ADOPTS WITH AMENDMENTS:

International Building Code 2018 (IBC 2018)

Heads up: There are no amended sections in this chapter.

The provisions of this chapter shall control the design and construction of facilities for accessibility for individuals with disabilities.

1102.1 Design

AMENDMENT
This section has been amended at the state or city level.
Buildings and facilities shall be designed and constructed to be accessible in accordance with this code and ICC A117.1, as detailed in this chapter.

1102.1.1 Alternate Methods

AMENDMENT
This section has been amended at the state or city level.
The application of Section 104.11 to this chapter shall be limited to the extent that alternate methods of construction, designs or technologies shall provide substantially equivalent or greater accessibility. Where approved by the building official, the provisions of the Fair Housing Act Amendments of 1988 may be considered as an alternate method to the criteria outlined in ICC A117.1 as it relates to covered multifamily dwellings.

ORS 447.220 is not a part of this code but is reprinted here for the reader's convenience:

447.220 Purpose. It is the purpose of ORS 447.210 to 447.280 to make affected buildings, including but not limited to commercial facilities, public accommodations, private entities, private membership clubs and churches, in the state accessible to and usable by persons with disabilities, as provided in the Americans with Disabilities Act, and to make covered multifamily dwellings in the state accessible to and usable by all persons with disabilities, as provided in the Fair Housing Act. In requiring that buildings and facilities be usable by persons with disabilities, it is not the intention of the Legislative Assembly to require that items of personal convenience such as rest rooms, telephones and drinking fountains be provided for members of the public who have disabilities if they are not otherwise provided for members of the public who do not have disabilities. However, pursuant to the Americans with Disabilities Act, the Director of the Department of Consumer and Business Services may provide greater protection to individuals with disabilities by adopting more stringent standards than prescribed by the Americans with Disabilities Act. [1971 c.320 §1; 1973 c.539 §2; 1979 c.133 §2; 1989 c.224 §110; 1993 c.503 §2]

1102.1.2 Amendments to ICC A117.1

AMENDMENT
This section has been amended at the state or city level.
The provisions of this section shall be considered amendments to ICC A117.1.

1102.1.2.1 Elevators—ICC A117.1, Section 407

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Section 407 is not adopted. Elevators are expressly regulated through the Elevator Code.

1102.1.2.2 Limited-Use/Limited-Application Elevators (LULA)—ICC A117.1, Section 408

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Section 408 is not adopted. LULAs are expressly regulated through the Elevator Code.

1102.1.2.3 Private Residence Elevators—ICC A117.1, Section 409

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Section 409 is not adopted. Private residence elevators are expressly regulated through the Elevator Code.

1102.1.2.4 Platform Lifts—ICC A117.1, Section 410

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Section 410 is not adopted. Platform lifts are expressly regulated through the Elevator Code.

1102.1.2.5 Door Opening Force—ICC A117.1, Section 404.2.8

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Section 404.2.8 is deleted in its entirety and replaced with the following: The opening force of doors along an accessible route shall be as follows:
  1. Exterior doors: 81/2 pounds-force (lbf) (37.8 N).
  2. Interior doors: 5 pounds-force (lbf) (22.2 N).
  3. Stairway doors at pressurized stair enclosures: 15 pounds (6.8 kg) at exterior doors.
  4. Where environmental conditions require greater closing pressure, power-operated doors shall be used within the accessible route.
  5. Fire doors shall have the minimum force necessary to close and latch the door.

1102.1.2.6 Detectable Warnings at Raised Marked Crossings—ICC A117.1, Section 406.12

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Section 406.12 is deleted in its entirety.

1102.1.2.7 Vehicle Space Width—ICC A117.1, Section 502.2

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Section 502.2 is deleted in its entirety and replaced with the following: Car and van parking spaces shall be designed in compliance with the Standards for Accessible Parking Places set forth by the Oregon Transportation Commission.

1102.1.2.8 Access Aisle Width—ICC A117.1, Section 502.4.2

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Section 502.4.2 is deleted in its entirety and replaced with the following: Access aisles serving parking spaces shall be designed in compliance with the Standards for Accessible Parking Places set forth by the Oregon Transportation Commission.

1102.1.2.9 Recreational Facilities—ICC A117.1, Chapter 11

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1, Chapter 11 is adopted as follows:
  1. Section 1101.2.1 General exceptions. Section 1101.2.1 is adopted in its entirety.
  2. Section 1101.2.2 Area of sport activity. Section 1101.2.2 is adopted but is restricted in application to sites where buildings and facilities meeting the definition of "Affected Buildings" are constructed. See ORS 447.210(1).
  3. Section 1101.2.3 Recreational boating facilities. Section 1101.2.3 is not adopted.
  4. Section 1101.2.4 Exercise machines and equipment. Section 1101.2.4 is not adopted.
  5. Section 1101.3 Protruding objects. Section 1101.3 is adopted in its entirety.
  6. Section 1102 Amusement rides. Section 1102 is not adopted. Amusement rides are regulated exclusively through the Oregon Amusement Ride and Device Specialty Code.
  7. Section 1103 Recreational boating facilities. Section 1103 is not adopted.
  8. Section 1104 Exercise machines and equipment. Section 1104 is not adopted.
  9. Section 1105 Fishing piers and platforms. Section 1105 is not adopted.
  10. Section 1106 Golf facilities. Section 1106 is not adopted.
  11. Section 1107 Miniature golf facilities. Section 1107 is adopted but is restricted in application to sites where buildings and facilities meeting the definition of "Affected Buildings" are constructed. See ORS 447.210(1).
  12. Section 1108 Play areas. Section 1108 is adopted but is restricted in application to children's play structures as governed by Section 424.
  13. Section 1109 Swimming pools, wading pools, hot tubs and spas. Section 1109 is not adopted.
  14. Section 1110 Shooting ranges. Section 1110 is adopted but is restricted in application to sites where buildings and facilities meeting the definition of "Affected Buildings" are constructed. See ORS 447.210(1).
Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to individuals with disabilities.
Sites, buildings, structures, facilities, elements and spaces shall be exempt from this chapter to the extent specified in this section.
Accessibility is not required in buildings and facilities, or portions thereof, to the extent permitted by Sections 1104 through 1111.
Spaces and elements within employee work areas shall only be required to comply with Sections 907.5.2.3.1, 1009 and 1104.3.1 and shall be designed and constructed so that individuals with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, other than raised courtroom stations in accordance with Section 1108.4.1.4, that are less than 300 square feet (30 m2) in area and located 7 inches (178 mm) or more above or below the ground or finished floor where the change in elevation is essential to the function of the space shall be exempt from all requirements.
Detached one- and two- family dwellings, their accessory structures and their associated sites and facilities are not required to comply with this chapter.

Group U occupancies are not required to comply with this chapter other than the following:

  1. In agricultural buildings, access is required to paved work areas and areas open to the general public.
  2. Private garages or carports that contain required accessible parking.
Structures, sites and equipment directly associated with the actual processes of construction including, but not limited to, scaffolding, bridging, materials hoists, materials storage or construction trailers are not required to comply with this chapter.
Raised areas used primarily for purposes of security, life safety or fire safety including, but not limited to, observation galleries, prison guard towers, fire towers or lifeguard stands are not required to comply with this chapter.
Spaces accessed only by ladders, catwalks, crawl spaces, freight elevators or very narrow passageways are not required to comply with this chapter.
Raised or lowered areas, or portions of areas, in places of religious worship that are less than 300 square feet (30 m2) in area and located 7 inches (178 mm) or more above or below the finished floor and used primarily for the performance of religious ceremonies are not required to comply with this chapter.
Spaces frequented only by service personnel for maintenance, repair or occasional monitoring of equipment are not required to comply with this chapter.
Highway tollbooths where the access is provided only by bridges above the vehicular traffic or underground tunnels are not required to comply with this chapter.
Buildings of Group R-1 containing not more than five sleeping units for rent or hire that are also occupied as the residence of the proprietor are not required to comply with this chapter.
Where a day care facility is part of a dwelling unit, only the portion of the structure utilized for the day care facility is required to comply with this chapter.
In detention and correctional facilities, common use areas that are used only by inmates or detainees and security personnel, and that do not serve holding cells or housing cells required to be Accessible units, are not required to comply with this chapter.
Walk-in cooler and freezer equipment accessed only from employee work areas is not required to comply with this chapter.

1103.2.15 Private Membership Clubs and Churches

AMENDMENT
This section has been amended at the state or city level.
In accordance with ORS 447.210(1), private membership clubs and churches that have more than one floor level and more than 4,000 square feet (372 m2) in ground area or more than one floor level and more than 20 feet (6096 mm) in height, measured from the top surface of the lowest flooring to the highest interior overhead finish of the building, are required to be accessible.

At least one accessible route within the site shall be provided from public transportation stops, accessible parking, accessible passenger loading zones, and public streets or sidewalks to the accessible building entrance served.

Exception: Other than in buildings or facilities containing or serving Type B units, an accessible route shall not be required between site arrival points and the building or facility entrance if the only means of access between them is a vehicular way not providing for pedestrian access.

1104.2 Within a Site

ILLUSTRATION

At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.

