ADOPTS WITH AMENDMENTS:

International Fire Code 2012 (IFC 2012)

Heads up: There are no suggested sections in this chapter.
Heads up: There are no amended sections in this chapter.
High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the following material-specific requirements shall apply:
  1. Aerosols shall be in accordance with Chapter 51.
  2. Flammable and combustible liquids shall be in accordance with Chapter 57.
  3. Hazardous materials shall be in accordance with Chapter 50.
  4. Storage of combustible paper records shall be in accordance with NFPA 13.
  5. Storage of combustible fibers shall be in accordance with Chapter 52.
  6. General storage of combustible material shall be in accordance with Chapter 3.
A permit shall be required as set forth in Section 105.6.
At the time of building permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International Building Code, the storage permit submittal shall include the information specified in this section. Following approval of the plans, a copy of the approved plans shall be maintained on the premises in an approved location. The plans shall include the following:
  1. Floor plan of the building showing locations and dimensions of high-piled storage areas.
  2. Usable storage height for each storage area.
  3. Number of tiers within each rack, if applicable.
  4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement.
  5. Aisle dimensions between each storage array.
  6. Maximum pile volume for each storage array.
  7. Location and classification of commodities in accordance with Section 3203.
  8. Location of commodities which are banded or encapsulated.
  9. Location of required fire department access doors.
  10. Type of fire suppression and fire detection systems.
  11. Location of valves controlling the water supply of ceiling and in-rack sprinklers.
  12. Type, location and specifications of smoke removal and curtain board systems.
  13. Dimension and location of transverse and longitudinal flue spaces.
  14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area shall be provided at the time of permit, when required by the fire code official.
When required by the fire code official, an evacuation plan for public accessible areas and a separate set of plans indicating location and width of aisles, location of exits, exit access doors, exit signs, height of storage, and locations of hazardous materials shall be submitted at the time of permit application for review and approval. Following approval of the plans, a copy of the approved plans shall be maintained on the premises in an approved location.
Commodities shall be classified as Class I, II, III, IV or high hazard in accordance with this section. Materials listed within each commodity classification are assumed to be unmodified for improved combustibility characteristics. Use of flame-retarding modifiers or the physical form of the material could change the classification. See Section 3203.7 for classification of Group A, B and C plastics.
Class I commodities are essentially noncombustible products on wooden or nonexpanded polyethylene solid deck pallets, in ordinary corrugated cartons with or without single-thickness dividers, or in ordinary paper wrappings with or without pallets. Class I commodities are allowed to contain a limited amount of Group A plastics in accordance with Section 3203.7.4. Examples of Class I commodities include, but are not limited to, the following:
  1. Alcoholic beverages not exceeding 20-percent alcohol
  2. Appliances noncombustible, electrical
  3. Cement in bags
  4. Ceramics
  5. Dairy products in nonwax-coated containers (excluding bottles)
  6. Dry insecticides
  7. Foods in noncombustible containers
  8. Fresh fruits and vegetables in nonplastic trays or containers
  9. Frozen foods
  10. Glass
  11. Glycol in metal cans
  12. Gypsum board
  13. Inert materials, bagged
  14. Insulation, noncombustible
  15. Noncombustible liquids in plastic containers having less than a 5-gallon (19 L) capacity
  16. Noncombustible metal products
Class II commodities are Class I products in slatted wooden crates, solid wooden boxes, multiple-thickness paperboard cartons or equivalent combustible packaging material with or without pallets. Class II commodities are allowed to contain a limited amount of Group A plastics in accordance with Section 3203.7.4. Examples of Class II commodities include, but are not limited to, the following:
Alcoholic beverages not exceeding 20-percent alcohol, in combustible containers
Foods in combustible containers
Incandescent or fluorescent light bulbs in cartons
Thinly coated fine wire on reels or in cartons

