Fire barrier walls shall meet the requirements of
this chapter and Chapter 4 except as modified by this chapter.
Fire barrier walls shall be continuous from one of the following or a combination thereof:
- An exterior wall to an exterior wall
- A floor below to a floor or roof above
- One fire barrier wall to another fire barrier wall, fire wall, or HC fire wall having a fire resistance rating of not less than that required for the fire barrier wall
Fire barrier walls shall be continuous through all concealed
spaces, such as those found above a ceiling, including
interstitial spaces.
Afire barrier wall required for an occupied space below
an interstitial space shall not be required to extend through
the interstitial space, provided that the construction assembly
forming the bottom of the interstitial space has a fire resistance
rating not less than that of the fire barrier wall.
The fire barrier wall shall be permitted to terminate at
an individually protected structural member in the same
plane, provided the structural member has a fire resistance
rating of not less than that required for the fire barrier wall.
Structural elements supporting fire barrier walls shall have a fire resistance rating of not less than required for the wall except as modified by NFPA 220, Standard on Types of Building Construction, 5.1.2.2.
Openings permitted in fire barrier walls shall comply
with the requirements of Sections 4.8 and 7.3.