Heads up:
There are no amended sections in this chapter.
Note: Boilers, pressure vessels and associated pressure piping are
regulated by the Oregon Boiler and Pressure Vessel Law and
rules. Any boiler or pressure vessel separated from the potable
water system by an approved backflow prevention device shall
have an installation permit and inspection and be approved with a
permit to operate by the Boiler Section of the Building Codes
Division. Such installations in single-family dwellings shall be
exempt from subsequent inspections required by ORS
480.560(1)(a) to (d).
Reference: ORS 480.525(2)(c).
Reference: ORS 480.525(2)(c).
In addition to the requirements of this code, the installation of boilers shall conform to the manufacturer's instructions. The manufacturer's rating data, the nameplate and operating instructions of a permanent type shall be attached to the boiler. Boilers shall have their controls set, adjusted and tested by the installer. A complete control diagram together with complete boiler operating instructions shall be furnished by the installer. Solid and liquid fuel-burning boilers shall be provided with combustion air as required by Chapter 17.
Packaged oil-fired boilers shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be listed and labeled in accordance with UL 834. Solid fuel-fired boilers shall be listed and labeled in accordance with UL 2523. Boilers shall be designed, constructed and certified in accordance with the ASME Boiler and Pressure Vessel Code, Section I or IV. Controls and safety devices for boilers with fuel input ratings of 12,500,000 Btu/hr (3 663 388 watts) or less shall meet the requirements of ASME CSD-1. Gas-fired boilers shall conform to the requirements listed in Chapter 24.
Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple boiler or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in the supply and return piping.
Exception:
Shutoff valves are not required in a system having a single low-pressure steam boiler.
In flood hazard areas established
by the Flood Plain Administrator,
boilers, water heaters and their control systems shall be located or installed in accordance with Section R322.1.6.
Boilers shall be equipped with pressure-relief valves with minimum rated capacities for the equipment served. Pressure-relief valves shall be set at the maximum rating of the boiler. Discharge shall be piped to drains by gravity to within 18 inches (457 mm) of the floor or to an open receptor.
Low-water cutoff controls and flow sensing controls required by Section M2002.5 shall automatically stop the combustion operation of the appliance when the water level drops below the lowest safe water level as established by the manufacturer or when the water circulation flow is less than that required for safe operation of the appliance, respectively.
Hot water boilers shall be provided with expansion tanks. Nonpressurized expansion tanks shall be securely fastened to the structure or boiler and supported to carry twice the weight of the tank filled with water. Provisions shall be made for draining nonpressurized tanks without emptying the system.
Pressurized expansion tanks shall be consistent with the volume and capacity of the system. Tanks shall be capable of withstanding a hydrostatic test pressure of two and one-half times the allowable working pressure of the system.
The minimum capacity of expansion tanks shall be determined from Table M2003.2.
SYSTEM VOLUMEb (gallons) |
PRESSURIZED DIAPHRAGM TYPE |
NONPRESSURIZED TYPE |
10 | 1.0 | 1.5 |
20 | 1.5 | 3.0 |
30 | 2.5 | 4.5 |
40 | 3.0 | 6.0 |
50 | 4.0 | 7.5 |
60 | 5.0 | 9.0 |
70 | 6.0 | 10.5 |
80 | 6.5 | 12.0 |
90 | 7.5 | 13.5 |
100 | 8.0 | 15.0 |
For SI: 1 gallon = 3.785 L, 1 pound per square inch gauge = 6.895 kPa, °C = [(°F)-32]/1.8.
- Based on average water temperature of 195°F (91°C), fill pressure of 12 psig and a maximum operating pressure of 30 psig.
- System volume includes volume of water in boiler, convectors and piping, not including the expansion tank.
Water heaters used to supply both potable hot water and hot water for space heating shall be installed in accordance with this chapter, Chapter 24, Chapter 28 and the manufacturer's instructions.
Water heaters shall be installed in accordance
the manufacturer's
instructions, the Plumbing Code
and the
applicable
requirements of this code. Water heaters installed in an attic shall comply with the requirements of Section M1305.1.3. Gas-fired water heaters shall comply with the requirements in Chapter 24. Domestic electric water heaters shall comply with UL 174. Oiled-fired water heaters shall comply with UL 732. Thermal solar water heaters shall comply with Chapter 23 and UL 174. Solid fuel-fired water heaters shall comply with UL 2523.
Fuel-fired water heaters shall not be installed in a room used as a storage closet. Water heaters located in a bedroom or bathroom shall be installed in a sealed enclosure so that combustion air will not be taken from the living space. Installation of direct-vent water heaters within an enclosure is not required.
Access to water heaters that are located in an attic or underfloor crawl space is permitted to be through a closet located in a sleeping room or bathroom where ventilation of those spaces is in accordance with this code.
Electric water heaters shall also be installed in accordance with the applicable provisions of
the Electrical Code.
Potable water heating devices that use refrigerant-to-water heat exchangers shall be approved and installed in accordance with the manufacturer's instructions.
Pool and spa heaters shall be installed in accordance with the manufacturer's installation instructions. Oil-fired pool heaters shall comply with UL 726. Electric pool and spa heaters shall comply with UL 1261.
The clearances shall not interfere with combustion air, draft hood or flue terminal relief, or accessibility for servicing.
Pool heaters shall have temperature-relief valves.
Where an integral bypass system is not provided as a part of the pool heater, a bypass line and valve shall be installed between the inlet and outlet piping for use in adjusting the flow of water through the heater.