Reporting of emergencies, coordination with emergency response forces, emergency plans and procedures for managing or responding to emergencies shall comply with the provisions of this section.
Exception: Firms that have approved on-premises fire-fighting organizations and that are in compliance with approved procedures for fire reporting.
Where required by this code, fire safety plans, emergency procedures and employee training programs shall be approved by the
fire code official.
Notification of emergency responders shall be in accordance with Sections
401.3.1 through
401.3.3.
In the event an
unwanted fire occurs on a property, the
owner or occupant shall immediately report such condition to the fire department.
Upon activation of a
fire alarm signal, employees or staff shall immediately notify the fire department.
A person shall not, by verbal or written directive, require any delay in the reporting of a fire to the fire department.
In the event an
unwanted fire is detected in a building or a
fire alarm activates, the emergency plan shall be implemented.
A person shall not give, signal or transmit a
false alarm.
Evacuations made necessary by the unplanned activation of a
fire alarm system or by any other emergency shall not be substituted for a required evacuation drill.
It shall be unlawful to interfere with, attempt to interfere with, conspire to interfere with, obstruct or restrict the mobility of or block the path of travel of a fire department emergency vehicle in any way, or to interfere with, attempt to interfere with, conspire to interfere with, obstruct or hamper any fire department operation.
In addition to the requirements of
Section 401, occupancies, uses and outdoor locations shall comply with the emergency preparedness requirements set forth in Sections
403.2 through
403.12.3.3. Where a fire safety and evacuation plan is required by Sections
403.2 through
403.11.5, evacuation drills shall be in accordance with
Section 405 and employee training shall be in accordance with
Section 406.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for Group A
occupancies, other than those occupancies used exclusively for purposes of religious worship with an
occupant load less than 2,000, and for buildings containing both a Group A occupancy and an
atrium. Group A occupancies shall comply with Sections
403.2.1 through
403.2.4.
In addition to the requirements of
Section 404.2, the fire safety and evacuation plans for assembly occupancies shall include a detailed seating plan,
occupant load and
occupant load limit. Deviations from the
approved plans shall be allowed provided that the
occupant load limit for the occupancy is not exceeded and the
aisles and
exit accessways remain unobstructed.
In theaters, motion picture theaters, auditoriums and similar assembly occupancies in Group A used for noncontinuous programs, an audible announcement shall be made not more than 10 minutes prior to the start of each program to notify the occupants of the location of the exits to be used in the event of a fire or other emergency.
Exception: In motion picture theaters, the announcement is allowed to be projected on the screen in a manner approved by the fire code official.
AMENDMENT
This section has been amended at the state or city level.
Places of assembly having continuous entertainment, music or other programs, shall announce the locations of
exits at the change of each entertainment set, but no less frequently than every 90 minutes.
AMENDMENT
This section has been amended at the state or city level.
Conventions, trade shows and exhibition events shall be conducted in accordance with fire safety requirements of the fire
department and the
Department of Licenses and Inspections.
The fire safety and evacuation plan required by
Section 404 shall include a description of special staff actions. This shall include procedures for stabilizing patients in a defend-in-place response, staged evacuation, or full evacuation in conjunction with the entire building if part of a multitenant
facility.
Employees shall be periodically instructed and kept informed of their duties and responsibilities under the plan. Records of instruction shall be maintained. Such instruction shall be reviewed by the staff not less than every two months. A copy of the plan shall be readily available at all times within the
facility.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for Group E occupancies and for buildings containing both a Group E occupancy and an
atrium. Group E occupancies shall comply with Sections
403.5.1 through
403.5.3.
Emergency evacuation drills shall be conducted at different hours of the day or evening, during the changing of classes, when the school is at assembly, during the recess or gymnastic periods, or during other times to avoid distinction between drills and actual fires.
Outdoor assembly areas shall be designated and shall be located a safe distance from the building being evacuated so as to avoid interference with fire department operations. The assembly areas shall be arranged to keep each class separate to provide accountability of all individuals.
An approved fire safety and evacuation plan in accordance with Section 404 shall be prepared and maintained for buildings containing a Group F occupancy where any of the following conditions apply:
- The Group F occupancy has an occupant load of 500 or more persons.
- The Group F occupancy has an occupant load of more than 100 persons above or below the lowest level of exit discharge.
- Group F pallet manufacturing and recycling facilities as required by Section 2810.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for Group H occupancies.
In addition to the requirements of
Section 404 and
Section 407.6, plans and diagrams shall be maintained in approved locations indicating the approximate plan for each area, the amount and type of HPM stored, handled and used, locations of shutoff valves for HPM supply piping, emergency telephone locations and locations of
exits.
The plans and diagrams required by Sections
404,
403.7.1.1 and
407.6 shall be maintained up to date and the
fire code official and fire department shall be informed of major changes.
Responsible persons shall be designated as an on-
site emergency response team and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses, identifying locations where HPM is stored, handled and used, and be familiar with the
chemical nature of such material. An adequate number of personnel for each work shift shall be designated.
Emergency drills of the on-
site emergency response team shall be conducted on a regular basis but not less than once every three months. Records of drills conducted shall be maintained.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for Group I occupancies. Group I occupancies shall comply with Sections
403.8.1 through
403.8.3.4.
The fire safety and evacuation plan required by
Section 404 shall include special employee actions, including fire protection procedures necessary for residents, and shall be amended or revised upon admission of any resident with unusual needs.
The fire evacuation plan required by
Section 404 shall include a description of special staff actions. In addition to the requirements of
Section 404, plans in Group I-
1, Condition 2 occupancies shall include procedures for evacuation through a refuge area in an adjacent
smoke compartment and then to an exterior assembly point.
A copy of the fire safety plan shall be maintained at the facility at all times. Plans shall include the following in addition to the requirements of Section 404:
- Location and number of resident sleeping rooms.
- Location of special locking or egress control arrangements.
Employees shall be periodically instructed and kept informed of their duties and responsibilities under the plan. Such instruction shall be reviewed by employees at intervals not exceeding two months. A copy of the plan shall be readily available at all times within the
facility.
Residents capable of assisting in their own evacuation shall be trained in the proper actions to take in the event of a fire. In Group I-
1, Condition 2 occupancies, training shall include evacuation through an adjacent
smoke compartment and then to an exterior assembly point. The training shall include actions to take if the primary escape route is blocked. Where the resident is given rehabilitation or habilitation training, methods of fire prevention and actions to take in the event of a fire shall be a part of the rehabilitation training program. Residents shall be trained to assist each other in case of fire to the extent their physical and mental abilities
permit them to do so without additional personal risk.
In addition to the evacuation drills required in
Section 405.2, employees shall participate in drills an additional two times a year on each shift. Twelve drills with all occupants shall be conducted in the first year of operation. Drills are not required to comply with the time requirements of
Section 405.4.
The fire safety and evacuation plans required by Section 404 shall include a description of special staff actions. Plans shall include all of the following in addition to the requirements of Section 404.
- Procedures for evacuation for patients with needs for containment or restraint and post-evacuation containment, where present.
- A written plan for maintenance of the means of egress.
- Procedure for a defend-in-place strategy.
- Procedures for a full-floor or building evacuation, where necessary.
A copy of the plan shall be maintained at the facility at all times. Plans shall include all of the following in addition to the requirements of Section 404:
- Location and number of patient sleeping rooms and operating rooms.
- Location of adjacent smoke compartments or refuge areas.
- Path of travel to adjacent smoke compartments.
- Location of special locking, delayed egress or access control arrangements.
- Location of elevators utilized for patient movement in accordance with the fire safety plan, where provided.
Emergency evacuation drills shall comply with Section 405.
Exceptions:
- The movement of patients to safe areas or to the exterior of the building is not required.
- Where emergency evacuation drills are conducted after visiting hours or where patients or residents are expected to be asleep, a coded announcement shall be an acceptable alternative to audible alarms.
Employees shall be instructed in the proper use of portable fire extinguishers and other manual fire suppression equipment. Training of new employees shall be provided promptly upon entrance to duty. Refresher training shall be provided not less than annually.
Group I-3 occupancies shall be provided with 24-hour staffing. An employee shall be within three floors or 300 feet (91 440 mm) horizontal distance of the access door of each resident housing area. In Group I-3 Conditions 3, 4 and 5, as defined in Chapter 2, the arrangement shall be such that the employee involved can start release of locks necessary for emergency evacuation or rescue and initiate other necessary emergency actions within 2 minutes of an alarm.
Exception: An employee shall not be required to be within three floors or 300 feet (91 440 mm) horizontal distance of the access door of each resident housing area in areas in which all locks are unlocked remotely and automatically in accordance with Section 408.4 of the International Building Code.