Exceptions:

  1. An accessible route is not required between accessible buildings, accessible facilities, accessible elements and accessible spaces that have, as the only means of access between them, a vehicular way not providing for pedestrian access.
  2. An accessible route to recreational facilities shall only be required to the extent specified in Section 1110.

Where a building or portion of a building is required to be accessible, at least one accessible route shall be provided to each portion of the building, to accessible building entrances connecting accessible pedestrian walkways and to the public way.

Exceptions:

  1. Stories and mezzanines exempted by Section 1104.4.
  2. In a building, room or space used for assembly purposes with fixed seating, an accessible route shall not be required to serve levels where wheelchair spaces are not provided.
  3. Vertical access to elevated employee work stations within a courtroom complying with Section 1108.4.1.4.
  4. An accessible route to recreational facilities shall only be required to the extent specified in Section 1110.

Common use circulation paths within employee work areas shall be accessible routes.

Exceptions:

  1. Common use circulation paths, located within employee work areas that are less than 1,000 square feet (93 m2) in size and defined by permanently installed partitions, counters, casework or furnishings, shall not be required to be accessible routes.
  2. Common use circulation paths, located within employee work areas, that are an integral component of equipment, shall not be required to be accessible routes.
  3. Common use circulation paths, located within exterior employee work areas that are fully exposed to the weather, shall not be required to be accessible routes.

Press boxes in a building, room or space used for assembly purposes shall be on an accessible route.

Exceptions:

  1. An accessible route shall not be required to press boxes in bleachers that have a single point of entry from the bleachers, provided that the aggregate area of all press boxes for each playing field is not more than 500 square feet (46 m2).
  2. An accessible route shall not be required to free-standing press boxes that are more than 12 feet (3660 mm) above grade provided that the aggregate area of all press boxes for each playing field is not more than 500 square feet (46 m2).

1104.4 Multistory Buildings and Facilities

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION

At least one accessible route shall connect each accessible story, mezzanine and occupied roofs in multilevel buildings and facilities.

Exceptions:

  1. An accessible route is not required to stories, mezzanines and occupied roofs that have an aggregate area of not more than 3,000 square feet (278.7 m2) and are located above and below accessible levels. This exception shall not apply to:

    1. 1.1. Multiple tenant facilities of Group M occupancies containing five or more tenant spaces used for the sales or rental of goods and where at least one such tenant space is located on a floor level above or below the accessible levels.
    2. 1.2. Stories or mezzanines containing offices of health care providers (Group B or I).
    3. 1.3. Passenger transportation facilities and airports (Group A-3 or B).
    4. 1.4. Government buildings.
  2. Stories, mezzanines or occupied roofs that do not contain accessible elements or other spaces as determined by Section 1107 or 1108 are not required to be served by an accessible route from an accessible level.
  3. In air traffic control towers, an accessible route is not required to serve the cab and the floor immediately below the cab.
  4. Where a two-story building or facility has one story or mezzanine with an occupant load of five or fewer persons that does not contain public use space, that story or mezzanine shall not be required to be connected by an accessible route to the story above or below.
  5. In private buildings or facilities that are less than three stories and that have less than 3,000 square feet (279 m2) per story, an accessible route shall not be required to connect stories provided that the building or facility is not a shopping center; shopping mall; professional office of a health care provider; or terminal, depot or other station used for specified public transportation or airport passenger terminal.
  6. In a parking garage of fewer than three stories, an accessible route need not be provided to an upper or lower floor level provided that all of the accessible parking spaces are provided on a floor level with an accessible route to an accessible building entrance or to another building.
  7. In a building of fewer than three stories, an accessible route need not be provided in the portion of the building that is one of the following occupancy classifications:
    1. 7.1. Groups F-1 and F-2.
    2. 7.2. Groups H-1, H-2, H-3, H-4 and H-5.
    3. 7.3. Group S-1 and 2.
    4. 7.4. Group U.
  8. In a mixed-occupancy building of fewer than three stories that contains a Group B or M occupancy mixed with a Group F-1 or F-2; Group H-2, H-3, H-4 or H-5; Group S-1 or S-2; or Group U occupancy, an accessible route need not be provided if the Group B or M occupancy is less than 3,000 square feet (279 m2) on any floor level without an accessible route.
  9. In a building or occupancy of fewer than two stories, an elevator need not be provided to a mezzanine that is less than 3,000 square feet (279 m2).
  10. In a building of fewer than three stories, an accessible route need not be provided where ramps, grade-level entries or accessible horizontal connections from adjacent buildings are provided to each floor level, provided all facilities, elements and spaces are connected to an accessible route.

1104.5 Elevators Required

AMENDMENT
This section has been amended at the state or city level.
Elevators shall be provided in all shopping centers; shopping malls; professional offices of health care providers (B or I occupancies); terminals, depots or other stations used for specified public transportation; airport passenger terminals; and government buildings that are covered by Title II of the Americans with Disabilities Act.
Exceptions:
  1. Elevators need not be provided in buildings and spaces listed in ORS 447.247(1)(a), which are exempt from the accessible route provisions identified Section 1104.4, Exception 4.
  2. Elevators need not be provided in buildings and spaces listed in ORS 447.247(1)(b), which are exempt from the accessible route provisions of Section 1104.4.
  3. Elevators are not required where a terminal, depot or other station used for specified public transportation or airport passenger terminals are provided with an accessible route to all portions of the facilities.
ORS 447.247 is not a part of this code but is reprinted here for the reader's convenience:

447.247 Elevators required; criteria; rules.
  1. Elevators are required:
    1. In all shopping centers, shopping malls, professional offices of health care providers and government buildings that are covered by Title II of the Americans with Disabilities Act.
    2. In all other commercial facilities, private entities and places of public accommodation covered by Title III of the Americans with Disabilities Act that have more than one floor level and more than 3,000 square feet in ground area or that are more than 20 feet in height, measured from the top surface of the lowest flooring to the highest interior overhead finish of the building; and
    3. In all private membership clubs and churches that have more than one floor level and more than 4,000 square feet in ground area or that are more than 20 feet in height, measured from the top surface of the lowest flooring to the highest interior overhead finish of the building.
  2. The Department of Consumer and Business Services may by rule create exceptions to the requirements of this section if this section would require an elevator in a building that would not be required to have an elevator under the provisions of the Americans with Disabilities Act or the Fair Housing Act. [1993 c.503 §6; 1995 c.307 §2]

1104.5 1104.6 Location

AMENDMENT
This section has been amended at the state or city level.

Accessible routes shall coincide with or be located in the same area as a general circulation path. Where the circulation path is interior, the accessible route shall be interior. Where only one accessible route is provided, the accessible route shall not pass through kitchens, storage rooms, restrooms, closets or similar spaces.

Exceptions:

  1. Accessible routes from parking garages contained within and serving Type B units are not required to be interior.
  2. A single accessible route is permitted to pass through a kitchen or storage room in an Accessible unit, Type A unit or Type B unit.

1104.6 1104.7 Security Barriers

AMENDMENT
This section has been amended at the state or city level.

Security barriers including, but not limited to, security bollards and security check points shall not obstruct a required accessible route or accessible means of egress.

Exception: Where security barriers incorporate elements that cannot comply with these requirements, such as certain metal detectors, fluoroscopes or other similar devices, the accessible route shall be permitted to be provided adjacent to security screening devices. The accessible route shall permit persons with disabilities passing around security barriers to maintain visual contact with their personal items to the same extent provided others passing through the security barrier.

In addition to accessible entrances required by Sections 1105.1.1 through 1105.1.7, at least 60 percent of all public entrances shall be accessible.

Exceptions:

  1. An accessible entrance is not required to areas not required to be accessible.
  2. Loading and service entrances that are not the only entrance to a tenant space.
Where provided, direct access for pedestrians from parking structures to buildings or facility entrances shall be accessible.
Where direct access is provided for pedestrians from a pedestrian tunnel or elevated walkway to a building or facility, at least one entrance to the building or facility from each tunnel or walkway shall be accessible.
Where restricted entrances are provided to a building or facility, at least one restricted entrance to the building or facility shall be accessible.
Where entrances used only by inmates or detainees and security personnel are provided at judicial facilities, detention facilities or correctional facilities, at least one such entrance shall be accessible.
If a service entrance is the only entrance to a building or a tenant space in a facility, that entrance shall be accessible.

At least one accessible entrance shall be provided to each tenant in a facility.

Exception: An accessible entrance is not required to self-service storage facilities that are not required to be accessible.

At least one accessible entrance shall be provided to each dwelling unit and sleeping unit in a facility.

Exception: An accessible entrance is not required to dwelling units and sleeping units that are not required to be Accessible units, Type A units or Type B units.

1106.1 Required

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION

Where parking is provided, accessible parking spaces shall be provided in compliance with Table 1106.1, except as required by Sections 1106.2 through 1106.4. Where more than one parking facility is provided on a site, the number of parking spaces required to be accessible shall be calculated separately for each parking facility.

Exception: This section does not apply to parking spaces used exclusively for buses, trucks, other delivery vehicles, law enforcement vehicles or vehicular impound and motor pools where lots accessed by the public are provided with an accessible passenger loading zone.

ORS 447.233(5) through (7) are not a part of this code but are reprinted here for the reader's convenience:

447.233 Accessible parking space requirements; inspection of spaces; violation.
  1. (5) The director is authorized to inspect parking spaces and facilities and buildings subject to the provisions of this section, and to do whatever is necessary to enforce the requirements, including the maintenance requirements, of this section. Municipalities and counties may administer and enforce the requirements of this section in the manner provided under ORS 455.148 or 455.150 for administration and enforcement of specialty codes. All plans for parking spaces subject to the provisions of this section must be approved by the director prior to the creation of the spaces.
  2. (6) Requirements adopted under this section do not apply to longterm parking facilities at the Portland International Airport.
  3. (7) Any reported violation of this section shall be investigated by the administrative authority. The administrative authority shall make a final decision and order correction, if necessary, within 30 days of notification. Any aggrieved person may appeal within 30 days of the decision by the administrative authority to the appropriate municipal appeals board or, at the option of the local jurisdiction, directly to the Building Codes Structures Board established under ORS 455.132. The appeal shall be acted upon within 60 days of filing. The decision of the municipal appeals board may be appealed to the board. The board shall act on the appeal within 60 days of filing. All appeals to the board shall be filed in accordance with ORS 455.690. [1979 c.809 §2; 1981 c.275 §1; 1983 c.338 §930; 1987 c.187 §1; 1989 c.243 §15; 1991 c.741 §6; 1993 c.503 §8; 1993 c.744 §77; 2001 c.573 §5; 2007 c.468 §1]
TABLE 1106.1
ACCESSIBLE PARKING SPACES
TOTAL PARKING
SPACES
PROVIDED
IN PARKING
FACILITIES
REQUIRED
MINIMUM
NUMBER OF
ACCESSIBLE
SPACES
NUMBER OF
VAN
ACCESSIBLE
SPACES
"WHEELCHAIR
USER ONLY"
SPACES
1 to 25 1 1
26 to 50 2 1
51 to 75 3 1
76 to 100 4 1
101 to 150 5 1
151 to 200 6 1
201 to 300 7 2
301 to 400 8 2
401 to 500 9 2
501 to 1,000 2% of total 1 in every 6
accessible spaces
or portion thereof
1,001 and over 20, plus one for
each 100,
or fraction
thereof, over
1,000
1 in every 6
accessible spaces
or portion thereof

Accessible parking spaces shall be provided in Group I-1, R-1, R-2, R-3 and R-4 occupancies in accordance with Items 1 through 4 as applicable.

  1. In Group R-2, R-3 and R-4 occupancies that are required to have Accessible, Type A or Type B dwelling units or sleeping units, at least 2 percent, but not less than one, of each type of parking space provided shall be accessible.
  2. In Group I-1 and R-1 occupancies, accessible parking shall be provided in accordance with Table 1106.1.
  3. Where at least one parking space is provided for each dwelling unit or sleeping unit, at least one accessible parking space shall be provided for each Accessible and Type A unit.
  4. Where parking is provided within or beneath a building, accessible parking spaces shall be provided within or beneath the building.
At least 10 percent, but not less than one, of care recipient and visitor parking spaces provided to serve hospital outpatient facilities shall be accessible.
At least 20 percent, but not less than one, of the portion of care recipient and visitor parking spaces serving rehabilitation facilities specializing in treating conditions that affect mobility and outpatient physical therapy facilities shall be accessible.

1106.5 Van Spaces

AMENDMENT
This section has been amended at the state or city level.

For every six or fraction of six accessible parking spaces, at least one shall be a van-accessible parking space. Where five or more parking spaces are designated accessible, any space that is designated as van accessible shall be reserved for wheelchair users.

Exception: In Group U private garages that serve Group R-2 and R-3 occupancies, van-accessible spaces shall be permitted to have vehicular routes, entrances, parking spaces and access aisles with a minimum vertical clearance of 7 feet (2134 mm).

1106.6 Location

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION

Accessible parking spaces shall be located on the shortest practical accessible route of travel from adjacent parking to an accessible building entrance. In parking facilities that do not serve a particular building, accessible parking spaces shall be located on the shortest route to an accessible pedestrian entrance to the parking facility. Where buildings have multiple accessible entrances with adjacent parking, accessible parking spaces shall be dispersed and located near the accessible entrances.

Exceptions:

  1. In multilevel parking structures, van-accessible parking spaces are permitted on one level.
  2. Accessible parking spaces shall be permitted to be located in different parking facilities if substantially equivalent or greater accessibility is provided in terms of distance from an accessible entrance or entrances, parking fee and user convenience.

1106.7 Surfaces and Identification of Parking Spaces

AMENDMENT
This section has been amended at the state or city level.

1106.7.1 General

AMENDMENT
This section has been amended at the state or city level.
Accessible car and van parking spaces shall comply with the surface requirements of ICC ANSI A117.1, Section 502. Accessible parking spaces, dimensions, markings and signs shall be designed in compliance with the Standards for Accessible Parking Places set forth by the Oregon Transportation Commission.

1106.7.2 Identification

AMENDMENT
This section has been amended at the state or city level.
Identification of accessible parking spaces shall be in accordance with the Standards for Accessible Parking Places set forth by the Oregon Transportation Commission.

1106.7 1106.8 Passenger Loading Zones

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Passenger loading zones shall be accessible.

1106.7.1 1106.8.1 Continuous Loading Zones

AMENDMENT
This section has been amended at the state or city level.
Where passenger loading zones are provided, one passenger loading zone in every continuous 100 linear feet (30.4 m) maximum of loading zone space shall be accessible.

1106.7.2 1106.8.2 Medical Facilities

AMENDMENT
This section has been amended at the state or city level.
A passenger loading zone shall be provided at an accessible entrance to licensed medical and long-term care facilities where people receive physical or medical treatment or care and where the period of stay exceeds 24 hours.

1106.8.2.1 Group I-2

AMENDMENT
This section has been amended at the state or city level.
In Group I-2 health care occupancies, at least one accessible entry shall be under shelter. Every such entry shall include a passenger loading zone.

1106.7.3 1106.8.3 Valet Parking

AMENDMENT
This section has been amended at the state or city level.
A passenger loading zone shall be provided at valet parking services.

1106.7.4 1106.8.4 Mechanical Access Parking Garages

AMENDMENT
This section has been amended at the state or city level.
Mechanical access parking garages shall provide at least one passenger loading zone at vehicle drop-off and vehicle pick-up areas.
In addition to the other requirements of this chapter, occupancies having dwelling units or sleeping units shall be provided with accessible features in accordance with this section.
Dwelling units and sleeping units that are required to be Accessible units, Type A units and Type B units shall comply with the applicable portions of Chapter 10 of ICC A117.1. Units required to be Type A units are permitted to be designed and constructed as Accessible units. Units required to be Type B units are permitted to be designed and constructed as Accessible units or as Type A units.

1107.3 Accessible Spaces

AMENDMENT
This section has been amended at the state or city level.

Rooms and spaces available to the general public or available for use by residents and serving Accessible units, Type A units or Type B units shall be accessible. Accessible spaces shall include toilet and bathing rooms, kitchen, living and dining areas and any exterior spaces, including patios, terraces and balconies.

Exceptions:

  1. Stories and mezzanines exempted by Section 1107.4.
  2. Recreational facilities in accordance with Section 1102.2.2.9.
  3. Exterior decks, patios or balconies that are part of Type B units and have impervious surfaces, and that are not more than 4 inches (102 mm) below the finished floor level of the adjacent interior space of the unit.

Not fewer than one accessible route shall connect accessible building or facility entrances with the primary entrance of each Accessible unit, Type A unit and Type B unit within the building or facility and with those exterior and interior spaces and facilities that serve the units.

Exceptions:

  1. If due to circumstances outside the control of the owner, either the slope of the finished ground level between accessible facilities and buildings exceeds one unit vertical in 12 units horizontal (1:12), or where physical barriers or legal restrictions prevent the installation of an accessible route, a vehicular route with parking that complies with Section 1106 at each public or common use facility or building is permitted in place of the accessible route.
  2. In Group I-3 facilities, an accessible route is not required to connect stories or mezzanines where Accessible units, all common use areas serving Accessible units and all public use areas are on an accessible route.
  3. In Group R-2 facilities with Type A units complying with Section 1107.6.2.2.1, an accessible route is not required to connect stories or mezzanines where Type A units, all common use areas serving Type A units and all public use areas are on an accessible route.
  4. In other than Group R-2 dormitory housing provided by places of education, in Group R-2 facilities with Accessible units complying with Section 1107.6.2.3.1, an accessible route is not required to connect stories or mezzanines where Accessible units, all common use areas serving Accessible units and all public use areas are on an accessible route.
  5. In Group R-1, an accessible route is not required to connect stories or mezzanines within individual units, provided the accessible level meets the provisions for Accessible units and sleeping accommodations for two persons minimum and a toilet facility are provided on that level.
  6. In congregate residences in Groups R-3 and R-4, an accessible route is not required to connect stories or mezzanines where Accessible units or Type B units, all common use areas serving Accessible units and Type B units and all public use areas serving Accessible units and Type B units are on an accessible route.
  7. An accessible route between stories is not required where Type B units are exempted by Section 1107.7.

1107.5 Group I

AMENDMENT
This section has been amended at the state or city level.
Accessible units, Type A units and Type B units shall be provided in Group I occupancies in accordance with Sections 1107.5.1 through 1107.5.5.

1107.5.1 Group I-1

AMENDMENT
This section has been amended at the state or city level.
Accessible units, Type A units and Type B units shall be provided in Group I-1 occupancies in accordance with Sections 1107.5.1.1 through 1107.5.1.4.2.

1107.5.1.1 Accessible Units

AMENDMENT
This section has been amended at the state or city level.
In Group I-1, Condition 1, at least 4 percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units. In Group I-1, Condition 2, at least 10 percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units. All Group I-1, Condition 2 assisted living facility and residential care facility dwelling and sleeping units shall be provided with one roll-in-type shower compartment in accordance with Section 1107.5.1.4.

1107.5.1.2 Type A Units

AMENDMENT
This section has been amended at the state or city level.
In Group I-1, Condition 2 assisted living facilities and residential care facilities, every dwelling unit or sleeping unit shall be a Type A unit and shall be provided with grab bars and a roll-in-type shower compartment in accordance with Section 1107.5.1.4.

1107.5.1.2 1107.5.1.3 Type B Units

AMENDMENT
This section has been amended at the state or city level.

In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

1107.5.1.4 Bathing Facilities

AMENDMENT
This section has been amended at the state or city level.
In all Group I-1, Condition 2 assisted living facilities and residential care facilities, the bathing facilities shall be provided with accessible features in accordance with Sections 1107.5.1.4.1 and 1107.5.1.4.2.

1107.5.1.4.1 Bathing Facilities Inside the Dwelling or Sleeping Unit

AMENDMENT
This section has been amended at the state or city level.
In all Group I-1, Condition 2 assisted living facilities and residential care facilities where bathing facilities are provided inside the dwelling or sleeping unit, one standard roll-in-type shower compartment shall be provided in each dwelling or sleeping unit. Grab bars shall be provided for water closets and shower compartments.

Exception: The folding seat is permitted to be omitted for standard roll-in-type shower compartments and the shower controls may be located on the side walls.

1107.5.1.4.2 Bathing Facilities Outside the Dwelling or Sleeping Unit

AMENDMENT
This section has been amended at the state or city level.
In all Group I-1, Condition 2 residential care facilities where bathing facilities are provided outside the dwelling or sleeping unit, one standard roll-in-type shower compartment shall be provided in each bathing facility, except in a bathing room where an accessible tub is provided. Grab bars shall be provided for water closets and shower compartments.

Exception: The folding seat is permitted to be omitted for standard roll-in-type shower compartments and the shower controls may be located on the side walls.
Accessible units and Type B units shall be provided in nursing homes of Group I-2 occupancies in accordance with Sections 1107.5.2.1 and 1107.5.2.2.
At least 50 percent but not less than one of each type of the dwelling units and sleeping units shall be Accessible units.

In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

1107.5.2.3 Bathing Facilities

AMENDMENT
This section has been amended at the state or city level.
In Group I-2, Condition 1 nursing homes, the folding seat is permitted to be omitted for standard roll-in-type shower compartments and the shower controls may be located on the side walls.
Accessible units and Type B units shall be provided in general-purpose hospitals, psychiatric facilities and detoxification facilities of Group I-2 occupancies in accordance with Sections 1107.5.3.1 and 1107.5.3.2.

At least 10 percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units.

Exception: Entry doors to Accessible dwelling units or sleeping units shall not be required to provide the maneuvering clearance beyond the latch side of the door.

In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

In hospitals and rehabilitation facilities of Group I-2 occupancies that specialize in treating conditions that affect mobility, or units within either that specialize in treating conditions that affect mobility, 100 percent of the dwelling units and sleeping units shall be Accessible units.
Accessible units shall be provided in Group I-3 occupancies in accordance with Sections 1107.5.5.1 through 1107.5.5.3.
In Group I-3 occupancies, at least 3 percent of the total number of sleeping units in the facility, but not less than one unit in each classification level, shall be Accessible units.

In addition to the Accessible units required by Section 1107.5.5.1, where special holding cells or special housing cells or rooms are provided, at least one serving each purpose shall be an Accessible unit. Cells or rooms subject to this requirement include, but are not limited to, those used for purposes of orientation, protective custody, administrative or disciplinary detention or segregation, detoxification and medical isolation.

Exception: Cells or rooms specially designed without protrusions and that are used solely for purposes of suicide prevention shall not be required to include grab bars.

Patient sleeping units or cells required to be Accessible units in medical care facilities shall be provided in addition to any medical isolation cells required to comply with Section 1107.5.5.2.
Accessible units, Type A units and Type B units shall be provided in Group R occupancies in accordance with Sections 1107.6.1 through 1107.6.4.
Accessible units and Type B units shall be provided in Group R-1 occupancies in accordance with Sections 1107.6.1.1 and 1107.6.1.2.

Accessible dwelling units and sleeping units shall be provided in accordance with Table 1107.6.1.1. On a multiple-building site, where structures contain more than 50 dwelling units or sleeping units, the number of Accessible units shall be determined per structure. On a multiple-building site, where structures contain 50 or fewer dwelling units or sleeping units, all dwelling units and sleeping units on a site shall be considered to determine the total number of Accessible units. Accessible units shall be dispersed among the various classes of units.

TABLE 1107.6.1.1

ACCESSIBLE DWELLING UNITS AND SLEEPING UNITS

TOTAL NUMBER OF
UNITS PROVIDED
MINIMUM REQUIRED NUMBER OF
ACCESSIBLE UNITS WITHOUT
ROLL-IN SHOWERS
MINIMUM REQUIRED NUMBER OF
ACCESSIBLE UNITS WITH
ROLL-IN SHOWERS
TOTAL NUMBER OF
REQUIRED ACCESSIBLE UNITS
1 to 25101
26 to 50202
51 to 75314
76 to 100415
101 to 150527
151 to 200628
201 to 3007310
301 to 4008412
401 to 5009413
501 to 1,0002% of total1% of total3% of total
Over 1,00020, plus 1 for each 100,
or fraction thereof, over 1,000
10 plus 1 for each 100, or
fraction thereof, over 1,000
30 plus 2 for each 100, or
fraction thereof, over 1,000

In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

Accessible units, Type A units and Type B units shall be provided in Group R-2 occupancies in accordance with Sections 1107.6.2.1 through 1107.6.2.3.

In live/work units constructed in accordance with Section 419, the nonresidential portion is required to be accessible. In a structure where there are four or more live/work units intended to be occupied as a residence, the residential portion of the live/work unit shall be a Type B unit.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

Type A units and Type B units shall be provided in apartment houses, monasteries and convents in accordance with Sections 1107.6.2.2.1 and 1107.6.2.2.2. Bedrooms in monasteries and convents shall be counted as units for the purpose of determining the number of units. Where the bedrooms are grouped in sleeping units, only one bedroom in each sleeping unit shall count toward the number of required Type A units.

In Group R-2 occupancies containing more than 20 dwelling units or sleeping units, at least 2 percent but not less than one of the units shall be a Type A unit. All Group R-2 units on a site shall be considered to determine the total number of units and the required number of Type A units. Type A units shall be dispersed among the various classes of units.

Exceptions:

  1. The number of Type A units is permitted to be reduced in accordance with Section 1107.7.
  2. Existing structures on a site shall not contribute to the total number of units on a site.

Where there are four or more dwelling units or sleeping units intended to be occupied as a residence in a single structure, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

In Group R-2 occupancies, other than live/work units, apartment houses, monasteries and convents falling within the scope of Sections 1107.6.2.1 and 1107.6.2.2, Accessible units and Type B units shall be provided in accordance with Sections 1107.6.2.3.1 and 1107.6.2.3.2. Bedrooms within congregate living facilities, dormitories, sororities, fraternities and boarding houses shall be counted as sleeping units for the purpose of determining the number of units. Where the bedrooms are grouped into dwelling or sleeping units, only one bedroom in each dwelling or sleeping unit shall be permitted to count toward the number of required Accessible units.
Accessible dwelling units and sleeping units shall be provided in accordance with Table 1107.6.1.1.

Where there are four or more dwelling units or sleeping units intended to be occupied as a residence in a single structure, every dwelling unit and every sleeping unit intended to be occupied as a residence shall be a Type B unit.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

In Group R-3 occupancies where there are four or more dwelling units or sleeping units intended to be occupied as a residence in a single structure, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit. Bedrooms within congregate living facilities, dormitories, sororities, fraternities, and boarding houses shall be counted as sleeping units for the purpose of determining the number of units.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

1107.6.4 Group R-4

AMENDMENT
This section has been amended at the state or city level.
Accessible units, Type A units and Type B units shall be provided in Group R-4 occupancies in accordance with Sections 1107.6.4.1 through 1107.6.4.4.2. Bedrooms in Group R-4 facilities shall be counted as sleeping units for the purpose of determining the number of units.

1107.6.4.1 Accessible Units

AMENDMENT
This section has been amended at the state or city level.
In Group R-4, Condition 1, at least one of the sleeping units shall be an Accessible unit. In Group R-4, Condition 2, at least 10 percent, but not less than one of the sleeping units shall be an Accessible unit. All Group R-4, Condition 2 assisted living facility and residential care dwelling and sleeping units shall be provided with a roll-in-type shower compartment in accordance with Section 1107.6.4.4.

1107.6.4.2 Type A Units

AMENDMENT
This section has been amended at the state or city level.
In Group R-4, Condition 2 assisted living facilities and residential care facilities, every dwelling unit or sleeping unit shall be a Type A unit and shall be provided with grab bars and a roll-in-type shower compartment in accordance with Sections 1107.6.4.4.1 and 1107.6.4.4.2.

1107.6.4.2 1107.6.4.3 Type B Units

AMENDMENT
This section has been amended at the state or city level.

In structures with four or more sleeping units intended to be occupied as a residence, every sleeping unit intended to be occupied as a residence shall be a Type B unit.

Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

1107.6.4.4 Bathing Facilities

AMENDMENT
This section has been amended at the state or city level.
In all Group R-4, Condition 2 assisted living facilities and residential care facilities, accessible features shall be provided in accordance with Sections 1107.6.4.4.1 and 1107.6.4.4.2.

1107.6.4.4.1 Bathing Facilities Inside Dwelling or Sleeping Units

AMENDMENT
This section has been amended at the state or city level.
In all Group R-4, Condition 2 assisted living facilities and residential care facilities where bathing facilities are provided inside the dwelling or sleeping unit, one standard roll-in-type shower compartment shall be provided in each dwelling or sleeping unit. Grab bars shall be provided for water closets and shower compartments.

Exception: The folding seat is permitted to be omitted for standard roll-in-type shower compartments and the shower controls may be located on the side walls.

1107.6.4.4.2 Bathing Facilities Outside Dwelling or Sleeping Units

AMENDMENT
This section has been amended at the state or city level.
In all Group R-4, Condition 2 residential care facilities where bathing facilities are provided outside the dwelling or sleeping unit, one standard roll-in-type shower compartment shall be provided in each bathing facility, except in a bathing room where an accessible tub is provided. Grab bars shall be provided for water closets and shower compartments.

Exception: The folding seat is permitted to be omitted for standard roll-in-type shower compartments and the shower controls may be located on the side walls.
Where specifically permitted by Section 1107.5 or 1107.6, the required number of Type A units and Type B units is permitted to be reduced in accordance with Sections 1107.7.1 through 1107.7.5.
Where elevator service is not provided in a structure, only the dwelling units and sleeping units that are located on stories indicated in Sections 1107.7.1.1 and 1107.7.1.2 are required to be Type A units and Type B units, respectively. The number of Type A units shall be determined in accordance with Section 1107.6.2.2.1.
At least one story containing dwelling units or sleeping units intended to be occupied as a residence shall be provided with an accessible entrance from the exterior of the structure and all units intended to be occupied as a residence on that story shall be Type B units.

Where stories have entrances not included in determining compliance with Section 1107.7.1.1, and such entrances are proximate to arrival points intended to serve units on that story, as indicated in Items 1 and 2, all dwelling units and sleeping units intended to be occupied as a residence served by that entrance on that story shall be Type B units.

  1. Where the slopes of the undisturbed site measured between the planned entrance and all vehicular or pedestrian arrival points within 50 feet (15 240 mm) of the planned entrance are 10 percent or less.
  2. Where the slopes of the planned finished grade measured between the entrance and all vehicular or pedestrian arrival points within 50 feet (15 240 mm) of the planned entrance are 10 percent or less.

Where arrival points are not within 50 feet (15 240 mm) of the entrance, the closest arrival point shall be used to determine access unless that arrival point serves the story required by Section 1107.7.1.1.

A multistory dwelling unit or sleeping unit that is not provided with elevator service is not required to be a Type B unit. Where a multistory unit is provided with external elevator service to only one floor, the floor provided with elevator service shall be the primary entry to the unit, shall comply with the requirements for a Type B unit and, where provided within the unit, a living area, a kitchen and a toilet facility shall be provided on that floor.
Where elevator service in the building provides an accessible route only to the lowest story containing dwelling units or sleeping units intended to be occupied as a residence, only the units on that story that are intended to be occupied as a residence are required to be Type B units.

On a site with multiple nonelevator buildings, the number of units required by Section 1107.7.1 to be Type B units is permitted to be reduced to a percentage that is equal to the percentage of the entire site having grades, prior to development, that are less than 10 percent, provided that all of the following conditions are met:

  1. Not less than 20 percent of the units required by Section 1107.7.1 on the site are Type B units.
  2. Units required by Section 1107.7.1, where the slope between the building entrance serving the units on that story and a pedestrian or vehicular arrival point is not greater than 8.33 percent, are Type B units.
  3. Units required by Section 1107.7.1, where an elevated walkway is planned between a building entrance serving the units on that story and a pedestrian or vehicular arrival point and the slope between them is 10 percent or less, are Type B units.
  4. Units served by an elevator in accordance with Section 1107.7.3 are Type B units.

The required number of Type A units and Type B units shall not apply to a site where the required elevation of the lowest floor or the lowest horizontal structural building members of nonelevator buildings are at or above the design flood elevation resulting in all of the following:

  1. A difference in elevation between the minimum required floor elevation at the primary entrances and vehicular and pedestrian arrival points within 50 feet (15 240 mm) exceeding 30 inches (762 mm).
  2. A slope exceeding 10 percent between the minimum required floor elevation at the primary entrances and vehicular and pedestrian arrival points within 50 feet (15 240 mm).

Where such arrival points are not within 50 feet (15 240 mm) of the primary entrances, the closest arrival points shall be used.

In addition to the other requirements of this chapter, the requirements of Sections 1108.2 through 1108.4 shall apply to specific occupancies.

1108.2 Assembly Area Seating

AMENDMENT
This section has been amended at the state or city level.
A building, room or space used for assembly purposes with fixed seating shall comply with Sections 1108.2.1 through 1108.2.5. Lawn seating that is provided accessory to an affected building shall comply with Section 1108.2.6. Assistive listening systems shall comply with Section 1108.2.7. Performance areas viewed from assembly seating areas shall comply with Section 1108.2.8. Dining areas shall comply with Section 1108.2.9.
If a service or facility is provided in an area that is not accessible, the same service or facility shall be provided on an accessible level and shall be accessible.
In rooms and spaces used for assembly purposes with fixed seating, accessible wheelchair spaces shall be provided in accordance with Sections 1108.2.2.1 through 1108.2.2.3.

Wheelchair spaces shall be provided in accordance with Table 1108.2.2.1.

TABLE 1108.2.2.1

ACCESSIBLE WHEELCHAIR SPACES

CAPACITY OF
SEATING IN
ASSEMBLY AREAS
MINIMUM REQUIRED NUMBER OF
WHEELCHAIR SPACES
4 to 251
26 to 502
51 to 1004
101 to 3005
301 to 5006
501 to 5,0006, plus 1 for each 150, or fraction thereof,
between 501 through 5,000
5,001 and over36 plus 1 for each 200, or fraction thereof,
over 5,000
In each luxury box, club box and suite within arenas, stadiums and grandstands, wheelchair spaces shall be provided in accordance with Table 1108.2.2.1.
In boxes other than those required to comply with Section 1108.2.2.2, the total number of wheelchair spaces provided shall be determined in accordance with Table 1108.2.2.1. Wheelchair spaces shall be located in not less than 20 percent of all boxes provided.
At least one companion seat shall be provided for each wheelchair space required by Sections 1108.2.2.1 through 1108.2.2.3.

In multilevel assembly seating areas, wheelchair spaces shall be provided on the main floor level and on one of each two additional floor or mezzanine levels. Wheelchair spaces shall be provided in each luxury box, club box and suite within assembly facilities.

Exceptions:

  1. In multilevel assembly seating areas utilized for worship services where the second floor or mezzanine level contains 25 percent or less of the total seating capacity, wheelchair spaces shall be permitted to all be located on the main level.
  2. In multilevel assembly seating areas where the second floor or mezzanine level provides 25 percent or less of the total seating capacity and 300 or fewer seats, all wheelchair spaces shall be permitted to be located on the main level.
  3. Wheelchair spaces in team or player seating serving areas of sport activity are not required to be dispersed.

At least 5 percent, but not less than one, of the total number of aisle seats provided shall be designated aisle seats and shall be the aisle seats located closest to accessible routes.

Exception: Designated aisle seats are not required in team or player seating serving areas of sport activity.

Lawn seating areas and exterior overflow seating areas, where fixed seats are not provided, shall connect to an accessible route.

Each building, room or space used for assembly purposes where audible communications are integral to the use of the space shall have an assistive listening system.

Exception: Other than in courtrooms, an assistive listening system is not required where there is no audio amplification system.

The number and type of receivers shall be provided for assistive listening systems in accordance with Table 1108.2.7.1.

Exceptions:

  1. Where a building contains more than one room or space used for assembly purposes, the total number of required receivers shall be permitted to be calculated based on the total number of seats in the building, provided that all receivers are usable with all systems and if the rooms or spaces used for assembly purposes required to provide assistive listening are under one management.
  2. Where all seats in a building, room or space used for assembly purposes are served by an induction loop assistive listening system, the minimum number of receivers required by Table 1108.2.7.1 to be hearing-aid compatible shall not be required.

TABLE 1108.2.7.1

RECEIVERS FOR ASSISTIVE LISTENING SYSTEMS

CAPACITY OF SEATING
IN ASSEMBLY AREAS
MINIMUM REQUIRED
NUMBER OF RECEIVERS
MINIMUM NUMBER OF RECEIVERS
TO BE HEARING-AID COMPATIBLE
50 or less22
51 to 2002, plus 1 per 25 seats over 50 seats*2
201 to 5002, plus 1 per 25 seats over 50 seats*1 per 4 receivers*
501 to 1,00020, plus 1 per 33 seats over 500 seats*1 per 4 receivers*
1,001 to 2,00035, plus 1 per 50 seats over 1,000 seats*1 per 4 receivers*
Over 2,00055, plus 1 per 100 seats over 2,000 seats*1 per 4 receivers*

Note: * = or fraction thereof

Where ticket windows are provided in stadiums and arenas, at least one window at each location shall have an assistive listening system.
Where stadiums, arenas and grandstands have 15,000 fixed seats or more and provide audible public announcements, they shall also provide prerecorded or real-time captions of those audible public announcements.
An accessible route shall directly connect the performance area to the assembly seating area where a circulation path directly connects a performance area to an assembly seating area. An accessible route shall be provided from performance areas to ancillary areas or facilities used by performers.

1108.2.9 Dining and Drinking Areas

AMENDMENT
This section has been amended at the state or city level.

In dining and drinking areas, all interior and exterior floor areas shall be accessible and be on an accessible route.

Exceptions:

  1. An accessible route between accessible levels and stories above or below is not required where permitted by Section 1104.4, Exception 1.
  2. In sports facilities, tiered dining areas providing seating required to be accessible shall be required to have accessible routes serving at least 25 percent of the dining area, provided that accessible routes serve accessible seating and where each tier is provided with the same services.
  3. Employee-only work areas shall comply with Sections 1103.2.2 and 1104.3.1.

1108.2.9.1 Dining Surfaces

AMENDMENT
This section has been amended at the state or city level.
Where dining surfaces for the consumption of food or drink are provided, at least 5 percent, but not less than one, of the dining surfaces for the seating and standing spaces shall be accessible and be distributed throughout the facility and located on a level accessed by an accessible route.

     Where a bar or counter exceeding 34 inches (864 mm) in height is provided for consumption of food or drink, a structurally integrated portion of the main bar or counter shall be provided, measuring a minimum 60 inches (1524 mm) long or 5 percent of the length, whichever is greater, and 28 to 34 inches (711 to 864 mm) high. Clear floor space for forward approach and knee and toe clearance shall be provided.

     Flip-up counters, adjacent tables and similar devices shall not be permitted to satisfy this requirement.

Self-service storage facilities shall provide accessible individual self-storage spaces in accordance with Table 1108.3.

TABLE 1108.3

ACCESSIBLE SELF-SERVICE STORAGE FACILITIES

TOTAL SPACES
IN FACILITY
MINIMUM NUMBER OF REQUIRED
ACCESSIBLE SPACES
1 to 2005%, but not less than 1
Over 20010, plus 2% of total number of units over 200
Accessible individual self-service storage spaces shall be dispersed throughout the various classes of spaces provided. Where more classes of spaces are provided than the number of required accessible spaces, the number of accessible spaces shall not be required to exceed that required by Table 1108.3. Accessible spaces are permitted to be dispersed in a single building of a multiple-building facility.
Judicial facilities shall comply with Sections 1108.4.1 and 1108.4.2.
Each courtroom shall be accessible and comply with Sections 1108.4.1.1 through 1108.4.1.5.

A wheelchair space shall be provided within the jury box.

Exception: Adjacent companion seating is not required.

Wheelchair spaces shall be provided in accordance with Table 1108.2.2.1. Designated aisle seats shall be provided in accordance with Section 1108.2.5.
An assistive listening system must be provided. Receivers shall be provided for the assistive listening system in accordance with Section 1108.2.7.1.
The judge's bench, clerk's station, bailiff's station, deputy clerk's station and court reporter's station shall be located on an accessible route. The vertical access to elevated employee work stations within a courtroom is not required at the time of initial construction, provided a ramp, lift or elevator can be installed without requiring reconfiguration or extension of the courtroom or extension of the electrical system.
The litigant's and counsel stations, including the lectern, shall be accessible.
Central holding cells and court-floor holding cells shall comply with Sections 1108.4.2.1 and 1108.4.2.2.
Where separate central holding cells are provided for adult males, juvenile males, adult females or juvenile females, one of each type shall be accessible. Where central holding cells are provided and are not separated by age or sex, at least one accessible cell shall be provided.
Where separate court-floor holding cells are provided for adult males, juvenile males, adult females or juvenile females, each courtroom shall be served by one accessible cell of each type. Where court-floor holding cells are provided and are not separated by age or sex, courtrooms shall be served by at least one accessible cell. Accessible cells shall be permitted to serve more than one courtroom.

1109.1 General

AMENDMENT
This section has been amended at the state or city level.

Accessible building features and facilities shall be provided in accordance with Sections 1109.2 through 1109.13.

Exception: Accessible units, Type A units and Type B units shall comply with Chapter 10 of ICC A117.1.

Each toilet room and bathing room shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing rooms provided within the facility shall not be located on the inaccessible floor. Except as provided for in Sections 1109.2.2 and 1109.2.3, at least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing room shall be accessible.

Exceptions:

  1. Toilet rooms or bathing rooms accessed only through a private office, not for common or public use and intended for use by a single occupant, shall be permitted to comply with the specific exceptions in ICC A117.1.
  2. This section is not applicable to toilet and bathing rooms that serve dwelling units or sleeping units that are not required to be accessible by Section 1107.
  3. Where multiple single-user toilet rooms or bathing rooms are clustered at a single location, at least 50 percent but not less than one room for each use at each cluster shall be accessible.
  4. Where no more than one urinal is provided in a toilet room or bathing room, the urinal is not required to be accessible.
  5. Toilet rooms or bathing rooms that are part of critical care or intensive care patient sleeping rooms serving Accessible units are not required to be accessible.
  6. Toilet rooms or bathing rooms designed for bariatrics patients are not required to comply with the toilet room and bathing room requirement in ICC A117.1. The sleeping units served by bariatrics toilet or bathing rooms shall not count toward the required number of Accessible sleeping units.
  7. Where toilet facilities are primarily for children's use, required accessible water closets, toilet compartments and lavatories shall be permitted to comply with children's provision of ICC A117.1.

In assembly and mercantile occupancies, an accessible family or assisted-use toilet room shall be provided where an aggregate of six or more male and female water closets is required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the family or assisted-use toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible family or assisted-use bathing room shall be provided. Fixtures located within family or assisted-use toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy.

Exception: Where each separate-sex bathing room has only one shower or bathtub fixture, a family or assisted-use bathing room is not required.

Family or assisted-use toilet and bathing rooms shall comply with Sections 1109.2.1.2 through 1109.2.1.7.

Family or assisted-use toilet rooms shall include only one water closet and only one lavatory. A family or assisted-use bathing room in accordance with Section 1109.2.1.3 shall be considered to be a family or assisted-use toilet room.

Exception: The following additional fixtures shall be permitted in a family or assisted-use toilet room:

  1. A urinal.
  2. A child-height water closet.
  3. A child-height lavatory.
Family or assisted-use bathing rooms shall include only one shower or bathtub fixture. Family or assisted-use bathing rooms shall also include one water closet and one lavatory. Where storage facilities are provided for separate-sex bathing rooms, accessible storage facilities shall be provided for family or assisted-use bathing rooms.
Family or assisted-use toilet and bathing rooms shall be located on an accessible route. Family or assisted-use toilet rooms shall be located not more than one story above or below separate-sex toilet rooms. The accessible route from any separate-sex toilet room to a family or assisted-use toilet room shall not exceed 500 feet (152 m).
In passenger transportation facilities and airports, the accessible route from separate-sex toilet rooms to a family or assisted-use toilet room shall not pass through security checkpoints.
Where doors swing into a family or assisted-use toilet or bathing room, a clear floor space not less than 30 inches by 48 inches (762 mm by 1219 mm) shall be provided, within the room, beyond the area of the door swing.
Doors to family or assisted-use toilet and bathing rooms shall be securable from within the room.
Where water closet compartments are provided in a toilet room or bathing room, at least 5 percent of the total number of compartments shall be wheelchair accessible. Where the combined total water closet compartments and urinals provided in a toilet room or bathing room is six or more, at least 5 percent of the total number of compartments shall be ambulatory accessible, provided in addition to the wheelchair-accessible compartment.
Where lavatories are provided, at least 5 percent, but not less than one, shall be accessible. Where an accessible lavatory is located within the accessible water closet compartment at least one additional accessible lavatory shall be provided in the multicompartment toilet room outside the water closet compartment. Where the total lavatories provided in a toilet room or bathing facility is six or more, at least one lavatory with enhanced reach ranges shall be provided.

Where sinks are provided, at least 5 percent but not less than one provided in accessible spaces shall be accessible.

Exception: Mop or service sinks are not required to be accessible.

Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible.
Where drinking fountains are provided on an exterior site, on a floor or within a secured area, the drinking fountains shall be provided in accordance with Sections 1109.5.1 and 1109.5.2.

Not fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.

Exceptions:

  1. A single drinking fountain with two separate spouts that complies with the requirements for people who use a wheelchair and standing persons shall be permitted to be substituted for two separate drinking fountains.
  2. Where drinking fountains are primarily for children's use, drinking fountains for people using wheelchairs shall be permitted to comply with the children's provisions in ICC A117.1 and drinking fountains for standing children shall be permitted to provide the spout at 30 inches (762 mm) minimum above the floor.

Where more than the minimum number of drinking fountains specified in Section 1109.5.1 is provided, 50 percent of the total number of drinking fountains provided shall comply with the requirements for persons who use a wheelchair and 50 percent of the total number of drinking fountains provided shall comply with the requirements for standing persons.

Exceptions:

  1. Where 50 percent of the drinking fountains yields a fraction, 50 percent shall be permitted to be rounded up or down, provided that the total number of drinking fountains complying with this section equals 100 percent of the drinking fountains.
  2. Where drinking fountains are primarily for children's use, drinking fountains for people using wheelchairs shall be permitted to comply with the children's provisions in ICC A117.1 and drinking fountains for standing children shall be permitted to provide the spout at 30 inches (762 mm) minimum above the floor.

Where provided, saunas and steam rooms shall be accessible.

Exception: Where saunas or steam rooms are clustered at a single location, at least 5 percent of the saunas and steam rooms, but not less than one, of each type in each cluster shall be accessible.

1109.7 Elevators

ILLUSTRATION
Passenger elevators on an accessible route shall be accessible and comply with Chapter 30.

1109.8 Lifts

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION

Platform (wheelchair) lifts are permitted to be a part of a required accessible route in new construction where indicated in Items 1 through 10. Platform (wheelchair) lifts shall be installed in accordance with the Elevator Code.

  1. An accessible route to a performing area and speaker platforms.
  2. An accessible route to wheelchair spaces required to comply with the wheelchair space dispersion requirements of Sections 1108.2.2 through 1108.2.6.
  3. An accessible route to spaces that are not open to the general public with an occupant load of not more than five.
  4. An accessible route within an individual dwelling unit or sleeping unit required to be an Accessible unit, Type A unit or Type B unit.
  5. An accessible route to jury boxes and witness stands; raised courtroom stations including judges' benches, clerks' stations, bailiffs' stations, deputy clerks' stations and court reporters' stations; and to depressed areas such as the well of the court.
  6. An accessible route to load and unload areas serving amusement rides.
  7. An accessible route to play components or soft contained play structures.
  8. An accessible route to team or player seating areas serving areas of sport activity.
  9. An accessible route instead of gangways serving recreational boating facilities and fishing piers and platforms.
  10. An accessible route where existing exterior site constraints make use of a ramp or elevator infeasible.
Where fixed or built-in storage elements such as cabinets, coat hooks, shelves, medicine cabinets, lockers, closets and drawers are provided in required accessible spaces, at least 5 percent, but not less than one of each type shall be accessible.
Accessible facilities and spaces shall be provided with the same storage elements as provided in the similar nonaccessible facilities and spaces.
Self-service shelves and display units shall be located on an accessible route. Such shelving and display units shall not be required to comply with reach-range provisions.

Passenger transit platform edges bordering a drop-off and not protected by platform screens or guards shall have a detectable warning.

Exception: Detectable warnings are not required at bus stops.

Where seating or standing space at fixed or built-in tables, counters or work surfaces is provided in accessible spaces, at least 5 percent of the seating and standing spaces, but not less than one, shall be accessible.

Exception: Check-writing surfaces at check-out aisles not required to comply with Section 1109.12.2 are not required to be accessible.

Accessible fixed or built-in seating at tables, counters or work surfaces shall be distributed throughout the space or facility containing such elements and located on a level accessed by an accessible route.
Visiting areas in judicial facilities and Group I-3 shall comply with Sections 1109.11.2.1 and 1109.11.2.2.

At least 5 percent, but not less than one of the cubicles, shall be accessible on both the visitor and detainee sides. Where counters are provided, at least one shall be accessible on both the visitor and detainee sides.

Exception: This requirement shall not apply to the detainee side of cubicles or counters at noncontact visiting areas not serving Accessible unit holding cells.

Where solid partitions or security glazing separate visitors from detainees, at least one of each type of cubicle or counter partition shall be accessible.
Service facilities shall provide for accessible features in accordance with Sections 1109.12.1 through 1109.12.5.
Where dressing rooms, fitting rooms or locker rooms are provided, at least 5 percent, but not less than one, of each type of use in each cluster provided shall be accessible.

Where check-out aisles are provided, accessible check-out aisles shall be provided in accordance with Table 1109.12.2. Where check-out aisles serve different functions, accessible check-out aisles shall be provided in accordance with Table 1109.12.2 for each function. Where check-out aisles are dispersed throughout the building or facility, accessible check-out aisles shall also be dispersed. Traffic control devices, security devices and turnstiles located in accessible check-out aisles or lanes shall be accessible.

Exception: Where the public use area is under 5,000 square feet (465 m2) not more than one accessible check-out aisle shall be required.

TABLE 1109.12.2

ACCESSIBLE CHECK-OUT AISLES

TOTAL CHECK-OUT
AISLES OF
EACH FUNCTION
MINIMUM NUMBER OF
ACCESSIBLE CHECK-OUT AISLES
OF EACH FUNCTION
1 to 41
5 to 82
9 to 153
Over 153, plus 20% of additional aisles
Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Food service lines shall be accessible. Where self-service shelves are provided, at least 50 percent, but not less than one, of each type provided shall be accessible.
Queue and waiting lines servicing accessible counters or check-out aisles shall be accessible.

Controls, operating mechanisms and hardware intended for operation by the occupant, including switches that control lighting and ventilation and electrical convenience outlets, in accessible spaces, along accessible routes or as parts of accessible elements shall be accessible.

Exceptions:

  1. Operable parts that are intended for use only by service or maintenance personnel shall not be required to be accessible.
  2. Electrical or communication receptacles serving a dedicated use shall not be required to be accessible.
  3. Where two or more outlets are provided in a kitchen above a length of counter top that is uninterrupted by a sink or appliance, one outlet shall not be required to be accessible.
  4. Floor electrical receptacles shall not be required to be accessible.
  5. HVAC diffusers shall not be required to be accessible.
  6. Except for light switches, where redundant controls are provided for a single element, one control in each space shall not be required to be accessible.
  7. Access doors or gates in barrier walls and fences protecting pools, spas and hot tubs shall be permitted to comply with Section 1010.1.9.2.

1109.14 Fuel-Dispensing Systems

AMENDMENT
This section has been amended at the state or city level.

1109.15 Gaming Machines and Gaming Tables

AMENDMENT
This section has been amended at the state or city level.

1110.1 General

AMENDMENT
This section has been amended at the state or city level.
Recreational facilities shall be provided with accessible features in accordance with Section 1102.2.2.9.

1110.2 Facilities Serving Group R-2, R-3 and R-4 Occupancies

AMENDMENT
This section has been amended at the state or city level.

1110.2.1 Facilities Serving Accessible Units

AMENDMENT
This section has been amended at the state or city level.

1110.2.2 Facilities Serving Type A and Type B Units in a Single Building

AMENDMENT
This section has been amended at the state or city level.

1110.2.3 Facilities Serving Type A and Type B Units in Multiple Buildings

AMENDMENT
This section has been amended at the state or city level.

1110.3 Other Occupancies

AMENDMENT
This section has been amended at the state or city level.

1110.4 Recreational Facilities

AMENDMENT
This section has been amended at the state or city level.

1110.4.1 Area of Sport Activity

AMENDMENT
This section has been amended at the state or city level.

1110.4.2 Team or Player Seating

AMENDMENT
This section has been amended at the state or city level.

1110.4.3 Bowling Lanes

AMENDMENT
This section has been amended at the state or city level.

1110.4.4 Court Sports

AMENDMENT
This section has been amended at the state or city level.

1110.4.5 Raised Boxing or Wrestling Rings

AMENDMENT
This section has been amended at the state or city level.

1110.4.6 Raised Refereeing, Judging and Scoring Areas

AMENDMENT
This section has been amended at the state or city level.

1110.4.7 Animal Containment Areas

AMENDMENT
This section has been amended at the state or city level.

1110.4.8 Amusement Rides

AMENDMENT
This section has been amended at the state or city level.

1110.4.8.1 Load and Unload Areas

AMENDMENT
This section has been amended at the state or city level.

1110.4.8.2 Wheelchair Spaces, Ride Seats Designed for Transfer and Transfer Devices

AMENDMENT
This section has been amended at the state or city level.

1110.4.8.3 Minimum Number

AMENDMENT
This section has been amended at the state or city level.

1110.4.9 Recreational Boating Facilities

AMENDMENT
This section has been amended at the state or city level.

1110.4.9.1 Boat Slips

AMENDMENT
This section has been amended at the state or city level.

1110.4.9.2 Dispersion

AMENDMENT
This section has been amended at the state or city level.

1110.4.9.3 Boarding Piers at Boat Launch Ramps

AMENDMENT
This section has been amended at the state or city level.

1110.4.10 Exercise Machines and Equipment

AMENDMENT
This section has been amended at the state or city level.

1110.4.11 Fishing Piers and Platforms

AMENDMENT
This section has been amended at the state or city level.

1110.4.12 Miniature Golf Facilities

AMENDMENT
This section has been amended at the state or city level.

1110.4.12.1 Minimum Number

AMENDMENT
This section has been amended at the state or city level.

1110.4.12.2 Miniature Golf Course Configuration

AMENDMENT
This section has been amended at the state or city level.

1110.4.12.3 Accessible Route

AMENDMENT
This section has been amended at the state or city level.

1110.4.13 Play Areas

AMENDMENT
This section has been amended at the state or city level.

1110.4.14 Swimming Pools, Wading Pools, Hot Tubs and Spas

AMENDMENT
This section has been amended at the state or city level.

1110.4.14.1 Raised Diving Boards and Diving Platforms

AMENDMENT
This section has been amended at the state or city level.

1110.4.14.2 Water Slides

AMENDMENT
This section has been amended at the state or city level.

1110.4.15 Shooting Facilities With Firing Positions

AMENDMENT
This section has been amended at the state or city level.

Section 1111 Signage

ILLUSTRATION

1111.1 Signs

AMENDMENT
This section has been amended at the state or city level.

Required accessible elements shall be identified by the International Symbol of Accessibility at the following locations:

  1. Accessible parking spaces required by Section 1106.1.

  2. Accessible parking spaces required by Section 1106.2.

    Exception: In Group I-1, R-2, R-3 and R-4 facilities, where parking spaces are assigned to specific dwelling units or sleeping units, identification of accessible parking spaces is not required.

  3. Accessible passenger loading zones.
  4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a single location.
  5. Accessible entrances where not all entrances are accessible.
  6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification.
  7. Family or assisted-use toilet and bathing rooms.
  8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
  9. Accessible areas of refuge in accordance with Section 1009.9.
  10. Exterior areas for assisted rescue in accordance with Section 1009.9.
  11. In recreational facilities, lockers that are required to be accessible in accordance with Section 1109.9.

1111.2 Directional Signage

AMENDMENT
This section has been amended at the state or city level.

Directional signage indicating the route to the nearest like accessible element shall be provided at the following locations. These directional signs shall include the International Symbol of Accessibility and sign characters shall meet the visual character requirements in accordance with ICC A117.1.

  1. Inaccessible building entrances.
  2. Inaccessible public toilets and bathing facilities.
  3. Elevators not serving an accessible route.
  4. At each separate-sex toilet and bathing room indicating the location of the nearest family/assisted use toilet or bathing room where provided in accordance with Section 1109.2.1.
  5. At exits and exit stairways serving a required accessible space, but not providing an approved accessible means of egress, signage shall be provided in accordance with Section 1009.10.

1111.3 Other Signs

AMENDMENT
This section has been amended at the state or city level.

Signage indicating special accessibility provisions shall be provided as shown.

  1. Each assembly area required to comply with Section 1108.2.7 shall provide a sign notifying patrons of the availability of assistive listening systems. The sign shall comply with ICC A117.1 requirements for visual characters and include the International Symbol of Access for Hearing Loss.

    Exception: Where ticket offices or windows are provided, signs are not required at each assembly area provided that signs are displayed at each ticket office or window informing patrons of the availability of assistive listening systems.

  2. At each door to an area of refuge providing direct access to a stairway, exterior area for assisted rescue, exit stairway, exit passageway or exit discharge, signage shall be provided in accordance with Section 1013.4.
  3. At areas of refuge, signage shall be provided in accordance with Section 1009.11.
  4. At exterior areas for assisted rescue, signage shall be provided in accordance with Section 1009.11.
  5. At two-way communication systems, signage shall be provided in accordance with Section 1009.8.2.
  6. In interior exit stairways and ramps, floor level signage shall be provided in accordance with Section 1023.9.
Where provided in the locations in Sections 1111.4.1 and 1111.4.2, variable message signs shall comply with the variable message sign requirements of ICC A117.1.
Where provided in transportation facilities, variable message signs conveying transportation-related information shall comply with Section 1111.4.

Where provided in buildings that are designated as emergency shelters, variable message signs conveying emergency-related information shall comply with Section 1111.4.

Exception: Where equivalent information is provided in an audible manner, variable message signs are not required to comply with ICC A117.1.

Section 1112 Clustered Mailboxes

AMENDMENT
This section has been amended at the state or city level.

1112.1 Accessible Routes

AMENDMENT
This section has been amended at the state or city level.
Clustered mailboxes on a site with an affected building shall be located on an accessible route in accordance with Sections 402 and 403 of ICC A117.1.

1112.2 Within a Site

AMENDMENT
This section has been amended at the state or city level.
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.

1112.3 Site Arrival Points

AMENDMENT
This section has been amended at the state or city level.
Accessible routes within the site shall be provided from public transportation stops, accessible parking, accessible passenger loading zones, and public streets or sidewalks to the accessible facilities served.

1112.3.1 Location

AMENDMENT
This section has been amended at the state or city level.
Location of clustered mailboxes shall be coordinated with the postal authority having jurisdiction.

1112.3.2 Access to Pedestrian Circulation

AMENDMENT
This section has been amended at the state or city level.
Where an improved walking surface such as a sidewalk is located within 50 feet (15 240 mm) of the pad on which a clustered mailbox unit is located, at least one accessible route shall connect the improved walking surface to the clustered mailbox pad. At least one pedestrian access route shall be provided within 50 feet (15 240 mm) from the vehicular way to the pad on which a clustered mailbox unit is located.

1112.4 Ramps, Curb Ramps and Barriers

AMENDMENT
This section has been amended at the state or city level.
Ramps along an accessible route to clustered mailboxes shall comply with Sections 405 and 406 of ICC A117.1.

1112.4.1 Curb Ramps

AMENDMENT
This section has been amended at the state or city level.
Where the accessible route to clustered mailboxes is obstructed by curbs, curb ramps shall be provided within 50 feet (15 240 mm) of the clustered mailbox location.

1112.4.2 Other Barriers

AMENDMENT
This section has been amended at the state or city level.
Where barriers such as grass medians, landscaping or loose gravel between the edge of the traveled surface and clustered mailbox pads occur, a solid-surfaced access shall be provided within 50 feet (15 240 mm) of the clustered mailbox location.

1112.4.3 Landings

AMENDMENT
This section has been amended at the state or city level.
All landings along an accessible route to clustered mailboxes shall comply with Section 405.7 of ICC A117.1.

1112.4.4 Edge Protection

AMENDMENT
This section has been amended at the state or city level.
Edge protection along an accessible route to clustered mailboxes shall comply with ICC A117.1, Section 405.9.

1112.5 Changes in Level

AMENDMENT
This section has been amended at the state or city level.
Changes in level in the traveled surface on an accessible route to clustered mailboxes shall comply with Section 303 of ICC A117.1.

1112.6 Surfaces

AMENDMENT
This section has been amended at the state or city level.
Traveled surfaces shall be stable, firm and slip resistant, and shall comply with Sections 302.1 and 302.3 of ICC A117.1. Changes in level in floor surfaces shall comply with Section 303 of ICC A117.1.

1112.7 Turning Space at Clustered Mailbox Units

AMENDMENT
This section has been amended at the state or city level.
At least one turning space shall be provided at the front of each clustered mailbox unit. The turning space shall conform to ICC A117.1, Section 304 and shall be either:
  1. A circular space having a diameter not less than 72 inches (1829 mm).
  2. A T-shaped space within a square not less than 72 inches (1829 mm) per side, with arms and base not less than 48 inches (1219 mm) wide. Each arm of the T shall be clear of obstructions not less than 24 inches (610 mm) in each direction, and the base shall be clear of obstructions not less than 36 inches (914 mm). The turning space shall be permitted to include knee and toe clearances complying with Section 306 only at the end of either the base or one arm.

1112.8 Protruding Objects

AMENDMENT
This section has been amended at the state or city level.
Protruding objects along the accessible route to clustered mailboxes shall conform to Section 307 of ICC A117.1.

1112.9 Clear Access Space

AMENDMENT
This section has been amended at the state or city level.
Clear access space conforming to Section 305 of ICC A117.1, shall be provided to each of the mailboxes at the clustered mailbox location. The clear access space and the turning space may overlap.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING