Cord-and-plug-connected appliances shall use cords suitable for the environment and physical conditions likely to be encountered. Flexible cords shall be used only where the appliance is listed to be connected with a flexible cord. The cord shall be identified as suitable for the purpose in the installation instructions of the appliance manufacturer. Receptacles for cord-and-plug-connected appliances shall be accessible and shall be located to avoid physical damage to the flexible cord. Except for a listed appliance marked to indicate that it is protected by a system of double-insulation, the flexible cord supplying an appliance shall terminate in a grounding-type attachment plug. A receptacle for a cord-and-plug- connected range hood shall be supplied by an individual branch circuit. Specific appliances have additional requirements as specified in Table E4101.3 (see Section E3909).
TABLE E4101.3
FLEXIBLE CORD LENGTH
MINIMUM CORD LENGTH (inches) | MAXIMUM CORD LENGTH (inches) | |
18 | 36 | |
Built-in dishwasher | 36 | 48 |
Trash compactor | 36 | 48 |
Range hoods | 18 | 36 |
For SI: 1 inch = 25.4 mm.
Each appliance shall be provided with a means to disconnect all ungrounded supply conductors. For fixed electric space-heating equipment, means shall be provided to disconnect the heater and any motor controller(s) and supplementary overcurrent-protective devices. Switches and circuit breakers used as a disconnecting means shall be of the indicating type. Disconnecting means shall be as set forth in Table E4101.5.
TABLE E4101.5
DISCONNECTING MEANS
DESCRIPTION | ALLOWED DISCONNECTING MEANS |
Permanently connected appliance rated at not over 300 volt-amperes or 1/8 horsepower. | Branch-circuit overcurrent device. |
Permanently connected appliances rated in excess of 300 volt-amperes or 1/8 horsepower. | Branch circuit breaker or switch located within sight of appliance or such devices in any location that are capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. |
Appliances listed for cord-and-plug connection. | A separable connector or attachment plug and receptacle provided with access. |
Permanently installed heating equipment with motors rated at not over 1/8 horsepower with supplementary overcurrent protection. | Disconnect, on the supply side of fuses, in sight from the supplementary overcurrent device, and in sight of the heating equipment or, in any location, if capable of being locked in the open position. |
Heating equipment containing motors rated over 1/8 horsepower with supplementary overcurrent protection. | Disconnect permitted to serve as required disconnect for both the heating equipment and the controller where, on the supply side of fuses, and in sight from the supplementary overcurrent devices, if the disconnecting means is also in sight from the controller, or is capable of being locked off and simultaneously disconnects the heater, motor controller(s) and supplementary overcurrent protective devices from all ungrounded conductors. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. The disconnecting means shall have an ampere rating not less than 125 percent of the total load of the motors and the heaters. |
Heating equipment containing no motor rated over 1/8 horsepower without supplementary overcurrent protection. | Branch-circuit switch or circuit breaker where within sight from the heating equipment or capable of being locked off and simultaneously disconnects the heater, motor controller(s) and supplementary overcurrent protective devices from all ungrounded conductors. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. The disconnecting means shall have an ampere rating not less than 125 percent of the total load of the motors and the heaters. |
Heating equipment containing motors rated over 1/8 horsepower without supplementary overcurrent protection. | Disconnecting means in sight from motor controller or as provided for heating equipment with motor rated over 1/8 horsepower with supplementary overcurrent protection and simultaneously disconnects the heater, motor controller(s) and supplementary overcurrent protective devices from all ungrounded conductors. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. The disconnecting means shall have an ampere rating not less than 125 percent of the total load of the motors and the heaters. |
Air-conditioning condensing units and heat pump units. | A readily accessible disconnect within sight from unit as the only allowable means.a |
Appliances and fixed heating equipment with unit switches having a marked OFF position. | Unit switch where an additional individual switch or circuit breaker serves as a redundant disconnecting means. |
Thermostatically controlled fixed heating equipment. | Thermostats with a marked OFF position that directly open all ungrounded conductors, which when manually placed in the OFF position are designed so that the circuit cannot be energized automatically and that are located within sight of the equipment controlled. |
For SI: 1 horsepower = 0.746 kW.
a. The disconnecting means shall be permitted to be installed on or within the unit. It shall not be located on panels designed to allow access to the unit or located so as to obscure the air-conditioning equipment nameplate(s).