About this chapter: Chapter 1 establishes the limits of applicability of the code and describes how the code is to be applied and enforced. Chapter 1 is in two parts: Part 1—Scope and Application and Part 2—Administration and Enforcement. Section 101 identifies what buildings, systems, appliances and equipment fall under its purview and references other I-Codes as applicable. Standards and codes are scoped to the extent referenced.

The code is intended to be adopted as a legally enforceable document and it cannot be effective without adequate provisions for its administration and enforcement. The provisions of Chapter 1 establish the authority and duties of the code official appointed by the authority having jurisdiction and also establish the rights and privileges of the design professional, contractor and property owner.

Part 1 Scope and Application

[A] 101.1 Title

AMENDMENT
This section has been amended at the state or city level.
These regulations shall be known as the Oregon Mechanical Specialty Code, hereinafter referred to as "this code."

[A] 101.2 Scope

AMENDMENT
This section has been amended at the state or city level.
The scope of this code is as provided in ORS 455.020(1) and as further noted in this section.
ORS 455.020 is not part of this code but is reprinted here for the reader's convenience:

455.020 Purpose; scope of application; exceptions; scope of rules; fees by rule.

  1. This chapter is enacted to enable the Director of the Department of Consumer and Business Services to promulgate a state building code to govern the construction, reconstruction, alteration and repair of buildings and other structures and the installation of mechanical devices and equipment therein, and to require the correction of unsafe conditions caused by earthquakes in existing buildings. The state building code shall establish uniform performance standards providing reasonable safeguards for health, safety, welfare, comfort and security of the residents of this state who are occupants and users of buildings, and will provide for the use of modern methods, devices, materials, techniques and practicable maximum energy conservation. [Formerly 456.755; 1991 c.227 §2; 1991 c.310 §2; 1995 c.304 §1; 1995 c.400 §5; 1999 c.1045 §13; 1999 c.1082 §11; 2001 c.710 §8]

     This code shall regulate the design, installation, alteration and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. This code shall also regulate those mechanical systems, system components, equipment and appliances specifically addressed herein. The installation of fuel gas distribution piping and equipment, fuel gas-fired appliances and fuel gas-fired appliance venting systems shall comply with Appendix C, "Fuel Gas," of this code.



     Detached one- and two-family dwellings and townhouses not more than three stories above grade plane height with a separate means of egress and their accessory structures shall comply with the Residential Code.

     The Oregon Mechanical Specialty Code, as adopted by the State of Oregon, Building Codes Division, includes portions of the International Mechanical Code pertaining to any construction, reconstruction, alteration, repair and installation of materials and equipment in or part of buildings and structures covered by the state building code.

     This code shall not apply to:
  1. The construction, alteration, moving, demolition, repair, maintenance and work located primarily in a public way.
  2. Mechanical equipment not specifically regulated in this code.
  3. Hydraulic flood control structures including, but not limited to, dams and levees.
  4. Mechanical equipment in or part of structures that are not covered by the state building code. Buildings exempt from the Building Code by ORS 455.315 shall comply with this code, as applicable.

[A] 101.2.1 Appendices

AMENDMENT
This section has been amended at the state or city level.
Provisions in the appendices shall not apply unless specifically adopted as noted in Sections 101.2.1.1 and 101.2.1.2.

101.2.1.1 Adopted Appendices

AMENDMENT
This section has been amended at the state or city level.
Appendix C, "Fuel Gas," is adopted by the State of Oregon, Building Codes Division, as part of the state building code.

101.2.1.2 Appendix Chapters Not Adopted

AMENDMENT
This section has been amended at the state or city level.
The following appendix chapters are informative only and not adopted by the State of Oregon, Building Codes Division, as part of the state building code:
  1. Appendix A, "Chimney Connector Pass-throughs."
  2. Appendix B, "Recommended Permit Fee Schedule."

[A] 101.3 Intent

AMENDMENT
This section has been amended at the state or city level.

101.3 Purpose

AMENDMENT
This section has been amended at the state or city level.
The purpose of this code, as provided in ORS 455.020(1) and noted in Section 101.2, is to establish minimum requirements to provide a reasonable level of safety, health, property and public welfare by regulating and controlling the design, construction, installation and location of mechanical systems.

[A] 101.4 Severability

AMENDMENT
This section has been amended at the state or city level.

If a section, subsection, sentence, clause or phrase of this code is, for any reason, held to be invalid, such decision shall not affect the validity of the remaining portions of this code.

Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern.

102.1.1 Statutory References

AMENDMENT
This section has been amended at the state or city level.
This code is adopted pursuant to Oregon Revised Statutes (ORS). Where this code and the statutes specify different requirements, the statute shall govern. Statutes related to this code include, but are not limited to, ORS 455.010 through 455.895 and ORS 447.210 through 447.310.
Statutes referenced may be obtained from the Building Codes Division, 1535 Edgewater St. NW, Salem, OR 97304 or P.O. Box 14470, Salem, OR 97309 at a nominal cost or read online at: www.oregon.gov/bcd.

[A] 102.2 Existing Installations

AMENDMENT
This section has been amended at the state or city level.

102.2 Referenced Codes and Standards

AMENDMENT
This section has been amended at the state or city level.
The codes and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections 102.2.1 and 102.2.2.

Exception: Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, the conditions of the listing and the manufacturer's installation instructions shall apply.

102.2.1 Conflicts

AMENDMENT
This section has been amended at the state or city level.
Where conflicts occur between provisions of this code and the referenced standards, the provisions of this code shall apply.

102.2.2 Provisions in Referenced Codes and Standards

AMENDMENT
This section has been amended at the state or city level.
Where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code, the provisions of this code, as applicable, shall take precedence over the provisions in the referenced code or standard.

[A] 102.2.1 Existing Buildings

AMENDMENT
This section has been amended at the state or city level.

[A] 102.3 Maintenance

AMENDMENT
This section has been amended at the state or city level.

102.3 Other Laws

AMENDMENT
This section has been amended at the state or city level.
The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law.

102.4 Application of References

AMENDMENT
This section has been amended at the state or city level.
Reference to chapter section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.

102.5 Existing Installations

AMENDMENT
This section has been amended at the state or city level.
Except as otherwise provided for in this chapter, a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, an existing mechanical system lawfully in existence at the time of the adoption of this code.
Occupied and existing structures under state law related to building inspection programs

Note: This information is provided for building official use and is not intended to provide direction to any other form of government outside of a building official operating under Oregon Building Codes Division's state laws and rules. Questions regarding this information should be addressed through local counsel.

Under ORS 476.030 and Chapter 455, building officials are prohibited from requiring corrections or any changes to an existing structure that is maintained in conformity with the state building code regulations in effect at the time of construction.

Under ORS Chapters 476 and 455, occupied structures which have no valid certificate of occupancy do not fall under the delegated authority from the state Building Codes Division. No state authority exists for building officials to access buildings or require corrections for structures unless a permit application is on file.

References within the state building code that provide access and investigative authority to building officials are rescinded and are not valid.

Under state authority, buildings occupied without a valid certificate of occupancy or permit are under the enforcement authority of the Office of State Fire Marshal.

Local programs should ensure that adequate local ordinances have been adopted allowing for enforcement action where a certificate of occupancy was not issued or where no permit has been applied for.

[A] 102.4 102.6 Additions, Alterations or Repairs

AMENDMENT
This section has been amended at the state or city level.

Additions, alterations, renovations or repairs to a mechanical system shall conform to that required for a new mechanical system without requiring the existing mechanical system to comply with all of the requirements of this code. Additions, alterations or repairs shall not cause an existing mechanical system to become unsafe, hazardous or overloaded.

Minor additions, alterations, renovations and repairs to existing mechanical systems shall meet the provisions for new construction, unless such work is done in the same manner and arrangement as was in the existing system, is not hazardous and is approved.

[A] 102.5 102.7 Change in Occupancy

AMENDMENT
This section has been amended at the state or city level.
It shall be unlawful to make a change in the occupancy of any structure that will subject the structure to any special provision of this code applicable to the new occupancy without approval. The building official shall certify that such structure meets the intent of the provisions of the Building Code.

[A] 102.6 102.8 Historic Buildings

AMENDMENT
This section has been amended at the state or city level.
The provisions of this code relating to the construction, alteration, repair, enlargement, restoration, relocation or moving of buildings or structures shall not be mandatory for existing buildings or structures identified and classified by the state or local municipality as historic buildings where such buildings or structures are judged by the building official to be safe and in the public interest of health, safety and welfare regarding any proposed construction, alteration, repair, enlargement, restoration, relocation or moving of buildings.

[A] 102.7 102.9 Moved Buildings

AMENDMENT
This section has been amended at the state or city level.
Except as determined by Section 102.5, mechanical systems that are a part of buildings or structures moved into or within the municipality shall comply with the provisions of this code for new installations. See ORS 455.410 for moved buildings.
ORS 455.410 is not part of this code but is reprinted here for the reader's convenience:

455.410 Relocated buildings, substantial compliance required; permits.
  1. Existing buildings or structures which are removed from their foundation and relocated to another site within this state shall be in substantial compliance as defined in subsections (2) and (3) of this section.
  2. "Substantial compliance" means compliance with local construction codes in effect as of the original permit date of the building or structure, or where there was no permitting required at the time of original construction, with basic health and safety standards, as described in the closest dated Uniform Housing Code, as published by the International Conference of Building Officials as of the date of construction. Only the insulation, overhead and underneath the structure, shall be upgraded to the current insulation requirements of the state building code, or to the maximum extent possible subject to the design of the structure. Nothing in this statute shall be construed to mean that all heating, plumbing and electrical systems shall be replaced with systems meeting current standards for new construction, except that any life-threatening deficiencies in those systems shall be repaired, notwithstanding that the cost of rehabilitation may exceed 50 percent of the value of the structure before rehabilitation.
  3. All foundation and basement construction on the structure and any remodeling at the new location shall be constructed subject to all applicable local current building and safety codes, or where none exist, with the applicable standards as described in the Uniform Housing Code described in subsection (2) of this section.
  4. All moved houses shall be provided with either battery-operated or hard-wired smoke detection devices located in accordance with the provisions of the state building code. Nothing in this section is intended to permit any person to move a structure unless the person first consults with the appropriate building inspection authority and obtains all required permits. [Formerly 456.756; 1989 c.1068 §1]

[A] 102.8 Referenced Codes and Standards

AMENDMENT
This section has been amended at the state or city level.

[A] 102.8.1 Conflicts

AMENDMENT
This section has been amended at the state or city level.

[A] 102.8.2 Provisions in Referenced Codes and Standards

AMENDMENT
This section has been amended at the state or city level.

[A] 102.9 Requirements Not Covered by This Code

AMENDMENT
This section has been amended at the state or city level.

[A] 102.10 Other Laws

AMENDMENT
This section has been amended at the state or city level.

[A] 102.11 Application of References

AMENDMENT
This section has been amended at the state or city level.

Part 2 Administration and Enforcement

[A] 103.1 General

AMENDMENT
This section has been amended at the state or city level.

103.1 Liability

AMENDMENT
This section has been amended at the state or city level.
See ORS 30.265 for regulations relating to liability.
ORS 30.265 is not part of this code but is reprinted here for the reader's convenience:

ORS 30.265 Scope of liability of public body, officers, employees and agents; liability in nuclear incident.
  1. Subject to the limitations of ORS 30.260 to 30.300, every public body is subject to civil action for its torts and those of its officers, employees and agents acting within the scope of their employment or duties, whether arising out of a governmental or proprietary function or while operating a motor vehicle in a ridesharing arrangement authorized under ORS 276.598.
  2. The sole cause of action for a tort committed by officers, employees or agents of a public body acting within the scope of their employment or duties and eligible for representation and indemnification under ORS 30.285 or 30.287 is an action under ORS 30.260 to 30.300. The remedy provided by ORS 30.260 to 30.300 is exclusive of any other action against any such officer, employee or agent of a public body whose act or omission within the scope of the officer's, employee's or agent's employment or duties gives rise to the action. No other form of civil action is permitted.
  3. If an action under ORS 30.260 to 30.300 alleges damages in an amount equal to or less than the damages allowed under ORS 30.271, 30.272 or 30.273, the sole cause of action for a tort committed by officers, employees or agents of a public body acting within the scope of their employment or duties and eligible for representation and indemnification under ORS 30.285 or 30.287 is an action against the public body. If an action is filed against an officer, employee or agent of a public body, and the plaintiff alleges damages in an amount equal to or less than the damages allowed under ORS 30.271, 30.272 or 30.273, the court upon motion shall substitute the public body as the defendant. Substitution of the public body as the defendant does not exempt the public body from making any report required under ORS 742.400.
  4. If an action under ORS 30.260 to 30.300 alleges damages in an amount greater than the damages allowed under ORS 30.271, 30.272 or 30.273, the action may be brought and maintained against an officer, employee or agent of a public body, whether or not the public body is also named as a defendant. An action brought under this subsection is subject to the limitations on damages imposed under ORS 30.271, 30.272 or 30.273, and the total combined amount recovered in the action may not exceed those limitations for a single accident or occurrence without regard to the number or types of defendants named in the action.
  5. Every public body is immune from liability for any claim for injury to or death of any person or injury to property resulting from an act or omission of an officer, employee or agent of a public body when such officer, employee or agent is immune from liability.
  6. Every public body and its officers, employees and agents acting within the scope of their employment or duties, or while operating a motor vehicle in a ridesharing arrangement authorized under ORS 276.598, are immune from liability for:
    1. Any claim for injury to or death of any person covered by any workers' compensation law.
    2. Any claim in connection with the assessment and collection of taxes.
    3. Any claim based upon the performance of or the failure to exercise or perform a discretionary function or duty, whether or not the discretion is abused.
    4. Any claim that is limited or barred by the provisions of any other statute, including but not limited to any statute of ultimate repose.
    5. Any claim arising out of riot, civil commotion or mob action or out of any act or omission in connection with the prevention of any of the foregoing.
    6. Any claim arising out of an act done or omitted under apparent authority of a law, resolution, rule or regulation that is unconstitutional, invalid or inapplicable except to the extent that they would have been liable had the law, resolution, rule or regulation been constitutional, valid and applicable, unless such act was done or omitted in bad faith or with malice.
  7. This section applies to any action of any officer, employee or agent of the state relating to a nuclear incident, whether or not the officer, employee or agent is acting within the scope of employment, and provided the nuclear incident is covered by an insurance or indemnity agreement under 42 U.S.C. 2210.
  8. Subsection (6)(c) of this section does not apply to any discretionary act that is found to be the cause or partial cause of a nuclear incident covered by an insurance or indemnity agreement under the provisions of 42 U.S.C. 2210, including but not limited to road design and route selection.