3203.4 Class III Commodities

AMENDMENT
This section has been amended at the state or city level.
Class III commodities are commodities of wood, paper, natural fiber cloth, or Group C plastics or products thereof, with or without pallets. Products are allowed to contain limited amounts of Group A or B plastics, such as metal bicycles with plastic handles, pedals, seats and tires. Group A plastics shall be limited in accordance with Section 3203.7.4. Examples of Class III commodities include, but are not limited to, the following:
  1. Aerosol, Level 1 (see Chapter 51 28)
  2. Combustible fiberboard
  3. Cork, baled
  4. Feed, bagged
  5. Fertilizers, bagged
  6. Food in plastic containers
  7. Furniture: wood, natural fiber, upholstered, nonplastic, wood or metal with plastic-padded and covered arm-rests
  8. Glycol in combustible containers not exceeding 25 percent
  9. Lubricating or hydraulic fluid in metal cans
  10. Lumber
  11. Mattresses, excluding foam rubber and foam plastics
  12. Noncombustible liquids in plastic containers having a capacity of more than 5 gallons (19 L)
  13. Paints, oil base, in metal cans
  14. Paper, waste, baled
  15. Paper and pulp, horizontal storage, or vertical storage that is banded or protected with approved wrap
  16. Paper in cardboard boxes
  17. Pillows, excluding foam rubber and foam plastics
  18. Plastic-coated paper food containers
  19. Plywood
  20. Rags, baled
  21. Rugs, without foam backing
  22. Sugar, bagged
  23. Wood, baled
  24. Wood doors, frames and cabinets
  25. Yarns of natural fiber and viscose
Class IV commodities are Class I, II or III products containing Group A plastics in ordinary corrugated cartons and Class I, II and III products with Group A plastic packaging, with or without pallets. Group B plastics and free-flowing Group A plastics are also included in this class. The total amount of nonfree-flowing Group A plastics shall be in accordance with Section 3203.7.4. Examples of Class IV commodities include, but are not limited to, the following:
  1. Aerosol, Level 2 (see Chapter 51 )
  2. Alcoholic beverages, exceeding 20-percent but less than 80-percent alcohol, in cans or bottles in cartons
  3. Clothing, synthetic or nonviscose
  4. Combustible metal products (solid)
  5. Furniture, plastic upholstered
  6. Furniture, wood or metal with plastic covering and padding
  7. Glycol in combustible containers (greater than 25 percent and less than 50 percent)
  8. Linoleum products
  9. Paints, oil base in combustible containers
  10. Pharmaceutical, alcoholic elixirs, tonics, etc.
  11. Rugs, foam back
  12. Shingles, asphalt
  13. Thread or yarn, synthetic or nonviscose
High-hazard commodities are high-hazard products presenting special fire hazards beyond those of Class I, II, III or IV. Group A plastics not otherwise classified are included in this class. Examples of high-hazard commodities include, but are not limited to, the following:
  1. Aerosol, Level 3 (see Chapter 51 )
  2. Alcoholic beverages, exceeding 80-percent alcohol, in bottles or cartons
  3. Commodities of any class in plastic containers in carousel storage
  4. Flammable solids (except solid combustible metals)
  5. Glycol in combustible containers (50 percent or greater)
  6. Lacquers, which dry by solvent evaporation, in metal cans or cartons
  7. Lubricating or hydraulic fluid in plastic containers
  8. Mattresses, foam rubber or foam plastics
  9. Pallets and flats which are idle combustible
  10. Paper and pulp, rolled, in vertical storage which is unbanded or not protected with an approved wrap
  11. Paper, asphalt, rolled, horizontal storage
  12. Paper, asphalt, rolled, vertical storage
  13. Pillows, foam rubber and foam plastics
  14. Pyroxylin
  15. Rubber tires
  16. Vegetable oil and butter in plastic containers
Plastics shall be designated as Group A, B or C in accordance with Sections 3203.7.1 through 3203.7.4.
Group A plastics are plastic materials having a heat of combustion that is much higher than that of ordinary combustibles, and a burning rate higher than that of Group B plastics. Examples of Group A plastics include, but are not limited to, the following:
  1. ABS (acrylonitrile-butadiene-styrene copolymer)
  2. Acetal (polyformaldehyde)
  3. Acrylic (polymethyl methacrylate)
  4. Butyl rubber
  5. EPDM (ethylene propylene rubber)
  6. FRP (fiberglass-reinforced polyester)
  7. Natural rubber (expanded)
  8. Nitrile rubber (acrylonitrile butadiene rubber)
  9. PET or PETE (polyethylene terephthalate)
  10. Polybutadiene
  11. Polycarbonate
  12. Polyester elastomer
  13. Polyethylene
  14. Polypropylene
  15. Polystyrene (expanded and unexpanded)
  16. Polyurethane (expanded and unexpanded)
  17. PVC (polyvinyl chloride greater than 15-percent plasticized, e.g., coated fabric unsupported film)
  18. SAN (styrene acrylonitrile)
  19. SBR (styrene butadiene rubber)
Group B plastics are plastic materials having a heat of combustion and a burning rate higher than that of ordinary combustibles, but not as high as those of Group A plastics. Examples of Group B plastics include, but are not limited to, the following:
  1. Cellulosics (cellulose acetate, cellulose acetate butyrate, ethyl cellulose)
  2. Chloroprene rubber
  3. Fluoroplastics (ECTFE, ethylene-chlorotrifluoroethylene copolymer; ETFE, ethylene-tetrafluoroethylene copolymer; FEP, fluorinated ethylene-propylene copolymer)
  4. Natural rubber (nonexpanded)
  5. Nylon (Nylon 6, Nylon 6/6)
  6. PVC (polyvinyl chloride greater than 5-percent, but not exceeding 15-percent plasticized)
  7. Silicone rubber
Group C plastics are plastic materials having a heat of combustion and a burning rate similar to those of ordinary combustibles. Examples of Group C plastics include, but are not limited to, the following:
  1. Fluoroplastics (PCTFE, polychlorotrifluoroethylene; PTFE, polytetrafluoroethylene)
  2. Melamine (melamine formaldehyde)
  3. Phenol
  4. PVC (polyvinyl chloride, rigid or plasticized less than 5 percent, e.g., pipe, pipe fittings)
  5. PVDC (polyvinylidene chloride)
  6. PVDF (polyvinylidene fluoride)
  7. PVF (polyvinyl fluoride)
  8. Urea (urea formaldehyde)
Figure 3203.7.4 shall be used to determine the quantity of Group A plastics allowed to be stored in a package or carton or on a pallet without increasing the commodity classification.

FIGURE 3203.7.4
MIXED COMMODITIESa, b
  1. This figure is intended to determine the commodity classification of a mixed commodity in a package, carton or on a pallet where plastics are involved.
  2. The following is an example of how to apply the figure: A package containing a Class III commodity has 12-percent Group A expanded plastic by volume. The weight of the unexpanded Group A plastic is 10 percent. This commodity is classified as a Class IV commodity. If the weight of the unexpanded plastic is increased to 14 percent, the classification changes to a high-hazard commodity.


High-piled storage areas, and portions of high-piled storage areas intended for storage of a different commodity class than adjacent areas, shall be designed and specifically designated to contain Class I, Class II, Class III, Class IV or high-hazard commodities. The designation of a high-piled combustible storage area, or portion thereof intended for storage of a different commodity class, shall be based on the highest hazard commodity class stored except as provided in Section 3204.2.
The designation of a high-piled combustible storage area, or portion thereof, is allowed to be based on a lower hazard class than that of the highest class of commodity stored when a limited quantity of the higher hazard commodity has been demonstrated by engineering analysis to be adequately protected by the automatic sprinkler system provided. The engineering analysis shall consider the ability of the sprinkler system to deliver the higher density required by the higher hazard commodity. The higher density shall be based on the actual storage height of the pile or rack and the minimum allowable design area for sprinkler operation as set forth in the density/area figures provided in NFPA 13. The contiguous area occupied by the higher hazard commodity shall not exceed 120 square feet (11 m2) and additional areas of higher hazard commodity shall be separated from other such areas by 25 feet (7620 mm) or more. The sprinkler system shall be capable of delivering the higher density over a minimum area of 900 square feet (84 m2) for wet pipe systems and 1,200 square feet (111 m2) for dry pipe systems. The shape of the design area shall be in accordance with Section 903.
The structural integrity of racks shall be maintained.
Clearance from ignition sources shall be provided in accordance with Section 305.
Smoking shall be prohibited. Approved "No Smoking" signs shall be conspicuously posted in accordance with Section 310.
When restocking is not being conducted, aisles shall be kept clear of storage, waste material and debris. Fire department access doors, aisles and exit doors shall not be obstructed. During restocking operations using manual stocking methods, a minimum unobstructed aisle width of 24 inches (610 mm) shall be maintained in 48-inch (1219 mm) or smaller aisles, and a minimum unobstructed aisle width of one-half of the required aisle width shall be maintained in aisles greater than 48 inches (1219 mm). During mechanical stocking operations, a minimum unobstructed aisle width of 44 inches (1118 mm) shall be maintained in accordance with Section 3206.9.
Pile dimensions and height limitations shall comply with Section 3207.3.
Where required by the fire code official, a visual method of indicating the maximum allowable storage height shall be provided.
Arrays shall comply with Section 3207.4.
Fire protection and life safety features for high-piled storage areas shall be in accordance with Sections 3206.2 through 3206.10.
Where required by Table 3206.2, fire detection systems, smoke and heat removal, draft curtains and automatic sprinkler design densities shall extend the lesser of 15 feet (4572 mm) beyond the high-piled storage area or to a permanent partition. Where portions of high-piled storage areas have different fire protection requirements because of commodity, method of storage or storage height, the fire protection features required by Table 3206.2 within this area shall be based on the most restrictive design requirements.
TABLE 3206.2
GENERAL FIRE PROTECTION AND LIFE SAFETY REQUIREMENTS
COMMODITY CLASS SIZE OF HIGH-PILED
STORAGE AREAa

(square feet)
(see Sections 3206.2
and 3206.4 )
ALL STORAGE AREAS
(See Sections 3206 , 3207 and 3208 )b
SOLID-PILED STORAGE, SHELF
STORAGE AND PALLETIZED STORAGE
(see Section 3207.3 )
Automatic fire-
extinguishing system
(see Section 3206.4 )
Fire
detection
system
(see Section 3206.5 )
Building
access
(see Section 3206.6 )
Smoke and
heat
removal
(see Section 3206.7 )
Draft
curtains
(see Section 3206.7 )
Maximum
pile dimensionc

(feet)
Maximum
permissible
storage heightd

(feet)
Maximum
pile volume
(cubic feet)
I-IV 0-500 Not
Requireda
Not
Required
Not
Requirede
Not
Required
Not
Required
Not
Required
Not
Required
Not Required
501-2,500 Not
Requireda
Yesi Not
Requirede
Not
Required
Not
Required
100 40 100,000
2,501-12,000
Public accessible
Yes Not
Required
Not
Requirede
Not
Required
Not
Required
100 40 400,000
2,501-12,000
Nonpublic accessible
(Option 1)
Yes Not
Required
Not
Requirede
Not
Required
Not
Required
100 40 400,000
2,501-12,000
Nonpublic accessible
(Option 2)
Not
Requireda
Yes Yes Yesj Yesj 100 30f 200,000
12,001-20,000 Yes Not
Required
Yes Yesj Not
Required
100 40 400,000
20,001-500,000 Yes Not
Required
Yes Yesj Not
Required
100 40 400,000
Greater than
500,000g
Yes Not
Required
Yes Yesj Not
Required
100 40 400,000
High
hazard
0-500 Not
Requireda
Not
Required
Not
Requirede
Not
Required
Not
Required
50 Not
Required
Not Required
501-2,500
Public accessible
Yes Not
Required
Not
Requirede
Not
Required
Not
Required
50 30 75,000
501-2,500
Nonpublic accessible
(Option 1)
Yes Not
Required
Not
Requirede
Not
Required
Not
Required
50 30 75,000
501-2,500
Nonpublic accessible
(Option 2)
Not
Requireda
Yes Yes Yesj Yesj 50 20 50,000
2,501-300,000 Yes Not
Required
Yes Yesj Not
Required
50 30 75,000
300,001-500,000g, h Yes Not
Required
Yes Yesj Not
Required
50 30 75,000
For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m3, 1 square foot = 0.0929 m2.
  1. When automatic sprinklers are required for reasons other than those in Chapter 32, the portion of the sprinkler system protecting the high-piled storage area shall be designed and installed in accordance with Sections 3207 and 3208.
  2. For aisles, see Section 3206.9.
  3. Piles shall be separated by aisles complying with Section 3206.9.
  4. For storage in excess of the height indicated, special fire protection shall be provided in accordance with Note g when required by the fire code official. See also Chapters 51 and 57 for special limitations for aerosols and flammable and combustible liquids, respectively.
  5. Section 503 shall apply for fire apparatus access.
  6. For storage exceeding 30 feet in height, Option 1 shall be used.
  7. Special fire protection provisions including, but not limited to, fire protection of exposed steel columns; increased sprinkler density; additional in-rack sprinklers, without associated reductions in ceiling sprinkler density; or additional fire department hose connections shall be provided when required by the fire code official.
  8. High-piled storage areas shall not exceed 500,000 square feet. A 2-hour fire wall constructed in accordance with Section 706 the International Building Code shall be used to divide high-piled storage exceeding 500,000 square feet in area.
  9. Not required when an automatic fire-extinguishing system is designed and installed to protect the high-piled storage area in accordance with Sections 3207 and 3208.
  10. Not required when storage areas are protected by early suppression fast response (ESFR) sprinkler systems installed in accordance with NFPA 13.
High-piled storage areas shall be separated from other portions of the building where required by Sections 3206.3.1 through 3206.3.2.2.
Mixed occupancies shall be separated in accordance with the International Building Code.
The aggregate of all high-piled storage areas within a building shall be used for the application of Table 3206.2 unless such areas are separated from each other by 1-hour fire barriers constructed in accordance with Section 707 the International Building Code. Openings in such fire barriers shall be protected by opening protectives having a 1-hour fire protection rating.
High-piled storage areas classified as Class I through IV not separated from high-piled storage areas classified as high hazard shall utilize the aggregate of all high-piled storage areas as high hazard for the purposes of the application of Table 3206.2. To be considered as separated, 1-hour fire barriers shall be constructed in accordance with Section 707 of the International Building Code. Openings in such fire barriers shall be protected by opening protectives having a 1-hour fire protection rating.

Exception: As provided for in Section 3204.2.

Automatic sprinkler systems shall be provided in accordance with Sections 3207, 3208 and 3209.
Where fire detection is required by Table 3206.2, an approved automatic fire detection system shall be installed throughout the high-piled storage area. The system shall be monitored and be in accordance with Section 907.
Where building access is required by Table 3206.2, fire apparatus access roads in accordance with Section 503 shall be provided within 150 feet (45 720 mm) of all portions of the exterior walls of buildings used for high-piled storage.
Exception: Where fire apparatus access roads cannot be installed because of topography, railways, waterways, non-negotiable grades or other similar conditions, the fire code official is authorized to require additional fire protection.
Where building access is required by Table 3206.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder.
A minimum of one access door shall be provided in each 100 lineal feet (30 480 mm), or fraction thereof, of the exterior walls that face required fire apparatus access roads. The required access doors shall be distributed such that the lineal distance between adjacent access doors does not exceed 100 feet (30 480 mm).
Access doors shall not be less than 3 feet (914 mm) in width and 6 feet 8 inches (2032 mm) in height. Roll-up doors shall not be used unless approved.
Only approved locking devices shall be used.
Where smoke and heat removal are required by Table 3206.2, smoke and heat vents shall be provided in accordance with Section 910. Where draft curtains are required by Table 3206.2, they shall be provided in accordance with Section 910.3.5.
Where exit passageways are required by the International Building Code for egress, a Class I standpipe system shall be provided in accordance with Section 905.
Aisles providing access to exits and fire department access doors shall be provided in high-piled storage areas exceeding 500 square feet (46 m2), in accordance with Sections 3206.9.1 through 3206.9.3. Aisles separating storage piles or racks shall comply with NFPA 13. Aisles shall also comply with Chapter 10.
Exception: Where aisles are precluded by rack storage systems, alternate methods of access and protection are allowed when approved.
Aisle width shall be in accordance with Sections 3206.9.1.1 and 3206.9.1.2.

Exceptions:

  1. Aisles crossing rack structures or storage piles, which are used only for employee access, shall be a minimum of 24 inches (610 mm) wide.
  2. Aisles separating shelves classified as shelf storage shall be a minimum of 30 inches (762 mm) wide.
Aisles in sprinklered buildings shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities.
Exception: Aisles in high-piled storage areas exceeding 2,500 square feet (232 m2) in area, that are accessible to the public and designated to contain high-hazard commodities, are protected by a sprinkler system designed for multiple-row racks of high-hazard commodities shall be a minimum of 44 inches (1118 mm) wide.

Aisles shall be a minimum of 96 inches (2438 mm) wide in areas accessible to the public where mechanical stocking methods are used.
Aisles in nonsprinklered buildings shall be a minimum of 96 inches (2438 mm) wide.
The required aisle width shall extend from floor to ceiling. Rack structural supports and catwalks are allowed to cross aisles at a minimum height of 6 feet 8 inches (2032 mm) above the finished floor level, provided that such supports do not interfere with fire department hose stream trajectory.
Dead-end aisles shall be in accordance with Chapter 10.
Portable fire extinguishers shall be provided in accordance with Section 906.
Shelf storage and storage in solid piles, solid piles on pallets and bin box storage in bin boxes not exceeding 5 feet (1524 mm) in any dimension, shall be in accordance with Sections 3206 and this section.
Where automatic sprinklers are required by Table 3206.2, an approved automatic sprinkler system shall be installed throughout the building or to 1-hour fire barriers constructed in accordance with Section 707 of the International Building Code. Openings in such fire barriers shall be protected by opening protectives having a 1-hour fire protection rating. The design and installation of the automatic sprinkler system and other applicable fire protection shall be in accordance with the International Building Code and NFPA 13.
Shelf storage greater than 12 feet (3658 mm) but less than 15 feet (4572 mm) in height shall be in accordance with the fire protection requirements set forth in NFPA 13. Shelf storage 15 feet (4572 mm) or more in height shall be protected in an approved manner with special fire protection, such as in-rack sprinklers.
Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with Table 3206.2.
Where an automatic sprinkler system design utilizes protection based on a closed array, array clearances shall be provided and maintained as specified by the standard used.
Rack storage shall be in accordance with Section 3206 and this section. Bin boxes exceeding 5 feet (1524 mm) in any dimension shall be regulated as rack storage.
Where automatic sprinklers are required by Table 3206.2, an approved automatic sprinkler system shall be installed throughout the building or to 1-hour fire barriers constructed in accordance with Section 707 of the International Building Code. Openings in such fire barriers shall be protected by opening protectives having a 1-hour fire protection rating. The design and installation of the automatic sprinkler system and other applicable fire protection shall be in accordance with Section 903.3.1.1 and the International Building Code.
Storage on plastic pallets or plastic shelves shall be protected by approved specially engineered fire protection systems.
Exception: Plastic pallets listed and labeled in accordance with UL 2335 shall be treated as wood pallets for determining required sprinkler protection.
Racks with solid shelving having an area greater than 32 square feet (3 m2), measured between approved flue spaces at all four edges of the shelf, shall be in accordance with this section.
Exceptions:
  1. Racks with mesh, grated, slatted or similar shelves having uniform openings not more than 6 inches (152 mm) apart, comprised of at least 50 percent of the overall shelf area, and with approved flue spaces are allowed to be treated as racks without solid shelves.
  2. Racks used for the storage of combustible paper records, with solid shelving, shall be in accordance with NFPA 13.
Fire protection for racks with solid shelving shall be in accordance with NFPA 13.
Flue spaces shall be provided in accordance with Table 3208.3. Required flue spaces shall be maintained.
TABLE 3208.3
REQUIRED FLUE SPACES FOR RACK STORAGE
RACK CONFIGURATION AUTOMATIC SPRINKLER PROTECTION SPRINKLER AT THE CEILING WITH OR WITHOUT MINIMUM IN-RACK SPRINKLERS IN-RACK SPRINKLERS AT EVERY TIER NONSPRINKLERED
≤ 25 feet > 25 feet Any height Any height
Storage height Option 1 Option 2
Single-row rack Transverse flue space Sizeb 3 inches Not Applicable 3 inches Not Required Not Required
Vertically aligned Not Required Not Applicable Yes Not Applicable Not Required
Longitudinal flue space Not Required Not Applicable Not Required Not Required Not Required
Double-row rack Transverse flue space Sizeb 6 inchesa 3 inches 3 inches Not Required Not Required
Vertically aligned Not Required Not Required Yes Not Applicable Not Required
Longitudinal flue space Not Required 6 inches 6 inches Not Required Not Required
Multi-row rack Transverse flue space Sizeb 6 inches Not Applicable 6 inches Not Required Not Required
Vertically aligned Not Required Not Applicable Yes Not Applicable Not Required
Longitudinal flue space Not Required Not Applicable Not Required Not Required Not Required
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
  1. Three-inch transverse flue spaces shall be provided at least every 10 feet where ESFR sprinkler protection is provided.
  2. Random variations are allowed, provided that the configuration does not obstruct water penetration.
Where required by the fire code official, flue spaces required by Table 3208.3, in single-, double- or multiple-row rack storage installations shall be equipped with approved devices to protect the required flue spaces. Such devices shall not be removed or modified.
Steel building columns shall be protected in accordance with NFPA 13.
Buildings with extra-high-rack combustible storage shall be protected with a specially engineered automatic sprinkler system. Extra-high-rack combustible storage shall be provided with additional special fire protection, such as separation from other buildings and additional built-in fire protection features and fire department access, when required by the fire code official.
Automated storage shall be in accordance with this section.
Where automatic sprinklers are required by Table 3206.2, the building shall be equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
High-piled storage areas having greater than 500 square feet (46 m2) of carousel storage shall be provided with automatic shutdown in accordance with one of the following:
  1. An automatic smoke detection system installed in accordance with Section 907, with coverage extending 15 feet (4575 mm) in all directions beyond unenclosed carousel storage systems and which sounds a local alarm at the operator's station and stops the carousel storage system upon the activation of a single detector.
  2. An automatic smoke detection system installed in accordance with Section 907 and within enclosed carousel storage systems, which sounds a local alarm at the operator's station and stops the carousel storage system upon the activation of a single detector.
  3. A single dead-man-type control switch that allows the operation of the carousel storage system only when the operator is present. The switch shall be in the same room as the carousel storage system and located to provide for observation of the carousel system.
High-piled storage areas with automated rack storage shall be provided with a manually activated emergency shutdown switch for use by emergency personnel. The switch shall be clearly identified and shall be in a location approved by the fire chief.
Records storage facilities used for the rack or shelf storage of combustible paper records greater than 12 feet (3658 mm) in height shall be in accordance with Sections 3206 and 3208 and NFPA 13. Palletized storage of records shall be in accordance with Section 3207.
Analyzing code differences
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING