UpCodes logo
Table of contentsContents
The provisions of this chapter shall apply to existing buildings constructed prior to the adoption of this code.
The intent of this chapter is to provide a minimum degree of fire and life safety to persons occupying existing buildings by providing for alterations to such buildings that do not comply with the minimum requirements of the International Building Code.
Permits shall be required as set forth in Section 105.7 and the International Building Code and this code.
Where a building is found to be in noncompliance, the fire code official shall duly notify the owner of the building. Upon receipt of such notice, the owner shall, subject to the following time limits, take necessary actions to comply with the provisions of this chapter.
Construction documents for the necessary alterations shall be completed within a time schedule approved by the fire code official.
Work on the required alterations to the building shall be completed within a time schedule approved by the fire code official.
The fire code official is authorized to grant necessary extensions of time when it can be shown that the specified time periods are not physically practical or pose an undue hardship. The granting of an extension of time for compliance shall be based on the showing of good cause and subject to the filing of an acceptable systematic plan of correction with the fire code official.
The following word and term shall, for the purpose of this chapter and as used elsewhere in this code, have the meaning shown herein.
EXISTING. Buildings, facilities or conditions that are already in existence, constructed or officially authorized prior to the adoption of this code.
Existing buildings shall comply with not less than the minimum provisions specified in Table 4603.1 and as further enumerated in Sections 4603.2 through 4603.7.3. The provisions of this chapter shall not be construed to allow the elimination of fire protection systems or a reduction in the level of fire safety provided in buildings constructed in accordance with previously adopted codes.
Exception: Group U occupancies.
TABLE 4603.1
OCCUPANCY AND USE REQUIREMENTS
SECTION USE OCCUPANCY CLASSIFICATION
HIgh rise Atrium and
covered mall
Under- ground
building
A B E F H-1 H-2 H-3 H-4 H-5 I-1 I-2 I-3 I-4 M R-1 R-2 R-3 R-4 S
4603.2 R R R R R R R R R R R R R R R R R R R R R
4603.3.1 R R R R R R
4603.3.2 R R R R R R R R R R R R R R R R
4603.3.3 R R R R R R R R R R R R R R R R
4603.3.4 R
4603.3.5 R R
4603.3.6 R R R R R R R R R R R R R R R R R
4603.3.7 R R R R R R R R R R R R R R R R R
4603.4 R R R R R
4603.5 R R R R R R R R R R R R R R R R R R R R
4603.6.1 R
4603.6.2 R
4603.6.3 R
4603.6.4 R
4603.6.5 R
4603.6.6 R
4603.6.7 R
4603.7 R R R R
4604.4 R R R R R R R R R R R R R R R R R R R R R R
R = The building is required to comply.
Existing elevators with a travel distance of 25 feet (7620 mm) or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3.
Interior vertical shafts, including but not limited to stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building, shall be enclosed or protected as specified in Sections 4603.3.1 through 4603.3.7.
In Group I occupancies, interior vertical openings connecting two or more stories shall be protected with 1-hour fire-resistance-rated construction.
In other than Group I occupancies, interior vertical openings connecting three to five stories shall be protected by either 1-hour fire-resistance-rated construction or an automatic sprinkler system shall be installed throughout the building in accordance with Section 903.3.1.1 or 903.3.1.2.

Exceptions:
  1. Vertical opening protection is not required for Group R-3 occupancies.
  2. Vertical opening protection is not required for open parking garages and ramps.
  3. Vertical opening protection for escalators shall be in accordance with Section 4603.3.5, 4603.3.6 or 4603.3.7.
In other than Group I occupancies, interior vertical openings connecting more than five stories shall be protected by 1-hour fire-resistance-rated construction.

Exceptions:
  1. Vertical opening protection is not required for Group R-3 occupancies.
  2. Vertical opening protection is not required for open parking garages and ramps.
  3. Vertical opening protection for escalators shall be in accordance with Section 4603.3.5, 4603.3.6 or 4603.3.7.
In other than Group I occupancies, interior vertical openings in a covered mall building or a building with an atrium shall be protected by either 1-hour fire-resistance-rated construction or an automatic sprinkler system shall be installed throughout the building in accordance with Section 903.3.1.1 or 903.3.1.2.
Exceptions:
  1. Vertical opening protection is not required for Group R-3 occupancies.
  2. Vertical opening protection is not required for open parking garages and ramps.
Escalators creating vertical openings connecting any number of stories shall be protected by either 1-hour fire-resistance-rated construction or an automatic fire sprinkler system in accordance with Section 903.3.1.1 installed throughout the building, with a draft curtain and closely spaced sprinklers around the escalator opening.
In other than Group B and M occupancies, escalators creating vertical openings connecting four or fewer stories shall be protected by either 1-hour fire-resistance-rated construction or an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 shall be installed throughout the building, and a draft curtain with closely spaced sprinklers shall be installed around the escalator opening.
In other than Group B and M occupancies, escalators creating vertical openings connecting five or more stories shall be protected by 1-hour fire-resistance-rated construction.
An automatic sprinkler system shall be provided in existing buildings in accordance with Sections 4603.4.1 and 4603.4.2.
An automatic sprinkler system shall be provided throughout existing buildings where cellulose nitrate film or pyroxylin plastics are manufactured, stored or handled in quantities exceeding 100 pounds (45 kg). Vaults located within buildings for the storage of raw pyroxylin shall be protected with an approved automatic sprinkler system capable of discharging 1.66 gallons per minute per square foot (68 L/min/m2) over the area of the vault.
An automatic sprinkler system shall be provided throughout existing Group I-2 fire areas. The sprinkler system shall be provided throughout the floor where the Group I-2 occupancy is located, and in all floors between the Group I-2 occupancy and the level of exit discharge.
Existing structures with occupied floors located more than 50 feet (15 240 mm) above or below the lowest level of fire department vehicle access shall be equipped with standpipes installed in accordance with Section 905. The standpipes shall have an approved fire department connection with hose connections at each floor level above or below the lowest level of fire department access. The fire code official is authorized to approve the installation of manual standpipe systems to achieve compliance with this section where the responding fire department is capable of providing the required hose flow at the highest standpipe outlet.
An approved fire alarm system shall be installed in existing buildings and structures in accordance with Sections 4603.6.1 through 4603.6.7 and provide occupant notification in accordance with Section 907.6 unless other requirements are provided by other sections of this code.
Exception: Occupancies with an existing, previously approved fire alarm system.
A fire alarm system shall be installed in existing Group E occupancies in accordance with Section 907.2.3.
Exceptions:
  1. A manual fire alarm system is not required in a building with a maximum area of 1,000 square feet (93 m2) that contains a single classroom and is located no closer than 50 feet (15 240 mm) from another building.
  2. A manual fire alarm system is not required in Group E occupancies with an occupant load less than 50.
An automatic fire alarm system shall be installed in existing Group I-1 residential care/assisted living facilities in accordance with Section 907.2.6.1.
Exceptions:
  1. Manual fire alarm boxes in resident or patient sleeping areas shall not be required at exits if located at all nurses' control stations or other constantly attended staff locations, provided such stations are visible and continuously accessible and that travel distances required in Section 907.5.2 are not exceeded.
  2. Where each sleeping room has a means of egress door opening directly to an exterior egress balcony that leads directly to the exits in accordance with Section 1019, and the building is not more than three stories in height.
An automatic fire alarm system shall be installed in existing Group I-2 occupancies in accordance with Section 907.2.6.2.
Exception: Manual fire alarm boxes in resident or patient sleeping areas shall not be required at exits if located at all nurses' control stations or other constantly attended staff locations, provided such stations are visible and continuously accessible and that travel distances required in Section 907.5.2.1 are not exceeded.
An automatic and manual fire alarm system shall be installed in existing Group I-3 occupancies in accordance with Section 907.2.6.3.
A fire alarm system and smoke alarms shall be installed in existing Group R-1 occupancies in accordance with Sections 4603.6.5.1 through 4603.6.5.2.1.
A manual fire alarm system that activates the occupant notification system in accordance with Section 907.6 shall be installed in existing Group R-1 hotels and motels more than three stories or with more than 20 sleeping units.
Exceptions:
  1. Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, exit court or yard.
  2. Manual fire alarm boxes are not required throughout the building when the following conditions are met:
    1. The building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2;
    2. The notification appliances will activate upon sprinkler water flow; and
    3. At least one manual fire alarm box is installed at an approved location.
An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.6 shall be installed in existing Group R-1 hotels and motels throughout all interior corridors serving sleeping rooms not equipped with an approved, supervised sprinkler system installed in accordance with Section 903.
Exception: An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit.
A manual fire alarm system that activates the occupant notification system in accordance with Section 907.6 shall be installed in existing Group R-1 boarding and rooming houses.
Exception: Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, exit court or yard.
An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.6 shall be installed in existing Group R-1 boarding and rooming houses throughout all interior corridors serving sleeping units not equipped with an approved, supervised sprinkler system installed in accordance with Section 903.
Exception: Buildings equipped with single-station smoke alarms meeting or exceeding the requirements of Section 907.2.11.1 and where the fire alarm system includes at least one manual fire alarm box per floor arranged to initiate the alarm.
An automatic or manual fire alarm system that activates the occupant notification system in accordance with Section 907.6 shall be installed in existing Group R-2 occupancies more than three stories in height or with more than 16 dwelling or sleeping units.
Exceptions:
  1. Where each living unit is separated from other contiguous living units by fire barriers having a fire-resistance rating of not less than 0.75 hour, and where each living unit has either its own independent exit or its own independent stairway or ramp discharging at grade.
  2. A separate fire alarm system is not required in buildings that are equipped throughout with an approved supervised automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 and having a local alarm to notify all occupants.
  3. A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 1023.6, Exception 4.
An automatic or manual fire alarm system that activates the occupant notification system in accordance with Section 907.6 shall be installed in existing Group R-4 residential care/assisted living facilities in accordance with Section 907.2.10.
Exceptions:
  1. Where there are interconnected smoke alarms meeting the requirements of Section 907.2.11 and there is at least one manual fire alarm box per floor arranged to continuously sound the smoke alarms.
  2. Other manually activated, continuously sounding alarms approved by the fire code official.
Single- and multiple-station smoke alarms shall be installed in existing Group R occupancies and in dwellings not classified as Group R occupancies in accordance with Sections 4603.7.1 through 4603.7.3.
Existing Group R occupancies and dwellings not classified as Group R occupancies not already provided with single-station smoke alarms shall be provided with single-station smoke alarms. Installation shall be in accordance with Section 907.2.11, except as provided in Sections 4603.7.2 and 4603.7.3.
Where more than one smoke alarm is required to be installed within an individual dwelling or sleeping unit, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed.
Exceptions:
  1. Interconnection is not required in buildings that are not undergoing alterations, repairs or construction of any kind.
  2. Smoke alarms in existing areas are not required to be interconnected where alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for interconnection without the removal of interior finishes.
Single-station smoke alarms shall receive their primary power from the building wiring provided that such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms with integral strobes that are not equipped with battery backup shall be connected to an emergency electrical system. Smoke alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection.
Exceptions:
  1. Smoke alarms are permitted to be solely battery operated in existing buildings where no construction is taking place.
  2. Smoke alarms are permitted to be solely battery operated in buildings that are not served from a commercial power source.
  3. Smoke alarms are permitted to be solely battery operated in existing areas of buildings undergoing alterations or repairs that do not result in the removal of interior walls or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for building wiring without the removal of interior finishes.
Means of egress in existing buildings shall comply with the minimum egress requirements when specified in Table 4603.1 as further enumerated in Sections 4604.2 through 4604.23, and the building code that applied at the time of construction. Where the provisions conflict, the most restrictive provision shall apply. Existing buildings that were not required to comply with a building code at the time of construction shall comply with the minimum egress requirements when specified in Table 4603.1 as further enumerated in Sections 4604.2 through 4604.23 and, in addition, shall have a life safety evaluation prepared, consistent with the requirements of Section 104.7.2. The life safety evaluation shall identify any changes to the means of egress that are necessary to provide safe egress to occupants and shall be subject to review and approval by the fire code official. The building shall be modified to comply with the recommendations set forth in the approved evaluation.
Elevators, escalators and moving walks shall not be used as a component of a required means of egress.
Exceptions:
  1. Elevators used as an accessible means of egress where allowed by Section 1007.4.
  2. Previously approved escalators and moving walks in existing buildings.
Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.
Exception: Approved self-luminous signs that provide evenly illuminated letters shall have a minimum luminance of 0.06 foot-lamberts (0.21 cd/m2).
Where emergency illumination is required in Section 4604.5, exit signs shall be visible under emergency illumination conditions.
Exception: Approved signs that provide continuous illumination independent of external power sources are not required to be connected to an emergency electrical system.
The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress:
  1. Group A having 50 or more occupants.
    Exception: Assembly occupancies used exclusively as a place of worship and having an occupant load of less than 300.
  2. Group B buildings three or more stories in height, buildings with 100 or more occupants above or below a level of exit discharge serving the occupants or buildings with 1,000 or more total occupants.
  3. Group E in interior stairs, corridors, windowless areas with student occupancy, shops and laboratories.
  4. Group F having more than 100 occupants.
    Exception: Buildings used only during daylight hours which are provided with windows for natural light in accordance with the International Building Code.
  5. Group I.
  6. Group M.
    Exception: Buildings less than 3,000 square feet (279 m2) in gross sales area on one story only, excluding mezzanines.
  7. Group R-1.
    Exception: Where each sleeping unit has direct access to the outside of the building at grade.
  8. Group R-2.
    Exception: Where each dwelling unit or sleeping unit has direct access to the outside of the building at grade.
  9. Group R-4.
    Exception: Where each sleeping unit has direct access to the outside of the building at ground level.
In other than Group I-2, the emergency power system shall provide power for not less than 60 minutes and consist of storage batteries, unit equipment or an on-site generator. In Group I-2, the emergency power system shall provide power for not less than 90 minutes and consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604.
Guards complying with this section shall be provided at the open sides of means of egress that are more than 30 inches (762 mm) above the floor or grade below.
Guards shall form a protective barrier not less than 42 inches (1067 mm) high.
Exceptions:
  1. Existing guards on the open side of stairs shall be not less than 30 inches (760 mm) high.
  2. Existing guards within dwelling units shall be not less than 36 inches (910 mm) high.
  3. Existing guards in assembly seating areas.
Open guards shall have balusters or ornamental patterns such that a 6-inch-diameter (152 mm) sphere cannot pass through any opening up to a height of 34 inches (864 mm).
Exceptions:
  1. At elevated walking surfaces for access to, and use of, electrical, mechanical or plumbing systems or equipment, guards shall have balusters or be of solid materials such that a sphere with a diameter of 21 inches (533 mm) cannot pass through any opening.
  2. In occupancies in Group I-3, F, H or S, the clear distance between intermediate rails measured at right angles to the rails shall not exceed 21 inches (533 mm).
  3. Approved existing open guards.
The means of egress width shall not be less than as required by the code under which constructed but not less than as required by this section. The total width of means of egress in inches (mm) shall not be less than the total occupant load served by the means of egress multiplied by the factors in Table 4604.7 and not less than specified elsewhere in this section. Multiple means of egress shall be sized such that the loss of any one means of egress shall not reduce the available capacity to less than 50 percent of the required capacity. The maximum capacity required from any story of a building shall be maintained to the termination of the means of egress.
TABLE 4604.7
EGRESS WIDTH PER OCCUPANT SERVED
OCCUPANCY WITHOUT SPRINKLER SYSTEM WITH SPRINKLER SYSTEMa
Stairways
(inches per occupant)
Other egress components (inches per occupant) Stairways
(inches per occupant)
Other egress components (inches per occupant)
Occupancies other than those listed below 0.3 0.2 0.2 0.15
Hazardous: H-1, H-2, H-3 and H-4 Not permitted Not permitted 0.3 0.2
Institutional: I-2 Not permitted Not permitted 0.3 0.2
For SI: 1 inch = 25.4 mm.
  1. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 28 inches (711 mm). Where this section requires a minimum clear width of 28 inches (711 mm) and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 28 inches (711 mm). The maximum width of a swinging door leaf shall be 48 inches (1219 mm) nominal. Means of egress doors in an occupancy in Group I-2 used for the movement of beds shall provide a clear width not less than 41.5 inches (1054 mm). The height of doors shall not be less than 80 inches (2032 mm).
Exceptions:
  1. The minimum and maximum width shall not apply to door openings that are not part of the required means of egress in occupancies in Groups R-2 and R-3.
  2. Door openings to storage closets less than 10 square feet (0.93 m2) in area shall not be limited by the minimum width.
