N1101.1 Scope

AMENDMENT
This section has been amended at the state or city level.
This chapter regulates the energy efficiency for the design and construction of buildings regulated by this code.
Exception: Portions of the building envelope that do not enclose conditioned space.

N1101.2 (R101.3) Intent

AMENDMENT
This section has been amended at the state or city level.

N1101.3 (R101.5.1) Compliance Materials

AMENDMENT
This section has been amended at the state or city level.

N1101.4 (R102.1.1) Above Code Programs

AMENDMENT
This section has been amended at the state or city level.
The building official or other authority having jurisdiction shall be permitted to deem a national, state, or local energy-efficiency program to exceed the energy efficiency required by this chapter. Buildings approved in writing by such an energy-efficiency program shall be considered in compliance with this chapter.

N1101.5 (R103.2) Information on Construction Documents

AMENDMENT
This section has been amended at the state or city level.

N1101.5.1 (R103.2.1) Thermal Envelope Depiction

AMENDMENT
This section has been amended at the state or city level.

N1101.6 (R202) Defined Terms

AMENDMENT
This section has been amended at the state or city level.

N1101.7 (R301.1) Climate Zones

AMENDMENT
This section has been amended at the state or city level.




FIGURE N1101.7 CLIMATE ZONES

TABLE N1101.7 CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY

Key: A — Moist, B — Dry, C — Marine. Absence of moisture designation indicates moisture regime is irrelevant.
Asterisk (*) indicates a warm-humid location.


US STATES

OKLAHOMA
3A Adair 3A Le Flore
3A Alfalfa 3A Lincoln
3A Atoka 3A Logan
4B Beaver 3A Love
3A Beckham 3A Major
3A Blaine 3A Marshall
3A Bryan 3A Mayes
3A Caddo 3A McClain
3A Canadian 3A McCurtain
3A Carter 3A McIntosh
3A Cherokee 3A Murray
3A Choctaw 3A Muskogee
4B Cimarron 3A Noble
3A Cleveland 3A Nowata
3A Coal 3A Okfuskee
3A Comanche 3A Oklahoma
3A Cotton 3A Okmulgee
3A Craig 3A Osage
3A Creek 3A Ottawa
3A Custer 3A Pawnee
3A Delaware 3A Payne
3A Dewey 3A Pittsburg
3A Ellis 3A Pontotoc
3A Garfield 3A Pottawatomie
3A Garvin 3A Pushmataha
3A Grady 3A Roger Mills
3A Grant 3A Rogers
3A Greer 3A Seminole
3A Harmon 3A Sequoyah
3A Harper 3A Stephens
3A Haskell 4B Texas
3A Hughes 3A Tillman
3A Jackson 3A Tulsa
3A Jefferson 3A Wagoner
3A Johnston 3A Washington
3A Kay 3A Washita
3A Kingfisher 3A Woods
3A Kiowa 3A Woodward
3A Latimer

N1101.7.1 (R301.2) Warm Humid Counties

AMENDMENT
This section has been amended at the state or city level.
Warm humid counties are identified in Table N1101.7 by an asterisk.

N1101.7.2 (R301.3) International Climate Zones

AMENDMENT
This section has been amended at the state or city level.

N1101.8 (R301.4) Tropical Climate Zone

AMENDMENT
This section has been amended at the state or city level.

N1101.9 (R302.1) Interior Design Conditions

AMENDMENT
This section has been amended at the state or city level.

N1101.10 (R303.1) Identification

AMENDMENT
This section has been amended at the state or city level.
Materials, systems and equipment shall be identified in a manner that will allow a determination of compliance with the applicable provisions of this chapter.

N1101.10.1 (R303.1.1) Building Thermal Envelope Insulation

AMENDMENT
This section has been amended at the state or city level.
An R-value identification mark shall be applied by the manufacturer to each piece of building thermal envelope insulation 12 inches (305 mm) or more wide. Alternately, the insulation installers shall provide a certification listing the type, manufacturer and R-value of the insulation installed in each element of the building thermal envelope. For blown or sprayed insulation (fiberglass and cellulose), the initial installed thickness, settled thickness, settled R-value, installed density, coverage area and number of bags installed shall be listed on the certification. For sprayed polyurethane foam (SPF) insulation, the installed thickness of the area covered and R-value of installed thickness shall be listed on the certificate. The insulation installer shall sign, date and post the certificate in a conspicuous location on the job site.

N1101.10.1.1 (R303.1.1.1) Blown or Sprayed Roof/Ceiling Insulation

AMENDMENT
This section has been amended at the state or city level.
The thickness of blown-in or sprayed roof/ceiling insulation (fiberglass or cellulose) shall be written in inches (mm) on markers that are installed at least once for every 300 square feet (28 square meters) throughout the attic space. The markers shall be affixed to the trusses or joists and marked with a minimum initial installed thickness with numbers not less than of 1 inch (25 mm) high. Each marker shall face the attic access opening. Spray polyurethane foam thickness and installed R-value shall be listed on the certificate provided by the insulation installer.

N1101.10.2 (R303.1.2) Insulation Mark Installation

AMENDMENT
This section has been amended at the state or city level.
Insulating materials shall be installed such that the manufacturer's R-value mark is readily observable upon inspection.

N1101.10.3 (R303.1.3) Fenestration Product Rating

AMENDMENT
This section has been amended at the state or city level.
U-factors of fenestration products (windows, doors, and skylights) shall be determined in accordance with NFRC 100 by an accredited, independent laboratory, and labeled and certified by the manufacturer.

Products lacking such a labeled U-factor shall be assigned a default U-factor from Table N1101.10.3(1) or N1101.10.3(2). The solar heat gain coefficient (SHGC) of glazed fenestration products (windows, glazed doors and skylights) shall be determined in accordance with NFRC 200 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such a labeled SHGC shall be assigned a default SHGC from Table 1101.10.3(3).

TABLE N1101.10.3(1) DEFAULT GLAZED FENESTRATION U-FACTORS

FRAME TYPE SINGLE
PANE
DOUBLE
PANE
SKYLIGHT
Single Double
Metal 1.20 0.80 2.00 1.30
Metal with Thermal Break 1.10 0.65 1.90 1.10
Nonmetal or Metal Clad 0.95 0.55 1.75 1.05
Glazed Block 0.60


TABLE N1101.10.3(2) DEFAULT DOOR U-FACTORS

DOOR TYPE U-FACTOR
Uninsulated Metal 1.20
Insulated Metal 0.60
Wood 0.50
Insulated, nonmetal edge, max 45% glazing,
any glazing double pane
0.35


TABLE N1101.10.3(3) DEFAULT GLAZED FENESTRATION SHGC

SINGLE GLAZED DOUBLE GLAZED GLAZED
BLOCK
Clear Tinted Clear Tinted
SHGC 0.8 0.7 0.7 0.6 0.6

N1101.10.4 (R303.1.4) Insulation Product Rating

AMENDMENT
This section has been amended at the state or city level.
The thermal resistance (R-value) of insulation shall be determined in accordance with the CFR Title 16, Part 460 in units of h x square foot x Fahrenheit/BTU at a mean temperature of 75°F (24°C).

N1101.10.4.1 (R303.1.4.1) Insulated Siding

AMENDMENT
This section has been amended at the state or city level.

N1101.11 (R303.2) Installation

AMENDMENT
This section has been amended at the state or city level.
All materials, systems and equipment shall be installed in accordance with the manufacturer's instructions and the provisions of this code.

N1101.11.1 (R303.2.1) Protection of Exposed Foundation Insulation

AMENDMENT
This section has been amended at the state or city level.
Insulation applied to the exterior basement walls, crawlspace walls, and the perimeter of slab-on-grade floors shall have a rigid, opaque and weather-resistance protective covering to prevent the degradation of the insulation's thermal performance. The protective covering shall cover the exposed exterior insulation and extend not less than 6 inches (153 mm) below grade.

N1101.12 (R303.3) Maintenance Information

AMENDMENT
This section has been amended at the state or city level.

N1101.13 (R401.2) Compliance

AMENDMENT
This section has been amended at the state or city level.
Compliance shall be demonstrated by either meeting the requirements of the 2009 International Energy Conservation Code® or meeting the requirements of this chapter. Climate zones from figure N1101.7 or Table 1101.7 shall be used in determining the applicable requirements from this chapter.

N1101.13.1 (R401.2.1) Tropical Zone

AMENDMENT
This section has been amended at the state or city level.

N1101.14 (R401.3) Certificate (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
UpCodes note: This section has been renumbered in "Appendix W, Energy Efficiency" to become Section W101.1.

N1102.1 (R402.1) General (Prescriptive)

AMENDMENT
This section has been amended at the state or city level.

N1102.1.1 (R402.1.1) Vapor Retarder

AMENDMENT
This section has been amended at the state or city level.

N1102.1.2 (R402.1.2) Insulation and Fenestration Criteria

AMENDMENT
This section has been amended at the state or city level.
The building thermal envelope shall meet the requirements of Table N1102.1.2 based on the climate zone specified in Section N1101.7.

TABLE N1102.1.2 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa, m

CLIMATE
ZONE
FENESTRATION
U-FACTORb
SKYLIGHTb
U-FACTOR
GLAZED
FENESTRATION
SHGC
CEILING
R-VALUE
WOOD
FRAME WALL
R-VALUE
MASS
WALL
R-VALUEi
FLOOR
R-VALUE
BASEMENTc
WALL
R-VALUE
SLABd
R-VALUE
& DEPTH
CRAWL
SPACEc

WALL
R-VALUE
3 0.40i 0.55 0.35e, j 30 13 8/13 19 5/13f 0l 5/13
4 except
Marine
0.35 0.60 NR 38 13 5/10 19 10 /13 10, 2 ft 10/13

For SI: 1 foot = 304.8 mm.
  1. R-values are minimums. U-factors and SHGC are maximums, R-19 batts compressed into nominal 2 x 6 framing cavity such that the R-Value is reduced by R-1 or more shall be marked with the compressed R-Value in addition to the full thickness R-value.
  2. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.

  3. The first R-value applies to continuous insulation, the second to framing cavity insulation; either insulation meets the requirement.
  4. R-5 shall be added to the required slab edge R-values for heated slabs. Insulation depth shall be the depth of the footing or 2 feet, whichever is less, in zones 1 through 3 for heated slabs.
  5. There are no SHGC requirements in the Marine Zone.
  6. Basement wall insulation is not required in warm-humid locations as defined by Figure N1101.7 and Table N1101.7.
  7. Or insulation sufficient to fill the framing cavity, R-19 minimum.
  8. "13+5" means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25 percent or less of the exterior, R-5 sheathing is not required where structural sheathing is used. If structural sheathing covers more than 25 percent of the exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2.
  9. For impact-rated fenestration complying with Section R301.2.1.2, the maximum U-factor shall be 0.75 in zone 2 and 0.65 in zone 3.
  10. For impact-resistant fenestration complying with Section R301.2.1.2 of the 2015 International Residential Code®, the maximum SHGC shall be 0.40.
  11. The second R-value applies when more than half the insulation is on the interior.
  12. If foundation/slab insulation is used and slab ledge exists 1/2 inch insulation in Vertical position is allowed as thermal break between slab edge and foundation wall so that slab can still bear on horizontal ledge.
  13. In addition to the requirements in Table N1102.1.2, one of the following improvements are required:
    1. Fenestration U Factors to be 0.35.
    2. Wood Frame Wall R-Value to be R15.
    3. Slab R-Value and Depth to be 5.2 feet.
    4. Ceiling R-Value to be R38.
    5. Exception: If duct testing is performed and passed in accordance with N1103.3.2 by either the post-construction test or rough-in test no further upgrade is required from the values in Table N1102.1.2.
Insulation material used in layers, such as framing cavity insulation, or continuous insulation shall be summed to compute the corresponding component R-value. The manufacturer's settled R-value shall be used for blown insulation. Computed R-values shall not include an R-value for other building materials or air films. Where insulated siding is used for the purpose of complying with the continuous insulation requirements of Table N1102.1.2, the manufacturer's labeled R-value for insulated siding shall be reduced by R-0.6.

N1102.1.4 (R402.1.4) U-factor Alternative

AMENDMENT
This section has been amended at the state or city level.
An assembly with a U-factor equal to or less than that specified in Table N1102.1.4 shall be permitted as an alternative to the R-value in Table N1102.1.2.

TABLE N1102.1.4 EQUIVALENT U-FACTORSa

CLIMATE
ZONE
FENESTRATION
U-FACTOR
SKYLIGHT
U-FACTOR
CEILING
U-FACTOR
FRAME
WALL
U-FACTOR
MASS WALL
U-FACTORb
FLOOR
U-FACTOR
BASEMENT
WALL
U-FACTOR
CRAWL
SPACE WALL
U-FACTOR
3 0.50 0.65 0.035 0.082 0.141 0.047 0.091c 0.136
4 except Marine 0.35 0.60 0.030 0.082 0.141 0.047 0.059 0.065
  1. Nonfenestration U-factors shall be obtained from measurements, calculation or an approved source.
  2. When more than half the insulation is on the interior, the mass wall U-factors shall be a maximum of 0.17 in Zone 1, 0.14 in Zone 2, 0.12 in Zone 3, 0.10 in Zone 4 except Marine, and the same as the frame wall U-factor in marine Zone 4 and in Zones 5 through 8.
  3. Basement wall U-factor of 0.360 in warm-humid locations as defined by Figure N1101.7 and Table N1101.7.

N1102.1.5 (R402.1.5) Total UA Alternative

AMENDMENT
This section has been amended at the state or city level.
If the total building thermal envelope UA (sum of U-factor times assembly area) is less than or equal to the total UA resulting from using the U-factors in Table 1102.1.4 (multiplied by the same assembly area as in the proposed building), the building shall be considered in compliance with Table N1102.1.2. The UA calculation shall be done using a method consistent with the ASHRAE Handbook of Fundamentals and shall include the thermal bridging effects of framing materials. The SHGC requirements shall be met in addition to UA compliance.

N1102.2 (R402.2) Specific Insulation Requirements (Prescriptive)

AMENDMENT
This section has been amended at the state or city level.

N1102.2.1 (R402.2.1) Ceilings With Attic Spaces

AMENDMENT
This section has been amended at the state or city level.
Where Section N1102.1.2 would require R-38 in the ceiling, R-30 shall be deemed to satisfy the requirement for R-38 wherever the full height of uncompressed R-30 insulation extends over the wall top plate at the eaves. Similarly, R-38 shall be deemed to satisfy the requirement for R-49 insulation wherever the full height of uncompressed R-38 insulation extends over the wall top plate at the eaves. This reduction shall not apply to the U-factor alternative approach in Section R1102.1.4 and the total UA alternative in Section R1102.1.5.

N1102.2.2 (R402.2.2) Ceilings Without Attic Spaces

AMENDMENT
This section has been amended at the state or city level.
Where Section N1102.1.2 would require insulation levels above R-30 and the design of the roof/ceiling assembly does not allow sufficient space for the required insulation, the minimum required insulation for such roof/ceiling assemblies shall be R-30. This reduction of insulation from the requirements of Section N1102.1.2 shall be limited to 500 square feet (46 square meters) or 20 percent of the total insulated ceiling area, whichever is less. Where Section N1102.1 would require insulation level R-30 and the design of the roof/ceiling assembly does not allow sufficient space for the required insulation, the minimum required insulation for such roof/ceiling assemblies shall be R-19. This reduction of insulation from the requirements of Section N1102.1 shall be limited to 500 square feet (46 square meters) or 20 percent of the total insulated ceiling area, whichever is less.

N1102.2.3 (R402.2.3) Eave Baffle

AMENDMENT
This section has been amended at the state or city level.

N1102.2.4 (R402.2.4) Access Hatches and Doors

AMENDMENT
This section has been amended at the state or city level.
Access doors from conditioned spaces to unconditioned spaces such as attics and crawl spaces shall be weatherstripped and insulated to a level equivalent to the insulation on the surrounding surfaces. Access shall be provided to all equipment that prevents damaging or compressing the insulation. A wood-framed or equivalent baffle or retainer is required to be provided when loose-fill insulation is installed, the purpose of which is to prevent the loose-fill insulation from spilling into the living space when the attic is opened, and to provide a permanent means of maintaining the installed R-value of the loose-fill insulation.

N1102.2.5 (R402.2.5) Mass Walls

AMENDMENT
This section has been amended at the state or city level.
Mass walls for the purposes of this chapter shall be considered above-grade walls of concrete block, concrete, insulated concrete form (ICF), masonry cavity, brick (other than brick veneer), earth (adobe, compressed earth block, rammed earth) and solid timber/logs.

N1102.2.6 (R402.2.6) Steel-Frame Ceilings, Walls, and Floors

AMENDMENT
This section has been amended at the state or city level.
Steel-frame ceilings, walls, and floors shall meet the insulation requirements of Table N1102.2.6 or shall meet the U-factor requirements of Table N1102.1.4. The calculation of the U-factor for a steel-frame envelope assembly shall use a series-parallel path calculation method.
Exception: In climate zones 1 and 2, the continuous insulation requirements in the Table N1102.2.6 shall be permitted to be reduced to R-3 for steel frame wall assemblies with studs spaced at 24 inches (610 mm) on center.


TABLE N1102.2.6 STEEL-FRAME CEILING, WALL AND FLOOR INSULATION (R-VALUE)

WOOD FRAME
R-VALUE
REQUIREMENT
COLD-FORMED STEEL
EQUIVALENT R-VALUEa
Steel Truss Ceilingsb
R-30 R-38 or R-30 + 3 or R-26 + 5
R-38 R-49 or R-38 + 3
R-49 R-38 + 5
Steel Joist Ceilingsb
R-30 R-38 in 2 × 4 or 2 × 6 or 2 × 8 R-49
in any framing
R-38 R-49 in 2 × 4 or 2 × 6 or 2 × 8 or 2 × 10
Steel-Framed Wall
R-13 R-13 + 5 or R-15 +4 or R-21 + 3 or R-0 +10
R-19 R-13 +9 or R-19 +8 or R-25 +7
R-21 R-13 +10 or R-19 + 9 or R-25 + 8
Steel-Framed Wall
Steel Joist Floor
R-13 R-19 in 2 x 6, R-19 + R-6 in 2 x 8 or 2 x 10
R-19 R-19 + R-6 in 2 x 6, or R-19 + R-12 in 2 x 8 or 2 x 10

  1. Cavity insulation R-value is listed first, followed by continuous insulation R-value.
  2. Insulation exceeding the height of the framing shall cover the framing.

N1102.2.7 (R402.2.7) Walls With Partial Structural Sheathing

AMENDMENT
This section has been amended at the state or city level.

N1102.2.8 (R402.2.8) Floors

AMENDMENT
This section has been amended at the state or city level.
Floor framing cavity insulation shall be installed to maintain permanent contact with the underside of the subfloor decking.

N1102.2.9 (R402.2.9) Basement Walls

AMENDMENT
This section has been amended at the state or city level.
Exterior walls associated with conditioned basements shall be insulated from the top of the basement wall down to 10 feet (3048 mm) below grade or to the basement floor, whichever is less. Walls associated with unconditioned basements shall meet this requirement unless the floor overhead is insulated in accordance with Sections N1102.1.2 and N1102.2.8.

N1102.2.10 (R402.2.10) Slab-On-Grade Floors

AMENDMENT
This section has been amended at the state or city level.
Slab-on-grade floors with a floor surface less than 12 inches (305 mm) below grade shall be insulated in accordance with Table N1102.1.2. The insulation shall extend downward from the top of the slab on the outside or inside of the foundation wall. Insulation located below grade shall be extended the distance provided in Table N1102.1.2 by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. Insulation extending away from the building shall be protected by pavement or by not less than 10 inches (254 mm) of soil. The top edge of the insulation installed between the exterior wall and the edge of the interior slab shall be permitted to be cut at a 45 degree (0.79 rad) angle away from the exterior wall. Slab-edge insulation is not required in jurisdictions designated by the building official as having a very heavy termite infestation.

N1102.2.11 (R402.2.11) Crawl Space Walls

AMENDMENT
This section has been amended at the state or city level.
As an alternative to insulating floors over crawl spaces, crawl space walls shall be permitted to be insulated when the crawl space is not vented to the outside. Crawl space wall insulation shall be permanently fastened to the wall and extend downward from the floor to the finished grade level and then vertically and/or horizontally for at least an additional 24 inches (610 mm). Exposed earth in unvented crawl space foundations shall be covered with a continuous Class I vapor retarder in accordance with this code. All joints of the vapor retarder shall overlap by 6 inches (153 mm) and be sealed or taped. The edges of the vapor retarder shall extend not less than 6 inches (153 mm) up the stem wall and shall be attached to the stem wall.

N1102.2.12 (R402.2.12) Masonry Veneer

AMENDMENT
This section has been amended at the state or city level.
Insulation shall not be required on the horizontal portion of the foundation that supports a masonry veneer.

N1102.2.13 (R402.2.13) Thermally Isolated Sunroom Insulation

AMENDMENT
This section has been amended at the state or city level.
The minimum ceiling insulation R-values shall be R-19 in Zones 1 through 4 and R-24 in Zones 5 through 8. The minimum wall R-value shall be R-13 in all zones. New walls separating the sunroom from the conditioned space shall meet the building thermal envelope requirements.

N1102.3 (R402.3) Fenestration (Prescriptive)

AMENDMENT
This section has been amended at the state or city level.

N1102.3.1 (R402.3.1) U-factor

AMENDMENT
This section has been amended at the state or city level.
An area-weighted average of fenestration products shall be permitted to satisfy the U-factor requirements.

N1102.3.2 (R402.3.2) Glazed Fenestration SHGC

AMENDMENT
This section has been amended at the state or city level.
An area-weighted average of fenestration products more than 50-percent glazed shall be permitted to satisfy the solar heat gain coefficient (SHGC) requirements.

N1102.3.3 (R402.3.3) Glazed Fenestration Exemption

AMENDMENT
This section has been amended at the state or city level.
Up to 15 square feet (1.4 square meters) of glazed fenestration per dwelling unit shall be permitted to be exempt from U-factor and SHGC requirements in Section N1102.1.2. This exemption shall not apply to the U-factor alternative approach in N1102.1.4 and the total UA alternative approach in N1102.1.5.

N1102.3.4 (R402.3.4) Opaque Door Exemption

AMENDMENT
This section has been amended at the state or city level.
One side-hinged opaque door assembly up to 24 square feet (2.22 square meters) in area is exempted from the U-factor requirement in Section N1102.1.2. This exemption shall not apply to the U-factor alternative approach in Section N1102.1.4 and the total UA alternative in Section N1102.1.5.

N1102.3.5 (R402.3.5) Thermally Isolated Sunroom U-factor Fenestration

AMENDMENT
This section has been amended at the state or city level.
For zones 4 through 8, the maximum fenestration U-factor shall be 0.50 and the maximum skylight U-factor shall be 0.75. New windows and doors separating the sunroom from conditioned space shall meet the building thermal envelope requirements.

N1102.3.6 Replacement Fenestration

AMENDMENT
This section has been amended at the state or city level.
Where some or all of an existing fenestration unit is replaced with a new fenestration product, including sash and glazing, the replacement fenestration unit shall meet the applicable requirements for U-factor and solar heat gain coefficient (SHGC) in Table N1102.1.2.

N1102.4 (R402.4) Air Leakage (Mandatory)

AMENDMENT
This section has been amended at the state or city level.

N1102.4.1 (R402.4.1) Building Thermal Envelope

AMENDMENT
This section has been amended at the state or city level.
The building thermal envelope shall be durably sealed to limit infiltration. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. The following shall be caulked, gasketed, weather-stripped or otherwise sealed with an air barrier material, suitable film or solid material.
  1. All joints seams and penetrations.
  2. Site-built windows, doors and skylights.
  3. Openings between window and door assemblies and their respective jambs and framing.
  4. Utility penetrations.
  5. Dropped ceilings or chases adjacent to the thermal envelope.
  6. Knee walls.
  7. Walls and ceilings separating the garage from conditioned spaces.
  8. Behind tubs and showers on exterior walls.
  9. Common walls between dwelling units.
  10. Attic access openings.
  11. Rim joists junction.
  12. Other sources of infiltration.

N1102.4.1.1 (R402.4.1.1) Installation Air Sealing and Insulation

AMENDMENT
This section has been amended at the state or city level.
Building envelope air tightness and insulation installation shall be demonstrated to comply with one of the following options given by Sections N1102.4.1.2 or N1102.4.1.3.

TABLE N1102.4.1.1 (R402.4.1.1)
AIR BARRIER AND INSULATION INSTALLATION
COMPONENT CRITERIA
Air barrier and thermal barrier Exterior thermal envelope insulation for framed walls is installed in substantial contact and continuous alignment with the building envelope air barrier. Breaks or joints in the air barrier are filled or repaired. Air-permeable insulation is not used as a sealing material. Air-permeable insulation is inside of an air barrier.
Ceiling/attic Air barrier in any dropped ceiling/soffit substantially aligned with insulation and any gaps are sealed. Attic access (except unvented attic), knee wall door, or drop down door stair is sealed.
Walls Corners and headers are insulated. Junction of foundation and sill plate is sealed.
Windows and doors The space between window/door jambs and framing are sealed.
Rim joists Rim joists are insulated and include an air barrier.
Floors (including above garage and cantilevered floors) Insulation is installed to maintain permanent contact with the underside of subfloor decking. Air barrier is installed at any exposed edge of floor.
Crawl space walls Insulation is permanently attached to walls. Exposed earth in unvented crawl spaces is covered with a Class I vapor retarder with overlapping joints taped.
Shafts, penetrations Duct shafts, utility penetrations, knee walls and flue shafts opening to exterior or unconditioned space are sealed.
Narrow cavities Batts in narrow cavities are cut to fit, or narrow cavities are filled by sprayed/blown insulation.
Garage separation Air sealing is provided between the garage and
conditioned space.
Recessed lighting Recessed light fixtures are air tight, IC rated and sealed to the drywall.
Exception: Fixtures in conditioned space.
Plumbing and wiring Insulation is placed between outside and pipes. Batt insulation is cut to fit around wiring and plumbing or sprayed/blown insulation extends behind piping and wiring.
Shower/tub on exterior wall Showers and tubs on exterior walls have insulation and an air barrier separating them from the exterior wall.
Electrical/phone box on exterior
walls
Air barrier extends behind boxes or air-sealed boxes are installed.
Common Wall Air barrier is installed in common wall between dwelling units.
HVAC register boots HVAC register boots that penetrate building envelope are sealed to subfloor and drywall.
Fireplaces Fireplace walls include an air barrier.
  1. In addition, inspection of log walls shall be in accordance with the provisions of ICC 400.

N1102.4.1.2 (R402.4.1.2) Testing Option

AMENDMENT
This section has been amended at the state or city level.
Tested air leakage rate is less than 7 ACH when tested with a blower door at a pressure of 50 Pascals (0.007 psi). Testing shall occur after rough in and after installation of penetrations of the building envelope including penetrations for utilities, plumbing, electrical, ventilation and combustion appliances.

During testing:
  1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed;
  2. Dampers shall be closed, but not sealed; including exhaust, intake, makeup air, back draft and flu dampers;
  3. Interior doors shall be open;
  4. Exterior openings for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;
  5. Heating and cooling system(s) shall be turned off;
  6. HVAC ducts shall not be sealed; and
  7. Supply and return registers, shall not be sealed.

N1102.4.1.3 Visual Inspection

AMENDMENT
This section has been amended at the state or city level.
The items listed in Table N1102.4.1.1 applicable to the method of construction, are field verified. Where required by the code official, an approved party independent from the installer of the insulation or contractor, shall inspect the air barrier and insulation. Where no approved party inspects these items the air barrier components shall be viewed as a part of the frame inspection or insulation inspection by the Authority Having Jurisdiction.

N1102.4.2 (R402.4.2) Fireplaces

AMENDMENT
This section has been amended at the state or city level.
New wood-burning fireplaces shall have outdoor combustion air.

N1102.4.3 (R402.4.3) Fenestration Air Leakage

AMENDMENT
This section has been amended at the state or city level.
Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 L divided by s divided by square meters), and swinging doors no more than 0.5 cfm per square foot (2.5 L divided by s divided by square meters), when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site-built windows, skylights, and doors.

N1102.4.4 (R402.4.4) Rooms Containing Fuel-Burning Appliances

AMENDMENT
This section has been amended at the state or city level.

N1102.4.5 (R402.4.5) Recessed Lighting

AMENDMENT
This section has been amended at the state or city level.
Recessed luminaries installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned space. All recessed luminaries shall be IC-rated and labeled as meeting ASTM E 283 when tested at 1.57 psi (75 Pa) pressure differential with no more than 2.0 cfm (0.944 L/s) of air movement from the conditioned space to the ceiling cavity. All recessed luminaries shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling cover.

N1102.5 (R402.5) Maximum Fenestration U-factor and SHGC (Mandatory)

AMENDMENT
This section has been amended at the state or city level.

N1103.1 (R403.1) Controls (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
At least one thermostat shall be installed for each separate heating and cooling system.

N1103.1.1 (R403.1.1) Programmable Thermostat

AMENDMENT
This section has been amended at the state or city level.
Where the primary heating system is a forced air furnace, at least one thermostat per dwelling unit shall be capable of controlling the heating and cooling system on a daily schedule to maintain different temperature set points at different times of the day. This thermostat shall include the capability to set back or temporarily operate the system to maintain zone temperature down to 55 degrees Fahrenheit (13 degrees Celsius) or up to 85 degrees Fahrenheit (29 degrees Celsius). The thermostat shall initially be programmed with a heating temperature set point no higher than 70 degrees Fahrenheit (21 degrees Celsius) and a cooling temperature set point no lower than 78 degrees Fahrenheit (26 degrees Celsius).

N1103.1.2 (R403.1.2) Heat Pump Supplementary Heat (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Heat pumps having supplementary electric-resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.

N1103.2 (R403.2) Hot Water Boiler Outdoor Temperature Setback

AMENDMENT
This section has been amended at the state or city level.

N1103.3 (R403.3) Ducts

AMENDMENT
This section has been amended at the state or city level.

N1103.3.1 (R403.3.1) Insulation (Prescriptive)

AMENDMENT
This section has been amended at the state or city level.
Supply ducts in attics shall be insulated to a minimum of R-8. All other ducts shall be insulated to a minimum of R-6..
Exception: Ducts or portions thereof located completely inside the building thermal envelope.

N1103.3.2 (R403.3.2) Sealing (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Ducts, air handlers, filter boxes and building cavities used as ducts shall be sealed. Joints and seams shall comply with Section M1601.4. For duct systems with sheet metal plenums, Y's and supply boots, only liquid applied sealants complying with UL 181 BM (Mastic or similar) or equivalent method, shall be used to seal inner liners and start collars to plenum and any other seams in the system. Duct tightness shall be verified by one of the following:
  1. Post-construction test: Leakage to outdoors shall be less than or equal to 8 cfm (3.78 L/s) per 100 square feet (9.29 square meters) of conditioned floor area or a total leakage less than or equal to 12 cfm (5.66 L/s) per 100 square feet (9.29 square meters) of conditioned floor area when tested at a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler end closure. All register boots shall be taped or otherwise sealed during the test.
  2. Rough-in test: Total leakage shall be less than or equal to 6 cfm (2.83 L/s) per 100 square feet (9.29 square meters) of conditioned floor area when tested at a pressure differential of 0.1 inch w.g. (25 Pa) across the roughed in system, including the manufacturer's air handler enclosure. All registered boots shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to 4 cfm (1.89 L/s) per 100 square feet (9.29 square meters) of conditioned floor space.
  3. Visual verification by the Authority Having Jurisdiction or an approved agency.
Exception: Duct tightness test is not required if the air handler and all ducts are located within conditioned space.

N1103.3.2.1 (R403.3.2.1) Sealed Air Handler

AMENDMENT
This section has been amended at the state or city level.

N1103.3.3 (R403.3.3) Duct Testing (Mandatory)

AMENDMENT
This section has been amended at the state or city level.

N1103.3.4 (R403.3.4) Duct Leakage (Prescriptive)

AMENDMENT
This section has been amended at the state or city level.

N1103.3.5 (R403.3.5) Building Cavities (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Building framing cavities shall not be used as supply ducts.

N1103.4 (R403.4) Mechanical System Piping Insulation (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Mechanical system piping capable of carrying fluids above 105 degree Fahrenheit (41 degrees Celsius) or below 55 degrees Fahrenheit (13 degrees Celsius) shall be insulated to a minimum of R-2.

N1103.4.1 (R403.4.1) Protection of Piping Insulation

AMENDMENT
This section has been amended at the state or city level.

N1103.5 (R403.5) Circulation Service Hot Water Systems From N1103.5.1 and N1103.5.2

AMENDMENT
This section has been amended at the state or city level.
Energy conservation measures for circulation service potable hot water systems shall be in accordance with Sections N1103.5.1 and N1103.5.2.

N1103.5.1 (R403.5.1) Heated Water Circulation and Temperature Maintenance Systems (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Heated water circulation systems shall be in accordance with Section R1103.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R1103.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.

N1103.5.1.1 (R403.5.1.1) Circulation Systems

AMENDMENT
This section has been amended at the state or city level.
Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermo-syphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water.

N1103.5.1.2 (R403.5.1.2) Heat Trace Systems

AMENDMENT
This section has been amended at the state or city level.
Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy.

N1103.5.2 (R403.5.2) Demand Recirculation Systems

AMENDMENT
This section has been amended at the state or city level.
A water distribution system having one or more recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe shall be a demand recirculation water system. Pumps shall have controls that comply with both of the following:
  1. The control shall start the pump upon receiving a signal from the action of a user of a fixture or appliance, sensing the presence of a user of a fixture or sensing the flow of hot or tempered water to a fixture fitting or appliance.
  2. The control shall limit the temperature of the water entering the cold water piping to 104 degrees Fahrenheit (40 degrees Celsius).

N1103.5.3 (R403.5.3) Hot Water Pipe Insulation (Prescriptive)

AMENDMENT
This section has been amended at the state or city level.
Insulation for hot water pipe with a minimum thermal resistance (R-value) of R-3 shall be applied to the following:
  1. Piping 1 inch (25 mm) and larger in nominal diameter.
  2. Piping serving more than one dwelling unit.
  3. Piping located outside the conditioned space.
  4. Piping from the water heater to the distribution manifold.
  5. Piping located under a floor slab.
  6. Buried in piping.
  7. Supply and return piping in recirculation systems other than demand recirculation systems.

N1103.5.4 (R403.5.4) Drain Water Heat Recovery Units

AMENDMENT
This section has been amended at the state or city level.

N1103.6 (R403.6) Mechanical Ventilation (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Outdoor air intakesshall have automatic or gravity dampers that close when the ventilation system is not operating.

N1103.6.1 (R403.6.1) Whole-House Mechanical Ventilation System Fan Efficacy

AMENDMENT
This section has been amended at the state or city level.

N1103.7 (R403.7) Equipment Sizing and Efficiency Rating (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Heating and cooling equipment shall be sized as specified in M1401.3.

N1103.8 (R403.8) Systems Serving Multiple Dwelling Units (Mandatory)

AMENDMENT
This section has been amended at the state or city level.

N1103.9 (R403.9) Snow Melt System Controls (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Snow- and ice-melting systems, supplied through energy service to the building shall include automatic controls capable of shutting off the system when the pavement temperature is above 50 degrees Fahrenheit (10 degrees Celsius), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40 degrees Fahrenheit (5 degrees Celsius).

N1103.10 (R403.10) Pools and Permanent Spa Energy Consumption (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Pools shall be provided with energy conservation measures in accordance with Sections N1103.10.2 through N1103.10.4.

N1103.10.1 (R403.10.1) Pool Heaters

AMENDMENT
This section has been amended at the state or city level.
All pool heaters shall be equipped with a readily accessible on-off switch to allow shutting off the heater without adjusting the thermostat setting. Pool heaters fired by natural gas or LPG shall not have continuously burning pilot lights.

N1103.10.2 (R403.10.2) Time Switches

AMENDMENT
This section has been amended at the state or city level.
Time switches that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on swimming pool heaters and pumps.
Exceptions:
  1. Where public health standards require 24-hour pump operation.
  2. Where pumps are required to operate solar- and waste-heat-recovery pool heating systems.
Outdoor heated pools and outdoor permanent spas shall be provided with a vapor-retardant cover or other approved vapor-retardant means.

Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site-recovered energy, such as from a heat pump or solar energy source, covers or other vapor-retardant means shall not be required.

N1103.11 (R403.11) Portable Spas (Mandatory)

AMENDMENT
This section has been amended at the state or city level.

N1103.12 (R403.12) Residential Pools and Permanent Residential Spas

AMENDMENT
This section has been amended at the state or city level.

Section N1104 (R404) Electrical Power and Lighting Systems (Mandatory)

AMENDMENT
This section has been amended at the state or city level.

N1104.1 (R404.1) Lighting Equipment (Mandatory)

AMENDMENT
This section has been amended at the state or city level.
Not less than 75 percent of the lamps in permanently installed luminaries shall be high-efficacy lamps or not less than 75 percent of the permanently installed luminaries shall contain only high-efficacy lamps.
Exception: Low-voltage lighting.

N1104.1.1 (R404.1.1) Lighting Equipment (Mandatory)

AMENDMENT
This section has been amended at the state or city level.

Section N1105 (R405) Simulated Performance Alternative (Performance)

AMENDMENT
This section has been amended at the state or city level.

N1105.1 (R405.1) Scope

AMENDMENT
This section has been amended at the state or city level.

N1105.2 (R405.2) Mandatory Requirements

AMENDMENT
This section has been amended at the state or city level.

N1105.3 (R405.3) Performance-Based Compliance

AMENDMENT
This section has been amended at the state or city level.

N1105.4 (R405.4) Documentation

AMENDMENT
This section has been amended at the state or city level.

N1105.4.1 (R405.4.1) Compliance Software Tools

AMENDMENT
This section has been amended at the state or city level.

N1105.4.2 (R405.4.2) Compliance Report

AMENDMENT
This section has been amended at the state or city level.

N1105.4.2.1 (R405.4.2.1) Compliance Report for Permit Application

AMENDMENT
This section has been amended at the state or city level.

N1105.4.2.2 (R405.4.2.2) Compliance Report for Certificate of Occupancy

AMENDMENT
This section has been amended at the state or city level.

N1105.4.3 (R405.4.3) Additional Documentation

AMENDMENT
This section has been amended at the state or city level.

N1105.5 (R405.5) Calculation Procedure

AMENDMENT
This section has been amended at the state or city level.

N1105.5.1 (R405.5.1) General

AMENDMENT
This section has been amended at the state or city level.

N1105.5.2 (R405.5.2) Residence Specifications

AMENDMENT
This section has been amended at the state or city level.

N1105.6 (R405.6) Calculation Software Tools

AMENDMENT
This section has been amended at the state or city level.

N1105.6.1 (R405.6.1) Minimum Capabilities

AMENDMENT
This section has been amended at the state or city level.

N1105.6.2 (R405.6.2) Specific Approval

AMENDMENT
This section has been amended at the state or city level.

N1105.6.3 (R405.6.3) Input Values

AMENDMENT
This section has been amended at the state or city level.

Section N1106 (R406) Energy Rating Index Compliance Alternative

AMENDMENT
This section has been amended at the state or city level.

N1106.1 (R406.1) Scope

AMENDMENT
This section has been amended at the state or city level.

N1106.2 (R406.2) Mandatory Requirements

AMENDMENT
This section has been amended at the state or city level.

N1106.3 (R406.3) Energy Rating Index

AMENDMENT
This section has been amended at the state or city level.

N1106.3.1 (R406.3.1) ERI Reference Design

AMENDMENT
This section has been amended at the state or city level.

N1106.4 (R406.4) ERI-Based Compliance

AMENDMENT
This section has been amended at the state or city level.

N1106.5 (R406.5) Verification by Approved Agency

AMENDMENT
This section has been amended at the state or city level.

N1106.6 (R406.6) Documentation

AMENDMENT
This section has been amended at the state or city level.

N1106.6.1 (R406.6.1) Compliance Software Tools

AMENDMENT
This section has been amended at the state or city level.

N1106.6.2 (R406.6.2) Compliance Report

AMENDMENT
This section has been amended at the state or city level.

N1106.6.3 (R406.6.3) Additional Documentation

AMENDMENT
This section has been amended at the state or city level.

N1106.7 (R406.7) Calculation Software Tools

AMENDMENT
This section has been amended at the state or city level.

N1106.7.1 (R406.7.1) Minimum Capabilities

AMENDMENT
This section has been amended at the state or city level.

N1106.7.2 (406.7.2) Specific Approval

AMENDMENT
This section has been amended at the state or city level.

N1106.7.3 (R406.7.3) Input Values

AMENDMENT
This section has been amended at the state or city level.

Section N1107 (R501) Existing Buildings — General

AMENDMENT
This section has been amended at the state or city level.

N1107.1 (R501.1) Scope

AMENDMENT
This section has been amended at the state or city level.

N1107.1.1 (R501.1.1) Additions, Alterations, or Repairs: General

AMENDMENT
This section has been amended at the state or city level.

N1107.2 (R501.2) Existing Buildings

AMENDMENT
This section has been amended at the state or city level.

N1107.3 (R501.3) Maintenance

AMENDMENT
This section has been amended at the state or city level.

N1107.4 (R501.4) Compliance

AMENDMENT
This section has been amended at the state or city level.

N1107.5 (R501.5) New and Replacement Materials

AMENDMENT
This section has been amended at the state or city level.

N1107.6 (R501.6) Historic Buildings

AMENDMENT
This section has been amended at the state or city level.

Section N1108 (R502) Additions

AMENDMENT
This section has been amended at the state or city level.

N1108.1 (R502.1) General

AMENDMENT
This section has been amended at the state or city level.

N1108.1.1 (R502.1.1) Prescriptive Compliance

AMENDMENT
This section has been amended at the state or city level.

N1108.1.1.1 (R502.1.1.1) Building Envelope

AMENDMENT
This section has been amended at the state or city level.

N1108.1.1.2 (R502.1.1.2) Heating and Cooling Systems

AMENDMENT
This section has been amended at the state or city level.

N1108.1.1.3 (R502.1.1.3) Service Hot Water Systems

AMENDMENT
This section has been amended at the state or city level.

N1108.1.1.4 (R502.1.1.4) Lighting

AMENDMENT
This section has been amended at the state or city level.

N1108.1.2 (R502.1.2) Existing Plus Addition Compliance (Simulated Performance Alternative)

AMENDMENT
This section has been amended at the state or city level.

Section N1109 (R503) Alterations

AMENDMENT
This section has been amended at the state or city level.

N1109.1 (R503.1) General

AMENDMENT
This section has been amended at the state or city level.

N1109.1.1 (R503.1.1) Building Envelope

AMENDMENT
This section has been amended at the state or city level.

N1109.1.1.1 (R503.1.1.1) Replacement Fenestration

AMENDMENT
This section has been amended at the state or city level.

N1109.1.2 (R503.1.2) Heating and Cooling Systems

AMENDMENT
This section has been amended at the state or city level.

N1109.1.3 (R503.1.3) Service Hot Water Systems

AMENDMENT
This section has been amended at the state or city level.

N1109.1.4 (R503.1.4) Lighting

AMENDMENT
This section has been amended at the state or city level.

N1109.2 (R503.2) Change in Space Conditioning

AMENDMENT
This section has been amended at the state or city level.

Section N1110 (R504) Repairs

AMENDMENT
This section has been amended at the state or city level.

N1110.1 (R504.1) General

AMENDMENT
This section has been amended at the state or city level.

N1110.2 (R504.2) Application

AMENDMENT
This section has been amended at the state or city level.

Section N1111 (R505) Change of Occupancy or Use

AMENDMENT
This section has been amended at the state or city level.

N1111.1 (R505.1) General

AMENDMENT
This section has been amended at the state or city level.

N1111.2 (R505.2) General

AMENDMENT
This section has been amended at the state or city level.