ADOPTS WITH AMENDMENTS:

International Building Code 2012 (IBC 2012)

Heads up: There are no amended sections in this chapter.

Chapter 11 Accessibility

AMENDMENT
This section has been amended at the state or city level.
For SI: 1 inch = 25.4 mm.
FIGURE 1


For SI: 1 foot = 304.8 mm. 1 degree = 0.01745 rad.
FIGURE 2


For SI: 1 foot = 304.8 mm, 1 degree = 0.01745.
FIGURE 3


For SI: 1 foot = 304.8 mm.
FIGURE 4


For SI: 1 inch = 25.4 mm.. 1 foot = 308.4 mm.
FIGURE 5


For SI: 1 inch = 25.4 mm., 1 foot = 304.8 mm.
FIGURE 6


For SI: 1 inch = 25.4 mm.
FIGURE 7


For SI: 1 inch = 25.4 mm., 1 foot = 304.8 mm.
FIGURE 8


For SI: 1 inch = 25.4 mm., 1 foot = 304.8 mm.
FIGURE 9


For SI: 1 inch = 25.4 mm., 1 foot = 304.8 mm.
FIGURE 10
The provisions of this chapter shall control the design and construction of facilities for accessibility to physically disabled persons.
Buildings and facilities shall be designed and constructed to be accessible in accordance with this code and ICC A117.1.

1101.2.1 Alternate Methods

AMENDMENT
This section has been amended at the state or city level.
The application of Section 104.11 to this chapter shall be limited to the extent that alternate methods of construction, designs or technologies shall provide substantially equivalent or greater accessibility. Where approved by the building official, the provisions of the Fair Housing Act Amendments of 1988 may be considered as an alternate method to the criteria outlined in ICC A117.1 as it relates to covered multifamily dwellings.

ORS 447.220 and 447.231 are not a part of this code but are reproduced here for the reader's convenience:

447.220 Purpose. It is the purpose of ORS 447.210 to 447.280 to make affected buildings, including but not limited to commercial facilities, public accommodations, private entities, private membership clubs and churches, in the state accessible to and usable by persons with disabilities, as provided in the Americans with Disabilities Act, and to make covered multifamily dwellings in the state accessible to and usable by all persons with disabilities, as provided in the Fair Housing Act. In requiring that buildings and facilities be usable by persons with disabilities, it is not the intention of the Legislative Assembly to require that items of personal convenience such as rest rooms, telephones and drinking fountains be provided for members of the public who have disabilities if they are not otherwise provided for members of the public who do not have disabilities. However, pursuant to the Americans with Disabilities Act, the Director of the Department of Consumer and Business Services may provide greater protection to individuals with disabilities by adopting more stringent standards than prescribed by the Americans with Disabilities Act. [1971 c.320 §1; 1973 c.539 §2; 1979 c.133 §2; 1989 c.224 §110; 1993 c.503 §2]

447.231 Rules to eliminate architectural barriers. Notwithstanding any other provision of law and the authority of any board within the Department of Consumer and Business Services, the Director of the Department of Consumer and Business Services shall adopt rules to conform the state building code to the Americans with Disabilities Act and the Fair Housing Act and the regulations adopted thereunder. In addition, the director shall adopt rules to conform the state building code to the provisions of ORS 447.210 to 447.280, to the extent to which any statute is stricter than the Americans with Disabilities Act or the Fair Housing Act. [1991 c.691 §2; 1993 c.503 §4; 2003 c.14 §269]

1101.2.2 Amendments to ICC A117.1

AMENDMENT
This section has been amended at the state or city level.
The provisions of this section shall be considered amendments to ICC A117.1.

1101.2.2.1 Elevators—ICC A117.1 Section 407

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Section 407 is not adopted. Elevators are expressly regulated through the Oregon Elevator Specialty Code.

1101.2.2.2 Limited-Use/Limited-Application Elevators (LULA)—ICC A117.1 Section 408

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Section 408 is not adopted. LULAs are expressly regulated through the Oregon Elevator Specialty Code.

1101.2.2.3 Private Residence Elevators—ICC A117.1 Section 409

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Section 409 is not adopted. Private residence elevators are expressly regulated through the Oregon Elevator Specialty Code.

1101.2.2.4 Platform Lifts—ICC A117.1 Section 410

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Section 410 is not adopted. Platform lifts are expressly regulated through the Oregon Elevator Specialty Code.

1101.2.2.5 Door Opening Force—ICC A117.1 Section 404.2.8

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Section 404.2.8 is deleted in its entirety and replaced with the following: The opening force of doors along an accessible route shall be as follows:
  1. Exterior doors: 81/2 pounds-force (lbf) (37.8 N).
  2. Interior doors: 5 pounds-force (lbf) (22.2 N).
  3. Stairway doors at pressurized stair enclosures: 15 pounds (6.8 kg) at exterior doors.
  4. Where environmental conditions require greater closing pressure, power-operated doors shall be used within the accessible route.
  5. Fire doors shall have the minimum force necessary to close and latch the door.

1101.2.2.6 Detectable Warnings at Raised Marked Crossings—ICC A117.1 Section 406.12

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Section 406.12 is deleted in its entirety.

1101.2.2.7 Vehicle Space Width—ICC A117.1 Section 502.2

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Section 502.2 is deleted in its entirety and replaced with the following: Car and van parking spaces shall be designed in compliance with the Standards for Accessible Parking Places set forth by the Oregon Transportation Commission.

1101.2.2.8 Access Aisle Width—ICC A117.1 Section 502.4.2

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Section 502.4.2 is deleted in its entirety and replaced with the following: Access aisles serving car parking spaces shall be designed in compliance with the Standards for Accessible Parking Places set forth by the Oregon Transportation Commission.

1101.2.2.9 Recreational Facilities—ICC A117.1 Chapter 11

AMENDMENT
This section has been amended at the state or city level.
ICC A117.1 Chapter 11 is adopted as follows:
  1. Section 1101.2.1 General exceptions. Section 1101.2.1 is adopted in its entirety.
  2. Section 1101.2.2 Area of sport activity. Section 1101.2.2 is adopted but is restricted in application to sites where buildings and facilities meeting the definition of "Affected Buildings" are constructed. See ORS 447.210(1).
  3. Section 1101.2.3 Recreational boating facilities. Section 1101.2.3 is adopted but is restricted in application to fixed (nonfloating) docks and piers.
  4. Section 1101.2.4 Exercise machines and equipment. Section 1101.2.4 is not adopted.
  5. Section 1101.3 Protruding objects. Section 1101.3 is adopted in its entirety.
  6. Section 1102 Amusement rides. Section 1102 is adopted but is restricted in application to those provisions providing accessibility to an amusement ride which is accessory to an "Affected Building." Amusement rides are regulated exclusively through Oregon Building Codes Division's "Elevator and Amusement Ride Safety Program."
  7. Section 1103 Recreational boating facilities. Section 1103 is adopted but is restricted in application to fixed (nonfloating) docks and piers.
  8. Section 1104 Exercise machines and equipment. Section 1104 is not adopted.
  9. Section 1105 Fishing piers and platforms. Section 1105 is adopted but is restricted in application to fixed (nonfloating) fishing piers and platforms.
  10. Section 1106 Golf facilities. Section 1106 is not adopted.
  11. Section 1107 Miniature golf facilities. Section 1107 is adopted but is restricted in application to sites where buildings and facilities meeting the definition of "Affected Buildings" are constructed. See ORS 447.210(1).
  12. Section 1108 Play areas. Section 1108 is adopted but is restricted in application to children's play structures as governed by Section 402.6.3.
  13. Section 1109 Swimming pools, wading pools, hot tubs and spas. Section 1109 is not adopted.
  14. Section 1110 Shooting ranges. Section 1110 is adopted but is restricted in application to sites where buildings and facilities meeting the definition of "Affected Buildings" are constructed. See ORS 447.210(1).

1101.3 Waivers and Modifications

AMENDMENT
This section has been amended at the state or city level.
Waivers and modifications shall be in accordance with ORS 447.250.

ORS 447.250 is not a part of this code but is reproduced here for the reader's convenience:

447.250 Waivers or modifications of standards and specifications; appeals board; procedures; fees.

  1. When a person or governmental entity undertaking the construction, renovation, alteration or modification of an affected building or its related facilities determines that a particular standard or specification exceeds the standards or specifications imposed by the Americans with Disabilities Act and the Fair Housing Act, and that full compliance with the standard or specification is impractical in that it would defeat the purpose of the project proposed or in process, it may apply to the appeals board having jurisdiction over the project for a waiver or modification of such standard or specification, setting forth the reasons for its determination and a proposal for the work complying with the particular standard or specification to the maximum extent that it considers practical.
    1. For projects involving a state correctional facility as defined in ORS 421.005(2), or a local correctional facility, as defined in ORS 169.005, the appeals board referred to in subsection (1) of this section is the Building Codes Structures Board established under ORS 455.132.
    2. For all other projects, the appeals board referred to in subsection (1) of this section is the appeals board established under ORS 455.020(4) by the municipality having jurisdiction over the project.
  2. The appeals board shall thereupon investigate the application. The board in its investigation shall be required to seek the advice of the Oregon Disabilities Commission or its designee in dealing with architectural barrier waivers. If the appeals board finds that the proposal submitted with the application would constitute a substantial compliance with, or an acceptable alternative to, the particular standard or specification in view of the objectives of ORS 447.210 to 447.280, the waiver shall be granted. If the board finds otherwise, the application shall be promptly denied with notice to the requesting person or governmental entity of the denial.
  3. The findings of the appeals board shall include the estimated building costs and the additional cost of construction to conform to the requirements of ORS 447.210 to 447.280 over the cost of a nonconforming feature or any other special reason or circumstance that, in the judgment of the board, justifies the decision.
  4. Any person aggrieved by the final decision of an appeals board may within 30 days of the decision appeal to the Director of the Department of Consumer and Business Services. In the case where no appeals board has been created the director shall have original jurisdiction of an application for a waiver. The applicant for a waiver or an appeal shall submit a fee of $20 payable to the director with the request for waiver or appeal. In determining an appeal or an original application, the procedures and standards of subsections (1) to (4) of this section shall apply to the director. [1971 c.320 §5; 1973 c.539 §7; 1979 c.133 §4; 1987 c.672 §3; 1989 c.224 §115; 1989 c.703 §2; 1993 c.744 §78; 1995 c.307 §3; 2001 c.517 §6]
Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities.
Sites, buildings, structures, facilities, elements and spaces shall be exempt from this chapter to the extent specified in this section.
Accessibility is not required in buildings and facilities, or portions thereof, to the extent permitted by Sections 1104 through 1110.
Existing buildings shall comply with Section 3411.
Spaces and elements within employee work areas shall only be required to comply with Sections 907.5.2.3.2, 1007 and 1104.3.1 and shall be designed and constructed so that individuals with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, that are less than 300 square feet (30 m2) in area and located 7 inches (178 mm) or more above or below the ground or finish floor where the change in elevation is essential to the function of the space shall be exempt from all requirements.
Detached one- and two-family dwellings and accessory structures, and their associated sites and facilities, are not required to be accessible.
Occupancies in Group U are exempt from the requirements of this chapter other than the following:
  1. In agricultural buildings, access is required to paved work areas and areas open to the general public.
  2. Private garages or carports that contain required accessible parking.
Structures, sites and equipment directly associated with the actual processes of construction including, but not limited to, scaffolding, bridging, materials hoists, materials storage or construction trailers are not required to be accessible.
Raised areas used primarily for purposes of security, life safety or fire safety including, but not limited to, observation galleries, prison guard towers, fire towers or lifeguard stands, are not required to be accessible or to be served by an accessible route.
Nonoccupiable spaces accessed only by ladders, catwalks, crawl spaces, freight elevators or very narrow passageways are not required to be accessible.
Spaces frequented only by personnel for maintenance, repair or monitoring of equipment are not required to be accessible. Such spaces include, but are not limited to, elevator pits, elevator penthouses, mechanical, electrical or communications equipment rooms, piping or equipment catwalks, water or sewage treatment pump rooms and stations, electric substations and transformer vaults, and highway and tunnel utility facilities.
Single-occupant structures accessed only by passageways below grade or elevated above grade including, but not limited to, toll booths that are accessed only by underground tunnels, are not required to be accessible.
Buildings of Group R-1 containing not more than five sleeping units for rent or hire that are also occupied as the residence of the proprietor are not required to be accessible.
Where a day care facility is part of a dwelling unit, only the portion of the structure utilized for the day care facility is required to be accessible.
In live/work units constructed in accordance with Section 419, the portion of the unit utilized for nonresidential use is required to be accessible. The residential portion of the live/work unit is required to be evaluated separately in accordance with Sections 1107.6.2 and 1107.7.
In detention and correctional facilities, common use areas that are used only by inmates or detainees and security personnel, and that do not serve holding cells or housing cells required to be accessible, are not required to be accessible or to be served by an accessible route.
Walk-in coolers and freezers intended for employee use only are not required to be accessible.

1103.2.16 Private Membership Clubs and Churches

AMENDMENT
This section has been amended at the state or city level.
In accordance with ORS 447.210(1), private membership clubs and churches that have more than one floor level and more than 4,000 square feet (372 m2) in ground area or more than one floor level and more than 20 feet (9096 mm) in height, measured from the top surface of the lowest flooring to the highest interior overhead finish of the building, are required to be accessible.
Accessible routes within the site shall be provided from public transportation stops; accessible parking; accessible passenger loading zones; and public streets or sidewalks to the accessible building entrance served.
Exception: Other than in buildings or facilities containing or serving Type B units, an accessible route shall not be required between site arrival points and the building or facility entrance if the only means of access between them is a vehicular way not providing for pedestrian access.

1104.2 Within a Site

ILLUSTRATION
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.
Exception: An accessible route is not required between accessible buildings, accessible facilities, accessible elements and accessible spaces that have, as the only means of access between them, a vehicular way not providing for pedestrian access.
When a building or portion of a building is required to be accessible, an accessible route shall be provided to each portion of the building, to accessible building entrances connecting accessible pedestrian walkways and the public way.
Exceptions:
  1. In a building, room or space used for assembly purposes with fixed seating, an accessible route shall not be required to serve levels where wheelchair spaces are not provided.
  2. In Group I-2 facilities, doors to sleeping units shall be exempted from the requirements for maneuvering clearance at the room side provided the door is a minimum of 44 inches (1118 mm) in width.
Common use circulation paths within employee work areas shall be accessible routes.
Exceptions:
  1. Common use circulation paths, located within employee work areas that are less than 1,000 square feet (93 m2) in size and defined by permanently installed partitions, counters, casework or furnishings, shall not be required to be accessible routes.
  2. Common use circulation paths, located within employee work areas, that are an integral component of equipment, shall not be required to be accessible routes.
  3. Common use circulation paths, located within exterior employee work areas that are fully exposed to the weather, shall not be required to be accessible routes.
Press boxes in a building, room or space used for assembly purposes shall be on an accessible route.
Exceptions:
  1. An accessible route shall not be required to press boxes in bleachers that have points of entry at only one level, provided that the aggregate area of all press boxes is 500 square feet (46 m2) maximum.
  2. An accessible route shall not be required to free-standing press boxes that are elevated above grade 12 feet (3660 mm) minimum provided that the aggregate area of all press boxes is 500 square feet (46 m2) maximum.

1104.4 Multilevel Buildings and Facilities

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
At least one accessible route shall connect each story and mezzanine in multistory buildings and facilities.
Exceptions:
  1. In private buildings or facilities that are less than three stories and that have less than 3,000 square feet (279 m2) per story, an accessible route shall not be required to connect stories provided that the building or facility is not a shopping center, a shopping mall, the professional office of a health care provider, a terminal, depot or other station used for specified public transportation or airport passenger terminal.
  2. Levels that do not contain accessible elements or other spaces as determined by Section 1107 or 1108 are not required to be served by an accessible route from an accessible level.
  3. In air traffic control towers, an accessible route is not required to serve the cab and the floor immediately below the cab.
  4. Where a two-story public building or facility has one story with an occupant load of five or fewer persons that does not contain public use space, that story shall not be required to be connected by an accessible route to the story above or below.
  5. Vertical access to elevated employee work stations within a courtroom is not required at the time of initial construction, provided a ramp, lift or elevator can be installed without requiring reconfiguration or extension of the courtroom or extension of the electrical system.
  6. In a parking garage of fewer than three stories, an accessible route need not be provided to an upper or lower floor level provided that all of the accessible parking spaces are provided on a floor level with an accessible route to an accessible building entrance or to another building.
  7. In a building of fewer than three stories, an accessible route need not be provided in the portion of the building that is of the following occupancy classifications:
    1. Group F-1 and 2;
    2. Group H-1, 2, 3, 4 and 5;
    3. Group S-1 and 2; and
    4. Group U.
  8. In a mixed-occupancy building of fewer than three stories, containing a Group B or M occupancy mixed with Group F-1 or 2; Group H-2, 3, 4 or 5; Group S-1 or S-2; or Group U occupancies, an accessible route need not be provided, if the Group B or M occupancy is less than 3,000 square feet (279 m2) on any floor level without an accessible route.
  9. In a building or occupancy of fewer than two stories, an elevator need not be provided to a mezzanine that is less than 3,000 square feet (279 m2).
  10. In a building of fewer than three stories, an accessible route need not be provided where ramps, grade-level entries or accessible horizontal connections from adjacent buildings are provided to each floor level, provided all facilities, elements and spaces are connected to an accessible route.

1104.5 Elevators Required

AMENDMENT
This section has been amended at the state or city level.
Elevators shall be provided in all shopping centers, shopping malls, professional offices of health care providers (B or I occupancies), a terminal, depot or other station used for specified public transportation or airport passenger terminals and government buildings that are covered by Title II of the Americans with Disabilities Act.
ORS447.247 is not a part of this code but is reproduced here for the reader's convenience:

447.247 Elevators required; criteria; rules.
  1. Elevators are required:
    1. In all shopping centers, shopping malls, professional offices of health care providers and government buildings that are covered by Title II of the Americans with Disabilities Act.
    2. In all other commercial facilities, private entities and places of public accommodation covered by Title III of the Americans with Disabilities Act that have more than one floor level and more than 3,000 square feet in ground area or that are more than 20 feet in height, measured from the top surface of the lowest flooring to the highest interior overhead finish of the building; and
    3. In all private membership clubs and churches that have more than one floor level and more than 4,000 square feet in ground area or that are more than 20 feet in height, measured from the top surface of the lowest flooring to the highest interior overhead finish of the building.
  2. The Department of Consumer and Business Services may by rule create exceptions to the requirements of this section if this section would require an elevator in a building that would not be required to have an elevator under the provisions of the Americans with Disabilities Act or the Fair Housing Act. [1993 c.503 §6; 1995 c.307 §2]
Exceptions:
  1. Elevators need not be provided in buildings and spaces listed in ORS 447.247(1)(a), which are exempt from the accessible route provisions identified Section 1104.4, Exception 4.
  2. Elevators need not be provided in buildings and spaces listed in ORS 447.247(1)(b), which are exempt from the accessible route provisions of Section 1104.4.
  3. Elevators are not required where a terminal, depot or other station used for specified public transportation or airport passenger terminals are provided with an accessible route to all portions of the facilities.

1104.5 1104.6 Location

AMENDMENT
This section has been amended at the state or city level.
Accessible routes shall coincide with or be located in the same area as a general circulation path. Where the circulation path is interior, the accessible route shall also be interior. Where only one accessible route is provided, the accessible route shall not pass through kitchens, storage rooms, restrooms, closets or similar spaces.
Exceptions:
  1. Accessible routes from parking garages contained within and serving Type B units are not required to be interior.
  2. A single accessible route is permitted to pass through a kitchen or storage room in an Accessible unit, Type A unit or Type B unit.

1104.6 1104.7 Security Barriers

AMENDMENT
This section has been amended at the state or city level.
Security barriers including, but not limited to, security bollards and security check points shall not obstruct a required accessible route or accessible means of egress.
Exception: Where security barriers incorporate elements that cannot comply with these requirements, such as certain metal detectors, fluoroscopes or other similar devices, the accessible route shall be permitted to be provided adjacent to security screening devices. The accessible route shall permit persons with disabilities passing around security barriers to maintain visual contact with their personal items to the same extent provided others passing through the security barrier.
In addition to accessible entrances required by Sections 1105.1.1 through 1105.1.6, at least 60 percent of all public entrances shall be accessible.
Exceptions:
  1. An accessible entrance is not required to areas not required to be accessible.
  2. Loading and service entrances that are not the only entrance to a tenant space.
Where provided, direct access for pedestrians from parking structures to buildings or facility entrances shall be accessible.
Where direct access is provided for pedestrians from a pedestrian tunnel or elevated walkway to a building or facility, at least one entrance to the building or facility from each tunnel or walkway shall be accessible.
Where restricted entrances are provided to a building or facility, at least one restricted entrance to the building or facility shall be accessible.
Where entrances used only by inmates or detainees and security personnel are provided at judicial facilities, detention facilities or correctional facilities, at least one such entrance shall be accessible.
If a service entrance is the only entrance to a building or a tenant space in a facility, that entrance shall be accessible.
At least one accessible entrance shall be provided to each tenant, dwelling unit and sleeping unit in a facility.
Exceptions:
  1. An accessible entrance is not required to tenants that are not required to be accessible.
  2. An accessible entrance is not required to dwelling units and sleeping units that are not required to be Accessible units, Type A units or Type B units.

1106.1 Required

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Where parking is provided, accessible parking spaces shall be provided in compliance with Table 1106.1, except as required by Sections 1106.2 through 1106.4. Where more than one parking facility is provided on a site, the number of parking spaces required to be accessible shall be calculated separately for each parking facility.
Exception: This section does not apply to parking spaces used exclusively for buses, trucks, other delivery vehicles, law enforcement vehicles or vehicular impound and motor pools where lots accessed by the public are provided with an accessible passenger loading zone.
TABLE 1106.1
ACCESSIBLE PARKING SPACES
TOTAL PARKING IN LOT MINIMUM NUMBER OF
ACCESSIBLE SPACES
NUMBER OF VAN ACCESSIBLE SPACES "WHEELCHAIR USER ONLY" SPACES
1 to 251 1 -
26 to 502 1 -
51 to 753 1 -
76 to 1004 1 -
101 to 1505 - 1
151 to 2006 - 1
201 to 3007 - 2
301 to 4008 - 2
401 to 5009 - 2
501 to 1,0002% of total - 1 in every
6 accessible spaces
or portion thereof
1,001 and over20, plus one for each 100,
or fraction thereof, over 1,000
- 1 in every
6 accessible spaces
or portion thereof

ORS 447.233(5) through (7) are not a part of this code but are reproduced here for the reader's convenience:

447.233 Accessible parking space requirements; inspection of spaces; violation.

(5) The director is authorized to inspect parking spaces and facilities and buildings subject to the provisions of this section, and to do whatever is necessary to enforce the requirements, including the maintenance requirements, of this section. Municipalities and counties may administer and enforce the requirements of this section in the manner provided under ORS 455.148 or 455.150 for administration and enforcement of specialty codes. All plans for parking spaces subject to the provisions of this section must be approved by the director prior to the creation of the spaces.

(6) Requirements adopted under this section do not apply to long-term parking facilities at the Portland International Airport.

(7) Any reported violation of this section shall be investigated by the administrative authority. The administrative authority shall make a final decision and order correction, if necessary, within 30 days of notification. Any aggrieved person may appeal within 30 days of the decision by the administrative authority to the appropriate municipal appeals board or, at the option of the local jurisdiction, directly to the Building Codes Structures Board established under ORS 455.132. The appeal shall be acted upon within 60 days of filing. The decision of the municipal appeals board may be appealed to the board. The board shall act on the appeal within 60 days of filing. All appeals to the board shall be filed in accordance with ORS 455.690. [1979 c.809 §2; 1981 c.275 §1; 1983 c.338 §930; 1987 c.187 §1; 1989 c.243 §15; 1991 c.741 §6; 1993 c.503 §8; 1993 c.744 §77; 2001 c.573 §5; 2007 c.468 §1]
At least 2 percent, but not less than one, of each type of parking space provided for occupancies in Groups R-2 and R-3, which are required to have Accessible, Type A or Type B dwelling or sleeping units, shall be accessible. Where parking is provided within or beneath a building, accessible parking spaces shall also be provided within or beneath the building.
At least 10 percent, but not less than one, of care recipient and visitor parking spaces provided to serve hospital outpatient facilities shall be accessible.
At least 20 percent, but not less than one, of the portion of care recipient and visitor parking spaces serving rehabilitation facilities specializing in treating conditions that affect mobility and outpatient physical therapy facilities shall be accessible.

1106.5 Van Spaces

AMENDMENT
This section has been amended at the state or city level.
For every six or fraction of six accessible parking spaces, at least one shall be a van-accessible parking space. Where five or more parking spaces are designated accessible, any space that is designated as van accessible shall be reserved for wheelchair users.
Exception: In Group R-2 and R-3 occupancies, van-accessible spaces located within private garages shall be permitted to have vehicular routes, entrances, parking spaces and access aisles with a minimum vertical clearance of 7 feet (2134 mm).

1106.6 Location

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Accessible parking spaces shall be located on the shortest practical accessible route of travel from adjacent parking to an accessible building entrance. In parking facilities that do not serve a particular building, accessible parking spaces shall be located on the shortest route to an accessible pedestrian entrance to the parking facility. Where buildings have multiple accessible entrances with adjacent parking, accessible parking spaces shall be dispersed and located near the accessible entrances.
Exceptions:
  1. In multilevel parking structures, van-accessible parking spaces are permitted on one level.
  2. Accessible parking spaces shall be permitted to be located in different parking facilities if substantially equivalent or greater accessibility is provided in terms of distance from an accessible entrance or entrances, parking fee and user convenience.

1106.7 Passenger Loading Zones

AMENDMENT
This section has been amended at the state or city level.

1106.7 Parking Spaces

AMENDMENT
This section has been amended at the state or city level.

1106.7.1 Continuous Loading Zones

AMENDMENT
This section has been amended at the state or city level.

1106.7.1 General

AMENDMENT
This section has been amended at the state or city level.
Accessible car and van parking spaces shall comply with the surface requirements of ICC ANSI A117.1 Section 502.

Accessible parking spaces, dimensions, markings and signs shall be designed in compliance with the Standards for Accessible Parking Places set forth by the Oregon Transportation Commission.

1106.7.2 Medical Facilities

AMENDMENT
This section has been amended at the state or city level.

1106.7.2 Identification

AMENDMENT
This section has been amended at the state or city level.
Identification of accessible parking spaces shall be in accordance with the Standards for Accessible Parking Places set forth by the Oregon Transportation Commission.

1106.7.3 Valet Parking

AMENDMENT
This section has been amended at the state or city level.

1106.7.4 Mechanical Access Parking Garages

AMENDMENT
This section has been amended at the state or city level.

1106.8 Passenger Loading Zones

AMENDMENT
This section has been amended at the state or city level.
Passenger loading zones shall be accessible.

1106.8.1 Continuous Loading Zones

AMENDMENT
This section has been amended at the state or city level.
Where passenger loading zones are provided, one passenger loading zone in every continuous 100 linear feet (30.4 m) maximum of loading zone space shall be accessible.

1106.8.2 Medical Facilities

AMENDMENT
This section has been amended at the state or city level.
A passenger loading zone shall be provided at an accessible entrance to licensed medical and long-term care facilities where people receive physical or medical treatment or care and where the period of stay exceeds 24 hours.

1106.8.2.1 Group I-2

AMENDMENT
This section has been amended at the state or city level.
In Group I-2 healthcare occupancies, at least one accessible entry shall be under shelter. Every such entry shall include a passenger loading zone.

1106.8.3 Valet Parking

AMENDMENT
This section has been amended at the state or city level.
A passenger loading zone shall be provided at valet parking services.

1106.8.4 Mechanical Access Parking Garages

AMENDMENT
This section has been amended at the state or city level.
Mechanical access parking garages shall provide at least one passenger loading zone at vehicle drop-off and vehicle pickup areas.
In addition to the other requirements of this chapter, occupancies having dwelling units or sleeping units shall be provided with accessible features in accordance with this section.
Dwelling units and sleeping units that are required to be Accessible units, Type A units and Type B units shall comply with the applicable portions of Chapter 10 of ICC A117.1. Units required to be Type A units are permitted to be designed and constructed as Accessible units. Units required to be Type B units are permitted to be designed and constructed as Accessible units or as Type A units.
Rooms and spaces available to the general public or available for use by residents and serving Accessible units, Type A units or Type B units shall be accessible. Accessible spaces shall include toilet and bathing rooms, kitchen, living and dining areas and any exterior spaces, including patios, terraces and balconies.
Exceptions:
  1. Recreational facilities in accordance with Section 1109.15.
  2. In Group I-2 facilities, doors to sleeping units shall be exempted from the requirements for maneuvering clearance at the room side provided the door is a minimum of 44 inches (1118 mm) in width.
At least one accessible route shall connect accessible building or facility entrances with the primary entrance of each Accessible unit, Type A unit and Type B unit within the building or facility and with those exterior and interior spaces and facilities that serve the units.
Exceptions:
  1. If due to circumstances outside the control of the owner, either the slope of the finished ground level between accessible facilities and buildings exceeds one unit vertical in 12 units horizontal (1:12), or where physical barriers or legal restrictions prevent the installation of an accessible route, a vehicular route with parking that complies with Section 1106 at each public or common use facility or building is permitted in place of the accessible route.
  2. Exterior decks, patios or balconies that are part of Type B units and have impervious surfaces, and that are not more than 4 inches (102 mm) below the finished floor level of the adjacent interior space of the unit.

1107.5 Group I

AMENDMENT
This section has been amended at the state or city level.
Accessible units, Type A units, and Type B units shall be provided in Group I occupancies in accordance with Sections 1107.5.1 through 1107.5.5.

1107.5.1 Group I-1

AMENDMENT
This section has been amended at the state or city level.
Accessible units, Type A units, and Type B units shall be provided in Group I-1 occupancies in accordance with Sections 1107.5.1.1 and 1107.5.1.3. All Group I-1, Condition 2 assisted living facilities and residential care facilities shall be provided with one standard roll-in-type shower compartment, in each dwelling or sleeping unit, where bathing facilities are provided inside the dwelling or sleeping unit. All Group I-1, Condition 2 residential care facilities shall be provided with a standard roll-in-type shower compartment, in each bathing facility provided outside the dwelling or sleeping unit, except in a bathing room where an accessible tub is provided.
Exception: In Group I-1, Condition 2 assisted living facilities, skilled nursing facilities and residential care facilities the folded seat is permitted to be omitted for standard roll-in-type shower compartments and the shower controls may be located on the side walls.

1107.5.1.1 Accessible Units

AMENDMENT
This section has been amended at the state or city level.
In Group I-1, Condition 1, at least 4 percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units. In Group I-1, Condition 2, at least 10 percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units.

1107.5.1.2 Type A Units

AMENDMENT
This section has been amended at the state or city level.
In Group I-1, Condition 2 assisted living facilities and residential care facilities, every dwelling unit or sleeping unit shall be a Type A unit.

1107.5.1.2 1107.5.1.3 Type B Units

AMENDMENT
This section has been amended at the state or city level.
In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.
Accessible units and Type B units shall be provided in nursing homes of Group I-2 occupancies in accordance with Sections 1107.5.2.1 and 1107.5.2.2.
At least 50 percent but not less than one of each type of the dwelling units and sleeping units shall be Accessible units.
In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.
Accessible units and Type B units shall be provided in general-purpose hospitals, psychiatric facilities and detoxification facilities of Group I-2 occupancies in accordance with Sections 1107.5.3.1 and 1107.5.3.2.
At least 10 percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units.
In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.
In hospitals and rehabilitation facilities of Group I-2 occupancies which specialize in treating conditions that affect mobility, or units within either which specialize in treating conditions that affect mobility, 100 percent of the dwelling units and sleeping units shall be Accessible units.
Accessible units shall be provided in Group I-3 occupancies in accordance with Sections 1107.5.5.1 through 1107.5.5.3.
In Group I-3 occupancies, at least 2 percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units.
In addition to the Accessible units required by Section 1107.5.5.1, where special holding cells or special housing cells or rooms are provided, at least one serving each purpose shall be an Accessible unit. Cells or rooms subject to this requirement include, but are not limited to, those used for purposes of orientation, protective custody, administrative or disciplinary detention or segregation, detoxification and medical isolation.
Exception: Cells or rooms specially designed without protrusions and that are used solely for purposes of suicide prevention shall not be required to include grab bars.
Patient sleeping units or cells required to be Accessible units in medical care facilities shall be provided in addition to any medical isolation cells required to comply with Section 1107.5.5.2.
Accessible units, Type A units and Type B units shall be provided in Group R occupancies in accordance with Sections 1107.6.1 through 1107.6.4.
Accessible units and Type B units shall be provided in Group R-1 occupancies in accordance with Sections 1107.6.1.1 and 1107.6.1.2.
Accessible dwelling units and sleeping units shall be provided in accordance with Table 1107.6.1.1. All dwelling units and sleeping units on a site shall be considered to determine the total number of Accessible units. Accessible units shall be dispersed among the various classes of units. Roll-in showers provided in Accessible units shall include a permanently mounted folding shower seat.

TABLE 1107.6.1.1
ACCESSIBLE DWELLING UNITS AND SLEEPING UNITS
TOTAL NUMBER OF
UNITS PROVIDED
MINIMUM REQUIRED NUMBER OF
ACCESSIBLE UNITS WITHOUT
ROLL-IN SHOWERS
MINIMUM REQUIRED NUMBER OF
ACCESSIBLE UNITS WITH
ROLL-IN SHOWERS
TOTAL NUMBER OF
REQUIRED ACCESSIBLE UNITS
1 to 25 1 0 1
26 to 50 2 0 2
51 to 75 3 1 4
76 to 100 4 1 5
101 to 150 5 2 7
151 to 200 6 2 8
201 to 300 7 3 10
301 to 400 8 4 12
401 to 500 9 4 13
501 to 1,000 2% of total 1% of total 3% of total
Over 1,000 20, plus 1 for each 100,
or fraction thereof, over 1,000
10 plus 1 for each 100, or
fraction thereof, over 1,000
30 plus 2 for each 100, or
fraction thereof, over 1,000
All interior and exterior spaces provided as part of or serving an Accessible dwelling unit or sleeping unit shall be accessible and be located on an accessible route.
Exceptions:
  1. Where multiple bathrooms are provided within an Accessible unit, at least one full bathroom shall be accessible.
  2. Where multiple-family or assisted bathrooms serve an Accessible unit, at least 50 percent but not less than one room for each use at each cluster shall be accessible.
  3. Five percent, but not less than one bed shall be accessible.
In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.
Accessible units, Type A units and Type B units shall be provided in Group R-2 occupancies in accordance with Sections 1107.6.2.1 and 1107.6.2.2.
Type A units and Type B units shall be provided in apartment houses, monasteries and convents in accordance with Sections 1107.6.2.1.1 and 1107.6.2.1.2.
In Group R-2 occupancies containing more than 20 dwelling units or sleeping units, at least 2 percent but not less than one of the units shall be a Type A unit. All Group R-2 units on a site shall be considered to determine the total number of units and the required number of Type A units. Type A units shall be dispersed among the various classes of units.
Exceptions:
  1. The number of Type A units is permitted to be reduced in accordance with Section 1107.7.
  2. Existing structures on a site shall not contribute to the total number of units on a site.
Where there are four or more dwelling units or sleeping units intended to be occupied as a residence in a single structure, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.
In Group R-2 occupancies, other than apartment houses, monasteries and convents, Accessible units and Type B units shall be provided in accordance with Sections 1107.6.2.2.1 and 1107.6.2.2.2.
Accessible dwelling units and sleeping units shall be provided in accordance with Table 1107.6.1.1.
Where there are four or more dwelling units or sleeping units intended to be occupied as a residence in a single structure, every dwelling unit and every sleeping unit intended to be occupied as a residence shall be a Type B unit.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.
In Group R-3 occupancies where there are four or more dwelling units or sleeping units intended to be occupied as a residence in a single structure, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.

1107.6.4 Group R-4

AMENDMENT
This section has been amended at the state or city level.
Accessible units, Type A units, and Type B units shall be provided in Group R-4 occupancies in accordance with Sections 1107.6.4.1 through 1107.6.4.3. All Group R-4, Condition 2 assisted living facilities and residential care facilities shall be provided with one standard roll-in-type shower compartment, in each dwelling or sleeping unit, where bathing facilities are provided inside the dwelling or sleeping unit. All Group R-4, Condition 2 residential care facilities shall be provided with a standard roll-in-type shower compartment, in each bathing facility provided outside the dwelling or sleeping unit, except in a bathing room where an accessible tub is provided.
Exception: In Group R-4, Condition 2 assisted living facilities, skilled nursing facilities and residential care facilities the folded seat is permitted to be omitted for standard roll-in-type shower compartments and the shower controls may be located on the side walls.

1107.6.4.1 Accessible Units

AMENDMENT
This section has been amended at the state or city level.
In Group R-4, Condition 1, at least one of the dwelling or sleeping units shall be an Accessible unit. In Group R-4, Condition 2, at least 10 percent, but not less than one, of the dwelling units and sleeping units shall be Accessible units.

1107.6.4.2 Type A Units

AMENDMENT
This section has been amended at the state or city level.
In Group R-4, Condition 2 assisted living facilities and residential care facilities, every dwelling unit or sleeping unit shall be a Type A unit.

1107.6.4.2 1107.6.4.3 Type B Units

AMENDMENT
This section has been amended at the state or city level.
In structures with four or more dwelling units or sleeping units intended to be occupied as a residence, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.
Where specifically permitted by Section 1107.5 or 1107.6, the required number of Type A units and Type B units is permitted to be reduced in accordance with Sections 1107.7.1 through 1107.7.5.
Where no elevator service is provided in a structure, only the dwelling units and sleeping units that are located on stories indicated in Sections 1107.7.1.1 and 1107.7.1.2 are required to be Type A units and Type B units, respectively. The number of Type A units shall be determined in accordance with Section 1107.6.2.1.1.
At least one story containing dwelling units or sleeping units intended to be occupied as a residence shall be provided with an accessible entrance from the exterior of the structure and all units intended to be occupied as a residence on that story shall be Type B units.
On all other stories that have a building entrance in proximity to arrival points intended to serve units on that story, as indicated in Items 1 and 2, all dwelling units and sleeping units intended to be occupied as a residence served by that entrance on that story shall be Type B units.
  1. Where the slopes of the undisturbed site measured between the planned entrance and all vehicular or pedestrian arrival points within 50 feet (15 240 mm) of the planned entrance are 10 percent or less, and
  2. Where the slopes of the planned finished grade measured between the entrance and all vehicular or pedestrian arrival points within 50 feet (15 240 mm) of the planned entrance are 10 percent or less.

Where no such arrival points are within 50 feet (15 240 mm) of the entrance, the closest arrival point shall be used unless that arrival point serves the story required by Section 1107.7.1.1.

A multistory dwelling or sleeping unit which is not provided with elevator service is not required to be a Type B unit. Where a multistory unit is provided with external elevator service to only one floor, the floor provided with elevator service shall be the primary entry to the unit, shall comply with the requirements for a Type B unit and a toilet facility shall be provided on that floor.
Where elevator service in the building provides an accessible route only to the lowest story containing dwelling or sleeping units intended to be occupied as a residence, only the units on that story which are intended to be occupied as a residence are required to be Type B units.
On a site with multiple nonelevator buildings, the number of units required by Section 1107.7.1 to be Type B units is permitted to be reduced to a percentage which is equal to the percentage of the entire site having grades, prior to development, which are less than 10 percent, provided that all of the following conditions are met:
  1. Not less than 20 percent of the units required by Section 1107.7.1 on the site are Type B units;
  2. Units required by Section 1107.7.1, where the slope between the building entrance serving the units on that story and a pedestrian or vehicular arrival point is no greater than 8.33 percent, are Type B units;
  3. Units required by Section 1107.7.1, where an elevated walkway is planned between a building entrance serving the units on that story and a pedestrian or vehicular arrival point and the slope between them is 10 percent or less are Type B units; and
  4. Units served by an elevator in accordance with Section 1107.7.3 are Type B units.
The required number of Type A units and Type B units shall not apply to a site where the required elevation of the lowest floor or the lowest horizontal structural building members of nonelevator buildings are at or above the design flood elevation resulting in:
  1. A difference in elevation between the minimum required floor elevation at the primary entrances and vehicular and pedestrian arrival points within 50 feet (15 240 mm) exceeding 30 inches (762 mm), and
  2. A slope exceeding 10 percent between the minimum required floor elevation at the primary entrances and vehicular and pedestrian arrival points within 50 feet (15 240 mm).
Where no such arrival points are within 50 feet (15 240 mm) of the primary entrances, the closest arrival points shall be used.
In addition to the other requirements of this chapter, the requirements of Sections 1108.2 through 1108.4 shall apply to specific occupancies.

1108.2 Assembly Area Seating

AMENDMENT
This section has been amended at the state or city level.
A building, room or space used for assembly purposes with fixed seating shall comply with Sections 1108.2.1 through 1108.2.5. Lawn seating which is provided accessory to an affected building shall comply with Section 1108.2.6. Assistive listening systems shall comply with Section 1108.2.7. Performance areas viewed from assembly seating areas shall comply with Section 1108.2.8. Dining areas shall comply with Section 1108.2.9.
If a service or facility is provided in an area that is not accessible, the same service or facility shall be provided on an accessible level and shall be accessible.
In theaters, bleachers, grandstands, stadiums, arenas and other fixed seating assembly areas, accessible wheelchair spaces shall be provided in accordance with Sections 1108.2.2.1 through 1108.2.2.4.
Wheelchair spaces shall be provided in accordance with Table 1108.2.2.1.

TABLE 1108.2.2.1
ACCESSIBLE WHEELCHAIR SPACES
CAPACITY OF
SEATING IN
ASSEMBLY AREAS
MINIMUM REQUIRED NUMBER OF
WHEELCHAIR SPACES
4 to 25 1
26 to 50 2
51 to 100 4
101 to 300 5
301 to 500 6
501 to 5,000 6, plus 1 for each 150, or fraction thereof,
between 501 through 5,000
5,001 and over 36 plus 1 for each 200, or fraction thereof,
over 5,000
In each luxury box, club box, and suite within arenas, stadiums and grandstands, wheelchair spaces shall be provided in accordance with Table 1108.2.2.1.
In boxes other than those required to comply with Section 1108.2.2.2, the total number of wheelchair spaces provided shall be determined in accordance with Table 1108.2.2.1. Wheelchair spaces shall be located in not less than 20 percent of all boxes provided.
At least one wheelchair space shall be provided in team or player seating areas serving areas of sport activity.
Exception: Wheelchair spaces shall not be required in team or player seating areas serving bowling lanes that are not required to be located on an accessible route in accordance with Section 1109.15.4.1.
At least one companion seat shall be provided for each wheelchair space required by Sections 1108.2.2.1 through 1108.2.2.3.
In multilevel assembly seating areas, wheelchair spaces shall be provided on the main floor level and on one of each two additional floor or mezzanine levels. Wheelchair spaces shall be provided in each luxury box, club box and suite within assembly facilities.
Exceptions:
  1. In multilevel assembly seating areas utilized for worship services where the second floor or mezzanine level contains 25 percent or less of the total seating capacity, wheelchair spaces shall be permitted to all be located on the main level.
  2. In multilevel assembly seating areas where the second floor or mezzanine level provides 25 percent or less of the total seating capacity and 300 or fewer seats, all wheelchair spaces shall be permitted to be located on the main level.
  3. Wheelchair spaces in team or player seating serving areas of sport activity are not required to be dispersed.
At least 5 percent, but not less than one, of the total number of aisle seats provided shall be designated aisle seats and shall be the aisle seats located closest to accessible routes.
Exception: Designated aisle seats are not required in team or player seating serving areas of sport activity.
Lawn seating areas and exterior overflow seating areas, where fixed seats are not provided, shall connect to an accessible route.
Each building, room or space used for assembly purposes where audible communications are integral to the use of the space shall have an assistive listening system.
Exception: Other than in courtrooms, an assistive listening system is not required where there is no audio amplification system.
Receivers shall be provided for assistive listening systems in accordance with Table 1108.2.7.1.
Exceptions:
  1. Where a building contains more than one room or space used for assembly purposes, the total number of required receivers shall be permitted to be calculated according to the total number of seats in the building, provided that all receivers are usable with all systems and if the rooms or spaces used for assembly purposes required to provide assistive listening are under one management.
  2. Where all seats in a building, room or space used for assembly purposes are served by an induction loop assistive listening system, the minimum number of receivers required by Table 1108.2.7.1 to be hearing-aid compatible shall not be required.
TABLE 1108.2.7.1
RECEIVERS FOR ASSISTIVE LISTENING SYSTEMS
CAPACITY OF SEATING
IN ASSEMBLY AREAS
MINIMUM REQUIRED
NUMBER OF RECEIVERS
MINIMUM NUMBER OF RECEIVERS TO BE
HEARING-AID COMPATIBLE
50 or less 2 2
51 to 200 2, plus 1 per 25 seats over 50 seats* 2
201 to 500 2, plus 1 per 25 seats over 50 seats* 1 per 4 receivers*
501 to 1,000 20, plus 1 per 33 seats over 500 seats* 1 per 4 receivers*
1,001 to 2,000 35, plus 1 per 50 seats over 1,000 seats* 1 per 4 receivers*
Over 2,000 55, plus 1 per 100 seats over 2,000 seats* 1 per 4 receivers*

Note: * = or fraction thereof
Where ticket windows are provided in stadiums and arenas, at least one window at each location shall have an assistive listening system.
Where stadiums, arenas and grandstands have 15,000 fixed seats or more and provide audible public announcements, they shall also provide prerecorded or real-time captions of those audible public announcements.
An accessible route shall directly connect the performance area to the assembly seating area where a circulation path directly connects a performance area to an assembly seating area. An accessible route shall be provided from performance areas to ancillary areas or facilities used by performers.

1108.2.9 Dining and Drinking Areas

AMENDMENT
This section has been amended at the state or city level.
In dining and drinking areas, all interior and exterior floor areas shall be accessible.

Exceptions:
  1. An accessible route between accessible levels and stories above or below is not required where permitted by Section 1104.4, Exception 1.
  2. In sports facilities, tiered dining areas providing seating required to be accessible shall be required to have accessible routes serving at least 25 percent of the dining area, provided that accessible routes serve accessible seating and where each tier is provided with the same services.
  3. Employee-only work areas shall comply with Sections 1103.2.3 and 1104.3.1.

1108.2.9.1 Dining Surfaces

AMENDMENT
This section has been amended at the state or city level.
Where dining surfaces for the consumption of food or drink are provided, at least 5 percent, but not less than one, of the dining surfaces for the seating and standing spaces shall be accessible and be distributed throughout the facility and located on a level accessed by an accessible route. Where a bar or counter is provided for consumption of food or drink exceeding 34 inches (864 mm) in height, a structurally integrated portion of the main bar or counter shall be provided, a minimum 60 inches (1524 mm) long or 5 percent of the length, whichever is greater, and 28 to 34 inches (711 mm to 864 mm) high. Clear floor space for forward approach and knee and toe clearance shall be provided.

     Flip-up counters, adjacent tables and similar devices shall not be permitted to satisfy this requirement.
Self-service storage facilities shall provide accessible individual self-storage spaces in accordance with Table 1108.3.

TABLE 1108.3
ACCESSIBLE SELF-SERVICE STORAGE FACILITIES
TOTAL SPACES IN
FACILITY
MINIMUM NUMBER OF REQUIRED
ACCESSIBLE SPACES
1 to 200 5%, but not less than 1
Over 200 10, plus 2% of total number of units over 200
Accessible individual self-service storage spaces shall be dispersed throughout the various classes of spaces provided. Where more classes of spaces are provided than the number of required accessible spaces, the number of accessible spaces shall not be required to exceed that required by Table 1108.3. Accessible spaces are permitted to be dispersed in a single building of a multibuilding facility.
Judicial facilities shall comply with Sections 1108.4.1 through 1108.4.3.
Each courtroom shall be accessible and comply with Sections 1108.4.1.1 through 1108.4.1.5.
A wheelchair space shall be provided within the jury box.
Exception: Adjacent companion seating is not required.
Wheelchair spaces shall be provided in accordance with Table 1108.2.2.1. Designated aisle seats shall be provided in accordance with Section 1108.2.5.
An assistive listening system must be provided. Receivers shall be provided for the assistive listening system in accordance with Section 1108.2.7.1.
The judge's bench, clerk's station, bailiff's station, deputy clerk's station and court reporter's station shall be located on an accessible route. The vertical access to elevated employee work stations within a courtroom is not required at the time of initial construction, provided a ramp, lift or elevator can be installed without requiring reconfiguration or extension of the courtroom or extension of the electrical system.
The litigant's and counsel stations, including the lectern, shall be accessible.
Central holding cells and court-floor holding cells shall comply with Sections 1108.4.2.1 and 1108.4.2.2.
Where separate central holding cells are provided for adult males, juvenile males, adult females or juvenile females, one of each type shall be accessible. Where central holding cells are provided and are not separated by age or sex, at least one accessible cell shall be provided.
Where separate court-floor holding cells are provided for adult males, juvenile males, adult females or juvenile females, each courtroom shall be served by one accessible cell of each type. Where court-floor holding cells are provided and are not separated by age or sex, courtrooms shall be served by at least one accessible cell. Accessible cells shall be permitted to serve more than one courtroom.
Visiting areas shall comply with Sections 1108.4.3.1 and 1108.4.3.2.
At least 5 percent but no fewer than one of the cubicles shall be accessible on both the visitor and detainee sides. Where counters are provided, at least one shall be accessible on both the visitor and detainee sides.
Exception: This requirement shall not apply to the detainee side of cubicles or counters at noncontact visiting areas not serving accessible holding cells.
Where solid partitions or security glazing separate visitors from detainees, at least one of each type of cubicle or counter partition shall be accessible.
Accessible building features and facilities shall be provided in accordance with Sections 1109.2 through 1109.15.
Exception: Accessible units, Type A units and Type B units shall comply with Chapter 10 of ICC A117.1.
Each toilet room and bathing room shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing rooms provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing room shall be accessible.
Exceptions:
  1. In toilet rooms or bathing rooms accessed only through a private office, not for common or public use and intended for use by a single occupant, any of the following alternatives are allowed:
    1. Doors are permitted to swing into the clear floor space, provided the door swing can be reversed to meet the requirements in ICC A117.1;
    2. The height requirements for the water closet in ICC A117.1 are not applicable;
    3. Grab bars are not required to be installed in a toilet room, provided that reinforcement has been installed in the walls and located so as to permit the installation of such grab bars; and
    4. The requirement for height, knee and toe clearance shall not apply to a lavatory.
  2. This section is not applicable to toilet and bathing rooms that serve dwelling units or sleeping units that are not required to be accessible by Section 1107.
  3. Where multiple single-user toilet rooms or bathing rooms are clustered at a single location, at least 50 percent but not less than one room for each use at each cluster shall be accessible.
  4. Where no more than one urinal is provided in a toilet room or bathing room, the urinal is not required to be accessible.
  5. Toilet rooms that are part of critical care or intensive care patient sleeping rooms are not required to be accessible.
  6. Where toilet facilities are primarily for children's use, required accessible water closets, toilet compartments and lavatories shall be permitted to comply with the children's provisions of ICC A117.1.
In assembly and mercantile occupancies, an accessible family or assisted-use toilet room shall be provided where an aggregate of six or more male and female water closets is required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the family or assisted-use toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible family or assisted-use bathing room shall be provided. Fixtures located within family or assisted-use toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy.
Exception: Where each separate-sex bathing room has only one shower or bathtub fixture, a family or assisted-use bathing room is not required.
Family or assisted-use toilet and bathing rooms shall comply with Sections 1109.2.1.2 through 1109.2.1.7.
Family or assisted-use toilet rooms shall include only one water closet and only one lavatory. A family or assisted-use bathing room in accordance with Section 1109.2.1.3 shall be considered a family or assisted-use toilet room.
Exception: A urinal is permitted to be provided in addition to the water closet in a family or assisted-use toilet room.
Family or assisted-use bathing rooms shall include only one shower or bathtub fixture. Family or assisted-use bathing rooms shall also include one water closet and one lavatory. Where storage facilities are provided for separate-sex bathing rooms, accessible storage facilities shall be provided for family or assisted-use bathing rooms.
Family or assisted-use toilet and bathing rooms shall be located on an accessible route. Family or assisted-use toilet rooms shall be located not more than one story above or below separate-sex toilet rooms. The accessible route from any separate-sex toilet room to a family or assisted-use toilet room shall not exceed 500 feet (152 m).
In passenger transportation facilities and airports, the accessible route from separate-sex toilet rooms to a family or assisted-use toilet room shall not pass through security checkpoints.
Where doors swing into a family or assisted-use toilet or bathing room, a clear floor space not less than 30 inches by 48 inches (762 mm by 1219 mm) shall be provided, within the room, beyond the area of the door swing.
Doors to family or assisted-use toilet and bathing rooms shall be securable from within the room.
Where water closet compartments are provided in a toilet room or bathing room, at least one wheelchair-accessible compartment shall be provided. Where the combined total water closet compartments and urinals provided in a toilet room or bathing room is six or more, at least one ambulatory-accessible water closet compartment shall be provided in addition to the wheelchair-accessible compartment.
Where lavatories are provided, at least 5 percent, but not less than one, shall be accessible. Where the total lavatories provided in a toilet room or bathing facility is six or more, at least one lavatory with enhanced reach ranges shall be provided.
Where sinks are provided, at least 5 percent but not less than one provided in accessible spaces shall be accessible.
Exception: Mop or service sinks are not required to be accessible.
Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible.
Where drinking fountains are provided on an exterior site, on a floor or within a secured area, the drinking fountains shall be provided in accordance with Sections 1109.5.1 and 1109.5.2.
No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.
Exceptions:
  1. A single drinking fountain that complies with the requirements for people who use a wheelchair and standing persons shall be permitted to be substituted for two separate drinking fountains.
  2. Where drinking fountains are primarily for children's use, drinking fountains for people using wheelchairs shall be permitted to comply with the children's provisions in ICC A117.1 and drinking fountains for standing children shall be permitted to provide the spout at 30 inches (762 mm) minimum above the floor.
Where more than the minimum number of drinking fountains specified in Section 1109.5.1 are provided, 50 percent of the total number of drinking fountains provided shall comply with the requirements for persons who use a wheelchair and 50 percent of the total number of drinking fountains provided shall comply with the requirements for standing persons.
Exceptions:
  1. Where 50 percent of the drinking fountains yields a fraction, 50 percent shall be permitted to be rounded up or down, provided that the total number of drinking fountains complying with this section equals 100 percent of the drinking fountains.
  2. Where drinking fountains are primarily for children's use, drinking fountains for people using wheelchairs shall be permitted to comply with the children's provisions in ICC A117.1 and drinking fountains for standing children shall be permitted to provide the spout at 30 inches (762 mm) minimum above the floor.
Where provided, saunas and steam rooms shall be accessible.
Exception: Where saunas or steam rooms are clustered at a single location, at least 5 percent of the saunas and steam rooms, but not less than one, of each type in each cluster shall be accessible.

1109.7 Elevators

ILLUSTRATION
Passenger elevators on an accessible route shall be accessible and comply with Chapter 30.

1109.8 Lifts

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Platform (wheelchair) lifts are permitted to be a part of a required accessible route in new construction where indicated in Items 1 through 10. Platform (wheelchair) lifts shall be installed in accordance with the Oregon Elevator Specialty Code.
  1. An accessible route to a performing area and speaker platforms in Group A occupancies.
  2. An accessible route to wheelchair spaces required to comply with the wheelchair space dispersion requirements of Sections 1108.2.2 through 1108.2.6.
  3. An accessible route to spaces that are not open to the general public with an occupant load of not more than five.
  4. An accessible route within a dwelling or sleeping unit.
  5. An accessible route to wheelchair seating spaces located in outdoor dining terraces in Group A-5 occupancies where the means of egress from the dining terraces to a public way are open to the outdoors.
  6. An accessible route to jury boxes and witness stands; raised courtroom stations including judges' benches, clerks' stations, bailiffs' stations, deputy clerks' stations and court reporters' stations; and to depressed areas such as the well of the court.
  7. An accessible route to load and unload areas serving amusement rides.
  8. An accessible route to play components or soft contained play structures.
  9. An accessible route to team or player seating areas serving areas of sport activity.
  10. An accessible route where existing exterior site constraints make use of a ramp or elevator infeasible.
Where fixed or built-in storage elements such as cabinets, coat hooks, shelves, medicine cabinets, lockers, closets and drawers are provided in required accessible spaces, at least 5 percent, but not less than one of each type shall be accessible.
Accessible facilities and spaces shall be provided with the same storage elements as provided in the similar nonaccessible facilities and spaces.
Self-service shelves and display units shall be located on an accessible route. Such shelving and display units shall not be required to comply with reach-range provisions.
Passenger transit platform edges bordering a drop-off and not protected by platform screens or guards shall have a detectable warning.
Exception: Detectable warnings are not required at bus stops.

1109.11 Seating at Tables, Counters and Work Surfaces

AMENDMENT
This section has been amended at the state or city level.
Where seating or standing space at fixed or built-in tables, counters or work surfaces is provided in accessible spaces, at least 5 percent of the seating and standing spaces, but not less than one, shall be accessible. In Group I-3 occupancy visiting areas at least 5 percent, but not less than one, cubicle or counter shall be accessible on both the visitor and detainee sides.
Exceptions:
  1. Check-writing surfaces at check-out aisles not required to comply with Section 1109.11.2 are not required to be accessible.
  2. In Group I-3 occupancies, the counter or cubicle on the detainee side is not required to be accessible at noncontact visiting areas or in areas not serving accessible holding cells or sleeping units.
Accessible fixed or built-in seating at tables, counters or work surfaces shall be distributed throughout the space or facility containing such elements and located on a level accessed by an accessible route.
Service facilities shall provide for accessible features in accordance with Sections 1109.12.1 through 1109.12.5.
Where dressing rooms, fitting rooms or locker rooms are provided, at least 5 percent, but not less than one, of each type of use in each cluster provided shall be accessible.
Where check-out aisles are provided, accessible check-out aisles shall be provided in accordance with Table 1109.12.2. Where check-out aisles serve different functions, at least one accessible check-out aisle shall be provided for each function. Where check-out aisles serve different functions, accessible check-out aisles shall be provided in accordance with Table 1109.12.2 for each function. Where check-out aisles are dispersed throughout the building or facility, accessible check-out aisles shall also be dispersed. Traffic control devices, security devices and turnstiles located in accessible check-out aisles or lanes shall be accessible.

TABLE 1109.12.2
ACCESSIBLE CHECK-OUT AISLES

TOTAL CHECK-OUT AISLES OF
EACH FUNCTION
MINIMUM NUMBER OF
ACCESSIBLE CHECK-OUT AISLES
OF EACH FUNCTION
1 to 41
5 to 82
9 to 153
Over 153, plus 20% of additional aisles
Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Food service lines shall be accessible. Where self-service shelves are provided, at least 50 percent, but not less than one, of each type provided shall be accessible.
Queue and waiting lines servicing accessible counters or check-out aisles shall be accessible.
Controls, operating mechanisms and hardware intended for operation by the occupant, including switches that control lighting and ventilation and electrical convenience outlets, in accessible spaces, along accessible routes or as parts of accessible elements shall be accessible.
Exceptions:
  1. Operable parts that are intended for use only by service or maintenance personnel shall not be required to be accessible.
  2. Electrical or communication receptacles serving a dedicated use shall not be required to be accessible.
  3. Where two or more outlets are provided in a kitchen above a length of counter top that is uninterrupted by a sink or appliance, one outlet shall not be required to be accessible.
  4. Floor electrical receptacles shall not be required to be accessible.
  5. HVAC diffusers shall not be required to be accessible.
  6. Except for light switches, where redundant controls are provided for a single element, one control in each space shall not be required to be accessible.
  7. Access doors or gates in barrier walls and fences protecting pools, spas and hot tubs shall be permitted to have operable parts of the release of latch on self-latching devices at 54 inches (1370 mm) maximum and 48 inches minimum above the finished floor or ground, provided the self-latching devices are not also self-locking devices, operated by means of a key, electronic opener, or integral combination lock.
Where operable windows are provided in rooms that are required to be accessible in accordance with Sections 1107.5.1.1, 1107.5.2.1, 1107.5.3.1, 1107.5.4, 1107.6.1.1, 1107.6.2.1.1, 1107.6.2.2.1 and 1107.6.4.1, at least one window in each room shall be accessible and each required operable window shall be accessible.
Exception: Accessible windows are not required in bathrooms and kitchens.

1109.14 Fuel-Dispensing Systems

AMENDMENT
This section has been amended at the state or city level.

1109.14 Reserved

AMENDMENT
This section has been amended at the state or city level.
Recreational and sports facilities shall be provided with accessible features in accordance with Sections 1109.15.1 through 1109.15.4.
In Group R-2 and R-3 occupancies where recreational facilities are provided serving a single building containing Type A units or Type B units, 25 percent, but not less than one, of each type of recreational facility shall be accessible. Every recreational facility of each type on a site shall be considered to determine the total number of each type that is required to be accessible.
In Group R-2 and R-3 occupancies on a single site where multiple buildings containing Type A units or Type B units are served by recreational facilities, 25 percent, but not less than one, of each type of recreational facility serving each building shall be accessible. The total number of each type of recreational facility that is required to be accessible shall be determined by considering every recreational facility of each type serving each building on the site.
All recreational and sports facilities not falling within the purview of Section 1109.15.1 or 1109.15.2 shall be accessible.
Recreational and sports facilities required to be accessible shall be exempt from this chapter to the extent specified in this section.
An accessible route shall be provided to at least 5 percent, but no less than one, of each type of bowling lane.
In court sports, at least one accessible route shall directly connect both sides of the court.
Raised boxing or wrestling rings are not required to be accessible.
Raised structures used solely for refereeing, judging or scoring a sport are not required to be accessible.
Raised diving boards and diving platforms are not required to be accessible.

Section 1110 Signage

ILLUSTRATION
Required accessible elements shall be identified by the International Symbol of Accessibility at the following locations:
  1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less.
  2. Accessible passenger loading zones.
  3. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a single location.
  4. Accessible entrances where not all entrances are accessible.
  5. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification.
  6. Family or assisted-use toilet and bathing rooms.
  7. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
  8. Accessible areas of refuge in accordance with Section 1007.9.
  9. Exterior areas for assisted rescue in accordance with Section 1007.9.
Directional signage indicating the route to the nearest like accessible element shall be provided at the following locations. These directional signs shall include the International Symbol of Accessibility:
  1. Inaccessible building entrances.
  2. Inaccessible public toilets and bathing facilities.
  3. Elevators not serving an accessible route.
  4. At each separate-sex toilet and bathing room indicating the location of the nearest family or assisted-use toilet or bathing room where provided in accordance with Section 1109.2.1.
  5. At exits and exit stairways serving a required accessible space, but not providing an approved accessible means of egress, signage shall be provided in accordance with Section 1007.10.
Signage indicating special accessibility provisions shall be provided as shown:
  1. Each assembly area required to comply with Section 1108.2.7 shall provide a sign notifying patrons of the availability of assistive listening systems.
    Exception: Where ticket offices or windows are provided, signs are not required at each assembly area provided that signs are displayed at each ticket office or window informing patrons of the availability of assistive listening systems.
  2. At each door to an area of refuge, an exterior area for assisted rescue, an egress stairway, exit passageway and exit discharge, signage shall be provided in accordance with Section 1011.4.
  3. At areas of refuge, signage shall be provided in accordance with Section 1007.11.
  4. At exterior areas for assisted rescue, signage shall be provided in accordance with Section 1007.11.
  5. At two-way communication systems, signage shall be provided in accordance with Section 1007.8.2.
  6. Within interior exit stairways and ramps, signage shall be provided in accordance with Section 1022.9.
Where provided in the locations in Sections 1110.4.1 and 1110.4.2, variable message signs (VMS) shall comply with the VMS requirements of ICC A117.1.
Where provided in transportation facilities, variable message signs conveying transportation-related information shall comply with Section 1110.4.
Where provided in buildings that are designated as emergency shelters, variable message signs conveying emergency-related information shall comply with Section 1110.4.
Exception: Where equivalent information is provided in an audible manner, VMS signs are not required to comply with ICC A117.1.

Section 1111 Clustered Mailboxes

AMENDMENT
This section has been amended at the state or city level.

1111.1 Accessible Routes

AMENDMENT
This section has been amended at the state or city level.
Clustered mailboxes on a site with an affected building shall be located on an accessible route in conformance with ICC A117.1, Sections 402 and 403.

1111.2 Within a Site

AMENDMENT
This section has been amended at the state or city level.
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.

1111.3 Site Arrival Points

AMENDMENT
This section has been amended at the state or city level.
Accessible routes within the site shall be provided from public transportation stops; accessible parking; accessible passenger loading zones; and public streets or sidewalks to the accessible facilities served.

1111.3.1 Location

AMENDMENT
This section has been amended at the state or city level.
Location of clustered mailboxes shall be coordinated with the postal authority having jurisdiction.

1111.3.2 Access to Pedestrian Circulation

AMENDMENT
This section has been amended at the state or city level.
Where an improved walking surface such as a sidewalk is located within 50 feet (15 240 mm) of the pad on which a clustered mailbox unit is located, at least one accessible route shall connect the improved walking surface to the clustered mailbox pad. At least one pedestrian access route shall be provided within 50 feet (15 240 mm) from the vehicular way to the pad on which a clustered mailbox unit is located.

1111.4 Ramps, Curb Ramps and Barriers

AMENDMENT
This section has been amended at the state or city level.
Ramps along an accessible route to clustered mailboxes shall be in conformance with ICC A117.1, Sections 405 and 406.

1111.4.1 Curb Ramps

AMENDMENT
This section has been amended at the state or city level.
Where the accessible route to clustered mailboxes is obstructed by curbs, curb ramps shall be provided within 50 feet (15 240 mm) of the clustered mailbox location.

1111.4.2 Other Barriers

AMENDMENT
This section has been amended at the state or city level.
Where barriers such as grass median, landscaping or loose gravel between the edge of the traveled surface and clustered mailbox pads occur, a solid surfaced access shall be provided within 50 feet (15 240 mm) of the clustered mailbox location.

1111.4.3 Landings

AMENDMENT
This section has been amended at the state or city level.
All landings along an accessible route to clustered mailboxes shall conform to ICC A117.1, Section 405.7.

1111.4.4 Edge Protection

AMENDMENT
This section has been amended at the state or city level.
Edge protection along an accessible route to clustered mailboxes shall comply with ICC A117.1, Section 405.9.

1111.5 Changes in Level

AMENDMENT
This section has been amended at the state or city level.
Changes in level in the traveled surface on an accessible route to clustered mailboxes shall comply with ICC A117.1, Section 303.

1111.6 Surfaces

AMENDMENT
This section has been amended at the state or city level.
Traveled surfaces shall be stable, firm and slip resistant, and shall comply with A117.1, Sections 302.1 and 302.3. Changes in level in floor surfaces shall comply with ICC A117.1, Section 303.

1111.7 Turning Space at Clustered Mailbox Units

AMENDMENT
This section has been amended at the state or city level.
At least one turning space shall be provided at the front of each clustered mailbox unit. The turning space shall conform to ICC A117.1, Section 304 and shall be either:
  1. A circular space having a 72-inch (1829 mm) minimum diameter; or
  2. A T-shaped space within a 72-inch (1829 mm) minimum square, with arms and base a minimum of 48 inches (1219 mm) in width. Each arm of the T shall be clear of obstructions 24 inches (610 mm) minimum in each direction, and the base shall be clear of obstructions of 36 inches (914 mm) minimum. The turning space shall be permitted to include knee and toe clearances complying with Section 306 only at the end of either the base or one arm.

1111.8 Protruding Objects

AMENDMENT
This section has been amended at the state or city level.
Protruding objects along the accessible route to clustered mailboxes shall conform to Section 307 of ICC A117.1.

1111.9 Clear Access Space

AMENDMENT
This section has been amended at the state or city level.
Clear access space conforming to ICC A117.1, Section 305 shall be provided to each of the mailboxes at the clustered mailbox location. The clear access space and the turning space may overlap.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING