ICC Performance Code for Buildings and Facilities 2018 (ICCPC 2018)

Heads up: There are no amended sections in this chapter.

User note:

About this chapter: Chapter 4 underscores the importance of the reliability of individual protection systems and strategies, as well as the reliability of the interaction of these systems in achieving the design performance level for a particular building or facility addressed in Chapter 3. Reliability is a function of many factors, including redundancy, maintenance, durability of materials, quality of installations and integrity of design.

To ensure reliability of the system necessary to meeting the performance objectives of building, facility or processes in accordance with the design.
Design, install and maintain systems, system components and equipment that provide a safety function in strict accordance with the manufacturers' instructions and with any applicable codes and standards.
Test and inspect systems, system components and equipment that provide a safety function in strict accordance with the manufacturers' instructions and with any applicable codes and standards for both the methods employed and the frequency.
Active fire protection systems such as fire alarm, suppression and smoke management systems shall undergo commissioning testing when first placed into service or following any substantial alteration.
Provide appropriate training to any people who operate, test, maintain or interpret information from any safety systems. Where such work is done by contractors, ensure that they have the necessary training and skills.
Design, installation and maintenance shall be performed only by qualified people as approved. Certification or records of training shall be provided.

Documentation shall be maintained at the building that details the systems installed and their required maintenance and testing methods and frequency. Records of such maintenance and testing shall be maintained that demonstrate compliance, the persons conducting the work and their qualifications.

To assist in the selection of appropriate materials and construction systems.
To ensure that a building will continue to satisfy the objectives of this code throughout its life.
From the time a certificate of occupancy is issued, primary building elements shall, with only normal maintenance, continue to satisfy the performance requirements of this code for the intended life of the building.
Where the useful life of building or facility elements or systems is less than the intended life of the building, provisions shall be made for timely replacement of those elements, so that the objective of this code and the design are maintained.
Where damage or deterioration to building or facility elements or systems will impact the objectives of this code or the design, those elements or systems shall be repaired or replaced in order to maintain the level of performance intended by this code.
In determining the useful service life of building elements, products or systems, an acceptable method for determining durability and service life shall be used.