    [1967 c.627 §§2,3,10; 1969 c.429 §1; 1975 c.609 §12; 1977 c.823 §2; 1981 c.490 §4; 1985 c.731 §31; 1987 c.705 §7; 1991 c.861 §1; 2005 c.22 §19; 2007 c.803 §4; 2011 c.270 §1]

[A] 103.2 Appointment

AMENDMENT
This section has been amended at the state or city level.

[A] 103.3 Deputies

AMENDMENT
This section has been amended at the state or city level.

[A] 103.4 Liability

AMENDMENT
This section has been amended at the state or city level.

[A] 103.4.1 Legal Defense

AMENDMENT
This section has been amended at the state or city level.

Section 104 Duties and Powers of the Code Building Official

AMENDMENT
This section has been amended at the state or city level.

[A] 104.1 General

AMENDMENT
This section has been amended at the state or city level.
The building official is hereby authorized and directed to enforce the provisions of this code and shall act on any question relative to the installation, alteration or repair of mechanical systems, except as otherwise specifically provided for by statutory requirements.

[A] 104.2 Applications and Permits

AMENDMENT
This section has been amended at the state or city level.
The building official shall receive applications, review construction documents and issue permits for the installation and alteration of mechanical systems, inspect the premises for which such permits have been issued and enforce compliance with the provisions of this code.

[A] 104.3 Inspections

AMENDMENT
This section has been amended at the state or city level.
The building official shall ensure all of the required inspections of this code are made by properly certified individuals. All Reports of such inspections shall be in writing and be certified by a responsible officer of such approved agency or by the responsible individual.

[A] 104.4 Right of Entry

AMENDMENT
This section has been amended at the state or city level.
(Not adopted by the State of Oregon Building Codes Division as part of the state building code.)

[A] 104.5 Identification

AMENDMENT
This section has been amended at the state or city level.

[A] 104.6 104.5 Notices and Orders

AMENDMENT
This section has been amended at the state or city level.
The building official shall issue all necessary notices or orders to ensure compliance with this code.

[A] 104.7 104.6 Department Records

AMENDMENT
This section has been amended at the state or city level.
The building official shall keep official records as dictated by OAR 166-150-0020 where a county has jurisdiction, OAR 166-200-0250 where a city has jurisdiction and OAR Division 166, Chapter 300 for the cities and counties where the State of Oregon has jurisdiction. Such records shall be retained in the official records for the period indicated in the respective OARs noted in this section. The building official shall maintain a permanent record of all permits issued in flood hazard areas, including copies of inspection reports and certifications required.
OAR 918-008-0000 is not part of this code but is reprinted here for the readers' convenience:

918-008-0000 Purpose and Scope.
  1. The Department of Consumer and Business Services, Building Codes Division, adopts model building codes, standards and other publications by reference, as necessary, through administrative rule to create the state building code. When a matter is included in a specialty code or referenced publication that is in conflict with Oregon Revised Statutes or Oregon Administrative Rules, the statute or rule applies and the code or standard provision does not. All remaining parts or application of the code or standard remain in effect.
  2. Unless required by law, matters generally not authorized for inclusion in a specialty code or referenced standard include, but are not limited to: licensing or certification requirements, or other qualifications and standards for businesses or workers; structures or equipment maintenance requirements; matters covered by federal or state law; and matters that conflict with other specialty codes or publications adopted by the department.
  3. OAR 918-008-0000 to OAR 918-008-0070 provides the process for adopting and amending the state building code that is consistent across all program areas.
  4. The state building code is derived from the most appropriate version of base model codes, which are updated periodically.
  5. The Oregon specialty code amendment process begins approximately midway into a code cycle.
  6. An appropriate advisory board approves or forwards the adoption of the Oregon specialty code and amendments to the Department for adoption.
  7. Notwithstanding sections (3) through (6) of this rule, the division may adopt supplemental code amendments as authorized by OAR 918-008-0028.

    [Publications: Publications referenced are available from the agency.]

    Stat. Auth.: ORS 447.020, 455.030 & 479.730

    Stats. Implemented: ORS 447.020, 455.030 & 479.730

    Hist.: BCD 26-1994, f. & cert. ef. 11-15-94; BCD 6-1997, f. & cert. ef. 4-1-97; BCD 3-2006(Temp), f. & cert. ef. 3-1-06 thru 8- 27-06; BCD 9-2006, f. 6-30-06, cert. ef. 7-1-06; BCD 1-2014, f. 1-22-14, cert. ef. 4-1-14

[A] 105.1 Modifications

AMENDMENT
This section has been amended at the state or city level.
Where there are practical difficulties involved in carrying out the provisions of this code, the building official shall have the authority to grant modifications for individual cases upon application of the owner or owner's authorized agent, provided that the building official shall first find that special individual reason makes the strict letter of this code impractical and the modification is in compliance with the intent and purpose of this code and does not lessen health, life and fire safety requirements. The details of action granting modifications shall be recorded and entered in the files of the mechanical inspection department.

[A] 105.2 Alternative Materials, Design and Methods, of Construction and Equipment and Appliances

AMENDMENT
This section has been amended at the state or city level.
The provisions of this code are not intended to prevent the installation of any material or to prohibit any method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material, design or method of construction shall be approved where the building official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, not less than the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety.
Supporting data, where necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.

[A] 105.3 Required Testing

AMENDMENT
This section has been amended at the state or city level.
Where there is insufficient evidence of compliance with the provisions of this code, or evidence that a material or method does not conform to the requirements of this code, or in order to substantiate claims for alternative materials or methods, the building official shall have the authority to require tests as evidence of compliance to be made at no expense to the municipality.

[A] 105.3.1 Test Methods

AMENDMENT
This section has been amended at the state or city level.
Test methods shall be as specified in this code or by other recognized test standards. In the absence of recognized and accepted test methods, the building official shall approve the testing procedures.
Tests shall be performed by an approved agency.

[A] 105.3.3 Test Reports

AMENDMENT
This section has been amended at the state or city level.
Reports of tests shall be retained by the building official for the period required for retention of public records.

[A] 105.4 Approved Materials and Equipment

AMENDMENT
This section has been amended at the state or city level.
Materials, equipment and devices approved by the building official shall be constructed and installed in accordance with such approval.
Materials, equipment, appliances and devices shall not be reused unless such elements have been reconditioned, tested and placed in good and proper working condition and approved.

[A] 106.1 Where Required

AMENDMENT
This section has been amended at the state or city level.

An owner, owner's authorized agent or contractor who desires to erect, install, enlarge, alter, repair, remove, convert or replace a mechanical system, the installation of which is regulated by this code, or to cause such work to be performed, shall first make application to the building official and obtain the required permit for the work.

Exception: Where equipment and appliance replacements or repairs must be performed in an emergency situation, the permit application shall be submitted to the building official within the next five business days.


ORS 455.058 is not part of this code but is reprinted here for the reader's convenience:

ORS 455.058 Investigation fee for work commenced without permit; rules. Except as provided in subsection (2) of this section, the Department of Consumer and Business Services, or a municipality administering and enforcing a building inspection program, may assess an investigation fee against a person that is required to obtain a permit for work on the electrical, gas, mechanical, elevator, boiler, plumbing or other systems of a building or structure if the work is commenced before the permit required for the work is obtained. The amount of the investigation fee shall be the average or actual additional cost of ensuring that a building, structure or system is in conformance with state building code requirements that results from the person not obtaining a required permit before work for which the permit is required commences.
  1. (2) This section does not apply to:
    1. An emergency repair required for health, safety, the prevention of property damage or the prevention of financial harm if the required building permit for the repair is obtained no later than five business days after commencement of the repair; or
    2. Any project for which construction, alteration, repair, maintenance or installation in a building or structure prior to obtaining a permit is expressly authorized by law.
  2. (3) The department may adopt rules and establish policies and procedures for use by the department or municipalities in assessing an investigation fee under this section. [2013 c.324 §2]

[A] 106.1.1 Annual Permit

AMENDMENT
This section has been amended at the state or city level.

[A] 106.1.2 Annual Permit Records

AMENDMENT
This section has been amended at the state or city level.

[A] 106.2 Permits Not Required Work Exempt From Permit

AMENDMENT
This section has been amended at the state or city level.

Permits shall not be required for the following:

  1. Portable heating appliances.
  2. Portable ventilation appliances and equipment.
  3. Portable cooling units.
  4. Steam, hot water or chilled water piping within any heating or cooling equipment or appliances regulated by this code.
  5. The replacement of any minor part that does not alter the approval of equipment or an appliance or make such equipment or appliance unsafe.
  6. Portable evaporative coolers.
  7. Self-contained refrigeration systems that contain 10 pounds (4.5 kg) or less of refrigerant, or that are actuated by motors of 1 horsepower (0.75 kW) or less.
  8. Portable fuel cell appliances that are not connected to a fixed piping system and are not interconnected to a power grid.
The requirements of Sections 106.3 through 106.4.5 shall apply unless specifically amended by a local municipality, under the authority of ORS 455.020.

[A] 106.3 Application for Permit

AMENDMENT
This section has been amended at the state or city level.
Each application for a permit, with the required fee, shall be filed with the building official on a form furnished for that purpose and shall contain a general description of the proposed work and its location. The application shall be signed by the owner or the owner's authorized agent. The permit application shall indicate the proposed occupancy of all parts of the building and of that portion of the site or lot, if any, not covered by the building or structure and shall contain such other information required by the building official.

     Where the local municipality has adopted a master permit or minor label program, see OAR Chapter 918, Division 100.

[A] 106.3.1 Construction Documents

AMENDMENT
This section has been amended at the state or city level.

Construction documents, engineering calculations, diagrams and other data shall be submitted in two or more sets with each application for a permit. The building official shall require construction documents, computations and specifications to be prepared and designed by a registered design professional where required by state law. Construction documents shall be drawn to scale and shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that the work conforms to the provisions of this code. Construction documents for buildings more than two stories in height shall indicate where penetrations will be made for mechanical systems.

Exception: The building official shall have the authority to waive the submission of construction documents, calculations or other data if the nature of the work applied for is such that reviewing of construction documents is not necessary to determine compliance with this code.

[A] 106.3.2 Preliminary Inspection

AMENDMENT
This section has been amended at the state or city level.
Before a permit is issued, the building official is authorized to inspect and evaluate the systems, equipment, buildings, devices, premises and spaces or areas to be used.

[A] 106.3.3 Time Limitation of Application

AMENDMENT
This section has been amended at the state or city level.
An application for a permit for any proposed work shall be deemed to have been abandoned 180 days after the date of filing, unless such application has been pursued in good faith or a permit has been issued; except that the building official shall have the authority to grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested in writing and justifiable cause demonstrated.

[A] 106.4 Permit Issuance Action on Permit

AMENDMENT
This section has been amended at the state or city level.
The application, construction documents and other data filed by an applicant for a permit shall be reviewed by the building official. If the building official finds that the proposed work conforms to the requirements of this code and all laws and ordinances applicable thereto, and that the fees specified in Section 106.5 have been paid, a permit shall be issued to the applicant.

     Where the local municipality has adopted a master permit or minor label program, see OAR Chapter 918, Division 100.

[A] 106.4.1 Approved Construction Documents

AMENDMENT
This section has been amended at the state or city level.

When the building official issues the permit where construction documents are required, the construction documents shall be endorsed in writing and stamped "APPROVED." Such approved construction documents shall not be changed, modified or altered without authorization from the building official. Work shall be done in accordance with the approved construction documents.

     The building official shall have the authority to issue a permit for the construction of part of a mechanical system before the construction documents for the entire system have been submitted or approved, provided that adequate information and detailed statements have been filed complying with all pertinent requirements of this code. The holder of such permit shall proceed at his or her own risk without assurance that the permit for the entire mechanical system will be granted.

[A] 106.4.2 Validity

AMENDMENT
This section has been amended at the state or city level.

The issuance of a permit or approval of construction documents shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code. A permit presuming to give authority to violate or cancel the provisions of this code shall be invalid.

     The issuance of a permit based on construction documents and other data shall not prevent the building official from thereafter requiring the correction of errors in said construction documents and other data or from preventing building operations from being carried on thereunder where in violation of this code.

[A] 106.4.3 Expiration

AMENDMENT
This section has been amended at the state or city level.
Every permit issued by the building official under the provisions of this code shall expire by limitation and become null and void if the work authorized by such permit is not commenced within 180 days from the date of such permit, or if the work authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days. Before such work recommences, a new permit shall be first obtained and the fee therefor shall be one-half the amount required for a new permit for such work, provided that changes have not been made and will not be made in the original construction documents for such work, and provided further that such suspension or abandonment has not exceeded one year.

[A] 106.4.4 Extensions

AMENDMENT
This section has been amended at the state or city level.
A permittee holding an unexpired permit shall have the right to apply for an extension of the time within which the permittee will commence work under that permit where work is unable to be commenced within the time required by this section for good and satisfactory reasons. The building official shall extend the time for action by the permittee for a period not exceeding 180 days if there is reasonable cause.

[A] 106.4.5 Suspension or Revocation of Permit

AMENDMENT
This section has been amended at the state or city level.
The building official shall have the authority to suspend or revoke a permit issued under the provisions of this code wherever the permit is issued in error or on the basis of incorrect, inaccurate or incomplete information, or in violation of any ordinance or regulation or any of the provisions of this code.

[A] 106.4.6 Retention of Construction Documents

AMENDMENT
This section has been amended at the state or city level.
One set of approved construction documents shall be retained by the building official for a period of not less than that dictated by OAR 166-150-0020 where a county has jurisdiction, OAR 166-200-0250 where a city has jurisdiction and OAR Division 166, Chapter 300 for the cities and counties where the State of Oregon has jurisdiction. One set of approved construction documents shall be returned to the applicant, and said set shall be kept on the site of the building or job at all times during which the work authorized thereby is in progress.
This code shall not require changes in the construction documents, construction or designated occupancy of a structure for which a lawful permit has been heretofore issued or otherwise lawfully authorized, and the construction of which has been pursued in good faith within 180 days after the effective date of this code and has not been abandoned.

[A] 106.4.8 Posting of Permit

AMENDMENT
This section has been amended at the state or city level.
The permit or a copy shall be kept on the site of the work until the completion of the project.
ORS 455.210(3)(a) is not part of this code but is reprinted here for the reader's convenience:

455.210 Fees; appeal of fees; surcharge; reduced fees; rules.

(3)(a) A municipality may adopt by ordinance or regulation such fees as may be necessary and reasonable to provide for the administration and enforcement of any specialty code or codes for which the municipality has assumed responsibility under ORS 455.148 or 455.150. A municipality shall give the director notice of the proposed adoption of a new or increased fee under this subsection. The municipality shall give the notice to the director at the time the municipality provides the opportunity for public comment under ORS 294.160 regarding the fee or, if the proposed fee is contained in an estimate of municipal budget resources, at the time notice of the last budget meeting is published under ORS 294.426. [Subsections (1) to (5) formerly 456.760; subsection (6) enacted as 1987 c.604 §6; 1997 c.856 §1; 1999 c.432 §1; 1999 c.1045 §24; 1999 c.1082 §9; 2001 c.573 §9; 2001 c.673 §1; 2005 c.193 §1; 2005 c.833 §3; 2007 c.69 §5; 2011 c.473 §29]

[A] 106.5 Fees

AMENDMENT
This section has been amended at the state or city level.
A permit shall not be issued, nor shall an amendment to a permit be released until the fee, or additional fee, if any, due to an increase of the mechanical system, has been paid in accordance with the schedules as established by the municipality, under authority of ORS 455.020 and 455.210, or as set forth in OAR Chapter 918, Division 440 where the State of Oregon has jurisdiction.
ORS 455.020(2) is not part of this code but is reprinted here for the reader's convenience:

455.020(2) Purpose: scope of application; exceptions; scope of rules; fees by rule.
  1. (2) The rules adopted pursuant to this chapter shall include structural standards; standards for the installation and use of mechanical, heating and ventilating devices and equipment; and standards for prefabricated structures; and shall, subject to ORS 455.210, prescribe reasonable fees for the issuance of building permits and similar documents, inspections and plan review services by the Department of Consumer and Business Services. The department may also establish, by rule, the amount of any fee pertaining to the state building code or any specialty code that is authorized by statute, but for which an amount is not specified by statute. [Formerly 456.755; 1991 c.227 §2; 1991 c.310 §2; 1995 c.304 §1; 1995 c.400 §5; 1999 c.1045 §13; 1999 c.1082 §11; 2001 c.710 §8]

[A] 106.5.1 Work Commencing Before Permit Issuance

AMENDMENT
This section has been amended at the state or city level.

106.5.1 Mechanical Permits

AMENDMENT
This section has been amended at the state or city level.
Fees shall be assessed in accordance with the provisions of this section and as set forth in the fee schedule of the municipality under the authority of ORS 455.210, or as set forth in OAR 918- 440-0050 where the State of Oregon has jurisdiction.

[A] 106.5.2 Fee Schedule

AMENDMENT
This section has been amended at the state or city level.

106.5.2 Work Commencing Before Permit Issuance

AMENDMENT
This section has been amended at the state or city level.
Any person who commences work on a mechanical system before obtaining the necessary permits shall be subject to 100 percent of the usual permit fee in addition to the required permit fees.
ORS 455.058 is not part of this code but is reprinted here for the reader's convenience:

455.058 Investigation fee for work commenced without permit; rules.
  1. Except as provided in subsection (2) of this section, the Department of Consumer and Business Services, or a municipality administering and enforcing a building inspection program, may assess an investigation fee against a person that is required to obtain a permit for work on the electrical, gas, mechanical, elevator, boiler, plumbing or other systems of a building or structure if the work is commenced before the permit required for the work is obtained. The amount of the investigation fee shall be the average or actual additional cost of ensuring that a building, structure or system is in conformance with state building code requirements that results from the person not obtaining a required permit before work for which the permit is required commences.
  2. This section does not apply to:
    1. An emergency repair required for health, safety, the prevention of property damage or the prevention of financial harm if the required building permit for the repair is obtained no later than five business days after commencement of the repair; or (b) Any project for which construction, alteration, repair, maintenance or installation in a building or structure prior to obtaining a permit is expressly authorized by law.
  3. The department may adopt rules and establish policies and procedures for use by the department or municipalities in assessing an investigation fee under this section. [2013 c.324 §2]

[A] 106.5.3 Fee Refunds

AMENDMENT
This section has been amended at the state or city level.
The building official is authorized to establish a refund program.
OAR 918-050-0100 is not part of this code but is reprinted here for the reader's convenience.

Uniform Fee Methodology

918-050-0100 Statewide Fee Methodologies for Residential and Commercial Permits.
  1. Residential construction permit fees shall be calculated using the following methodologies:
    1. A plumbing permit fee for new construction includes one kitchen and is based on the number of bathrooms, from one to three, on a graduated scale. An additional set fee shall be assessed for each additional bath or kitchen.
      1. No additional fee shall be charged for the first 100 feet of water and sewer lines, hose bibbs, icemakers, underfloor lowpoint drains, and rain drain packages that include the piping, gutters, downspouts, and perimeter system.
      2. The plumbing permit fee described in this section does not include:
        1. Any storm water retention/detention facility;
        2. Irrigation and fire suppression systems; or
        3. Additional water, sewer and service piping or private storm drainage systems exceeding the first 100 feet.
      3. Permit fees for an addition, alteration, or repair shall be calculated based on the number of fixtures, appurtenances, and piping, with a set minimum fee.
    2. A mechanical permit fee shall be calculated per appliance and related equipment, with a set minimum fee.
    3. Effective January 1, 2009, a structural permit fee for new construction and additions shall be calculated using the ICC Building Valuation Data Table current as of April 1 of each year, multiplied by the square footage of the dwelling to determine the valuation. The valuation shall then be applied to the municipality's fee schedule to determine the permit fee. The plan review fee shall be based on a predetermined percentage of the permit fee set by the municipality.
      1. The square footage of a dwelling, addition, or garage shall be determined from outside exterior wall to outside exterior wall for each level.
      2. The square footage of a carport, covered porch, patio, or deck shall be calculated separately at fifty percent of the value of a private garage from the ICC Building Valuation Data Table current as of April 1.
      3. Permit fees for an alteration or repair shall be calculated based on the fair market value as determined by the building official, and then applying the valuation to the municipality's fee schedule.
  2. Commercial construction permit fees shall be calculated using the following methodologies:
    1. A plumbing permit fee shall be calculated based on the number of fixtures and footage of piping, with a set minimum fee.
    2. A mechanical permit fee shall be calculated based on the value of the mechanical equipment and installation costs and applied to the municipality's fee schedule with a set minimum fee.
    3. A structural permit fee shall be calculated by applying the valuation to the municipality's fee schedule with a minimum set fee. Valuation shall be the greater of either:
      1. The valuation based on the ICC Building Valuation Data Table current as of April 1 of each year, using the occupancy and construction type as determined by the building official, multiplied by the square footage of the structure; or
      2. The value as stated by the applicant.
      3. When the construction or occupancy type does not fit the ICC Building Valuation Data Table, the valuation shall be determined by the building official with input from the applicant.
Stat. Auth.: ORS 455.048 & 455.055

Stats. Implemented: ORS 455.046 & 455.055

Hist.: BCD 9-2000, f. 6-15-00, cert. ef. 10-1-00; BCD 31-2005, f. 12-30-05, cert. ef. 1-1-06; BCD 5-2007, f. 5-11-07, cert. ef. 7-1-07; BCD 27-2008, f. ef.12-12-08, cert. ef. 1-1-09; BCD 7-2009, f. 9-30-09, cert. ef. 10-1-09

106.5.4 Plan Review Fees

AMENDMENT
This section has been amended at the state or city level.
Where a plan or other data is required to be submitted by Section 106.3.1, a plan review fee shall be paid at the time of submitting plans and specifications for review. The plan review fees for mechanical work shall be a percentage of the total permit fee as set forth in Section 106.5.

106.5.4.1 Separate Fees for Plan Review

AMENDMENT
This section has been amended at the state or city level.
The plan review fees in this section are separate fees from the permit fees specified in Section 106.5 and are in addition to the permit fees. The state surcharge is not applied to plan review fees.

106.5.4.2 Incomplete or Changed Plans

AMENDMENT
This section has been amended at the state or city level.
When plans are incomplete or changed so as to require additional plan review, an additional plan review fee shall be charged according to the rate established by the municipality, or OAR Chapter 918, Division 460 where the State of Oregon has jurisdiction.

[A] 107.1 General

AMENDMENT
This section has been amended at the state or city level.
The building official is authorized to conduct such inspections as are deemed necessary to determine compliance with the provisions of this code. Construction or work for which a permit is required shall be subject to inspection by the building official, and such construction or work shall remain accessible and exposed for inspection purposes until approved. Approval as a result of an inspection shall not be construed to be an approval of a violation of the provisions of this code. Inspections presuming to give authority to violate or cancel the provisions of this code shall not be valid.

[A] 107.2 Required Inspections and Testing

AMENDMENT
This section has been amended at the state or city level.

The building official, upon notification from the permit holder or the permit holder's agent, shall make the following inspections and other such inspections as necessary, and shall either release that portion of the construction or shall notify the permit holder or the permit holder's agent of violations that must be corrected. The holder of the permit shall be responsible for the scheduling of such inspections.

  1. Underground inspection shall be made after trenches or ditches are excavated and bedded, piping installed, and before backfill is put in place. Where excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site.
  2. Rough-in inspection shall be made after the roof, framing, fireblocking and bracing are in place and all ducting and other components to be concealed are complete, and prior to the installation of wall or ceiling membranes.
  3. Final inspection shall be made upon completion of the mechanical system.

Exception: Ground-source heat pump loop systems tested in accordance with Section 1210.10 shall be permitted to be backfilled prior to inspection.

The requirements of this section shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and before any portion of such equipment or appliances is concealed by any permanent portion of the structure.

[A] 107.2.1 Other Inspections

AMENDMENT
This section has been amended at the state or city level.
In addition to the inspections specified in Section 107.2, the building official is authorized to make or require other inspections of any construction work to ascertain compliance with the provisions of this code that are enforced.

[A] 107.2.2 Inspection Requests

AMENDMENT
This section has been amended at the state or city level.
It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code.

[A] 107.2.3 Approval Required

AMENDMENT
This section has been amended at the state or city level.
Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the building official. The building official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the building official.

[A] 107.2.4 Approved Inspection Agencies

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.5 Evaluation and Follow-Up Inspection Services

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.5.1 Evaluation Service

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.5.2 Follow-Up Inspection

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.5.3 Test and Inspection Records

AMENDMENT
This section has been amended at the state or city level.

[A] 107.3 Testing

AMENDMENT
This section has been amended at the state or city level.
Mechanical systems shall be tested as required in this code and in accordance with Sections 107.3.1 through 107.3.3. Tests shall be made by the permit holder and observed by the building official.

[A] 107.3.1 New, Altered, Extended or Repaired Systems

AMENDMENT
This section has been amended at the state or city level.
New mechanical systems and parts of existing systems, which have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects.

[A] 107.3.2 Apparatus, Material and Labor for Tests

AMENDMENT
This section has been amended at the state or city level.
Apparatus, material and labor required for testing a mechanical system or part thereof shall be furnished by the permit holder.

[A] 107.3.3 Reinspection and Testing

AMENDMENT
This section has been amended at the state or city level.
Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be resubmitted to the building official for inspection and testing. Reinspection fees shall be in accordance with a rate established by the municipality, or as established by the state where the State of Oregon has jurisdiction.

107.4 Contractor Responsibilities

AMENDMENT
This section has been amended at the state or city level.
It shall be the responsibility of every contractor who enters into contracts for the installation or repair of mechanical systems for which a permit is required to comply with adopted state and local rules and regulations concerning licensing and permits.

[A] 107.4 107.5 Approval

AMENDMENT
This section has been amended at the state or city level.
After the prescribed tests and inspections indicate that the work complies in all respects with this code, a notice of approval shall be issued by the building official.

[A] 107.4.1 107.5.1 Revocation

AMENDMENT
This section has been amended at the state or city level.
The building official is authorized to, in writing, suspend or revoke a notice of approval issued under the provisions of this code wherever the notice is issued in error, on the basis of incorrect information supplied, or where it is determined that the building or structure, premise or portion thereof is in violation of any ordinance or regulation or any of the provisions of this code.

[A] 107.5 Temporary Connection

AMENDMENT
This section has been amended at the state or city level.
The building official shall have the authority to authorize the temporary connection of a mechanical system to the sources of energy for the purpose of testing mechanical systems or for use under a temporary certificate of occupancy.

[A] 107.6 Connection of Service Utilities

AMENDMENT
This section has been amended at the state or city level.
A person shall not make connections from a utility, source of energy, fuel or power to any building or system that is regulated by this code for which a permit is required, until authorized by the building official.

[A] 108.1 Unlawful Acts

AMENDMENT
This section has been amended at the state or city level.

108.1 Prohibited Acts

AMENDMENT
This section has been amended at the state or city level.
Prohibited acts are described in ORS 455.450.
ORS 455.450 is not part of this code but is reprinted here for the reader's convenience:

455.450 Prohibited acts. A person may not:
  1. Violate, or procure or assist in the violation of, any final order the Director of the Department of Consumer and Business Services, an advisory board, a state administrative officer or any local appeals board, building official or inspector, concerning the application of the state building code in a particular case or concerning a license, certificate, registration or other authorization.
  2. Engage in, or procure or assist any other person to engage in, any conduct or activity for which a permit, label, license, certificate, registration or other formal authorization is required by any specialty code, any provision of ORS 446.003 to 446.200, 446.225 to 446.285, 446.395 to 446.420, 446.566 to 446.646, 446.666 to 446.746, 479.510 to 479.945, 479.950 and 480.510 to 480.670, this chapter or ORS chapter 447, 460 or 693 or any rule adopted or order issued for the administration and enforcement of these provisions without first having obtained such permit, label, license, certificate, registration or other formal authorization.
  3. Violate, or procure or assist in the violation of, any standard, specification, requirement, prohibition or other technical provision set forth in the state building code or an applicable local building code or in any rule or order of the Department of Consumer and Business Services, an advisory board, a local governing body or local building official. [Formerly 456.885 (1); 2007 c.306 §3]

[A] 108.2 Notice of Violation

AMENDMENT
This section has been amended at the state or city level.
The building official is authorized to serve a notice of violation or order to the person responsible for the erection, installation, alteration, extension or repair of mechanical work in violation of the provisions of this code, or in violation of a detail statement or the approved construction documents thereunder, or in violation of a permit or certificate issued under the provisions of this code. Such order shall direct the discontinuance of the illegal action or condition and the abatement of the violation.

[A] 108.3 Prosecution of Violation

AMENDMENT
This section has been amended at the state or city level.

[A] 108.4 108.3 Violation Penalties

AMENDMENT
This section has been amended at the state or city level.
Persons who violate a provision of this code or fail to comply with any of the requirements thereof or who erect, install, alter or repair mechanical work in violation of the approved construction documents or directive of the building official, or of a permit or certificate issued under the provisions of this code may be subject to penalties as prescribed by law.

108.3.1 Penalty Amounts

AMENDMENT
This section has been amended at the state or city level.
Penalty amounts, except those described in Section 106.5.1, are limited by ORS 455.895 or as adopted by the municipality having authority. Local authority to levy penalties is limited to violations of code application.
ORS 455.895 is not part of this code but is reprinted here for the reader's convenience:

455.895 Civil penalties.
    1. The State Plumbing Board may impose a civil penalty against a person as provided under ORS 447.992 and 693.992. Amounts recovered under this paragraph are subject to ORS 693.165.
    2. The Electrical and Elevator Board may impose a civil penalty against a person as provided under ORS 479.995. Amounts recovered under this paragraph are subject to ORS 479.850.
    3. The Board of Boiler Rules may impose a civil penalty against a person as provided under ORS 480.670. Amounts recovered under this paragraph are subject to ORS 480.670.
  1. The Department of Consumer and Business Services, or an appropriate advisory board, if any, may at its discretion impose a civil penalty against any person who violates the state building code or ORS 446.003 to 446.200, 446.225 to 446.285, 446.395 to 446.420, 446.566 to 446.646, 446.666 to 446.746, 479.510 to 479.945, 479.950 or 480.510 to 480.670, or this chapter or ORS chapter 447, 460 or 693, or any rule adopted or order issued for the administration and enforcement of those statutes. Except as provided in subsections (3), (4) and (9) of this section or ORS 446.995, a civil penalty imposed under this section must be in an amount determined by the appropriate advisory board or the department of not more than $5,000 for each offense or, in the case of a continuing offense, not more than $1,000 for each day of the offense.
  2. Each violation of ORS 446.003 to 446.200 or 446.225 to 446.285, or any rule or order issued under ORS 446.003 to 446.200 or 446.225 to 446.285, constitutes a separate violation with respect to each manufactured structure or with respect to each failure or refusal to allow or perform an act required thereby, except that the maximum civil penalty may not exceed $1 million for any related series of violations occurring within one year from the date of the first violation.
  3. The department may impose a civil penalty of not more than $25,000 against a public body responsible for administering and enforcing a building inspection program. As used in this subsection, "public body" has the meaning given that term in ORS 174.109.
  4. The maximum penalty established by this section for a violation may be imposed only upon a finding that the person has engaged in a pattern of violations. The department, by rule, shall define what constitutes a pattern of violations. Except as provided in subsections (1) and (10) of this section, moneys received from any civil penalty under this section are appropriated continuously for and shall be used by the department for enforcement and administration of provisions and rules described in subsection (2) of this section.
  5. Civil penalties under this section shall be imposed as provided in ORS 183.745.
  6. A civil penalty imposed under this section may be remitted or reduced upon such terms and conditions as the department or the appropriate advisory board considers proper and consistent with the public health and safety. In any judicial review of a civil penalty imposed under this section, the court may, in its discretion, reduce the penalty.
  7. Any officer, director, shareholder or agent of a corporation, or member or agent of a partnership or association, who personally participates in or is an accessory to any violation by the partnership, association or corporation of a provision or rule described in subsection (2) of this section is subject to the penalties prescribed in this section.
  8. In addition to the civil penalty set forth in subsection (1) or (2) of this section, any person who violates a provision or rule described in subsection (2) of this section may be required by the department or the appropriate advisory board to forfeit and pay to the General Fund of the State Treasury a civil penalty in an amount determined by the department or advisory board that does not exceed five times the amount by which such person profited in any transaction that violates a provision or rule described in subsection (2) of this section.
  9. If a civil penalty is imposed for a violation of a provision of ORS 446.566 to 446.646 and the violation relates to a filing or failure to file with a county assessor functioning as agent of the department, the department, after deducting an amount equal to the department's procedural, collection and other related costs and expenses, shall forward one-half of the remaining civil penalty amount to the county in which the manufactured structure is located at the time of the violation. [1991 c.792 §4; 1991 c.734 §111; 1999 c.1045 §19; 2001 c.411 §21; 2003 c.14 §286; 2003 c.655 §76; 2007 c.549 §6; 2007 c.898 §1; 2013 c.324 §11]

[A] 108.5 108.4 Stop Work Orders

AMENDMENT
This section has been amended at the state or city level.
Upon notice from the building official that mechanical work is being performed contrary to the provisions of this code or in a dangerous or unsafe manner, such work shall immediately cease. Such notice shall be in writing and shall be given to the owner of the property, or to the owner's authorized agent, or to the person doing the work. The notice shall state the conditions under which work is authorized to resume. Where an emergency exists, the building official shall not be required to give a written notice prior to stopping the work. Any person who shall continue any work on the system after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, may be liable for a fine.
The requirements of Sections 108.5 through 108.7.1 are not adopted by the State of Oregon Building Codes Division as part of the state building code but may be specifically adopted by a local municipality.

[A] 108.6 108.5 Abatement of Violation

AMENDMENT
This section has been amended at the state or city level.
The imposition of the penalties herein prescribed shall not preclude the legal officer of the municipality from instituting appropriate action to prevent unlawful construction or to restrain, correct or abate a violation, or to prevent illegal occupancy of a building, structure or premises, or to stop an illegal act, conduct, business or utilization of the mechanical system on or about any premises.

[A] 108.7 108.6 Unsafe Mechanical Systems

AMENDMENT
This section has been amended at the state or city level.
A mechanical system that is unsafe, constitutes a fire or health hazard, or is otherwise dangerous to human life, as regulated by this code, is hereby declared as an unsafe mechanical system. Use of a mechanical system regulated by this code constituting a hazard to health, safety or welfare by reason of inadequate maintenance, dilapidation, fire hazard, disaster, damage or abandonment is hereby declared an unsafe use. Such unsafe equipment and appliances are hereby declared to be a public nuisance and shall be abated by repair, rehabilitation, demolition or removal.

[A] 108.7.1 108.6.1 Authority to Condemn Mechanical Systems

AMENDMENT
This section has been amended at the state or city level.

Where the building official determines that any mechanical system, or portion thereof, regulated by this code has become hazardous to life, health, property, or has become insanitary, the building official shall order in writing that such system either be removed or restored to a safe condition. A time limit for compliance with such order shall be specified in the written notice. A person shall not use or maintain a defective mechanical system after receiving such notice.

