 350 | 420 | 490 |
Double island (per side) | 175 | 210 | 280 | 385 |
Eyebrow | 175 | 175 | NA | NA |
Backshelf/pass-over | 210 | 210 | 280 | NA |
NA = Not allowed
If a kitchen/dining facility has a total kitchen hood exhaust airflow rate greater than 5000 cfm then it shall have one of the following:
- At least 50% of all replacement air is transfer air that would otherwise be exhausted.
- Demand ventilation systems on at least 75% of the exhaust air. Such systems shall be capable of and configured to provide at least 50% reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent, and combustion products during cooking and idle.
- Listed energy recovery devices that result in a sensible energy recovery ratio of not less than 40% on at least 50% of the total exhaust airflow. A 40% sensible energy recovery ratio shall mean a change in the dry-bulb temperature of the outdoor air supply equal to 40% of the difference between the outdoor air and entering exhaust air dry-bulb temperatures at design conditions.
An approved field test method shall be used to evaluate design airflow rates and demonstrate proper capture and containment performance of installed commercial kitchen exhaust systems. Where demand ventilation systems are used to meet Section 6.5.7.2.3, additional performance testing shall be required to demonstrate proper capture and containment at minimum airflow.
Buildings with laboratory exhaust systems having a total exhaust rate greater than 5000 cfm shall include at least one of the following features:
- VAV laboratory exhaust and room supply system capable of and configured to reduce exhaust and makeup airflow rates and/or incorporate a heat recovery system to precondition makeup air from laboratory exhaust that shall meet the following: A + B × (E/M) ≥ 50%where
A = percentage that the exhaust and makeup airflow rates can be reduced from design conditions B = sensible energy recovery ratio E = exhaust airflow rate through the heat recovery device at design conditions M = makeup airflow rate of the system at design conditions. - VAV laboratory exhaust and room supply systems that are required to have minimum circulation rates to comply with code or accreditation standards shall be capable of and configured to reduce zone exhaust and makeup airflow rates to the regulated minimum circulation values or the minimum required to maintain pressurization relationship requirements. Systems serving nonregulated zones shall be capable of and configured to reduce exhaust and makeup airflow rates to 50% of the zone design values or the minimum required to maintain pressurization relationship requirements.
- Direct makeup (auxiliary) air supply equal to at least 75% of the exhaust airflow rate, heated no warmer than 2°F below room set point, cooled to no cooler than 3°F above room set point, no humidification added, and no simultaneous heating and cooling used for dehumidification control.
Exception to 6.5.8.1
Loading docks equipped with air curtains.
Radiant heating systems that are used as primary or supplemental heating for enclosed spaces must be in conformance with the governing provisions of the standard, including but not limited to the following:
Cooling systems shall not use hot-gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot-gas bypass shall be limited as indicated in Table 6.5.9 for VAV units and single-zone VAV units. Hot-gas bypass shall not be used on constant-volume units.
Table 6.5.9 Hot-Gas Bypass Limitation
Rated Capacity | Maximum Hot-Gas Bypass, % of Total Capacity |
---|---|
≤240,000 Btu/h | 15% |
>240,000 Btu/h | 10% |
Any conditioned space with a door, including doors with more than one-half glass, opening to the outdoors shall be provided with controls that, when any such door is open,
- disable mechanical heating or reset the heating set point to 55°F or lower within five minutes of the door opening and
- disable mechanical cooling or reset the cooling set point to 90°F or greater within five minutes of the door opening. Mechanical cooling may remain enabled if outdoor air temperature is below space temperature.
Exceptions to 6.5.10
- Building entries with automatic closing devices.
- Any space without a thermostat.
- Alterations to existing buildings.
- Loading docks.
Refrigeration systems that comprise refrigerated display cases, walk-in coolers, or walk-in freezers connected to remote compressors, remote condensers, or remote condensing units shall meet the requirements of Sections 6.5.11.1 and 6.5.11.2.
Exception to 6.5.11
Systems utilizing transcritical refrigeration cycle or ammonia refrigerant.
Fan-powered condensers shall conform to the following requirements:
- Design saturated condensing temperatures for air-cooled condensers shall be less than or equal to the design dry-bulb temperature plus 10°F for low-temperature refrigeration systems and less than or equal to the design dry-bulb temperature plus 15°F for medium-temperature refrigeration systems.
- Saturated condensing temperature for blend refrigerants shall be determined using the average of liquid and vapor temperatures as converted from the condenser drain pressure.
- Condenser fan motors that are less than 1 hp shall use electronically commutated motors, permanent split-capacitor-type motors, or three-phase motors.
- All condenser fans for air-cooled condensers, evaporatively cooled condensers, and air- or water-cooled fluid coolers or cooling towers shall incorporate one of the following continuous variable-speed fan control approaches and shall reduce fan motor demand to no more than 30% of design wattage at 50% of design air volume:
- Refrigeration system condenser control for air-cooled condensers shall use variable set-point control logic to reset the condensing temperature set point in response to ambient dry-bulb temperature.
- Refrigeration system condenser control for evaporatively cooled condensers shall use variable set-point control logic to reset the condensing temperature set point in response to ambient wet-bulb temperature.
- Multiple fan condensers shall be controlled in unison.
- The minimum condensing temperature set point shall be no greater than 70°F.
Refrigeration compressor systems shall conform to the following requirements:
- Compressors and multiple-compressor systems suction groups shall include control systems that use floating suction pressure control logic to reset the target suction pressure temperature based on the temperature requirements of the attached refrigeration display cases or walk-ins. Exceptions to 6.5.11.2(a)
- Single-compressor systems that do not have variable-capacity capability.
- Suction groups that have a design saturated suction temperature equal to or greater than 30°F, suction groups that comprise the high stage of a two-stage or cascade system, or suction groups that primarily serve chillers for secondary cooling fluids.
- Liquid subcooling shall be provided for all low-temperature compressor systems with a design cooling capacity equal to or greater than 100,000 Btu/h with a design saturated suction temperature equal to or less than —10°F. The subcooled liquid temperature shall be controlled at a maximum temperature set point of 50°F at the exit of the subcooler using either compressor economizer (interstage) ports or a separate compressor suction group operating at a saturated suction temperature equal to or greater than 18°F.
- Subcooled liquid lines are subject to the insulation requirements of Table 6.8.3-2.
- All compressors that incorporate internal or external crankcase heaters shall provide a means to cycle the heaters off during compressor operation.
HVAC systems only serving the heating, cooling, or ventilating needs of a computer room with IT equipment load greater than 10 kW shall comply with ASHRAE Standard 90.4, Energy Standard for Data Centers.
Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.
(Not Used)
Construction documents shall require that, within 90 days after the date of system acceptance, record documents be provided to the building owner or the designated representative of the building owner. Record documents shall include, as a minimum, the location and performance data on each piece of equipment; general configuration of the duct and pipe distribution system, including sizes; and the terminal air or water design flow rates.
Construction documents shall require that an operating manual and a maintenance manual be provided to the building owner or the designated representative of the building owner within 90 days after the date of system acceptance. These manuals shall be in accordance with industry-accepted standards (see Informative Appendix E) and shall include, at a minimum, the following:
- Submittal data stating equipment size and selected options for each piece of equipment requiring maintenance.
- Operation manuals and maintenance manuals for each piece of equipment and system requiring maintenance, except equipment not furnished as part of the project. Required routine maintenance actions shall be clearly identified.
- Names and addresses of at least one service agency.
- HVAC controls system maintenance and calibration information, including wiring diagrams, schematics, and control sequence descriptions. Desired or field-determined set points shall be permanently recorded on control drawings at control devices or, for digital control systems, in programming comments.
- A complete narrative of how each system is intended to operate, including suggested set points.
Construction documents shall require that all HVAC systems be balanced in accordance with generally accepted engineering standards (see Informative Appendix E). Construction documents shall require that a written balance report be provided to the building owner or the designated representative of the building owner for HVAC systems serving zones with a total conditioned area exceeding 5000 ft2.
Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions.
Exceptions to 6.7.3.3.3
Impellers need not be trimmed nor pump speed adjusted
- for pumps with pump motors of 10 hp or less or
- when throttling results in no greater than 5% of the nameplate horsepower draw, or 3 hp, whichever is greater, above that required if the impeller was trimmed.
Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Efficiency Requirements
Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
---|---|---|---|---|---|
Air conditioners, air cooled | <65,000 Btu/hb | All | Split system, three phase and applications outside U.S. single phase b | 13.0 SEER before 1/1/2023 13.4 SEER2 after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
Single-package, three phase and applications outside U.S. single phase b | 14.0 SEER before 1/1/2023 13.4 SEER2 after 1/1/2023 |
||||
Space constrained, air cooled | ≤30,000 Btu/hb | All | Split system, three phase and applications outside U.S. single phase b | 12.0 SEER before 1/1/2023 11.7 SEER2 after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
Single package, three phase and applications outside U.S. single phase b | 12.0 SEER before 1/1/2023 11.7 SEER2 after 1/1/2023 |
||||
Small duct, high velocity, air cooled | <65,000 Btu/hb | All | Split system, three phase and applications outside U.S. single phase b | 12.0 SEER before 1/1/2023 12.0 SEER2 after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
Air conditioners, air cooled | ≥65,000 Btu/h and <135,000 Btu/h | Electric resistance (or none) |
Split system and single package | 11.2 EER 12.9 IEER before 1/1/2023 14.8 IEER after 1/1/2023 |
AHRI 340/360 |
All other | 11.0 EER 12.7 IEER before 1/1/2023 14.6 IEER after 1/1/2023 |
||||
≥135,000 Btu/h and <240,000 Btu/h | Electric resistance (or none) |
11.0 EER 12.4 IEER before 1/1/2023 14.2 IEER after 1/1/2023 |
|||
All other | 10.8 EER 12.2 IEER before 1/1/2023 14.0 IEER after 1/1/2023 |
||||
≥240,000 Btu/h and <760,000 Btu/h | Electric resistance (or none) |
10.0 EER 11.6 IEER before 1/1/2023 13.2 IEER after 1/1/2023 |
|||
All other | 9.8 EER 11.4 IEER before 1/1/2023 13.0 IEER after 1/1/2023 |
||||
≥760,000 Btu/h | Electric resistance (or none) |
9.7 EER 11.2 IEER before 1/1/2023 12.5 IEER after 1/1/2023 |
|||
All other | 9.5 EER 11.0 IEER before 1/1/2023 12.3 IEER after 1/1/2023 |
||||
Air conditioners, water cooled | <65,000 Btu/h | All | Split system and single package | 12.1 EER 12.3 IEER |
AHRI 210/240 |
≥65,000 Btu/h and <135,000 Btu/h | Electric resistance (or none) |
12.1 EER 13.9 IEER |
AHRI 340/360 | ||
All other | 11.9 EER 13.7 IEER |
||||
≥135,000 Btu/h and <240,000 Btu/h | Electric resistance (or none) |
12.5 EER 13.9 IEER |
|||
All other | 12.3 EER 13.7 IEER |
||||
≥240,000 Btu/h and <760,000 Btu/h | Electric resistance (or none) |
12.4 EER 13.6 IEER |
|||
All other | 12.2 EER 13.4 IEER |
||||
≥760,000 Btu/h | Electric resistance (or none) |
12.2 EER 13.5 IEER |
|||
All other | 12.0 EER 13.3 IEER |
||||
Air conditioners, evaporatively cooled | <65,000 Btu/hb | All | Split system and single package | 12.1 EER 12.3 IEER |
AHRI 210/240 |
≥65,000 Btu/h and <135,000 Btu/h | Electric resistance (or none) |
12.1 EER 12.3 IEER |
AHRI 340/360 | ||
All other | 11.9 EER 12.1 IEER |
||||
≥135,000 Btu/h and <240,000 Btu/h | Electric resistance (or none) |
12.0 EER 12.2 IERR |
|||
All other | 11.8 EER 12.0 IEER |
||||
≥240,000 Btu/h and <760,000 Btu/h | Electric resistance (or none) |
11.9 EER 12.1 IEER |
|||
All other | 11.7 EER 11.9 IEER |
||||
≥760,000 Btu/h | Electric resistance (or none) |
11.7 EER 11.9 IEER |
|||
All other | 11.5 EER 11.7 IEER |
||||
Condensing units, air cooled | ≥135,000 Btu/h | 10.5 EER 11.8 IEER |
AHRI 365 | ||
Condensing units, water cooled | ≥135,000 Btu/h | 13.5 EER 14.0 IEER |
AHRI 365 | ||
Condensing units, evaporatively cooled | ≥135,000 Btu/h | 13.5 EER 14.0 IEER |
AHRI 365 |
a. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
b. Single-phase, U.S. air-cooled air conditioners <65,000 Btu/h are regulated as consumer products by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430. SEER and SEER2 values for single-phase products are set by the U.S. Department of Energy.
Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum efficiency requirements of single-phase air conditioners for U.S. applications.
Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
---|---|---|---|---|---|
Air cooled (cooling mode) |
<65,000 Btu/h | All | Split system, three phase and applications outside U.S. single phase b | 14.0 SEER before 1/1/2023 14.3 SEER2 after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
Single package, three phase and applications outside U.S. single phase b | 14.0 SEER before 1/1/2023 13.4 SEER2 after 1/1/2023 |
||||
Space constrained, air cooled (cooling mode) |
≤30,000 Btu/h | All | Split system, three phase and applications outside U.S. single phase b | 12.0 SEER before 1/1/2023 11.7 SEER2 after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
Single package, three phase and applications outside U.S. single phase b | 12.0 SEER before 1/1/2023 11.7 SEER2 after 1/1/2023 |
||||
Small duct, high velocity, air cooled (cooling mode) |
<65,000 Btu/h | All | Split System, three phase and applications outside U.S. single phase b | 12.0 SEER before 1/1/2023 12.0 SEER2 after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
Air cooled (cooling mode) |
≥65,000 Btu/h and <135,000 Btu/h | Electric resistance (or none) |
Split system and single package | 11.0 EER 12.2 IEER before 1/1/2023 14.1 IEER after 1/1/2023 |
AHRI 340/360 |
All other | 10.8 EER 12.0 IEER before 1/1/2023 13.9 IEER after 1/1/2023 |
||||
≥135,000 Btu/h and <240,000 Btu/h | Electric resistance (or none) |
10.6 EER 11.6 IEER before 1/1/2023 13.5 IEER after 1/1/2023 |
|||
All other | 10.4 EER 11.4 IEER before 1/1/2023 13.3 IEER after 1/1/2023 |
||||
≥240,000 Btu/h | Electric resistance (or none) |
9.5 EER 10.6 IEER before 1/1/2023 12.5 IEER after 1/1/2023 |
|||
All other | 9.3 EER 10.4 IEER before 1/1/2023 12.3 IEER after 1/1/2023 |
||||
Air cooled (heating mode) |
<65,000 Btu/h (cooling capacity) |
Split system, three phase and applications outside U.S. single phase b | 8.2 HSPF before 1/1/2023 7.5 HSPF2 after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
|
Single package, three phase and applications outside U.S. single phase b | 8.0 HSPF before 1/1/2023 6.7 HSPF2 after 1/1/2023 |
||||
Space constrained, air cooled (heating mode) |
≤30,000 Btu/h (cooling capacity) |
Split system, three phase and applications outside U.S. single phase b | 7.4 HSPF before 1/1/2023 6.3 HSPF2after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
|
Single package, three phase and applications outside U.S. single phase b | 7.4 HSPF before 1/1/2023 6.3 HSPF2 after 1/1/2023 |
||||
Small duct high velocity, air cooled (heating mode) |
<65,000 Btu/h | Split system, three phase and applications outside U.S. single phase b | 7.2 HSPF before 1/1/2023 6.1 HSPF2 after 1/1/2023 |
AHRI 210/240-2017 before 1/1/2023 AHRI 210/240-2023 after 1/1/2023 |
|
Air cooled (heating mode) |
≥65,000 Btu/h and <135,000 Btu/h (cooling capacity) |
47°F db/43°F wb outdoor air |
3.30 COPH before 1/1/2023 3.40 COPH after 1/1/2023 |
AHRI 340/360 | |
17°F db/15°F wb outdoor air |
2.25 COPH | ||||
≥135,000 Btu/h (cooling capacity) and <240,000 Btu/h |
47°F db/43°F wb outdoor air |
3.20 COPH before 1/1/2023 3.30 COPH after 1/1/2023 |
|||
17°F db/15°F wb outdoor air |
2.05 COPH | ||||
≥240,000 Btu/h (cooling capacity) |
47°F db/43°F wb outdoor air |
3.20 COPH | |||
17°F db/15°F wb outdoor air |
2.05 COPH |
a. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
b. Single-phase, U.S. air-cooled heat pumps <65,000 Btu/h are regulated as consumer products by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430. SEER, SEER2, and HSPF values for single-phase products are set by the U.S. Department of Energy.
Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum.
Table 6.8.1-3 Water-Chilling Packages—Minimum Efficiency Requirementsa,b,e
Equipment Type | Size Category | Units | Path A | Path B | Test Procedurec |
---|---|---|---|---|---|
Air cooled chillers | <150 tons | EER (Btu/Wh) | ≥10.100 FL | ≥9.700 FL | AHRI 550/590 |
≥13.700 IPLV.IP | ≥15.800 IPLV.IP | ||||
≥150 tons | ≥10.100 FL | ≥9.700 FL | |||
≥14.000 IPLV.IP | ≥16.100 IPLV.IP | ||||
Air cooled without condenser, electrically operated | All capacities | EER (Btu/Wh) | Air-cooled chillers without condenser must be rated with matching condensers and comply with air-cooled chiller efficiency requirements | AHRI 550/590 | |
Water cooled, electrically operated positive displacement | <75 tons | kW/ton | ≤0.750 FL | ≤0.780 FL | AHRI 550/590 |
≤0.600 IPLV.IP | ≤0.500 IPLV.IP | ||||
≥75 tons and <150 tons | ≤0.720 FL | ≤0.750 FL | |||
≤0.560 IPLV.IP | ≤0.490 IPLV.IP | ||||
≥150 tons and <300 tons | ≤0.660 FL | ≤0.680 FL | |||
≤0.540 IPLV.IP | ≤0.440 IPLV.IP | ||||
≥300 tons and <600 tons | ≤0.610 FL | ≤0.625 FL | |||
≤0.520 IPLV.IP | ≤0.410 IPLV.IP | ||||
≥600 tons | ≤0.560 FL | ≤0.585 FL | |||
≤0.500 IPLV.IP | ≤0.380 IPLV.IP | ||||
Water cooled, electrically operated centrifugal | <150 tons | kW/ton | ≤0.610 FL | ≤0.695 FL | AHRI 550/590 |
≤0.550 IPLV.IP | ≤0.440 IPLV.IP | ||||
≥150 tons and <300 tons | ≤0.610 FL | ≤0.635 FL | |||
≤0.550 IPLV.IP | ≤0.400 IPLV.IP | ||||
≥300 tons and <400 tons | ≤0.560 FL | ≤0.595 FL | |||
≤0.520 IPLV.IP | ≤0.390 IPLV.IP | ||||
≥400 tons and <600 tons | ≤0.560 FL | ≤0.585 FL | |||
≤0.500 IPLV.IP | ≤0.380 IPLV.IP | ||||
≥600 tons | ≤0.560 FL | ≤0.585 FL | |||
≤0.500 IPLV.IP | ≤0.380 IPLV.IP | ||||
Air cooled absorption, single effect | All capacities | COP (W/W) | ≥0.600 FL | NAd | AHRI 560 |
Water cooled absorption, single effect | All capacities | COP (W/W) | ≥0.700 FL | NAd | AHRI 560 |
Absorption double effect, indirect fired | All capacities | COP (W/W) | ≥1.000 FL | NAd | AHRI 560 |
≥1.050 IPLV.IP | |||||
Absorption double effect, direct fired | All capacities | COP (W/W) | ≥1.000 FL | NAd | AHRI 560 |
≥1.000 IPLV |
a. The requirements for centrifugal chillers shall be adjusted for nonstandard rating conditions per Section 6.4.1.2.1 and are only applicable for the range of conditions listed there. The requirements for air-cooled, water-cooled positive displacement and absorption chillers are at standard rating conditions defined in the reference test procedure.
b. Both the full-load and IPLV.IP requirements must be met or exceeded to comply with this standard. When there is a Path B, compliance can be with either Path A or Path B for any application.
c. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
d. NA means the requirements are not applicable for Path B, and only Path A can be used for compliance.
e. FL is the full-load performance requirements, and IPLV.IP is for the part-load performance requirements.
Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air-Conditioner Heat Pumps—Minimum Efficiency Requirements
Equipment Type | Size Category (Input) | Subcategory or Rating Condition | Minimum Efficiencyd | Test Procedurea |
---|---|---|---|---|
PTAC (cooling mode) standard size | <7000 Btu/h | 95°F db/75°F wb outdoor airc |
11.9 EER | AHRI 310/380 |
≥7000 Btu/h and ≤15,000 Btu/h | 14.0 — (0.300 × Cap/1000) EERe | |||
>15,000 Btu/h | 9.5 EER | |||
PTAC (cooling mode) nonstandard sizea | <7000 Btu/h | 95°F db/75°F wb outdoor airc |
9.4 EER | AHRI 310/380 |
≥7000 Btu/h and ≤15,000 Btu/h | 10.9 — (0.213 × Cap/1000) EERe | |||
>15,000 Btu/h | 7.7 EER | |||
PTHP (cooling mode) standard size | <7000 Btu/h | 95°F db/75°F wb outdoor airc |
11.9 EER | AHRI 310/380 |
≥7000 Btu/h and ≤15,000 Btu/h | 14.0 — (0.300 × Cap/1000) EERe | |||
>15,000 Btu/h | 9.5 EER | |||
PTHP (cooling mode) nonstandard sizeb | <7000 Btu/h | 95°F db/75°F wb outdoor airc |
9.3 EER | AHRI 310/380 |
≥7000 Btu/h and ≤15,000 Btu/h | 10.8 — (0.213 × Cap/1000) EERe | |||
>15,000 Btu/h | 7.6 EER | |||
PTHP (heating mode) standard size |
<7000 Btu/h | 47°F db/43°F wb outdoor air |
3.3 COPH | AHRI 310/380 |
≥7000 Btu/h and ≤15,000 Btu/h | 3.7 — (0.052 × Cap/1000) COPHe | |||
>15,000 Btu/h | 2.90 COPH | |||
PTHP (heating mode) nonstandard sizeb |
<7000 Btu/h | 47°F db/43°F wb outdoor air |
2.7 COPH | AHRI 310/380 |
≥7000 Btu/h and ≤15,000 Btu/h | 2.9 — (0.026 × Cap/1000) COPHe | |||
>15,000 Btu/h | 2.5 COPH | |||
SPVAC (cooling mode) single and three phase | <65,000 Btu/h | 95°F db/75°F wb outdoor airc |
11.0 EER | AHRI 390 |
≥65,000 Btu/h and <135,000 Btu/h | 10.0 EER | |||
≥135,000 Btu/h and <240,000 Btu/h | 10.0 EER | |||
SPVHP (cooling mode) | <65,000 Btu/h | 95°F db/75°F wb outdoor airc |
11.0 EER | AHRI 390 |
≥65,000 Btu/h and <135,000 Btu/h | 10.0 EER | |||
≥135,000 Btu/h and <240,000 Btu/h | 10.0 EER | |||
SPVHP (heating mode) |
<65,000 Btu/h | 47°F db/43°F wb outdoor air |
3.3 COPH | AHRI 390 |
≥65,000 Btu/h and <135,000 Btu/h | 3.0 COPH | |||
≥135,000 Btu/h and <240,000 Btu/h | 3.0 COPH |
a. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
b. Nonstandard size units must be factory labeled as follows: "MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS." Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in.2.
c. The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil.
d. Room air conditioners are regulated as consumer products by 10 CFR 430. For U.S. applications of room air conditioners, refer to Informative Appendix F, Table F-3, for the USDOE minimum efficiency requirements for U.S. applications.
e. "Cap" in EER and COPH equations for PTACs and PTHPs means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.
Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air-Conditioner Heat Pumps—Minimum Efficiency Requirements
Equipment Type | Size Category (Input) | Subcategory or Rating Condition | Minimum Efficiencyd | Test Procedurea |
---|---|---|---|---|
Room air conditioners without reverse cycle with louvered sides for applications outside U.S.d | <6000 Btu/h | 11.0 CEER | ANSI/AHAM RAC-1 | |
≥6000 Btu/h and <8000 Btu/h | 11.0 CEER | |||
≥8000 Btu/h and <14,000 Btu/h | 10.9 CEER | |||
≥14,000 Btu/h and <20,000 Btu/h | 10.7 CEER | |||
≥20,000 Btu/h and <28,000 Btu/h | 9.4 CEER | |||
≥28,000 Btu/h | 9.0 CEER | |||
Room air conditioners without louvered sides | <6000 Btu/h | 10.0 CEER | ANSI/AHAM RAC-1 | |
≥6000 Btu/h and <8000 Btu/h | 10.0 CEER | |||
≥8000 Btu/h and <11,000 Btu/h | 9.6 CEER | |||
≥11,000 Btu/h and <14,000 Btu/h | 9.5 CEER | |||
≥14,000 Btu/h and <20,000 Btu/h | 9.3 CEER | |||
≥20,000 Btu/h | 9.4 CEER | |||
Room air conditioners with reverse cycle, with louvered sides for applications outside U.S.d | <20,000 Btu/h | 9.8 CEER | ANSI/AHAM RAC-1 | |
≥20,000 Btu/h | 9.3 CEER | |||
Room air conditioners with reverse cycle without louvered sides for applications outside U.S.d | <14,000 Btu/h | 9.3 CEER | ANSI/AHAM RAC-1 | |
≥14,000 Btu/h | 8.7 CEER | |||
Room air conditioners, casement only for applications outside U.S.d | All | 9.5 CEER | ANSI/AHAM RAC-1 | |
Room air conditioners, casement slider for applications outside U.S.d | All | 10.4 CEER | ANSI/AHAM RAC-1 |
a. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
b. Nonstandard size units must be factory labeled as follows: "MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS." Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in.2.
c. The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil.
d. Room air conditioners are regulated as consumer products by 10 CFR 430. For U.S. applications of room air conditioners, refer to Informative Appendix F, Table F-3, for the USDOE minimum efficiency requirements for U.S. applications.
e. "Cap" in EER and COPH equations for PTACs and PTHPs means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.
Table 6.8.1-5 Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit Heaters—Minimum Efficiency Requirements
Equipment Type | Size Category (Input) | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
---|---|---|---|---|
Warm-air furnace, gas fired for application outside the U.S.g | <225,000 Btu/h | Maximum capacityc | 80% AFUE (nonweatherized) or 81% AFUE (weatherized) or 80% Etb,d |
10 CFR 430 Appendix N or Section 2.39, Thermal Efficiency, ANSI Z21.47 |
Warm-air furnace, gas fired | ≥225,000 Btu/h | Maximum capacityc | 80% Etb,d before 1/1/2023 81% Etd after 1/1/2023 |
Section 2.39, Thermal Efficiency, ANSI Z21.47 |
Warm-air furnace, oil fired for application outside the U.S.g | <225,000 Btu/h | Maximum capacityc | 83% AFUE (nonweatherized) or 78% AFUE (weatherized) or 80% Etb,d |
10 CFR 430 Appendix N or Section 42, Combustion, UL 727 |
Warm-air furnace, oil fired | ≥225,000 Btu/h | Maximum capacityc | 81% Etd before 1/1/2023 82% Etd after 1/1/2023 |
Section 42, Combustion, UL 727 |
Electric furnaces for applications outside the U.S.g | <225,000 Btu/h | All | 96% AFUE | 10 CFR 430 Appendix N |
Warm-air duct furnaces, gas fired | All capacities | Maximum capacityc | 80% Ece | Section 2.10, Efficiency, ANSI Z83.8 |
Warm-air unit heaters, gas fired | All capacities | Maximum capacityc | 80% Ece,f | Section 2.10, Efficiency, ANSI Z83.8 |
Warm-air unit heaters, oil fired | All capacities | Maximum capacityc | 80% Ece,f | Section 40, Combustion, UL 731 |
a. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
b. Combination units (i.e., furnaces contained within the same cabinet as an air conditioner) not covered by 10 CFR 430 (i.e., three-phase power or with cooling capacity greater than or equal to 65,000 Btu/h) may comply with either rating. All other units greater than 225,000 Btu/h sold in the U.S. must meet the AFUE standards for consumer products and test using USDOE's AFUE test procedure at 10 CFR 430, Subpart B, Appendix N.
c. Compliance of multiple firing rate units shall be at the maximum firing rate.
d. Et = thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75% of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.
e. Ec = combustion efficiency (100% less flue losses). See test procedure for detailed discussion.
f. Units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper.
g. For U.S. applications of federal covered <225,000 Btu/h products, see Informative Appendix F, Table F-4.
Equipment Typea | Subcategory or Rating Condition | Size Category (Input) | Minimum Efficiencyi | Efficiency as of 3/2/2022 | Test Procedure |
---|---|---|---|---|---|
Boilers, hot water | Gas firedh | <300,000 Btu/hf,g for applications outside U.S.i | 82% AFUE | 82% AFUE | 10 CFR 430 Appendix N |
≥300,000 Btu/h and ≤2,500,000 Btu/hd | 80% Etc | 80% Etc | 10 CFR 431.86 | ||
>2,500,000 Btu/had | 82% Ecb | 82% Ecb | |||
Oil firede | <300,000 Btu/hf,g for applications outside U.S.i | 84% AFUE | 84% AFUE | 10 CFR 430 Appendix N |
|
≥300,000 Btu/h and ≤2,500,000 Btu/hd | 82% Etc | 82% Etc | 10 CFR 431.86 | ||
>2,500,000 Btu/had | 84% Ecb | 84% Ecb | |||
Boilers, steam | Gas fired | <300,000 Btu/hf for applications outside U.S.i | 80% AFUE | 80% AFUE | 10 CFR 430 Appendix N |
Gas fired—all, except natural draft | ≥300,000 Btu/h and ≤2,500,000 Btu/hd | 79% Etc | 79% Etc | 10 CFR 431.86 | |
>2,500,000 Btu/had | 79% Etc | 79% Etc | |||
Gas fired—natural draft | ≥300,000 Btu/h and ≤2,500,000 Btu/hd | 77% Etc | 79% Etc | ||
>2,500,000 Btu/had | 77% Etc | 79% Etc | |||
Oil firede | <300,000 Btu/hf for applications outside U.S.i | 82% AFUE | 82% AFUE | 10 CFR 430 Appendix N |
|
≥300,000 Btu/h and ≤2,500,000 Btu/hd | 81% Etc | 81% Etc | 10 CFR 431.86 | ||
>2,500,000 Btu/had | 81% Etc | 81% Etc |
a. These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.
b. Ec = combustion efficiency (100% less flue losses). See reference document for detailed information.
c. Et = thermal efficiency. See reference document for detailed information.
d. Maximum capacity—minimum and maximum ratings as provided for and allowed by the unit's controls.
e. Includes oil-fired (residual).
f. Boilers shall not be equipped with a constant burning pilot light.
g. A boiler not equipped with a tankless domestic water-heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied.
i. See Informative Appendix F, Table F-4, for U.S. minimum efficiencies for residential products covered by USDOE requirements for U.S. applications.
Equipment Type | Total System Heat-Rejection Capacity at Rated Conditions | Subcategory or Rating Conditionh | Performance Requireda,b,c,f,g | Test Procedured,e |
---|---|---|---|---|
Propeller or axial fan open-circuit cooling towers | All | 95°F entering water 85°F leaving water 75°F entering wb |
≥40.2 gpm/hp | CTI ATC-105 and CTI STD-201 RS |
Centrifugal fan open-circuit cooling towers | All | 95°F entering water 85°F leaving water 75°F entering wb |
≥20.0 gpm/hp | CTI ATC-105 and CTI STD-201 RS |
Propeller or axial fan closed-circuit cooling towers | All | 102°F entering water 90°F leaving water 75°F entering wb |
≥16.1 gpm/hp | CTI ATC-105S and CTI STD-201 RS |
Centrifugal fan closed-circuit cooling towers | All | 102°F entering water 90°F leaving water 75°F entering wb |
≥7.0 gpm/hp | CTI ATC-105S and CTI STD-201 RS |
Propeller or axial fan dry coolers (air-cooled fluid coolers) | All | 115°F entering water 105°F leaving water 95°F entering db |
≥4.5 gpm/hp | CTI ATC-105DS |
Propeller or axial fan evaporative condensers | All | R-448A test fluid 165°F entering gas temperature 105°F condensing temperature 75°F entering wb |
≥160,000 Btu/h•hp | CTI ATC-106 |
Propeller or axial fan evaporative condensers | All | Ammonia test fluid 140°F entering gas temperature 96.3°F condensing temperature 75°F entering wb |
≥134,000 Btu/h•hp | CTI ATC-106 |
Centrifugal fan evaporative condensers | All | R-448A test fluid 165°F entering gas temperature 105°F condensing temperature 75°F entering wb |
≥137,000 Btu/h•hp | CTI ATC-106 |
Centrifugal fan evaporative condensers | All | Ammonia test fluid 140°F entering gas temperature 96.3°F condensing temperature 75°F entering wb |
≥110,000 Btu/h•hp | CTI ATC-106 |
Air cooled condensers | All | 125°F condensing temperature 190°F entering gas temperature 15°F subcooling 95°F entering db |
≥176,000 Btu/h•hp | AHRI 460 |
a. For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the thermal rating condition listed in Table 6.8.1-7 divided by the fan motor nameplate power.
b. For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the thermal rating condition listed in Table 6.8.1-7 divided by the sum of the fan motor nameplate power and the integral spray pump motor nameplate power.
c. For purposes of this table, dry-cooler performance is defined as the process water flow rating of the unit at the thermal rating condition listed in Table 6.8.1-7 divided by the total fan motor nameplate power of the unit, and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the total fan motor nameplate power of the unit.
d. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
e. The efficiencies and test procedures for both open- and closed-circuit cooling towers are not applicable to hybrid cooling towers that contain a combination of separate wet and dry heat exchange sections. The certification requirements do not apply to field-erected cooling towers.
f. All cooling towers shall comply with the minimum efficiency listed in the table for that specific type of tower with the capacity effect of any project-specific accessories and/or options included in the capacity of the cooling tower.
g. For purposes of this table, evaporative condenser performance is defined as the heat rejected at the specified rating condition in the table, divided by the sum of the fan motor nameplate power and the integral spray pump nameplate power.
h. Requirements for evaporative condensers are listed with ammonia (R-717) and R-448A as test fluids in the table. Evaporative condensers intended for use with halocarbon refrigerants other than R-448A must meet the minimum efficiency requirements listed above with R-448A as the test fluid. For ammonia, the condensing temperature is defined as the saturation temperature corresponding to the refrigerant pressure at the condenser entrance. For R-448A, which is a zeotropic refrigerant, the condensing temperature is defined as the arithmetic average of the dew point and the bubble point temperatures corresponding to the refrigerant pressure at the condenser entrance.
Table 6.8.1-8 Electrically Operated Variable-Refrigerant-Flow Air Conditioners—Minimum Efficiency Requirements
Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency | Test Procedure |
---|---|---|---|---|---|
VRF air conditioners, air cooled | <65,000 Btu/h | All | VRF multisplit system | 13.0 SEER | AHRI 1230 |
≥65,000 Btu/h and <135,000 Btu/h | Electric resistance (or none) |
VRF multisplit system | 11.2 EER 15.5 IEER |
||
≥135,000 Btu/h and <240,000 Btu/h | Electric resistance (or none) |
VRF multisplit system | 11.0 EER 14.9 IEER |
||
≥240,000 Btu/h | Electric resistance (or none) |
VRF multisplit system | 10.0 EER 13.9 IEER |
Table 6.8.1-9 Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements
Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency | Test Procedure |
---|---|---|---|---|---|
VRF air cooled (cooling mode) |
<65,000 Btu/h | All | VRF multisplit system | 13.0 SEER | AHRI 1230 |
≥65,000 Btu/h and <135,000 Btu/h | Electric resistance (or none) |
11.0 EER 14.6 IEER |
|||
VRF multisplit system with heat recovery | 10.8 EER 14.4 IEER |
||||
≥135,000 Btu/h and <240,000 Btu/h | VRF multisplit system | 10.6 EER 13.9 IEER |
|||
VRF multisplit system with heat recovery | 10.4 EER 13.7 IEER |
||||
≥240,000 Btu/h | VRF multisplit system | 9.5 EER 12.7 IEER |
|||
VRF multisplit system with heat recovery | 9.3 EER 12.5 IEER |
||||
VRF water source (cooling mode) |
<65,000 Btu/h | All | VRF multisplit systems 86°F entering water |
12.0 EER 16.0 IEER |
AHRI 1230 |
VRF multisplit systems with heat recovery 86°F entering water |
11.8 EER 15.8 IEER |
||||
≥65,000 Btu/h and <135,000 Btu/h | VRF multisplit system 86°F entering water |
12.0 EER 16.0 IEER |
|||
VRF multisplit system with heat recovery 86°F entering water |
11.8 EER 15.8 IEER |
||||
≥135,000 Btu/h and <240,000 Btu/h | VRF multisplit system 86°F entering water |
10.0 EER 14.0 IEER |
|||
VRF multisplit system with heat recovery 86°F entering water |
9.8 EER 13.8 IEER |
||||
≥240,000 Btu/h | VRF multisplit system 86°F entering water |
10.0 EER 12.0 IEER |
|||
VRF multisplit system with heat recovery 86°F entering water |
9.8 EER 11.8 IEER |
||||
VRF groundwater source (cooling mode) |
<135,000 Btu/h | All | VRF multisplit system 59°F entering water |
16.2 EER | AHRI 1230 |
VRF multisplit system with heat recovery 59°F entering water |
16.0 EER | ||||
≥135,000 Btu/h | VRF multisplit system 59°F entering water |
13.8 EER | |||
VRF multisplit system with heat recovery 59°F entering water |
13.6 EER | ||||
VRF ground source (cooling mode) |
<135,000 Btu/h | All | VRF multisplit system 77°F entering water |
13.4 EER | AHRI 1230 |
VRF multisplit system with heat recovery 77°F entering water |
13.2 EER | ||||
≥135,000 Btu/h | VRF multisplit system 77°F entering water |
11.0 EER | |||
VRF multisplit system with heat recovery 77°F entering water |
10.8 EER | ||||
VRF air cooled (heating mode) |
<65,000 Btu/h (cooling capacity) |
VRF multisplit system | 7.7 HSPF | AHRI 1230 | |
≥65,000 Btu/h and <135,000 Btu/h (cooling capacity) |
VRF multisplit system 47°F db/43°F wb outdoor air | 3.3 COPH | |||
17°F db/15°F wb outdoor air |
2.25 COPH | ||||
≥135,000 Btu/h (cooling capacity) |
VRF multisplit system 47°F db/43°F wb outdoor air |
3.2 COPH | |||
17°F db/15°F wb outdoor air |
2.05 COPH | ||||
VRF water source (heating mode) |
<65,000 Btu/h (cooling capacity) |
VRF multisplit system 68°F entering water |
4.3 COPH | AHRI 1230 | |
≥65,000 Btu/h and <135,000 Btu/h (cooling capacity) |
VRF multisplit system 68°F entering water |
4.3 COPH | |||
≥135,000 Btu/h and <240,000 Btu/h (cooling capacity) |
VRF multisplit system 68°F entering water |
4.0 COPH | |||
≥240,000 Btu/h (cooling capacity) | VRF multisplit system 68°F entering water |
3.9 COPH | |||
VRF groundwater source (heating mode) |
<135,000 Btu/h (cooling capacity) |
VRF multisplit system 50°F entering water |
3.6 COPH | AHRI 1230 | |
≥135,000 Btu/h (cooling capacity) |
VRF multisplit system 50°F entering water |
3.3 COPH | |||
VRF ground source (heating mode) |
<135,000 Btu/h (cooling capacity) |
VRF multisplit system 32°F entering water |
3.1 COPH | AHRI 1230 | |
≥135,000 Btu/h (cooling capacity) |
VRF multisplit system 32°F entering water |
2.8 COPH |
Table 6.8.1-10 Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms—Minimum Efficiency Requirements
Equipment Type | Standard Model | Net Sensible Cooling Capacity | Minimum Net Sensible COP | Rating Conditions Return air (dry bulb/dew point) | Test Procedure |
---|---|---|---|---|---|
Air cooled | Downflow | <80,000 Btu/h | 2.70 | 85°F/52°F (Class 2) | AHRI 1360 |
≥80,000 Btu/h and <295,000 Btu/h | 2.58 | ||||
≥295,000 Btu/h | 2.36 | ||||
Upflow—ducted | <80,000 Btu/h | 2.67 | |||
≥80,000 Btu/h and <295,000 Btu/h | 2.55 | ||||
≥295,000 Btu/h | 2.33 | ||||
Upflow—nonducted | <65,000 Btu/h | 2.16 | 75°F/52°F (Class 1) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.04 | ||||
≥240,000 Btu/h | 1.89 | ||||
Horizontal | <65,000 Btu/h | 2.65 | 95°F/52°F (Class 3) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.55 | ||||
≥240,000 Btu/h | 2.47 | ||||
Air cooled with fluid economizer | Downflow | <80,000 Btu/h | 2.70 | 85°F/52°F (Class 1) | AHRI 1360 |
≥80,000 Btu/h and <295,000 Btu/h | 2.58 | ||||
≥295,000 Btu/h | 2.36 | ||||
Upflow—ducted | <80,000 Btu/h | 2.67 | |||
≥80,000 Btu/h and <295,000 Btu/h | 2.55 | ||||
≥295,000 Btu/h | 2.33 | ||||
Upflow—nonducted | <65,000 Btu/h | 2.09 | 75°F/52°F (Class 1) | ||
≥65,000 Btu/h and <240,000 Btu/h | 1.99 | ||||
≥240,000 Btu/h | 1.81 | ||||
Horizontal | <65,000 Btu/h | 2.65 | 95°F/52°F (Class 3) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.55 | ||||
≥240,000 Btu/h | 2.47 | ||||
Water cooled | Downflow | <80,000 Btu/h | 2.82 | 85°F/52°F (Class 1) | AHRI 1360 |
≥80,000 Btu/h and <295,000 Btu/h | 2.73 | ||||
≥295,000 Btu/h | 2.67 | ||||
Upflow—ducted | <80,000 Btu/h | 2.79 | |||
≥80,000 Btu/h and <295,000 Btu/h | 2.70 | ||||
≥295,000 Btu/h | 2.64 | ||||
Upflow—nonducted | <65,000 Btu/h | 2.43 | 75°F/52°F (Class 1) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.32 | ||||
≥240,000 Btu/h | 2.20 | ||||
Horizontal | <65,000 Btu/h | 2.79 | 95°F/52°F (Class 3) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.68 | ||||
≥240,000 Btu/h | 2.60 | ||||
Water cooled with fluid economizer | Downflow | <80,000 Btu/h | 2.77 | 85°F/52°F (Class 1) | AHRI 1360 |
≥80,000 Btu/h and <295,000 Btu/h | 2.68 | ||||
≥295,000 Btu/h | 2.61 | ||||
Upflow—ducted | <80,000 Btu/h | 2.74 | |||
≥80,000 Btu/h and <295,000 Btu/h | 2.65 | ||||
≥295,000 Btu/h | 2.58 | ||||
Upflow—nonducted | <65,000 Btu/h | 2.35 | 75°F/52°F (Class 1) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.24 | ||||
≥240,000 Btu/h | 2.12 | ||||
Horizontal | <65,000 Btu/h | 2.71 | 95°F/52°F (Class 3) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.60 | ||||
≥240,000 Btu/h | 2.54 | ||||
Glycol cooled | Downflow | <80,000 Btu/h | 2.56 | 85°F/52°F (Class 1) | AHRI 1360 |
≥80,000 Btu/h and <295,000 Btu/h | 2.24 | ||||
≥295,000 Btu/h | 2.21 | ||||
Upflow, ducted | <80,000 Btu/h | 2.53 | |||
≥80,000 Btu/h and <295,000 Btu/h | 2.21 | ||||
≥295,000 Btu/h | 2.18 | ||||
Upflow, nonducted | <65,000 Btu/h | 2.08 | 75°F/52°F (Class 1) | ||
≥65,000 Btu/h and <240,000 Btu/h | 1.90 | ||||
≥240,000 Btu/h | 1.81 | ||||
Horizontal | <65,000 Btu/h | 2.48 | 95°F/52°F (Class 3) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.18 | ||||
≥240,000 Btu/h | 2.18 | ||||
Glycol cooled with fluid economizer | Downflow | <80,000 Btu/h | 2.51 | 85°F/52°F (Class 1) | AHRI 1360 |
≥80,000 Btu/h and <295,000 Btu/h | 2.19 | ||||
≥295,000 Btu/h | 2.15 | ||||
Upflow, ducted | <80,000 Btu/h | 2.48 | |||
≥80,000 Btu/h and <295,000 Btu/h | 2.16 | ||||
≥295,000 Btu/h | 2.12 | ||||
Upflow, nonducted | <65,000 Btu/h | 2.00 | 75°F/52°F (Class 1) | ||
≥65,000 Btu/h and <240,000 Btu/h | 1.82 | ||||
≥240,000 Btu/h | 1.73 | ||||
Horizontal | <65,000 Btu/h | 2.44 | 95°F/52°F (Class 3) | ||
≥65,000 Btu/h and <240,000 Btu/h | 2.10 | ||||
≥240,000 Btu/h | 2.10 |
Table 6.8.1-11 Commercial Refrigerators, Commercial Freezers, and Refrigeration—Minimum Efficiency Requirements
Equipment Category | Condensing Unit Configuration | Equipment Family | Rating Temp., °F | Operating Temp., °F | Equipment Classificationc | Maximum Daily Energy Consumption, kWh/dayd,e | Test Standard |
---|---|---|---|---|---|---|---|
Remote condensing commercial refrigerators and commercial freezers | Remote (RC) | Vertical open (VOP) | 38 (M) | ≥32 | VOP.RC.M | 0.64 × TDA + 4.07 | AHRI 1200 |
0 (L) | <32 | VOP.RC.L | 2.20 × TDA + 6.85 | ||||
Semivertical open (SVO) | 38 (M) | ≥32 | SVO.RC.M | 0.66 × TDA + 3.18 | |||