Provisions shall be made for residents in Group I-3 Conditions 3, 4 and 5, as defined in
Chapter 2, to readily notify an employee of an emergency.
Keys necessary for unlocking doors installed in a
means of egress shall be individually identifiable by both touch and sight.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for buildings containing a Group M occupancy where the Group M occupancy has an
occupant load of 500 or more persons or more than 100 persons above or below the lowest l
evel of exit discharge and for buildings containing both a Group M occupancy and an
atrium.
An approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for Group R-1 occupancies. Group R-1 occupancies shall comply with Sections
403.10.1.1 through
403.10.1.3.
A diagram depicting two evacuation routes shall be posted on or immediately adjacent to every required egress door from each hotel or motel
sleeping unit.
Upon discovery of a fire or suspected fire, hotel and motel employees shall perform the following duties:
- Activate the fire alarm system, where provided.
- Notify the public fire department.
- Take other action as previously instructed.
Information shall be provided in the fire safety and evacuation plan required by
Section 404 to allow guests to decide whether to evacuate to the outside, evacuate to an
area of refuge, remain in place, or any combination of the three.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for Group R-2 college and university buildings. Group R-2 college and university buildings shall comply with Sections
403.10.2.1.1 and
403.10.2.1.2.
Emergency evacuation drills shall be conducted at different hours of the day or evening, during the changing of classes, when school is at assembly, during recess or gymnastic periods or during other times to avoid distinction between drills and actual fires. One required drill shall be held during hours after sunset or before sunrise.
Fire emergency guides shall be provided for Group R-2 occupancies. Guide contents, maintenance and distribution shall comply with Sections
403.10.2.2.1 through
403.10.2.2.3.
A fire emergency guide shall describe the location, function and use of fire protection equipment and appliances available for use by residents, including
fire alarm systems,
smoke alarms and portable fire extinguishers. Guides shall include an emergency evacuation plan for each
dwelling unit.
A copy of the emergency guide shall be given to each tenant prior to initial occupancy.
A diagram depicting two evacuation routes shall be posted on or immediately adjacent to every required egress door from each
dormitory sleeping unit. Evacuation diagrams shall be reviewed and updated as needed to maintain accuracy.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for Group R-4 occupancies. Group R-4 occupancies shall comply with Sections
403.10.3.1 through
403.10.3.6.
The fire safety and evacuation plan required by
Section 404 shall include special employee actions, including fire protection procedures necessary for residents, and shall be amended or revised upon admission of a resident with unusual needs.
A copy of the plan shall be maintained at the facility at all times. Plans shall include the following in addition to the requirements of Section 404:
- Location and number of resident sleeping rooms.
- Location of special locking or egress control arrangements.
Employees shall be periodically instructed and kept informed of their duties and responsibilities under the plan. Records of instruction shall be maintained. Such instruction shall be reviewed by employees at intervals not exceeding two months. A copy of the plan shall be readily available at all times within the
facility.
Residents capable of assisting in their own evacuation shall be trained in the proper actions to take in the event of a fire. The training shall include actions to take if the primary escape route is blocked. Where the resident is given rehabilitation or habilitation training, methods of fire prevention and actions to take in the event of a fire shall be a part of the rehabilitation training program. Residents shall be trained to assist each other in case of fire to the extent their physical and mental abilities
permit them to do so without additional personal risk.
In addition to the evacuation drills required in
Section 405.2, employees shall participate in drills an additional two times a year on each shift. Twelve drills with all occupants shall be conducted in the first year of operation.
Emergency evacuation drills shall involve the actual evacuation of residents to a selected assembly point and shall provide residents with experience in exiting through all required exits. All required exits shall be used during emergency evacuation drills.
Exception: Actual exiting from emergency escape and rescue windows shall not be required. Opening the emergency escape and rescue window and signaling for help shall be an acceptable alternative.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for covered
malls exceeding 50,000 square feet (4645 m
2) in aggregate floor area and for
open mall buildings exceeding 50,000 square feet (4645 m
2) in aggregate area within the perimeter line.
The lease plan shall be submitted to the
fire code official for approval, and shall be maintained on
site for immediate reference by responding fire service personnel.
The lease plans shall be revised annually or as often as necessary to keep them current. Modifications or changes in tenants or occupancies shall not be made without prior approval of the
fire code official and
building official.
Tenant identification shall be provided for secondary exits from occupied tenant spaces that lead to an exit corridor or directly to the exterior of the building. Tenant identification shall be posted on the exterior side of the exit or exit access door and shall identify the business name and address using plainly legible letters and numbers that contrast with their background.
Exception: Tenant identification is not required for anchor stores.
The fire safety and evacuation plan shall provide for compliance with the requirements for unoccupied tenant spaces in
Section 311.
AMENDMENT
This section has been amended at the state or city level.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for
high-rise buildings.
An
approved fire safety and evacuation plan in accordance with
Section 404 shall be prepared and maintained for underground buildings.
In buildings using occupant evacuation elevators in accordance with
Section 3008 of the
International Building Code, the fire safety and evacuation plan and the training required by Sections
404 and
406, respectively, shall incorporate specific procedures for the occupants using such elevators.
Special requirements for public safety shall be in accordance with Sections
403.12.1 through
403.12.3.3.
Where, in the opinion of the
fire code official, it is essential for public safety in a place of assembly or any other place where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest or activity, the
owner,
agent or lessee shall provide one or more
fire watch personnel, as required and
approved.
Fire watch personnel shall comply with Sections
403.12.1.1 and
403.12.1.2.
Fire watch personnel shall remain on duty while places requiring a
fire watch are open to the public, or when an activity requiring a
fire watch is being conducted.
On-duty fire watch personnel shall have the following responsibilities:
- Keep diligent watch for fires, obstructions to means of egress and other hazards.
- Take prompt measures for remediation of hazards and extinguishment of fires that occur.
- Take prompt measures to assist in the evacuation of the public from the structures.
Where the fire code official determines that an indoor or outdoor gathering of persons has an adverse impact on public safety through diminished access to buildings, structures, fire hydrants and fire apparatus access roads or where such gatherings adversely affect public safety services of any kind, the fire code official shall have the authority to order the development of or prescribe a public safety plan that provides an approved level of public safety and addresses the following items:
- Emergency vehicle ingress and egress.
- Fire protection.
- Emergency egress or escape routes.
- Emergency medical services.
- Public assembly areas.
- The directing of both attendees and vehicles, including the parking of vehicles.
- Vendor and food concession distribution.
- The need for the presence of law enforcement.
- The need for fire and emergency medical services personnel.
- The need for a weather monitoring person.
Where
facilities or events involve a gathering of more than 500 people, crowd managers shall be provided in accordance with Sections
403.12.3.1 through
403.12.3.3.
Not fewer than two trained crowd managers, and not fewer than one trained crowd manager for each 250 persons or portion thereof, shall be provided for the gathering.
Exceptions:
- Outdoor events with fewer than 1,000 persons in attendance shall not require crowd managers.
- Assembly occupancies used exclusively for religious worship with an occupant load not exceeding 1,000 shall not require crowd managers.
- The number of crowd managers shall be reduced where, in the opinion of the fire code official, the fire protection provided by the facility and the nature of the event warrant a reduction.
Training for crowd managers shall be approved.
The duties of crowd managers shall include, but not be limited to:
- Conduct an inspection of the area of responsibility and identify and address any egress barriers.
- Conduct an inspection of the area of responsibility to identify and mitigate any fire hazards.
- Verify compliance with all permit conditions, including those governing pyrotechnics and other special effects.
- Direct and assist the event attendees in evacuation during an emergency.
- Assist emergency response personnel where requested.
- Other duties required by the fire code official.
- Other duties as specified in the fire safety plan.
Fire evacuation plans shall include the following:
- Emergency egress or escape routes and whether evacuation of the building is to be complete by selected floors or areas only or with a defend-in-place response.
- Procedures for employees who must remain to operate critical equipment before evacuating.
- Procedures for the use of elevators to evacuate the building where occupant evacuation elevators complying with Section 3008 of the International Building Code are provided.
- Procedures for assisted rescue for persons unable to use the general means of egress unassisted.
- Procedures for accounting for employees and occupants after evacuation has been completed.
- Identification and assignment of personnel responsible for rescue or emergency medical aid.
- The preferred and any alternative means of notifying occupants of a fire or emergency.
- The preferred and any alternative means of reporting fires and other emergencies to the fire department or designated emergency response organization.
- Identification and assignment of personnel who can be contacted for further information or explanation of duties under the plan.
- A description of the emergency voice/alarm communication system alert tone and preprogrammed voice messages, where provided.
Fire safety plans shall include the following:
- The procedure for reporting a fire or other emergency.
The life safety strategy including the following:
- 2.1. Procedures for notifying occupants, including areas with a private mode alarm system.
- 2.2. Procedures for occupants under a defend-in-place response.
- 2.3. Procedures for evacuating occupants, including those who need evacuation assistance.
Site plans indicating the following:
- 3.1. The occupancy assembly point.
- 3.2. The locations of fire hydrants.
- 3.3. The normal routes of fire department vehicle access.
Floor plans identifying the locations of the following:
- 4.1. Exits.
- 4.2. Primary evacuation routes.
- 4.3. Secondary evacuation routes.
4.4. Accessible egress routes.
- 4.4.1. Areas of refuge.
- 4.4.2. Exterior areas for assisted rescue.
- 4.5. Refuge areas associated with smoke barriers and horizontal exits.
- 4.6. Manual fire alarm boxes.
- 4.7. Portable fire extinguishers.
- 4.8. Occupant-use hose stations.
- 4.9. Fire alarm annunciators and controls.
- A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures.
- Identification and assignment of personnel responsible for maintenance of systems and equipment installed to prevent or control fires.
- Identification and assignment of personnel responsible for maintenance, housekeeping and controlling fuel hazard sources.
Lockdown plans shall include the following:
- Identification of individuals authorized to issue a lockdown order.
- Security measures used during normal operations, when the building is occupied, that could adversely affect egress or fire department operations.
- A description of identified emergency and security threats addressed by the plan, including specific lockdown procedures to be implemented for each threat condition.
Means and methods of initiating a lockdown plan for each threat, including:
- 4.1. The means of notifying occupants of a lockdown event, which shall be distinct from the fire alarm signal.
- 4.2. Identification of each door or other access point that will be secured.
- 4.3. A description of the means or methods used to secure doors and other access points.
- 4.4. A description of how locking means and methods are in compliance with the requirements of this code for egress and accessibility.
- Procedures for reporting to the fire department any lockdown condition affecting egress or fire department operations.
- Procedures for determining and reporting the presence or absence of occupants to emergency response agencies during a lockdown.
- Means for providing two-way communication between a central location and each area subject to being secured during a lockdown.
- Identification of the prearranged signal for terminating the lockdown.
- Identification of individuals authorized to issue a lockdown termination order.
- Procedures for unlocking doors and verifying that the means of egress has been returned to normal operations upon termination of the lockdown.
- Training procedures and frequency of lockdown plan drills.
Lockdown plan drills shall be conducted in accordance with the approved plan. Such drills shall not be substituted for fire and evacuation drills required by
Section 405.2.
Fire safety and evacuation plans shall be reviewed or updated annually or as necessitated by changes in staff assignments, occupancy or the physical arrangement of the building.
Fire safety and evacuation plans shall be available in the workplace for reference and review by employees, and copies shall be furnished to the
fire code official for review on request.
The fire safety and evacuation plans shall be distributed to the tenants and building service employees by the
owner or
owner's
agent. Tenants shall distribute to their employees applicable parts of the fire safety plan affecting the employees' actions in the event of a fire or other emergency.
Responsibility for the planning and conduct of drills shall be assigned to competent persons designated to exercise leadership.
Drills shall be held at unexpected times and under varying conditions to simulate the unusual conditions that occur in case of fire.
Records shall be maintained of required emergency evacuation drills and include the following information:
- Identity of the person conducting the drill.
- Date and time of the drill.
- Notification method used.
- Employees on duty and participating.
- Number of occupants evacuated.
- Special conditions simulated.
- Problems encountered.
- Weather conditions when occupants were evacuated.
- Time required to accomplish complete evacuation.
As building occupants arrive at the assembly point, efforts shall be made to determine if all occupants have been successfully evacuated or have been accounted for.
An electrically or mechanically operated signal used to recall occupants after an evacuation shall be separate and distinct from the signal used to initiate the evacuation. The recall signal initiation means shall be manually operated and under the control of the person in charge of the premises or the official in charge of the incident. Persons shall not reenter the premises until authorized to do so by the official in charge.
Where fire safety and evacuation plans are required by
Section 403, employees shall be trained in fire emergency procedures based on plans prepared in accordance with
Section 404.
Employees shall receive training in the contents of fire safety and evacuation plans and their duties as part of new employee orientation and not less than annually thereafter. Records of training shall be maintained.
Employees shall be trained in fire prevention, evacuation and fire safety in accordance with Sections
406.3.1 through
406.3.4.
Employees shall be apprised of the fire hazards of the materials and processes to which they are exposed. Each employee shall be instructed in the proper procedures for preventing fires in the conduct of their assigned duties.
Employees shall be familiarized with the
fire alarm and evacuation signals, their assigned duties in the event of an alarm or emergency, evacuation routes,
areas of refuge, exterior assembly areas and procedures for evacuation.
Employees assigned fire-fighting duties shall be trained to know the locations and proper use of portable fire extinguishers or other manual fire-fighting equipment and the protective clothing or equipment required for its safe and proper use.
Where a
facility has a
lockdown plan, employees shall be trained on their assigned duties and procedures in the event of an emergency
lockdown.
Persons responsible for the operation of areas in which
hazardous materials are stored, dispensed, handled or used shall be familiar with the
chemical nature of the materials and the appropriate mitigating actions necessary in the event of a fire, leak or spill. Responsible persons shall be designated and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses and identification of where
hazardous materials are located, and shall have
access to
Safety Data Sheets and be knowledgeable in the
site emergency response procedures.
AMENDMENT
This section has been amended at the state or city level.
AMENDMENT
This section has been amended at the state or city level.
Pursuant to the Pennsylvania Uniform Construction Code Act (UCC), and Section B-429 of the
Philadelphia Building Code, child day care
facilities are permitted to operate in a one or two-family
dwelling unit (home) provided the
facility conforms to this Section.
AMENDMENT
This section has been amended at the state or city level.
A
dwelling unit where child day care services are provided for 12 or fewer children shall be classified as an R-3 occupancy and as a Family Child Day Care
Facility, provided that it is in accordance with all of the following:
- The dwelling unit is contained within a one or two-family dwelling.
- Child day care services are provided for less than 24 hours.
- The dwelling unit is used primarily as a private residence.
- The provision of child day care services is accessory to the principal use of the dwelling unit as a residence.
AMENDMENT
This section has been amended at the state or city level.
A license to operate a Family Child Day Care
Facility shall be required pursuant to Section F-105.6.2.
AMENDMENT
This section has been amended at the state or city level.
At least one portable fire extinguisher with a minimum rating of 2A:10-B:C shall be mounted in the portion of the building used for the Family Child Day Care
Facility and in kitchens and other cooking areas used by the Family Child Day Care
Facility.
AMENDMENT
This section has been amended at the state or city level.
Portable heating devices that produce an open flame shall not be used in buildings during the operating hours of a Family Child Day Care
Facility.
AMENDMENT
This section has been amended at the state or city level.
Family Child Day Care
Facilities that are classified as Group R3 occupancies pursuant to Section B-429.1.1 of the
Philadelphia Building Code with six or fewer children shall comply with Sections F-408.4.1and F-408.4.2.
AMENDMENT
This section has been amended at the state or city level.
A
single-station smoke alarm shall be installed in each
story including
basements. The
smoke alarms shall be powered by either the building wiring
system or 10-year, non-removable batteries, both of which shall be listed by Underwriters Laboratories and shall sound an alarm when activated that is audible to persons in the
dwelling unit's
indoor child care spaces with all intervening doors closed. Where battery powered
smoke alarms are used, the building
owner shall keep the proof and date of purchase of the
smoke alarms in the unit's fire drill logs.
AMENDMENT
This section has been amended at the state or city level.
The
dwelling unit and the accessory Family Child Day Care
Facility shall comply with the
means of egress requirements for an R-3 occupancy and licensure under 55 PA Code Chapter 3290 (relating to Family Child Day Care
Facilities).
AMENDMENT
This section has been amended at the state or city level.
Family Child Day Care
Facilities that are classified as Group R3 occupancies pursuant to Section B-429.1.1 of the
Philadelphia Building Code that provide child day care services to more than six but no more than 12 children shall comply with Sections F-408.5.1 through F-408.5.2.
AMENDMENT
This section has been amended at the state or city level.
The
dwelling unit and the accessory Family Child Day Care
Facility shall comply with the
means of egress requirements for an R-3 occupancy and licensure under 55 PA Code Chapter 3280 (relating to Group Child Day Care
Facilities).