  3. Width of door leafs in revolving doors that comply with Section 1008.1.4.1 shall not be limited.
  4. Door openings within a dwelling unit shall not be less than 78 inches (1981 mm) in height.
  5. Exterior door openings in dwelling units, other than the required exit door, shall not be less than 76 inches (1930 mm) in height.
  6. Exit access doors serving a room not larger than 70 square feet (6.5 m2) shall be not less than 24 inches (610 mm) in door width.
The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a force of not more than 15 pounds (66 N). The door shall be set in motion when subjected to a force not exceeding 30 pounds (133 N). The door shall swing to a full-open position when subjected to a force of not more than 50 pounds (222 N). Forces shall be applied to the latch side.
Revolving doors shall comply with the following:
  1. A revolving door shall not be located within 10 feet (3048 mm) of the foot or top of stairs or escalators. A dispersal area shall be provided between the stairs or escalators and the revolving doors.
  2. The revolutions per minute for a revolving door shall not exceed those shown in Table 4604.10.
  3. Each revolving door shall have a conforming side- hinged swinging door in the same wall as the revolving door and within 10 feet (3048 mm).
Exceptions:
  1. A revolving door is permitted to be used without an adjacent swinging door for street-floor elevator lobbies provided a stairway, escalator or door from other parts of the building does not discharge through the lobby and the lobby does not have any occupancy or use other than as a means of travel between elevators and a street.
  2. Existing revolving doors where the number of revolving doors does not exceed the number of swinging doors within 20 feet (6096 mm).
TABLE 4604.10
REVOLVING DOOR SPEEDS
INSIDE DIAMETER POWER-DRIVEN-TYPE SPEED CONTROL(RPM) MANUAL-TYPE SPEED CONTROL (RPM)
6' 6" 11 12
7' 0" 10 11
7' 6" 9 11
8' 0" 9 10
8' 6" 8 9
9' 0" 8 9
9' 6" 7 8
10' 0" 7 8
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
A revolving door used as a component of a means of egress shall comply with Section 4604.10 and all of the following conditions:
  1. Revolving doors shall not be given credit for more than 50 percent of the required egress capacity.
  2. Each revolving door shall be credited with not more than a 50-person capacity.
  3. Revolving doors shall be capable of being collapsed when a force of not more than 130 pounds (578 N) is applied within 3 inches (76 mm) of the outer edge of a wing.
Existing stairs in buildings shall be permitted to remain if the rise does not exceed 81/4 inches (210 mm) and the run is not less than 9 inches (229 mm). Existing stairs can be rebuilt.
Exception: Other stairs approved by the fire code official.
The replacement of an existing stairway in a structure shall not be required to comply with the new stairway requirements of Section 1009 where the existing space and construction will not allow a reduction in pitch or slope.
Existing winders shall be allowed to remain in use if they have a minimum tread depth of 6 inches (152 mm) and a minimum tread depth of 9 inches (229 mm) at a point 12 inches (305 mm) from the narrowest edge.
Existing circular stairs shall be allowed to continue in use provided the minimum depth of tread is 10 inches (254 mm) and the smallest radius shall not be less than twice the width of the stairway.
Stairways shall have handrails on at least one side. Handrails shall be located so that all portions of the stairway width required for egress capacity are within 44 inches (1118 mm) of a handrail.
Exception: Aisle stairs provided with a center handrail are not required to have additional handrails.
Handrail height, measured above stair tread nosings, shall be uniform, not less than 30 inches (762 mm) and not more than 42 inches (1067 mm).
Ramp runs utilized as part of a means of egress shall have a running slope not steeper than one unit vertical in 10 units horizontal (10-percent slope). The slope of other ramps shall not be steeper than one unit vertical in eight units horizontal (12.5-percent slope).
Existing ramps are permitted to have a minimum width of 30 inches (762 mm) but not less than the width required for the number of occupants served as determined by Section 1005.1.
Fire escape stairs shall comply with Sections 4604.17.1 through 4604.17.7.
Fire escape stairs shall be permitted in existing buildings but shall not constitute more than 50 percent of the required exit capacity.
Openings within 10 feet (3048 mm) of fire escape stairs shall be protected by fire door assemblies having a minimum 3/4-hour fire-resistance rating.
Exception: In buildings equipped throughout with an approved automatic sprinkler system, opening protection is not required.
Fire escape stairs shall meet the minimum width, capacity, riser height and tread depth as specified in Section 4604.11.
Access to a fire escape from a corridor shall not be through an intervening room. Access to a fire escape stair shall be from a door or window meeting the criteria of Section 1005.1. Access to a fire escape stair shall be directly to a balcony, landing or platform. These shall be no higher than the floor or window sill level and no lower than 8 inches (203 mm) below the floor level or 18 inches (457 mm) below the window sill.
Components of fire escape stairs shall be constructed of noncombustible materials. Fire escape stairs and balconies shall support the dead load plus a live load of not less than 100 pounds per square foot (4.78 kN/m2). Fire escape stairs and balconies shall be provided with a top and intermediate handrail on each side. The fire code official is authorized to require testing or other satisfactory evidence that an existing fire escape stair meets the requirements of this section.
The lowest balcony shall not be more than 18 feet (5486 mm) from the ground. Fire escape stairs shall extend to the ground or be provided with counterbalanced stairs reaching the ground.
Exception: For fire escape stairs serving 10 or fewer occupants, an approved fire escape ladder is allowed to serve as the termination.
Fire escapes shall be kept clear and unobstructed at all times and shall be maintained in good working order.
Corridors serving an occupant load greater than 30 and the openings therein shall provide an effective barrier to resist the movement of smoke. Transoms, louvers, doors and other openings shall be kept closed or self- closing.
Exceptions:
  1. Corridors in occupancies other than in Group H, which are equipped throughout with an approved automatic sprinkler system.
  2. Patient room doors in corridors in occupancies in Group I-2 where smoke barriers are provided in accordance with the International Building Code.
  3. Corridors in occupancies in Group E where each room utilized for instruction or assembly has at least one-half of the required means of egress doors opening directly to the exterior of the building at ground level.
  4. Corridors that are in accordance with the International Building Code.
Openings in corridor walls shall comply with the requirements of the International Building Code.
Exceptions:
  1. Where 20-minute fire door assemblies are required, solid wood doors at least 1.75 inches (44 mm) thick or insulated steel doors are allowed.
  2. Openings protected with fixed wire glass set in steel frames.
  3. Openings covered with 0.5-inch (12.7 mm) gypsum wallboard or 0.75-inch (19.1 mm) plywood on the room side.
  4. Opening protection is not required when the building is equipped throughout with an approved automatic sprinkler system.
Where more than one exit or exit access doorway is required, the exit access shall be arranged such that dead ends do not exceed the limits specified in Table 4604.18.2.
Exception: A dead-end passageway or corridor shall not be limited in length where the length of the dead-end passageway or corridor is less than 2.5 times the least width of the dead-end passageway or corridor.
TABLE 4604.18.2
COMMON PATH, DEAD-END AND TRAVEL DISTANCE LIMITS (by occupancy)
OCCUPANCY COMMON PATH LIMIT DEAD-END LIMIT TRAVEL DISTANCE LIMIT
Unsprinklered
(feet)
Sprinklered
(feet)
Unsprinklered
(feet)
Sprinklered
feet)
Unsprinklered
(feet)
Sprinklered
(feet)
Group A 20/75a 20/75a 20b 20b 200 250
Group B 75 100 50 50 200 250
Group E 75 75 20 50 200 250
Group F-1, S-1d 75 100 50 50 200 250
Group F-2, S-2d 75 100 50 50 300 400
Group H-1 25 25 0 0 75 75
Group H-2 50 100 0 0 75 100
Group H-3 50 100 20 20 100 150
Group H-4 75 75 20 20 150 175
Group H-5 75 75 20 50 150 200
Group I-1 75 75 20 50 200 250
Group I-2 (Health Care) NRe NRe NR NR 150 200c
Group I-3
(Detention and Correctional—
Use Conditions II, III, IV, V)
100 100 NR NR 150c 200c
Group I-4 (Day Care Centers) NR NR 20 20 200 250
Group M (Covered Mall) 75 100 50 50 200 400
Group M (Mercantile) 75 100 50 50 200 250
Group R-1 (Hotels) 75 75 50 50 200 250
Group R-2 (Apartments) 75 75 50 50 200 250
Group R-3 (One- and Two- Family) NR NR NR NR NR NR
Group R-4 (Residential Care/Assisted Living) NR NR NR NR NR NR
Group U 75 75 20 50 200 250
For SI: 1 foot = 304.8 mm.
  1. 20 feet for common path serving 50 or more persons; 75 feet for common path serving less than 50 persons.
  2. See Section 1028.9.5 for dead-end aisles in Group A occupancies.
  3. This dimension is for the total travel distance, assuming incremental portions have fully utilized their allowable maximums. For travel distance within the room, and from the room exit access door to the exit, see the appropriate occupancy chapter.
  4. See the International Building Code for special requirements on spacing of doors in aircraft hangars.
  5. Any patient sleeping room, or any suite that includes patient sleeping rooms, of more than 1,000 square feet (93 m2) shall have at least two exit access doors placed a distance apart equal to not less than one-third of the length of the maximum overall diagonal dimension of the patient sleeping room or suite to be served, measured in a straight line between exit access doors.
NR = No requirements.
Exits shall be located so that the maximum length of exit access travel, measured from the most remote point to an approved exit along the natural and unobstructed path of egress travel, does not exceed the distances given in Table 4604.18.2.
The common path of egress travel shall not exceed the distances given in Table 4604.18.2.
A stairway in an exit enclosure which continues below its level of exit discharge shall be arranged and marked to make the direction of egress to a public way readily identifiable.
Exception: Stairs that continue one-half story beyond their levels of exit discharge need not be provided with barriers where the exit discharge is obvious.
Exterior exit stairs shall be separated from the interior of the building as required in Section 1026.6. Openings shall be limited to those necessary for egress from normally occupied spaces.

Exceptions:
  1. Separation from the interior of the building is not required for buildings that are two stories or less above grade where the level of exit discharge serving such occupancies is the first story above grade.
  2. Separation from the interior of the building is not required where the exterior stairway is served by an exterior balcony that connects two remote exterior stairways or other approved exits, with a perimeter that is not less than 50 percent open. To be considered open, the opening shall be a minimum of 50 percent of the height of the enclosing wall, with the top of the opening not less than 7 feet (2134 mm) above the top of the balcony.
  3. Separation from the interior of the building is not required for an exterior stairway located in a building or structure that is permitted to have unenclosed interior stairways in accordance with Section 1022.
  4. Separation from the interior of the building is not required for exterior stairways connected to open-ended corridors, provided that:
    1. The building, including corridors and stairs, is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
    2. The open-ended corridors comply with Section 1018.
    3. The open-ended corridors are connected on each end to an exterior exit stairway complying with Section 1026.
    4. At any location in an open-ended corridor where a change of direction exceeding 45 degrees occurs, a clear opening of not less than 35 square feet (3 m2) or an exterior stairway shall be provided. Where clear openings are provided, they shall be located so as to minimize the accumulation of smoke or toxic gases.
The minimum clear width of aisles shall be:
  1. Forty-two inches (1067 mm) for aisle stairs having seating on each side.
    Exception: Thirty-six inches (914 mm) where the aisle serves less than 50 seats.
  2. Thirty-six inches (914 mm) for stepped aisles having seating on only one side.
    Exception: Thirty inches (760 mm) for catchment areas serving not more than 60 seats.
  3. Twenty inches (508 mm) between a stepped aisle handrail or guard and seating when the aisle is subdivided by the handrail.
  4. Forty-two inches (1067 mm) for level or ramped aisles having seating on both sides.
    Exception: Thirty-six inches (914 mm) where the aisle serves less than 50 seats.
  5. Thirty-six inches (914 mm) for level or ramped aisles having seating on only one side.
    Exception: Thirty inches (760 mm) for catchment areas serving not more than 60 seats.
  6. Twenty-three inches (584 mm) between a stepped stair handrail and seating where an aisle does not serve more than five rows on one side.
Existing stairs shall be marked in accordance with Section 1022.8.
Existing buildings of Groups A, B, E, I, M and R-1 having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access shall be provided with luminous egress path markings in accordance with Section 1024.
Exception: Open, unenclosed stairwells in historic buildings designated as historic under a state or local historic preservation program.
Existing tire storage yards shall be provided with fire apparatus access roads in accordance with Sections 4605.1.1 and 4605.1.2.
Access roadways shall be within 150 feet (45 720 mm) of any point in the storage yard where storage piles are located, at least 20 feet (6096 mm) from any storage pile.
Fire apparatus access roads shall be located within all pile clearances identified in Section 2505.4 and within all fire breaks required in Section 2505.5.