     Where such mechanical system is to be disconnected, written notice as prescribed in Section 108.2 shall be given. In cases of immediate danger to life or property, such disconnection shall be made immediately without such notice.

[A] 108.7.2 108.6.2 Authority to Order Disconnection of Energy Sources

AMENDMENT
This section has been amended at the state or city level.
The building official shall have the authority to order disconnection of energy sources supplied to a building, structure or mechanical system regulated by this code, where it is determined that the mechanical system or any portion thereof has become hazardous or unsafe. Written notice of such order to disconnect service and the causes therefor shall be given within 24 hours to the owner, the owner's authorized agent and occupant of such building, structure or premises, provided, however, that in cases of immediate danger to life or property, such disconnection shall be made immediately without such notice. Where energy sources are provided by a public utility, the building official shall immediately notify the serving utility in writing of the issuance of such order to disconnect.

[A] 108.7.3 108.6.3 Connection After Order to Disconnect

AMENDMENT
This section has been amended at the state or city level.

A person shall not make energy source connections to mechanical systems regulated by this code that have been disconnected or ordered to be disconnected by the building official, or the use of which has been ordered to be discontinued by the building official until the building official authorizes the reconnection and use of such mechanical systems.

     Where a mechanical system is maintained in violation of this code, and in violation of a notice issued pursuant to the provisions of this section, the building official shall institute appropriate action to prevent, restrain, correct or abate the violation.

Section 109 Means Board of Appeals

AMENDMENT
This section has been amended at the state or city level.

[A] 109.1 Application for Appeal

AMENDMENT
This section has been amended at the state or city level.

109.1 General

AMENDMENT
This section has been amended at the state or city level.
In order to hear and decide appeals of orders, decisions, or determinations made by the building official relative to the application and interpretation of this code, the local municipality shall establish an appeals procedure.

[A] 109.1.1 Limitation of Authority

AMENDMENT
This section has been amended at the state or city level.
An application for appeal shall be based on a claim that the true intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply, or an equally good or better form of construction is proposed. An appeals board, where appointed, shall have no authority to waive requirements of this code.

[A] 109.2 Membership of Board

AMENDMENT
This section has been amended at the state or city level.

109.2 Qualifications

AMENDMENT
This section has been amended at the state or city level.
An appeals board, where appointed, shall consist of members who are qualified by experience and training to pass on matters pertaining to professions or disciplines applicable to this code.

[A] 109.2.1 Qualifications

AMENDMENT
This section has been amended at the state or city level.

[A] 109.2.2 Alternate Members

AMENDMENT
This section has been amended at the state or city level.

[A] 109.2.3 Chairman

AMENDMENT
This section has been amended at the state or city level.

[A] 109.2.4 Disqualification of Member

AMENDMENT
This section has been amended at the state or city level.

[A] 109.2.5 Secretary

AMENDMENT
This section has been amended at the state or city level.

[A] 109.2.6 Compensation of Members

AMENDMENT
This section has been amended at the state or city level.

[A] 109.3 Notice of Meeting

AMENDMENT
This section has been amended at the state or city level.

109.3 Alternative Appeal Process

AMENDMENT
This section has been amended at the state or city level.
ORS 455.475 provides an alternative appeal process to any established by a local municipality. An applicant for a building permit may choose to appeal a building official's decision to a local appeals board or directly to the appropriate specialty code program chief.

Note: Forms for filing an appeal under ORS 455.475 are available online at: www.oregon.gov/bcd.
ORS 455.475 is not part of this code but is reprinted here for the reader's convenience:

455.475. Appeal of decision of building official.
  1. An applicant for a building permit may appeal a decision made by a building official under authority established pursuant to ORS 455.148, 455.150 or 455.467. The following apply to an appeal under this subsection:
    1. An appeal regarding the interpretation or application of a particular specialty code provision shall be made first to the appropriate specialty code chief inspector of the Department of Consumer and Business Services. The decision of the department chief inspector may be appealed to the appropriate advisory board. The decision of the advisory board may only be appealed to the Director of the Department of Consumer and Business Services if codes in addition to the applicable specialty code are at issue.
    2. If the appropriate advisory board determines that a decision by the department chief inspector is a major code interpretation, then the inspector shall distribute the decision in writing to all applicable specialty code public and private inspection authorities in the state. The decision shall be distributed within 60 days after the board's determination, and there shall be no charge for the distribution of the decision. As used in this paragraph, a "major code interpretation" means a code interpretation decision that affects or may affect more than one job site or more than one inspection jurisdiction.
  2. Except as provided in subsection (1) of this section, an applicant for a building permit may appeal the decision of a building official on any matter relating to the administration and enforcement of this chapter to the department. The appeal must be in writing. A decision by the department on an appeal filed under this subsection is subject to judicial review as provided in ORS 183.484.
  3. If an appeal is made under this section, an inspection authority shall extend the plan review deadline by the number of days it takes for a final decision to be issued for the appeal. [1999 c.1045 §23; 2001 c.573 §15; 2013 c. 528 §13]
ORS 455.690 is not part of this code but is reprinted here for the reader's convenience:

455.690 Appeal to advisory boards.

Any person aggrieved by the final decision of a municipal appeals board or a subordinate officer of the Department of Consumer and Business Services as to the application of any provision of a specialty code may, within 30 days after the date of the decision, appeal to the appropriate advisory board. The appellant shall submit a fee of $20, payable to the department, with the request for appeal. The final decision of the involved municipality or state officer shall be subject to review and final determination by the appropriate advisory board as to technical and scientific determinations related to the application of the specialty code involved. [Formerly 456.850; 1993 c.744 §98]

[A] 109.4 Open Hearing

AMENDMENT
This section has been amended at the state or city level.

[A] 109.4.1 Procedure

AMENDMENT
This section has been amended at the state or city level.

[A] 109.5 Postponed Hearing

AMENDMENT
This section has been amended at the state or city level.

[A] 109.6 Board Decision

AMENDMENT
This section has been amended at the state or city level.

[A] 109.6.1 Resolution

AMENDMENT
This section has been amended at the state or city level.

[A] 109.6.2 Administration

AMENDMENT
This section has been amended at the state or city level.

[A] 109.7 Court Review

AMENDMENT
This section has been amended at the state or city level.

[A] 110.1 General

AMENDMENT
This section has been amended at the state or city level.
The building official is authorized to issue a permit for temporary equipment, systems and uses. Such permits shall be limited as to time of service, but shall not be permitted for more than 180 days. The building official is authorized to grant extensions for demonstrated cause.
Temporary equipment, systems and uses shall conform to the structural strength, fire safety, means of egress, accessibility, light, ventilation and sanitary requirements of this code as necessary to ensure the public health, safety and general welfare.

[A] 110.3 Temporary Utilities

AMENDMENT
This section has been amended at the state or city level.
The building official is authorized to give permission to temporarily supply utilities before an installation has been fully completed and the final certificate of completion has been issued. The part covered by the temporary certificate shall comply with the requirements specified for temporary lighting, heat or power in the code.

[A] 110.4 Termination of Approval

AMENDMENT
This section has been amended at the state or city level.
The building official is authorized to terminate such permit for temporary equipment, systems or uses and to order the temporary equipment, systems or uses to be discontinued.